This mechanical schedules document for the VA Loch Raven Construct Consolidated Boiler Spaces project in Baltimore, MD provides comprehensive equipment specifications for a complex mechanical system upgrade. The document details multiple mechanical systems including three 6,695 MBH Cleaver Brooks fire tube boilers, hydronic pumps, gas booster skids, make-up air units, exhaust fans, air terminal units, and various supporting equipment like air separators, expansion tanks, and fuel oil transfer pumps. The mechanical design incorporates redundant systems with specifications for electrical connections, flow rates, temperature ranges, and performance metrics, with equipment from manufacturers like Bell & Gossett, Daikin, Greenheck, and Modine. The project appears to be a comprehensive upgrade of the mechanical infrastructure for the VA facility, with bid documents dated 07/07/2025 and a mechanical design focused on efficiency, reliability, and precise environmental control.

View the file

Other files

Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

VA Project No.

AG Project No.

A u to d e s k D o c s /0

V A

M C

L o c h R a v e n

B o ile r C o n s o lid a ti o n /0

V A

L R

B o ile r C o n s o lid a ti o n

R

M

E P

.r v t

/1

/2

:2

:5

A

M

M-801

MECHANICAL SCHEDULES Loch Raven Construct Consolidated Boiler Spaces

BALTIMORE MD

0123038

07/07/2025 GSC ZGC

BID DOCUMENTS

512-23-154

HOT WATER BOILER SCHEDULE

MARK DESCRIPTION TYPE

OUTPUT

(MBH)

WATER PERFORMANCE

MAWP

(PSIG)

HEATING

SURFACE

(SQ. FT.)

SAFETY RELIEF VALVES BURNER REQUIREMENTS NATURAL GAS PERFORMANCE ULSD FO PERFORMANCE ELECTRICAL CONNECTION SIZES OVERALL DIMENSIONS

APPROX.

OPERATING

WEIGHT (LBS)

BASIS OF DESIGN

SUPPLY WATER

TEMPERATURE

(DEG F)

RETURN WATER

TEMPERATURE

(DEG F)

DESIGN FLOW

RATE (GPM)

LOWEST

PRESSURE,

SVB1 (PSIG)

HIGHEST

PRESSURE,

SVB2 (PSIG)

BURNER FUELS

(PRIMARY /

SECONDARY)

IGNITER FUELS

(PRIMARY /

SECONDARY)

EMISSIONS

RATING (PPM

NOx)

FD FAN

MOTOR HP

INPUT

(MBH)

MIN. BOILER

EFFICIENCY (%)

AVAIL. GAS

PRESS.

(PSIG)

INPUT

(MBH)

MIN. BOILER

EFFICIENCY (%)

OIL PUMP

MOTOR

(HP)

AIR COMPRESSOR

MOTOR (HP)

AVAIL. FUEL

PRESS.

(PSIG)

BOILER

BLOWER

V/PH/HZ

OIL PUMP

V/HZ/PH

AIR COMPRESSOR

V/PH/HZ

GAS

(IN.)

OIL

(IN.)

HW INLET

(IN.)

HW OUTLET

(IN.)

DRAIN AIR VENT FLUE

VENT

(IN.) WIDTH HEIGHT MANUFACTURER MODEL NO.V/PH/HZ FLA MCA MOP MIN. SCCR (AMPS) QTY. SIZE (IN.) QTY. SIZE (IN.)

10-B-1-1 4-PASS WETBACK FIRE TUBE 6,695 180 160 670 200 1,000 73 75 NAT. GAS / FUEL OIL NAT. GAS / PROPANE 30 15 8,370 80 1 8,166 82 1/2 3 100 460/3/60 40 - 50 5K 460/3/60 N/A 460/3/60 2 1 6 6 2 2 1 1.5 16 82.75 101.75 30,000 CLEAVER BROOKS CBLE-4W-200W

10-B-1-2 4-PASS WETBACK FIRE TUBE 6,695 180 160 670 200 1,000 73 75 NAT. GAS / FUEL OIL NAT. GAS / PROPANE 30 15 8,370 80 1 8,166 82 1/2 3 100 460/3/60 40 - 50 5K 460/3/60 N/A 460/3/60 2 1 6 6 2 2 1 1.5 16 82.75 101.75 30,000 CLEAVER BROOKS CBLE-4W-200W

10-B-1-3 4-PASS WETBACK FIRE TUBE 6,695 180 160 670 200 1,000 73 75 NAT. GAS / FUEL OIL NAT. GAS / PROPANE 30 15 8,370 80 1 8,166 82 1/2 3 100 460/3/60 40 - 50 5K 460/3/60 N/A 460/3/60 2 1 6 6 2 2 1 1.5 16 82.75 101.75 30,000 CLEAVER BROOKS CBLE-4W-200W

NOTES:

1. PROVIDE SINGLE POINT ELECTRICAL CONNECTION FOR EACH FORCED DRAFT FAN, FORCED DRAFT FAN AIR CONDITIONER, ATOMIZING AIR COMPRESSOR, AND BOILER CONTROL PANEL.

