S02 Elec CD Drawing.pdf
PDF 3 MB Posted
- Solicitation number
- 36C24226R0034
About this file
This document set comprises electrical construction drawings and specifications for the replacement of chillers at New York Harbor Healthcare System located at 423 East 23rd Street, New York, NY, as part of Phase II of a chiller replacement project (Project Number 630-16-101).
The project requires removal of existing electrical infrastructure including three AMPGARD Motor Control Centers (MCC1, MCC2, and MCC3), existing chiller feeders, and associated conduit and cabling, with specific emphasis on proper disposal procedures including verification and removal of any PCB-containing equipment. The contractor must install three new chillers (CH-1, CH-2, and CH-3) with associated Variable Frequency Drives (VFDs), control panels, and MOD-BUS communication cable runs. Power requirements include furnishing and installing shielded 3-1/C#2 cables with #6 bare copper ground in new RGS conduit from switchgear sections K-2C, K-1D, and J-1C to the new equipment. The work involves connections to existing 4.16KV/480Y/277V and 208V/3PH systems, installation of control circuits at 120V single-phase, and provision of 3/4" RGS conduit with shielded twisted pair cables for control communications. All new overhead electrical conduit must be installed tight to the ceiling or at minimum 8 feet above finished floor. The contractor must engage authorized VAMC contractor CRASCO INC. for specific terminations and control room equipment programming. Construction must maintain a clean chiller plant environment with daily debris removal, and all work is subject to compliance with electrical codes, NEC standards, and UL-classified firestop systems where penetrations are required through rated walls.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPECIAL PURPOSE RECEPTACLE - FLUSH FLOOR MOUNTED
SPECIAL PURPOSE RECEPTACLE - CEILING MOUNTED
SPECIAL PURPOSE RECEPTACLE - MOUNTED 18" AFF
QUADRUPLEX RECEPTACLE - FLUSH FLOOR MOUNTED
DUPLEX RECEPTACLE - FLUSH FLOOR MOUNTED
SINGLE RECEPTACLE - MOUNTED 18" AFF
QUADRUPLEX RECEPTACLE - MOUNTED 18" AFF
UTILITY KILOWATT-HOUR METER
DUPLEX RECEPTACLE - EMERGENCY POWER - MOUNTED 18" AFF
DUPLEX RECEPTACLE - CEILING MOUNTED
DUPLEX RECEPTACLE - SPLIT WIRED - MOUNTED 18" AFF
DUPLEX RECEPTACLE - MOUNTED 6" ABOVE COUNTER
MAGNETIC STARTER
SAFETY SWITCH - FUSIBLE
SAFETY SWITCH - NON-FUSIBLE
EQUIPMENT - MOTOR
BRANCH CIRCUIT PANELBOARD - FLUSH MOUNTED
DISTRIBUTION PANELBOARD OR SWITCHBOARD
MOTOR CONTROL CENTER
BRANCH CIRCUIT PANELBOARD - SURFACE MOUNTED
CONTROL PANEL
TRANSFORMER
POWER SYMBOLS
AUTOMATIC TRANSFER SWITCH
METER
CIRCUIT BREAKER
GROUND
ONE-LINE DIAGRAM SYMBOLS
GENERATOR
DELTA-WYE TRANSFORMER
SWITCH
SERVICE DROP
CONDUIT - CAPPED
CABLE TRAY
SEALING FITTING
EXPANSION FITTING
CONDUIT FITTING (CONDULET)
JUNCTION BOX
CONDUIT - FLEXIBLE
CONDUIT - CONTINUED
CONDUIT - CONCEALED BELOW
SLAB OR GRADE
CONDUIT - UP AND DOWN
(CHANGE IN ELEVATION)
CONDUIT - TURNING UP
CONDUIT - EXPOSED
CONDUIT - CONCEALED IN
SUSPENDED CEILING OR WALL
CONDUIT - TURNING DOWN
REVISION CALL-OUT
ROOM NUMBER
FEEDER CALL-OUT
KEYED NOTE
MECHANICAL EQUIPMENT CALL-OUT: REFER TO
THE EQUIPMENT DATA SCHEDULE FOR DETAILS
GENERAL SYMBOLS
JUNCTION BOX - EMERGENCY POWER
SHEET KEY NOTE
WIRING AND CONDUITS
NEW EQUIPMENT (TYPICAL)
EXISTING EQUIPMENT (TYPICAL)
DEMOLITION EQUIPMENT (TYPICAL)
WALL MOUNT BRACKET (TYPICAL)
T-1
45 KVA 3Ø
208Y/120VAC
# AF
# AT
# A
# A
G
ST
SPD
VFD
GROUND FAULT
PROTECTED BREAKER
SHUNT TRIP BREAKER
CONTACTOR
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
DRAWOUT CIRCUIT BREAKER
# AF
# AT
FUSE
PANELBOARD
SURGE PROTECTION DEVICE
THERMAL OVERLOAD
VARIABLE FREQUENCY DRIVE
K
KIRK KEY INTERLOCK
DPM
DIGITAL POWER METER
QUADRUPLEX RECEPTACLE - MOUNTED 6" ABOVE
COUNTER
Room name
101A
PLUMBING EQUIPMENT CALL-OUT: REFER TO
THE EQUIPMENT DATA SCHEDULE FOR DETAILS
J
J
M
G
# A
# POLES
PANEL
M
F
VFD
T
POLE MOUNTED TRANSFORMER
T
J
DUPLEX RECEPTACLE (NEMA 5-20R) - MOUNTED 18" AFF
GFI GROUND FAULT CIRCUIT INTERRUPTER
SS SURGE SUPPRESSOR (ISOLATED GROUND
TYPE)
WP WEATHERPROOF
H HOSPITAL GRADE
TP TAMPER PROOF
D DEDICATED
FLOOR BOX - SEE SPECS OR KEYED NOTES ON
PLAN FOR DETAILS
COMBINATION STARTER
VFD VARIABLE FREQUENCY DRIVE
AC
AC
GROUND BAR
100A4G
# KVA/KW
480Y/277V, 3Ø, 4W
49 ELECTRONIC OVERLOAD
AHU
GWH1
AH(1)
MOTOR NUMBER TYP.
L
L
ELECTRICAL ABBREVIATIONS LIST
SS STAINLESS STEEL
SSW SELECTOR SWITCH
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TC TIMECLOCK
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL
CABINET
TV TELEVISION
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UT UNDERGROUND TELEPHONE
UTP UNSHIELDED TWISTED PAIR
UTIL UTILITY
UV UNIT VENTILATOR OR
ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
ANGLE
@ AT
DELTA
' FEET
" INCHES
# NUMBER
Φ PHASE
C CENTER LINE
P PLATE
MTS MANUAL TRANSFER SWITCH
MTR MOTOR, MOTORIZED
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT
UNIT
PCB POLYCHLORINATED BYPHENYL
PC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
POE POWER-OVER-ETHERNET
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QTY QUANTITY
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SF SQUARE FEET/FOOT
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
SPKR SPEAKER
SP SPARE
SR SURFACE RACEWAY
1P 1 POLE (2P, 3P, 4P, ETC.)
1PH 1 PHASE
2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)
W2 TWO-WIRE (3W, 4W, ETC.)
