S02 Elec CD Drawing.pdf

PDF 3 MB Posted

Attached to
Y1DZ--NRM - CONSTR PROJ - 630-26-102 Design Build HVAC Bldgs. 4 and 5
Solicitation number
36C24226R0034
Issued by

About this file

This document set comprises electrical construction drawings and specifications for the replacement of chillers at New York Harbor Healthcare System located at 423 East 23rd Street, New York, NY, as part of Phase II of a chiller replacement project (Project Number 630-16-101).

The project requires removal of existing electrical infrastructure including three AMPGARD Motor Control Centers (MCC1, MCC2, and MCC3), existing chiller feeders, and associated conduit and cabling, with specific emphasis on proper disposal procedures including verification and removal of any PCB-containing equipment. The contractor must install three new chillers (CH-1, CH-2, and CH-3) with associated Variable Frequency Drives (VFDs), control panels, and MOD-BUS communication cable runs. Power requirements include furnishing and installing shielded 3-1/C#2 cables with #6 bare copper ground in new RGS conduit from switchgear sections K-2C, K-1D, and J-1C to the new equipment. The work involves connections to existing 4.16KV/480Y/277V and 208V/3PH systems, installation of control circuits at 120V single-phase, and provision of 3/4" RGS conduit with shielded twisted pair cables for control communications. All new overhead electrical conduit must be installed tight to the ceiling or at minimum 8 feet above finished floor. The contractor must engage authorized VAMC contractor CRASCO INC. for specific terminations and control room equipment programming. Construction must maintain a clean chiller plant environment with daily debris removal, and all work is subject to compliance with electrical codes, NEC standards, and UL-classified firestop systems where penetrations are required through rated walls.

View the file

Other files

File Type Posted
36C24226R0034 0005.docx DOCX document
Amendment 00004 RFI Answers.docx DOCX document
36C24226R0034 0004.docx DOCX document
Amendment 00003 RFI Answers.docx DOCX document
S02 Mechanical Print Chiller Plant Drawing.pdf PDF
S02 Architectural Drawing.pdf PDF
36C24226R0034 0003.docx DOCX document
S02 Mech_CD Drawing.pdf PDF
36C24226R0034 0002.docx DOCX document
VA Privacy Training Document.pdf PDF
36C24226R0034 0001.pdf PDF
36C24226R0034_1.1.docx DOCX document
S02 52.225-2 BUY AMERICAN CERTIFICATE 2.1.docx DOCX document
S02 LIMITATION ON SUBCONTRACTING 2.1.docx DOCX document
S02 INSTRUCTIONS TO BIDDERS REGARDING TAX EXEMPTION IN NY 2.1.docx DOCX document
S02 Privacy Training for Personnel without Access to VA Computer 1.1.pdf PDF
SCA Wagw No 2015 4187 Rev 34 12032025.1.pdf PDF
S02 Participation Goals for Minorities and Females 2.1.pdf PDF
01 35 26 Safety Requirements Design Build HVAC Bldgs. 4 and 5.1.docx DOCX document
01 00 00 General Requirements Design Build HVAC Bldgs. 4 and 5.1.docx DOCX document
S02 FAR DEVIATION FEB 2025 NOTICE 2.1.docx DOCX document
S02 AUTODESK Contractors Access Instructions 1.1.pdf PDF
S02 LIQUIDATED DAMAGES FORMULATION MEMO 2.1.docx DOCX document
S02 SAFETY AND ENVIRONMENTAL RECORD 2.1.docx DOCX document
013200 Construction Documentation Design Build HVAC Bldgs. 4 and 5.1.docx DOCX document
WD NY20250003 Mod 17 12122025.1.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SPECIAL PURPOSE RECEPTACLE - FLUSH FLOOR MOUNTED

SPECIAL PURPOSE RECEPTACLE - CEILING MOUNTED

SPECIAL PURPOSE RECEPTACLE - MOUNTED 18" AFF

QUADRUPLEX RECEPTACLE - FLUSH FLOOR MOUNTED

DUPLEX RECEPTACLE - FLUSH FLOOR MOUNTED

SINGLE RECEPTACLE - MOUNTED 18" AFF

QUADRUPLEX RECEPTACLE - MOUNTED 18" AFF

UTILITY KILOWATT-HOUR METER

DUPLEX RECEPTACLE - EMERGENCY POWER - MOUNTED 18" AFF

DUPLEX RECEPTACLE - CEILING MOUNTED

DUPLEX RECEPTACLE - SPLIT WIRED - MOUNTED 18" AFF

DUPLEX RECEPTACLE - MOUNTED 6" ABOVE COUNTER

MAGNETIC STARTER

SAFETY SWITCH - FUSIBLE

SAFETY SWITCH - NON-FUSIBLE

EQUIPMENT - MOTOR

BRANCH CIRCUIT PANELBOARD - FLUSH MOUNTED

DISTRIBUTION PANELBOARD OR SWITCHBOARD

MOTOR CONTROL CENTER

BRANCH CIRCUIT PANELBOARD - SURFACE MOUNTED

CONTROL PANEL

TRANSFORMER

POWER SYMBOLS

AUTOMATIC TRANSFER SWITCH

METER

CIRCUIT BREAKER

GROUND

ONE-LINE DIAGRAM SYMBOLS

GENERATOR

DELTA-WYE TRANSFORMER

SWITCH

SERVICE DROP

CONDUIT - CAPPED

CABLE TRAY

SEALING FITTING

EXPANSION FITTING

CONDUIT FITTING (CONDULET)

JUNCTION BOX

CONDUIT - FLEXIBLE

CONDUIT - CONTINUED

CONDUIT - CONCEALED BELOW

SLAB OR GRADE

CONDUIT - UP AND DOWN

(CHANGE IN ELEVATION)

CONDUIT - TURNING UP

CONDUIT - EXPOSED

CONDUIT - CONCEALED IN

SUSPENDED CEILING OR WALL

CONDUIT - TURNING DOWN

REVISION CALL-OUT

ROOM NUMBER

FEEDER CALL-OUT

KEYED NOTE

MECHANICAL EQUIPMENT CALL-OUT: REFER TO

THE EQUIPMENT DATA SCHEDULE FOR DETAILS

GENERAL SYMBOLS

JUNCTION BOX - EMERGENCY POWER

SHEET KEY NOTE

WIRING AND CONDUITS

NEW EQUIPMENT (TYPICAL)

EXISTING EQUIPMENT (TYPICAL)

DEMOLITION EQUIPMENT (TYPICAL)

WALL MOUNT BRACKET (TYPICAL)

T-1

45 KVA 3Ø

208Y/120VAC

# AF

# AT

# A

# A

G

ST

SPD

VFD

GROUND FAULT

PROTECTED BREAKER

SHUNT TRIP BREAKER

CONTACTOR

CURRENT TRANSFORMER

POTENTIAL TRANSFORMER

DRAWOUT CIRCUIT BREAKER

# AF

# AT

FUSE

PANELBOARD

SURGE PROTECTION DEVICE

THERMAL OVERLOAD

VARIABLE FREQUENCY DRIVE

K

KIRK KEY INTERLOCK

DPM

DIGITAL POWER METER

QUADRUPLEX RECEPTACLE - MOUNTED 6" ABOVE

COUNTER

Room name

101A

PLUMBING EQUIPMENT CALL-OUT: REFER TO

THE EQUIPMENT DATA SCHEDULE FOR DETAILS

J

J

M

G

# A

# POLES

PANEL

M

F

VFD

T

POLE MOUNTED TRANSFORMER

T

J

DUPLEX RECEPTACLE (NEMA 5-20R) - MOUNTED 18" AFF

GFI GROUND FAULT CIRCUIT INTERRUPTER

SS SURGE SUPPRESSOR (ISOLATED GROUND

TYPE)

WP WEATHERPROOF

H HOSPITAL GRADE

TP TAMPER PROOF

D DEDICATED

FLOOR BOX - SEE SPECS OR KEYED NOTES ON

PLAN FOR DETAILS

COMBINATION STARTER

VFD VARIABLE FREQUENCY DRIVE

AC

AC

GROUND BAR

100A4G

# KVA/KW

480Y/277V, 3Ø, 4W

49 ELECTRONIC OVERLOAD

AHU

GWH1

AH(1)

MOTOR NUMBER TYP.