2. BOILERS SHALL NOT BE PROVIDED WITH A FLUE GAS ECONOMIZER.

3. PROVIDE UNIT-MOUNTED, NFPA 85 COMPLIANT, UL 508A, CONTROL PANEL TO CONTAIN BURNER MANAGEMENT SYSTEM (BMS) AND COMBUSTION CONTROL SYSTEM (CCS). PROVIDE PANEL AIR CONDITIONER PER SCHEDULE. REFER TO SPECIFICATIONS FOR DETAILED PANEL CONSTRUCTION REQUIREMENTS.

4. PROVIDE WITH LOW NOx BURNERS. FLUE GAS RECIRCULATION MAY BE USED AS REQUIRED TO OBTAIN EMISSIONS.

5. BOILERS SHALL BE CONSTRUCTED AND ASME STAMPED FOR LISTED MAWP.

6. PROVIDE FD FAN VARIABLE FREQUENCY DRIVE, UNIT-MOUNTED AND ADJACENT TO BOILER CONTROL PANEL.

7. BACKUP IGNITER FUEL SHALL BE PROPANE. AVAILABLE PROPANE PRESSURE IS 1.5 PSIG.

8. BASIS OF DESIGN MANUFACTURER PROVIDE A SINGLE PRESSURE RELIEF VALVE AS INDICATED IN THE SCHEDULE. CONTRACTOR RESPONSIBLE FOR COORDINATION OF LAYOUT, MATERIALS, AND LABOR FOR MORE THAN A SINGLE VALVE, IF PROVIDED.

NOTES:

1. PROVIDE HOT GAS BYPASS FOR OPERATION DURING LOW LOAD OPERATIONS.

2. MOUNT CONDENSING UNIT ON ROOF. SEE SHEET MH103 FOR MORE INFORMATION.

3. PROVIDE WITH LOW AMBIENT KIT TO OPERATE DOWN TO 0°f AMBIENT.

4. PROVIDE WITH NON-FUSED DISCONNECT SWITCH.

5. MOUNT INDOOR UNIT IN HORIZONTAL CONFIGURATION SUPPORTED FROM STRUCTURE ABOVE.

6. ROUTE CONDENSATE TO LOCATION INDICATED ON PLANS.

7. PROVIDE WITH SEPARATE 208/1/60, 15A CONNECTION FOR CONTROLLER.

8. PROVIDE WITH R-32 REFRIGERANT. PROVIDE WITH MANUFACTURER STANDARD REFRIGERANT DETECTION SYSTEM.

HYDRONIC PUMP SCHEDULE

MARK LOCATION SYSTEM TYPE

FLUID DATA PUMP DATA ELECTRICAL DATA BASIS OF DESIGN

FLOW (GPM) HEAD (FT) NPSHR FLUID TEMP.

IMPELLER

SIZE % EFF.

SUCT. SIZE

(IN.)

DISCH. SIZE

(IN.)

MOTOR SIZE

(HP) MOTOR RPM V/PH/HZ MANUFACTURER MODEL NO.

10-PHWP-1-1 BUILDING 10 PRIMARY HEATING WATER END SUCTION 670 55 8.86 180 8.625 84 5 4 15 1800 460/3/60 BELL & GOSSETT e-1510

10-PHWP-1-2 BUILDING 10 PRIMARY HEATING WATER END SUCTION 670 55 8.86 180 8.625 84 5 4 15 1800 460/3/60 BELL & GOSSETT e-1510

10-PHWP-1-3 BUILDING 10 PRIMARY HEATING WATER END SUCTION 670 55 8.86 180 8.625 84 5 4 15 1800 460/3/60 BELL & GOSSETT e-1510

10-SHWP-1-1 BUILDING 10 SECONDARY HEATING WATER END SUCTION 670 100 8.37 180 10.875 82 4 3 25 1800 460/3/60 BELL & GOSSETT e-1510

10-SHWP-1-2 BUILDING 10 SECONDARY HEATING WATER END SUCTION 670 100 8.37 180 10.875 82 4 3 25 1800 460/3/60 BELL & GOSSETT e-1510

10-SHWP-1-3 BUILDING 10 SECONDARY HEATING WATER END SUCTION 670 100 8.37 180 10.875 82 4 3 25 1800 460/3/60 BELL & GOSSETT e-1510

1-HHWP-B-1 BUILDING 1 BUILDING 1 HEATING WATER END SUCTION 470 130 7.6 180 12.625 75 4 3 25 1800 460/3/60 BELL & GOSSETT e-1510

1-HHWP-B-2 BUILDING 1 BUILDING 1 HEATING WATER END SUCTION 470 130 7.6 180 12.625 75 4 3 25 1800 460/3/60 BELL & GOSSETT e-1510

