Full Set - Drawings Chiller.pdf
PDF 10 MB Posted
- Attached to
- C1NB--Cooling Tower Replacement Project 595-11-135 Federal contract opportunity
- Solicitation number
- 36C24420R0014
About this file
This document package includes drawings and specifications for a chiller replacement project. The project scope involves removing existing chillers and related equipment and installing new water-cooled centrifugal chillers, pumps, cooling towers, and associated mechanical, electrical and controls systems. Miller-Remick LLC prepared the design documents as a professional engineering firm. The drawings provide demolition, mechanical, electrical and controls plans along with notes, schedules, details and diagrams for the project. Specifications include equipment data and control strategies. The project is for the Department of Veterans Affairs to support facilities in Building 10.
This pre-solicitation notice is for a design-build project to replace cooling towers at the Lebanon Veterans Affairs Medical Center in Lebanon, Pennsylvania. The project scope involves providing design and construction services to renovate the cooling towers under Project No. 595-11-135. The design was previously completed in 2011-2012 but requires updating to meet specifications. The selected contractor will complete any remaining design work and perform construction. The solicitation will be a two-phase best value procurement open only to 100% SDVOSB firms. The anticipated contract value is between $2-5 million. The solicitation and 455-day period of performance are planned to start in February 2020.
View the file
Other files for this federal contract opportunity
Show all 28
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CHILLER REPLACEMENT
NO. DESCRIPTION DATE
BLDG. 10
B
A
C
D
E
F
1 2 3 4 5 6 87 9
97 8654321
BID DOCUMENTS
FULLY SPRINKLERED
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
Department of Veterans Affairs
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0089
B
A
C
D
E
F
GENERAL
COVER SHEET & DRAWING INDEX
GI001
DRMP
PLAN
NORTH
ACTUAL
NORTH
BLDG. 10
B
A
C
D
E
F
1 2 3 4 5 6 87 9
97 8654321
BID DOCUMENTS
FULLY SPRINKLERED
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
Department of Veterans Affairs
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0089
B
A
C
D
E
F
STRUCTURAL
PLAN, NOTES, & DETAILS
S-101
DSER
BLDG. 10
B
A
C
D
E
F
1 2 3 4 5 6 87 9
97 8654321
BID DOCUMENTS
FULLY SPRINKLERED
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
Department of Veterans Affairs
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0089
B
A
C
D
E
F
MECHANICAL
ABBREVIATIONS, NOTES,
& SYMBOLS
M-001
ARFPB
GENERATOR
ROOM
SHOWER
BOILER
ROOM
STORAGE
CHILLER
ROOM
CHILLER REPLACEMENT
NO. DESCRIPTION DATE
BLDG. 10
B
A
C
D
E
F
1 2 3 4 5 6 87 9
97 8654321
BID DOCUMENTS
FULLY SPRINKLERED
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
Department of Veterans Affairs
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0089
B
A
C
D
E
F
MECHANICAL
DEMOLITION PLAN
MD101
ROOM
SHOWER
BOILER
ROOM
STORAGE
CHILLER
ROOM
CHILLER REPLACEMENT
NO. DESCRIPTION DATE
BLDG. 10
B
A
C
D
E
F
1 2 3 4 5 6 87 9
97 8654321
BID DOCUMENTS
FULLY SPRINKLERED
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