3PH 3 PHASE
A AMPERE
AAP ALARM ANNUNCIATOR PANEL
AC ABOVE COUNTER
AIR CONDITIONER
ALTERNATING CURRENT
ACC ACCESSIBLE
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT (KILOAMPS)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT INTERRUPTER
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
APPROX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BATT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATED
CAP CAPACITY
CAT CATALOG, CATEGORY
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CLG CEILING
COAX COAXIAL CABLE
COMM COMMUNICATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
COORDCOORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CTR CENTER
CU COPPER
CU FT CUBIC FEET
dB DECIBEL
DB DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLISH/DEMOLITION
DEPT DEPARTMENT
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WALL HEATER
ELECTRIC WATER HEATER
EX EXISTING
EXP EXPLOSION PROOF
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FU FUSE
FUDS FUSED SAFETY DISCONNECT SWITCH
FVR FULL VOLTAGE REVERSING
FVNR FULL VOLTAGE NON-REVERSING
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BDGYPSUM BOARD
HID HIGH-INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
IES ILLUMINATION ENGINEERING SOCIETY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
I/W INTERLOCK WITH
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LED LIGHT-EMITTING DIODE
LF LINEAR FEET/FOOT
LM LUMEN
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
METAL-CLAD (CONDUIT)
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOA MULTIOUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MT MOUNT
A1 b
E1 c d
T1
'LPN'
ELECTRICAL SYMBOL NOTES
THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER
CASE LETTER AND NUMBER.
THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.
EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING
MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES
DIRECTIONAL ARROW ON ILLUMINATED FACE(S).
DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR
THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND
REQUIREMENTS.
PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING
SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR
DESIGNATION CODES.
SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE
NUMBER INDICATED IN THE HEXAGON.
HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT
DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.
CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL
SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE
A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
'LPN'-1,3,5
EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE
AND DIRECTIONAL ARROW.
EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE
FACE AND DIRECTIONAL ARROWS.
E2
EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS
CONTROLLED BY SWITCH 'c'.
EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING
FIXTURES INDICATED BY 'd'.
EXAMPLE: TRANSFORMER TYPE 'T1'.
EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.
DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE
NOTE NUMBER INDICATED IN THE SQUARE.
GENERAL ELECTRICAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN
ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED
PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND
WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA STANDARDS.
PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE
BUILDING CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.
FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL
PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE
WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTING REQUIREMENT AND
THE APPLICABLE BUILDING CODES.
VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED
MOUNTING HARDWARE TO SUIT THE PARTICULAR INSTALLATION.
PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.
BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO
AVOID CONFLICT DURING CONSTRUCTION.
ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND
ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR
SPARE, OR SPACE.
MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO
INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR
MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE
ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".
ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR
EQUIPMENT MANUFACTURER'S SPECIFICATIONS.
CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE
DEVICE'S SCREW TERMINALS.
MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT
UNLESS NOTED OTHERWISE.
ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.
ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON
VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND
CONDUIT OR WHERE CONCRETE-ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE,
LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR FINAL CONNECTIONS.
ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN
APPROVED THIRD PARTY TESTING AGENCY.
FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE
SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC
PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE
MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT
BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.
PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE
BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS
DETERMINED BY THE GOVERNMENT, SHALL BE PROVIDED.
19. PROVIDE ARC FLASH LABELING FOR NEW ELECTRICAL WORK.
20. NO "HOT" ELECTRICAL WORK IS PERMITTED. ALL SHUTDOWNS MUST BE SUBMITTED WITH A MINIMUM
OF TWO WEEK NOTICE.
SHORT CIRCUIT CURRENT CALCULATIONS WILL BE
PERFORMED ON THE ELECTRICAL SYSTEM USING A
BOLTED THREE PHASE FAULT CONDITION FOR
CALCULATIONS TO ACHIEVE MAXIMUM THERMAL AND
MECHANICAL STRESS TO THE SYSTEM FOR
CALCULATIONS PURPOSES. EXISTING SHORT CIRCUIT
VALUES WILL BE USED OUTSIDE THE WORK AREA, FOR
THE STARTING POINT OF THE CALCULATIONS.
METHOD OF SHORT CIRCUIT
CURRENT CALCULATIONS
USING OHM'S LAW AND THE KNOWN RESISTIVITY
CONSTANT OF CONDUCTOR METAL (CIRCULAR MIL-OHM
PER FOOT) FOR COPPER CONDUCTORS, OUR INTENT IS
TO CALCULATE THE REQUIRED WIRE SIZE NECESSARY SO
AS NOT TO EXCEED THE RECOMMENDED VOLTAGE DROP
OF 3% FOR BRANCH CIRCUIT CONDUCTORS.
METHOD OF VOLTAGE DROP
CALCULATIONS
LIGHT FIXTURE SCHEDULE
SYMBOL LABEL
TYPE OF
LAMP
BALLAST/
DRIVER
WATTS/
FIXTURE
VOLTAGE DESCRIPTION
BASIS OF DESIGN
MANUFACTURER/CATALOG NUMBER
NOTES:
1. MANUFACTURER AND CATALOG NUMBERS SHOWN ARE FOR BASIS OF DESIGN, DESCRIPTIVE AND QUALITY STANDARDS ONLY, NOT TO BE USED FOR ORDERING WITHOUT VERIFICATION AND
APPROVAL. CONTRACTOR TO PROVIDE PRODUCT OR EQUAL FOR APPROVAL BY OWNER, ARCHITECT AND ENGINEER. ENGINEER SHALL NOT BE RESPONSIBLE FOR MISMATCHED OR INACCURATE
PART NUMBERS.
2. EM - SWITCHED EMERGENCY LIGHT (CIRCUITED FROM NORMAL AND EMERGENCY BACK-UP POWER)
EM NL - UN-SWITCHED EMERGENCY LIGHT (CIRCUITED FROM EMERGENCY POWER)
NL - NIGHT LIGHT
EX - EXISTING TO REMAIN
R - RELOCATED
3. VERIFY ALL LIGHT FIXTURE MOUNTING TYPES AND COLORS WITH ARCHITECT.
4. ALL FLUORESCENT LIGHT FIXTURES MUST HAVE INDIVIDUAL DISCONNECTING MEANS LOCATED AT EACH FIXTURE.
5. FOR ALL LED LIGHT FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC
PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT
BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTRLLED STATE AUTOMATICALLY. PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
EB 1.5
EMERGENCY DOUBLE HEAD LIGHT FIXTURE WITH BATTERY
BACKUP
LITHONIA MODEL#
ELM2
OR APPROVED EQUIVALENT
E1 LED 3.3
LED EMERGENCY EXIT SIGN WITH DIRECTIONAL INDICATOR AND
BATTERY BACKUP
LITHONIA MODEL#
EXR LED EL M6
OR APPROVED EQUIVALENT
A
M
ELECTRICAL SYMBOL LEGEND
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
Revisions: Date
CONSULTANTS:
REPLACE CHILLERS,
PHASE II
630-16-101
NEW YORK HARBOR HEALTHCARE
SYSTEM
423 EAST 23RD STREET,NEW YORK, NY
17-054
CONTRACT DOCUMENTS
FULLY SPRINKLERED
12/20/2019 10CARDAS
4#
E-001
ELECTRICAL SYMBOLS, GENERAL NOTES
AND ABBREVIATIONS
DocuSign Envelope ID: DDA8ACE4-4A59-45AB-B19C-E9B7A0DD6973
12/20/2019
24 26 28 30 32
24 26 28 30
GG
FF
HH
JJ
LL
2312 14 16 18 20 22
EE
FF
HH
JJ
LL
21 22.5
I-1
K-1
K-2
J-1
J-2
J-1
J-2
K-1
K-2
CONTROL
ROOM
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
AB
AA
AC
AY
AX
AW
AH(1)
AM(2)
AU
MCC 1
MCC 2MCC 3
M
BG
AG(1)
AF(1)
AE(1)
AD(1)
AJ(1)
AI(1)
AL(2)
AK(2)
AT
AR
AS
AV
SEE DETAIL
2/ED101
BKR FRONT
PCD
(TYP)
1 1
XFMR
4160/480-277V
3000KVA
METERING
MAIN
4000 AF
SPACE
SPARE
800 AF
MCC 2
800 AF
DIST BD
DPD
2000 AF
MCC 3
800 AF
MCC 1
800 AF
ATS #8
1600 AF
0 4 8 16
NORTH
PLAN
Scale: 1/8" = 1'-0"
FIRST FLOOR DEMO PLAN
1. FOR GENERAL NOTES, SYMBOLS AND
ABBREVIATIONS, SEE DRAWING E-001.