4-HHWP-B-1 BUILDING 4 BUILDING 4 HEATING WATER INLINE 80 55 6.65 180 9.5 56 2 2 3 1800 208/3/60 BELL & GOSSETT e-80SC

4-HHWP-B-2 BUILDING 4 BUILDING 4 HEATING WATER INLINE 80 55 6.65 180 9.5 56 2 2 3 1800 208/3/60 BELL & GOSSETT e-80SC

5-HHWP-1-1 BUILDING 5 BUILDING 5 HEATING WATER INLINE 80 55 6.65 180 9.5 56 2 2 3 1800 208/3/60 BELL & GOSSETT e-80SC

5-HHWP-1-2 BUILDING 5 BUILDING 5 HEATING WATER INLINE 80 55 6.65 180 9.5 56 2 2 3 1800 208/3/60 BELL & GOSSETT e-80SC

5-HHWP-1-3 BUILDING 5 BUILDING 5 HEATING WATER INLINE 80 55 6.65 180 9.5 56 2 2 3 1800 208/3/60 BELL & GOSSETT e-80SC

6-HHWP-1-1 BUILDING 6 BUILDING 6 HEATING WATER INLINE

CIRCULATOR

15 20 --- 180 - 43 1.25 1.25 1/6 3392 120/1/60 BELL & GOSSETT ECOCIRC XL 36-45

6-HHWP-1-1 BUILDING 6 BUILDING 6 HEATING WATER INLINE

CIRCULATOR

15 20 --- 180 - 43 1.25 1.25 1/6 3392 120/1/60 BELL & GOSSETT ECOCIRC XL 36-45

10-HHWP-2-1 BUILDING 10 BUILDING 10 HEATING WATER INLINE

CIRCULATOR

61 30 --- 180 - 56 1.5 1.5 3 2234 460/3/60 BELL & GOSSETT ECOCIRC XL

110-180

10-HHWP-2-2 BUILDING 10 BUILDING 10 HEATING WATER INLINE

CIRCULATOR

61 30 --- 180 - 56 1.5 1.5 3 2234 460/3/60 BELL & GOSSETT ECOCIRC XL

110-180

NOTES:

1. PROVIDE SUCTION DIFFUSER OR REDUCING SUCTION DIFFUSER FOR EACH PUMP. COORDINATE SIZING BETWEEN SUCTION PIPING AND PUMP SUCTION FLANGE SIZE REQUIRED FOR PERFORMANCE INDICATED.

2. PROVIDE LEVELING GROUT AND BASE GROUTING IN ACCORDANCE WITH SPECIFICATIONS AND MANUFACTURERS REQUIREMENTS. COORDINATE INSTALLATION WITH COLD AND HOT ALIGNMENT ACTIVITIES.

3. DISCONNECT AND VARIABLE FREQUENCY DRIVE PROVIDED BY DIVISION 26.

4. PROVIDE INSULATION BOX PER DETAIL AND AS SPECIFIED.

5. INSTALL PER END SUCTION PUMP DETAIL.

6. DRAIN PUMP BASE PAN TO NEAREST FLOOR DRAIN. PROVIDE COPPER TYPE L PIPING FOR ALL DRAIN PIPING. TERMINATE AT FLOOR DRAIN WITH DIAGONAL CUT TO PREVENT CONNECTION.

FLOW METER SCHEDULE

DEVICE

NUMBER SERVICE SYSTEM / LOCATION TYPE SENSING DIRECTION ACCURACY TURNDOWN

PIPE SIZE

(IN.)

MAX. FLOW DESIGN FLOW

OUTPUT BASIS OF DESIGNPPH GPM CFH PPH GPM CFH

FE 04004 HHW TO DISTRIBUTION BOILER PLANT FLANGED, MAGNETIC UNI-DIRECTIONAL +/- 1.0% 10 TO 1 8 - 2,010 - - 1,340 - 4-20 mA YOKOGAWA

FE 02001 SW TO HEATING HW SYSTEM BOILER PLANT FLANGED, NUTATING DISC UNI-DIRECTIONAL +/- 1.5% 10 TO 1 2-1/2 - 250 - - 250 - 4-20 mA BADGER

FE 04101 HHS FROM BLR-01 BOILER PLANT FLANGED, MAGNETIC UNI-DIRECTIONAL +/- 1.0% 10 TO 1 6 - 800 - - 670 - 4-20 mA YOKOGAWA

FE 04201 HHS FROM BLR-02 BOILER PLANT FLANGED, MAGNETIC UNI-DIRECTIONAL +/- 1.0% 10 TO 1 6 - 800 - - 670 - 4-20 mA YOKOGAWA

FE 04301 HHS FROM BLR-03 BOILER PLANT FLANGED, MAGNETIC UNI-DIRECTIONAL +/- 1.0% 10 TO 1 6 - 800 - - 670 - 4-20 mA YOKOGAWA

FE 12113 NG TO BLR-01 BOILER PLANT FLANGED, THERMAL MASS UNI-DIRECTIONAL +/- 0.5% 20 TO 1 3 - - 10,000 - - 8,370 4-20 mA SIERRA

FE 12213 NG TO BLR-02 BOILER PLANT FLANGED, THERMAL MASS UNI-DIRECTIONAL +/- 0.5% 20 TO 1 3 - - 10,000 - - 8,370 4-20 mA SIERRA

