This mechanical schedules document for the VA Loch Raven Construct Consolidated Boiler Spaces project in Baltimore, MD provides comprehensive equipment specifications for a complex mechanical system upgrade. The document details multiple mechanical systems including three 6,695 MBH Cleaver Brooks fire tube boilers, hydronic pumps, gas booster skids, make-up air units, exhaust fans, air terminal units, and various supporting equipment like air separators, expansion tanks, and fuel oil transfer pumps. The mechanical design incorporates redundant systems with specifications for electrical connections, flow rates, temperature ranges, and performance metrics, with equipment from manufacturers like Bell & Gossett, Daikin, Greenheck, and Modine. The project appears to be a comprehensive upgrade of the mechanical infrastructure for the VA facility, with bid documents dated 07/07/2025 and a mechanical design focused on efficiency, reliability, and precise environmental control.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
VA Project No.
AG Project No.
A u to d e s k D o c s /0
V A
M C
L o c h R a v e n
B o ile r C o n s o lid a ti o n /0
V A
L R
B o ile r C o n s o lid a ti o n
R
M
E P
.r v t
/1
/2
:2
:5
A
M
M-801
MECHANICAL SCHEDULES Loch Raven Construct Consolidated Boiler Spaces
BALTIMORE MD
0123038
07/07/2025 GSC ZGC
BID DOCUMENTS
512-23-154
HOT WATER BOILER SCHEDULE
MARK DESCRIPTION TYPE
OUTPUT
(MBH)
WATER PERFORMANCE
MAWP
(PSIG)
HEATING
SURFACE
(SQ. FT.)
SAFETY RELIEF VALVES BURNER REQUIREMENTS NATURAL GAS PERFORMANCE ULSD FO PERFORMANCE ELECTRICAL CONNECTION SIZES OVERALL DIMENSIONS
APPROX.
OPERATING
WEIGHT (LBS)
BASIS OF DESIGN
SUPPLY WATER
TEMPERATURE
(DEG F)
RETURN WATER
TEMPERATURE
(DEG F)
DESIGN FLOW
RATE (GPM)
LOWEST
PRESSURE,
SVB1 (PSIG)
HIGHEST
PRESSURE,
SVB2 (PSIG)
BURNER FUELS
(PRIMARY /
SECONDARY)
IGNITER FUELS
(PRIMARY /
SECONDARY)
EMISSIONS
RATING (PPM
NOx)
FD FAN
MOTOR HP
INPUT
(MBH)
MIN. BOILER
EFFICIENCY (%)
AVAIL. GAS
PRESS.
(PSIG)
INPUT
(MBH)
MIN. BOILER
EFFICIENCY (%)
OIL PUMP
MOTOR
(HP)
AIR COMPRESSOR
MOTOR (HP)
AVAIL. FUEL
PRESS.
(PSIG)
BOILER
BLOWER
V/PH/HZ
OIL PUMP
V/HZ/PH
AIR COMPRESSOR
V/PH/HZ
GAS
(IN.)
OIL
(IN.)
HW INLET
(IN.)
HW OUTLET
(IN.)
DRAIN AIR VENT FLUE
VENT
(IN.) WIDTH HEIGHT MANUFACTURER MODEL NO.V/PH/HZ FLA MCA MOP MIN. SCCR (AMPS) QTY. SIZE (IN.) QTY. SIZE (IN.)
10-B-1-1 4-PASS WETBACK FIRE TUBE 6,695 180 160 670 200 1,000 73 75 NAT. GAS / FUEL OIL NAT. GAS / PROPANE 30 15 8,370 80 1 8,166 82 1/2 3 100 460/3/60 40 - 50 5K 460/3/60 N/A 460/3/60 2 1 6 6 2 2 1 1.5 16 82.75 101.75 30,000 CLEAVER BROOKS CBLE-4W-200W
10-B-1-2 4-PASS WETBACK FIRE TUBE 6,695 180 160 670 200 1,000 73 75 NAT. GAS / FUEL OIL NAT. GAS / PROPANE 30 15 8,370 80 1 8,166 82 1/2 3 100 460/3/60 40 - 50 5K 460/3/60 N/A 460/3/60 2 1 6 6 2 2 1 1.5 16 82.75 101.75 30,000 CLEAVER BROOKS CBLE-4W-200W
10-B-1-3 4-PASS WETBACK FIRE TUBE 6,695 180 160 670 200 1,000 73 75 NAT. GAS / FUEL OIL NAT. GAS / PROPANE 30 15 8,370 80 1 8,166 82 1/2 3 100 460/3/60 40 - 50 5K 460/3/60 N/A 460/3/60 2 1 6 6 2 2 1 1.5 16 82.75 101.75 30,000 CLEAVER BROOKS CBLE-4W-200W
NOTES:
1. PROVIDE SINGLE POINT ELECTRICAL CONNECTION FOR EACH FORCED DRAFT FAN, FORCED DRAFT FAN AIR CONDITIONER, ATOMIZING AIR COMPRESSOR, AND BOILER CONTROL PANEL.