2. FOR LOCATION OF NEW CHILLER AND VFD,
SEE MECHANICAL DRAWINGS.
3. KEEP CHILLER PLANT CLEAN AND FREE OF
DEBRIS DURING DEMO AND CONSTRUCTION.
REMOVE DEMO AND CONSTRUCTION DEBRIS
DAILY.
4. LETTER CODES WITHIN TRIANGLES BY
DASHED MOTOR SYMBOLS ARE DEFINED ON
DRAWING E-601.
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
Revisions: Date
CONSULTANTS:
REPLACE CHILLERS,
PHASE II
630-16-101
NEW YORK HARBOR HEALTHCARE
SYSTEM
423 EAST 23RD STREET,NEW YORK, NY
17-054
CONTRACT DOCUMENTS
FULLY SPRINKLERED
12/20/2019 10CARDAS
4#
ED101
ELECTRICAL AND CHILLER ROOM
DEMOLITION
1. DISCONNECT MOTORS. REMOVE WIRE AND
CONDUIT BACK TO MCC/SPARE STARTERS.
DISPOSE OF WIRE AND CONDUIT. SEE E-601
FOR MOTOR POWER SOURCE.
2. MCC3 IS TO REMAIN AND THE EC IS TO MARK
DISCONNECTED MOTOR STARTERS AS SPARE.
3. MCC1 AND MCC2'S ASSOCIATED ELETRICAL
FEEDER CONDUIT AND WIRE WILL BE
REMOVED BACK TO PCD. THEIR ASSOCIATED
BREAKERS WILL BE TEMPORARILY MARKED
AS SPARE. AFTER MOTORS ARE
DISCONNECTED, MCC1 AND MCC2 WILL ALSO
BE REMOVED.
Scale: NTS
FIRST FLOOR DEMO PLAN ELEVATION (BREAKER FRONT) OF PCD
DASHED LINES INDICATE DEMO AREA
SHEET KEYNOTES:
K-1D
K-2C
J-1C
CONTROL
ROOM
CCU1 CCU2 CCU3
SEE DETAIL
3/E101
MCC 3 MCC 2
MCC 1
BKR FRONT
PCD
CONTROL
ROOM
K-1D
CHILLER 1
J-1C
CHILLER 2 CHILLER 3
CHILLER 4
K-2C
SEE DETAIL
4/E101
CHILLED WATER
PUMP SKID
CD-3BCD-2BCD-1B
EXISTING
MCC 3
BKR FRONT
NIC
SSF-1
CONDENSED WATER
PUMP SKID
E1
EB
EB
MCC 2
800 AF
MCC 1
800 AF
PUMP
SKID #2
800 AF
PUMP
SKID #1
800 AF
0 4 8 16
NORTH
PLAN
Scale: 1/8" = 1'-0"
DEMO FIRST FLOOR POWER PLAN
0 4 8 16
NORTH
PLAN
Scale: 1/8" = 1'-0"
NEW WORK FIRST FLOOR POWER PLAN
FIRST FLOOR POWER PLAN:
1. EXISTING 3" RGS CONDUIT RUNS FROM
SWITCHGEAR SECTION K-1D, K-2C, J-1C TO
AMPGARD STARTER. REMOVE EXISTING
3-1/C#1+1#1 GROUND CABLE.
2. REMOVE AND DISPOSE OF EXISTING AMPGARD
MCC STARTER TRANSFORMER. VERIFY IF
EXISTING MCC CONTAINS PCB. IF PCB'S ARE
PRESENT, DISPOSE OF ACCORDING TO LAW.
3. REMOVE AND DISPOSE EXISTING POWER AND
CONTROL CONDUIT WIREWAY AND WIRING.
4. EXISTING JUNCTION BOX ON CHILLER SHALL BE
REMOVED AND DISPOSED.
5. DEMO FEEDER RACEWAYS AND CONDUCTORS
FOR PUMPS BACK TO MCC #1 & #2. SEE ED101
6. REMOVE MCC 1 AND MCC 2. SEE ED101.
7. MCC 3 TO REMAIN IN PLACE
8. 800 AF CIRCUIT BREAKERS TO BE REUSED.
REMOVE OLD NAME PLATES AND REPLACE WITH
NEW PLATES.
FIRST FLOOR POWER PLAN:
1. FURNISH AND INSTALL 3# 5KV #2 CABLES WITH 1 #6
BARE GROUND IN 3" RGS CONDUIT.
2. FURNISH AND INSTALL 1-RGS CONDUIT WITH 2-2 #16
SHIELDED TWISTED PAIR CABLE.
3. NEW VARIABLE SPEED DRIVE FURNISHED WITH
CHILLER.
4. NEW CHILLER.
5. FURNISH AND INSTALL 3-3/4" RGS. CONDUIT FILLS
SHOWN ON E102, E103 AND E104.
6. CH-4 IS EXISTING WITH EXISTING CONDUITS AND
FILLS.
7. SEE DWG E-601 FOR CIRCUIT BREAKER,
CONDUCTOR AND CONDUIT SIZES.
8. FOR AIR CIRCUIT BREAKER PRODUCT INFORMATION
CONSIDER SQUARE D MODEL D52065 800 AF.
9. PROVIDE 3/4" RGS CONDUIT WITH 8 COND #16.
10. REMOVE OLD NAMEPLATE, REPLACE WITH NEW
PLATES DUPLICATING CHILLER NUMBERS.
11. SINGLE PHASE 120 VOLT CONTROL CIRCUIT FROM
PUMP PANEL TO DDC PANEL.
12. TIE 120V WP/GFCI RECEPTACLE TO NEAREST
EXISTING RECEPTACLE.
13. TIE INTO EXISTING LIGHTING CIRCUIT.
1. FOR GENERAL NOTES, SYMBOLS AND
ABBREVIATIONS, SEE DRAWING E-001.
2. FOR LOCATION OF NEW CHILLER AND VFD,
SEE MECHANICAL DRAWINGS.
3. KEEP CHILLER PLANT CLEAN AND FREE OF
DEBRIS DURING DEMO AND CONSTRUCTION.
CONTRACTOR TO REMOVE DEMO AND
CONSTRUCTION DEBRIS DAILY.
