S02 Mech_CD Drawing.pdf
PDF 3 MB Posted
- Solicitation number
- 36C24226R0034
About this file
This is a comprehensive mechanical contract document set for the "Replace Chillers Phase II" project at New York Harbor Healthcare System, located at 423 E 23rd Street, New York, NY. The contract documents include mechanical general information, demolition plans, new work plans, flow diagrams, mechanical details, sections, schedules, and control specifications for a chilled water plant upgrade.
The project involves the demolition of existing centrifugal chillers, pumps, and associated piping, along with installation of four new 1,200-ton variable primary water-cooled centrifugal chillers (CCU1-CCU3 plus existing CCU4) with R-134A refrigerant, four 2,400 GPM chilled water pumps (P-1 through P-4), four 2,880 GPM condenser water pumps (P-5 through P-8), a side-stream sediment separator with 50-micron filters, air separator, pressurized expansion tank (1,980 gallons), and associated control valves and piping systems. All new chillers shall feature variable speed drives with direct digital controls (DDC) integrated via BACnet MS/TP protocol into the existing building management system. The control sequence specifies lead-lag operation with equalized run-time, chiller plant optimization algorithms maintaining 30-80% part-load ratio ranges, and modulating control valves for both chilled and condenser water circuits. Construction work must be performed during the yearly plant shutdown from approximately November 30 through April 15. All equipment must meet UL standards, VA standards, and applicable local, state, and national codes. The schedules detail pump specifications (1,240-2,400 GPM chilled water flow at 42-54°F temperature range; 1,635-3,600 GPM condenser water flow at 85-95°F), chiller efficiency minimums of 0.6 kW/ton full-load capacity with NPLV ratings, and refrigerant monitoring with automatic plant shutdown capabilities upon detection of refrigerant leaks.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A/E ARCHITECT / ENGINEER
AAHX AIR TO AIR HEAT EXCHANGER
AB AIR BLENDER
AAV AUTOMATIC AIR VENT
ACC AIR-COOLED CONDENSER
ACCH AIR-COOLED CHILLER
ACCU AIR-COOLED CONDENSING UNIT
ACU AIR CONDITIONING UNIT
ACD AUTOMATIC CONTROL DAMPER,
MODULATING
ACD-TP AUTOMATIC CONTROL DAMPER,TWO
POSITION
AD ACCESS DOOR
AF AFTER FILTER
AFCV AIR FLOW CONTROL VALVE
AFD AIR FLOW DEVICE
AFF ABOVE FINISHED FLOOR
AFMD AIR FLOW MEASURING DEVICE
AFW AIR FOIL WHEEL (FAN)
AHU AIR-HANDLING UNIT
AMP AMPERGE
AP ACCESS PANEL
APD AIR PRESSURE DROP
ARI AIR CONDITIONING AND REFRIGERATION
INSTITUTE
AS AIR SEPARATOR
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
AW AIR WASHER
AXF AXIAL FLOW
B BOILER
BD BUTTERFLY DAMPER
BDD BACKDRAFT DAMPER
BDR BASE BOARD RADIATOR
BFP BACKFLOW PREVENTER
BFT BOILER PLANT FIRE TUBE
BHP BRAKE HORSEPOWER
BHW HOT WATER HEATING BOILER
BHX BOILER BLOWDOWN HEAT EXCHANGER
BIW BACKWARD INCLINED WHEEL (FAN)
BSC BIOLOGICAL SAFETY CABINETS
BT BUFFER TANK
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C CELCIUS
CC COOLING COIL
CCD COOLING COIL CONDENSATE DRAIN
CD CHILLER DRIVE
CENT CENTRIFICAL
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFT CUBIC FEET
CFP CHEMICAL FEED PUMP
CCU CHILLER
CHW CHILLER WATER
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CWR CONDENSER WATER TO TOWER
CWTT CONDENSER WATER TO TOWER
CWS CONDENSER WATER FROM TOWER
CWFT CONDENSER WATER FROM TOWER
CI CAST IRON
CM CARBON MONOXIDE
CM CUBIC METER
CM/S CUBIC METER PER SECOND
CO CLEAN OUT
CO2 CARBON DIOXODE
COMP COMPRESSOR UNIT
COP COEFFICIENT OF PERFORMANCE
CP CONDENSATE PUMP
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONSTANT VOLUME
CW COLD WATER (POTABLE)
CHWCC CHILLED WATER COOLING COIL
D DAMPER - AUTOMATIC
D-1 OUTDOOR AIR DAMPER
D-2 RETURN AIR DAMPER
D-3 RELIEF AIR DAMPER
D-4 ECONOMIZER OUTDOOR AIR DAMPER
dB DECIBELS Db DRY-BULB TEMPERATURE
DDC DIRECT DIGITAL CONTROLS
DEG DEGREE
DF DIFFUSER
DIA DIAMETER
DIW DEIONIZED WATER
DP DEW POINT TEMPERATURE
DP DIFFUSER PLATE
DPA DIFFERENTIAL PRESSURE ASSEMBLY
DPS DIFFERENTIAL PRESSURE SENSOR
DX DIRECT EXPANSION
DXCC DIRECT EXPANSION COOLING COIL
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
ECC ENGINEERING CONTROL CENTER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EG EXHAUST GRILLE
EGS EMERGENCY GAS SHUTOFF
EH EXHAUST HOOD
EJ EXPANSION JOINT
EMD END OF MAIN DRIP (STEAM)
ENT ENTERING
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
ETR EXISTING TO REMAIN
F FAHRENHEIT
F&T FLOAT AND THERMOSTATIC
F/SDPR COMBINATION FIRE SMOKE DAMPER
FA FREE AREA
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT (4 PIPE)
FCW FORWARD CURVED WHEEL (FAN)
FD FLOOR DRAIN
FD FIRE DAMPER
FF FINAL FILTER
FM FLOW METER
FPM FEET PER MINUTE
FPS FEET PER SECOND
FRP FIBER REINFORCED POLYESTER
FS FLOW SWITCH
FSTAT FREEZESTAT
FT FEET
FT-LB FOOT-POUND
FTR FIN TUBE RADIATION
FV FACE VELOCITY
GA GAUGE
GAL GALLONS
GH GRAVITY HOOD
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GS GALVANIZED STEEL
H HUMIDIFER
H&CW HOT & COLD WATER
HAC HOUSEKEEPING AID CLOSET
HB HOSE BIBB
HC HEATING COIL
HD HEAD
HD HOOD
HHW HEATING HOT WATER
HHWC HEATING HOT WATER COIL
HHWP HEATING HOT WATER PUMP
HHWR HEATING HOT WATER RETURN
HHWS HEATING HOT WATER SUPPLY
HOA HAND/OFF/AUTOMATIC
HP HEAT PUMP
HP HORSEPOWER
HPDT HIGH PRESSURE DRIP TRAP
HPR HIGH PRESSURE RETURN (STEAM
CONDENSATE)
HPS HIGH PRESSURE SUPPLY (STEAM)
HRC HEAT RECOVERY COIL
HRD HEAT RECOVERY DEVICE
HRP HYDRONIC RADIANT (CEILING) PANEL
HRW HEAT RECOVERY WHEEL
HSTAT HUMIDISTAT
HUM HUMIDIFIER UNIT MOUNTED
HVU HEATING AND VENTILATING UNIT
HW HOT WATER
HWC HOT WATER COIL
HWUH HOT WATER UNIT HEATER
HX HEAT EXCHANGER
Hz HERTZ
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
IBT INVERTED BUCKET TRAP
ICF IN-LINE CENTRIFUGAL FAN
ICU INTENSIVE CARE UNIT
ID INSIDE DIAMETER
IFB INTEGRAL FACE AND BYPASS
IN INCHES
IN HG INCHES OF MERCURY
IN WC INCH WATER COLUMN
IN WG INCH WATER GAUGE
IN-LB INCH-POUND
IPLV INTERGRATED PART LOAD VALUE
IRH INTRARED HEATER
IS INSECT SCREEN
IV INLET VANES
kg KILOGRAM kg/HR KILOGRAM PER HOUR kPa KILOPASCAL kW KILOWATT kWh KILOWATT HOUR
L LITER
L/s LITERS PER SECOND
LAT LEAVING AIR TEMPERATURE
LBS/HR POUNDS PER HOUR
LF LINEAR FOOT (FEET)
LH LATENT HEAT
LPC LOW PRESSURE RETURN (STEAM
CONDENSATE)
LPS LOW PRESSURE SUPPLY (STEAM)
LSD LINEAR SLOT DIFFUSER
LTCP LOCAL TEMPERATURE CONTROL
PANEL
LVG LEAVING
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M METER, SI UNIT
M/s METERS PER SECOND (OR
METERS/SECOND)
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAV MANUAL AIR VENT