FE 12313 NG TO BLR-03 BOILER PLANT FLANGED, THERMAL MASS UNI-DIRECTIONAL +/- 0.5% 20 TO 1 3 - - 10,000 - - 8,370 4-20 mA SIERRA

FE 03164 FO TO BLR-01 BOILER PLANT THREADED, POS. DISP. UNI-DIRECTIONAL +/- 1.0% 10 TO 1 1 - 3 - - 2 - SCALABLE NPN

TRANSISTOR

FLOMEC G2 SERIES

FE 03264 FO TO BLR-02 BOILER PLANT THREADED, POS. DISP. UNI-DIRECTIONAL +/- 1.0% 10 TO 1 1 - 3 - - 2 - SCALABLE NPN

TRANSISTOR

FLOMEC G2 SERIES

FE 03364 FO TO BLR-03 BOILER PLANT THREADED, POS. DISP. UNI-DIRECTIONAL +/- 1.0% 10 TO 1 1 - 3 - - 2 - SCALABLE NPN

TRANSISTOR

FLOMEC G2 SERIES

FE 03001 FO TO FOPS-01 BOILER PLANT THREADED, POS. DISP. UNI-DIRECTIONAL +/- 1.0% 20 TO 1 2 - 7 - - 7 - SCALABLE NPN

TRANSISTOR

FLOMEC G2 SERIES

FE 03002 FO FROM FOPS-02 BOILER PLANT THREADED, POS. DISP. UNI-DIRECTIONAL +/- 1.0% 20 TO 1 2 - 7 - - 7 - SCALABLE NPN

TRANSISTOR

FLOMEC G2 SERIES

FE 04006 HHW TO BOILER PLANT BOILER PLANT FLANGED, MAGNETIC UNI-DIRECTIONAL +/- 1.0% 10 TO 1 2 - 200 - - 150 - 4-20mA YOKOGAWA

FE 04005 HHW DECOUPLER BOILER PLANT FLANGED, MAGNETIC BI-DIRECTIONAL +/- 1.0% 10 TO 1 8 - 1,340 - - 670 - 4-20mA YOKOGAWA

FE 12001 GAS BOOSTER DISCHARGE BOILER PLANT FLANGED, THERMAL MASS UNI-DIRECTIONAL +/- 1.0% 20 TO 1 6 - - 20,000 - - 16,740 4-20 mA SIERRA

FE 04011 HHW TO BUILDING 01 BUILDING 01 FLANGED, MAGNETIC UNI-DIRECTIONAL +/- 1.0% 10 TO 1 6 - - - - 4-20 mA YOKOGAWA

FE 04041 HHW TO BUILDING 04 BUILDING 05 FLANGED, MAGNETIC UNI-DIRECTIONAL +/- 1.0% 10 TO 1 3 - - - - 4-20 mA YOKOGAWA

FE 04051 HHW TO BUILDING 05 BUILDING 06 FLANGED, MAGNETIC UNI-DIRECTIONAL +/- 1.0% 10 TO 1 3 - - - - 4-20 mA YOKOGAWA

FE 04061 HHW TO BUILDING 06 BUILDING 07 FLANGED, MAGNETIC UNI-DIRECTIONAL +/- 1.0% 10 TO 1 2 - - - - 4-20 mA YOKOGAWA

FE 04071 HHW TO BUILDING 07 BUILDING 04 FLANGED, MAGNETIC UNI-DIRECTIONAL +/- 1.0% 10 TO 1 3 - - - - 4-20 mA YOKOGAWA

NOTES:

1. REVIEW REQUIRED UPSTREAM AND DOWNSTREAM PIPING CONDITIONS AND VERIFY THEY MEET THE METER MANUFACTURERS REQUIREMENTS PRIOR TO COMPLETING INSTALLATION.

2. METERS SHALL BE LOCATED IN AN ACCESSIBLE AREA. IF MOUNTED HIGHER THAN SEVEN (7) FEET ABOVE THE FINISHED FLOOR, PROVIDE REMOTE MOUNTED ELECTRONICS. MOUNT PER MANUFACTURERS REQUIREMENTS AT 5'-0"

ABOVE FINISHED FLOOR.

3. REFER TO SPECIFICATIONS FOR ADDITIONAL COMMUNICATION AND CONTROL REQUIREMENTS OF METER TRANSMITTER AND ELECTRONICS.

AUTOMATIC FUEL OIL TRANSFER PUMP SCHEDULE

MARK TYPE GPH OIL GRADE VISCOSITY

OIL TEMPERATURE

(°F)

MINIMUM SYSTEM PRESSURE

(PSIG)

PUMP DISCHARGE PRESSURE

(PSIG) MOTOR HP V/PH/HZ LENGTH WIDTH HEIGHT MANUFACTURER MODEL NO.