L

L

ELECTRICAL ABBREVIATIONS LIST

SS STAINLESS STEEL

SSW SELECTOR SWITCH

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

TC TIMECLOCK

TEL TELEPHONE

TEL/DATA TELEPHONE/DATA

TERM TERMINAL

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TR TAMPER RESISTANT

T-STAT THERMOSTAT

TTB TELEPHONE TERMINAL BOARD

TTC TELEPHONE TERMINAL

CABINET

TV TELEVISION

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITER'S LABORATORY

UT UNDERGROUND TELEPHONE

UTP UNSHIELDED TWISTED PAIR

UTIL UTILITY

UV UNIT VENTILATOR OR

ULTRAVIOLET

V VOLT

VA VOLT-AMPERES

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

W WATT

W/ WITH

WH WATER HEATER

W/O WITHOUT

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

ANGLE

@ AT

DELTA

' FEET

" INCHES

# NUMBER

Φ PHASE

C CENTER LINE

P PLATE

MTS MANUAL TRANSFER SWITCH

MTR MOTOR, MOTORIZED

NA NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATION

NFDS NON-FUSED SAFETY DISCONNECT

SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OH OVERHEAD

OL OVERLOAD

PA PUBLIC ADDRESS

PB PULL BOX OR PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT

UNIT

PCB POLYCHLORINATED BYPHENYL

PC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

POE POWER-OVER-ETHERNET

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (CONDUIT)

PWR POWER

QTY QUANTITY

RCP REFLECTED CEILING PLAN

RCPT RECEPTACLE

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

RTU ROOF TOP UNIT

SC SURFACE CONDUIT

SEC SECONDARY

SF SQUARE FEET/FOOT

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SIM SIMILAR

S/N SOLID NEUTRAL

SPEC SPECIFICATION

SPKR SPEAKER

SP SPARE

SR SURFACE RACEWAY

1P 1 POLE (2P, 3P, 4P, ETC.)

1PH 1 PHASE

2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)

W2 TWO-WIRE (3W, 4W, ETC.)

3PH 3 PHASE

A AMPERE

AAP ALARM ANNUNCIATOR PANEL

AC ABOVE COUNTER

AIR CONDITIONER

ALTERNATING CURRENT

ACC ACCESSIBLE

ACLG ABOVE CEILING

ADO AUTOMATIC DOOR OPENER

A/E ARCHITECT/ENGINEER

AF AMP FRAME

AFC AVAILABLE FAULT CURRENT (KILOAMPS)

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFI ARC FAULT CIRCUIT INTERRUPTER

AHJ AUTHORITY HAVING JURISDICTION

AHU AIR HANDLING UNIT

AIC AMPERE INTERRUPTING CAPACITY

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

APPROX APPROXIMATELY

ARCH ARCHITECT, ARCHITECTURAL

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

BAS BUILDING AUTOMATION SYSTEM

BATT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISHED FLOOR

BLDG BUILDING

BMS BUILDING MANAGEMENT SYSTEM

BYP BYPASS

C CONDUIT

CAB CABINET

CALC CALCULATED

CAP CAPACITY

CAT CATALOG, CATEGORY

CATV COMMUNITY ANTENNA TELEVISION

CB CIRCUIT BREAKER

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR-FURNISHED

CKT CIRCUIT

CLG CEILING

COAX COAXIAL CABLE

COMM COMMUNICATION

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR CONTINUOUS

CONTR CONTRACTOR

COORDCOORDINATE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CTR CENTER

CU COPPER

CU FT CUBIC FEET

dB DECIBEL

DB DIRECT BURIAL

DC DIRECT CURRENT

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLISH/DEMOLITION

DEPT DEPARTMENT

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DS SAFETY DISCONNECT SWITCH

DT DOUBLE THROW

DWG DRAWING

EC ELECTRICAL CONTRACTOR

EG EQUIPMENT GROUND

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

EM EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EPO EMERGENCY POWER OFF

EQUIP EQUIPMENT

ESMT EASEMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WALL HEATER

ELECTRIC WATER HEATER

EX EXISTING

EXP EXPLOSION PROOF

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FCU FAN COIL UNIT

FIXT FIXTURE

FLR FLOOR

FLUOR FLUORESCENT

FU FUSE

FUDS FUSED SAFETY DISCONNECT SWITCH

FVR FULL VOLTAGE REVERSING

FVNR FULL VOLTAGE NON-REVERSING

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI GROUND FAULT CIRCUIT INTERRUPTER

GND GROUND

GRS GALVANIZED RIGID STEEL (CONDUIT)

GYP BDGYPSUM BOARD

HID HIGH-INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND AIR

CONDITIONING

IES ILLUMINATION ENGINEERING SOCIETY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

IR INFRARED

I/W INTERLOCK WITH

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LED LIGHT-EMITTING DIODE

LF LINEAR FEET/FOOT

LM LUMEN

LRA LOCKED ROTOR AMPS

LT LIGHT

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC MECHANICAL CONTRACTOR

METAL-CLAD (CONDUIT)

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MOA MULTIOUTLET ASSEMBLY

MSBD MAIN SWITCHBOARD

MT MOUNT

A1 b

E1 c d

T1

'LPN'

ELECTRICAL SYMBOL NOTES

THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER

CASE LETTER AND NUMBER.

THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.

EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.

EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING

MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES

DIRECTIONAL ARROW ON ILLUMINATED FACE(S).

DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER

FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR

THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND

REQUIREMENTS.

PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING

SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR

DESIGNATION CODES.

SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE

NUMBER INDICATED IN THE HEXAGON.

HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT

DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.

CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL

SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.

SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE

A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.

'LPN'-1,3,5

EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE

AND DIRECTIONAL ARROW.

EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE

FACE AND DIRECTIONAL ARROWS.

E2

EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS

CONTROLLED BY SWITCH 'c'.

EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING

FIXTURES INDICATED BY 'd'.

EXAMPLE: TRANSFORMER TYPE 'T1'.

EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.

DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE

NOTE NUMBER INDICATED IN THE SQUARE.

GENERAL ELECTRICAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN

ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED

PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND

WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA STANDARDS.

PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE

BUILDING CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.

FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL

PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE

WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTING REQUIREMENT AND

THE APPLICABLE BUILDING CODES.

VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED

MOUNTING HARDWARE TO SUIT THE PARTICULAR INSTALLATION.

PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.

BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.

COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO

AVOID CONFLICT DURING CONSTRUCTION.

ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND

ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR

SPARE, OR SPACE.

MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO

INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR

MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE

ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".

ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR

EQUIPMENT MANUFACTURER'S SPECIFICATIONS.

CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE

DEVICE'S SCREW TERMINALS.

MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT

UNLESS NOTED OTHERWISE.

ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.

ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.

ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON

VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND

CONDUIT OR WHERE CONCRETE-ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE,

LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR FINAL CONNECTIONS.

ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN

APPROVED THIRD PARTY TESTING AGENCY.

FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE

SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC

PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE

MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT

BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.

PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.

IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE

BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS

DETERMINED BY THE GOVERNMENT, SHALL BE PROVIDED.

19. PROVIDE ARC FLASH LABELING FOR NEW ELECTRICAL WORK.

20. NO "HOT" ELECTRICAL WORK IS PERMITTED. ALL SHUTDOWNS MUST BE SUBMITTED WITH A MINIMUM

OF TWO WEEK NOTICE.

SHORT CIRCUIT CURRENT CALCULATIONS WILL BE

PERFORMED ON THE ELECTRICAL SYSTEM USING A

BOLTED THREE PHASE FAULT CONDITION FOR

CALCULATIONS TO ACHIEVE MAXIMUM THERMAL AND

MECHANICAL STRESS TO THE SYSTEM FOR

CALCULATIONS PURPOSES. EXISTING SHORT CIRCUIT

VALUES WILL BE USED OUTSIDE THE WORK AREA, FOR

THE STARTING POINT OF THE CALCULATIONS.