MAX MAXIMUM
MB MIXING BOX
MBH 1000 BTUH
MCA MINIMUM BRANCH CIRCUIT AMPACITY
MER MECHANICAL EQUIPMENT ROOM
MERV MINIMUM EFFICIENCY REPORTING
VALUE
MHP MOTOR HORSEPOWER
MIN MINIMUM
MM MILLIMETER
MOV MOTOR OPERATED VALVE
MPR MEDIUM PRESSURE RETURN (STEAM
CONDENSATE)
MPS MEDIUM PRESSURE SUPPLY (STEAM)
MTD MEAN TEMPERATURE DIFFERENCE
MVD MANUAL VOLUME DAMPER
NA NOT APPLICABLE
NC NOISE CRITERIA
NC NORMALLY CLOSED
NO NORMALLY OPEN
NOAA NATIONAL OCEANIC & ATMOSPHERIC
ADMINISTRATION
NOM NOMINAL
NPLV NON-STANDARD PART LOAD VALUE
NPSH NET POSITIVE SUCTION HEAD
NTS NOT TO SCALE
OA OUTSIDE AIR
OAI OUTSIDE AIR INTAKE
OD OUTSIDE DIAMETER
OR OPERATING ROOM
OSA OUTSIDE SUPPLY AIR (CONDITIONED)
P PUMP
PC PUMPED CONDENSATE
PCF POUNDS PER CUBIC FOOT (FEET)
PD PRESSURE DROP
PF PRE-FILTER
PG PRESSURE GAGE
PHC PREHEAT COIL
PHCP PREHEAT COIL PUMP
PPM PARTS PER MILLION
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH –
ABSOLUTE
PSIG POUNDS PER SQUARE INCH – GAGE
PSS PRIMARY SECONDARY SYSTEM
PSV PRESSURE SAFETY VALVE
R/E RETURN OR EXHAUST
RA RETURN AIR
RAT RETURN AIR TEMPERATURE
RDS ROOM DATA SHEETS
REA RELIEF AIR
RF RETURN FAN
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RL REFRIGERANT LIQUID LINE
RLA RUN LOAD AMPERE
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION
RTU ROOF TOP UNIT
RV RELIEF VALVE
SA SUPPLY AIR
SAD SOUND ATTENUATING DEVICE
SAT SUPPLY AIR TEMPERATURE
SC SHADING COEFFICIENT
SCFM STANDARD CUBIC FEET PER MINUTE
SCR SILICON CONTROLLED RECTIFIER
SD SMOKE DETECTOR
SD SUPPLY AIR DIFFUSER
SDPR SMOKE DAMPER
SDR SMOKE DAMPER (RETURN)
SDS SMOKE DAMPER (SUPPLY)
SEN SENSIBLE HEAT
SF SUPPLY FAN
SH STEAM HUMIDIFIER
SHC STEAM HEATING COIL
SI SQUARE INCHES
SP STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SPD SUPPLY PROCESS AND DISTRIBUTION
SPRV STEAM PRESSURE REDUCING VALVE
SPS STATIC PRESSURE SENSOR
SQ FT SQUARE FOOT (FEET)
SR SUPPLY AIR REGISTER
SS STAINLESS STEEL
SSR SOLID SEPARATOR
ST STEAM TRAP
SV STEAM SAFETY VALVE
SVS STEAM VENT SILENCER
T & PCV TEMPERATURE AND PRESSURE
CONTROL VALVE
TAB TESTING, ADJUSTING, BALANCE
TD TEMPERATURE DIFFERENCE
TDH TOTAL DYNAMIC HEAD
TDS TOTAL DISSOLVED SOLIDS
TP TRAP
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
UC UNDER CUT
UH UNIT HEATER
UL UNDERWRITERS LABORATORY
V VALVE
VAF VANE-AXIAL FAN
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL OPPOSED
BLADE)
VFD VARIABLE FREQUENCY DRIVE
VHA VETERANS HEALTH ADMINISTRATION
VI VIBRATION ISOLATOR
VP VACUUM PUMP
VPS VARIABLE PRIMARY SYSTEM
VR VACUUM (STEAM CONDENSATE)
RETURN
VSD VARIABLE SPEED DRIVE
VUH VERTICAL UNIT HEATER
W WATTS
Wb WET-BULB (TEMPERATURE)
WFCV WATER FLOW CONTROL VALVE
WFM WATER FLOWMETER
WFMD WATER FLOW MEASURING DEVICE
WG WATER GAGE
WPD WATER SIDE PRESSURE DROP
XT EXPANSION TANK
YR YEAR
MECHANICAL ABBREVIATIONS
1. WORK SHALL CONFORM TO APPLICABLE LOCAL, STATE, AND NATIONAL CODES AND APPLICABLE VA STANDARDS.
2. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S WRITTEN RECOMMENDATIONS.
3. OBTAIN AND PAY FOR PERMITS, FEES, AND INSPECTIONS REQUIRED FOR THIS WORK.
4. PROVIDE NEW MATERIALS, EQUIPMENT AND PRODUCTS INCORPORATED IN THE WORK, OF A SUITABLE GRADE FOR THE PURPOSES INTENDED.
5. WHERE POSSIBLE, PROVIDE STANDARD PRODUCTS OF THE VARIOUS MANUFACTURERS EXCEPT WHERE SPECIAL CONSTRUCTION OR PERFORMANCE FEATURES ARE
REQUIRED.
6. PROVIDE FOR APPROVAL, EQUIPMENT OR MATERIAL DEVIATIONS FROM INDICATED CONTRACT REQUIREMENTS SHALL BE SUBJECT TO THE APPROVAL OF THE COR. SUBMIT PROPOSED EQUIPMENT DEVIATIONS THAT ARE SIMILAR BOTH IN QUALITY AND CAPACITY TO THAT EQUIPMENT SPECIFIED, AS SOLELY DETERMINED BY THE COR.
7. PROVIDE MECHANICAL EQUIPMENT THAT IS LISTED AND LABELED BY UNDERWRITERS LABORATORIES (U.L.).
8. INSTALL EQUIPMENT WITH PROPER CLEARANCES FOR REQUIRED PIPING AND ELECTRICAL SERVICES AND CONNECTIONS. INSTALL EQUIPMENT WITH REQUIRED ACCESS AND CLEARANCES IN ACCORDANCE WITH MANUFACTURER'S WRITTEN RECOMMENDATIONS AND APPLICABLE CODES AND STANDARDS.
9. COORDINATE LOCATION, INSTALLATION, AND ROUTING OF DUCTWORK, PIPING, AND EQUIPMENT WITH WORK OF OTHER TRADES.
10. PROVIDE SUPPORT FOR MECHANICAL EQUIPMENT. COORDINATE SUPPORT LOCATIONS WITH OTHER DISCIPLINES PRIOR TO INSTALLATION.
11. PROVIDE POWER CONNECTIONS TO EQUIPMENT PROVIDED UNDER THIS CONTRACT AS WORK OF DIVISION 26.
12. PROVIDE CONTROL WIRING FOR MECHANICAL EQUIPMENT AS WORK OF DIVISION 23.
13. COORDINATE AND DETERMINE EXACT ROUTING OF DUCTWORK AND PIPING IN THE FIELD. DUCTWORK AND PIPING LAYOUTS AND LOCATIONS ARE SCHEMATIC. DO NOT SCALE
THESE DRAWINGS.
14. FIELD VERIFY DIMENSIONS BY ACTUAL MEASUREMENT AND OBSERVATION BEFORE ORDERING OR FABRICATING DUCTWORK, PIPING OR EQUIPMENT.
15. INSTALL DUCTWORK AND PIPING AS HIGH AS POSSIBLE. PROVIDE OFFSETS, FITTINGS, AND DIMENSIONAL TRANSITIONS NOT SHOWN BUT REQUIRED TO MAINTAIN MINIMUM
CLEAR SPACE TO BUILDING SURFACES AT NO ADDITIONAL COST.
16. PATCH, PAINT AND CLEAN SURFACES SUSTAINING DAMAGE ASSOCIATED WITH MECHANICAL WORK OF THIS CONTRACT, UNLESS NOTED OTHERWISE.
17. SUBMIT BOUND SET OF OPERATING AND MAINTENANCE INSTRUCTIONS FOR EQUIPMENT AT COMPLETION OF PROJECT.
18. INSTALL ESCUTCHEONS IN ALL PLACES WHERE PIPING PENETRATES A WALL IN AN EXPOSED LOCATION.
19. CONDUCT A COMPLETE REVIEW OF DRAWINGS, INCLUDING SCHEDULES AND DETAILS, PRIOR TO BEGINNING MECHANICAL SYSTEM INSTALLATION. RESOLVE CONFLICTS WITH
COR.
20. INSTALL PIPING INDICATED TO BE EXPOSED AND PIPING IN EQUIPMENT ROOMS AND SERVICE AREAS AT RIGHT ANGLES OR PARALLEL TO BUILDING WALLS. DIAGONAL RUNS
ARE NOT ACCEPTABLE UNLESS SPECIFICALLY INDICATED OTHERWISE.
21. INSTALL PIPING FREE OF SAGS AND BENDS.
22. INSTALL PIPING TO ALLOW APPLICATION OF INSULATION.
23. PIPING SHALL NOT BE ROUTED OVER TELECOM OR ELECTRICAL EQUIPMENT.
24. PREPARE CONTRACTOR COORDINATION DRAWINGS SHOWING MECHANICAL SYSTEMS AND EQUIPMENT FOR COORDINATION WITH WORK OF OTHER DIVISIONS AND WORK BY
THE GOVERNMENT.
A. INCLUDE PLAN VIEWS, SECTIONS, AND ELEVATIONS, AS REQUIRED, TO FULLY COORDINATE ALL NEW WORK WITH ITSELF AND EXISTING CONDITIONS.
B. DRAWINGS SHALL SHOW, BUT NOT BE LIMITED TO, DUCTWORK, AIR DISTRIBUTION, MECHANICAL EQUIPMENT, MECHANICAL PIPING, FIRE PROTECTION PIPING, PLUMBING PIPING, CABLE TRAYS, LIGHTING FIXTURES, BEAMS AND JOISTS (WITH ELEVATIONS MARKED), ELECTRICAL CONDUIT LARGER THAN 2 INCHES IN DIAMETER.
C. DO NOT BEGIN FABRICATION OR PLACE EQUIPMENT ORDERS UNTIL COORDINATION DRAWINGS HAVE BEEN APPROVED.
D. INSTALLATION COMMENCED PRIOR TO COORDINATION DRAWING APPROVAL IS TAKEN AT THE CONTRACTORS OWN RISK. MODIFY, MOVE OR RECONFIGURE WORK
LACKING COORDINATION AT NO ADDITIONAL COST.