4. NEW OVERHEAD ELECTRICAL CONDUIT MUST
BE RIGHT TO THE CEILING OR AT MINIMUM OF
8 FEET+ ABOVE THE FINISHED FLOOR.
4 4 4
2 2
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
Revisions: Date
CONSULTANTS:
REPLACE CHILLERS,
PHASE II
630-16-101
NEW YORK HARBOR HEALTHCARE
SYSTEM
423 EAST 23RD STREET,NEW YORK, NY
17-054
CONTRACT DOCUMENTS
FULLY SPRINKLERED
12/20/2019 10CARDAS
4#
E-101
ELECTRICAL AND CHILLER ROOM
DEMOLITION AND NEW WORK
EXISTING CONDUIT
Scale: NTS
EXISTING FIRST FLOOR DEMO PLAN ELEVATION
(BREAKER FRONT) OF PCD, REMOVE OLD NAME
PLATES
Scale: NTS
EXISTING FIRST FLOOR POWER PLAN ELEVATION
(BREAKER FRONT) OF PCD, ADD NEW NAME
PLATES
NEW WORK KEYNOTES:
DEMO SHEET KEYNOTES:
12 12 12
M
J
M
50 67
5IN
800/5
SECTION K-2A
SECTION K-2B
13.2KV/4.16V
2500KVA
TRANSFORMER K-2
SWITCHGEAR K-2
SWITCHGEAR K-2
SWITCHGEAR PC-1A
PULLBOX-I
CABLE MANHOLE
13.2KV CON-ED
FEEDERS. 3ɸ, 3W
208V/3PH
SWITCHBOARD SS-1A
M
5IN
3"C, RGS
PROVIDE 3-1/C#2 WITH #6 BARE CU
IN NEW CONDUIT
3/4" RGS C, 3/C#18 SHLD
W/DRAIN WIRE
CONTROL
ROOM
CHILLER 2
3/4" RGS C, 3#10+1#10G
OIL
HEATER
OIL
PUMP
CHILLER
MOTOR
3" RGS C,
3#1/C+1#1G
4160V
VARIABLE
SPEED DRIVE
(VFD)
3/4" RGS C, 2#12+1#12G
15KV, 3-1/C#2/0
150/5
SECTION K-2C
50 51
5IN
SECTION K-2D
SPACE
ONLY
4160V/3PH
200/5
1000/1500KVA
3PH
3/4"C, 2-2#16 SHIELDED
TWISTED PAIR
50 67
5IN
800/5
SECTION K-2A
SECTION K-2B
2500KVA
TRANSFORMER K-2
SWITCHGEAR K-2
SWITCHGEAR K-2
SWITCHGEAR PC-1A
PULLBOX-I
CABLE MANHOLE
13.2KV CON-ED
FEEDERS. 3ɸ, 3W
208V/3PH
SWITCHBOARD SS-1A
5IN
15KV, 3-1/C#2/0
150/5
SECTION K-2C
50 51
5IN
SECTION K-2D
SPACE
ONLY
4160V/3PH
200/5
1000/1500KVA
3PH
3"C, RGS
REMOVE EXISTING 3-1/C#1 WITH #1G
CABLE
4160V AMPGARD
MCC STARTER
CCU2
4.16KV-208Y/120V
A
M
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
Revisions: Date
CONSULTANTS:
REPLACE CHILLERS,
PHASE II
630-16-101
NEW YORK HARBOR HEALTHCARE
SYSTEM
423 EAST 23RD STREET,NEW YORK, NY
17-054
CONTRACT DOCUMENTS
FULLY SPRINKLERED
12/20/2019 10CARDAS
4#
E-102
KEY NOTES:
1. REMOVE EXISTING 3" RIGID STEEL CONDUIT
WHICH CONTAINS 3-1/C#1 TYPE XLPE CABLES
WITH LEAD SHEATH AND #1 GROUND WIRE.
REMOVE AND DISPOSE EXISTING CABLE FROM
THE SWITCHGEAR SECTION K-2C TO THE
EXISTING AMPGARD STARTER.
2. REMOVE AND DISPOSE EXISTING AMPGARD
STARTER.
3. PROVIDE SHIELDED 3-1/C#2 CABLES WITH A #6
BARE CU GROUND IN NEW RGS CONDUIT.
4. ELECTRICALLY INSTALL VARIABLE SPEED DRIVE
(FURNISHED WITH CHILLER) AS PER
MANUFACTURERS RECOMMENDATIONS. SEE
MECHANICAL DRAWINGS.
5. ELECTRICALLY INSTALL CHILLER AS PER
MANUFACTURERS RECOMMENDATIONS. SEE
MECHANICAL DRAWINGS.
6. ELECTRICALLY INSTALL CHILLER CONTROL
PANEL AS FURNISHED BY CHILLER
MANUFACTURER AS PART OF CHILLER PACKAGE.
7. PROVIDE MOD-BUS COMMUNICATION CABLE
RUNS FROM VARIABLE SPEED DRIVE TO THE
CHILLER CONTROL PANEL.
8. ADJUST SWITCHGEAR SETTINGS TO MATCH FULL
LOAD AMPS FROM NAMEPLATE DATA OF CHILLER
2.
1. FOR GENERAL NOTES, SYMBOLS AND
ABBREVIATIONS, SEE DRAWING E-001.
2. KEEP CHILLER PLANT CLEAN AND FREE OF
DEBRIS DURING DEMO AND CONSTRUCTION.
REMOVE DEMO AND CONSTRUCTION DEBRIS
DAILY.
3. ENGAGE AUTHORIZED VAMC CONTRACTOR:
CRASCO INC., (PHONE:(703) 643-2952,
CONTACT NAME: JOHN CICCONE) AND MAKE
CONNECTIONS, AND COMPLETE THE
TERMINATIONS. AND PROGRAM THE CONTROL
ROOM EQUIPMENT.
4. COORDINATE ROUTING AND SUPPORT OF ALL
CONDUITS WITH EXISTING AND NEWLY
INSTALLED PIPING AND OTHER OVERHEAD
INTERFERENCES.
