Full Set - Drawings Chiller.pdf

PDF 10 MB Posted

Attached to
C1NB--Cooling Tower Replacement Project 595-11-135 Federal contract opportunity
Solicitation number
36C24420R0014
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 4

About this file

This document package includes drawings and specifications for a chiller replacement project. The project scope involves removing existing chillers and related equipment and installing new water-cooled centrifugal chillers, pumps, cooling towers, and associated mechanical, electrical and controls systems. Miller-Remick LLC prepared the design documents as a professional engineering firm. The drawings provide demolition, mechanical, electrical and controls plans along with notes, schedules, details and diagrams for the project. Specifications include equipment data and control strategies. The project is for the Department of Veterans Affairs to support facilities in Building 10.

This pre-solicitation notice is for a design-build project to replace cooling towers at the Lebanon Veterans Affairs Medical Center in Lebanon, Pennsylvania. The project scope involves providing design and construction services to renovate the cooling towers under Project No. 595-11-135. The design was previously completed in 2011-2012 but requires updating to meet specifications. The selected contractor will complete any remaining design work and perform construction. The solicitation will be a two-phase best value procurement open only to 100% SDVOSB firms. The anticipated contract value is between $2-5 million. The solicitation and 455-day period of performance are planned to start in February 2020.

View the file

Other files for this federal contract opportunity

Other files attached to C1NB--Cooling Tower Replacement Project 595-11-135, newest first.
File Type Posted
36C24420R0014 A0004_1.docx DOCX document
Qs and As A0004.pdf PDF
EXHIBIT B - Past Performance Relevancy Questionnaire REV.docx DOCX document
36C24420R0014 A0004.pdf PDF
RLS Construction Group LLC.pdf PDF
District Veterans Contracting Inc.pdf PDF
AEONRG LLC.pdf PDF
36C24420R0014 A0003_1.docx DOCX document
SAW Contracting Inc.pdf PDF
36C24420R0014 A0003.pdf PDF
36C24420R0014-A0002000.docx DOCX document
36C24420R0014-A0002001.pdf PDF
36C24420R0014-A0001001.docx DOCX document
36C24420R0014-A0001002.pdf PDF
36C24420R0014-020.docx DOCX document
36C24420R0014-021.docx DOCX document
36C24420R0014-014.pdf PDF
36C24420R0014-013.pdf PDF
36C24420R0014-012.docx DOCX document
36C24420R0014-022.docx DOCX document
36C24420R0014-023.docx DOCX document
36C24420R0014-016.docx DOCX document
36C24420R0014-019.docx DOCX document
36C24420R0014-018.docx DOCX document
36C24420R0014-017.docx DOCX document
36C24420R0014-015.pdf PDF
36C24420R0014-011.docx DOCX document
36C24420R0014-001.docx DOCX document
Show all 28