Department of Veterans Affairs
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0089
B
A
C
D
E
F
MECHANICAL
FLOOR PLAN
M-101
BLDG. 10
B
A
C
D
E
F
1 2 3 4 5 6 87 9
97 8654321
BID DOCUMENTS
FULLY SPRINKLERED
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
Department of Veterans Affairs
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0089
B
A
C
D
E
F
MECHANICAL
DETAILS
M-501
BLDG. 10
B
A
C
D
E
F
1 2 3 4 5 6 87 9
97 8654321
BID DOCUMENTS
FULLY SPRINKLERED
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
Department of Veterans Affairs
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0089
B
A
C
D
E
F
MECHANICAL
FLOW/CONTROL DIAGRAM
M-601
BLDG. 10
B
A
C
D
E
F
1 2 3 4 5 6 87 9
97 8654321
BID DOCUMENTS
FULLY SPRINKLERED
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
Department of Veterans Affairs
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0089
B
A
C
D
E
F
MECHANICAL
SCHEDULES
M-602
ARFPB
SIZE IN FLOW WPD
IN GPM FT
10-AS 1 BUILDING 10
CHILLED
WATER
FULL FLOW
TANGENTIAL
12 2842 1.4 NO BELL & GOSSET OR EQUAL
BUILT-IN
STRAINER
REQ'D
AIR SEPARATOR SCHEDULE
MARK LOCATION
SYSTEM
AND/OR
SERVICE
TYPE
AIR SEPARATOR
BASIS OF DESIGN OR
APPROVED EQUAL
EWT LWT MAX WPD FLOW EWT LWT
MAX
WPD
TONS °F °F FT GPM °F °F FT
10-WCCH-1 BLDG 10 CAMPUS CENTRIFUGAL 950 0.58 0.355 1421 58 42 10 500 0.00010 3060 85 95 17 0.00025 876 1200 3 480 VFD
SINGLE POINT POWER
CONNECTION
10-WCCH-2 BLDG 10 CAMPUS CENTRIFUGAL 950 0.58 0.355 1421 58 42 10 500 0.00010 3060 85 95 17 0.00025 876 1200 3 480 VFD
SINGLE POINT POWER
CONNECTION
1. SEE SPECIFICATIONS FOR OTHER APPLICABLE ENGINEERING REQUIREMENTS.
2. "MAX kW/TON" AND "MIN COP" SPECIFIED ARE AT DESIGN CONDITION INDICATED.
FOULING
FACTOR
REMARKS
PHASE
TYPE
MAX
kW/TON
MAX IPLV
(kW/TON) FLOW @ FULL
CAPACITY GPM
SPEED
CONTROL
WATER COOLED CHILLER SCHEDULE
CAPACIT
YMARK
MCA VOLTMOCP
3. BOTH THE EVAPORATOR AND CONDENSER SHALL BE DESIGNED FOR VARIABLE FLOW.
EVAPORATOR CONDENSER
FOULING
FACTOR
ELECTRICAL
NOTES
LOCATION
AREA AND/OR
BLDG SERVED
MINIMUM
ALLOWABLE FLOW
GPM
IN IN IN IN IN IN GPM FT FT °F HP
10-P-1
MECHANICAL
ROOM
BUILDING 10 CHILLED WATER 8 6 31 8 6 30
HORZ SPLIT
CASE
WATER 1421 150 30 55 79 100 3 480 1750 VFD
BELL & GOSSETT HSC-S 6X8X17M OR
EQUAL
N+1
10-P-2
MECHANICAL
ROOM
BUILDING 10 CHILLED WATER 8 6 31 8 6 30
HORZ SPLIT
CASE
WATER 1421 150 30 55 79 100 3 480 1750 VFD
BELL & GOSSETT HSC-S 6X8X17M OR
EQUAL
N+1
10-P-3
MECHANICAL
ROOM
BUILDING 10 CHILLED WATER 8 6 31 8 6 30
HORZ SPLIT
CASE
WATER 1421 150 30 55 79 100 3 480 1750 VFD
BELL & GOSSETT HSC-S 6X8X17M OR
EQUAL
N+1
10-P-4
MECHANICAL
ROOM
BUILDING 10 CONDENSER WATER 12 10 36.75 12 10 35
HORZ SPLIT
CASE
WATER 3060 70 30 95 80 75 3 480 1750 VFD
BELL & GOSSETT HSC-S 10x12x12M OR
EQUAL
N+1
10-P-5
MECHANICAL
ROOM
BUILDING 10 CONDENSER WATER 12 10 36.75 12 10 35
HORZ SPLIT
CASE
WATER 3060 70 30 95 80 75 3 480 1750 VFD
BELL & GOSSETT HSC-S 10x12x12M OR
EQUAL
N+1
10-P-6
MECHANICAL
ROOM
BUILDING 10 CONDENSER WATER 12 10 36.75 12 10 35
HORZ SPLIT
CASE
WATER 3060 70 30 95 80 75 3 480 1750 VFD
BELL & GOSSETT HSC-S 10x12x12M OR
EQUAL
N+1
HEAD BASIS OF DESIGN OR
APPROVED EQUAL
REMARKS
PUMP SCHEDULE
CIRCULATING FLUID
FLUID
FLOW
MIN %
EFF
ELECTRICAL MOTOR
NOMINAL
POWER
SUCTION
DIAM.