2. BOILERS SHALL NOT BE PROVIDED WITH A FLUE GAS ECONOMIZER.
3. PROVIDE UNIT-MOUNTED, NFPA 85 COMPLIANT, UL 508A, CONTROL PANEL TO CONTAIN BURNER MANAGEMENT SYSTEM (BMS) AND COMBUSTION CONTROL SYSTEM (CCS). PROVIDE PANEL AIR CONDITIONER PER SCHEDULE. REFER TO SPECIFICATIONS FOR DETAILED PANEL CONSTRUCTION REQUIREMENTS.
4. PROVIDE WITH LOW NOx BURNERS. FLUE GAS RECIRCULATION MAY BE USED AS REQUIRED TO OBTAIN EMISSIONS.
5. BOILERS SHALL BE CONSTRUCTED AND ASME STAMPED FOR LISTED MAWP.
6. PROVIDE FD FAN VARIABLE FREQUENCY DRIVE, UNIT-MOUNTED AND ADJACENT TO BOILER CONTROL PANEL.
7. BACKUP IGNITER FUEL SHALL BE PROPANE. AVAILABLE PROPANE PRESSURE IS 1.5 PSIG.
8. BASIS OF DESIGN MANUFACTURER PROVIDE A SINGLE PRESSURE RELIEF VALVE AS INDICATED IN THE SCHEDULE. CONTRACTOR RESPONSIBLE FOR COORDINATION OF LAYOUT, MATERIALS, AND LABOR FOR MORE THAN A SINGLE VALVE, IF PROVIDED.
NOTES:
1. PROVIDE HOT GAS BYPASS FOR OPERATION DURING LOW LOAD OPERATIONS.
2. MOUNT CONDENSING UNIT ON ROOF. SEE SHEET MH103 FOR MORE INFORMATION.
3. PROVIDE WITH LOW AMBIENT KIT TO OPERATE DOWN TO 0°f AMBIENT.
4. PROVIDE WITH NON-FUSED DISCONNECT SWITCH.
5. MOUNT INDOOR UNIT IN HORIZONTAL CONFIGURATION SUPPORTED FROM STRUCTURE ABOVE.
6. ROUTE CONDENSATE TO LOCATION INDICATED ON PLANS.
7. PROVIDE WITH SEPARATE 208/1/60, 15A CONNECTION FOR CONTROLLER.
8. PROVIDE WITH R-32 REFRIGERANT. PROVIDE WITH MANUFACTURER STANDARD REFRIGERANT DETECTION SYSTEM.
HYDRONIC PUMP SCHEDULE
MARK LOCATION SYSTEM TYPE
FLUID DATA PUMP DATA ELECTRICAL DATA BASIS OF DESIGN
FLOW (GPM) HEAD (FT) NPSHR FLUID TEMP.
IMPELLER
SIZE % EFF.
SUCT. SIZE
(IN.)
DISCH. SIZE
(IN.)
MOTOR SIZE
(HP) MOTOR RPM V/PH/HZ MANUFACTURER MODEL NO.
10-PHWP-1-1 BUILDING 10 PRIMARY HEATING WATER END SUCTION 670 55 8.86 180 8.625 84 5 4 15 1800 460/3/60 BELL & GOSSETT e-1510
10-PHWP-1-2 BUILDING 10 PRIMARY HEATING WATER END SUCTION 670 55 8.86 180 8.625 84 5 4 15 1800 460/3/60 BELL & GOSSETT e-1510
10-PHWP-1-3 BUILDING 10 PRIMARY HEATING WATER END SUCTION 670 55 8.86 180 8.625 84 5 4 15 1800 460/3/60 BELL & GOSSETT e-1510
10-SHWP-1-1 BUILDING 10 SECONDARY HEATING WATER END SUCTION 670 100 8.37 180 10.875 82 4 3 25 1800 460/3/60 BELL & GOSSETT e-1510
10-SHWP-1-2 BUILDING 10 SECONDARY HEATING WATER END SUCTION 670 100 8.37 180 10.875 82 4 3 25 1800 460/3/60 BELL & GOSSETT e-1510
10-SHWP-1-3 BUILDING 10 SECONDARY HEATING WATER END SUCTION 670 100 8.37 180 10.875 82 4 3 25 1800 460/3/60 BELL & GOSSETT e-1510
1-HHWP-B-1 BUILDING 1 BUILDING 1 HEATING WATER END SUCTION 470 130 7.6 180 12.625 75 4 3 25 1800 460/3/60 BELL & GOSSETT e-1510
1-HHWP-B-2 BUILDING 1 BUILDING 1 HEATING WATER END SUCTION 470 130 7.6 180 12.625 75 4 3 25 1800 460/3/60 BELL & GOSSETT e-1510