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CHILLER REPLACEMENT

NO. DESCRIPTION DATE

BLDG. 10

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

BID DOCUMENTS

FULLY SPRINKLERED

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0089

B

A

C

D

E

F

GENERAL

COVER SHEET & DRAWING INDEX

GI001

DRMP

PLAN

NORTH

ACTUAL

NORTH

BLDG. 10

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

BID DOCUMENTS

FULLY SPRINKLERED

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0089

B

A

C

D

E

F

STRUCTURAL

PLAN, NOTES, & DETAILS

S-101

DSER

BLDG. 10

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

BID DOCUMENTS

FULLY SPRINKLERED

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0089

B

A

C

D

E

F

MECHANICAL

ABBREVIATIONS, NOTES,

& SYMBOLS

M-001

ARFPB

GENERATOR

ROOM

SHOWER

BOILER

ROOM

STORAGE

CHILLER

ROOM

CHILLER REPLACEMENT

NO. DESCRIPTION DATE

BLDG. 10

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

BID DOCUMENTS

FULLY SPRINKLERED

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0089

B

A

C

D

E

F

MECHANICAL

DEMOLITION PLAN

MD101

ROOM

SHOWER

BOILER

ROOM

STORAGE

CHILLER

ROOM

CHILLER REPLACEMENT

NO. DESCRIPTION DATE

BLDG. 10

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

BID DOCUMENTS

FULLY SPRINKLERED

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0089

B

A

C

D

E

F

MECHANICAL

FLOOR PLAN

M-101

BLDG. 10

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

BID DOCUMENTS

FULLY SPRINKLERED

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0089

B

A

C

D

E

F

MECHANICAL

DETAILS

M-501

BLDG. 10

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

BID DOCUMENTS

FULLY SPRINKLERED

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0089

B

A

C

D

E

F

MECHANICAL

FLOW/CONTROL DIAGRAM

M-601

BLDG. 10

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

BID DOCUMENTS

FULLY SPRINKLERED

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0089

B

A

C

D

E

F

MECHANICAL

SCHEDULES

M-602

ARFPB

SIZE IN FLOW WPD

IN GPM FT

10-AS 1 BUILDING 10

CHILLED

WATER

FULL FLOW

TANGENTIAL

12 2842 1.4 NO BELL & GOSSET OR EQUAL

BUILT-IN

STRAINER

REQ'D

AIR SEPARATOR SCHEDULE

MARK LOCATION

SYSTEM

AND/OR

SERVICE

TYPE

AIR SEPARATOR

BASIS OF DESIGN OR

APPROVED EQUAL

EWT LWT MAX WPD FLOW EWT LWT

MAX

WPD

TONS °F °F FT GPM °F °F FT

10-WCCH-1 BLDG 10 CAMPUS CENTRIFUGAL 950 0.58 0.355 1421 58 42 10 500 0.00010 3060 85 95 17 0.00025 876 1200 3 480 VFD

SINGLE POINT POWER

CONNECTION

10-WCCH-2 BLDG 10 CAMPUS CENTRIFUGAL 950 0.58 0.355 1421 58 42 10 500 0.00010 3060 85 95 17 0.00025 876 1200 3 480 VFD

SINGLE POINT POWER

CONNECTION

1. SEE SPECIFICATIONS FOR OTHER APPLICABLE ENGINEERING REQUIREMENTS.

2. "MAX kW/TON" AND "MIN COP" SPECIFIED ARE AT DESIGN CONDITION INDICATED.

