Bldg 74 ACM Survey Report.pdf

PDF 5 MB Posted

Attached to
Y1DA--LTSCI VA Dallas 549-820B Long Term Spinal Cord Injury
Solicitation number
36C10F22R0045
Issued by

About this file

This is a solicitation for a long term spinal cord injury project at the VA Medical Center in Dallas, Texas. The solicitation is for project 549-820B and involves renovations and upgrades to Building 74 which serves as the Spinal Cord Injury building. The work includes upgrades to mechanical, electrical, and plumbing systems as well as installation of new finishes, fixtures, and casework. Bids are due by February 22, 2022 and the contract is expected to be awarded by April 2022. The estimated value of the contract is between $5-10 million. The solicitation is being conducted by the Department of Veterans Affairs Office of Construction and Facilities Management.

View the file

Other files

File Type Posted
Part II of II RFI Response.pdf PDF
01 45 00 chart.pdf PDF
36C10F22R0045 0013.docx DOCX document
RE trailer plan REV.pdf PDF
sign IN-01.33.pdf PDF
RE Field Office REV.pdf PDF
ADD-02 SPECs.pdf PDF
ADD-02 DWGs.pdf PDF
36C10F22R0045 0012.docx DOCX document
LTSCI ADDDENDUM 01drawings RV.pdf PDF
36C10F22R0045 0011.docx DOCX document
36C10F22R0045 0010.docx DOCX document
36C10F22R0045 0009.docx DOCX document
36C10F22R0045 0008.docx DOCX document
83-GL-101 VA-Attachment RFI.pdf PDF
36C10F22R0045 0007.docx DOCX document
36C10F22R0045 0006.docx DOCX document
36C10F22R0045 0005.docx DOCX document
1 17 RESIDENT ENGINEER FIeld Office.pdf PDF
LTSCI Pre-proposal visit Sign In Sheets.pdf PDF
1 17 RESIDENT ENGINEER RE FIeld Office.pdf PDF
36C10F22R0045 0004.docx DOCX document
36C10F22R0045 0003.docx DOCX document
36C10F22R0045 0002.docx DOCX document
36C10F22R0045 0001.docx DOCX document
23 b Mechl DWGs 2of12sp.pdf PDF
01_a Civil DWGs 1of4 tt1.pdf PDF
01_d Civil DWGs 4of4 oc.pdf PDF
23 d Mechl DWGs 4of12sp.pdf PDF
04 IRRIGATION DWGs 1of1.pdf PDF
22 a Plmbg DWGs 1of8 tt.pdf PDF
27_a TELECOM DWGs 1of1sp.pdf PDF
26_g Elecl DWGs 7of7g.pdf PDF
20_GENERAL Vol 3 DWGs tt.pdf PDF
LTSCI ProjMan VOL 01 part 1of2 div00-div08 tt1.pdf PDF
26_d Elecl DWGs 4of7sp.pdf PDF
09_f Archl DWGs 6of12sp.pdf PDF
08.0 a Structl DWGs 1of4 tt1.pdf PDF
LTSCI ProjMan VOL 01 part 2of2 div09-div14 tt.pdf PDF
83 LTSCI MES part 1of6.pdf PDF
09_l Archl DWGs 12of12sp.pdf PDF
23 f Mechl DWGs 6of12sp.pdf PDF
VA LTSCI Bid Pack B Suppl Info part 2of2 g.pdf PDF
09_j Archl DWGs 10of12sp.pdf PDF
09_h Archl DWGs 8of12sp.pdf PDF
22 f Plmbg DWGs 6of8 tt.pdf PDF
26_b Elecl DWGs 2of7 tt.pdf PDF
26_f Elecl DWGs 6of7 tt.pdf PDF
22 c Plmbg DWGs 3of8 tt1.pdf PDF
23 c Mechl DWGs 3of12sp.pdf PDF
Show 40 more

Latest 50 of 117 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL ASBESTOS

SURVEY REPORT

FOR

ASBESTOS-CONTAINING MATERIALS

Prepared for:

Page Southerland Page, LLP 3500 Maple Avenue, Suite 600

Dallas, Texas 75219

Attn:

Mr. Dee Maxey

Senior Vice President

Project Name:

LT-SCI (VA Project #549-820 / PSP Project #309070)

Project Building:

Building 74

Spinal Cord Injury Building VA Medical Center - Dallas, Texas

CONXSIS Project No. 10-002-1

Date: December 27, 2010

Prepared by:

POB 120725

Arlington, Texas 76012-0725

(817) 348-0060 (Phone)

(817) 469-8311 (Fax) www.CONXSIS.com

ASBESTOS SURVEY REPORT

Building 74, Spinal Cord Injury Building, VA Medical Center, Dallas, Texas

TABLE OF CONTENTS

1. Introduction

2. Summary 2.1.Asbestos-Containing Material Listing 2.2.Recommendations

3. Survey Scope of Work

4. Assumptions

5. Limitations

6. Applicable Regulatory Standards

7. Survey and Sample Collection Procedure

8. Previous Survey / Plans Review

9. Suspect ACM Materials Not Sampled

10. Survey Sampling Results

11. Appendices

Building 74, Spinal Cord Injury Building, VA Medical Center, Dallas, Texas PAGE 1 OF 22

1. Introduction

In accordance with our proposal dated September 21, 2010, the CONXSIS Group, Inc. (CONXSIS) performed an asbestos visual assessment at selected locations of Building 74, Spinal Cord Injury Building, VA Medical Center, Dallas, Texas. The assessment occurred on October 14, 2010. No representatives of the client were present during the assessment on October 14, 2010.

The 76,561 square feet building was identified to have been constructed in 1996. A total of 87 samples were collected from the building during this assessment on October 14, 2010.

The objective of the Asbestos Survey is to determine the location and quantity of asbestos-containing materials (ACM) at the Project building and to provide budget estimates for asbestos abatement activities to address the ACM at the below mention building:

Building 74, Spinal Cord Injury Building, VA Medical Center, Dallas, Texas

CONXSIS’ Scope of Work included:

Reviewed existing asbestos survey conducted by Micro Air of Texas, Inc., dated June 14, 2010.

Field verified the location of ACMs identified in Micro Air of Texas, Inc. survey.

Collected additional samples as necessary for demolition-specific survey data and specifications.

Estimated approximate quantities and general locations of ACM.

Assessed the condition of the ACM identified.

Assigned a hazard rating to each type of ACM.

This report has been prepared for the use of Page Southerland Page, LLP. Our investigation was performed using the degree of care and skill ordinarily exercised under similar circumstances by professional consultants practicing in this or similar localities. No other warranty or guarantee, expressed or implied, is made as to the conclusions included in this report.

Building 74, Spinal Cord Injury Building, VA Medical Center, Dallas, Texas PAGE 2 OF 22

CONXSIS did not perform destructive sampling procedures at the site; therefore, regardless of the thoroughness of this survey, it is possible that suspected asbestos-containing materials (ACMs) might exist in the building beneath the floors, behind walls, within pipe chases, or in other inaccessible locations. If, during renovation or demolition activities, materials not addressed in this survey are discovered, these materials should be sampled and analyzed for asbestos content prior to disturbance.