4-HHWP-B-1 BUILDING 4 BUILDING 4 HEATING WATER INLINE 80 55 6.65 180 9.5 56 2 2 3 1800 208/3/60 BELL & GOSSETT e-80SC
4-HHWP-B-2 BUILDING 4 BUILDING 4 HEATING WATER INLINE 80 55 6.65 180 9.5 56 2 2 3 1800 208/3/60 BELL & GOSSETT e-80SC
5-HHWP-1-1 BUILDING 5 BUILDING 5 HEATING WATER INLINE 80 55 6.65 180 9.5 56 2 2 3 1800 208/3/60 BELL & GOSSETT e-80SC
5-HHWP-1-2 BUILDING 5 BUILDING 5 HEATING WATER INLINE 80 55 6.65 180 9.5 56 2 2 3 1800 208/3/60 BELL & GOSSETT e-80SC
5-HHWP-1-3 BUILDING 5 BUILDING 5 HEATING WATER INLINE 80 55 6.65 180 9.5 56 2 2 3 1800 208/3/60 BELL & GOSSETT e-80SC
6-HHWP-1-1 BUILDING 6 BUILDING 6 HEATING WATER INLINE
CIRCULATOR
15 20 --- 180 - 43 1.25 1.25 1/6 3392 120/1/60 BELL & GOSSETT ECOCIRC XL 36-45
6-HHWP-1-1 BUILDING 6 BUILDING 6 HEATING WATER INLINE
CIRCULATOR
15 20 --- 180 - 43 1.25 1.25 1/6 3392 120/1/60 BELL & GOSSETT ECOCIRC XL 36-45
10-HHWP-2-1 BUILDING 10 BUILDING 10 HEATING WATER INLINE
CIRCULATOR
61 30 --- 180 - 56 1.5 1.5 3 2234 460/3/60 BELL & GOSSETT ECOCIRC XL
110-180
10-HHWP-2-2 BUILDING 10 BUILDING 10 HEATING WATER INLINE
CIRCULATOR
61 30 --- 180 - 56 1.5 1.5 3 2234 460/3/60 BELL & GOSSETT ECOCIRC XL
110-180
NOTES:
1. PROVIDE SUCTION DIFFUSER OR REDUCING SUCTION DIFFUSER FOR EACH PUMP. COORDINATE SIZING BETWEEN SUCTION PIPING AND PUMP SUCTION FLANGE SIZE REQUIRED FOR PERFORMANCE INDICATED.
2. PROVIDE LEVELING GROUT AND BASE GROUTING IN ACCORDANCE WITH SPECIFICATIONS AND MANUFACTURERS REQUIREMENTS. COORDINATE INSTALLATION WITH COLD AND HOT ALIGNMENT ACTIVITIES.
3. DISCONNECT AND VARIABLE FREQUENCY DRIVE PROVIDED BY DIVISION 26.
4. PROVIDE INSULATION BOX PER DETAIL AND AS SPECIFIED.
5. INSTALL PER END SUCTION PUMP DETAIL.
6. DRAIN PUMP BASE PAN TO NEAREST FLOOR DRAIN. PROVIDE COPPER TYPE L PIPING FOR ALL DRAIN PIPING. TERMINATE AT FLOOR DRAIN WITH DIAGONAL CUT TO PREVENT CONNECTION.
FLOW METER SCHEDULE
DEVICE
NUMBER SERVICE SYSTEM / LOCATION TYPE SENSING DIRECTION ACCURACY TURNDOWN
PIPE SIZE
(IN.)
MAX. FLOW DESIGN FLOW
OUTPUT BASIS OF DESIGNPPH GPM CFH PPH GPM CFH
FE 04004 HHW TO DISTRIBUTION BOILER PLANT FLANGED, MAGNETIC UNI-DIRECTIONAL +/- 1.0% 10 TO 1 8 - 2,010 - - 1,340 - 4-20 mA YOKOGAWA
FE 02001 SW TO HEATING HW SYSTEM BOILER PLANT FLANGED, NUTATING DISC UNI-DIRECTIONAL +/- 1.5% 10 TO 1 2-1/2 - 250 - - 250 - 4-20 mA BADGER
FE 04101 HHS FROM BLR-01 BOILER PLANT FLANGED, MAGNETIC UNI-DIRECTIONAL +/- 1.0% 10 TO 1 6 - 800 - - 670 - 4-20 mA YOKOGAWA
FE 04201 HHS FROM BLR-02 BOILER PLANT FLANGED, MAGNETIC UNI-DIRECTIONAL +/- 1.0% 10 TO 1 6 - 800 - - 670 - 4-20 mA YOKOGAWA
FE 04301 HHS FROM BLR-03 BOILER PLANT FLANGED, MAGNETIC UNI-DIRECTIONAL +/- 1.0% 10 TO 1 6 - 800 - - 670 - 4-20 mA YOKOGAWA
FE 12113 NG TO BLR-01 BOILER PLANT FLANGED, THERMAL MASS UNI-DIRECTIONAL +/- 0.5% 20 TO 1 3 - - 10,000 - - 8,370 4-20 mA SIERRA