25. KEEP THE CHILLER PLANT CLEAN AND FREE OF DEBRIS DURING CONSTRUCTION. REMOVE CONSTRUCTION DEBRIS DAILY.
MECHANICAL GENERAL NOTES
T
CO2 CARBON DIOXIDE
THERMOSTAT
SUPPLY DIFFUSER
RETURN DIFFUSER/GRILLE
EXHAUST GRILLE
ROUND FLEX DUCT
EG-88 2000 DIFFUSER TAG | DIFFUSER CFM
LINEAR SLOT DIFFUSER
BALANCING DAMPER
(RECTANGULAR)
BALANCING DAMPER
(ROUND)
FIRE DAMPER
SMOKE DAMPER
D
R INCLINED RISE, IN
DIRECTION OF AIRFLOW
INCLINED DROP, IN DIRECTION
OF AIRFLOW
CONNECT NEW DUCT
TO EXISTING
LIMIT OF DEMOLITION
VANED ELBOW (PROVIDE ALL
SQUARE OR RECTANGULAR
ELBOWS WITH VANES EVEN IF
SYMBOL IS MISSING)
STANDARD RADIUS ELBOW
(LONG RADIUS)
10x8 NEW DUCT (INSIDE
DIMENSIONS: WIDTH X DEPTH)
EXISTING DUCT TO REMAIN
EXISTING DUCT TO BE
DEMOLISHED
DUCT TRANSITION
SIDE MOUNTED GRILLE
SUPPLY
RETURN45°
45°
DN
DN
UP
UP
DNUP
STANDARD BRANCH SUPPLY OR
RETURN, NO SPLITTER (45° TAP)
SUPPLY DUCT (UP & DOWN)
EXHAUST DUCT (UP & DOWN)
RETURN DUCT (UP & DOWN)
MECHANICAL LEGEND
HPS
LPS
LPC
CHS
CHR
HIGH PRESSURE STEAM
PIPING (60 PSI)
LOW PRESSURE STEAM PIPING
(15 PSI AND BELOW)
LOW PRESSURE STEAM
CONDENSATE RETURN
CHILLED WATER SUPPLY PIPING
CHILLED WATER RETURN PIPING
PIPE UP
PIPE DOWN
BOTTOM CONNECTION
TOP CONNECTION
CAPPED OUTLET
GLOBE VALVE
GATE VALVE
BALL VALVE
STEAM SAFETY VALVE
PRESSURE REGULATING VALVE
WYE STRAINER VALVE
BALANCING VALVE
MOTORIZED CONTROL VALVE
STEAM TRAPCOND CONDENSATE DRAIN LINE
HPR HIGH PRESSURE STEAM
CONDENSATE RETURN
CWS
CWR
CONDENSER WATER SUPPLY PIPING
CONDENSER WATER RETURN PIPING
RLS REFRIGERANT LINE SET (LIQUID
AND SUCTION)
CONNECT TO EXISTING PIPE
LIMITS OF DEMOLITION
INLINE CENTRIFUGAL PUMP
TANGENTIAL AIR SEPARATOR
EXPANSION TANK
WALL-MOUNTED INDOOR
SPLIT-SYSTEM
SPLIT-SYSTEM CONDENSING UNIT
UTILITY SET EXHAUST FAN
STEAM PRESSURE
REDUCING STATION
DRAIN VALVE
TEST PLUG
SUPPLY
TERMINAL UNIT SUPPLY
DUCT BRANCH (CONICAL
TAP)
TERMINAL UNIT
CHECK VALVE
MOTORIZED CONTROL VALVEM
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
/1 /2
:4
:2
P M
M-001
MECHANICAL GENERAL INFORMATION
1 12DJR DJR/PLH
REPLACE CHILLERS PH. II
NEW YORK HARBOR HEALTHCARE
SYSTEM
423 E 23RD STREET, NEW YORK, NY 12/20/2019
CONTRACT DOCUMENTS
630-16-10117-054
DocuSign Envelope ID: F59BCCEA-213D-434D-883A-29537521E0FC
12/19/2019
A
18 19 21 22.5
FF
HH
JJ
LL
EE
ETR-CCU4
(1200 TONS)
P-14 2000
GPM
P-13 3000
GPM
STANDBY
P-12 3000
GPM
P-11 3000
GPM
CCU1,
1000 TONS
CCU2,
1000 TONS
CCU3,
1000 TONS
P1, 2000 GPM2
P2, 2000 GPM2
P3, 2000 GPM2
P4, 4200 GPM2P5, 2000 GPM2
P6, 3000 GPM2
P7, 3000 GPM2P8, 3000 GPM
STANDBY
P9, 3000 GPM2
P10, 3000 GPM2
20" CWTT UP AT
TOP OF ELBOW
18" CWS UP
20" CWR UP AT
TOP OF ELBOW
20" CWFT UP AT
TOP OF ELBOW
EXISTING
12" CAP
3 (TYP.)
3 (TYP.)
ETR- MAIN
PUMP PAD
CONCRETE
INTERIA PAD (TYP.)
3/4" LPC5
DOWNSTREAM
OF VALVING
ETR- STEAM
UNIT HEATER
ETR- STEAM
UNIT HEATER
12" CHR
C H
S
C H
S
16" 12"
12"
12" 1
12"
18"
18"
12"
12"
18"
12"
18"24" CHS
24" CHS
16" CHS
24" CHR
18" Ø CHR
12" CWR
12" Ø CHR
ETR VFD
VFD P-5 - P-14
ETR REFRIGERANT
SENSORS
ETR REFRIGERANT
MONITORING PANEL
ETR SPRINKLER
BFP
CT-1 MOTOR CONTROL
CENTER
CT-5/CHWP/TWP MOTOR
CONTROL CENTER
CHEMICAL
TREATMENT
MCCCONTROL PANEL
20" CHS
7 7
ETR CONCRETE PAD
10x20
10x20
10x20
(TYP.)
ETR, 5-EF-6
32x24 26x24 26x20 18x20
20x10
20x10
20x10 20x10
20x10
MCC
MCC
B R
ID
G
E
CHILLER NOT
IN CONTRACT
CH-4 VFD, ETR
CONTROL
ROOM
ETR CHW POT FEEDER AND
FILTER
# KEY NOTES:
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
SHEET NOTES:
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
/1 /2
:4
:5
P M
MD101
CHILLED WATER PLANT - DEMOLITION
PLAN
2 12DJR DJR/PLH
REPLACE CHILLERS PH. II
NEW YORK HARBOR HEALTHCARE
SYSTEM
423 E 23RD STREET, NEW YORK, NY 12/20/2019
CONTRACT DOCUMENTS
630-16-10117-054
Scale: 1/4" = 1'-0"
FIRST FLOOR MECHANICAL DEMOLITION PLAN 0 4 8 16
NORTH
PLAN
1 DEMOLISH CENTRIFUGAL CHILLER AND
SUPPORTS.
2 DEMOLISH PUMP AND CONCRETE INTERTIA BASE.
MAIN CONCRETE EQUIPMENT PAD IS EXISTING TO
REMAIN.
3 DEMOLISH CHILLED WATER PIPING, INSULATION,
HANGERS, AND SUPPORTS.
4 DEMOLISH CONDENSER WATER PIPING, HANGERS,
AND SUPPORTS.
5 DEMOLISH LOW PRESSURE STEAM CONDENSATE
PIPING. INSULATION, HANGERS, AND SUPPORTS.
6 REMOVE WINDOW TO ALLOW PATH OF
EQUIPMENT REMOVAL, REFER TO
ARCHITECTURAL DRAWINGS FOR FURTHER
INFORMATION.
7 REMOVE R-13 REFRIGERANT MONITORING
SENSOR AND SUPPORTS. APPROXIMATELY 12'
A.F.F. RETAIN TUBING.
8 REMOVE AND STORE REFRIGERANT EVACUATION
EXHAUST DUCTS AND SUPPORTS, FROM 9" A.F.F.
TO 12' A.F.F. TO FACILITATE CHILLER
REPLACEMENT.
9 EXISTING 8" RIGGING I-BEAM, 12'-1" A.F.F.
10 REMOVE PIPE OFFSET AND 12" STUB ON EACH
SIDE OF OFFSET WITHOUT DISTURBING OFFSET
FITTINGS. PERFORM WORK USING GLOVEBAG
REMOVAL METHOD FOR ASBESTOS CONTAINING
MATERIAL.
1. PERFORM CONSTRUCTION WORK DURING YEARLY
PLANT SHUTDOWN FROM APPROXIMATELY NOVEMBER
30 THROUGH APPROXIMATELY APRIL 15. COORDINATE
EXACT DATES WITH THE COR.
2. KEEP EQUIPMENT PROVIDED FOR THIS WORK IN LOCAL,
OFF SITE STORAGE UNTIL THE EQUIPMENT IS READY TO
BE INSTALLED.
3. DO NOT BEGIN DEMOLITION UNTIL REPLACEMENT
CHILLERS AND PUMP SETS ARE IN CONTRACTOR'S OFF
SITE STORAGE FACILITY.
4. PRIOR TO PLANT SHUTDOWN, ERECT SCAFFOLDING
THROUGHOUT THE PLANT TO PROVIDE ACCESS TO
PIPING THAT WILL BE DEMOLISHED, AS WELL AS TO
ALLOW FOR INSTALLATION OF NEW PIPING. CONSTRUCT
SCAFFOLDING SO AS TO PROTECT PLANT OCCUPANTS
FROM FALLING ITEMS OR DEBRIS.
5 DURING DEMOLITION WORK AND NEW WORK, COVER
EXISTING ELECTRICAL PANELS, DRY-TYPE SPRINKLER
VALVES, VARIABLE FREQUENCY DRIVES, CONTROLLERS,
AND ALL OTHER EXISTING ITEMS THAT COULD BE
DAMAGED BY DUST OR WATER WITH PLASTIC SHEETING.
CONFIRM LOCATION AND QUANTITY OF ALL SUCH
EQUIPMENT. PERFORM WET MOPPING DAILY TO
PREVENT DAMAGE TO EXISTING EQUIPMENT.
6 PAINT ALL NEW CONCRETE PADS, EXISTING TO REMAIN
CONCRETE PADS, AND NEW EXTENSIONS ON EXISTING
CONCRETE PADS SAFETY YELLOW. FIELD VERIFY
LOCATION AND SIZE OF PADS.
7 REFER TO G-SERIES SHEETS FOR ICRA BARRIERS.
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
18 19 21 22.5
FF
HH
JJ
LL
EE
CD-1B CD-2B CD-3B
CCU1
(TYP.)
