This document provides details on a federal contract opportunity for long term spinal cord injury services. The solicitation number is 36C10F22R0045 and is being issued by the Department of Veterans Affairs Office of Construction and Facilities Management for Y1DA--LTSCI VA Dallas 549-820B Long Term Spinal Cord Injury services. The opportunity type is a solicitation for LONG TERM SPINAL CORD INJURY services at location 549-820B. No other details are provided on response dates, pricing terms, set asides, or incumbent. The related file ADD-02 DWGs.pdf presumably contains drawings but its content is not specified.
View the file
Other files
Show 40 more
Latest 50 of 117 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
05/31/2023
Page Southerland Page, Inc.
Firm Registration No.15868
05/31/2023
Page Southerland Page, Inc.
Firm Registration No.15868
UP
DN1
83-PP-404
F
F
D
D
16.2
17.1
16.6
MATCHLINE
SEE
F4 83-PP-1B1d
83 - EOI
1/2" DCW
1 1/2" DCW
1/2" DHW
83-PP-403
MG4
MG4
MG4
83-PP-403
PP11
PP12
2"DHW
3"DCW
2"NPW
3"D
CW
2"N
PW
1 1/2"MA 1 1/2"O2
1"O 2 1 1/2"M
V1"M A
1"DHW
1"DCW
1"DHW
1 1/2"DCW
3/4"DHW
3/4"DCW
1 1/2"DCW
3/4"DHW
1 1/2"O2
2"MA
2"MV
1/2"DCW
1/2"DHW
2"DHW
4"DCW
1 1/2"NPW
2"NPW
2 1/2"DCW
1 1/4"DHW
3/4"NPW
2 1/2"DCW
1 1/4"DHW
1"DHWR
3/4"NPW
2 1/2"DCW
1 1/4"DHW
3"DCW
2"DHW
2"NPW
1"DHW
R
1"DHWR
1"D
HWR
1"DHWR
CONTRACTOR TO COORDINATE
WITH LANDSCAPE DRAWINGS
AND MAKE CONNECTIONS AS
REQUIRED TO COMPLETE THE
IRRIGATION SYSTEM
CONTRACTOR TO COORDINATE
WITH LANDSCAPE DRAWINGS
AND MAKE CONNECTIONS AS
REQUIRED TO COMPLETE THE
IRRIGATION SYSTEM
3"D
CW
2"D
HW
2"N
PW
1"D
HWR
1 1/2"M V
1"O
1"M A
1 1/2"M V
1 1/2"O
1 1/2"M A
1 1/2"M V
1 1/2"M A
1 1/2"O
1 1/2"M A
1 1/2"M V
1 1/2"O
3"D
CW
2"D
HW
2"N
PW
1"D
HWR
1"DHWR
3/4"NPW
2"N
PW
3"D
CW1"DHWR
2"D
HW
1"DHWR
2"D
HW
3"D
CW
1"DHWR
2"D
HW
3"D
CW
PP20
PP20
2"NPW
2"D
HW
1"DHWR
3"D
CW
2"
NPW
2"
DHW
1"
DHW
R
3"
DCW
1"DCW
1"DHW
3"
DCW
2"
NPW
2"
DHW
1"
DHW
R
3"
DCW
2"
NPW
2"
DHW
1"
DHW
R
1"M A1 1/2"M
V
1"O2
2" M
A
2" M
V
1 1 /2
"O
PP20
1"DHWR
1"DHW
R
2"DHW
M A
T C
H
LI
N E
S E
E
F
3-
P P
-1 B a
1"NPW
3/4"NPW
83-PP-302
83-PP-301 8
83-PP-303
83-PP-303
83-PP-303
83-PP-301
83-PP-303
83-PP-303
83-PP-303
83-PP-303
83-PP-303
83-PP-303
1 1/2"O2
3/4"NPW
1"DHW
R
1 1/4"DHW
3/4"DHW
1 1/2"DCW
3/4"N P
W1 1/4"D H
W
1"D H
W R1"D
C W
1"D H
W
3/4"D C
W
3/4"D H
W
2" NPW UP
MATCHLIN
E
SEE
F4
83-P P-1
B1d
MATCHLINE
SEE
F4 83-PP-1B1a
KEYED NOTES
DESCRIPTIONNUMBER
D A
T E
S
A M
P
Drawing Title
Approved Project Director:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
PSP 309070 Revisions Date
ARCHITECT/ENGINEERS: Office of
Construction and
Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
FILE NAME
Project Abbreviation
F
E
D
C
B
A
F
IL
E N
A M
E
KEY PLAN
FULLY SPRINKLERED
(NOT TO SCALE)
Page Southerland Page, LLP.