FE 12213 NG TO BLR-02 BOILER PLANT FLANGED, THERMAL MASS UNI-DIRECTIONAL +/- 0.5% 20 TO 1 3 - - 10,000 - - 8,370 4-20 mA SIERRA
FE 12313 NG TO BLR-03 BOILER PLANT FLANGED, THERMAL MASS UNI-DIRECTIONAL +/- 0.5% 20 TO 1 3 - - 10,000 - - 8,370 4-20 mA SIERRA
FE 03164 FO TO BLR-01 BOILER PLANT THREADED, POS. DISP. UNI-DIRECTIONAL +/- 1.0% 10 TO 1 1 - 3 - - 2 - SCALABLE NPN
TRANSISTOR
FLOMEC G2 SERIES
FE 03264 FO TO BLR-02 BOILER PLANT THREADED, POS. DISP. UNI-DIRECTIONAL +/- 1.0% 10 TO 1 1 - 3 - - 2 - SCALABLE NPN
TRANSISTOR
FLOMEC G2 SERIES
FE 03364 FO TO BLR-03 BOILER PLANT THREADED, POS. DISP. UNI-DIRECTIONAL +/- 1.0% 10 TO 1 1 - 3 - - 2 - SCALABLE NPN
TRANSISTOR
FLOMEC G2 SERIES
FE 03001 FO TO FOPS-01 BOILER PLANT THREADED, POS. DISP. UNI-DIRECTIONAL +/- 1.0% 20 TO 1 2 - 7 - - 7 - SCALABLE NPN
TRANSISTOR
FLOMEC G2 SERIES
FE 03002 FO FROM FOPS-02 BOILER PLANT THREADED, POS. DISP. UNI-DIRECTIONAL +/- 1.0% 20 TO 1 2 - 7 - - 7 - SCALABLE NPN
TRANSISTOR
FLOMEC G2 SERIES
FE 04006 HHW TO BOILER PLANT BOILER PLANT FLANGED, MAGNETIC UNI-DIRECTIONAL +/- 1.0% 10 TO 1 2 - 200 - - 150 - 4-20mA YOKOGAWA
FE 04005 HHW DECOUPLER BOILER PLANT FLANGED, MAGNETIC BI-DIRECTIONAL +/- 1.0% 10 TO 1 8 - 1,340 - - 670 - 4-20mA YOKOGAWA
FE 12001 GAS BOOSTER DISCHARGE BOILER PLANT FLANGED, THERMAL MASS UNI-DIRECTIONAL +/- 1.0% 20 TO 1 6 - - 20,000 - - 16,740 4-20 mA SIERRA
FE 04011 HHW TO BUILDING 01 BUILDING 01 FLANGED, MAGNETIC UNI-DIRECTIONAL +/- 1.0% 10 TO 1 6 - - - - 4-20 mA YOKOGAWA
FE 04041 HHW TO BUILDING 04 BUILDING 05 FLANGED, MAGNETIC UNI-DIRECTIONAL +/- 1.0% 10 TO 1 3 - - - - 4-20 mA YOKOGAWA
FE 04051 HHW TO BUILDING 05 BUILDING 06 FLANGED, MAGNETIC UNI-DIRECTIONAL +/- 1.0% 10 TO 1 3 - - - - 4-20 mA YOKOGAWA
FE 04061 HHW TO BUILDING 06 BUILDING 07 FLANGED, MAGNETIC UNI-DIRECTIONAL +/- 1.0% 10 TO 1 2 - - - - 4-20 mA YOKOGAWA
FE 04071 HHW TO BUILDING 07 BUILDING 04 FLANGED, MAGNETIC UNI-DIRECTIONAL +/- 1.0% 10 TO 1 3 - - - - 4-20 mA YOKOGAWA
NOTES:
1. REVIEW REQUIRED UPSTREAM AND DOWNSTREAM PIPING CONDITIONS AND VERIFY THEY MEET THE METER MANUFACTURERS REQUIREMENTS PRIOR TO COMPLETING INSTALLATION.
2. METERS SHALL BE LOCATED IN AN ACCESSIBLE AREA. IF MOUNTED HIGHER THAN SEVEN (7) FEET ABOVE THE FINISHED FLOOR, PROVIDE REMOTE MOUNTED ELECTRONICS. MOUNT PER MANUFACTURERS REQUIREMENTS AT 5'-0"
ABOVE FINISHED FLOOR.
3. REFER TO SPECIFICATIONS FOR ADDITIONAL COMMUNICATION AND CONTROL REQUIREMENTS OF METER TRANSMITTER AND ELECTRONICS.
AUTOMATIC FUEL OIL TRANSFER PUMP SCHEDULE
MARK TYPE GPH OIL GRADE VISCOSITY
OIL TEMPERATURE
(°F)
MINIMUM SYSTEM PRESSURE
(PSIG)
PUMP DISCHARGE PRESSURE
(PSIG) MOTOR HP V/PH/HZ LENGTH WIDTH HEIGHT MANUFACTURER MODEL NO.