METHOD OF SHORT CIRCUIT

CURRENT CALCULATIONS

USING OHM'S LAW AND THE KNOWN RESISTIVITY

CONSTANT OF CONDUCTOR METAL (CIRCULAR MIL-OHM

PER FOOT) FOR COPPER CONDUCTORS, OUR INTENT IS

TO CALCULATE THE REQUIRED WIRE SIZE NECESSARY SO

AS NOT TO EXCEED THE RECOMMENDED VOLTAGE DROP

OF 3% FOR BRANCH CIRCUIT CONDUCTORS.

METHOD OF VOLTAGE DROP

CALCULATIONS

LIGHT FIXTURE SCHEDULE

SYMBOL LABEL

TYPE OF

LAMP

BALLAST/

DRIVER

WATTS/

FIXTURE

VOLTAGE DESCRIPTION

BASIS OF DESIGN

MANUFACTURER/CATALOG NUMBER

NOTES:

1. MANUFACTURER AND CATALOG NUMBERS SHOWN ARE FOR BASIS OF DESIGN, DESCRIPTIVE AND QUALITY STANDARDS ONLY, NOT TO BE USED FOR ORDERING WITHOUT VERIFICATION AND

APPROVAL. CONTRACTOR TO PROVIDE PRODUCT OR EQUAL FOR APPROVAL BY OWNER, ARCHITECT AND ENGINEER. ENGINEER SHALL NOT BE RESPONSIBLE FOR MISMATCHED OR INACCURATE

PART NUMBERS.

2. EM - SWITCHED EMERGENCY LIGHT (CIRCUITED FROM NORMAL AND EMERGENCY BACK-UP POWER)

EM NL - UN-SWITCHED EMERGENCY LIGHT (CIRCUITED FROM EMERGENCY POWER)

NL - NIGHT LIGHT

EX - EXISTING TO REMAIN

R - RELOCATED

3. VERIFY ALL LIGHT FIXTURE MOUNTING TYPES AND COLORS WITH ARCHITECT.

4. ALL FLUORESCENT LIGHT FIXTURES MUST HAVE INDIVIDUAL DISCONNECTING MEANS LOCATED AT EACH FIXTURE.

5. FOR ALL LED LIGHT FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC

PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT

BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTRLLED STATE AUTOMATICALLY. PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.

EB 1.5

EMERGENCY DOUBLE HEAD LIGHT FIXTURE WITH BATTERY

BACKUP

LITHONIA MODEL#

ELM2

OR APPROVED EQUIVALENT

E1 LED 3.3

LED EMERGENCY EXIT SIGN WITH DIRECTIONAL INDICATOR AND

BATTERY BACKUP

LITHONIA MODEL#

EXR LED EL M6

OR APPROVED EQUIVALENT

A

M

ELECTRICAL SYMBOL LEGEND

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of

Construction and Facilities

Management

PROJECT MANAGER:

ACG Project Number

Revisions: Date

CONSULTANTS:

REPLACE CHILLERS,

PHASE II

630-16-101

NEW YORK HARBOR HEALTHCARE

SYSTEM

423 EAST 23RD STREET,NEW YORK, NY

17-054

CONTRACT DOCUMENTS

FULLY SPRINKLERED

12/20/2019 10CARDAS

4#

E-001

ELECTRICAL SYMBOLS, GENERAL NOTES

AND ABBREVIATIONS

DocuSign Envelope ID: DDA8ACE4-4A59-45AB-B19C-E9B7A0DD6973

12/20/2019

24 26 28 30 32

24 26 28 30

GG

FF

HH

JJ

LL

2312 14 16 18 20 22

EE

FF

HH

JJ

LL

21 22.5

I-1

K-1

K-2

J-1

J-2

J-1

J-2

K-1

K-2

CONTROL

ROOM

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

AB

AA

AC

AY

AX

AW

AH(1)

AM(2)

AU

MCC 1

MCC 2MCC 3

M

BG

AG(1)

AF(1)

AE(1)

AD(1)

AJ(1)

AI(1)

AL(2)

AK(2)

AT

AR

AS

AV

SEE DETAIL

2/ED101

BKR FRONT

PCD

(TYP)

1 1

XFMR

4160/480-277V

3000KVA

METERING

MAIN

4000 AF

SPACE

SPARE

800 AF

MCC 2

800 AF

DIST BD

DPD

2000 AF

MCC 3

800 AF

MCC 1

800 AF

ATS #8

1600 AF

0 4 8 16

NORTH

PLAN

Scale: 1/8" = 1'-0"

FIRST FLOOR DEMO PLAN

1. FOR GENERAL NOTES, SYMBOLS AND

ABBREVIATIONS, SEE DRAWING E-001.

2. FOR LOCATION OF NEW CHILLER AND VFD,

SEE MECHANICAL DRAWINGS.

3. KEEP CHILLER PLANT CLEAN AND FREE OF

DEBRIS DURING DEMO AND CONSTRUCTION.

REMOVE DEMO AND CONSTRUCTION DEBRIS

DAILY.

4. LETTER CODES WITHIN TRIANGLES BY

DASHED MOTOR SYMBOLS ARE DEFINED ON

DRAWING E-601.

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of

Construction and Facilities

Management

PROJECT MANAGER:

ACG Project Number

Revisions: Date

CONSULTANTS:

REPLACE CHILLERS,

PHASE II

630-16-101

NEW YORK HARBOR HEALTHCARE

SYSTEM

423 EAST 23RD STREET,NEW YORK, NY

17-054

CONTRACT DOCUMENTS

FULLY SPRINKLERED

12/20/2019 10CARDAS

4#

ED101

ELECTRICAL AND CHILLER ROOM

DEMOLITION

1. DISCONNECT MOTORS. REMOVE WIRE AND

CONDUIT BACK TO MCC/SPARE STARTERS.

DISPOSE OF WIRE AND CONDUIT. SEE E-601

FOR MOTOR POWER SOURCE.

2. MCC3 IS TO REMAIN AND THE EC IS TO MARK

DISCONNECTED MOTOR STARTERS AS SPARE.

3. MCC1 AND MCC2'S ASSOCIATED ELETRICAL

FEEDER CONDUIT AND WIRE WILL BE

REMOVED BACK TO PCD. THEIR ASSOCIATED

BREAKERS WILL BE TEMPORARILY MARKED

AS SPARE. AFTER MOTORS ARE

DISCONNECTED, MCC1 AND MCC2 WILL ALSO

BE REMOVED.

Scale: NTS

FIRST FLOOR DEMO PLAN ELEVATION (BREAKER FRONT) OF PCD

DASHED LINES INDICATE DEMO AREA

SHEET KEYNOTES:

K-1D

K-2C

J-1C

CONTROL

ROOM

CCU1 CCU2 CCU3

SEE DETAIL

3/E101

MCC 3 MCC 2

MCC 1

BKR FRONT

PCD

CONTROL

ROOM

K-1D

CHILLER 1

J-1C

CHILLER 2 CHILLER 3

CHILLER 4

K-2C

SEE DETAIL

4/E101

CHILLED WATER

PUMP SKID

CD-3BCD-2BCD-1B

EXISTING

MCC 3

BKR FRONT

NIC

SSF-1

CONDENSED WATER

PUMP SKID

E1

EB

EB

MCC 2

800 AF

MCC 1

800 AF

PUMP

SKID #2

800 AF

PUMP

SKID #1

800 AF

0 4 8 16

NORTH

PLAN

Scale: 1/8" = 1'-0"

DEMO FIRST FLOOR POWER PLAN

0 4 8 16

NORTH

PLAN

Scale: 1/8" = 1'-0"

NEW WORK FIRST FLOOR POWER PLAN

FIRST FLOOR POWER PLAN:

1. EXISTING 3" RGS CONDUIT RUNS FROM

SWITCHGEAR SECTION K-1D, K-2C, J-1C TO

AMPGARD STARTER. REMOVE EXISTING

3-1/C#1+1#1 GROUND CABLE.