DISHCHARGE
DIAM
SUCT TO DISCH
FLANGE TO FLANGE
DISTANCE
SUCT TO DISCH
FLANGE TO FLANGE
DISTANCE
TYPE
SUCTION
DIAM.
DISHCHARGE
DIAM
EXISTING PUMP NEW PUMP
PHASE VOLT
MAX
RPM
SPEED CONTROL
(PROVIDED BY PUMP
MANUFACTURER)
MARK LOCATION
AREA
AND/OR
BLDG
SERVED
SYSTEM AND/OR
SERVICE
NPSH AVAILABLE TEMPERATURE
MIN MAX
GAL °F °F PSIG PSIG PSIG GAL GAL IN IN
10-ET 1 BUILDING 10
CHILLED
WATER
VERTICAL
DIAPHRAGM
30000 40 95 60 PSIG 110 125 370 170 3/4 - BELL & GOSSETT B-1400 OR EQUAL
RELIEF
VALVE
MIN BLADDER
VOLUME
COLD WATER
FILL SIZE BASIS OF DESIGN OR APPROVED
EQUAL
EXPANSION TANK SCHEDULE
MARK LOCATION
SYSTEM
AND/OR
SERVICE
TYPE
APPROX
SYSTEM
VOLUME
SYSTEM
TEMPERATURE
INITIAL
PRESSURE IN
TANK
MAX
OPERATING
PRESSURE
MIN VOLUME
TANK
PIPE SIZE
TO TANK
Central Chiller Plant
Cooling
Distribution
Pump
Thermal
Storage Tank
Pump
Thermal
Storage
Chiller Pump
Thermal
Storage Chiller
Setpoint
Current
Limit
Setpoint
Off-peak
Chiller
Pump
Off-peak
Chiller
Chiller Cooling Only On Off Off Off 100% Off Off
Tank Discharge
Only On On (42°F) Off Off NA Off Off
Simultaneous Chiller
Cooling & Tank
Discharge On On (42°F) On 42°F* 50%* Off Off
Tank Charging Only Off
On (match TS
Chiller Pump) On 22°F 100% Off Off
Simultaneous Chiller
Cooling & Tank
Charging On
On (match TS
Chiller Pump) On 22°F 100% On 42°F
Off Off Off Off Off Off Off Off
Chiller Load
(% Full Load)
Wet Bulb
(°F)
Tower Setpoint
(°F)
Chiller + Tower Power
(kW)
100% 78
75% 74
50% 70
50% 60
25% 66
CHILLER REPLACEMENT
NO. DESCRIPTION DATE
BLDG. 10
B
A
C
D
E
F
1 2 3 4 5 6 87 9
97 8654321
BID DOCUMENTS
FULLY SPRINKLERED
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
Department of Veterans Affairs
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0089
B
A
C
D
E
F
MECHANICAL
CONTROLS
NOTES
M-801
BLDG. 10
B
A
C
D
E
F
1 2 3 4 5 6 87 9
97 8654321
BID DOCUMENTS
FULLY SPRINKLERED
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
Department of Veterans Affairs
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0089
B
A
C
D
E
F
MECHANICAL
CONTROLS
POINTS SUMMARY
M-802
ARFPB
E le c tr ic
P n e u m a ti c
E le c tr ic
P n e u m a ti c
S ta tu s
T e m p e ra tu re
P re s s u re
H u m id it y
F lo w
C u rr e n t
D a ta
E q u ip m e n t S ta tu s
L o w L im it
H ig h L im it
S c h e d u le
S ta rt /S to p
L e a d
/L a g
T e m p e ra tu re
C o n tr o l
E n th a lp y E c o n o m iz e r
P re s s u re /V o lu m e
C o n tr o l
H u m id it y C o n tr o l
H u m id it y R e s e t
V a lu e
S ta tu s
F a u lt
O p p e ra ti n g S p e e d
V
F D
H e rt z
A m p s
A c tu a l a n d
P re c e n t o f F u ll
C a p a c it y A m p s
O p e ra ti n g K
W
S u p p ly T e m p S e tp o in t
S u p p ly T e m p e ra tu re A d ju s t
C h il le d W a te r S u p p ly
T e m p e ra tu re
C h il le d W a te r R e tu rn T e m p e ra tu re
C h il le d W a te r F lo w
S ta tu s
C o n d e n s e r W a te r S u p p ly
T e m p
C o n d e n s e r W a te r R e tu rn T e m p
C o n d e n s e r W a te r F lo w
S ta tu s
E v a p o ra to r R e fr ig e ra n t T e m p
E v a p o ra to r R e fr ig e ra n t P re s s u re
C o n d e n s e r R e fr ig e ra n t T e m p