Surveyed by:

Jeffrey R. Smith

Department of State Health Services Individual Asbestos Consultant

License #105079

Report Written by:

Manju Ramasamudra

Department of State Health Services (DSHS) Individual Asbestos Consultant

License #105455

Building 74, Spinal Cord Injury Building, VA Medical Center, Dallas, Texas PAGE 3 OF 22

2. Summary

CONXSIS performed an Asbestos Survey and Hazard Assessment at Building 74, Spinal Cord Injury Building, VA Medical Center, Dallas, Texas on October 14, 2010. The following report summarizes the independent conclusions representing CONXSIS’ best professional judgment based on information and data available to us during the course of this survey. Factual information regarding operations, conditions, and tests data provided by the Client, Owner or their representative has been assumed to be correct and complete. Additionally, the conclusions presented are based on the conditions that existed on the date (October 14, 2010) of the assessment.

The 76,561 square feet building was identified to have been constructed in 1996. A total of 87 samples were collected from the building during this assessment on October 14, 2010.

2.1. Asbestos-Containing Material Listing

No homogeneous materials were identified as asbestos-containing material during the CONXSIS Asbestos Survey on October 14, 2010. In addition, review of the existing asbestos survey conducted by Micro Air of Texas, Inc. dated June 14, 2010 identified no homogeneous material of asbestos-containing materials.

Building 74, Spinal Cord Injury Building, VA Medical Center, Dallas, Texas PAGE 4 OF 22

2.2. Suspect ACMs

Although not included in CONXSIS’ scope of work, the following is included for informational purposes:

A. The following suspect asbestos-containing materials were not sampled as part of this scope of work:

Suspect fibrous electrical cable covering was not sampled due to the danger of possible electrocution.

Since ordinary demolition activities do not include sanding, grinding, cutting, and abrading, these materials may remain in place during building demolition as long as they remain in good condition and are not friable.

If the material is in poor condition and is friable at the time of demolition or renovation, or if it will be subjected to sanding, grinding, cutting, or abrading, it should first be removed by a licensed asbestos removal contractor and disposed of as asbestos-containing waste.

When removing asphalt-roofing products, the material should be removed using a method that does not subject the material to sanding, cutting, grinding, or abrading (hand tools). Asbestos-containing roofing may be disposed of as construction debris.

2.3. Recommendations

No further action is needed at this time.

Building 74, Spinal Cord Injury Building, VA Medical Center, Dallas, Texas PAGE 5 OF 22

3. Survey Scope of Work

This survey was conducted for the purpose of identifying asbestos-containing materials (ACM) throughout the building and to conduct a hazard assessment on existing ACM. The survey was non-destructive in nature and limited only to those areas that were readily accessible.

Specific areas to which access was limited by tenant request, unavailability of keys, or by site conditions included the following:

Behind the walls

Beneath the floors

Any suspect ACM not sampled as part of the assessment and any additional suspect materials identified behind walls and beneath the floors should be sampled prior to repair, renovation, or demolition activities.

Building 74, Spinal Cord Injury Building, VA Medical Center, Dallas, Texas PAGE 6 OF 22

4. Assumptions

The report was prepared based on the following assumptions:

Our on-site inspection only included areas readily accessible and viewable and did not include any destructive inspection actions such as demolition of walls and floors.

Our ACM quantification process was based on the assumptions identified above.

Our asbestos abatement budget estimate of probable costs is based on standard industry rates for work of a similar nature. Actual asbestos abatement costs can only be determined by a bid or negotiation process with duly licensed asbestos abatement contractor(s) which includes project-specific specifications and a definitive scope of work prepared by a duly licensed asbestos professional.

Building 74, Spinal Cord Injury Building, VA Medical Center, Dallas, Texas PAGE 7 OF 22

5. Limitations

CONXSIS did not attempt to disassemble mechanical equipment, open pipe chases, or access materials within wall voids. Regardless of the thoroughness of a survey, the possibility exists that some areas containing asbestos were not identified, were inaccessible, or were different from those at the specific locations surveyed. The findings and opinions presented are relative to the dates of our site work and should not be relied upon to represent conditions at substantially later dates. Changes in the condition of ACM may change over time due to renovations and/or repairs.

This report is for the exclusive use of the Client and its agents and use by any unauthorized parties in whole or in part, except as directed by legal jurisdiction, is at the sole risk of the user. If this assessment includes reliance on work products and/or documents prepared by others, CONXSIS has no responsibility for the accuracy of information contained therein.

Although this assessment has attempted to identify the presence or absence of ACM, potential sources of ACM may have escaped detection due to: (1) the scope of this assessment, (2) the inaccuracy of records, interviews, work products or documents made available to CONXSIS for this report, (3) the presence of undetected or unreported renovations and repairs, (4) inaccessible areas, and/or (5) deliberate concealment of detrimental information.

Estimates presented in this report are based upon observations during the survey and owner-provided information. These reasonable estimates may be affected by unanticipated conditions potentially present in inaccessible or un-surveyed areas. CONXSIS does not warrant or guarantee the quantity estimates. The use of such estimates shall be at the user's own risk and shall constitute a release and agreement to defend and indemnify CONXSIS from and against any liability. If questions arise during the planning for renovation, demolition, or other construction activities, CONXSIS should be notified to permit review of the data and present recommendations.

Interior of the following rooms were inaccessible during our Asbestos Survey on October 14, 2010: None.

Building 74, Spinal Cord Injury Building, VA Medical Center, Dallas, Texas PAGE 8 OF 22

6. Applicable Regulatory Standards

The following regulatory standards and specific asbestos-related statutes/protocols were applied by CONXSIS and its contract laboratory during the performance of field efforts related to this study, analytical review of resulting bulk samples, and reduction of observations and data into this report.

29 CFR 1910.1101 (formerly 1926.58) - Construction Industry

This regulation addresses asbestos exposure during construction and renovation activity and sets forth standards which employers must follow in protecting and documenting the protection of workers. The current survey was based on the Final Rules for Asbestos Exposure in General Industry and Construction, issued August 10, 1996, and effective October 1, 1995.

An employer or owner may demonstrate that PACM (includes thermal system insulation, sprayed-on or troweled-on surfacing material, and debris in work areas where such material is present) does or does not contain asbestos by having conducted an inspection pursuant to requirements of the Asbestos Hazard Emergency Response Act (AHERA), 40 CFR 763, Subpart E, to be discussed below. Material testing is to include analysis of a minimum of at least three bulk samples of each homogeneous area of PACM collected in a randomly distributed manner. The tests, evaluation and sample collection are to be performed by an accredited/licensed inspector or by a CIH. The employer/building owner may demonstrate that a non-PACM material such as flooring material, including associated mastic and backing, does not contain asbestos based upon recognized analytical techniques. The material sampled may be designated as "asbestos free" if such material does not contain greater than 1% asbestos.

29 CFR 1910.134 - Respirator Program

This regulation outlines rules for respiratory protection in a specific work environment. A respirator program must be put into place when asbestos is disturbed (i.e. during the performance of response actions), and as necessitated by OSHA in the designation of a “regulated area" during the performance of Class I, II, or III work. A respirator program must be put into place with the implementation of an Operations and Maintenance (O&M) Program for the safe management of asbestos-containing material (ACM) in place.