10-FOPS-1-1 POSITIVE DISPLACEMENT 925 NO. 2

(ULSD)

45 SSU 60 100 125 (2) 2 460/3/60 65' - 0 1/2" 30' - 0 1/2" 6' - 2" PREFERRED UTILITIES

MFG CORP

ATPSF-206BGZ133

3-D-DP-L

NOTES:

1. PROVIDE WITH INTEGRAL DISCONNECT.

2. PROVIDE WITH FACTORY 120V/1-PH STEP DOWN TRANSFORMER FOR CONTROLS.

3. PROVIDE TEFC PUMP MOTORS.

4. PROVIDE INLET VALVE ASSEMBLY FOR LEVEL CONTROL.

5. UNIT SHALL BE DUPLEX TYPE WITH REDUNDANT POSITIVE DISPLACEMENT PUMPS.

6. PROVIDE WITH DUPLEX STRAINER DIFFERENTIAL PRESSURE SWITCH.

7. PROVIDE WITH SET LEAK DETECTION SWITCH.

8. PROVIDE WITH BUILDING AUTOMATION SYSTEM (BAS) DISCRETE OUTPUT CONTACTS.

GAS BOOSTER SKID SCHEDULE

MARK

PEAK GAS

FLOW

(SCFH)

MINIMUM GAS

FLOW (SCFH)

INLET

PRESSURE

(IN. WC)

DISCHARGE

PRESSURE (IN. WC)

RATED MAXIMUM

OPERATING

PRESSURE, MOP

(PSIG) INLET (IN.) OUTLET (IN.) MOTOR HP

MOTOR SPEED

(RPM)

VOLTS/PHASE/

HERTZ MANUFACTURER MODEL

GBS-01 18000 1800 5.0 83 7 4 4 (2) @ 10 3500 460/3/60 SPENCER TURBINE GL-3010-R

NOTES:

1. PROVIDE LOW PRESSURE GAS CUT-OFF SWITCH WITH MANUAL RESET. SET CUT-OFF PRESSURE AT 4.5 IN WG.

2. PROVIDE CLASS I, DIVISION II, GROUP D EXPLOSION PROOF CONSTRUCTION.

3. PROVIDE UL 508A CERTIFIED CONTROL PANEL MEETING THE SEQUENCE OF OPERATIONS AND SPECIFICATION REQUIREMENTS.

MINI-SPLIT DUCTLESS HEAT PUMP SCHEDULE

INDOOR UNIT OUTDOOR UNIT

MARK MODEL NO.

SA CFM (HIGH

SPEED)

TOTAL COOLING

CAPACITY (MBH)

TOTAL HEATING

CAPACITY (MBH) MARK

MODEL

NO. SEER2

NOM.

TONS

AMBIENT

TEMP. (°F)

UNIT ELECTRICAL

MCA MOCP V/PH/HZ

10-IDU-1-1 FTXF18AXVJU 715 18.1 21.6 10-ODU-3-1 RXF18AXJVU 21 1.5 94 16.34 20 208/1/60

10-IDU-1-2 FTXF18AXVJU 715 18.1 21.6 10-ODU-3-2 RXF18AXJVU 21 1.5 94 16.34 20 208/1/60

NOTES:

1. INDOOR UNIT TO BE POWERED BY OUTDOOR UNIT.

2. PROVIDE WITH FACTORY MOUNTED CONDENSATE PUMP.

3. PROVIDE WITH R-32 OR R-454B REFRIGERANT.

4. CONFIRM FINAL REFRIGERANT PIPING LENGTH PRIOR TO ORDER AND PROVIDE MANUFACTURER LONG LINE KIT AS NECESSARY.

5. 10-IDU-1-2 SHALL BE INTERLOCKED WITH GENERATOR TRANSFER SWITCH SUCH THAT WHENEVER GENERATOR IS RUNNING, DUCTLESS UNIT SHALL DE-ENERGIZE.

EXHAUST FAN SCHEDULE

MARK MANUFACTURER MODEL NO. TYPE CFM

ESP

(IN-WG) FAN RPM

ELECTRICAL DRIVE

TYPE

MAX

SONES NOTESMCA/HP V/PH/HZ

10-EF-3-1 GREENHECK CUE-160-A UPBLAST ROOF 3000 0.5 1,364 4.2/2.0 460/3/60 DIRECT 17.9 2,3

10-EF-3-2 GREENHECK CUE-160-A UPBLAST ROOF 3000 0.5 1,364 4.2/2.0 460/3/60 DIRECT 17.9 2,3

10-EF-3-3 GREENHECK CUE-160-A UPBLAST ROOF 3000 0.5 1,364 4.2/2.0 460/3/60 DIRECT 17.9 2,3

10-EF-3-4 GREENHECK CUE-160-A UPBLAST ROOF 3000 0.5 1,364 4.2/2.0 460/3/60 DIRECT 17.9 2,3

10-EF-3-5 PENN BARRY FX18BH UPBLAST ROOF 3000 1.0 1,131 5.8/1.0 208/3/60 BELT 16.7 1,2,3

NATURAL GAS PRESSURE REGULATOR VALVE SCHEDULE (PRV)