(TYP.)
ETR-CCU4
1200 TONS
CCU2 CCU3
6 6 6
ETR-STEAM
UNIT HEATER
ETR-STEAM
UNIT HEATER
1 1
3 3 3
18" CHR
C H
S
C H
S
24" CHR 24" CHR
C H
S
20" CHS 12" CHS
C W
S
20" CWS
14" CWS
12" CHS12" CHS
(TYP.)
4 (TYP.)
(TYP.)
5 (TYP.)
24" CHR
10 3/4" LPC
20" CWS
12" CHR
24" CWR
ETR REFRIGERANT
SENSORS
ETR REFRIGERANT
MONITORING PANEL
ETR CHEMICAL TREATMENT AREA
CONTROL PANEL
M-504
M-504
M-504
M-505
M-505
M-504
M-504
12" CHS
ETR CONCRETE PAD
32x24 26x24 26x20 18x20
20x10
ETR, 5-EF-6, BALANCE TO 8000
CFM
20x10 20x10
20x10
C W
S
C W
S
MCC
MCC (ON
FLOOR)
12" CHR
C W
R
14" CWR
C W
R
24" CWR
C W
R
C W
R
C W
R
14" CWS
C H
S
C H
R
C H
R
20" CHR18" CHR12" CHR
C W
S
14" CWS
C W
R
CHILLER NOT
IN CONTRACT
P-1 P-2 P-3 P-4P-5 P-6 P-7 P-8
43'-6"
CCU4 VFD, ETR
CONTROL
ROOM
SSF-1
ETR CHW POT FEEDER AND
FILTER
C H
R
AS-1
12" C H R
24" CHR
C H
R
ET-1
NEW 4" CONCRETE PAD,
EXTENSION OF EXISTING PAD,
PAINT SAFETY YELLOW
8" CWS
8" CWS
C W
S 8
C W
S
3"
C H
R
CONNECT TO EXISTING
CONDENSER WATER RETURN
TO COOLING TOWERS
CONNECT TO EXISTING
CONDENSER WATER SUPPLY
FROM COOLING TOWERS
12" CHR
24" CHS
C H
S
C H
S
C H
S
EXIST. CHR FROM BUILDING 1 EXIST. CHS TO BUILDING 1
EXIST. CHR
FROM
BUILDING 6
EXIST. CHS TO
BUILDING 6
24" CHS
CHILLED WATER PUMP SKID
CONDENSER WATER PUMP SKID
8"
8"
14" VALVED AND CAPPED FOR
CONNECTION TO FUTURE
TEMP. COOLING TOWER
12" VALVED AND CAPPED
FOR CONNECTION TO
FUTURE TEMP. CHILLER
20" CHR
STRAINER
NOTE: ALL NEW CHILLED WATER, CONDENSER WATER,
DOMESTIC COLD/HOT/HOT RETURN PIPING, DOMESTIC
TEMPERED WATER PIPING, EMERGENCY SHOWER
PIPING, AND STEAM/STEAM CONDENSATE SHALL BE
PAINTED AND LABELED IN ACCORDANCE WITH
SPECIFICATION SECTION 09 91 00, 3.10. COLOR OF
PAINT SHALL BE THE COLOR LISTED IN THE "COLOR OF
BACKGROUND" COLUMN IN THE TABLE CONTAINED IN
THE SPECIFICATION SECTION LISTED ABOVE. FOR
INSULATED PIPES, THE PAINT SHALL BE APPLIED TO
THE INSULATION AFTER THE INSULATION IS INSTALLED.
EXIST. LOCKER ROOM
EXIST. TOILET AND
SHOWER ROOM
P-707
NEW EMERGENCY SHOWER, EYE AND
FACE WASH, CONFIRM LOCATION WITH
COR. EXTEND 1-1/4" DCW AND 1-1/4" DHW
FROM NEAREST DCW AND DHW LINES TO
TEMPERING VALVE, AND EXTEND 1/2"
TEMPERED WATER LINE TO SHOWER/EYE
WASH. PROVIDE 1/2" HOT WATER
RECIRCULATION LINE AND CONNECT TO
NEAREST RECIRCULATION LINE. FIELD
CONFIRM SIZE AND LOCATION OF
EXISTING PIPING.
14" CWS
BUTTERFLY
VALVE (TYP.)
# KEY NOTES:
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
SHEET NOTES:
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
/1 /2
:5
:0
P M
MP101
CHILLED WATER PLANT - NEW WORK
PLAN
3 12DJR DJR/PLH
REPLACE CHILLERS PH. II
NEW YORK HARBOR HEALTHCARE
SYSTEM
423 E 23RD STREET, NEW YORK, NY 12/20/2019
CONTRACT DOCUMENTS
630-16-10117-054
Scale: 1/4" = 1'-0"
CHILLED WATER PLANT NEW WORK PLAN 0 4 8 16
NORTH
PLAN
1 PROVIDE CENTRIFUGAL CHILLER, MOUNT ON
EXISTING TO REMAIN CONCRETE EQUIPMENT PAD.
PROVIDE AND MOUNT ON VIBRATION ISOLATORS.
PAINT PAD SAFETY YELLOW.
2 PROVIDE SKID MOUNTED PUMP PACKAGE. MOUNT
ON EXISTING CONCRETE PAD, AND EXTEND PAD AS
REQUIRED. PROVIDE AND MOUNT ON VIBRATION
ISOLATORS, PROVIDE WITH ALL VALVE WORK AND
24" PIPE HEADERS.
3 PROVIDE CHILLER VARIABLE SPEED DRIVE. REFER
TO ELECTRICAL FOR FURTHER INFORMATION.
4 PROVIDE CHILLED WATER PIPING, INSULATION,
HANGERS, AND SUPPORTS COMPLETE WTH
SEISMIC BRACING.
5 PROVIDE CONDENSER WATER PIPING, HANGERS,
AND SUPPORTS COMPLETE WTH SEISMIC BRACING.
6 HOIST NEW EQUIPMENT THROUGH WINDOW
OPENING, REFER TO ARCHITECTURAL DRAWINGS
FOR FURTHER INFORMATION.
7 PROVIDE R-134A REFRIGERANT MONITORING
SENSOR AND SUPPORTS. CALIBRATE THE EXISTING
REFRIGERANT MONITORING PANEL TO R-134A
REFRIGERANT PER MANUFACTURER'S
RECOMMENDATIONS. INTERLOCK PANEL OUTPUTS
TO THE NEW CHILLER PLANT CONTROL PANEL.
TEST AND COMMISSION SYSTEM TO ENSURE THAT
THE SYSTEM DETECTS REFRIGERANT,
DE-ENERGIZES THE EXISTING EXHAUST FAN,
OPENS AND CLOSES ASSOCIATED DAMPERS, AND
PERFORMS OTHER REQUIRED FUNCTIONS.
8 EXTEND EXISTING CONCRETE PAD TO SUIT NEW
CHILLER. PAINT ENTIRE PAD SAFETY YELLOW.
9 REINSTALL REFRIGERANT EVACUATION EXHAUST
DUCT AND SUPPORTS.
10 SIDE-STREAM SEDIMENT FILTER. SEE 5/M-503.
11 2" COLD WATER MAKEUP, EXTEND AND CONNECT
TO NEAREST DOMESTIC COLD WATER LINE
(MINIMUM 2" SIZE).
12 GLOBE VALVE IN 2" BYPASS LINE.
13 2" BALL VALVE.
14 2" PRESSURE REDUCING VALVE.
15 CONTROL CABINET ENCLOSURE WITH DDC
EQUIPMENT CONTROLLERS FOR CCU-1, CCU-2 AND
CCU-3; DDC CHILLED WATER PLANT CONTROLLER;
AND DDC CHILLED WATER SYSTEM OPTIMIZER.
INCORPORATE EXISTING DDC CONTROLS FOR
CCU-4. UPDATE GRAPHICS ON THE DDC
WORKSTATION.
16 CONTROL CABINET ENCLOSURE WITH DDC
EQUIPMENT CONTROLLERS FOR CHILLED WATER
AND CONDENSER WATER PUMP SKIDS
17 2-WAY MODULATING CHILLED WATER BYPASS
VALVE IN 8" BYPASS LINE.
18 REMOVE CAP ON EXISTING 12" PIPE AND INSTALL
NEW ISOLATION VALVE AND CAP FOR CONNECTION
TO FUTURE TEMPORARY CHILLER.
19 12" RUNOUT VALVED AND CAPPED FOR
CONNECTION TO FUTURE TEMPORARY COOLING
TOWER.
N
AREA OF WORK
KEY PLAN
SCALE: NO SCALE
1. PERFORM CONSTRUCTION WORK DURING YEARLY
PLANT SHUTDOWN FROM APPROXIMATELY NOVEMBER
30 THROUGH APPROXIMATELY APRIL 15. COORDINATE
EXACT DATES WITH THE COR.
2. KEEP EQUIPMENT PROVIDED FOR THIS WORK IN LOCAL,
OFF SITE STORAGE UNTIL THE EQUIPMENT IS READY TO
BE INSTALLED.
3. DO NOT BEGIN DEMOLITION UNTIL REPLACEMENT
CHILLERS AND PUMP SETS ARE IN CONTRACTOR'S OFF
SITE STORAGE FACILITY.
4. PRIOR TO PLANT SHUTDOWN, ERECT SCAFFOLDING
THROUGHOUT THE PLANT TO PROVIDE ACCESS TO
PIPING THAT WILL BE DEMOLISHED, AS WELL AS TO
ALLOW FOR INSTALLATION OF NEW PIPING. CONSTRUCT
SCAFFOLDING SO AS TO PROTECT PLANT OCCUPANTS
FROM FALLING ITEMS OR DEBRIS.
5 DURING DEMOLITION WORK AND NEW WORK, COVER
EXISTING ELECTRICAL PANELS, DRY-TYPE SPRINKLER
VALVES, VARIABLE FREQUENCY DRIVES, CONTROLLERS,
AND ALL OTHER EXISTING ITEMS THAT COULD BE
DAMAGED BY DUST OR WATER WITH PLASTIC SHEETING.