10-FOPS-1-1 POSITIVE DISPLACEMENT 925 NO. 2
(ULSD)
45 SSU 60 100 125 (2) 2 460/3/60 65' - 0 1/2" 30' - 0 1/2" 6' - 2" PREFERRED UTILITIES
MFG CORP
ATPSF-206BGZ133
3-D-DP-L
NOTES:
1. PROVIDE WITH INTEGRAL DISCONNECT.
2. PROVIDE WITH FACTORY 120V/1-PH STEP DOWN TRANSFORMER FOR CONTROLS.
3. PROVIDE TEFC PUMP MOTORS.
4. PROVIDE INLET VALVE ASSEMBLY FOR LEVEL CONTROL.
5. UNIT SHALL BE DUPLEX TYPE WITH REDUNDANT POSITIVE DISPLACEMENT PUMPS.
6. PROVIDE WITH DUPLEX STRAINER DIFFERENTIAL PRESSURE SWITCH.
7. PROVIDE WITH SET LEAK DETECTION SWITCH.
8. PROVIDE WITH BUILDING AUTOMATION SYSTEM (BAS) DISCRETE OUTPUT CONTACTS.
GAS BOOSTER SKID SCHEDULE
MARK
PEAK GAS
FLOW
(SCFH)
MINIMUM GAS
FLOW (SCFH)
INLET
PRESSURE
(IN. WC)
DISCHARGE
PRESSURE (IN. WC)
RATED MAXIMUM
OPERATING
PRESSURE, MOP
(PSIG) INLET (IN.) OUTLET (IN.) MOTOR HP
MOTOR SPEED
(RPM)
VOLTS/PHASE/
HERTZ MANUFACTURER MODEL
GBS-01 18000 1800 5.0 83 7 4 4 (2) @ 10 3500 460/3/60 SPENCER TURBINE GL-3010-R
NOTES:
1. PROVIDE LOW PRESSURE GAS CUT-OFF SWITCH WITH MANUAL RESET. SET CUT-OFF PRESSURE AT 4.5 IN WG.
2. PROVIDE CLASS I, DIVISION II, GROUP D EXPLOSION PROOF CONSTRUCTION.
3. PROVIDE UL 508A CERTIFIED CONTROL PANEL MEETING THE SEQUENCE OF OPERATIONS AND SPECIFICATION REQUIREMENTS.
MINI-SPLIT DUCTLESS HEAT PUMP SCHEDULE
INDOOR UNIT OUTDOOR UNIT
MARK MODEL NO.
SA CFM (HIGH
SPEED)
TOTAL COOLING
CAPACITY (MBH)
TOTAL HEATING
CAPACITY (MBH) MARK
MODEL
NO. SEER2
NOM.
TONS
AMBIENT
TEMP. (°F)
UNIT ELECTRICAL
MCA MOCP V/PH/HZ
10-IDU-1-1 FTXF18AXVJU 715 18.1 21.6 10-ODU-3-1 RXF18AXJVU 21 1.5 94 16.34 20 208/1/60
10-IDU-1-2 FTXF18AXVJU 715 18.1 21.6 10-ODU-3-2 RXF18AXJVU 21 1.5 94 16.34 20 208/1/60
NOTES:
1. INDOOR UNIT TO BE POWERED BY OUTDOOR UNIT.
2. PROVIDE WITH FACTORY MOUNTED CONDENSATE PUMP.
3. PROVIDE WITH R-32 OR R-454B REFRIGERANT.
4. CONFIRM FINAL REFRIGERANT PIPING LENGTH PRIOR TO ORDER AND PROVIDE MANUFACTURER LONG LINE KIT AS NECESSARY.
5. 10-IDU-1-2 SHALL BE INTERLOCKED WITH GENERATOR TRANSFER SWITCH SUCH THAT WHENEVER GENERATOR IS RUNNING, DUCTLESS UNIT SHALL DE-ENERGIZE.