5. NEW OVERHEAD ELECTRICAL CONDUIT MUST
BE RIGHT TO THE CEILING OR AT MINIMUM OF
8 FEET+ ABOVE THE FINISHED FLOOR.
Scale: NTS
DEMO CONTROL/POWER WIRING
Scale: NTS
NEW CONTROL/POWER WIRING
CHILLER CH-2 POWER AND CONTROL
WIRING
SHEET KEYNOTES:
M
50 67
5IN
800/5
50 27
13.2KV/4.16V
2500KVA
TRANSFORMER K-1
SWITCHGEAR K-1
SWITCHGEAR I-1
SWITCHGEAR PC-1B
PULLBOX-I
CABLE MANHOLE
13.2KV CON-ED
FEEDERS. 3ɸ, 3W
208V/3PH
SWITCHBOARD SS-1A
M
5IN
3"C, RGS
PROVIDE 3-1/C#2 WITH #6 BARE CU
IN NEW CONDUIT
3/4" RGS C, 3/C#18 SHLD
W/DRAIN WIRE
CONTROL
ROOM
CHILLER 1
3/4" RGS C, 3#10+1#10G
OIL
HEATER
OIL
PUMP
CHILLER
MOTOR
3" RGS C,
3#1/C+1#1G
4160V
VARIABLE
SPEED DRIVE
(VFD)
3/4" RGS C, 2#12+1#12G
15KV, 3-1/C#2/0
150/5
SPACE
ONLY
4160V/3PH
1000/1500KVA
3PH
3/4"C, 2-2#16 SHIELDED
TWISTED PAIR
13.2KV/4.16V
2500KVA
TRANSFORMER K-1
SWITCHGEAR K-1
SWITCHGEAR K-1
SWITCHGEAR PC-1B
PULLBOX-I
CABLE MANHOLE
13.2KV CON-ED
FEEDERS. 3ɸ, 3W
208V/3PH
SWITCHBOARD SS-1B
15KV, 3-1/C#2/0
1000/1500KVA
3PH
3"C, RGS
REMOVE EXISTING 3-1/C#1 WITH #1G
CABLE
4160V AMPGARD
MCC STARTER
SECTION K-1D
50 51
5IN
200/5
EXISTING EMPTY
CONDUIT
EXISTING EMPTY
CONDUIT
50 67
5IN
800/5
SECTION K-1X
SECTION K-1X
5IN
150/5
SECTION K-1X
SPACE
ONLY
4160V/3PH
200/5
SECTION K-1D
50 51
5IN
CCU1
SECTION K-1X SECTION K-1X SECTION K-1X
A
M
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
Revisions: Date
CONSULTANTS:
REPLACE CHILLERS,
PHASE II
630-16-101
NEW YORK HARBOR HEALTHCARE
SYSTEM
423 EAST 23RD STREET,NEW YORK, NY
17-054
CONTRACT DOCUMENTS
FULLY SPRINKLERED
12/20/2019 10CARDAS
4#
E-103
KEY NOTES:
1. REMOVE EXISTING 3" RIGID STEEL CONDUIT
WHICH CONTAINS 3-1/C#1 TYPE XLPE CABLES
WITH LEAD SHEATH AND #1 GROUND WIRE.
REMOVE AND DISPOSE EXISTING CABLE FROM
THE SWITCHGEAR SECTION K-1D TO THE
EXISTING AMPGARD STARTER.
2. REMOVE AND DISPOSE EXISTING AMPGARD
STARTER.
3. PROVIDE SHIELDED 3-1/C#2 CABLES WITH #6
BARE CU GROUND IN NEW RGS CONDUIT.
4. ELECTRICALLY INSTALL VARIABLE SPEED DRIVE
(FURNISHED WITH CHILLER) AS PER
MANUFACTURERS RECOMMENDATIONS. SEE
MECHANICAL DRAWINGS.
5. ELECTRICALLY INSTALL CHILLER AS PER
MANUFACTURERS RECOMMENDATIONS. SEE
MECHANICAL DRAWINGS.
6. ELECTRICALLY INSTALL CHILLER CONTROL
PANEL AS FURNISHED BY CHILLER
MANUFACTURER AS PART OF CHILLER PACKAGE.
7. PROVIDE CABLE RUNS FROM VARIABLE SPEED
DRIVE TO THE CHILLER CONTROL PANEL.
8. ADJUST SWITCHGEAR SETTINGS TO MATCH FULL
LOAD AMPS FROM NAMEPLATE DATA OF CHILLER
1.
1. FOR GENERAL NOTES, SYMBOLS AND
ABBREVIATIONS, SEE DRAWING E-001.
2. KEEP THE CHILLER PLANT CLEAN AND FREE
OF DEBRIS DURING DEMO AND
CONSTRUCTION. REMOVE DEMO AND
CONSTRUCTION DEBRIS DAILY.
3. ENGAGE AUTHORIZED VAMC CONTRACTOR:
CRASCO INC., (PHONE:(703) 643-2952,
CONTACT NAME: JOHN CICCONE) MAKE
CONNECTIONS, COMPLETE THE
TERMINATIONS. AND PROGRAM THE CONTROL
ROOM EQUIPMENT.
4. COORDINATE ROUTING AND SUPPORT OF ALL
CONDUITS WITH EXISTING AND NEWLY
INSTALLED PIPING AND OTHER OVERHEAD
INTERFERENCES.
5. NEW OVERHEAD ELECTRICAL CONDUIT MUST
BE RIGHT TO THE CEILING OR AT MINIMUM OF
8 FEET+ ABOVE THE FINISHED FLOOR.
Scale: NTS
Scale: NTS
DEMO CONTROL/POWER WIRING
NEW CONTROL/POWER WIRING
CHILLER CH-1 POWER AND CONTROL
WIRING
SHEET KEYNOTES:
M
50 67
5IN
800/5
SECTION J-1A
SECTION J-1B
13.2KV/4.16V
2500KVA
TRANSFORMER J-1
SWITCHGEAR J-1
SWITCHGEAR J-1
OUTDOOR
SWITCHGEAR
PULLBOX-I
CABLE MANHOLE
13.2KV CON-ED
FEEDERS. 3ɸ, 3W
208V/3PH
STAFF RESIDENCE
SWITCHBOARD
M
5IN
3"C, RGS
PROVIDE 3-1/C#2 WITH #6 BARE CU
IN NEW CONDUIT
3/4" RGS C, 3/C#18 SHLD
W/DRAIN WIRE
CONTROL
ROOM
CHILLER 3
3/4" RGS C, 3#10+1#10G
OIL
HEATER
OIL
PUMP
CHILLER
MOTOR
3" RGS C,
3#1/C+1#1G
4160V
VARIABLE
SPEED DRIVE
(VFD)
3/4" RGS C, 2#12+1#12G
15KV, 3-1/C#2/0
150/5
SECTION J-1C
50 51
5IN
SECTION J-1D
SPACE
ONLY
4160V/3PH
200/5
1000/1500KVA
3PH
3/4"C, 2-2#16 SHIELDED
TWISTED PAIR
50 67
5IN
800/5
SECTION J-1A
13.2KV/4.16V
2500KVA
TRANSFORMER J-1
SWITCHGEAR J-1
SWITCHGEAR J-1
OUTDOOR
SWITCHGEAR
PULLBOX-I
CABLE MANHOLE
13.2KV CON-ED
FEEDERS. 3ɸ, 3W
208V/3PH
STAFF RESIDENCE
SWITCHBOARD
15KV, 3-1/C#2/0
SECTION J-1C
50 51
5IN
4160V/3PH
200/5
1000/1500KVA
3PH
3"C, RGS
REMOVE EXISTING 3-1/C#1 WITH #1G
CABLE
4160V AMPGARD
MCC STARTER
SECTION J-1B
5IN
150/5
SECTION J-1D
SPACE
ONLY
4160V/3PH
EXISTING EMPTY
CONDUIT
CCU3
A
M
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
Revisions: Date
CONSULTANTS:
REPLACE CHILLERS,
PHASE II
630-16-101
NEW YORK HARBOR HEALTHCARE
SYSTEM
423 EAST 23RD STREET,NEW YORK, NY
17-054
CONTRACT DOCUMENTS
FULLY SPRINKLERED
12/20/2019 10CARDAS
4#
E-104
KEY NOTES:
1. REMOVE EXISTING 3" RIGID STEEL CONDUIT
WHICH CONTAINS 3-1/C#1 TYPE XLPE CABLES
WITH LEAD SHEATH AND #1 GROUND WIRE.
REMOVE AND DISPOSE EXISTING CABLE FROM
THE SWITCHGEAR SECTION J-1C TO THE
EXISTING AMPGARD STARTER.
2. REMOVE AND DISPOSE EXISTING AMPGARD
STARTER.