MARK LOCATION EQUIPMENT INPUT (SCFH)

INLET PRESSURE

(IN WG)

OUTLET PRESSURE (IN

WG)

VALVE SIZE

(INCHES) Basis Notes

PRV-01 BOILER PLANT BLR-01 8,370 30 22-28 2.5

PRV-02 BOILER PLANT BLR-02 8,370 30 22-28 2.5

PRV-03 BOILER PLANT BLR-03 8,370 30 22-28 2.5

LOUVER SCHEDULE

UNIT NO. SIZE (W" x H") CURB CAP (W" x H") AIRFLOW (CFM) PRESSURE DROP (IN-WG) SERVICE LOCATION BASIS OF DESIGN

10-GLP-3-1 68x80 76x88 26,700 0.099 EXHAUST AIR GENERATOR ROOM GREENHECK: ESD-635PD

10-GLP-3-2 68x86 76x94 28,550 0.195 MAKE UP AIR GENERATOR ROOM GREENHECK: ESD-635PD

10-GLP-3-3 28X44 36X52 6,000 0.194 MAKE UP AIR BOILER ROOM GREENHECK: ESD-635PD

10-GLP-3-4 28X44 36X52 6,000 0.194 MAKE UP AIR BOILER ROOM GREENHECK: ESD-635PD

10-GLP-3-5 26x26 34x34 3,000 0.161 MAKE UP AIR GAS BOOSTER ROOM GREENHECK: ESD-635PD

10-GLP-3-6 14X14 22X22 900 0.125 EXHAUST AIR BOILER ROOM GREENHECK: ESD-635PD

10-GLP-3-7 16X16 24X24 1,100 0.15 OUTSIDE AIR MEZZANINE GREENHECK: ESD-635PD

NOTES:

1. ALL LOUVERS TO BE AMCA 540 AND AMCA 550 LISTED.

2. PROVIDE ALL LOUVERS WITH INSECT SCREEN, 12" CURB, DUCTED INSTALLATION, AND 700 FPM MAXIMUM THROAT VELOCITY FOR INTAKE APPLICATION.

HOT WATER UNIT HEATER SCHEDULE

MARK MODEL NO. SA CFM (MAX.) EAT (°F) LAT (°F) GPM EAT (F°) LWT (F°)

ACTUAL HEATING

CAPACITY (MBH)

STANDARD HEATING

CAPACITY (MBH) FAN MOTOR HP V/PH/HZ NOTES

10-HWUH-1-1 MODINE: HSB 18 340 50 81.0 1.3 GPM 180 160 11.8 12.6 1/60 115/1/60 1,3

10-HWUH-1-2 MODINE: HSB 18 340 50 81.0 1.3 GPM 180 160 11.8 12.6 1/60 115/1/60 1,3

10-HWUH-1-3 MODINE: HSB 18 340 50 81.0 1.3 GPM 180 160 11.8 12.6 1/60 115/1/60 1,3

10-HWUH-1-4 MODINE: HSB 18 340 50 81.0 1.3 GPM 180 160 11.8 12.6 1/60 115/1/60 1,3

10-HWUH-1-5 MODINE: HSB 18 340 50 81.0 1.3 GPM 180 160 11.8 12.6 1/60 115/1/60 1,3

10-HWUH-1-6 MODINE: HSB 18 340 50 81.0 1.3 GPM 180 160 11.8 12.6 1/60 115/1/60 1,3

10-HWUH-1-7 MODINE: HSB 18 340 50 81.0 1.3 GPM 180 160 11.8 12.6 1/60 115/1/60 1,3

10-HWUH-1-8 MODINE: HSB 165 3240 50 83.8 13.6 GPM 180 160 123.0 130.9 1/3 115/1/60 1,2,3

MISCELLANEOUS EQUIPMENT SCHEDULE

DESIGNATION EQUIPMENT DESCRIPTION BASIS OF DESIGN COMMENTS

1-AS-B-1 AIR SEPARATOR 6 INCH FLANGED CONNECTIONS, 125 PSIG MAWP, 470 GPM

DESIGN, 550 GPM MAXIMUM, ASME CERTIFIED STAMP, 1.7 FT HD

DESIGN PRESSURE DROP, OPERATING WEIGHT - 366 LBS

BELL & GOSSETT

CRSN-6F'