CONFIRM LOCATION AND QUANTITY OF ALL SUCH
EQUIPMENT. PERFORM WET MOPPING DAILY TO
PREVENT DAMAGE TO EXISTING EQUIPMENT.
6 PAINT ALL NEW CONCRETE PADS, EXISTING TO REMAIN
CONCRETE PADS, AND NEW EXTENSIONS ON EXISTING
CONCRETE PADS SAFETY YELLOW. FIELD VERIFY
LOCATION AND SIZE OF PADS.
7 REFER TO G-SERIES SHEETS FOR ICRA BARRIERS.
Progress Issuance 4 Date 4
CCU-4
CCU-1
CCU-2
CCU-3
12" CWR
FROM BLDG. 6
18" CWR
FROM BLDG. 1
P-5
P-4
P-3
P-2
P-1
P-11
P-12
P-14
P-13
P-10
P-9
P-8
P-7
P-6
CT-1 CT-2
CT-3 CT-4
12"
24"
24"
20"
16"
12"
12"
12"
12"
12"
12"
12"
12"
12" 12"
12"
12"
12"
12" 12" 12"
18" 18"
18"
18"
12"
12"
12"
12"
12"
12"
12"
12"
12"
12"
12"
12"
12"
12" CAPPED
12"
24"
16"
24"
20"12"
12"
12"
24"
24"
24" BRIDGE
18"
18"
18"
18"
12"
12"
16"
18"
STANDBY
20"
STANDBY
24"
12"
20"
20"
18"
18"
CT-A CT-B
CT-C CT-D
CHILLER 4 NOT
IN CONTRACT
SEPARATE CONTRACT
THROUGH ROOF UP
TO COOLING TOWERS
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
/1 /2
:4
:2
P M
M-501
CHILLED AND CONDENSER WATER
DEMOLITION FLOW DIAGRAM
4 12DJR DJR/PLH
REPLACE CHILLERS PH. II
NEW YORK HARBOR HEALTHCARE
SYSTEM
423 E 23RD STREET, NEW YORK, NY 12/20/2019
CONTRACT DOCUMENTS
630-16-10117-054
Scale: N.T.S
CHILLED AND CONDENSER WATER FLOW DIAGRAM - DEMOLITION
CT-1 CT-2
CT-3 CT-4
CT-A CT-B
CT-C CT-D
CCU1 CCU2 CCU3 ETR CCU4
18" CHR FROM
BLDG. 1
12" CHR FROM
BLDG. 6
12" CHS TO
BLDG. 6
18" CHS TO
BLDG. 1
CWR CWR CWR
C H
R
C H
S
CHS CHSCHS
CHILLED WATER PUMPS
P-1
P-2
P-3
P-4
CONDENSER WATER PUMPS
P-5
P-6
P-7
P-8
18", ETR
18", ETR
24", ETR
24" ETR
12", ETR
12" CHS 12" CHS 12" CHS 12" CHS, ETR
24"
CHR CHR CHR
24"
20" CHR
12" CHR
12" CHR, ETR
18" CHR12" CHR 12" CHR
12" CHR
CWS
24" CWS
18" CWS
18" CWS
14" CWS
14" CWS
CWS
14" CWS14" CWS
14" CWS
14" CWR
14" CWR
14" CWR 14" CWR
24"
CONNECT BELOW ROOF
TO 24" CWS PROVIDED AS
WORK OF SEPARATE
CONTRACT
COOLING TOWERS AND WORK
ABOVE ROOF NIC
ROOF LINE
24" CWR24" CWR
C W
S
CHS
C W
R
CWR
24"
12" CHS16" CWS
20" CHS
20" CHS
24" CWS
24" CWR
CWR
GENERAL NOTES:
1. CWS: CONDENSING WATER FROM COOLING
TOWERS TO CHILLERS.
2. CWR: CONDENSING WATER FROM CHILLERS TO
COOLING TOWERS.
12", ETR
12", ETR
CWS CWS CWS
CHS CHS
CWS
CWS
CWS
CWS
CHILLED WATER
PUMP SKID
CONDENSER WATER
PUMP SKID
M M M
M M M
TO SIDE-STREAM
SEPARATOR, SEE
5/M-503
12"
STRAINER (TYP.)
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
/1 /2
:4
:2
P M
M-502
CHILLED AND CONDENSER WATER
NEW WORK FLOW DIAGRAM
5 12DJR DJR/PLH
REPLACE CHILLERS PH. II
NEW YORK HARBOR HEALTHCARE
SYSTEM
423 E 23RD STREET, NEW YORK, NY 12/20/2019
CONTRACT DOCUMENTS
630-16-10117-054
Scale: N.T.S
CHILLED AND CONDENSER WATER FLOW DIAGRAM - NEW WORK
Progress Issuance 4 Date 4
NOM. SIZE (IN.)
PIPE (FT.)
TUBING (FT.)
5 FT
THRU 3/4
1 1 1/4
1 1/2
HANGER ROD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR
LOW TEMPERATURE
PIPE)
PROVIDE HIGH
COMPRESSIVE
STRENGHT
INSULATION (9 PSF
MIN. DENSITY) UNDER
INSULATION SHIELD
INSULATION SHIELD AT
HANGER
WELD
SADDLE
ADJUSTABLE CLEVIS HANGER TYPE 1 - SEE
SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER TYPE 43 - SEE
SPECIFICATIONS
1/2" DIA. HANGER RODS WITH 36"
MAX. SPACING ON EACH CHANNEL
BAND
1-5/8" 12 GAUGE CHANNEL
OR 2" x 2" x 1/4" ANGLE
NOTES:
SEE SPECIFICATIONS FOR
DETAILED HANGER
REQUIREMENTS. SIDE VIEW TRAPEZE HANGER
FOR UP TO 1000 LB. UNIFORM
LOAD
1" MAX.
PROVIDE INSULATION SHIELD &
INSERT FOR ALL PIPING (8" MIN.)
2 2 1/2 3 4 5 6 8 10 12
11 12 14 16 17 19 22 23
9 10 12 13 14 16 - -
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE
MAXIMUM PIPE/TUBING SUPPORT SPACING
EXISTING BEAM
EXISTING CONCRETE PAD
NEW CONCRETE PAD
#4 x30" AT 12" O.C.
DOWELL INTO EXISTING
CONCRETE PAD
THERMOMETER (TYP)
MARINE WATER
BOX TYP.
EVAP
COND
EVAP
COND
VIBRATION
ISOLATION
AS
SPECIFIED
EXIST. CONCRETE
PAD
PRESSURE RELIEF
DEVICE
CONDENSER END EVAPORATOR END
FLOOR DRAINFLOOR DRAIN
WATER FLOW
MEASURING
DEVICE
BUTTERFLY
CONTROL VALVE
TYP.
TO
COOLING
TOWER
PIPE HANGERS
TYP.
FROM COOLING
TOWER
VENT PIPE
CWR
CWS
CHS
CHR
NOTE:
1. DRAIN ALL LOW POINTS OF SYSTEMS TO
NEAREST FLOOR DRAIN.
2. COLLECT VENT PIPES FROM ALL REFRIGERANT
PRESSURE RELIEF DEVICES AND EXTEND TO
EXTERIOR OF BUILDING IN ACCORDANCE WITH
ASHRAE STANDARD 15. HEADER SIZE TO EQUAL
OR EXCEED TOTAL AREA OF DEVICES
CONNECTED TO THE HEADER. AFTER
COMBINING THE VENTS FROM ALL CHILLERS,
CONNECT TO EXISTING VENT PENETRATING
PLAN SOUTH WALL BETWEEN CCU1 AND CCU2.
3. PROVIDE MODULATING BUTTERFLY VALVES ON
BOTH CHWR & CWR. VALVES CONTROLLED BY
ECC.
4. PROVIDE A FLOW METER AT THE INLET TO THE
CONDENSER AND EVAPORATOR AT EACH
CHILLER. METERS SHALL BE ULTRASONIC
CLAMP-ON STYLE, BADGER METER MODEL TFX
ULTRA (OR EQUAL). METERS SHALL BE
PROVIDED WITH AN RS485 AND SHALL BE
CONNECTED TO THE ECC VIA BACnet MS/TP
PROTOCOL.
MASTER CONTROL PANEL
VFD (1 PER PUMP)
DISCHARGE HEADER
SUCTION HEADER
BASE-MOUNTED
END SUCTION
PUMP (TYP.)
1/4" DIAMOND PLATE DECKING
BUTTERFLY
ISOLATION
VALVE (TYP.)
ADJUSTABLE HEIGHT HEADER SUPPORTS
CHECK VALVE (1 PER PUMP)
H.S.S. FRAME
INERTIA BASE
NOTES:
1. PROVIDE ANALOG PRESSURE GAUGES AT EACH PUMP AND
ACROSS THE SUPPLY AND SUCTION HEADERS.
SUCTION DIFFUSER
WITH STRAINER (TYP.)
SYSTEM FLOW FROM
CONDENSER WATER PUMP
SIDE-STREAM TO
SEDIMENT SEPARATOR
AUTO-PURGE VALVE &
CONTROLLER
SOLID PURGE OUTLET FROM
SEPARATOR
PUMP
SYSTEM
FLOW
ANALOG
PRESSURE
GAUGES
CONTROL PANEL
SEDIMENT
SEPARATOR
GROOVED COUPLING
CONNECTIONS
CONNECTION SPOOL
SIDE-STREAM RETURN
TO SYSTEM FLOW
ROUTE TO DRAIN
MANUFACTURER-
PROVIDED SKID
EXIST. CONCRETE PAD
FLOOR
CONNECT TO SIDE OF PIPE
MAIN. AVOID TOP OR BOTTOM
CONNECTIONS TO PREVENT
AIR OR DEBRIS FROM
ENTERING PIPE TO THE TANK.
LOCK-SHIELD TYPE SHUTOFF
VALVE.