1800 Main Street Suite 123
Dallas, TX 75201 pagethink.com
TEL
FAX
ARCHITECTURE / ENGINEERING / INTERIORS / CONSULTING
Austin / Dallas / Denver / Houston / Washington DC /
International Affiliate Offices
214 522 3900
214 522 4380
DWG
C
U se rs \b k in m a n \D o c u m e n ts
\3 b P -S
C I- R -C
E N
T R A L b k in m a n R K W
J .r v t
/3
/2
:2 :3
P
M
C:\Users\bkinman\Documents\309070b3P-SCI-R18-CENTRAL_bkinmanR4KWJ.rvt
83-PP-1B1b
CONSTRUCTION
VA-LTSCIF-D
RCM
549-820B
EGH
PLUMBING SYSTEMS - FLOOR PLAN - LEVEL B1 AREA B
LONG TERM SPINAL CORD INJURY
VA NORTH TEXAS HEALTH CARE SYSTEM
4500 S. LANCASTER RD. DALLAS, TX 75216OFFICE OF CONSTRUCTION AND FACILITIES
MANAGEMENT DIRECTOR, CENTRAL REGION
06 MAY 2021
BID PACKAGE B
SCALE: 1/8" = 1'-0"F4 PLUMBING SYSTEMS - FLOOR PLAN - LEVEL B1 AREA B
BF
C
D
G
A
H
E
0' 16'4' 8' 32'
NORTH
PLAN
MG4 1" AIR, OXYGEN, & VACUUM UP TO ZONE
VALVE BOX ON 1ST FLOOR.
PP11 3/4" & 1" NPW TAPS FOR IRRIGATION
CONTRACTOR TO CONNECT. EACH TAP
PROVIDED WITH BALL DRIP.
PP12 2"NPW LINE FOR MAKE-UP TO FIRE
SUPPLY TANK. DROP INTO TOP OF TANK -
COORDINATE LOCATION WITH FIRE PUMP
EQUIPMENT. INTERLOCK FILL VALVE
WITH FIRE TANK SUPPLY CONTROLS.
PP20 DOMESTIC HOT WATER RECIRCULATION
VALVE SET TO A MINIMUM FLOW RATE OF
5.0 GPM UNO. REFER TO DETAIL.
1 ADDENDUM 1 31 MAY 2023
P
83/31vt
P
83/20vt
P
83/21vt
SAN
SAN
V
V
SAN
SAN
SAN
SAN
SAN
SAN
SAN
SA
N
SA
N
SAN
V
V V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
S A
N
V
V V
V
SA
N
SA
N
SA
N
SAN
SAN
SAN
4 "FD-B
4 "FD-B
4 "FD-B
4 "FD-B
4 "FD-B
4 "FD-B
4 "FD-B
4 "FD-B
4" FD-F
2" V
4" SAN
4" SAN
4" SAN 4" SAN
4" V
4" SAN
4" SAN
2" SAN
6" SAN
4" SAN
6" SAN
6" SAN
6" SAN
6" SAN
3" SAN
2" SAN
4" SAN
2" SAN
3" SAN
2" SAN
2" SAN
2" SAN
2" V
2" V
3" V
3" V
2" V
3" V
3" V
2" V
3" V
3" V
2" V
3" V2" V
2" V
2" V
3" V
3" V
2" V
4" SAN
4" SAN
2" V
2" V
4" V
4" SAN
4" SAN
4" SAN
4" SAN
4" SAN
4" SAN
3" V
3" V
3" V
3" V
DOMESTIC WATER
STORAGE TANK VENT
DRAIN BELOW
STORAGE TANK
WATER-PROOFING
REFER TO 83-
PL-1B1b.
DRAIN BELOW
STORAGE TANK
WATER-PROOFING
PROVIDE STAINLESS STEEL
SLEEVE AROUND SANITARY
PIPES ABOVE STORAGE
TANK(S)
OVER FLOW PIT FOR
DRAINAGE BELOW TANK
WATER-PROOFING
OVER FLOW PIT FOR
DRAINAGE BELOW TANK
WATER-PROOFING
8" VENT TERMINAL FOR
DOMESTIC WATER STORAGE TANK. PROVIDE MAX.
NO. 25 STAINLESS STEEL MESH FOR INSECT & BIRD
SCREENING. EXTEND MESH MIN. 6" BELOW VENT
AND TERMINATE 12" AFR.