3. PROVIDE NEW SHIELDED 3-1/C#2 CABLES WITH
#6 BARE CU GROUND IN NEW RGS CONDUIT.
4. ELECTRICALLY INSTALL VARIABLE SPEED DRIVE
(FURNISHED WITH CHILLER) AS PER
MANUFACTURERS RECOMMENDATIONS. SEE
MECHANICAL DRAWINGS.
5. ELECTRICALLY INSTALL CHILLER AS PER
MANUFACTURERS RECOMMENDATIONS. SEE
MECHANICAL DRAWINGS.
6. ELECTRICALLY INSTALL CHILLER CONTROL
PANEL AS FURNISHED BY CHILLER
MANUFACTURER AS PART OF CHILLER PACKAGE.
7. PROVIDE MOD-BUS COMMUNICATION CABLE
RUNS FROM VARIABLE SPEED DRIVE TO THE
CHILLER CONTROL PANEL.
8. ADJUST SWITCHGEAR SETTINGS TO MATCH NEW
FULL LOAD AMPS OF CHILLER 3.
1. FOR GENERAL NOTES, SYMBOLS AND
ABBREVIATIONS, SEE DRAWING E-001.
2. KEEP THE CHILLER PLANT CLEAN AND FREE
OF DEBRIS DURING DEMO AND
CONSTRUCTION. REMOVE DEMO AND
CONSTRUCTION DEBRIS DAILY.
3. CONTRACTOR SHALL ENGAGE AUTHORIZED
VAMC CONTRACTOR:
CRASCO INC., (PHONE:(703) 643-2952,
CONTACT NAME: JOHN CICCONE) MAKE
CONNECTIONS, COMPLETE THE
TERMINATIONS. AND PROGRAM THE CONTROL
ROOM EQUIPMENT.
4. COORDINATE ROUTING AND SUPPORT OF ALL
CONDUITS WITH EXISTING AND NEWLY
INSTALLED PIPING AND OTHER OVERHEAD
INTERFERENCES.
5. NEW OVERHEAD ELECTRICAL CONDUIT MUST
BE RIGHT TO THE CEILING OR AT MINIMUM OF
8 FEET+ ABOVE THE FINISHED FLOOR.
Scale: NTS
Scale: NTS
CHILLER CH-3 POWER AND CONTROL
WIRING
DEMO CONTROL/POWER WIRING
NEW CONTROL/POWER WIRING
SHEET KEYNOTES:
1. WALL ASSEMBLY - MIN 4-7/8 IN. AND 6-1/8 IN. THICK NORMAL WEIGHT OR LIGHTWEIGHT (100-150 PCF)
CONCRETE FOR 1 AND 2 HR RATED ASSEMBLIES, RESPECTIVELY. WALL MAY ALSO BE CONSTRUCTED OF
ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF OPENING IS 14-1/8 IN.
SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF
MANUFACTURERS.
THE F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE HOURLY FIRE RATING OF THE WALL
ASSEMBLY IN WHICH IT IS INSTALLED.
2. THROUGH PENETRANTS - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER
CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN
PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING SHALL BE MIN 0 IN. TO MAX 1-3/8 IN. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING
TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE- THE FOLLOWING TYPES AND SIZES OF STEEL PIPES MAY BE USED:
1A. NOM 4 IN. DIAM (OR SMALLER) SCHEDULE 7 (OR HEAVIER) STEEL PIPE.
2A. NOM 8 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
3A. NOM 10 IN. DIAM (OR SMALLER) SCHEDULE 20 (OR HEAVIER) STEEL PIPE.
WHEN STEEL PIPE IS USED, T RATING IS 1/4 HR FOR NOM 4 IN. DIAM (OR SMALLER) AND 0 HR FOR STEEL
PIPES GREATER THAN NOM 4 IN. DIAM.
B. IRON PIPE - NOM 4 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE. WHEN IRON PIPE IS USED T
RATING IS 1/4 HR.
C. CONDUIT - NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING (EMT) OR STEEL
CONDUIT. WHEN EMT OR STEEL CONDUIT IS USED T RATING IS 1/4 HR.
D. COPPER TUBING - NOM 4 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING WHEN
COPPER TUBE IS USED T RATING IS 0 HR.
E. COPPER PIPE - NOM 4 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE. WHEN COPPER
PIPE IS USED T RATING IS 0 HR.
3. FILL, VOID OR CAVITY MATERIAL - SEALANT - MIN 5/8 IN. AND 1-1/4 IN. THICKNESS OF FILL MATERIAL
FOR 1 AND 2 HR RATED WALL ASSEMBLIES, RESPECTIVELY, APPLIED WITHIN THE ANNULUS, FLUSH WITH
BOTH SURFACE OF WALL. AT POINT CONTACT LOCATION BETWEEN PENETRANT AND PERIPHERY OF
OPENING, A MIN 1/2 IN. DIAM BEAD OF FILL MATERIAL SHALL BE INSTALLED AT THE
CONCRETE/PENETRANT INTERFACE ON BOTH SURFACES OF WALL.
PASSIVE FIRE PROTECTION PARTNERS - 4800DW
*BEARING THE UL CLASSIFICATION MARK
A
M
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
Revisions: Date
CONSULTANTS:
REPLACE CHILLERS,
PHASE II
630-16-101
NEW YORK HARBOR HEALTHCARE
SYSTEM
423 EAST 23RD STREET,NEW YORK, NY
17-054
CONTRACT DOCUMENTS
FULLY SPRINKLERED
12/20/2019 10CARDAS
4#
E-501
ELECTRICAL DETAILS
Scale: NTS
W-J-1040 UL DETAIL
AH AE AF AG AO AI AJ AN AD
MCC1
AK AL AM AP AQ
SPACE
CW
PUMP
SKID
1 1 11 1 1 1 1 1 1 1
2 2
2-3.5" RGS CONDUITS WITH 3# 600KCML
AND 1 #1 GND IN EACH CONDUIT
2-3.5" RGS CONDUITS WITH 3# 600KCML
AND 1 #1 GND IN EACH CONDUIT
SPARE
REMAINS
REMOVE
MCC2 MCC3
M M M M M M M M M
800A
M M M M M
800A 800A 800A 1600A
7 8 1 2 3 4 5 6
4000A
M M M M M
AE AE
M
BC
M
BE
M
BF
M
M M
MCC-3
MCC-2
MCC-1
EMERGENCY PANEL IN
EXISTING CHILLER PLANT
ROOM
AP-
EM-
EXISTING
MCC
4#6 & 1#8G - 1 1/4" C
PC-D-1
PC-D-2
PC-D-3
MCC-1 MCC-2 MCC-3
POWER CENTER SECONDARY GEAR SCHEDULE
POWER CENTER SECONDARY GEAR SCHEDULE POWER CENTER SECONDARY GEAR SCHEDULE
D E
S I G
N A
T I O
N P
C C
P C
B
P C
A
CIRC.
NO.-
MAIN DEVICE
DEVICE
SIZE
POLES
"N"-NEUT.
BAR
CONN.
OVER-
CUR-
RENT
SIZE
FEEDER
CONTROLLED
DEVICE TYPE
CIRC.
NO.-
MAIN DEVICE
DEVICE
SIZE
POLES
"N"-NEUT.
BAR
CONN.