1-ET-B-1 EXPANSION TANK VERTICAL BLADDER STYLE, 125 PSIG MAWP, 240 DEG F MDMT,

106 GALLON VOLUME, 30.4 GALLON ACCEPTANCE VOLUME

ASME CERTIFIED STAMP

BELL & GOSSETT

B400

4-AS-B-1 AIR SEPARATOR 2.5 INCH FLANGED CONNECTIONS, 125 PSIG MAWP, 80 GPM

DESIGN, 96 GPM MAXIMUM, ASME CERTIFIED STAMP, 1.1 FT HD

DESIGN PRESSURE DROP, OPERATING WEIGHTT - 84 LBS

BELL & GOSSETT

CRSN-2-1/2F

4-ET-B-1 EXPANSION TANK VERTICAL BLADDER STYLE, 125 PSIG MAWP, 240 DEG F MDMT,

23 GALLON VOLUME, 7.6 GALLON ACCEPTANCE VOLUME, ASME

CERTIFIED STAMP

BELL & GOSSETT

B85

5-AS-1-1 AIR SEPARATOR 4 INCH FLANGED CONNECTIONS, 125 PSIG MAWP, 150 GPM

DESIGN, 245 GPM MAXIMUM, ASME CERTIFIED STAMP, 0.41 FT

HD DESIGN PRESSURE DROP, OPERATING WEIGHT 147 LBS

BELL & GOSSETT

CRSN-4F

5-ET-1-1 EXPANSION TANK VERTICAL BLADDER STYLE, 125 PSIG MAWP, 240 DEG F MDMT,

23 GALLON VOLUME, 8.4 GALLON ACCEPTANCE VOLUME, ASME

CERTIFIED STAMP

TACO CA90-125

10-AS-01 AIR SEPARATOR 8 INCH FLANGED CONNECTIONS, 125 PSIG MAWP, 1,340 GPM

DESIGN, 1,900 GPM MAXIMUM; ASME CERTIFIED STAMP, 1.93 FT

HD DESIGN PRESSURE DROP; OPERATING WEIGHT - 1,200 LBS

BELL & GOSSETT

RL-8F

10-ET-1-1 EXPANSION TANK VERTICAL BLADDER TYPE, 125 PSIG MAWP, 240 DEG F MDMT,

158 GALLON VOLUME, 84 GALLON ACCEPTANCE VOLUME; ASME

CERTIFIED STAMP

BELL & GOSSETT

CA600-125

10-ET-1-2 EXPANSION TANK VERTICAL BLADDER TYPE, 125 PSIG MAWP, 240 DEG F MDMT,

158 GALLON VOLUME, 84 GALLON ACCEPTANCE VOLUME; ASME

CERTIFIED STAMP

BELL & GOSSETT

CA600-125

FUEL OIL FILTER SCHEDULE

MARK MANUFACTURER MODEL FLOW (GPH) FLOW (PSI) VOLTS/PHASE/HZ MOTOR HP

10-FOF-1-1 PREFERRED UTLITIES PF-505-BGZ-1333 1200 50 120/1/60 3/4

AIR DEVICE SCHEDULE

NO. MIN CFM MAX CFM

NECK

SIZE

(WxH)

NECK

SIZE (ø)

MAX. NC TYPE BASIS OF DESIGN

TRANSFER AIR

T1 0 155 8x8 15 DEFLECTION PRICE 510Z

T2 0 210 8 18 SQUARE PLAQUE PRICE SPD

SUPPLY AIR

S1 0 110 6 18 SQUARE PLAQUE PRICE SPD

S4 0 250 8 18 SQUARE PLAQUE PRICE SPD

S10 1750 2125 25 DRUM PRICE HCD

S20 0 250 6x10 20 DEFLECTION PRICE 510

S21 2530 3000 18x36 29 DEFLECTION PRICE 510

EXHAUST AIR

E1 0 195 6 15 PERFORATED PRICE PDDR

E2 0 200 6 18 PERFORATED PRICE PDDR

E3 1400 1560 26x18 30 DEFLECTION PRICE 530

E4 0 240 10x6 30 DEFLECTION PRICE 530

FUEL OIL TANK SCHEDULE

MARK BASIS OF DESIGN CAPACITY (G) LENGTH DIAMETER

10-AST-01 HIGHLAND TANK 15,000 25'-6" 10'-6"

10-AST-02 HIGHLAND TANK 15,000 25'-6" 10'-6"

GENERATOR DAY TANK SCHEDULE

MARK MANUFACTURER MODEL NO. CAPACITY (GAL) VOLTS/PHASE/HZ

10-DT-01 PREFERRED ULTILITIES DTBG-220 220 120/1/60

MAKE-UP AIR UNIT SCHEDULE

MARK

EWT

(DEG. F)

LWT

(DEG. F)

EAT

(DEG. F)

LAT

(DEG. F)

CAPACITY

MBH GPM HEATING TYPE CFM FAN ESP (IN WC) FAN RPM MOTOR HP

ELECTRICAL WEIGHT

(LBS) BASIS OF DESIGN COMMENTSV PH HZ

10-MAU-1-1 180 160 14 55 266.9 26.7 HOT WATER 6000 0.50 1187 7.5 460 3 60 963 DAIKIN: CAH009GHCM PROVIDE 2" MERV 8 FILTERS

10-MAU-1-2 180 160 14 55 266.9 26.7 HOT WATER 6000 0.50 1187 7.5 460 3 60 963 DAIKIN: CAH009GHCM PROVIDE 2" MERV 8 FILTERS

DOAS WITH ERV SCHEDULE

UNIT NO. AREA SERVED LOCATION

OUTSIDE AIR ECM SUPPLY FAN ECM EXHAUST FAN PLATE TYPE TOTAL ENERGY RECOVERY TOTAL EFFECTIVENESS DX COOLING SYSTEM EA FILTER OA FILTER

V/PH/HZ

ELECTRICAL

DATA

INDOOR

UNIT

WEIGHT

(LBS)

OUTDOOR UNIT

V/PH/HZ MCAO MOPO

OUTDOOR

UNIT

WEIGHT

(LBS) BASIS OF DESIGNMAX. CFM

FAN

WHEEL

TYPE

MAX.