29 CFR 1910.1001 - General Industry

This regulation addresses potential asbestos exposure involving general industry applications other than construction and renovation workers. This standard establishes minimum standards for the protection of workers involved in asbestos-related work or employees exposed to asbestos-contaminated places.

These standards include required work practices, engineering controls, permissible exposure limits, written programs for respiratory protection and medical surveillance, methods for compliance, hazard communication, housekeeping, competent person training and responsibilities, and required record keeping.

Building 74, Spinal Cord Injury Building, VA Medical Center, Dallas, Texas PAGE 9 OF 22

40 CFR 763, Subpart E - Asbestos in Schools / Commercial Buildings

In October, 1986, AHERA was signed into law. Included in this law were specific provisions directing the USEPA to establish regulations and address standards for identifying, evaluating and controlling asbestos materials in schools (40 CFR, Part 763 Subpart E). This rule requires that all nonprofit elementary and secondary schools, both public and private, inspect their school buildings for asbestos-containing building materials (ACBM), develop a plan to manage the asbestos for each school building, notify parents and staff regarding management plan availability, provide asbestos awareness training to school maintenance and custodial workers among other requirements of the law. AHERA required schools to perform building inspections and prepare management plans for asbestos-containing building materials (ACBM). Later, in 1995, OSHA adopted AHERA inspection protocols and procedures for use in public buildings (per 29 CFR 1910.1101). These protocols are used as the framework for OSHA inspections and inspection procedures utilized for this assessment.

40 CFR 61, Subpart M National Emissions Standards for Hazardous Air Pollutants (NESHAP)

This regulation provides for the control of environmental releases of asbestos caused by renovation and/or renovation activities. These regulations specify control requirements for most asbestos emissions and include work practices being followed to minimize the release of asbestos fibers during handling, removal and disposal of asbestos waste materials. NESHAP regulations are frequently enforced by a State or local agency. The NESHAP Standard requires:

No discharge of visible emissions to the outside air during the collection processing, packaging, or transporting of any asbestos-containing waste material;

Adequate wetting of asbestos-containing material; and

Processing of asbestos-containing waste material into non-friable forms.

25 TAC §295, Texas Asbestos Health Protection Rules

The State of Texas adopted rules (statutes) governing asbestos maintenance, removal and/or any related asbestos response action involving PACM or ACM. These rules, the Texas Asbestos Health Protection Rules (TAHPR), also include licensing requirements for individuals, consultants, abatement firms and building owners when asbestos is present, and/or when testing is performed to locate such material.

Rules were issued under 25 TAC 295.71. Every aspect of asbestos management from inspection to removal, and maintenance in place, is to be performed by a licensed individual trained in accordance with TAHPR requirements.

Building 74, Spinal Cord Injury Building, VA Medical Center, Dallas, Texas PAGE 10 OF 22

Beginning January 1, 2002, Texas Senate Bill 509, formally codified under 25 TAC 295.34 (l), required municipalities to verify that an asbestos survey has been conducted prior to issuing renovation/demolition permits for the interiors of public or commercial buildings. Such surveys must comply with state and federal laws governing asbestos surveys, must incorporate the areas of the building where renovation or demolition will occur, and must accurately describe the building materials where the renovation/demolition will take place.

In accordance with 25 TAC 295.34 (i), contractor installation of asbestos-containing products (unless there is no alternative building material) was prohibited. Additionally, contractors are required to have material safety data sheets (MSDS’s) for all newly installed building materials (25 TAC 295.34 (j)).

Maintaining and archiving the MSDS’s along with an architect or engineer signed statement stating the absence of ACM in new construction products will serve the purpose of a survey. This effort is intended to alleviate the need for an asbestos survey for the same areas, if they are to be renovated in the future.

Building 74, Spinal Cord Injury Building, VA Medical Center, Dallas, Texas PAGE 11 OF 22

7. Survey and Sample Collection Procedure

Based on United States Environmental Protection Agency (USEPA) guidance documents, CONXSIS considered that all material applications identified during the visual assessment were suspect ACM and sampled as described below.

Bulk samples were collected of any materials which were suspected of containing asbestos with the exception of fire doors. Fire doors were not sampled because the damage caused by sampling would render these materials friable and may also void the fire rating. Since these materials were not sampled, they should be assumed to be asbestos containing unless sampled and proven otherwise. Sampling of these assumed ACMs should be performed prior to any renovation or other activity that may cause a material disturbance.

Samples of the remaining suspect ACM were taken in accordance with USEPA recommendations.

The number and location of samples collected were based on the type of material, the manner of application, and the homogeneity of the ACM (similarity of color, texture, and type). Each sample was collected and placed into an individual sample container. The sample location was noted on the field survey form and assigned an individual identification number. This number was affixed to the sample container as the sample was collected. The survey form was also used to note the material type and general condition of the material. During the inspection, each suspect material's accessibility, location, and friability were recorded. This information was used to assess the potential hazard of the ACM and to prioritize response action recommendations.

The USEPA defines asbestos-containing materials (ACM) as those that contain greater than one percent asbestos. Friable materials are defined as those that can be crumbled or reduced to powder by hand pressure.

CONXSIS utilized the “positive-stop” method of sample analysis. In this method, analysis is stopped on a group of samples once the first positive (e.g., greater than 1% asbestos) sample is analyzed.

According to the USEPA, if one sample of a homogenous material is identified to be asbestos containing, the entire material must be considered asbestos containing. By using the positive-stop method, CONXSIS reduces the Client’s laboratory analysis cost by not analyzing the additional samples.

Samples collected were carried and submitted under Chain-of-Custody to Steve Moody Micro Services, Inc., Farmers Branch, Texas for analysis of asbestos using USEPA Method 40 CFR, Chapter 1, Part 763, Subpart F, Appendix A, also known as Polarized Light Microscopy (PLM). Steve Moody Micro Services, Inc. is certified by the National Voluntary Laboratory Accreditation Program (NVLAP) and licensed by the Texas Department of State Health Services.

Building 74, Spinal Cord Injury Building, VA Medical Center, Dallas, Texas PAGE 12 OF 22

8. Previous Survey / Plans Review

CONXSIS was provided with an existing asbestos survey conducted by Micro Air of Texas, Inc. dated June 14, 2010. Review of the Micro Air of Texas, Inc. asbestos survey identified the following information:

Micro Air performed a comprehensive asbestos survey of Building 74 on June 14, 2010.

Building 74 has a basement level with a swimming pool base, mechanical rooms, a pipe chase with a gravel floor, and a connecting corridor leading to Building 2. The first floor of the building is characterized by four wings (A-Wing, B-Wing, C-Wing and D-Wing). Improvements on the first floor include offices, a pharmacy, swimming pool, recreation center, physical therapy rooms, exam rooms and patient rooms. Building 74 does not have an attic. Finish materials inside Building 74 consist of concrete floors with vinyl floor tile, rubber flooring, sheet vinyl flooring, ceramic tile and carpeting. Walls are sheetrock with cove base; ceilings consist of several different types of lay-in tile. The exterior of the building is brick with a flat roof.