OVER-
CUR-
RENT
SIZE
FEEDER
CONTROLLED
DEVICE TYPE
1 4000 3+N 4000 PC-A-1
1 4000 3+N 4000 PC-B-1
1 4000 3+N 4000 PC-C-1
DRAWOUT AIR FRAME
DRAWOUT AIR FRAME
DRAWOUT AIR FRAME
1 800 3 800 PC-D-1 DRAWOUT AIR FRAME
2 800 3 800 PC-D-2
3 800 3+N 800 PC-D-3
4 100 3+N - SPARE
5 800 3+N 800 PC-D-5
6 2000 3+N 600 PC-D-6
7 400 3 - SPARE
8 400 3 - SPARE
9 4000 3+N 4000 SPARE DRAWOUT AIR FRAME
W/GND. CURRENT TRIP.
P-3
CHW
PUMP
SKID
1 1 1
A
M
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
Revisions: Date
CONSULTANTS:
REPLACE CHILLERS,
PHASE II
630-16-101
NEW YORK HARBOR HEALTHCARE
SYSTEM
423 EAST 23RD STREET,NEW YORK, NY
17-054
CONTRACT DOCUMENTS
FULLY SPRINKLERED
12/20/2019 10CARDAS
4#
E-601
ELECTRICAL SINGLE LINE
KEY NOTES:
1. MOTOR TO BE REMOVED.
2. ELECTRICAL CONTRACTOR (EC) TO REUSE TWO
EXISTING DRAW OUT AIR BREAKER FRAME SIZE
800AMP 3 PHASE 480 VOLT. EC TO INSTALL WIRE
AND CONDUIT FROM EXISTING SWITCHGEAR /
800 AF CIRCUIT BREAKERS TO POWER
CONNECTION BOXES OF CW AND CHW PUMP
SKIDS AND TERMINATE.
1. DISCONNECT MOTORS. REMOVE WIRE AND
CONDUIT BACK TO MOTOR CONTROLLER.
CONTRACTOR TO DISPOSE OF WIRE AND
CONDUIT.
2. KEEP THE CHILLER PLANT CLEAN AND FREE
OF DEBRIS DURING DEMO AND
CONSTRUCTION. REMOVE DEMO AND
CONSTRUCTION DEBRIS DAILY.
Scale: NTS
ELECTRICAL SINGLE LINE
SHEET KEYNOTES:
CCU-3
CCU-4
NEW
CHILLER
CCU-2 CCU-1
NEW
CHILLER
NEW
CHILLER
CW
PUMP
SKID
CHW
PUMP
SKID
EXISTING
CHILLER
REMAINS
VFD VFD
800AT
800AF
600AT
800AF
MCC 1
MCC 2
MCC 3
PULLBOX-I
Y
PHASING RECEPTACLE
WITH P.T.
NEON TUBE
C.T.
KEY INTERLOCK
13.2 KV CON ED
FEEDERS 3Ph, 3W
EQUIPPED
SPACE
ONLY
I-1A
K
Y
K
Y
K
Y
K
Y
K
TRANSFORMER I-1
TRANSFORMER J-1
TRANSFORMER J-2
TRANSFORMER K-1
TRANSFORMER K-2
LOAD BUS I-1
I-1B I-1C I-1D
J-1A
J-1B
J-1C J-1D
J-2A
J-2B J-2C
J-2D
K-1A K-1B K-1C K-1D
K-2A K-2B K-2C K-2D
EQUIPPED
SPACE
ONLY
EQUIPPED
SPACE
ONLY
EQUIPPED
SPACE
ONLY
EQUIPPED
SPACE
ONLY
I-1
J-1
J-2
K-1
PULLBOX-J
PULLBOX-K
K-2
(2) 13.2 KV CON ED
FEEDERS 3Ph, 3W
(2) 13.2 KV CON ED
FEEDERS 3Ph, 3W
PROPERTY LINE
MANHOLE
(TYPICAL)
LOAD BUS J-1
LOAD BUS J-2
LOAD BUS K-1
LOAD BUS K-2
EMPTY CONDUIT FOR
FUTURE BUILDING
5KV UNFUSED
ISOLATING SWITCH
4000A 4000A 4000A
POWER CENTER BRACED FOR
50,000 A. RMS SYM. MINIMUM.
149,600A RMS
SYM. (TYPICAL)
EXISTING 180/208V
SWITCHGEAR (FOR
STAFF RESIDENCE
DISCONNECT & REMOVE
EXIST CABLES TO
MAN HOLE
OUTDOOR, PAD MTD
5KV-208/120V, 300KVA
TRANSF. 3 PHASE
5KV DISCONNECT SW.
ABANDON EXIST. 180/208V
MANHOLE IN STREET.
POWER CENTER BRACED
FOR 42,500A RMS
SYM. MINIMUM.
32,400A RMS
SYM. TYPICAL
EMPTY CONDUIT FOR
FUTURE BUILDING FOR 480
VOLT POWER CENTERS.
4000A
MOTOR
CONTROLLER
MOTOR CONTROLLERS
EXISTING, TO
REMAIN CHILLER
CONTROLLER
4160KV - 480/277V
2000/3000KVA CAST COIL TRANSF.
PC-D
SS-A SS-B SS-C
EXISTING SWITCHBOARDS (208V)
PC-A
PC-B
PC-C
26,800A RMS
SYM. TYPICAL
4.16KV - 208/120V
1000/1500KVA(TYPICAL)
1000 TON
CHILLER
CHILLER
BY OTHERS PULLBOX A
SYN BUS
21,100A RMS SYM.
21,100A RMS SYM.
21,100A RMS SYM.
5KV SYN BUS SCHEME
NO SCALE
32,400A
RMS SYM
TP.
2500/3750 KVA
13.2 KV-4.16 KV
4.16 RELAYING SCHEME
NOTES
1. PROVIDE RELAYS SHOWN
TYPICALLY FOR EACH SYNC. BUS
C.B., LOAD BUS MAIN C.B., MOTOR
FEEDER C.B. AND POWER CENTER
C.B.
51N
MAIN INCOM, C/B
800/5
150/5
51N
MOTOR FEEDER C/B
POWER CENTER
FEEDER C/B
51N
SYN. BUS C/B
51N
POWER CENTER
200/5 FOR 1000KVA TRANSF.
400/5 FOR 2000KVA TRANSF.
HIGH VOLTAGE
CONTROLLER
1000 TON
CHILLER MOTOR
800/5
LOAD BUS
CURRENT
TRANSF.
RATION
CURRENT
TRANSFORMER
(TYPICAL)
IEEE RELAY
NUMBER
(TYPICAL)
SYBCHRONOUS BUS
200E FUSE TYPICAL
1000 KVA
TYPICAL
01.
02.
03.
04.
05.
06.
07.
08.
09.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
15 04
03 15 04
03 15
03 15
03 15
PULLBOX B
HEXAGON 17 HERE
PULLBOX FOR FUTURE
BUILDING (PHASE 1C)
36300A
RMS SYM
4000 A BUS
CONNECT NEW
WIRING TO CHILLER
REMOVE
A
M
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
Revisions: Date
CONSULTANTS:
REPLACE CHILLERS,
PHASE II
630-16-101
NEW YORK HARBOR HEALTHCARE
SYSTEM
423 EAST 23RD STREET,NEW YORK, NY
17-054
CONTRACT DOCUMENTS
FULLY SPRINKLERED
12/20/2019 10CARDAS
4#
E-602
ELECTRICAL SINGLE LINE
Scale: NTS
ELECTRICAL SINGLE LINE
KEY NOTES:
1. SHORT CIRCUIT VALUES FOR OVER CURRENT
PROTECTIVE DEVICE COORDINATION STUDY TO
BE DETERMINED AT A LATER DATE BY
ELECTRICAL CONTRACTOR. FOR CONDUIT SIZE
AND FILL SEE E-601.