TANK CONNECTION LOCATIONS
MAY VARY DEPENDING ON
TANK SIZE AND
MANUFACTURER.
NOTES:
TO FLOOR DRAIN
HOUSEKEEPING PAD
RELIEF PLUG
PRE-CHARGING
AIR
CONNECTION
PRESSURE GUAGE
AUTOMATIC AIR VENT
SAFETY RELIEF VALVE
1FROM SYSTEM
AIR VENT (HIGH CAPACITY FLOAT TYPE)
DOMESTIC COLD WATER MAKE-UP
WITH RPBP AND PRV, SEE PLUMBING
PLANS
AIR SEPARATOR
(WITHOUT STRAINER)
ROUT FULL SIZE DRAIN LINE
TO NEAREST FLOOR DRAIN.
REFER TO PLUMBING
DRAWINGS FOR FLOOR DRAIN
LOCATION.
TO PUMP SUCTION
FLOOR
PRESSURIZED
EXPANSION TANK
ABOVE 2" [50mm] DIA. PIPE 2" [50mm] DIA. & SMALLER
VERTICAL
2 1/2" [65mm] DIA.
ABOVE 2" [50mm] DIA. PIPE 2" [50mm] DIA. & SMALLER
HORIZONTAL
2 1/2" [65mm] DIA.
FLEXIBLE CONNECTOR (TYPICAL)
PUMP
CONCRETE INERTIA BASE
WITH SPRING ISOLATORS
NOTES:
SEE SPECIFICATION SECTION "PUMPS"
FOR Y STRAINER OPTION
PUMP SKID
1" MIN. DIA. PIPE STAND
DRAIN
SUCTION DIFFUSER WITH BUILT IN
STRAINER. OPTIONAL: LONG
RADIUS ELBOW AND INLET
STRAINER WITH 3 X DIA. STRAIGHT
INLET TO PUMP
PRESSURE GAUGE
STRAINER
BUTTERFLY SHUT-OFF VALVE
CHECK VALVE
TO DISCHARGE
HEADER
TO SUCTION
HEADER
CONCRETE
FLOOR SLAB
CLIP ANGLE
STEEL EXPANSION SHIELD FOR
EXISTING CONSTRUCTION AND
INSERTS FOR NEW CONSTRUCTION
THIS TYPE SHALL BE USED ONLY IN
SLABS OR BEAMS OF 4" MIN. DEPTH
TURNBUCKLE
3/8" MIN. DIA.
HANGER RODS
3/8" MIN. DIA. EXPANSION BOLTS FOR
EXISTING CONSTRUCTION AND
INSERTS FOR NEW CONSTRUCTION
3/8" MIN. DIA. INSERTS NEW
CONSTRUCTION ONLY
NUTS &
WASHERS
3/8" MIN. DIA.
HANGER
RODS
FOR PIPES UNDER 2" IN SIZE USE 1 1/2"
X 1 1/2" X 1/4" ANGLE. ALL PIPES 2" AND
LARGER USE 3" X 3" X 1/4" ANGLE
PROVIDE VOLUME
DAMPER AT EACH
BRANCH DUCT
1/4W OR 4" MIN.
BRANCH DUCT
MAIN EXHAUST OR RETURN
AIR FLOW
AIR FLOW
VD
W
PLAN VIEW
NOTES:
1. DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
2. DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR
FOR MULTI-BLADE DAMPERS & ROUND DAMPERS.
SECTIONSIDE ELEVATION
1/2" ROUND ROD PIN
1/8" CLEARANCE
ALL AROUND
INSIDE END
BEARING
INSULATION
STAND-OFF
DAMPER BLADE
HANDLE
WITH
LOCKING
QUADRANT
STIFFEN BLADE
AS REQUIRED
INSULATION SEE
SPECIFICATION
DUCT
OUTSIDE END BEARING
TYPICAL WATER
PIPING
REDUCER, IF REQUIRED
3/4" BALL
VALVE
ADAPTER TO 3/4" HOSE
THREAD. PROVIDE
HOSE CAP NUT
NOTES:
1. DRAIN ALL LOW POINTS AS INDICATED ABOVE.
2. WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS
AND/OR PLANS, LOCATE DRAIN AT BOTTOM OF SCALE POCKET.
TYPICAL CHILLED WATER AND HOT WATER
PIPING DRAIN VALVE CONNECTIONS
ELEVATION:
THREADED PIPING
ELEVATION:
WELDED PIPING
1/4" COPPER TUBING
1/2" X 4" NIPPLE
AIR VENT
1/2" BALL VALVE
MV
OR
AV
CIRCULATING WATER
PIPING
ELEVATION
NOTES:
1. VENT ALL HIGH POINTS AS INDICATED ABOVE.
2. IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN.
TYPICAL MANUAL AIR VENT
NOTES:
1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS THIGHTLY.
2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.
3. SEE SMACNA 2005, FIGURE 9-16
INSULATION
DUCT
GASKET
INSULATION
SECTION "A-A"
ACCESS PANEL
CASING
GASKET HANDLE INSIDE
FLEXIBLE WASHER
FACTORY
FABRICATED LATCH
SECTION "B-B"
ACCESS DOOR
INSULATION
"B" "B"
"A"
"A"
EQUIPMENT
BASE ANCHOR BOLT
NEOPRENE
WASHER & SLEEVE
BONDED
STEEL PLATE
FLOOR
RESILIENT
PAD
CROSS
BRACING RODS
ALL FOUR SIDES
CLAMP
HANGER ROD
(TYP.)
LOCK NUTS
(TYP.)
EQUIPMENT WEIGHT
250 LBS OR LESS
FLOOR MOUNT EQUIPMENT
RESTRAINED BY RESILIENT PADS
(TYPE DS)
SEISMIC BRACING FOR LIGHT
SUSPENDED EQUIPMENT
NOTE:
NOT REQUIRED FOR TERMINAL
UNITS
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
/1 /2
:4
:3
P M
M-503
MECHANICAL DETAILS
6 12DJR DJR/PLH
REPLACE CHILLERS PH. II
NEW YORK HARBOR HEALTHCARE
SYSTEM
423 E 23RD STREET, NEW YORK, NY 12/20/2019
CONTRACT DOCUMENTS
630-16-10117-054
Scale: N.T.S.
PIPE HANGER
Scale: N.T.S.
CONCRETE EQUIPMENT BASES
Scale: N.T.S.
WATER COOLED CHILLER DETAIL
Scale:
PUMP SKID DETAIL
Scale: N.T.S
SIDE-STREAM SEPARATOR DETAIL
Scale: 1/8" = 1'-0"
AIR SEPARATOR AND EXPANSION TANK PIPING DETAIL
Scale: N.T.S.
INSTALLATION OF THERMOMETER WELLS
N.T.S
Scale: N.T.S.
SKID-MOUNTED PUMP WITH FLEXIBLE CONNECTOR
Scale: N.T.S.
SECURING HANGER RODS IN CONCRETE
Scale: N.T.S.
EXHAUST OR RETURN BRANCH DUCTWORK
Scale: N.T.S.
VOLUME DAMPER DETAIL
Scale: N.T.S.
DRAIN VALVE AND AIR VENT CONNECTIONS (HYDRONIC SYSTEMS)
Scale: N.T.S.
ACCESS PANEL AND DOOR DETAIL
Scale: N.T.S.
SEISMIC BRACING FOR EQUIPMENT
FIRST FLOOR
26.67
19 2119 21
P-1,2,3,&4 P-5,6,7,&8
24" CWS
EXISTING HOUSEKEEPING
PAD 43'-6" L x 17'-1" W x 6" D
(EXTEND AS NEEDED FOR
NEW PUMP SKIDS)
8" CWS
8" CWS
C H
R
C H
R
FIRST FLOOR
26.67
1921 1921
CD-1BCD-2BCD-3B
14" CWS
24" CWS
12" CWS TO
CH-2
FIRST FLOOR
26.67
CD-3B
P-5,6,7,&8
14" CWS
C H
R
20" CHR
JJ LLJJ LL
M-504
CCU1
SPRING ISOLATOR (TYP.)
24" CWR20" CHS
12" CHS
14" CWR
24" CWS
14" CWS
24x32
24x32
10x20
10x20
ETR - 5EF-6
STRAINER
FIRST FLOOR
26.67
192122.5 192122.5
CCU3 CCU2 CCU1
C W
R
C W
R
C W
R
C H
S
20" CHR 18" CHR 12" CHR
24" CWR 24" CWR
C H
S
C H
R
C H
R
C H
S
C H
R
10x20
V-CW-1
V-TW-1
CV-4
V-CW-2
V-TW-2
V-CW-3
V-TW-3
THERMOMETER
(TYP. OF 12)
PRESSURE GAUGE
(TYP. OF 12)
14" CWS
14" CWS
14" CWS
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
/1 /2
:4
:4
P M
M-504
MECHANICAL SECTIONS
7 12DJR DJR/PLH
REPLACE CHILLERS PH. II
NEW YORK HARBOR HEALTHCARE
SYSTEM
423 E 23RD STREET, NEW YORK, NY 12/20/2019
CONTRACT DOCUMENTS
630-16-10117-054
Scale: 1/4" = 1'-0"
SECTION AT PUMP SKIDS
Scale: 1/4" = 1'-0"
SECTION AT CHILLER DRIVES
Scale: 1/4" = 1'-0"
SECTION AT PUMP SKID #2
Scale: 1/4" = 1'-0"
SECTION AT CCU1
Scale: 1/4" = 1'-0"
SECTION AT CHILLERS - LOOKING EAST 0 2 4 8 0 2 4 8
0 2 4 8 0 2 4 8 0 2 4 8
JJ LLJJ LL
CCU3
SPRING ISOLATOR (TYP.)
24" CWR14" CWR
20x10
10x20 10x20
20x10
10x20
20" CHR
12" CHR
12" CHS
26x20
STRAINER
JJ LLJJ LL
M-504
CCU2
SPRING ISOLATOR (TYP.)