Fiberglass pipe insulation with white mastic wrap was observed throughout the building. Gray mastic is present on some of the metal HVAC ducts. Vibration dampeners were rubber.

A total of 125 bulk material samples were collected during this comprehensive survey, and all of the collected samples were analyzed by PLM.

No asbestos-containing material was identified.

Building 74, Spinal Cord Injury Building, VA Medical Center, Dallas, Texas PAGE 13 OF 22

9. Suspect ACM Materials Not Sampled

During the course of the property visit, CONXSIS performed a preliminary review of interior, accessible areas of the subject building for the presence of suspect asbestos-containing materials (ACMs). This limited asbestos survey was conducted for overview purposes only. Additional suspect materials may exist in concealed locations (behind walls and above ceilings, beneath the floors, within machinery, etc.). Also, not all suspect materials may have been sampled due to the condition or the location of the suspect materials. Destructive sampling of suspect ACMs was not performed. Suspect ACMs in an overall undamaged condition were not sampled, as that will damage the materials. CONXSIS will not be responsible for damaging materials or causing the materials to become friable. The USEPA defines asbestos-containing material as material containing greater than one percent asbestos. This review was not a pre-demolition/renovation survey or for regulatory submittal purposes.

No other suspect and/or presumed ACMs were observed within the subject building during the property visit.

Building 74, Spinal Cord Injury Building, VA Medical Center, Dallas, Texas PAGE 14 OF 22

10. Survey Sampling Results

The results of the Survey are presented in the tables on the following pages. The tables describe the entire suspect Asbestos-Containing Materials (ACMs) identified in the building and list respective sample numbers and laboratory results. Sample numbers presented in the tables correspond to the sample numbers on attached Laboratory Analysis Forms. Also presented in the tables is the estimated quantity and assessed friability for each suspect ACM. For each suspect material identified as ACM, the assessed hazard potential is presented along with CONXSIS’ recommended response action. Hazard potential for each material application is based on the material condition and accessibility to the public and maintenance personnel.

Glossary of Items for the following Table

Type of Asbestos (1) CH = Chrysotile AM = Amosite CR = Crocidolite AN = Anthophyllite TR = Tremolite AC = Actinolite ND = No Asbestos Detected PC = Point Count Method

Type of ACM (2) M = Miscellaneous S = Surfacing TSI = Thermal Systems Insulation

Friability (3) F = Friable NF = Non Friable

Physical Condition (4) G = Good D = Damaged SD = Significantly Damaged

Potential for Disturbance (5) NPD = No Potential for Disturbance PD = Potential for Disturbance PSD = Potential for Significant Disturbance

Assessment Category (6) 1 = Damaged or significantly damaged TSI ACBM, 2 = Damaged friable surfacing ACBM 3 = Significantly damaged friable surfacing ACBM 4 = Damaged or significantly damaged friable miscellaneous ACBM 5 = ACBM with potential for damaged 6 = ACBM potential for significant damage 7 = Any remaining friable ACBM or friable suspected

ACBM

X = not applicable

Unit of Measurement SF = Square Feet

LF = Linear Feet

Sample Description

Sample Location

Sample Analyzed

Yes/No

Approximate

ACM

Quantity

Assessment Category

Physical Condition

Friable Yes/No

Type of

ACM

% and Type of Asbestos Detected

Sample ID Potential For

Distrubance

Building 74, VA Medical Center

Homogeneous Area 1

Wall Covering, Light Purple

Yes M No G XND - Wall Covering74-201 PDMain Entrance along East Side

Yes M No G XND - Wall Covering74-202 PDOut Side Room 1A-101

Yes M No G XND - Wall Covering74-203 PDOut Side Room 1B-208

Homogeneous Area 2

Wall Covering, Dark Purple

Yes M No G XND - Wall Covering74-204 PDMain Lobby at Pharmacy

Yes M No G XND - Wall Covering74-205 PDOut Side Room 1D-119

Yes M No G XND - Wall Covering74-206 PDOut Side Room 1C-162

Sample Location

Sample Analyzed

Yes/No

Approximate

ACM

Quantity

Assessment Category

Physical Condition

Friable Yes/No

Type of

ACM

% and Type of Asbestos Detected

Sample ID Potential For

Distrubance

Building 74, VA Medical Center

Homogeneous Area 3

Wall Covering, White with Pink and Green Spotches

Yes M No G XND - Wall Covering74-207 PDMain Lobby at Pharmacy

Yes M No G XND - Wall Covering74-208 PDOut Side Room 1C-122

Yes M No G XND - Wall Covering74-209 PDOut Side Room 1C-162

Homogeneous Area 4

Wall Covering, Peach with Black Spotches

Yes M No G XND - Wall Covering74-210 PDOut side Room 1D-106B

Yes M No G XND - Wall Covering74-211 PDOut Side Room 1C-171

Yes M No G XND - Wall Covering74-212 PDOut Side Room 1C-151

Sample Location

Sample Analyzed

Yes/No

Approximate

ACM

Quantity

Assessment Category

Physical Condition

Friable Yes/No

Type of

ACM

% and Type of Asbestos Detected

Sample ID Potential For

Distrubance

Building 74, VA Medical Center

Homogeneous Area 5

Wall Covering, Tan and Brown Speckled

Yes M No G XND - Wall Covering74-213 PDRoom 1B-220 by Water Fountain

Yes M No G XND - Wall Covering74-214 PDOut Side Room 1C-154C

Yes M No G XND - Wall Covering74-215 PDRoom 1C-154 @ Room 1C-154A

Homogeneous Area 6

Wall Covering, Beige with Green Spotches

Yes M No G XND - Wall Covering74-216 PDRoom 1C-154E

Yes M No G XND - Wall Covering74-217 PDRoom 1C-154 West Wing

Yes M No G XND - Wall Covering74-218 PDRoom 1C-154

Sample Location

Sample Analyzed

Yes/No

Approximate

ACM

Quantity

Assessment Category

Physical Condition

Friable Yes/No

Type of

ACM

% and Type of Asbestos Detected

Sample ID Potential For

Distrubance

Building 74, VA Medical Center

Homogeneous Area 7

Covebase and Associated Mastic, Peach Cove Base

Yes M No G XND - Cove Base ND - Yellow Mastic

74-219 PDRoom 1C-154 West Wing

Yes M No G XND - Cove Base ND - Yellow Mastic

74-220 PDRoom 1C-127

Yes M No G XND - Cove Base ND - Yellow Mastic

74-221 PDOut Side Room 1D-119

Homogeneous Area 8

Covebase and Associated Mastic, Purple Cove Base

Yes M No G XND - Cove Base ND - Yellow Mastic

74-222 PDOut Side Room 220 by Water Fountain

Yes M No G XND - Cove Base ND - Yellow Mastic

74-223 PDOut Side Room 1C-171

Yes M No G XND - Cove Base ND - Yellow Mastic

74-224 PDOut Side Room 1B-224

Sample Location

Sample Analyzed

Yes/No

Approximate

ACM

Quantity

Assessment Category

Physical Condition

Friable Yes/No

Type of

ACM

% and Type of Asbestos Detected

Sample ID Potential For

Distrubance

Building 74, VA Medical Center

Homogeneous Area 9

Wall Covering, Green with Horizontal Pattern

Yes M No G XND - Wall Covering74-225 PDRoom 1C-154, Large MTS Room Behind Door

Yes M No G XND - Wall Covering74-226 PDRoom 1C-154, Large MTS Room Behind Suite Door