2. REMOVE AND DISPOSE OF EXISTING AMPGARD

MCC STARTER TRANSFORMER. VERIFY IF

EXISTING MCC CONTAINS PCB. IF PCB'S ARE

PRESENT, DISPOSE OF ACCORDING TO LAW.

3. REMOVE AND DISPOSE EXISTING POWER AND

CONTROL CONDUIT WIREWAY AND WIRING.

4. EXISTING JUNCTION BOX ON CHILLER SHALL BE

REMOVED AND DISPOSED.

5. DEMO FEEDER RACEWAYS AND CONDUCTORS

FOR PUMPS BACK TO MCC #1 & #2. SEE ED101

6. REMOVE MCC 1 AND MCC 2. SEE ED101.

7. MCC 3 TO REMAIN IN PLACE

8. 800 AF CIRCUIT BREAKERS TO BE REUSED.

REMOVE OLD NAME PLATES AND REPLACE WITH

NEW PLATES.

FIRST FLOOR POWER PLAN:

1. FURNISH AND INSTALL 3# 5KV #2 CABLES WITH 1 #6

BARE GROUND IN 3" RGS CONDUIT.

2. FURNISH AND INSTALL 1-RGS CONDUIT WITH 2-2 #16

SHIELDED TWISTED PAIR CABLE.

3. NEW VARIABLE SPEED DRIVE FURNISHED WITH

CHILLER.

4. NEW CHILLER.

5. FURNISH AND INSTALL 3-3/4" RGS. CONDUIT FILLS

SHOWN ON E102, E103 AND E104.

6. CH-4 IS EXISTING WITH EXISTING CONDUITS AND

FILLS.

7. SEE DWG E-601 FOR CIRCUIT BREAKER,

CONDUCTOR AND CONDUIT SIZES.

8. FOR AIR CIRCUIT BREAKER PRODUCT INFORMATION

CONSIDER SQUARE D MODEL D52065 800 AF.

9. PROVIDE 3/4" RGS CONDUIT WITH 8 COND #16.

10. REMOVE OLD NAMEPLATE, REPLACE WITH NEW

PLATES DUPLICATING CHILLER NUMBERS.

11. SINGLE PHASE 120 VOLT CONTROL CIRCUIT FROM

PUMP PANEL TO DDC PANEL.

12. TIE 120V WP/GFCI RECEPTACLE TO NEAREST

EXISTING RECEPTACLE.

13. TIE INTO EXISTING LIGHTING CIRCUIT.

1. FOR GENERAL NOTES, SYMBOLS AND

ABBREVIATIONS, SEE DRAWING E-001.

2. FOR LOCATION OF NEW CHILLER AND VFD,

SEE MECHANICAL DRAWINGS.

3. KEEP CHILLER PLANT CLEAN AND FREE OF

DEBRIS DURING DEMO AND CONSTRUCTION.

CONTRACTOR TO REMOVE DEMO AND

CONSTRUCTION DEBRIS DAILY.

4. NEW OVERHEAD ELECTRICAL CONDUIT MUST

BE RIGHT TO THE CEILING OR AT MINIMUM OF

8 FEET+ ABOVE THE FINISHED FLOOR.

4 4 4

2 2

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of

Construction and Facilities

Management

PROJECT MANAGER:

ACG Project Number

Revisions: Date

CONSULTANTS:

REPLACE CHILLERS,

PHASE II

630-16-101

NEW YORK HARBOR HEALTHCARE

SYSTEM

423 EAST 23RD STREET,NEW YORK, NY

17-054

CONTRACT DOCUMENTS

FULLY SPRINKLERED

12/20/2019 10CARDAS

4#

E-101

ELECTRICAL AND CHILLER ROOM

DEMOLITION AND NEW WORK

EXISTING CONDUIT

Scale: NTS

EXISTING FIRST FLOOR DEMO PLAN ELEVATION

(BREAKER FRONT) OF PCD, REMOVE OLD NAME

PLATES

Scale: NTS

EXISTING FIRST FLOOR POWER PLAN ELEVATION

(BREAKER FRONT) OF PCD, ADD NEW NAME

PLATES

NEW WORK KEYNOTES:

DEMO SHEET KEYNOTES:

12 12 12

M

J

M

50 67

5IN

800/5

SECTION K-2A

SECTION K-2B

13.2KV/4.16V

2500KVA

TRANSFORMER K-2

SWITCHGEAR K-2

SWITCHGEAR K-2

SWITCHGEAR PC-1A

PULLBOX-I

CABLE MANHOLE

13.2KV CON-ED

FEEDERS. 3ɸ, 3W

208V/3PH

SWITCHBOARD SS-1A

M

5IN

3"C, RGS

PROVIDE 3-1/C#2 WITH #6 BARE CU

IN NEW CONDUIT

3/4" RGS C, 3/C#18 SHLD

W/DRAIN WIRE

CONTROL

ROOM

CHILLER 2

3/4" RGS C, 3#10+1#10G

OIL

HEATER

OIL

PUMP

CHILLER

MOTOR

3" RGS C,

3#1/C+1#1G

4160V

VARIABLE

SPEED DRIVE

(VFD)

3/4" RGS C, 2#12+1#12G

15KV, 3-1/C#2/0

150/5

SECTION K-2C

50 51

5IN

SECTION K-2D

SPACE

ONLY

4160V/3PH

200/5

1000/1500KVA

3PH

3/4"C, 2-2#16 SHIELDED

TWISTED PAIR

50 67

5IN

800/5

SECTION K-2A

SECTION K-2B

2500KVA

TRANSFORMER K-2

SWITCHGEAR K-2

SWITCHGEAR K-2

SWITCHGEAR PC-1A

PULLBOX-I

CABLE MANHOLE

13.2KV CON-ED

FEEDERS. 3ɸ, 3W

208V/3PH

SWITCHBOARD SS-1A

5IN

15KV, 3-1/C#2/0

150/5

SECTION K-2C

50 51

5IN

SECTION K-2D

SPACE

ONLY

4160V/3PH

200/5

1000/1500KVA

3PH

3"C, RGS

REMOVE EXISTING 3-1/C#1 WITH #1G

CABLE

4160V AMPGARD

MCC STARTER

CCU2

4.16KV-208Y/120V

A

M

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of

Construction and Facilities

Management

PROJECT MANAGER:

ACG Project Number

Revisions: Date

CONSULTANTS:

REPLACE CHILLERS,

PHASE II

630-16-101

NEW YORK HARBOR HEALTHCARE

SYSTEM

423 EAST 23RD STREET,NEW YORK, NY

17-054

CONTRACT DOCUMENTS

FULLY SPRINKLERED

12/20/2019 10CARDAS

4#

E-102

KEY NOTES:

1. REMOVE EXISTING 3" RIGID STEEL CONDUIT

WHICH CONTAINS 3-1/C#1 TYPE XLPE CABLES

WITH LEAD SHEATH AND #1 GROUND WIRE.

REMOVE AND DISPOSE EXISTING CABLE FROM

THE SWITCHGEAR SECTION K-2C TO THE

EXISTING AMPGARD STARTER.

2. REMOVE AND DISPOSE EXISTING AMPGARD

STARTER.

3. PROVIDE SHIELDED 3-1/C#2 CABLES WITH A #6

BARE CU GROUND IN NEW RGS CONDUIT.

4. ELECTRICALLY INSTALL VARIABLE SPEED DRIVE

(FURNISHED WITH CHILLER) AS PER

MANUFACTURERS RECOMMENDATIONS. SEE

MECHANICAL DRAWINGS.

5. ELECTRICALLY INSTALL CHILLER AS PER

MANUFACTURERS RECOMMENDATIONS. SEE

MECHANICAL DRAWINGS.

6. ELECTRICALLY INSTALL CHILLER CONTROL

PANEL AS FURNISHED BY CHILLER

MANUFACTURER AS PART OF CHILLER PACKAGE.

7. PROVIDE MOD-BUS COMMUNICATION CABLE

RUNS FROM VARIABLE SPEED DRIVE TO THE

CHILLER CONTROL PANEL.

8. ADJUST SWITCHGEAR SETTINGS TO MATCH FULL

LOAD AMPS FROM NAMEPLATE DATA OF CHILLER

2.