FOULING

FACTOR

REMARKS

PHASE

TYPE

MAX

kW/TON

MAX IPLV

(kW/TON) FLOW @ FULL

CAPACITY GPM

SPEED

CONTROL

WATER COOLED CHILLER SCHEDULE

CAPACIT

YMARK

MCA VOLTMOCP

3. BOTH THE EVAPORATOR AND CONDENSER SHALL BE DESIGNED FOR VARIABLE FLOW.

EVAPORATOR CONDENSER

FOULING

FACTOR

ELECTRICAL

NOTES

LOCATION

AREA AND/OR

BLDG SERVED

MINIMUM

ALLOWABLE FLOW

GPM

IN IN IN IN IN IN GPM FT FT °F HP

10-P-1

MECHANICAL

ROOM

BUILDING 10 CHILLED WATER 8 6 31 8 6 30

HORZ SPLIT

CASE

WATER 1421 150 30 55 79 100 3 480 1750 VFD

BELL & GOSSETT HSC-S 6X8X17M OR

EQUAL

N+1

10-P-2

MECHANICAL

ROOM

BUILDING 10 CHILLED WATER 8 6 31 8 6 30

HORZ SPLIT

CASE

WATER 1421 150 30 55 79 100 3 480 1750 VFD

BELL & GOSSETT HSC-S 6X8X17M OR

EQUAL

N+1

10-P-3

MECHANICAL

ROOM

BUILDING 10 CHILLED WATER 8 6 31 8 6 30

HORZ SPLIT

CASE

WATER 1421 150 30 55 79 100 3 480 1750 VFD

BELL & GOSSETT HSC-S 6X8X17M OR

EQUAL

N+1

10-P-4

MECHANICAL

ROOM

BUILDING 10 CONDENSER WATER 12 10 36.75 12 10 35

HORZ SPLIT

CASE

WATER 3060 70 30 95 80 75 3 480 1750 VFD

BELL & GOSSETT HSC-S 10x12x12M OR

EQUAL

N+1

10-P-5

MECHANICAL

ROOM

BUILDING 10 CONDENSER WATER 12 10 36.75 12 10 35

HORZ SPLIT

CASE

WATER 3060 70 30 95 80 75 3 480 1750 VFD

BELL & GOSSETT HSC-S 10x12x12M OR

EQUAL

N+1

10-P-6

MECHANICAL

ROOM

BUILDING 10 CONDENSER WATER 12 10 36.75 12 10 35

HORZ SPLIT

CASE

WATER 3060 70 30 95 80 75 3 480 1750 VFD

BELL & GOSSETT HSC-S 10x12x12M OR

EQUAL

N+1

HEAD BASIS OF DESIGN OR

APPROVED EQUAL

REMARKS

PUMP SCHEDULE

CIRCULATING FLUID

FLUID

FLOW

MIN %

EFF

ELECTRICAL MOTOR

NOMINAL

POWER

SUCTION

DIAM.

DISHCHARGE

DIAM

SUCT TO DISCH

FLANGE TO FLANGE

DISTANCE

SUCT TO DISCH

FLANGE TO FLANGE

DISTANCE

TYPE

SUCTION

DIAM.

DISHCHARGE

DIAM

EXISTING PUMP NEW PUMP

PHASE VOLT

MAX

RPM

SPEED CONTROL

(PROVIDED BY PUMP

MANUFACTURER)

MARK LOCATION

AREA

AND/OR

BLDG

SERVED

SYSTEM AND/OR

SERVICE

NPSH AVAILABLE TEMPERATURE

MIN MAX

GAL °F °F PSIG PSIG PSIG GAL GAL IN IN

10-ET 1 BUILDING 10

CHILLED

WATER

VERTICAL

DIAPHRAGM

30000 40 95 60 PSIG 110 125 370 170 3/4 - BELL & GOSSETT B-1400 OR EQUAL

RELIEF

VALVE

MIN BLADDER

VOLUME

COLD WATER

FILL SIZE BASIS OF DESIGN OR APPROVED

EQUAL

EXPANSION TANK SCHEDULE

MARK LOCATION

SYSTEM

AND/OR

SERVICE

TYPE

APPROX

SYSTEM

VOLUME

SYSTEM

TEMPERATURE

INITIAL

PRESSURE IN

TANK

MAX

OPERATING

PRESSURE

MIN VOLUME

TANK

PIPE SIZE

TO TANK

Central Chiller Plant

Cooling

Distribution

Pump

Thermal

Storage Tank

Pump

Thermal

Storage

Chiller Pump

Thermal

Storage Chiller

Setpoint

Current

Limit

Setpoint

Off-peak

Chiller

Pump

Off-peak

Chiller

Chiller Cooling Only On Off Off Off 100% Off Off

Tank Discharge

Only On On (42°F) Off Off NA Off Off

Simultaneous Chiller

Cooling & Tank

Discharge On On (42°F) On 42°F* 50%* Off Off

Tank Charging Only Off

On (match TS

Chiller Pump) On 22°F 100% Off Off

Simultaneous Chiller

Cooling & Tank

Charging On

On (match TS

Chiller Pump) On 22°F 100% On 42°F

Off Off Off Off Off Off Off Off

Chiller Load

(% Full Load)

Wet Bulb

(°F)

Tower Setpoint

(°F)

Chiller + Tower Power

(kW)