Yes M No G XND - Wall Covering74-227 PDRoom 1C-154, East Wall Small MTS Room Across from Large MTS Room

Homogeneous Area 10

Carpet and Associated Mastic, 2' X 2' Squares, Green

Yes M No G XND - Carpet ND - Carpet Pad ND - Yellow Mastic

74-228 PDRoom 1C-154, Large MTS room North

Yes M No G XND - Carpet ND - Carpet Pad ND - Yellow Mastic

74-229 PDRoom 1C-154, Large MTS room South

Yes M No G XND - Carpet ND - Carpet Pad ND - Yellow Mastic

74-230 PDRoom 1C-154, Small MTS Room Across from Large MTS Room

Sample Location

Sample Analyzed

Yes/No

Approximate

ACM

Quantity

Assessment Category

Physical Condition

Friable Yes/No

Type of

ACM

% and Type of Asbestos Detected

Sample ID Potential For

Distrubance

Building 74, VA Medical Center

Homogeneous Area 11

Carpet and Associated Mastic, 2' X 2' Squares, Blue Green with Circle Pattern

Yes M No G XND - Carpet ND - Carpet Pad ND - Yellow Mastic

74-231 PDRoom 1c-154, Corridor North

Yes M No G XND - Carpet ND - Carpet Pad ND - Yellow Mastic

74-232 PDRoom 1c-154, Corridor Middle

Yes M No G XND - Carpet ND - Carpet Pad ND - Yellow Mastic

74-233 PDRoom 1c-154, Corridor South

Homogeneous Area 12

Non Skid Strip, Black Yes M No G XND - Non Skid Strip ND - Clear Mastic

74-234 PDRoom 1B-111AA

Yes M No G XND - Non Skid Strip ND - Clear Mastic

74-235 PDRoom 1B-111AB

Yes M No G XND - Non Skid Strip ND - Clear Mastic

74-236 PDRoom 1B-111AC

Sample Location

Sample Analyzed

Yes/No

Approximate

ACM

Quantity

Assessment Category

Physical Condition

Friable Yes/No

Type of

ACM

% and Type of Asbestos Detected

Sample ID Potential For

Distrubance

Building 74, VA Medical Center

Homogeneous Area 13

Ceramic Tile and Associated Grout, 12" X 12" Tile

Yes M No G XND - Ceramic Tile ND - Grout ND - Cream Mastic

74-237 PDRoom 1B-111AB

Yes M No G XND - Ceramic Tile ND - Grout

74-238 PDRoom 1C-154E

Yes M No G XND - Ceramic Tile ND - Grout

74-239 PDRoom 1C-154E

Homogeneous Area 14

Carpet and Associated Mastic, 2' X 2' Squares, Maroon with Stripe Pattern

Yes M No G XND - Carpet ND - Carpet Pad ND - Yellow Mastic

74-240 PDRoom 1B-120A

Yes M No G XND - Carpet ND - Carpet Pad ND - Yellow Mastic

74-241 PDRoom 1A-101

Yes M No G XND - Carpet ND - Carpet Pad

74-242 PDRoom 1A-142

Sample Location

Sample Analyzed

Yes/No

Approximate

ACM

Quantity

Assessment Category

Physical Condition

Friable Yes/No

Type of

ACM

% and Type of Asbestos Detected

Sample ID Potential For

Distrubance

Building 74, VA Medical Center

Homogeneous Area 15

Covebase and Associated Mastic, Maroon

Yes M No G XND - Cove Base ND - Yellow Mastic

74-243 PDRoom 1B-120A

Yes M No G XND - Cove Base ND - Yellow Mastic

74-244 PDRoom 1A-101

Yes M No G XND - Cove Base ND - Yellow Mastic

74-245 PDRoom 1A-142

Homogeneous Area 16

Carpet and Associated Mastic, 2' X 2' Squares, Purple

Yes M No G XND - Carpet ND - Carpet Pad ND - Yellow Mastic

74-246 PDRoom 1B-220

Yes M No G XND - Carpet ND - Carpet Pad ND - Yellow Mastic

74-247 PDSection C Nurse's Station

Yes M No G XND - Carpet ND - Carpet Pad

74-248 PDRoom 1D-100

Sample Location

Sample Analyzed

Yes/No

Approximate

ACM

Quantity

Assessment Category

Physical Condition

Friable Yes/No

Type of

ACM

% and Type of Asbestos Detected

Sample ID Potential For

Distrubance

Building 74, VA Medical Center

Homogeneous Area 17

Wall Covering, Maroon Speckled

Yes M No G XND - Wall Covering74-249 PDRoom 1A-142, Behind Entrance

Yes M No G XND - Wall Covering74-250 PDRoom 1A-142A, Door Way

Yes M No G XND - Wall Covering74-251 PDRoom 1A-142, SE Corner

Homogeneous Area 18

Wall Covering, Beige with Maroon Swirls

Yes M No G XND - Wall Covering74-252 PDRoom 1A-142, Behind Entrance

Yes M No G XND - Wall Covering74-253 PDRoom 1A-142 @ Room 1A-142B

Yes M No G XND - Wall Covering ND - Joint Compound

74-254 PDRoom 1A-142 @ Room 1A-142D

Sample Location

Sample Analyzed

Yes/No

Approximate

ACM

Quantity

Assessment Category

Physical Condition

Friable Yes/No

Type of

ACM

% and Type of Asbestos Detected

Sample ID Potential For

Distrubance

Building 74, VA Medical Center

Homogeneous Area 19

Carpet and Associated Mastic, 2' X 2' Squares, Maroon Multi Color

Yes M No G XND - Carpet ND - Carpet Pad ND - Yellow Mastic

74-255 PDRoom 1A-142, Behind Entrance

Yes M No G XND - Carpet ND - Carpet Pad ND - Yellow Mastic

74-256 PDRoom 1A-142, SE Corner

Yes M No G XND - Carpet ND - Carpet Pad ND - Yellow Mastic

74-257 PDRoom 1C-143

Homogeneous Area 20

Caulking, Gray, Wall Filler

Yes M No G XND - Caulking74-258 PDRoom BA-112

Homogeneous Area 21

Sink Undercoating, Black

Yes S No G XND - Sink Undercoating

74-259 PDRoom 1D-120

Yes S No G XND - Sink Undercoating

74-260 PDRoom 1D-120

Sample Location

Sample Analyzed

Yes/No

Approximate

ACM

Quantity

Assessment Category

Physical Condition

Friable Yes/No

Type of

ACM

% and Type of Asbestos Detected

Sample ID Potential For

Distrubance

Building 74, VA Medical Center

Homogeneous Area 22

Wall Covering, Blue Orange and Green (Blue)