14" CWR
12" CHR
24" CWR
14" CWS
12" CHS
10x20
26x24
10x20
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
/1 /2
:4
:4
P M
M-505
MECHANICAL SECTIONS
8 12DJR DJR/PLH
REPLACE CHILLERS PH. II
NEW YORK HARBOR HEALTHCARE
SYSTEM
423 E 23RD STREET, NEW YORK, NY 12/20/2019
CONTRACT DOCUMENTS
630-16-10117-054
Scale: 1/4" = 1'-0"
SECTION AT CCU3
Scale: 1/4" = 1'-0"
SECTION AT CCU2
0 2 4 8
0 2 4 8
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
/1 /2
:4
:5
P M
M-601
MECHANICAL SCHEDULES
9 12DJR DJR/PLH
REPLACE CHILLERS PH. II
NEW YORK HARBOR HEALTHCARE
SYSTEM
423 E 23RD STREET, NEW YORK, NY 12/20/2019
CONTRACT DOCUMENTS
630-16-10117-054
NOTES:
P-8 CHILLER PLANT BUILDINGS 1 AND 6 CONDENSER WATER BASE-MOUNTED END SUCTION CONDENSER WATER 1635 3600 130 85/95 82 200 1750 VARIABLE SEE NOTES
P-7 CHILLER PLANT BUILDINGS 1 AND 6 CONDENSER WATER BASE-MOUNTED END SUCTION CONDENSER WATER 1635 3600 130 85/95 82 200 1750 VARIABLE SEE NOTES
P-6 CHILLER PLANT BUILDINGS 1 AND 6 CONDENSER WATER BASE-MOUNTED END SUCTION CONDENSER WATER 1635 3600 130 85/95 82 200 1750 VARIABLE SEE NOTES
P-5 CHILLER PLANT BUILDINGS 1 AND 6 CONDENSER WATER BASE-MOUNTED END SUCTION CONDENSER WATER 1635 3600 130 85/95 82 200 1750 VARIABLE SEE NOTES
P-4 CHILLER PLANT BUILDINGS 1 AND 6 CHILLED WATER BASE-MOUNTED END SUCTION CHILLED WATER 1240 2400 185 42/54 80 200 1750 VARIABLE SEE NOTES
P-3 CHILLER PLANT BUILDINGS 1 AND 6 CHILLED WATER BASE-MOUNTED END SUCTION CHILLED WATER 1240 2400 185 42/54 80 200 1750 VARIABLE SEE NOTES
P-2 CHILLER PLANT BUILDINGS 1 AND 6 CHILLED WATER BASE-MOUNTED END SUCTION CHILLED WATER 1240 2400 185 42/54 80 200 1750 VARIABLE SEE NOTES
P-1 CHILLER PLANT BUILDINGS 1 AND 6 CHILLED WATER BASE-MOUNTED END SUCTION CHILLED WATER 1240 2400 185 42/54 80 200 1750 VARIABLE SEE NOTES
FLUID MIN FLOW (GPM) DESIGN FLOW (GPM) HEAD (FT. W.G.) TEMPERATURE RANGE (F) NOMINAL POWER (HP.) R.P.M. SPEED CONTROL
MARK LOCATION AREA SERVED SYSTEM TYPE
CIRCULATING FLUID
MIN % EFF
PUMP MOTOR
REMARKS
HYDRONIC PUMP SCHEDULE
NOTES
ETR CCU4 CHILLER PLANT BUILDINGS 1 AND 6 CHILLED WATER 1200 2 0.6014 0.3747 0.0001 2400 54 42 18.4 0.00025 3600 85 95 22.7 721.7 128 225 4160 3 43138 UNIT IS EXISTING
CCU3 CHILLER PLANT BUILDINGS 1 AND 6 CHILLED WATER 1200 2 0.5597 0.3560 0.0001 2400 54 42 22.4 0.00025 3600 85 95 28.1 671.6 119 200 4160 3 55000 SEE NOTES
CCU2 CHILLER PLANT BUILDINGS 1 AND 6 CHILLED WATER 1200 2 0.5597 0.3560 0.0001 2400 54 42 22.4 0.00025 3600 85 95 28.1 671.6 119 200 4160 3 55000 SEE NOTES
CCU1 CHILLER PLANT BUILDINGS 1 AND 6 CHILLED WATER 1200 2 0.5597 0.3560 0.0001 2400 54 42 22.4 0.00025 3600 85 95 28.1 671.6 119 200 4160 3 55000 SEE NOTES
FOULING FACTOR FLOW (GPM) EWT (°F) LWT(°F) MAX WPD (FT. HD) FOULING FACTOR FLOW (GPM) EWT(°F) LWT(°F) MAX WPD (FT. HD) POWER KW MCA MOCP VOLTS PHASE
MARK NO. LOCATION BUILDING/AREA SERVED SERVICE
FULL LOAD
CAPACITY (TONS)
NO. PASSES
MIN. EFF. FULL
LOAD (KW/TON)
MIN. NPLV
(KW/TON)
EVAPORATOR CONDENSER ELECTRICAL
OPERATING
WEIGHT (LBS)
REMARKS
VARIABLE PRIMARY WATER COOLED CENTRIFUGAL CHILLER SCHEDULE
1) BASIS OF DESIGN LAKOS TBX-1100
2) MOUNT SKID ON 4" CONCRETE PAD
2) PROVIDE WITH ELECTRICAL CONTROL BOX W/ 120 VOLT TRANSFORMER IN NEMA 4X ENCLOSURE WITH SAFETY DISCONNECT AND HOA SWITCH
3) WITH INLET/OUTLET PRESSURE GAUGES: 0-100 PSI
4) WITH DIFFERENTIAL PRESSURE INDICATOR WITH DRY CONTACT TO DDC
5)WITH AUTO PURGE TO DRAIN
NOTES:
SSF-1 CHILLER PLANT CONDENSER WATER SIDE STREAM 1 50 MICRON 1006 20 480/3/60 27 100 DEG F 150 PSI 2442 SEE NOTES
NUMBER OF FILTERS FILTER TYPE
PUMP (HP) VOLT/PH/HZ
FULL LOAD
AMPS
MARK LOCATION SYSTEM TYPE
CIRCULATING FLUID
FLOW (GPM)
ELECTRICAL DATA
MAX
TEMPERATURE
MAX PRESSURE WEIGHT (LBS) REMARKS
SIDE STREAM SEPARATOR SCHEDULE
1) INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
NOTES:
V-TW-5 CONDENSER WATER BYPASS CONTROL 3-WAY MODULATING
V-TW-4 CCU-4 CONDENSER WATER CONTROL 2-WAY MODULATING 3,600 3 1,663 1
V-TW-3 CCU-3 CONDENSER WATER CONTROL 2-WAY MODULATING 3,600 3 1,663 1
V-TW-2 CCU-2 CONDENSER WATER CONTROL 2-WAY MODULATING 3,600 3 1,663 1
V-TW-1 CCU-1 CONDENSER WATER CONTROL 2-WAY MODULATING 3,600 3 1,663 1
V-CW-5 CHILLED WATER BYPASS CONTROL 2-WAY MODULATING 1310 3 1
V-CW-4 CCU-4 CHILLED WATER CONTROL 2-WAY MODULATING 2,400 3 1,386 1
V-CW-3 CCU-3 CHILLED WATER CONTROL 2-WAY MODULATING 2,400 3 1,386 1
V-CW-2 CCU-2 CHILLED WATER CONTROL 2-WAY MODULATING 2,400 3 1,386 1
V-CW-1 CCU-1 CHILLED WATER CONTROL 2-WAY MODULATING 2,400 3 1,386 1
GPM PSI
MARK LOCATION SERVICE FUNCTION TYPE FLOW MAX PD Cv REMARKS
VALVE SCHEDULE AIR SEPARATOR SCHEDULE
MARK
SYSTEM AND/OR
SERVICE TYPE SIZE FLOW WPD
BUILT-IN STRAINER
REQUIRED REMARKS
AS-1 CHILLED WATER TANGENTIAL, FLANGED 16" 7200 GPM 5 ftH2O No 1, 2, 3, 4
REMARKS:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
2. PROVIDE SKIRT FOR FLOOR MOUNTING TO SUPPORT FLOODED WEIGHT OF UNIT.
3. MAXIMUM ALLOWABLE DIAMTER: 48". MAXIMUM ALLOWABLE HEIGHT: 105". MAXIMUM ALLOWABLE FLOODED WEIGHT: 8,500 LBS.
4. INSULATE AIR SEPARATOR WITH 1-1/2" MINERAL FIBER BOARD INSULATION WITH ALL-SERVICE JACKET.
EXPANSION TANK SCHEDULE
MARK SYSTEM TYPE
SYSTEM TEMPERATURE
RANGE
INITIAL
PRESSURE IN
TANK
MAX
OPERATING
PRESSURE
FILL PRESSURE AT TANK MIN VOLUME
TANK
MIN BLADDER
VOLUME
PIPE SIZE TO
TANK REMARKSMIN TEMP MAX TEMP RELIEF VALVE AT TANK
ET-1 CHILLED WATER VERTICAL PRESSURIZED
BLADDER
40 °F 65 °F 26.0 psi 80.0 psi 80.0 psi 89.0 psi 1980.0 gal 1980.0 gal 3" 1, 2, 3, 4
REMARKS:
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
2. PROVIDE SKIRT FOR FLOOR MOUNTING TO SUPPORT FLOODED WEIGHT OF UNIT.
3. MAXIMUM ALLOWABLE DIAMTER: 72". MAXIMUM ALLOWABLE HEIGHT: 127". MAXIMUM ALLOWABLE FLOODED WEIGHT: 20,500 LBS.
4. INSULATE EXPANSION TANK WITH 1-1/2" MINERAL FIBER BOARD INSULATION WITH ALL-SERVICE JACKET.
PP-707
EMERGENCY SHOWER, EYE AND FACE
WASH
- - 1-1/4 1-1/4 - - N/A NO
IN IN IN IN
MARK DESCRIPTION
WASTE PIPE VENT PIPE COLD WATER HOT WATER
WASTE FIXTURE UNITS WATER FIXTURE UNITS WRIST BLADE HANDLES ELECTRIC SENSOR REMARKS
PLUMBING FIXTURE SCHEDULE
1. PROVIDE NON-OVERLOADING MOTOR SELECTIONS.
2. PROVIDE INVERTER DUTY RATED MOTOR.
3. PUMPS P-1 THROUGH P-4 SHALL BE FACTORY SKID MOUNTED AND TESTED ASSEMBLY INCLUDING SUCTION DIFFUSERS WITH STRAINERS AND REMOVABLE STARTUP SCREENS, INLET AND OUTLET BUTTERFLY ISOLATION VALVES, VARIABLE FREQUENCY DRIVES, DISCHARGE CHECK VALVES, SUCTION AND DISCHARGE HEADERS SIZED FOR FULL
FLOW OF ALL PUMPS, ANALOG PRESSURE GAUGES FOR EACH PUMP AND FOR PUMP SKID, CONTROL PANEL, AND LIFTING LUGS. FACTORY WIRE ENTIRE SKID FOR SINGLE POINT POWER CONNECTION AND SINGLE POINT CONTROLS POWER CONNECTION.