V V
8" V
8" V
8" V
V
V
4" V
SAN
4" SAN
V
4" V
V
4" V
SAN
4" SAN
3"V
2"SAN
4"SAN
4"SAN
4"SAN
2"V
3"SAN
3"SAN
2"SAN
4"SAN
2"V 2"V
4"SAN
4"SAN
2"V
4"SAN
6"SAN
4"SAN
6"SAN
2"V
2"V
4"V
4"SAN
2"SAN
4"V
8"V
4"V 8"V
4"SAN
4"SAN
4"SAN
4"SAN
4"SAN
4" S
A N
2" V
4"SSPD
2"V
2"V
2" S
A N
2"V
2"SAN
2"SAN
3"SAN
4"SAN
2"SAN
4"SAN
4"SAN
4"SAN
4"SAN
2"V
4"SAN
P-505
P-524
P-101
P-418
P-524
P-505
P-418
P-101
P-502
P-505
P-418 P-528
P-528
P-528
P-418
P-101
P-524
P-502
83-ESP-3
4" SSPD
4" SSPD
4" SSPD4" SSPD
4 "FD-B
OIL INTERCEPTOR RE.
DETAIL 4/83-PP-403
4" SAN
4" SSPD
4" SSPD
D A
A M
P
Drawing Title
Approved Project Director:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
PSP 309070 Revisions Date
ARCHITECT/ENGINEERS: Office of
Construction and
Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
FILE NAME
Project Abbreviation
F
E
D
C
B
A
F
IL
E N
A M
E
FULLY SPRINKLERED
Page Southerland Page, LLP.
1800 Main Street Suite 123
Dallas, TX 75201 pagethink.com
TEL
FAX
ARCHITECTURE / ENGINEERING / INTERIORS / CONSULTING
Austin / Dallas / Denver / Houston / Washington DC /
International Affiliate Offices
214 522 3900
214 522 4380
DWG
C
U se rs \b k in m a n \D o c u m e n ts
\3 b P -S
C I- R -C
E N
T R A L b k in m a n R K W
J .r v t
/2
/2
:2 :3
A
M
C:\Users\bkinman\Documents\309070b3P-SCI-R18-CENTRAL_bkinmanR4KWJ.rvt
83-PL-202
CONSTRUCTION
VA-LTSCIF-D
RCM
549-820B
EGH
PLUMBING WASTE, DRAIN AND VENT - ISOMETRICS
LONG TERM SPINAL CORD INJURY
VA NORTH TEXAS HEALTH CARE SYSTEM
4500 S. LANCASTER RD. DALLAS, TX 75216OFFICE OF CONSTRUCTION AND FACILITIES
MANAGEMENT DIRECTOR, CENTRAL REGION
06 MAY 2021
BID PACKAGE B
SCALE:F4 SANITARY RISER - AREA B
1 ADDENDUM 2 31 MAY 2023
bkinman Snapshot
83-PP-404
D.8
D.9
E.4
E.5
E.6
E.8
F.1
D.4
16.6
83-PP-404
83-PP-404
83-PP-403
4" V
2" V
6"SSD
4"SAN
4"
SAN
6"SSD
"S
W
6"
SAN
"S
W
6"
SAN
6"SAN
2"SAN
4"SSD
2"
SAN
2"
SAN
4"SSD
4"SAN
Sump Pit
Sump Pit
6"SW
4"V
6"
SAN
6"
SAN
6"SW
4"SAN
4" S
A N
4"SAN
Sump Pit
Sump Pit
4"SAN
4"SW
4"SAN
6"
SW
4"
SA
N
4"
SA
N
6"
SW
4"SAN
8" V
4"
SAN
2"V
4" V
6"SW
4"V
"S
W
8" V
4"V
4"V 4" V
4" V
4"SAN
4"SAN
FUEL OIL TANK
4"SAN
PROVIDE WATER-TIGHT SLEEVE A MIN. OF 2
PIPE SIZES LARGER FOR SANITARY LINES
ABOVE DCW TANK.
NC
REFER TO ARCHITECTURAL DWGS, F1/83-A-315
AND F7/83-AS-502 FOR ADDITIONAL INFO AT
TUNNEL AND PERIMETER DRAIN SYSTEM
6" SW
4" SSD UP
2" V DN
4" SW UP
2" V UP
6" SSD DN
4" SSD UP
6" SSD DN
4" SAN UP
4" SAN UP
4" FD-J
4" FD-J
4"
SSPD
4"
SSPD
100 GALLON OIL
INTERCEPTOR RE.
DETAIL 4/83-PP-403.