Yes M No G XND - Wall Covering74-261 PDRoom BA-130

Wall Covering, Blue Orange and Green (Orange)

Yes M No G XND - Wall Covering74-262 PDRoom BA-130

Wall Covering, Blue Orange and Green (Green)

Yes M No G XND - Wall Covering74-263 PDRoom BA-130

Homogeneous Area 23

Covebase and Associated Mastic, Blue Green Cove Base

Yes M No G XND - Cove Base ND - Yellow Mastic

74-264 PDRoom BA-132

Yes M No G XND - Cove Base ND - Yellow Mastic

74-265 PDRoom BA-132

Yes M No G XND - Cove Base

74-266 PDRoom BA-132

Sample Location

Sample Analyzed

Yes/No

Approximate

ACM

Quantity

Assessment Category

Physical Condition

Friable Yes/No

Type of

ACM

% and Type of Asbestos Detected

Sample ID Potential For

Distrubance

Building 74, VA Medical Center

Homogeneous Area 24

Caulking, White, Around Restroom Fixtures (Sink)

Yes M No G XND - Caulking74-267 PDRoom 1A-115

Caulking, White, Around Restroom Fixtures (Urinal)

Yes M No G XND - Caulking74-268 PDRoom 1A-113

Caulking, White, Around Restroom Fixtures (Toilet)

Yes M No G XND - Caulking74-269 PDRoom 1C-154E

Homogeneous Area 25

Brick and Associated Mortar, Red Brick

Yes M No G XND - Brick ND - Mortar

74-270 PDNW Corner

Yes M No G XND - Brick ND - Mortar

74-271 PDNE Corner

Yes M No G XND - Brick ND - Mortar

74-272 PDSE Corner

Sample Location

Sample Analyzed

Yes/No

Approximate

ACM

Quantity

Assessment Category

Physical Condition

Friable Yes/No

Type of

ACM

% and Type of Asbestos Detected

Sample ID Potential For

Distrubance

Building 74, VA Medical Center

Homogeneous Area 26

Caulking, Around Door and Window Frames

Yes M No G XND - Caulking74-273 PDWest Entry

Yes M No G XND - Caulking74-274 PDNorth Central Window

Yes M No G XND - Caulking74-275 PDEast Entry

Homogeneous Area 27

Expansion Joint, Red Yes M No G XND - Expansion Material

74-276 PDEast Side

Yes M No G XND - Expansion Material

74-277 PDNorth Side West End

Yes M No G XND - Expansion Material

74-278 PDNorth Side East End

Sample Location

Sample Analyzed

Yes/No

Approximate

ACM

Quantity

Assessment Category

Physical Condition

Friable Yes/No

Type of

ACM

% and Type of Asbestos Detected

Sample ID Potential For

Distrubance

Building 74, VA Medical Center

Homogeneous Area 28

Roof, Membrane Roof, Flat Roof

Yes M No G XND - Foam ND - Rubber Membrane

74-279 PDOver Pool

Yes M No G XND - Foam ND - Rubber Membrane

74-280 PDEast Side South End

Yes M No G XND - Foam ND - Rubber Membrane

74-281 PDEast Side North End

Homogeneous Area 29

Roof, Sealer, at Penetrations and Seams

Yes M No G XND - Roof Sealant74-282 PDSE Corner

Yes M No G XND - Roof Sealant74-283 PDNE Corner

Yes M No G XND - Roof Sealant74-284 PDNW Corner

Sample Location

Sample Analyzed

Yes/No

Approximate

ACM

Quantity

Assessment Category

Physical Condition

Friable Yes/No

Type of

ACM

% and Type of Asbestos Detected

Sample ID Potential For

Distrubance

Building 74, VA Medical Center

Homogeneous Area 30

Wall Covering, Gray with Gray Spots

Yes M No G XND - Wall Covering74-285 PDRoom 1B-120A

Yes M No G XND - Wall Covering74-286 PDRoom 1B-120A

Yes M No G XND - Wall Covering74-287 PDRoom 120A

1. CH = Chrysotile; AM = Amosite; CR = Crocidolite; AN = Anthophyllite; TR = Tremolite; AC = Actinolite; ND = No Asbestos Detected; or PC = Point Count Method

2. M = Miscellaneous; S = Surfacing; or TSI = Thermal Systems Insulation

3. F = Friable or NF = Non Friable

4. G = Good; D = Damaged; or SD = Significantly Damaged

5. NPD = No Potential for Disturbance; PD = Potential for Disturbance; or PSD = Potential for Significant Disturbance

6. 1 = Damaged or significantly damaged TSI ACBM, 2 = Damaged friable surfacing ACBM, 3 = Significantly damaged friable surfacing ACBM, 4 = Damaged or significantly damaged friable miscellaneous ACBM, 5 = ACBM with potential for damage, 6 = ACBM potential for significant damage, 7 = Any remaining friable ACBM or friable suspected ACBM, or X = not applicable

SF = Square Feet LF = Linear Feet

11. Appendices

Appendix A— Laboratory Results and Chain of Custody Appendix B— ACM Sample Location Drawings Appendix C— Prior ACM Survey Reports Appendix D— ACM Location Drawings Appendix E— Certificates and Licenses

Appendix A

Laboratory Results and Chain of Custody

PLM Summary Report

Client :

Project :

Project # :

Identification :

Test Method :

ConXsis

VA Medical Center Dallas, Building #74

10-002-01

Asbestos, Bulk Sample Analysis

Polarized Light Microscopy / Dispersion Staining (PLM/DS)

EPA Method 600 / R-93 / 116

Sample Number Client Sample Description / Location Asbestos Content

Sample Date :

On 10/15/2010, eighty seven (87) bulk material samples were submitted by a representative of ConXsis for asbestos analysis by PLM/DS. The PLM

Detail Report is attached; additional information may be found therein. The results are summarized below:

Lab Job No. :

Report Date :

10B-10553

10/14/2010

10/19/2010

2051 Valley View Lane

Farmers Branch, TX 75234 Phone: (972) 241-8460

Steve Moody Micro Services, LLC NVLAP Lab No. 102056

TDSHS License No. 30-0084

74-201 Wall Covering (Light Purple) None Detected - Wall Covering

74-202 Wall Covering (Light Purple) None Detected - Wall Covering

74-203 Wall Covering (Light Purple) None Detected - Wall Covering

74-204 Wall Covering (Dark Purple) None Detected - Wall Covering

74-205 Wall Covering (Dark Purple) None Detected - Wall Covering

74-206 Wall Covering (Dark Purple) None Detected - Wall Covering

74-207 Wall Covering (White with Pink and Green Splotches) None Detected - Wall Covering

74-208 Wall Covering (White with Pink and Green Splotches) None Detected - Wall Covering

74-209 Wall Covering (White with Pink and Green Splotches) None Detected - Wall Covering