C o n d e n s e r R e fr ig e ra n t P re s s u re
C a p a c it y L im it A d ju s t
L u b ri c a ti o n O il P re s s u re
PUMP 10-P-1 START/STOP SST-1 ● ● ●
PUMP 10-P-1 SPEED CONTROL SC-1 ● ● ●
PUMP 10-P-1 VFD BACnet COMM COMM ● ● ● ● ● ●
PUMP 10-P-2 START/STOP SST-2 ● ● ●
PUMP 10-P-2 SPEED CONTROL SC-2 ● ● ●
PUMP 10-P-2 VFD BACnet COMM COMM ● ● ● ● ● ●
PUMP 10-P-3 START/STOP SST-3 ● ● ●
PUMP 10-P-3 SPEED CONTROL SC-3 ● ● ●
PUMP 10-P-3 VFD BACnet COMM COMM ● ● ● ● ● ●
PUMP 10-P-4 START/STOP SST-4 ● ● ●
PUMP 10-P-4 SPEED CONTROL SC-4 ● ● ●
PUMP 10-P-4 VFD BACnet COMM COMM ● ● ● ● ● ●
PUMP 10-P-5 START/STOP SST-5 ● ● ●
PUMP 10-P-5 SPEED CONTROL SC-5 ● ● ●
PUMP 10-P-5 VFD BACnet COMM COMM ● ● ● ● ● ●
PUMP 10-P-6 START/STOP SST-6 ● ● ●
PUMP 10-P-6 SPEED CONTROL SC-6 ● ● ●
PUMP 10-P-6 VFD BACnet COMM COMM ● ● ● ● ● ●
Chiller 10-CH-1 Stop/Start SST-7 ● ● ●
Chilled Water Valve Position ZC-1 C ● ●
Chilled Water Valve End Switch ZS-1 ● ● ●
Condenser Water Valve Position ZC-2 C ● ●
Condenser Water Valve End Switch ZS-2 ● ● ●
Chilled Water Supply Temp TT-1 ● 38 48 ●
Chilled Water Return Temp TT-2 ● ●
Chilled Water Diff Pressure DPT-1 ● ● ● Convert Differential Pressure to Flow Through Chiller
10-CH-1 BACnet Comm COMM ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
Chiller 10-CH-2 Stop/Start SST-8 ● ● ●
Chilled Water Valve Position ZC-3 C ● ●
Chilled Water Valve End Switch ZS-3 ● ● ●
Condenser Water Valve Position ZC-4 C ● ●
Condenser Water Valve End Switch ZS-4 ● ● ●
Chilled Water Supply Temp TT-3 ● ●
Chilled Water Return Temp TT-4 ● 38 48 ●
Chilled Water Diff Pressure DPT-2 ● ● ● Convert Differential Pressure to Flow Through Chiller
10-CH-2 Backnet Comm COMM ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●
System Differential Pressure DPT-3 ● ●
System Supply Temperature TT-5 ● ●
System Return Temperature TT-6 ● ●
System Flow FT-1 ● ●
Chiller Bypass Valve ZC-5 C ● ●
Chilled Water bypass Valve End Switch ZS-5 ● ● ● ●
Chilled Water Minimum Flow Bypass Valve ZC-6 C ● ●
Colling Tower 1 Fan Stap/Stop SST-9 A Thru D ● ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project
Colling Tower 1 Fan Speed Control SC-9 A Thru D ● ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project
Cooling Tower 1 VFD Backnet Comm COMM A Thru D ● ● ● ● ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project
Colling Tower 1 Circ Pump Start/stop SST- 10 A Thru D ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project
Cooling Tower 1 Circ Pump Status CT-10 A Thru D ● ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project
Cooling Tower 1 Isolation Valve ZC-7 A Thru D C ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project
Cooling Tower 1 Isolation Valve End Switch ZS-7 A Thru D ● ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project
Colling Tower 2 Fan Stap/Stop SST-11 A Thru D ● ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project
Colling Tower 2 Fan Speed Control SC11 A Thru D ● ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project
Cooling Tower 2 VFD Backnet Comm COMM A Thru D ● ● ● ● ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project