ESP

FAN

WHEEL

TYPE

MAX.

ESP

SUMMER WINTER

SUMMER% WINTER%

EAT

DB

(°F)

EAT

WB

(°F)

LAT

DB

(°F)

LAT

WB

(°F)

MAX

FACE

VEL.

(FPM)

TOTAL

CAP.

(MBH)

SENS.

CAP.

(MBH) MERV

APD

MERV

APD

MCA MOCP MARK

CAPACITY

(MBH)

AMBIENT

SUMMER

AMBIENT

WINTER SEER2QTY.

POWER

(kW)

MAX

RPM

EXHAUST

CFM QTY.

POWER

(kW)

MAX.

RPM

INPUT AIR CONDITIONS

OUTPUT AIR

CONDITIONS INPUT AIR CONDITIONS

OUTPUT AIR

CONDITIONS

INITIAL FINAL INITIAL FINAL

OA EAT

DB (°F)

OA EAT

WB (°F)

EA EAT

DB (°F)

EA EAT

WB (°F)

OA LAT

DB (°F)

OA LAT

WB (°F)

OA EAT

DB (°F)

OA EAT

WB (°F)

EA EAT

DB (°F)

EA EAT

WB (°F)

OA LAT

DB (°F)

OA LAT

WB (°F)

10-DOAS-2-1 CONTROL ROOM MEZZANINE 1100 1 2.0 2550 BC 1.5 900 1 2 2250 BC 1.0 94 75 75 62.6 80.2 67.4 14 11.8 70 53 46.2 35.7 75% 80% 80.2 67.4 55.0 54.0 350 44.1 30.1 8 0.25 1.0 13 0.4 1 208/3/60 13.83 15 833 10-AHUCU-3-1 96 94 14 16.0 208/1/60 34.6 35 220 OXYGEN 8 H15IN-ERV-BP/DAIKIN RXTA60AAVJU

AIR TERMINAL UNIT SCHEDULE

UNIT NO. LOCATION INLET SIZE OUTLET SIZE

DESIGN

CFM

MAX

APD

NC

RATING

HEATING COIL CHARACTERISTICS

V/PH/HZ COMMENTSMBH LAT (°F) EWT (°F)

LWT

(°F) GPM

NO. OF

ROWS WPD

10-ATU-1-1 CONTROL ROOM 12 16"X15" 890 0.5 25 26.5 74 180 160 2.6 1 5 24 VDC

10-ATU-1-2 MENS LOCKER 4 12"X8" 100 0.5 25 3.6 79 180 160 0.4 1 5 24 VDC

10-ATU-1-3 WOMENS LOCKER 4 12"X8" 110 0.5 25 5.1 89 180 160 0.5 1 5 24 VDC

NOTES:

1. PROVIDE WITH ECM FAN OR FAN CAPABLE OF BEING CONTROLLED BY FACTORY VFD.

2. PROVIDE MFR. REMOTE MOUNTED ELECTRICAL/CONTROL PANEL TO BE FIELD WIRED AND CONNECTED TO UNIT BY ELECTRICAL CONTRACTOR.

NOTES:

1. MOUNT UNITS AT ± 9'-0" A.F.F. AND ADJUST HORIZONTAL DEFLECTOR BLADES SUCH THAT AIRFLOW IS DIRECTED AT A 45 DEGREE ANGLE TO THE FLOOR.

2. PROVIDE WITH CLASS 1 DIVISION II GROUP D EXPLOSION PROOF MOTOR AND CONSTRUCTION.

3. PROVIDE UNIT OR REMOTE MOUNTED THERMOSTAT, CONNECT TO ASSOCIATED UNIT HEATER.

NOTES:

1. FAN SHALL BE SPARK B RESISTANT CONSTRUCTION WITH CLASS 1 DIVISION II GROUP D EXPLOSION PROOF MOTOR, AND STAINLESS STEEL HARDWARE.

2. FAN SHALL BE HIGH WIND RATED AND SHALL BE MOUNTED TO HIGH WIND RATED CURB.

3. PROVIDE FAN WITH FACTORY MOUNTED VFD WITH BAS INTERFACE.

NOTES:

1. PROVIDE WITH INTEGRAL RUPTURE BASIN.

2. PROVIDE WITH FACTORY MOUNTED CONTROL PANEL.

3. PROVIDE WITH FACTORY MOUNTED RETURN PUMP.

Revisions Date

2 Bid Addendum 2 01/12/2026

Sheets
M-801 - MECHANICAL SCHEDULES