74-210 Wall Covering (Peach with Black Specks) None Detected - Wall Covering

74-211 Wall Covering (Peach with Black Specks) None Detected - Wall Covering

74-212 Wall Covering (Peach with Black Specks) None Detected - Wall Covering

74-213 Wall Covering (Tan and Brown Speckled) None Detected - Wall Covering

74-214 Wall Covering (Tan and Brown Speckled) None Detected - Wall Covering

74-215 Wall Covering (Tan and Brown Speckled) None Detected - Wall Covering

74-216 Wall Covering (Beige with Green Splotches) None Detected - Wall Covering

74-217 Wall Covering (Beige with Green Splotches) None Detected - Wall Covering

74-218 Wall Covering (Beige with Green Splotches) None Detected - Wall Covering

74-219 Cove Base (Peach) and Mastic None Detected - Cove Base

None Detected - Yellow Mastic

74-220 Cove Base (Peach) and Mastic None Detected - Cove Base

None Detected - Yellow Mastic

Project :

Project # :

Identification :

Test Method :

ConXsis

VA Medical Center Dallas, Building #74

10-002-01

Asbestos, Bulk Sample Analysis

Polarized Light Microscopy / Dispersion Staining (PLM/DS)

EPA Method 600 / R-93 / 116

Sample Number Client Sample Description / Location Asbestos Content

Sample Date :

On 10/15/2010, eighty seven (87) bulk material samples were submitted by a representative of ConXsis for asbestos analysis by PLM/DS. The PLM

Detail Report is attached; additional information may be found therein. The results are summarized below:

Lab Job No. :

Report Date :

10B-10553

10/14/2010

10/19/2010

2051 Valley View Lane

Farmers Branch, TX 75234 Phone: (972) 241-8460

Steve Moody Micro Services, LLC NVLAP Lab No. 102056

TDSHS License No. 30-0084

74-221 Cove Base (Peach) and Mastic None Detected - Cove Base

None Detected - Yellow Mastic

74-222 Cove Base (Purple) and Mastic None Detected - Cove Base

None Detected - Yellow Mastic

74-223 Cove Base (Purple) and Mastic None Detected - Cove Base

None Detected - Yellow Mastic

74-224 Cove Base (Purple) and Mastic None Detected - Cove Base

None Detected - Yellow Mastic

74-225 Wall Covering (Green with Horizontal Pattern) None Detected - Wall Covering

74-226 Wall Covering (Green with Horizontal Pattern) None Detected - Wall Covering

74-227 Wall Covering (Green with Horizontal Pattern) None Detected - Wall Covering

74-228 2' x 2' Carpet Squares (Green) and Mastic None Detected - Carpet

None Detected - Carpet Pad

None Detected - Yellow Mastic

74-229 2' x 2' Carpet Squares (Green) and Mastic None Detected - Carpet

None Detected - Carpet Pad

None Detected - Yellow Mastic

74-230 2' x 2' Carpet Squares (Green) and Mastic None Detected - Carpet

None Detected - Carpet Pad

None Detected - Yellow Mastic

74-231 2' x 2' Carpet Squares (Blue Green with Circle Pattern) and

Mastic

None Detected - Carpet

None Detected - Carpet Pad

None Detected - Yellow Mastic

74-232 2' x 2' Carpet Squares (Blue Green with Circle Pattern) and

Mastic

None Detected - Carpet

None Detected - Carpet Pad

None Detected - Yellow Mastic

74-233 2' x 2' Carpet Squares (Blue Green with Circle Pattern) and

Mastic

None Detected - Carpet

None Detected - Carpet Pad

Project :

Project # :

Identification :

Test Method :

ConXsis

VA Medical Center Dallas, Building #74

10-002-01

Asbestos, Bulk Sample Analysis

Polarized Light Microscopy / Dispersion Staining (PLM/DS)

EPA Method 600 / R-93 / 116

Sample Number Client Sample Description / Location Asbestos Content

Sample Date :

On 10/15/2010, eighty seven (87) bulk material samples were submitted by a representative of ConXsis for asbestos analysis by PLM/DS. The PLM

Detail Report is attached; additional information may be found therein. The results are summarized below:

Lab Job No. :

Report Date :

10B-10553

10/14/2010

10/19/2010

2051 Valley View Lane

Farmers Branch, TX 75234 Phone: (972) 241-8460

Steve Moody Micro Services, LLC NVLAP Lab No. 102056

TDSHS License No. 30-0084

74-234 Non Skid Strips None Detected - Non-skid Strip

None Detected - Clear Mastic

74-235 Non Skid Strips None Detected - Non-skid Strip

None Detected - Clear Mastic

74-236 Non Skid Strips None Detected - Non-skid Strip

None Detected - Clear Mastic

74-237 Ceramic Tile and Grout None Detected - Ceramic Tile

None Detected - Grout

None Detected - Cream Mastic

74-238 Ceramic Tile and Grout None Detected - Ceramic Tile

None Detected - Grout

74-239 Ceramic Tile and Grout None Detected - Ceramic Tile

None Detected - Grout

74-240 2' x 2' Carpet Squares (Maroon with Stripe Pattern) and

Mastic

None Detected - Carpet

None Detected - Carpet Pad

None Detected - Yellow Mastic

74-241 2' x 2' Carpet Squares (Maroon with Stripe Pattern) and

Mastic

None Detected - Carpet

None Detected - Carpet Pad

None Detected - Yellow Mastic

74-242 2' x 2' Carpet Squares (Maroon with Stripe Pattern) and

Mastic

None Detected - Carpet

None Detected - Carpet Pad

None Detected - Yellow Mastic

74-243 Cove Base (Maroon) and Mastic None Detected - Cove Base

None Detected - Yellow Mastic

74-244 Cove Base (Maroon) and Mastic None Detected - Cove Base

None Detected - Yellow Mastic

74-245 Cove Base (Maroon) and Mastic None Detected - Cove Base

Project :

Project # :

Identification :

Test Method :

ConXsis

VA Medical Center Dallas, Building #74

10-002-01

Asbestos, Bulk Sample Analysis

Polarized Light Microscopy / Dispersion Staining (PLM/DS)

EPA Method 600 / R-93 / 116

Sample Number Client Sample Description / Location Asbestos Content

Sample Date :

On 10/15/2010, eighty seven (87) bulk material samples were submitted by a representative of ConXsis for asbestos analysis by PLM/DS. The PLM

Detail Report is attached; additional information may be found therein. The results are summarized below:

Lab Job No. :

Report Date :

10B-10553

10/14/2010

10/19/2010

2051 Valley View Lane

Farmers Branch, TX 75234 Phone: (972) 241-8460

Steve Moody Micro Services, LLC NVLAP Lab No. 102056

TDSHS License No. 30-0084

74-246 2' x 2' Carpet Squares (Purple) and Mastic None Detected - Carpet

None Detected - Carpet Pad

None Detected - Yellow Mastic

74-247 2' x 2' Carpet Squares (Purple) and Mastic None Detected - Carpet

None Detected - Carpet Pad

None Detected - Yellow Mastic

74-248 2' x 2' Carpet Squares (Purple) and Mastic None Detected - Carpet

None Detected - Carpet Pad

None Detected - Yellow Mastic

74-249 Wall Covering (Maroon Speckled) None Detected - Wall Covering

74-250 Wall Covering (Maroon Speckled) None Detected - Wall Covering

74-251 Wall Covering (Maroon Speckled) None Detected - Wall Covering

74-252 Wall Covering (Beige with Maroon Swirls) None Detected - Wall Covering

74-253 Wall Covering (Beige with Maroon Swirls) None Detected - Wall Covering

74-254 Wall Covering (Beige with Maroon Swirls) None Detected - Joint Compound

None Detected - Wall Covering

74-255 2' x 2' Carpet Squares (Maroon Multicolored) and Mastic None Detected - Carpet