1. FOR GENERAL NOTES, SYMBOLS AND

ABBREVIATIONS, SEE DRAWING E-001.

2. KEEP CHILLER PLANT CLEAN AND FREE OF

DEBRIS DURING DEMO AND CONSTRUCTION.

REMOVE DEMO AND CONSTRUCTION DEBRIS

DAILY.

3. ENGAGE AUTHORIZED VAMC CONTRACTOR:

CRASCO INC., (PHONE:(703) 643-2952,

CONTACT NAME: JOHN CICCONE) AND MAKE

CONNECTIONS, AND COMPLETE THE

TERMINATIONS. AND PROGRAM THE CONTROL

ROOM EQUIPMENT.

4. COORDINATE ROUTING AND SUPPORT OF ALL

CONDUITS WITH EXISTING AND NEWLY

INSTALLED PIPING AND OTHER OVERHEAD

INTERFERENCES.

5. NEW OVERHEAD ELECTRICAL CONDUIT MUST

BE RIGHT TO THE CEILING OR AT MINIMUM OF

8 FEET+ ABOVE THE FINISHED FLOOR.

Scale: NTS

DEMO CONTROL/POWER WIRING

Scale: NTS

NEW CONTROL/POWER WIRING

CHILLER CH-2 POWER AND CONTROL

WIRING

SHEET KEYNOTES:

M

50 67

5IN

800/5

50 27

13.2KV/4.16V

2500KVA

TRANSFORMER K-1

SWITCHGEAR K-1

SWITCHGEAR I-1

SWITCHGEAR PC-1B

PULLBOX-I

CABLE MANHOLE

13.2KV CON-ED

FEEDERS. 3ɸ, 3W

208V/3PH

SWITCHBOARD SS-1A

M

5IN

3"C, RGS

PROVIDE 3-1/C#2 WITH #6 BARE CU

IN NEW CONDUIT

3/4" RGS C, 3/C#18 SHLD

W/DRAIN WIRE

CONTROL

ROOM

CHILLER 1

3/4" RGS C, 3#10+1#10G

OIL

HEATER

OIL

PUMP

CHILLER

MOTOR

3" RGS C,

3#1/C+1#1G

4160V

VARIABLE

SPEED DRIVE

(VFD)

3/4" RGS C, 2#12+1#12G

15KV, 3-1/C#2/0

150/5

SPACE

ONLY

4160V/3PH

1000/1500KVA

3PH

3/4"C, 2-2#16 SHIELDED

TWISTED PAIR

13.2KV/4.16V

2500KVA

TRANSFORMER K-1

SWITCHGEAR K-1

SWITCHGEAR K-1

SWITCHGEAR PC-1B

PULLBOX-I

CABLE MANHOLE

13.2KV CON-ED

FEEDERS. 3ɸ, 3W

208V/3PH

SWITCHBOARD SS-1B

15KV, 3-1/C#2/0

1000/1500KVA

3PH

3"C, RGS

REMOVE EXISTING 3-1/C#1 WITH #1G

CABLE

4160V AMPGARD

MCC STARTER

SECTION K-1D

50 51

5IN

200/5

EXISTING EMPTY

CONDUIT

EXISTING EMPTY

CONDUIT

50 67

5IN

800/5

SECTION K-1X

SECTION K-1X

5IN

150/5

SECTION K-1X

SPACE

ONLY

4160V/3PH

200/5

SECTION K-1D

50 51

5IN

CCU1

SECTION K-1X SECTION K-1X SECTION K-1X

A

M

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of

Construction and Facilities

Management

PROJECT MANAGER:

ACG Project Number

Revisions: Date

CONSULTANTS:

REPLACE CHILLERS,

PHASE II

630-16-101

NEW YORK HARBOR HEALTHCARE

SYSTEM

423 EAST 23RD STREET,NEW YORK, NY

17-054

CONTRACT DOCUMENTS

FULLY SPRINKLERED

12/20/2019 10CARDAS

4#

E-103

KEY NOTES:

1. REMOVE EXISTING 3" RIGID STEEL CONDUIT

WHICH CONTAINS 3-1/C#1 TYPE XLPE CABLES

WITH LEAD SHEATH AND #1 GROUND WIRE.

REMOVE AND DISPOSE EXISTING CABLE FROM

THE SWITCHGEAR SECTION K-1D TO THE

EXISTING AMPGARD STARTER.

2. REMOVE AND DISPOSE EXISTING AMPGARD

STARTER.

3. PROVIDE SHIELDED 3-1/C#2 CABLES WITH #6

BARE CU GROUND IN NEW RGS CONDUIT.

4. ELECTRICALLY INSTALL VARIABLE SPEED DRIVE

(FURNISHED WITH CHILLER) AS PER

MANUFACTURERS RECOMMENDATIONS. SEE

MECHANICAL DRAWINGS.

5. ELECTRICALLY INSTALL CHILLER AS PER

MANUFACTURERS RECOMMENDATIONS. SEE

MECHANICAL DRAWINGS.

6. ELECTRICALLY INSTALL CHILLER CONTROL

PANEL AS FURNISHED BY CHILLER

MANUFACTURER AS PART OF CHILLER PACKAGE.

7. PROVIDE CABLE RUNS FROM VARIABLE SPEED

DRIVE TO THE CHILLER CONTROL PANEL.

8. ADJUST SWITCHGEAR SETTINGS TO MATCH FULL

LOAD AMPS FROM NAMEPLATE DATA OF CHILLER

1.

1. FOR GENERAL NOTES, SYMBOLS AND

ABBREVIATIONS, SEE DRAWING E-001.

2. KEEP THE CHILLER PLANT CLEAN AND FREE

OF DEBRIS DURING DEMO AND

CONSTRUCTION. REMOVE DEMO AND

CONSTRUCTION DEBRIS DAILY.

3. ENGAGE AUTHORIZED VAMC CONTRACTOR:

CRASCO INC., (PHONE:(703) 643-2952,

CONTACT NAME: JOHN CICCONE) MAKE

CONNECTIONS, COMPLETE THE

TERMINATIONS. AND PROGRAM THE CONTROL

ROOM EQUIPMENT.

4. COORDINATE ROUTING AND SUPPORT OF ALL

CONDUITS WITH EXISTING AND NEWLY

INSTALLED PIPING AND OTHER OVERHEAD

INTERFERENCES.

5. NEW OVERHEAD ELECTRICAL CONDUIT MUST

BE RIGHT TO THE CEILING OR AT MINIMUM OF

8 FEET+ ABOVE THE FINISHED FLOOR.

Scale: NTS

Scale: NTS

DEMO CONTROL/POWER WIRING

NEW CONTROL/POWER WIRING

CHILLER CH-1 POWER AND CONTROL

WIRING

SHEET KEYNOTES:

M

50 67

5IN

800/5

SECTION J-1A

SECTION J-1B

13.2KV/4.16V

2500KVA

TRANSFORMER J-1

SWITCHGEAR J-1

SWITCHGEAR J-1

OUTDOOR

SWITCHGEAR

PULLBOX-I

CABLE MANHOLE

13.2KV CON-ED

FEEDERS. 3ɸ, 3W

208V/3PH

STAFF RESIDENCE

SWITCHBOARD

M

5IN

3"C, RGS

PROVIDE 3-1/C#2 WITH #6 BARE CU

IN NEW CONDUIT

3/4" RGS C, 3/C#18 SHLD

W/DRAIN WIRE

CONTROL

ROOM

CHILLER 3

3/4" RGS C, 3#10+1#10G

OIL

HEATER

OIL

PUMP

CHILLER

MOTOR

3" RGS C,

3#1/C+1#1G

4160V

VARIABLE

SPEED DRIVE

(VFD)