D A
A M
P
Drawing Title
Approved Project Director:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
PSP 309070 Revisions Date
ARCHITECT/ENGINEERS: Office of
Construction and
Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
FILE NAME
Project Abbreviation
F
E
D
C
B
A
F
IL
E N
A M
E
FULLY SPRINKLERED
Page Southerland Page, LLP.
1800 Main Street Suite 123
Dallas, TX 75201 pagethink.com
TEL
FAX
ARCHITECTURE / ENGINEERING / INTERIORS / CONSULTING
Austin / Dallas / Denver / Houston / Washington DC /
International Affiliate Offices
214 522 3900
214 522 4380
DWG
C
U se rs \b k in m a n \D o c u m e n ts
\3 b P -S
C I- R -C
E N
T R A L b k in m a n R K W
J .r v t
/2
/2
:3 :1
A
M
C:\Users\bkinman\Documents\309070b3P-SCI-R18-CENTRAL_bkinmanR4KWJ.rvt
83-PP-201
CONSTRUCTION
VA-LTSCIF-D
Checker
549-820B
Author
PLUMBING - ENLARGED PLANS
LONG TERM SPINAL CORD INJURY
VA NORTH TEXAS HEALTH CARE SYSTEM
4500 S. LANCASTER RD. DALLAS, TX 75216OFFICE OF CONSTRUCTION AND FACILITIES
MANAGEMENT DIRECTOR, CENTRAL REGION
06 MAY 2021
BID PACKAGE B
SCALE: 1/4" = 1'-0"1 83-PL-1B2b ENLARGED PLAN - LEVEL B2
1 ADDENDUM 2 31 MAY 2023
4" MIN
NOTE:
1. SUPPORT PIPING 6" AND LARGER TO PREVENT HORIZONTAL MOVEMENT OF JOINTS IN ACCORDANCE WITH CISPI STANDARD 310. ABOVE
DETAILS SHOW SOME EXAMPLES OF SUPPORTING PIPING. NOTE THAT NOT ALL ARRANGEMENTS NECESSARY TO ACCOMPLISH THE WORK ARE
SHOWN. CONTRACTOR SHALL SUPPORT PIPING AT OTHER CONDITIONS SIMILAR TO ABOVE. ALL DETAILS SHALL BE SUBMITTED FOR APPROVAL
PRIOR TO WORK.
2. CONTRACTOR SHALL ENSURE THAT ALL SUPPORT ATTACHMENT METHODS CAN SUPPORT THE MAXIMUM ENCOUNTERED THRUST FROM
HYDROSTATIC LOADS.
HUBLESS PIPE SUPPORT FOR CONCRETE STRUCTURE
SCALE: NOT TO SCALE
SECTION: SUPPORT @ BEAM
SECTION: SUPPORT @ BEAM
SECTION: SUPPORT @ JOIST
SECTION: SUPPORT @ COLUMN
SECTION: SUPPORT @ COLUMN
SECTION: SUPPORT @ COLUMN
PLAN: SUPPORT @ JOIST OR BEAM
5 6
71 RISER CLAMP
2 HANGER ROD
3 HEAVY DUTY DOUBLE BOLT PIPE CLAMP
4 STEEL BRACKET
5 CONCRETE INSERTS OR DRILLED IN ANCHORS
6 CONCRETE ATTACHMENT PLATE
7 JOIST OR BEAM
NOTES:
DETAIL KEY
2" OR AS HIGH
AS POSSIBLE
SANITARY STACK
& VENT CONNECTIONS
SCALE: NOT TO SCALE
PIPE SUPPORT, TYP.
CAPPED VENT
VENT STACK
SANITARY WASTE
STACK
TYPICAL FLOOR
CAPPED SANITARY
WASTE
CEILING
3" OR AS LOW AS POSSIBLE
BOTTOM OF STRUCTURE
30°
STORM DRAIN DOWNSPOUT NOZZLE
SCALE: NOT TO SCALE
EXTERIOR WALL
1"X 1_8" S.S. WALL FLANGE
S.S.
DOWNSPOUT
NOZZLE
CONCRETE SPLASH
BLOCK. REFER TO
ARCHITECTURAL.
STORM RISER
PIPE SLEEVE THROUGH
EXTERIOR WALL
TIGHTLY PACKED
BACKING MATERIAL.