4. PUMPS P-5 THROUGH P-8 SHALL BE FACTORY SKID MOUNTED AND TESTED ASSEMBLY INCLUDING SUCTION DIFFUSERS WITH STRAINERS AND REMOVABLE STARTUP SCREENS, INLET AND OUTLET BUTTERFLY ISOLATION VALVES, VARIABLE FREQUENCY DRIVES, DISCHARGE CHECK VALVES, SUCTION AND DISCHARGE HEADERS SIZED FOR FULL
FLOW OF ALL PUMPS, ANALOG PRESSURE GAUGES FOR EACH PUMP AND FOR PUMP SKID, CONTROL PANEL, AND LIFTING LUGS. ADDITIONALLY, PROVIDE 480V/3Ph POWER SOURCE FOR SIDE STREAM SEPARATOR SKID (60 AMP NEMA 1, FUSED, 3 POLE, DISCONNECT SWITCH WITH 40 AMP CLASS RK1 FUSES PREWIRED AND MOUNTED TO CONDENSER WATER PUMP SKID). FACTORY WIRE ENTIRE SKID FOR SINGLE POINT POWER CONNECTION AND SINGLE POINT CONTROLS POWER CONNECTION.
5. AT FULL FLOW CONDITIONS, PUMP PACKAGE P-1 THROUGH P-4 SHALL DELIVER 7,200 GPM WITH ANY THREE PUMPS OPERATING. CONTROLS SHALL PREVENT MORE THAN (3) PUMPS FROM RUNNING SIMULTANEOUSLY. CONTROLS SHALL SOFT START PUMPS VIA THE VFDs.
6. AT FULL FLOW CONDITIONS, PUMP PACKAGE P-5 THROUGH P-8 SHALL DELIVER 10,800 GPM WITH ANY THREE PUMPS OPERATING. CONTROLS SHALL PREVENT MORE THAN (3) PUMPS FROM RUNNING SIMULTANEOUSLY. CONTROLS SHALL SOFT START PUMPS VIA THE VFDs.
7. COORDINATE WITH THIRD PARTY CHILLER PLANT CONTROLS.
8. COORDINATE MINIMUM FLOWRATES WITH ACTUAL CHILLERS FURNISHED.
9. CONDENSER WATER PUMP NPSHR: 20.7 FT. CHILLED WATER PUMP NPSHR: 17.4 FT.
1. BASIS OF DESIGN IS YORK YK. PROVIDE WITH HINGED MARINE WATER BOXES (HINGED END CAPS) FOR TUBE ACCESS, ISOLATION VALVES, CONTROL VALVES, MAINTENANCE RECEPTACLE, SINGLE POINT POWER CONNECTION, CHILLED AND CONDENSER WATER FLOW SWITCHES, VARIABLE EVAPORATOR AND CONDENSER FLOW, AND VSD
(VARIABLE SPEED DRIVE) WITH POWER FILTER.
2. REFRIGERANT : R-134A; 2,215 POUNDS PER CHILLER.
3. PROVIDE DDC CONTROLLER FOR OPERATION OF CHILLER. FULLY INTEGRATE CHILLER DDC CONTROLS INTO EXISTING 3RD PARTY BUILDING DDC CONTROLS. PROVIDE CONTROL VOLTAGE TRANSFORMER.
4. CONDENSER SHALL BE CAPABLE OF OPERATING DOWN TO 50 DEGREES F. ENTERING WATER TEMPERATURE.
5. CHILLER SHALL BE CAPABLE OF 10-100% UNLOADING.
6. MAXIMUM ALLOWABLE A-WEIGHTED SOUND PRESSURE LEVEL IS 81 dBA AT FULL COMPRESSOR SPEED WHEN TESTED IN ACCORDANCE WITH AHRI STANDARD 575-2017.
7. MAXIMUM ALLOWABLE OPERATING WEIGHT: 55,000 LBS.
REFRIGERANT LEAK DETECTION AND EVACUATION SEQUENCE OF OPERATION (DDC):
REFRIGERANT LEAK DETECTION SYSTEM IS EXISTING TO REMAIN. THE SYSTEM IS INTERLOCKED WITH THE EXISTING EXHAUST FAN. UPON DETECTION OF REFRIGERANT GAS IN THE ATMOSPHERE, THE MONITOR SHALL DE-ENERGIZE ALL CHILLERS THROUGH THE CPO, ACTIVATE THE EXISTING EXHAUST FAN, AND ACTIVATE THE EXISTING EVACUATION HORN AND STROBE. FAN
SHALL RUN CONTINUOUSLY. MANUAL RESET OF SYSTEM SHALL BE REQUIRED.
Revisions: Date
Drawing Title:
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER:
E
D C
B A
2 3 4 5 6 7
E D
C B
A
1 2 3 4 5 6 7
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
/1 /2
:4
:5
P M
M-701
CONTROLS
10 12DJR DJR/PLH
REPLACE CHILLERS PH. II
NEW YORK HARBOR HEALTHCARE
SYSTEM
423 E 23RD STREET, NEW YORK, NY 12/20/2019
CONTRACT DOCUMENTS
630-16-10117-054
CHILLER/COOLING TOWER SYSTEM SEQUENCE OF OPERATION
I System Description A. The chilled water (CHW) system consists of four 1200 ton, VSD-driven, water-cooled centrifugal chillers (C-1 thru C-4). There are four 2400 GPM, VSD-driven, primary CHW pumps (P-1 thru P-4) piped to a common header, so that any CHW pump shall be capable of running with any chiller, and the pumps can be sequenced independently of chillers for optimization algorithms. The CHW system is piped in a variable primary flow configuration, with a 2-way, CHW bypass valve across the chillers and pumps to maintain minimum flow through the operating chillers. Each chiller shall be equipped with chilled water and condenser water modulating control valves complete with actuator and end switches. One CHW differential- pressure transmitter shall be located in the central plant and another in a suitable location near the end (index circuit) of the building-loop.
B. The condenser water (CW) system consists of twelve individual cooling tower (CT) cells, with a common sump and VSD-driven fans. There are four 2880 GPM, VSD-driven CW pumps (P-5 thru P-8) piped to a common header, so that any CW pump or group of pumps, based upon energy/maintenance cost optimization algorithms, shall be capable of running with any chiller and CT combination. Each CT cell shall be equipped with a 2-position isolation valve, complete with actuator and end switches. The CT piping shall include a bypass valve, complete with actuator.
C. Provide an interface utilizing BACnet MS/TP protocol to connect the new chillers to the facility's existing Automated Logic Building Management System (BMS). Provide all network automation engines and field controllers that are required to fully integrate the new chillers into the existing BMS. A loss of communications at the existing web-based operator workstation (OWS) shall not affect the operation or performance of the chiller plant optimization (CPO) program.
D. The CPO feature is designed to minimize the combined electrical energy consumption of the operating chiller(s), chilled and condenser water pump(s), and cooling tower fan(s) as constrained by meeting the building chilled water flow and temperature requirements.
II. Chiller Plant Enable/Disable A. The chiller plant shall be enabled and disabled either manually by an operator command or automatically through the BMS. In the automatic mode, the BMS shall enable the chiller plant whenever the outdoor air dry-bulb temperature (OAT) exceeds the chiller plant enable set-point 55°F (adj.), and disable the chiller plant when the OAT is less than the chiller plant enable set-point minus differential 5°F(adj.).
B. When the chiller plant is disabled, all chillers shall be commanded off, the cooling tower bypass valve (V- TW-5) shall close, and the chilled water bypass valve (V-CW-5) shall open. The chilled water pumps, condenser water pumps, and cooling tower fans that were operating at the time the plant was commanded off shall operate at full speed for 5 minutes (adjustable) to remove residual heat from the system. After this period of time, all pumps and cooling tower fans shall be commanded off, and all control valves (V-CW-1 thru V-CW-8, V-TW-1 thru V-TW-8) shall close.
III. Lead-Lag The chillers, pumps, and cooling towers operating order shall be determined by equalization of run-time. The CPO program shall totalize run-hours for each device and adjust the operating order. If a chiller, pump, or cooling tower failure is detected (an alarm shall annunciate upon failure) or becomes unavailable due to maintenance, it will be shut down BMS and the next available device in the sequence shall be started.
IV. Initial Start-up and Adding Additional Chillers A. The following sequence applies to the specific case when the CPO needs to start the first chiller. The starting sequence for additional chillers will be different as described in section IV-D.
1. Command associated CHW (V-CW-1 thru V-CW-4), CW (V-TW-1 thru V-TW-4), and CT cell control valves to fully open position. The active CT cell shall be determined by the BMS on a rotating basis to equalized run time between cells.
2. Once valve positions have been proven fully open by end switches, command the first available CHW and CW pump to start.
3. Prove CHW and CW pump running status using a current-sensing relay. After a 60 second (adj.)
stabilization delay, command 1st chiller to start.
B. A Pulldown routine shall load-limit the chiller (through its current-limit…