Colling Tower 2 Circ Pump Start/Stop SST-12 A Thru D ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project
Cooling Tower 2 Circ Pump Status CT-12 A Thru D ● ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project
Cooling Tower 2 Isolation Valve ZC-8 A Thru D ● ● Four Points, Installed in Cooling Tower Project, Reprogramed In This Project
Cooling Tower 2 Isolation Valve End Switch ZS-8 A Thru D ● ● ●
Colling Tower 3 Fan Stap/Stop SST-13 A Thru D ● ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project
Colling Tower 3 Fan Speed Control SC-13 A Thru D ● ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project
Cooling Tower 3 VFD Backnet Comm COMM A Thru D ● ● ● ● ● ● Installed in Cooling Tower Project
Colling Tower 3 Circ Pump SST 14 A Thru D ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project
Cooling Tower 3 Circ Pump Status CT-14 A Thru D ● ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project
Cooling Tower 3 Isolation Valve ZC-9 A Thru D ● ● Installed in Cooling Tower Project, Reprogramed In This Project
Cooling Tower 3 Isolation Valve End Switch ZS-9 A Thru D ● ● ●
Cooling Tower Return Water Temp TT-7 ● 50 88 ● Installed in Cooling Tower Project
Outside Air Wet Bulb Temperature WBT-1 ● ●
REMARK
POINTS SUMMARY - CHILLED WATER SYSTEM
SYSTEM COMPONENT P
o in t
ID
D e v ic e F a il P o s it io n
O
O p e n
(C
C lo s e d
System Outputs
Application/Function
G ra p h ic D is p la y
T re n d in g
DIGITAL COMMUNICATIONS
System Inputs System Software/Control
Binary Analog Binary Analog Alarm Processing
BLDG. 10
B
A
C
D
E
F
1 2 3 4 5 6 87 9
97 8654321
BID DOCUMENTS
FULLY SPRINKLERED
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
Department of Veterans Affairs
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0089
B
A
C
D
E
F
ELECTRICAL
ABBREVIATIONS & SYMBOLS
E-001
MJRMJR
L L
BLDG. 10
B
A
C
D
E
F
1 2 3 4 5 6 87 9
97 8654321
BID DOCUMENTS
FULLY SPRINKLERED
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
Department of Veterans Affairs
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0089
B
A
C
D
E
F
ELECTRICAL
NOTES
E-002
ROOM
SHOWER
ROOM
TREATMENT
ROOM
MEZZANINE
OFFICE TOILET
BOILER
ROOM
STORAGE
CHILLER
ROOM
CHILLER REPLACEMENT
NO. DESCRIPTION DATE
BLDG. 10
B
A
C
D
E
F
1 2 3 4 5 6 87 9
97 8654321
BID DOCUMENTS
FULLY SPRINKLERED
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
Department of Veterans Affairs
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0089
B
A
C
D
E
F
ELECTRICAL
POWER PLAN
E-101
ELECTRICAL
SINGLE LINE DIAGRAM
E-601
CHILLER REPLACEMENT
NO. DESCRIPTION DATE
BLDG. 10
B
A
C
D
E
F
1 2 3 4 5 6 87 9
97 8654321
BID DOCUMENTS
FULLY SPRINKLERED
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
Department of Veterans Affairs
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0089
B
A
C
D
E
F
| 00 - General |
| GI001 |
| GI001 |
| 01 - Structural |
| S-101 |
| S-101 |
| 02 - Mechanical |
| M-001 |
| M-001 |
| 03 - Electrical |
| E-001 |
| E-001 |
| E-001 |
| E-002 |
| E-002 |
| E-002 |
| E-101 |
| E-101 |
| E-101 |
| E-601 |
| E-601 |
| E-601 |
File details come from the government source that posted it. Updated .