EXHAUST FAN SCHEDULE
MARK MANUFACTURER MODEL NO. TYPE CFM
ESP
(IN-WG) FAN RPM
ELECTRICAL DRIVE
TYPE
MAX
SONES NOTESMCA/HP V/PH/HZ
10-EF-3-1 GREENHECK CUE-160-A UPBLAST ROOF 3000 0.5 1,364 4.2/2.0 460/3/60 DIRECT 17.9 2,3
10-EF-3-2 GREENHECK CUE-160-A UPBLAST ROOF 3000 0.5 1,364 4.2/2.0 460/3/60 DIRECT 17.9 2,3
10-EF-3-3 GREENHECK CUE-160-A UPBLAST ROOF 3000 0.5 1,364 4.2/2.0 460/3/60 DIRECT 17.9 2,3
10-EF-3-4 GREENHECK CUE-160-A UPBLAST ROOF 3000 0.5 1,364 4.2/2.0 460/3/60 DIRECT 17.9 2,3
10-EF-3-5 PENN BARRY FX18BH UPBLAST ROOF 3000 1.0 1,131 5.8/1.0 208/3/60 BELT 16.7 1,2,3
NATURAL GAS PRESSURE REGULATOR VALVE SCHEDULE (PRV)
MARK LOCATION EQUIPMENT INPUT (SCFH)
INLET PRESSURE
(IN WG)
OUTLET PRESSURE (IN
WG)
VALVE SIZE
(INCHES) Basis Notes
PRV-01 BOILER PLANT BLR-01 8,370 30 22-28 2.5
PRV-02 BOILER PLANT BLR-02 8,370 30 22-28 2.5
PRV-03 BOILER PLANT BLR-03 8,370 30 22-28 2.5
LOUVER SCHEDULE
UNIT NO. SIZE (W" x H") CURB CAP (W" x H") AIRFLOW (CFM) PRESSURE DROP (IN-WG) SERVICE LOCATION BASIS OF DESIGN
10-GLP-3-1 68x80 76x88 26,700 0.099 EXHAUST AIR GENERATOR ROOM GREENHECK: ESD-635PD
10-GLP-3-2 68x86 76x94 28,550 0.195 MAKE UP AIR GENERATOR ROOM GREENHECK: ESD-635PD
10-GLP-3-3 28X44 36X52 6,000 0.194 MAKE UP AIR BOILER ROOM GREENHECK: ESD-635PD
10-GLP-3-4 28X44 36X52 6,000 0.194 MAKE UP AIR BOILER ROOM GREENHECK: ESD-635PD
10-GLP-3-5 26x26 34x34 3,000 0.161 MAKE UP AIR GAS BOOSTER ROOM GREENHECK: ESD-635PD
10-GLP-3-6 14X14 22X22 900 0.125 EXHAUST AIR BOILER ROOM GREENHECK: ESD-635PD
10-GLP-3-7 16X16 24X24 1,100 0.15 OUTSIDE AIR MEZZANINE GREENHECK: ESD-635PD
NOTES:
1. ALL LOUVERS TO BE AMCA 540 AND AMCA 550 LISTED.
2. PROVIDE ALL LOUVERS WITH INSECT SCREEN, 12" CURB, DUCTED INSTALLATION, AND 700 FPM MAXIMUM THROAT VELOCITY FOR INTAKE APPLICATION.
HOT WATER UNIT HEATER SCHEDULE
MARK MODEL NO. SA CFM (MAX.) EAT (°F) LAT (°F) GPM EAT (F°) LWT (F°)
ACTUAL HEATING
CAPACITY (MBH)
STANDARD HEATING
CAPACITY (MBH) FAN MOTOR HP V/PH/HZ NOTES
10-HWUH-1-1 MODINE: HSB 18 340 50 81.0 1.3 GPM 180 160 11.8 12.6 1/60 115/1/60 1,3
10-HWUH-1-2 MODINE: HSB 18 340 50 81.0 1.3 GPM 180 160 11.8 12.6 1/60 115/1/60 1,3
10-HWUH-1-3 MODINE: HSB 18 340 50 81.0 1.3 GPM 180 160 11.8 12.6 1/60 115/1/60 1,3
10-HWUH-1-4 MODINE: HSB 18 340 50 81.0 1.3 GPM 180 160 11.8 12.6 1/60 115/1/60 1,3
10-HWUH-1-5 MODINE: HSB 18 340 50 81.0 1.3 GPM 180 160 11.8 12.6 1/60 115/1/60 1,3
10-HWUH-1-6 MODINE: HSB 18 340 50 81.0 1.3 GPM 180 160 11.8 12.6 1/60 115/1/60 1,3
10-HWUH-1-7 MODINE: HSB 18 340 50 81.0 1.3 GPM 180 160 11.8 12.6 1/60 115/1/60 1,3
10-HWUH-1-8 MODINE: HSB 165 3240 50 83.8 13.6 GPM 180 160 123.0 130.9 1/3 115/1/60 1,2,3
MISCELLANEOUS EQUIPMENT SCHEDULE
DESIGNATION EQUIPMENT DESCRIPTION BASIS OF DESIGN COMMENTS
1-AS-B-1 AIR SEPARATOR 6 INCH FLANGED CONNECTIONS, 125 PSIG MAWP, 470 GPM
DESIGN, 550 GPM MAXIMUM, ASME CERTIFIED STAMP, 1.7 FT HD
DESIGN PRESSURE DROP, OPERATING WEIGHT - 366 LBS
BELL & GOSSETT
CRSN-6F'
1-ET-B-1 EXPANSION TANK VERTICAL BLADDER STYLE, 125 PSIG MAWP, 240 DEG F MDMT,
106 GALLON VOLUME, 30.4 GALLON ACCEPTANCE VOLUME
ASME CERTIFIED STAMP
BELL & GOSSETT
B400