100% 78

75% 74

50% 70

50% 60

25% 66

CHILLER REPLACEMENT

NO. DESCRIPTION DATE

BLDG. 10

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

BID DOCUMENTS

FULLY SPRINKLERED

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0089

B

A

C

D

E

F

MECHANICAL

CONTROLS

NOTES

M-801

BLDG. 10

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

BID DOCUMENTS

FULLY SPRINKLERED

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0089

B

A

C

D

E

F

MECHANICAL

CONTROLS

POINTS SUMMARY

M-802

ARFPB

E le c tr ic

P n e u m a ti c

E le c tr ic

P n e u m a ti c

S ta tu s

T e m p e ra tu re

P re s s u re

H u m id it y

F lo w

C u rr e n t

D a ta

E q u ip m e n t S ta tu s

L o w L im it

H ig h L im it

S c h e d u le

S ta rt /S to p

L e a d

/L a g

T e m p e ra tu re

C o n tr o l

E n th a lp y E c o n o m iz e r

P re s s u re /V o lu m e

C o n tr o l

H u m id it y C o n tr o l

H u m id it y R e s e t

V a lu e

S ta tu s

F a u lt

O p p e ra ti n g S p e e d

V

F D

H e rt z

A m p s

A c tu a l a n d

P re c e n t o f F u ll

C a p a c it y A m p s

O p e ra ti n g K

W

S u p p ly T e m p S e tp o in t

S u p p ly T e m p e ra tu re A d ju s t

C h il le d W a te r S u p p ly

T e m p e ra tu re

C h il le d W a te r R e tu rn T e m p e ra tu re

C h il le d W a te r F lo w

S ta tu s

C o n d e n s e r W a te r S u p p ly

T e m p

C o n d e n s e r W a te r R e tu rn T e m p

C o n d e n s e r W a te r F lo w

S ta tu s

E v a p o ra to r R e fr ig e ra n t T e m p

E v a p o ra to r R e fr ig e ra n t P re s s u re

C o n d e n s e r R e fr ig e ra n t T e m p

C o n d e n s e r R e fr ig e ra n t P re s s u re

C a p a c it y L im it A d ju s t

L u b ri c a ti o n O il P re s s u re

PUMP 10-P-1 START/STOP SST-1 ● ● ●

PUMP 10-P-1 SPEED CONTROL SC-1 ● ● ●

PUMP 10-P-1 VFD BACnet COMM COMM ● ● ● ● ● ●

PUMP 10-P-2 START/STOP SST-2 ● ● ●

PUMP 10-P-2 SPEED CONTROL SC-2 ● ● ●

PUMP 10-P-2 VFD BACnet COMM COMM ● ● ● ● ● ●

PUMP 10-P-3 START/STOP SST-3 ● ● ●

PUMP 10-P-3 SPEED CONTROL SC-3 ● ● ●

PUMP 10-P-3 VFD BACnet COMM COMM ● ● ● ● ● ●

PUMP 10-P-4 START/STOP SST-4 ● ● ●

PUMP 10-P-4 SPEED CONTROL SC-4 ● ● ●

PUMP 10-P-4 VFD BACnet COMM COMM ● ● ● ● ● ●

PUMP 10-P-5 START/STOP SST-5 ● ● ●

PUMP 10-P-5 SPEED CONTROL SC-5 ● ● ●

PUMP 10-P-5 VFD BACnet COMM COMM ● ● ● ● ● ●

PUMP 10-P-6 START/STOP SST-6 ● ● ●

PUMP 10-P-6 SPEED CONTROL SC-6 ● ● ●

PUMP 10-P-6 VFD BACnet COMM COMM ● ● ● ● ● ●

Chiller 10-CH-1 Stop/Start SST-7 ● ● ●

Chilled Water Valve Position ZC-1 C ● ●

Chilled Water Valve End Switch ZS-1 ● ● ●

Condenser Water Valve Position ZC-2 C ● ●

Condenser Water Valve End Switch ZS-2 ● ● ●

Chilled Water Supply Temp TT-1 ● 38 48 ●

Chilled Water Return Temp TT-2 ● ●

Chilled Water Diff Pressure DPT-1 ● ● ● Convert Differential Pressure to Flow Through Chiller

10-CH-1 BACnet Comm COMM ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●

Chiller 10-CH-2 Stop/Start SST-8 ● ● ●

Chilled Water Valve Position ZC-3 C ● ●

Chilled Water Valve End Switch ZS-3 ● ● ●

Condenser Water Valve Position ZC-4 C ● ●

Condenser Water Valve End Switch ZS-4 ● ● ●

Chilled Water Supply Temp TT-3 ● ●

Chilled Water Return Temp TT-4 ● 38 48 ●

Chilled Water Diff Pressure DPT-2 ● ● ● Convert Differential Pressure to Flow Through Chiller

10-CH-2 Backnet Comm COMM ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●

System Differential Pressure DPT-3 ● ●

System Supply Temperature TT-5 ● ●

System Return Temperature TT-6 ● ●

System Flow FT-1 ● ●

Chiller Bypass Valve ZC-5 C ● ●

Chilled Water bypass Valve End Switch ZS-5 ● ● ● ●

Chilled Water Minimum Flow Bypass Valve ZC-6 C ● ●

Colling Tower 1 Fan Stap/Stop SST-9 A Thru D ● ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project