3/4" RGS C, 2#12+1#12G

15KV, 3-1/C#2/0

150/5

SECTION J-1C

50 51

5IN

SECTION J-1D

SPACE

ONLY

4160V/3PH

200/5

1000/1500KVA

3PH

3/4"C, 2-2#16 SHIELDED

TWISTED PAIR

50 67

5IN

800/5

SECTION J-1A

13.2KV/4.16V

2500KVA

TRANSFORMER J-1

SWITCHGEAR J-1

SWITCHGEAR J-1

OUTDOOR

SWITCHGEAR

PULLBOX-I

CABLE MANHOLE

13.2KV CON-ED

FEEDERS. 3ɸ, 3W

208V/3PH

STAFF RESIDENCE

SWITCHBOARD

15KV, 3-1/C#2/0

SECTION J-1C

50 51

5IN

4160V/3PH

200/5

1000/1500KVA

3PH

3"C, RGS

REMOVE EXISTING 3-1/C#1 WITH #1G

CABLE

4160V AMPGARD

MCC STARTER

SECTION J-1B

5IN

150/5

SECTION J-1D

SPACE

ONLY

4160V/3PH

EXISTING EMPTY

CONDUIT

CCU3

A

M

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of

Construction and Facilities

Management

PROJECT MANAGER:

ACG Project Number

Revisions: Date

CONSULTANTS:

REPLACE CHILLERS,

PHASE II

630-16-101

NEW YORK HARBOR HEALTHCARE

SYSTEM

423 EAST 23RD STREET,NEW YORK, NY

17-054

CONTRACT DOCUMENTS

FULLY SPRINKLERED

12/20/2019 10CARDAS

4#

E-104

KEY NOTES:

1. REMOVE EXISTING 3" RIGID STEEL CONDUIT

WHICH CONTAINS 3-1/C#1 TYPE XLPE CABLES

WITH LEAD SHEATH AND #1 GROUND WIRE.

REMOVE AND DISPOSE EXISTING CABLE FROM

THE SWITCHGEAR SECTION J-1C TO THE

EXISTING AMPGARD STARTER.

2. REMOVE AND DISPOSE EXISTING AMPGARD

STARTER.

3. PROVIDE NEW SHIELDED 3-1/C#2 CABLES WITH

#6 BARE CU GROUND IN NEW RGS CONDUIT.

4. ELECTRICALLY INSTALL VARIABLE SPEED DRIVE

(FURNISHED WITH CHILLER) AS PER

MANUFACTURERS RECOMMENDATIONS. SEE

MECHANICAL DRAWINGS.

5. ELECTRICALLY INSTALL CHILLER AS PER

MANUFACTURERS RECOMMENDATIONS. SEE

MECHANICAL DRAWINGS.

6. ELECTRICALLY INSTALL CHILLER CONTROL

PANEL AS FURNISHED BY CHILLER

MANUFACTURER AS PART OF CHILLER PACKAGE.

7. PROVIDE MOD-BUS COMMUNICATION CABLE

RUNS FROM VARIABLE SPEED DRIVE TO THE

CHILLER CONTROL PANEL.

8. ADJUST SWITCHGEAR SETTINGS TO MATCH NEW

FULL LOAD AMPS OF CHILLER 3.

1. FOR GENERAL NOTES, SYMBOLS AND

ABBREVIATIONS, SEE DRAWING E-001.

2. KEEP THE CHILLER PLANT CLEAN AND FREE

OF DEBRIS DURING DEMO AND

CONSTRUCTION. REMOVE DEMO AND

CONSTRUCTION DEBRIS DAILY.

3. CONTRACTOR SHALL ENGAGE AUTHORIZED

VAMC CONTRACTOR:

CRASCO INC., (PHONE:(703) 643-2952,

CONTACT NAME: JOHN CICCONE) MAKE

CONNECTIONS, COMPLETE THE

TERMINATIONS. AND PROGRAM THE CONTROL

ROOM EQUIPMENT.

4. COORDINATE ROUTING AND SUPPORT OF ALL

CONDUITS WITH EXISTING AND NEWLY

INSTALLED PIPING AND OTHER OVERHEAD

INTERFERENCES.

5. NEW OVERHEAD ELECTRICAL CONDUIT MUST

BE RIGHT TO THE CEILING OR AT MINIMUM OF

8 FEET+ ABOVE THE FINISHED FLOOR.

Scale: NTS

Scale: NTS

CHILLER CH-3 POWER AND CONTROL

WIRING

DEMO CONTROL/POWER WIRING

NEW CONTROL/POWER WIRING

SHEET KEYNOTES:

1. WALL ASSEMBLY - MIN 4-7/8 IN. AND 6-1/8 IN. THICK NORMAL WEIGHT OR LIGHTWEIGHT (100-150 PCF)

CONCRETE FOR 1 AND 2 HR RATED ASSEMBLIES, RESPECTIVELY. WALL MAY ALSO BE CONSTRUCTED OF

ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF OPENING IS 14-1/8 IN.

SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF

MANUFACTURERS.

THE F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE HOURLY FIRE RATING OF THE WALL

ASSEMBLY IN WHICH IT IS INSTALLED.

2. THROUGH PENETRANTS - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER

CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN

PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING SHALL BE MIN 0 IN. TO MAX 1-3/8 IN. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING

TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:

A. STEEL PIPE- THE FOLLOWING TYPES AND SIZES OF STEEL PIPES MAY BE USED:

1A. NOM 4 IN. DIAM (OR SMALLER) SCHEDULE 7 (OR HEAVIER) STEEL PIPE.

2A. NOM 8 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

3A. NOM 10 IN. DIAM (OR SMALLER) SCHEDULE 20 (OR HEAVIER) STEEL PIPE.

WHEN STEEL PIPE IS USED, T RATING IS 1/4 HR FOR NOM 4 IN. DIAM (OR SMALLER) AND 0 HR FOR STEEL

PIPES GREATER THAN NOM 4 IN. DIAM.

B. IRON PIPE - NOM 4 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE. WHEN IRON PIPE IS USED T

RATING IS 1/4 HR.

C. CONDUIT - NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING (EMT) OR STEEL

CONDUIT. WHEN EMT OR STEEL CONDUIT IS USED T RATING IS 1/4 HR.

D. COPPER TUBING - NOM 4 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING WHEN

COPPER TUBE IS USED T RATING IS 0 HR.

E. COPPER PIPE - NOM 4 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE. WHEN COPPER

PIPE IS USED T RATING IS 0 HR.

3. FILL, VOID OR CAVITY MATERIAL - SEALANT - MIN 5/8 IN. AND 1-1/4 IN. THICKNESS OF FILL MATERIAL

FOR 1 AND 2 HR RATED WALL ASSEMBLIES, RESPECTIVELY, APPLIED WITHIN THE ANNULUS, FLUSH WITH

BOTH SURFACE OF WALL. AT POINT CONTACT LOCATION BETWEEN PENETRANT AND PERIPHERY OF

OPENING, A MIN 1/2 IN. DIAM BEAD OF FILL MATERIAL SHALL BE INSTALLED AT THE

CONCRETE/PENETRANT INTERFACE ON BOTH SURFACES OF WALL.

PASSIVE FIRE PROTECTION PARTNERS - 4800DW

*BEARING THE UL CLASSIFICATION MARK

A

M

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of

Construction and Facilities

Management

PROJECT MANAGER:

ACG Project Number

Revisions: Date

CONSULTANTS:

REPLACE CHILLERS,

PHASE II

630-16-101

NEW YORK HARBOR HEALTHCARE

SYSTEM

423 EAST 23RD STREET,NEW YORK, NY

17-054

CONTRACT DOCUMENTS

FULLY SPRINKLERED

12/20/2019 10CARDAS

4#

E-501

ELECTRICAL DETAILS

Scale: NTS

W-J-1040 UL DETAIL

AH AE AF AG AO AI AJ AN AD

MCC1

AK AL AM AP AQ

SPACE

CW

PUMP

SKID

1 1 11 1 1 1 1 1 1 1

2 2

2-3.5" RGS CONDUITS WITH 3# 600KCML

AND 1 #1 GND IN EACH CONDUIT

2-3.5" RGS CONDUITS WITH 3# 600KCML

AND 1 #1 GND IN EACH CONDUIT

SPARE

REMAINS

REMOVE

MCC2 MCC3

M M M M M M M M M

800A

M M M M M

800A 800A 800A 1600A

7 8 1 2 3 4 5 6

4000A

M M M M M

AE AE

M

BC

M

BE

M

BF

M

M M

MCC-3

MCC-2

MCC-1

EMERGENCY PANEL IN

EXISTING CHILLER PLANT

ROOM

AP-

EM-

EXISTING

MCC

4#6 & 1#8G - 1 1/4" C

PC-D-1

PC-D-2

PC-D-3

MCC-1 MCC-2 MCC-3

POWER CENTER SECONDARY GEAR SCHEDULE

POWER CENTER SECONDARY GEAR SCHEDULE POWER CENTER SECONDARY GEAR SCHEDULE

D E

S I G

N A

T I O

N P

C C

P C

B

P C

A

CIRC.