4-AS-B-1 AIR SEPARATOR 2.5 INCH FLANGED CONNECTIONS, 125 PSIG MAWP, 80 GPM
DESIGN, 96 GPM MAXIMUM, ASME CERTIFIED STAMP, 1.1 FT HD
DESIGN PRESSURE DROP, OPERATING WEIGHTT - 84 LBS
BELL & GOSSETT
CRSN-2-1/2F
4-ET-B-1 EXPANSION TANK VERTICAL BLADDER STYLE, 125 PSIG MAWP, 240 DEG F MDMT,
23 GALLON VOLUME, 7.6 GALLON ACCEPTANCE VOLUME, ASME
CERTIFIED STAMP
BELL & GOSSETT
B85
5-AS-1-1 AIR SEPARATOR 4 INCH FLANGED CONNECTIONS, 125 PSIG MAWP, 150 GPM
DESIGN, 245 GPM MAXIMUM, ASME CERTIFIED STAMP, 0.41 FT
HD DESIGN PRESSURE DROP, OPERATING WEIGHT 147 LBS
BELL & GOSSETT
CRSN-4F
5-ET-1-1 EXPANSION TANK VERTICAL BLADDER STYLE, 125 PSIG MAWP, 240 DEG F MDMT,
23 GALLON VOLUME, 8.4 GALLON ACCEPTANCE VOLUME, ASME
CERTIFIED STAMP
TACO CA90-125
10-AS-01 AIR SEPARATOR 8 INCH FLANGED CONNECTIONS, 125 PSIG MAWP, 1,340 GPM
DESIGN, 1,900 GPM MAXIMUM; ASME CERTIFIED STAMP, 1.93 FT
HD DESIGN PRESSURE DROP; OPERATING WEIGHT - 1,200 LBS
BELL & GOSSETT
RL-8F
10-ET-1-1 EXPANSION TANK VERTICAL BLADDER TYPE, 125 PSIG MAWP, 240 DEG F MDMT,
158 GALLON VOLUME, 84 GALLON ACCEPTANCE VOLUME; ASME
CERTIFIED STAMP
BELL & GOSSETT
CA600-125
10-ET-1-2 EXPANSION TANK VERTICAL BLADDER TYPE, 125 PSIG MAWP, 240 DEG F MDMT,
158 GALLON VOLUME, 84 GALLON ACCEPTANCE VOLUME; ASME
CERTIFIED STAMP
BELL & GOSSETT
CA600-125
FUEL OIL FILTER SCHEDULE
MARK MANUFACTURER MODEL FLOW (GPH) FLOW (PSI) VOLTS/PHASE/HZ MOTOR HP
10-FOF-1-1 PREFERRED UTLITIES PF-505-BGZ-1333 1200 50 120/1/60 3/4
AIR DEVICE SCHEDULE
NO. MIN CFM MAX CFM
NECK
SIZE
(WxH)
NECK
SIZE (ø)
MAX. NC TYPE BASIS OF DESIGN
TRANSFER AIR
T1 0 155 8x8 15 DEFLECTION PRICE 510Z
T2 0 210 8 18 SQUARE PLAQUE PRICE SPD
SUPPLY AIR
S1 0 110 6 18 SQUARE PLAQUE PRICE SPD
S4 0 250 8 18 SQUARE PLAQUE PRICE SPD
S10 1750 2125 25 DRUM PRICE HCD
S20 0 250 6x10 20 DEFLECTION PRICE 510
S21 2530 3000 18x36 29 DEFLECTION PRICE 510
EXHAUST AIR
E1 0 195 6 15 PERFORATED PRICE PDDR
E2 0 200 6 18 PERFORATED PRICE PDDR
E3 1400 1560 26x18 30 DEFLECTION PRICE 530
E4 0 240 10x6 30 DEFLECTION PRICE 530
FUEL OIL TANK SCHEDULE
MARK BASIS OF DESIGN CAPACITY (G) LENGTH DIAMETER
10-AST-01 HIGHLAND TANK 15,000 25'-6" 10'-6"
10-AST-02 HIGHLAND TANK 15,000 25'-6" 10'-6"
GENERATOR DAY TANK SCHEDULE
MARK MANUFACTURER MODEL NO. CAPACITY (GAL) VOLTS/PHASE/HZ
10-DT-01 PREFERRED ULTILITIES DTBG-220 220 120/1/60
MAKE-UP AIR UNIT SCHEDULE
MARK
EWT
(DEG. F)
LWT
(DEG. F)
EAT
(DEG. F)
LAT
(DEG. F)
CAPACITY
MBH GPM HEATING TYPE CFM FAN ESP (IN WC) FAN RPM MOTOR HP
ELECTRICAL WEIGHT
(LBS) BASIS OF DESIGN COMMENTSV PH HZ
10-MAU-1-1 180 160 14 55 266.9 26.7 HOT WATER 6000 0.50 1187 7.5 460 3 60 963 DAIKIN: CAH009GHCM PROVIDE 2" MERV 8 FILTERS
10-MAU-1-2 180 160 14 55 266.9 26.7 HOT WATER 6000 0.50 1187 7.5 460 3 60 963 DAIKIN: CAH009GHCM PROVIDE 2" MERV 8 FILTERS
DOAS WITH ERV SCHEDULE
UNIT NO. AREA SERVED LOCATION
OUTSIDE AIR ECM SUPPLY FAN ECM EXHAUST FAN PLATE TYPE TOTAL ENERGY RECOVERY TOTAL EFFECTIVENESS DX COOLING SYSTEM EA FILTER OA FILTER
V/PH/HZ
ELECTRICAL
DATA
INDOOR
UNIT
WEIGHT
(LBS)
OUTDOOR UNIT
V/PH/HZ MCAO MOPO
OUTDOOR
UNIT
WEIGHT
(LBS) BASIS OF DESIGNMAX. CFM
FAN
WHEEL
TYPE
MAX.