None Detected - Carpet Pad

None Detected - Yellow Mastic

74-256 2' x 2' Carpet Squares (Maroon Multicolored) and Mastic None Detected - Carpet

None Detected - Carpet Pad

None Detected - Yellow Mastic

74-257 2' x 2' Carpet Squares (Maroon Multicolored) and Mastic None Detected - Carpet

None Detected - Carpet Pad

None Detected - Yellow Mastic

74-258 Caulk (Gray), Wall Filler None Detected - Caulking

74-259 Sink Undercoating (Black) None Detected - Sink Undercoating

74-260 Sink Undercoating (Black) None Detected - Sink Undercoating

Project :

Project # :

Identification :

Test Method :

ConXsis

VA Medical Center Dallas, Building #74

10-002-01

Asbestos, Bulk Sample Analysis

Polarized Light Microscopy / Dispersion Staining (PLM/DS)

EPA Method 600 / R-93 / 116

Sample Number Client Sample Description / Location Asbestos Content

Sample Date :

On 10/15/2010, eighty seven (87) bulk material samples were submitted by a representative of ConXsis for asbestos analysis by PLM/DS. The PLM

Detail Report is attached; additional information may be found therein. The results are summarized below:

Lab Job No. :

Report Date :

10B-10553

10/14/2010

10/19/2010

2051 Valley View Lane

Farmers Branch, TX 75234 Phone: (972) 241-8460

Steve Moody Micro Services, LLC NVLAP Lab No. 102056

TDSHS License No. 30-0084

74-261 Wall Covering (Blue, Orange, and Green) None Detected - Wall Covering

74-262 Wall Covering (Blue, Orange, and Green) None Detected - Wall Covering

74-263 Wall Covering (Blue, Orange, and Green) None Detected - Wall Covering

74-264 Cove Base (Blue Green) and Mastic None Detected - Cove Base

None Detected - Yellow Mastic

74-265 Cove Base (Blue Green) and Mastic None Detected - Cove Base

None Detected - Yellow Mastic

74-266 Cove Base (Blue Green) and Mastic None Detected - Cove Base

None Detected - Yellow Mastic

74-267 Caulk, Restroom Fixtures None Detected - Caulking

74-268 Caulk, Restroom Fixtures None Detected - Caulking

74-269 Caulk, Restroom Fixtures None Detected - Caulking

74-270 Brick (Red) and Mortar None Detected - Brick

None Detected - Mortar

74-271 Brick (Red) and Mortar None Detected - Brick

None Detected - Mortar

74-272 Brick (Red) and Mortar None Detected - Brick

None Detected - Mortar

74-273 Caulk, Door and Window Frames None Detected - Caulking

74-274 Caulk, Door and Window Frames None Detected - Caulking

74-275 Caulk, Door and Window Frames None Detected - Caulking

74-276 Expansion Joint Material None Detected - Expansion Material

74-277 Expansion Joint Material None Detected - Expansion Material

74-278 Expansion Joint Material None Detected - Expansion Material

Project :

Project # :

Identification :

Test Method :

ConXsis

VA Medical Center Dallas, Building #74

10-002-01

Asbestos, Bulk Sample Analysis

Polarized Light Microscopy / Dispersion Staining (PLM/DS)

EPA Method 600 / R-93 / 116

Sample Number Client Sample Description / Location Asbestos Content

Sample Date :

On 10/15/2010, eighty seven (87) bulk material samples were submitted by a representative of ConXsis for asbestos analysis by PLM/DS. The PLM

Detail Report is attached; additional information may be found therein. The results are summarized below:

Lab Job No. :

Report Date :

10B-10553

10/14/2010

10/19/2010

2051 Valley View Lane

Farmers Branch, TX 75234 Phone: (972) 241-8460

Steve Moody Micro Services, LLC NVLAP Lab No. 102056

TDSHS License No. 30-0084

74-279 Roof Membrane with Insulation None Detected - Foam

None Detected - Rubber Membrane

74-280 Roof Membrane with Insulation None Detected - Foam

None Detected - Rubber Membrane

74-281 Roof Membrane with Insulation None Detected - Foam

None Detected - Rubber Membrane

74-282 Roof Sealer, on Seams and Penetrations None Detected - Roof Sealant

74-283 Roof Sealer, on Seams and Penetrations None Detected - Roof Sealant

74-284 Roof Sealer, on Seams and Penetrations None Detected - Roof Sealant

74-285 Wall Covering (Gray Cloth) None Detected - Wall Covering

74-286 Wall Covering (Gray Cloth) None Detected - Wall Covering

74-287 Wall Covering (Gray Cloth) None Detected - Wall Covering

Brian R. SchmidtAnalyst(s):

Lab Director : Steve Moody Approved Signatory :

Thank you for choosing Steve Moody Micro Services

These samples were analyzed by layers. Quantification, unless otherwise noted, is performed by calibrated visual estimate. Results may not be reproduced except in full. This test report relates only to the samples tested. These test results do not imply endorsement by NVLAP or any agency of the U.S. Government. Accredited by the

National Voluntary Laboratory Accreditation Program for Bulk Asbestos Fiber Analysis under Lab Code 102056.

Lab Manager : Bruce Crabb Approved Signatory :

PLM Detail Report

Project # : 10-002-01

Sample Number Layer Components % Of

Sample

Analysis

Date

% of

Layer Analyst

Supplement to PLM Summary Report

Client :

Project :

ConXsis

VA Medical Center Dallas, Building #74

Lab Job No. :

Report Date :

10B-10553

10/19/2010

2051 Valley View Lane

Farmers Branch, TX 75234 Phone: (972) 241-8460

Steve Moody Micro Services, LLC NVLAP Lab No. 102056

TDSHS License No. 30-0084

Synthetic Fibers74-201 Wall Covering (Light Purple) 100% 10/1815% BS

Cotton Fibers74-201 Wall Covering (Light Purple) 100% 10/1815% BS

Vinyl Binders74-201 Wall Covering (Light Purple) 100% 10/1870% BS

Synthetic Fibers74-202 Wall Covering (Light Purple) 100% 10/1815% BS

Cotton Fibers74-202 Wall Covering (Light Purple) 100% 10/1815% BS

Vinyl Binders74-202 Wall Covering (Light Purple) 100% 10/1870% BS

Synthetic Fibers74-203 Wall Covering (Light Purple) 100% 10/1815% BS

Cotton Fibers74-203 Wall Covering (Light Purple) 100% 10/1815% BS

Vinyl Binders74-203 Wall Covering (Light Purple) 100% 10/1870% BS

Synthetic Fiber Mesh74-204 Wall Covering (Dark Purple) 100% 10/18100% BS

Synthetic Fiber Mesh74-205 Wall Covering (Dark Purple) 100% 10/18100% BS

Synthetic Fiber…