NO.-

MAIN DEVICE

DEVICE

SIZE

POLES

"N"-NEUT.

BAR

CONN.

OVER-

CUR-

RENT

SIZE

FEEDER

CONTROLLED

DEVICE TYPE

CIRC.

NO.-

MAIN DEVICE

DEVICE

SIZE

POLES

"N"-NEUT.

BAR

CONN.

OVER-

CUR-

RENT

SIZE

FEEDER

CONTROLLED

DEVICE TYPE

1 4000 3+N 4000 PC-A-1

1 4000 3+N 4000 PC-B-1

1 4000 3+N 4000 PC-C-1

DRAWOUT AIR FRAME

DRAWOUT AIR FRAME

DRAWOUT AIR FRAME

1 800 3 800 PC-D-1 DRAWOUT AIR FRAME

2 800 3 800 PC-D-2

3 800 3+N 800 PC-D-3

4 100 3+N - SPARE

5 800 3+N 800 PC-D-5

6 2000 3+N 600 PC-D-6

7 400 3 - SPARE

8 400 3 - SPARE

9 4000 3+N 4000 SPARE DRAWOUT AIR FRAME

W/GND. CURRENT TRIP.

P-3

CHW

PUMP

SKID

1 1 1

A

M

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of

Construction and Facilities

Management

PROJECT MANAGER:

ACG Project Number

Revisions: Date

CONSULTANTS:

REPLACE CHILLERS,

PHASE II

630-16-101

NEW YORK HARBOR HEALTHCARE

SYSTEM

423 EAST 23RD STREET,NEW YORK, NY

17-054

CONTRACT DOCUMENTS

FULLY SPRINKLERED

12/20/2019 10CARDAS

4#

E-601

ELECTRICAL SINGLE LINE

KEY NOTES:

1. MOTOR TO BE REMOVED.

2. ELECTRICAL CONTRACTOR (EC) TO REUSE TWO

EXISTING DRAW OUT AIR BREAKER FRAME SIZE

800AMP 3 PHASE 480 VOLT. EC TO INSTALL WIRE

AND CONDUIT FROM EXISTING SWITCHGEAR /

800 AF CIRCUIT BREAKERS TO POWER

CONNECTION BOXES OF CW AND CHW PUMP

SKIDS AND TERMINATE.

1. DISCONNECT MOTORS. REMOVE WIRE AND

CONDUIT BACK TO MOTOR CONTROLLER.

CONTRACTOR TO DISPOSE OF WIRE AND

CONDUIT.

2. KEEP THE CHILLER PLANT CLEAN AND FREE

OF DEBRIS DURING DEMO AND

CONSTRUCTION. REMOVE DEMO AND

CONSTRUCTION DEBRIS DAILY.

Scale: NTS

ELECTRICAL SINGLE LINE

SHEET KEYNOTES:

CCU-3

CCU-4

NEW

CHILLER

CCU-2 CCU-1

NEW

CHILLER

NEW

CHILLER

CW

PUMP

SKID

CHW

PUMP

SKID

EXISTING

CHILLER

REMAINS

VFD VFD

800AT

800AF

600AT

800AF

MCC 1

MCC 2

MCC 3

PULLBOX-I

Y

PHASING RECEPTACLE

WITH P.T.

NEON TUBE

C.T.

KEY INTERLOCK

13.2 KV CON ED

FEEDERS 3Ph, 3W

EQUIPPED

SPACE

ONLY

I-1A

K

Y

K

Y

K

Y

K

Y

K

TRANSFORMER I-1

TRANSFORMER J-1

TRANSFORMER J-2

TRANSFORMER K-1

TRANSFORMER K-2

LOAD BUS I-1

I-1B I-1C I-1D

J-1A

J-1B

J-1C J-1D

J-2A

J-2B J-2C

J-2D

K-1A K-1B K-1C K-1D

K-2A K-2B K-2C K-2D

EQUIPPED

SPACE

ONLY

EQUIPPED

SPACE

ONLY

EQUIPPED

SPACE

ONLY

EQUIPPED

SPACE

ONLY

I-1

J-1

J-2

K-1

PULLBOX-J

PULLBOX-K

K-2

(2) 13.2 KV CON ED

FEEDERS 3Ph, 3W

(2) 13.2 KV CON ED

FEEDERS 3Ph, 3W

PROPERTY LINE

MANHOLE

(TYPICAL)

LOAD BUS J-1

LOAD BUS J-2

LOAD BUS K-1

LOAD BUS K-2

EMPTY CONDUIT FOR

FUTURE BUILDING

5KV UNFUSED

ISOLATING SWITCH

4000A 4000A 4000A

POWER CENTER BRACED FOR

50,000 A. RMS SYM. MINIMUM.

149,600A RMS

SYM. (TYPICAL)

EXISTING 180/208V

SWITCHGEAR (FOR

STAFF RESIDENCE

DISCONNECT & REMOVE

EXIST CABLES TO

MAN HOLE

OUTDOOR, PAD MTD

5KV-208/120V, 300KVA

TRANSF. 3 PHASE

5KV DISCONNECT SW.

ABANDON EXIST. 180/208V

MANHOLE IN STREET.

POWER CENTER BRACED

FOR 42,500A RMS

SYM. MINIMUM.

32,400A RMS

SYM. TYPICAL

EMPTY CONDUIT FOR

FUTURE BUILDING FOR 480

VOLT POWER CENTERS.

4000A

MOTOR

CONTROLLER

MOTOR CONTROLLERS

EXISTING, TO

REMAIN CHILLER

CONTROLLER

4160KV - 480/277V

2000/3000KVA CAST COIL TRANSF.

PC-D

SS-A SS-B SS-C

EXISTING SWITCHBOARDS (208V)

PC-A

PC-B

PC-C

26,800A RMS

SYM. TYPICAL

4.16KV - 208/120V

1000/1500KVA(TYPICAL)

1000 TON

CHILLER

CHILLER

BY OTHERS PULLBOX A

SYN BUS

21,100A RMS SYM.

21,100A RMS SYM.

21,100A RMS SYM.

5KV SYN BUS SCHEME

NO SCALE

32,400A

RMS SYM

TP.

2500/3750 KVA

13.2 KV-4.16 KV

4.16 RELAYING SCHEME

NOTES

1. PROVIDE RELAYS SHOWN

TYPICALLY FOR EACH SYNC. BUS

C.B., LOAD BUS MAIN C.B., MOTOR

FEEDER C.B. AND POWER CENTER

C.B.

51N

MAIN INCOM, C/B

800/5

150/5

51N

MOTOR FEEDER C/B

POWER CENTER

FEEDER C/B

51N

SYN. BUS C/B

51N

POWER CENTER

200/5 FOR 1000KVA TRANSF.

400/5 FOR 2000KVA TRANSF.

HIGH VOLTAGE

CONTROLLER

1000 TON

CHILLER MOTOR

800/5

LOAD BUS

CURRENT

TRANSF.

RATION

CURRENT

TRANSFORMER

(TYPICAL)

IEEE RELAY

NUMBER

(TYPICAL)

SYBCHRONOUS BUS

200E FUSE TYPICAL

1000 KVA

TYPICAL

01.

02.

03.

04.

05.

06.

07.

08.