2. REPLACE CHILLER FEEDERS, VFD CONTROLLERS
TO CHILLER 1,2, AND 3 CCU-1, CCU-2 AND CCU-3.
3. EXISTING CHILLER #4 TO REMAIN CCU-4.
4. REMOVE MOTOR CONTROL CENTERS, MCC#2
AND MCC#3.
5. REUSE 800AF CIRCUIT BREAKER IN EXISTING
POWER CENTER "D" AND ADJUST TRIP TO 800
AMPS.
6. REUSE EXISTING 800AF CIRCUIT BREAKER AND
ADJUST TRIP TO 800A.
1. CONTRACTOR IS RESPONSIBLE FOR KEEPING
THE CHILLER PLANT CLEAN AND FREE OF
DEBRIS DURING DEMO AND CONSTRUCTION.
CONTRACTOR TO REMOVE DEMO AND
CONSTRUCTION DEBRIS DAILY.
LEGEND
EACH - CUSTOMERS PROPERTY LINE CABLE MANHOLE - 8'-6"X4'-6"X6'-0"
PRECAST TYPE IN ACCORADANCE WITH CON EDISON DWG. NO. 1632-B-REV 2.
EACH - 15KV, 3-1/2C, #2/0 FEEDERS WITH UNGROUNDED NEUTRAL, TYPE XLPE
WITH LEAD SHEATH, INSTALL IN 5" PVC CONDUIT WITH 2/0 GROUND WIRE.
CONDUIT ABOVE GRADE SHALL BE STEEL.
EACH - 15KV, PRIMARY METERING CUBICLE, AS PER CON EDISON
REQUIREMENTS. PROVIDE CTS, PTS, PHASING RECEPT, NEON TUBES ETC.
EACH - 15KV, 1000 MVA 1200 AMPERE, LOAD BREAK FUSED INTERRUPTER
SWITCH WITH KEY INTERLOCK, WITH GROUNDING SWITCH & FUSE
COMPARTMENT AS PER CON EDISON REQUIREMENTS.
EACH -- 13.2 KV/4.16, 2500 KVA/3650 KVA NETWORK TYPE DRY, CAST RESIN
TRANSFORMERS WITH FAN COOLING.
EACH -- 4.16 KV METAL CLAD SWITCHGEAR WITH DRAWOUT AIRFRAME CIRCUIT
BREAKER AND INCORPORATING THE FOLLOWING FEATURES:
A) EACH LOAD BUS CIRCUIT BREAKER CUBICLE SHALL BE EQUIPPED WITH
AN AMMETER AND A 4 POSITON SELECTOR SWITCH.
B) EACH LOAD BUS, MAIN INCOMING CIRCUIT BREAKER CUBICLE SHALL BE
EQUIPPED WITH A VOLT METER, A 4 POSITION SELECTOR SWITCH AND
REQUIRED POTENTIAL TRANSFORMERS.
C) EACH CIRCUIT BREAKER SHALL HAVE A CONTINUOUS CURRENT RATING
OF 1200 AMPERES AND A MINIMUM INTERRUPTING RATION OF 350 MVA.
4.16 METAL CLAD SWITCHGEAR, SYNCHRONOUS BUS WITH DRAWOUT CB, 1200
AMPERE, 350 MVA. EACH CB SHALL BE EQUIPPED WITH AN AMMETER AND A 4
POSITION SELECTOR SWITCH.
EACH, 2 SETS OF 3 - 250 MCM XLPE CABLES, LEAD SHEATHED WITH 2/0,
GROUND WIRE IN 4" RIGID STEEL CONDUIT.
EACH -- 15KV, 3-1/C, #2/0, TYPE XLPE CABLES WITH LEAD SHEATH INSTALLED IN
4" RIGID STEEL CONDUIT WITH 2/0 GROUND WIRE.
EACH -- 5KV, 3-1/C, #3/0, TYPE XLPE CABLES WITH LEAD SHEATH INSTALLED IN
3" RIGID STEEL CONDUIT - INCLUDE 2/0 GROUND WIRE.
EACH -- 5KV, 3-1/C, 500 MCM TYPE XLPE CABLES WITH LEAD SHEATH INSTALLED
IN 4" CONDUIT. INCLUDE 2/0 GROUND WIRE.
EACH -- 5KV, 3-1/C, #1 TYPE XLPE CABLES WITH LEAD SHEATH AND #1 GROUND
WIRE INSTALLED IN 3" RIGID STEEL CONDUIT.
5KV, 3-1/C, #4 TYPE XLPE CABLES WITH LEAD SHEATH AND #4 GROUND WIRE
INSTALLED IN 3" RIGID STEEL CONDUIT EXCEPT UNDERGROUND CONDUIT
SHALL BE PVC.
EACH -- 4" RIGID STEEL EMPTY CONDUIT.
EACH -- GROUNDING SWITCH.
EACH TYPICAL POT HEAD.
5KV FEEDER BY OTHER TO REMAIN.
SEE DETAIL SHEETS E102, E103, E104
CONDUIT AND CABLE BY OTHERS SHALL BE CUT BACK TO CEILING.
PULL BOX BY OTHERS TO REMAIN, SPLICE NEW 5KV CABLES, TO CABLES IN
PULL BOX.
EACH -- 5" PVC EMPTY CONDUIT FOR UNDERGROUND INSTALLATION. CONDUIT
ABOVE GRADE, SHALL BE STEEL.
8-500 MCM IN 2-4" CONCRETE ENCASED PVC CONDUIT UNDERGROUND & RIGID
STEEL WITHIN THE BUILDING.
EXISTING CT CABINET. REMOVE CT'S & UTILIZE CT CABINET AS JUNCTION BOX.
SHEET KEYNOTES:
(P1)(P5)(P1)(P5)
(P2)(P6)
(P3)(P7)
(P4)(P8)
800A
A
M
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
Revisions: Date
CONSULTANTS:
REPLACE CHILLERS,
PHASE II
630-16-101
NEW YORK HARBOR HEALTHCARE
SYSTEM
423 EAST 23RD STREET,NEW YORK, NY
17-054
CONTRACT DOCUMENTS
FULLY SPRINKLERED
12/20/2019 10CARDAS
4#
E-603
ELECTRICAL SCHEMATIC & EQUIPMENT
SCHEDULE
Scale: NTS
ELECTRICAL SCHEMATIC TYPICAL NEW PUMP SKID
1. SEE TABLE 1 FOR PUMP HORSEPOWER AND FULL
LOAD AMPS (FLA).
2. REFER TO E-601.
SHEET KEYNOTES:
Scale: NTS
TABLE 1 ELECTRICAL EQUIPMENT SCHEDULE
| Sheets and Views |
| E-001-E-001 |
| ED101-ED101 |
| E-101-E101 |
| E-102-E-102 |
| E-103-E-103 |
| E-104-E-104 |
| E-501-E-601 |
| E-601 - NEW-E-601 |
| E-602 - NEW-E-602 |
| E-603-E-603 |
| 2019-12-20T06:41:59-0800 | |