Colling Tower 1 Fan Speed Control SC-9 A Thru D ● ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project

Cooling Tower 1 VFD Backnet Comm COMM A Thru D ● ● ● ● ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project

Colling Tower 1 Circ Pump Start/stop SST- 10 A Thru D ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project

Cooling Tower 1 Circ Pump Status CT-10 A Thru D ● ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project

Cooling Tower 1 Isolation Valve ZC-7 A Thru D C ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project

Cooling Tower 1 Isolation Valve End Switch ZS-7 A Thru D ● ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project

Colling Tower 2 Fan Stap/Stop SST-11 A Thru D ● ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project

Colling Tower 2 Fan Speed Control SC11 A Thru D ● ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project

Cooling Tower 2 VFD Backnet Comm COMM A Thru D ● ● ● ● ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project

Colling Tower 2 Circ Pump Start/Stop SST-12 A Thru D ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project

Cooling Tower 2 Circ Pump Status CT-12 A Thru D ● ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project

Cooling Tower 2 Isolation Valve ZC-8 A Thru D ● ● Four Points, Installed in Cooling Tower Project, Reprogramed In This Project

Cooling Tower 2 Isolation Valve End Switch ZS-8 A Thru D ● ● ●

Colling Tower 3 Fan Stap/Stop SST-13 A Thru D ● ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project

Colling Tower 3 Fan Speed Control SC-13 A Thru D ● ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project

Cooling Tower 3 VFD Backnet Comm COMM A Thru D ● ● ● ● ● ● Installed in Cooling Tower Project

Colling Tower 3 Circ Pump SST 14 A Thru D ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project

Cooling Tower 3 Circ Pump Status CT-14 A Thru D ● ● ● 4 Points, Installed in Cooling Tower Project, Reprogramed In This Project

Cooling Tower 3 Isolation Valve ZC-9 A Thru D ● ● Installed in Cooling Tower Project, Reprogramed In This Project

Cooling Tower 3 Isolation Valve End Switch ZS-9 A Thru D ● ● ●

Cooling Tower Return Water Temp TT-7 ● 50 88 ● Installed in Cooling Tower Project

Outside Air Wet Bulb Temperature WBT-1 ● ●

REMARK

POINTS SUMMARY - CHILLED WATER SYSTEM

SYSTEM COMPONENT P

o in t

ID

D e v ic e F a il P o s it io n

O

O p e n

(C

C lo s e d

System Outputs

Application/Function

G ra p h ic D is p la y

T re n d in g

DIGITAL COMMUNICATIONS

System Inputs System Software/Control

Binary Analog Binary Analog Alarm Processing

BLDG. 10

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

BID DOCUMENTS

FULLY SPRINKLERED

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0089

B

A

C

D

E

F

ELECTRICAL

ABBREVIATIONS & SYMBOLS

E-001

MJRMJR

L L

BLDG. 10

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

BID DOCUMENTS

FULLY SPRINKLERED

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0089

B

A

C

D

E

F

ELECTRICAL

NOTES

E-002

ROOM

SHOWER

ROOM

TREATMENT

ROOM

MEZZANINE

OFFICE TOILET

BOILER

ROOM

STORAGE

CHILLER

ROOM

CHILLER REPLACEMENT

NO. DESCRIPTION DATE

BLDG. 10

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

BID DOCUMENTS

FULLY SPRINKLERED

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0089

B

A

C

D

E

F

ELECTRICAL

POWER PLAN

E-101

ELECTRICAL

SINGLE LINE DIAGRAM

E-601

CHILLER REPLACEMENT

NO. DESCRIPTION DATE

BLDG. 10

B

A

C

D

E

F

1 2 3 4 5 6 87 9

97 8654321

BID DOCUMENTS

FULLY SPRINKLERED

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

Department of Veterans Affairs

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Miller-Remick LLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering

A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0089

B

A

C

D

E

F

00 - General
GI001
GI001
01 - Structural
S-101
S-101
02 - Mechanical
M-001
M-001
03 - Electrical
E-001
E-001
E-001
E-002
E-002
E-002
E-101
E-101
E-101
E-601
E-601
E-601