09.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

15 04

03 15 04

03 15

03 15

03 15

PULLBOX B

HEXAGON 17 HERE

PULLBOX FOR FUTURE

BUILDING (PHASE 1C)

36300A

RMS SYM

4000 A BUS

CONNECT NEW

WIRING TO CHILLER

REMOVE

A

M

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of

Construction and Facilities

Management

PROJECT MANAGER:

ACG Project Number

Revisions: Date

CONSULTANTS:

REPLACE CHILLERS,

PHASE II

630-16-101

NEW YORK HARBOR HEALTHCARE

SYSTEM

423 EAST 23RD STREET,NEW YORK, NY

17-054

CONTRACT DOCUMENTS

FULLY SPRINKLERED

12/20/2019 10CARDAS

4#

E-602

ELECTRICAL SINGLE LINE

Scale: NTS

ELECTRICAL SINGLE LINE

KEY NOTES:

1. SHORT CIRCUIT VALUES FOR OVER CURRENT

PROTECTIVE DEVICE COORDINATION STUDY TO

BE DETERMINED AT A LATER DATE BY

ELECTRICAL CONTRACTOR. FOR CONDUIT SIZE

AND FILL SEE E-601.

2. REPLACE CHILLER FEEDERS, VFD CONTROLLERS

TO CHILLER 1,2, AND 3 CCU-1, CCU-2 AND CCU-3.

3. EXISTING CHILLER #4 TO REMAIN CCU-4.

4. REMOVE MOTOR CONTROL CENTERS, MCC#2

AND MCC#3.

5. REUSE 800AF CIRCUIT BREAKER IN EXISTING

POWER CENTER "D" AND ADJUST TRIP TO 800

AMPS.

6. REUSE EXISTING 800AF CIRCUIT BREAKER AND

ADJUST TRIP TO 800A.

1. CONTRACTOR IS RESPONSIBLE FOR KEEPING

THE CHILLER PLANT CLEAN AND FREE OF

DEBRIS DURING DEMO AND CONSTRUCTION.

CONTRACTOR TO REMOVE DEMO AND

CONSTRUCTION DEBRIS DAILY.

LEGEND

EACH - CUSTOMERS PROPERTY LINE CABLE MANHOLE - 8'-6"X4'-6"X6'-0"

PRECAST TYPE IN ACCORADANCE WITH CON EDISON DWG. NO. 1632-B-REV 2.

EACH - 15KV, 3-1/2C, #2/0 FEEDERS WITH UNGROUNDED NEUTRAL, TYPE XLPE

WITH LEAD SHEATH, INSTALL IN 5" PVC CONDUIT WITH 2/0 GROUND WIRE.

CONDUIT ABOVE GRADE SHALL BE STEEL.

EACH - 15KV, PRIMARY METERING CUBICLE, AS PER CON EDISON

REQUIREMENTS. PROVIDE CTS, PTS, PHASING RECEPT, NEON TUBES ETC.

EACH - 15KV, 1000 MVA 1200 AMPERE, LOAD BREAK FUSED INTERRUPTER

SWITCH WITH KEY INTERLOCK, WITH GROUNDING SWITCH & FUSE

COMPARTMENT AS PER CON EDISON REQUIREMENTS.

EACH -- 13.2 KV/4.16, 2500 KVA/3650 KVA NETWORK TYPE DRY, CAST RESIN

TRANSFORMERS WITH FAN COOLING.

EACH -- 4.16 KV METAL CLAD SWITCHGEAR WITH DRAWOUT AIRFRAME CIRCUIT

BREAKER AND INCORPORATING THE FOLLOWING FEATURES:

A) EACH LOAD BUS CIRCUIT BREAKER CUBICLE SHALL BE EQUIPPED WITH

AN AMMETER AND A 4 POSITON SELECTOR SWITCH.

B) EACH LOAD BUS, MAIN INCOMING CIRCUIT BREAKER CUBICLE SHALL BE

EQUIPPED WITH A VOLT METER, A 4 POSITION SELECTOR SWITCH AND

REQUIRED POTENTIAL TRANSFORMERS.

C) EACH CIRCUIT BREAKER SHALL HAVE A CONTINUOUS CURRENT RATING

OF 1200 AMPERES AND A MINIMUM INTERRUPTING RATION OF 350 MVA.

4.16 METAL CLAD SWITCHGEAR, SYNCHRONOUS BUS WITH DRAWOUT CB, 1200

AMPERE, 350 MVA. EACH CB SHALL BE EQUIPPED WITH AN AMMETER AND A 4

POSITION SELECTOR SWITCH.

EACH, 2 SETS OF 3 - 250 MCM XLPE CABLES, LEAD SHEATHED WITH 2/0,

GROUND WIRE IN 4" RIGID STEEL CONDUIT.

EACH -- 15KV, 3-1/C, #2/0, TYPE XLPE CABLES WITH LEAD SHEATH INSTALLED IN

4" RIGID STEEL CONDUIT WITH 2/0 GROUND WIRE.

EACH -- 5KV, 3-1/C, #3/0, TYPE XLPE CABLES WITH LEAD SHEATH INSTALLED IN

3" RIGID STEEL CONDUIT - INCLUDE 2/0 GROUND WIRE.

EACH -- 5KV, 3-1/C, 500 MCM TYPE XLPE CABLES WITH LEAD SHEATH INSTALLED

IN 4" CONDUIT. INCLUDE 2/0 GROUND WIRE.

EACH -- 5KV, 3-1/C, #1 TYPE XLPE CABLES WITH LEAD SHEATH AND #1 GROUND

WIRE INSTALLED IN 3" RIGID STEEL CONDUIT.

5KV, 3-1/C, #4 TYPE XLPE CABLES WITH LEAD SHEATH AND #4 GROUND WIRE

INSTALLED IN 3" RIGID STEEL CONDUIT EXCEPT UNDERGROUND CONDUIT

SHALL BE PVC.

EACH -- 4" RIGID STEEL EMPTY CONDUIT.

EACH -- GROUNDING SWITCH.

EACH TYPICAL POT HEAD.

5KV FEEDER BY OTHER TO REMAIN.

SEE DETAIL SHEETS E102, E103, E104

CONDUIT AND CABLE BY OTHERS SHALL BE CUT BACK TO CEILING.

PULL BOX BY OTHERS TO REMAIN, SPLICE NEW 5KV CABLES, TO CABLES IN

PULL BOX.

EACH -- 5" PVC EMPTY CONDUIT FOR UNDERGROUND INSTALLATION. CONDUIT

ABOVE GRADE, SHALL BE STEEL.

8-500 MCM IN 2-4" CONCRETE ENCASED PVC CONDUIT UNDERGROUND & RIGID

STEEL WITHIN THE BUILDING.

EXISTING CT CABINET. REMOVE CT'S & UTILIZE CT CABINET AS JUNCTION BOX.

SHEET KEYNOTES:

(P1)(P5)(P1)(P5)

(P2)(P6)

(P3)(P7)

(P4)(P8)

800A

A

M

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of

Construction and Facilities

Management

PROJECT MANAGER:

ACG Project Number

Revisions: Date

CONSULTANTS:

REPLACE CHILLERS,

PHASE II

630-16-101

NEW YORK HARBOR HEALTHCARE

SYSTEM

423 EAST 23RD STREET,NEW YORK, NY

17-054

CONTRACT DOCUMENTS

FULLY SPRINKLERED

12/20/2019 10CARDAS

4#

E-603

ELECTRICAL SCHEMATIC & EQUIPMENT

SCHEDULE

Scale: NTS

ELECTRICAL SCHEMATIC TYPICAL NEW PUMP SKID

1. SEE TABLE 1 FOR PUMP HORSEPOWER AND FULL

LOAD AMPS (FLA).

2. REFER TO E-601.

SHEET KEYNOTES:

Scale: NTS

TABLE 1 ELECTRICAL EQUIPMENT SCHEDULE

Sheets and Views
E-001-E-001
ED101-ED101
E-101-E101
E-102-E-102
E-103-E-103
E-104-E-104
E-501-E-601
E-601 - NEW-E-601
E-602 - NEW-E-602
E-603-E-603
2019-12-20T06:41:59-0800
Digitally verifiable PDF exported from www.docusign.com

File details come from the government source that posted it. Updated .