ESP
FAN
WHEEL
TYPE
MAX.
ESP
SUMMER WINTER
SUMMER% WINTER%
EAT
DB
(°F)
EAT
WB
(°F)
LAT
DB
(°F)
LAT
WB
(°F)
MAX
FACE
VEL.
(FPM)
TOTAL
CAP.
(MBH)
SENS.
CAP.
(MBH) MERV
APD
MERV
APD
MCA MOCP MARK
CAPACITY
(MBH)
AMBIENT
SUMMER
AMBIENT
WINTER SEER2QTY.
POWER
(kW)
MAX
RPM
EXHAUST
CFM QTY.
POWER
(kW)
MAX.
RPM
INPUT AIR CONDITIONS
OUTPUT AIR
CONDITIONS INPUT AIR CONDITIONS
OUTPUT AIR
CONDITIONS
INITIAL FINAL INITIAL FINAL
OA EAT
DB (°F)
OA EAT
WB (°F)
EA EAT
DB (°F)
EA EAT
WB (°F)
OA LAT
DB (°F)
OA LAT
WB (°F)
OA EAT
DB (°F)
OA EAT
WB (°F)
EA EAT
DB (°F)
EA EAT
WB (°F)
OA LAT
DB (°F)
OA LAT
WB (°F)
10-DOAS-2-1 CONTROL ROOM MEZZANINE 1100 1 2.0 2550 BC 1.5 900 1 2 2250 BC 1.0 94 75 75 62.6 80.2 67.4 14 11.8 70 53 46.2 35.7 75% 80% 80.2 67.4 55.0 54.0 350 44.1 30.1 8 0.25 1.0 13 0.4 1 208/3/60 13.83 15 833 10-AHUCU-3-1 96 94 14 16.0 208/1/60 34.6 35 220 OXYGEN 8 H15IN-ERV-BP/DAIKIN RXTA60AAVJU
AIR TERMINAL UNIT SCHEDULE
UNIT NO. LOCATION INLET SIZE OUTLET SIZE
DESIGN
CFM
MAX
APD
NC
RATING
HEATING COIL CHARACTERISTICS
V/PH/HZ COMMENTSMBH LAT (°F) EWT (°F)
LWT
(°F) GPM
NO. OF
ROWS WPD
10-ATU-1-1 CONTROL ROOM 12 16"X15" 890 0.5 25 26.5 74 180 160 2.6 1 5 24 VDC
10-ATU-1-2 MENS LOCKER 4 12"X8" 100 0.5 25 3.6 79 180 160 0.4 1 5 24 VDC
10-ATU-1-3 WOMENS LOCKER 4 12"X8" 110 0.5 25 5.1 89 180 160 0.5 1 5 24 VDC
NOTES:
1. PROVIDE WITH ECM FAN OR FAN CAPABLE OF BEING CONTROLLED BY FACTORY VFD.
2. PROVIDE MFR. REMOTE MOUNTED ELECTRICAL/CONTROL PANEL TO BE FIELD WIRED AND CONNECTED TO UNIT BY ELECTRICAL CONTRACTOR.
NOTES:
1. MOUNT UNITS AT ± 9'-0" A.F.F. AND ADJUST HORIZONTAL DEFLECTOR BLADES SUCH THAT AIRFLOW IS DIRECTED AT A 45 DEGREE ANGLE TO THE FLOOR.
2. PROVIDE WITH CLASS 1 DIVISION II GROUP D EXPLOSION PROOF MOTOR AND CONSTRUCTION.
3. PROVIDE UNIT OR REMOTE MOUNTED THERMOSTAT, CONNECT TO ASSOCIATED UNIT HEATER.
NOTES:
1. FAN SHALL BE SPARK B RESISTANT CONSTRUCTION WITH CLASS 1 DIVISION II GROUP D EXPLOSION PROOF MOTOR, AND STAINLESS STEEL HARDWARE.
2. FAN SHALL BE HIGH WIND RATED AND SHALL BE MOUNTED TO HIGH WIND RATED CURB.
3. PROVIDE FAN WITH FACTORY MOUNTED VFD WITH BAS INTERFACE.
NOTES:
1. PROVIDE WITH INTEGRAL RUPTURE BASIN.
2. PROVIDE WITH FACTORY MOUNTED CONTROL PANEL.
3. PROVIDE WITH FACTORY MOUNTED RETURN PUMP.
Revisions Date
2 Bid Addendum 2 01/12/2026
| Sheets |
| M-801 - MECHANICAL SCHEDULES |