PIPE THROUGH WALL
CAULK WEATHER TIGHT
ROUTE PIPE AS LOW
AS POSSIBLE. PROVIDE
BLOCKING AND SUPPORT
CENTER NOZZLE IN
METAL PANELS
NOTE:
1. COORDINATE LOCATION WITH ARCHITECT, LANDSCAPE ARCHITECT AND CIVIL ENGINEER.
2. COORDINATE WALL PENETRATION CONSTRUCTION WITH ARCHITECT.
DOWNSPOUT FABRICATION:
1. MATERIAL: STAINLESS STEEL PIPE WELDED 360 ANNULARLY TO WALL FLANGE WITH
MINIMUM DISCOLORATION FROM WELDING.
2. SUBMIT TO SAMPLE TO ARCHITECT PRIOR TO FABRICATION OF ANY NOZZLES FOR
INSTALLATION.
1" LONG S.S. WELD BEAD AT PIPE CENTER
4" FROM EDGE TO SERVE AS A DRIP.
DD
ROOF
POST HYDRANT
UNDERDECK CLAMP
3/4" CW
DRAIN LINE. ROUTE TO
NEAREST INDIRECT WASTE.
SELF DRAINING ROOF POST HYDRANT
SCALE: NOT TO SCALE
WOODFORD MODEL #RHY2-MS
1/2"
PIPE PENETRATION THRU RATED WALL
SCALE: NO SCALE
IN
S
U
LA
T E
D P
IP
E
T H
R O
U G
H W
A
LL
B A
R E
P
IP
E T
H R
O U
G H
W
A
LL
FIRE RATED WALL
SCHEDULE 40 STEEL
SLEEVE
MINERAL WOOL BACKING
PIPE INSULATION
FIRE STOP SEALANT
PIPE PENETRATION THRU EXT. WALL
SCALE: NO SCALE
IN
S
U
LA
T E
D P
IP
E
T H
R O
U G
H W
A
LL
B A
R E
P
IP
E T
H R
O U
G H
W
A
LL
WALL FLANGE.
PROVIDE
INTERIOR WALL
FLANGE
WHEN EXPOSED
SCHEDULE 40 STEEL SLEEVE
TIGHTLY PACKED
BACKING MATERIAL
PIPE INSULATION
CAULK WEATHER TIGHT
UTILITY ENTRANCE
SCALE: NO SCALE
BLIND FLANGE
REFER TO THRUST BLOCK DETAIL
L3X3X5/16 X6"
WELDED TO OUTSIDE
OF SLEEVE (TWO
SIDES)
SCHEDULE 40 STEEL
PIPE SLEEVE
L3X3X5/16 X3" WELDED
TO TOP OF SLEEVE AND
DRILLED FOR TIE RODS
(TYP. 2)
CONCRETE FLOOR
SLAB
MINIMUM 3/4"
TIE RODS
NOTES:
1. RODS, CLAMPS, BOLTS, WASHERS, STRAPS, ETC. SHALL CONFORM TO NFPA 24.
2. MINIMIZE THE LENGTH OF PIPING UNDER THE STRUCTURE.
3. CAST PIPE SLEEVE INTO STRUCTURE. COORDINATE SLEEVE INSTALLATION WITH
STRUCTURAL ENGINEER.
4. PROVIDE BURIAL DEPTH TO TOP OF PIPE AS PER NFPA 24 OR MINIMUM 36".
5. SEAL SPACE BETWEEN SLEEVE AND PIPE WATERTIGHT.
6. PROVIDE BLIND FLANGE FOR INSTALLATION OF UNDERGROUND PIPING. REMOVE END
PLATE TO CONTINUE PIPING INSTALLATION.
STRAP CLAMP
3" MIN.
MECHANICAL JOINT
12"
MIN.
PUSH-ON OR
MECHANICAL JOINT
9.8
5.7
18.2
10.6
12.9
7.5
8"
6"
45° BEND90° BENDTEE & END
b
MINIMUM THRUST BLOCK BEARING AREA, A(b) = bxh [SQ FT]
NOMINAL PIPE SIZE[IN]
BEARING THRUST BLOCK
SCALE: NOT TO SCALE
14.827.419.410" b b
UNDISTURBED
EARTH
THRUST BLOCK
0°
90°
90° ELBOW 45° ELBOW
135°
TEE & END
18" MIN.
NOTE:
1. BEARING AREA: A(b) = WIDTH X HEIGHT = bxh. SQUARE CONFIGURATION PREFERRED
HOWEVER RECTANGULAR ACCEPTABLE IF b 2h. WHERE ADEQUATE BEARING CAN NOT BE
OBTAINED PROVIDE TIE RODS IN LIEU OF THRUST BLOCK.
2. THRUST BLOCK TO BEAR ON UNDISTURBED EARTH. OTHERWISE, PROVIDE FILL
BETWEEN BEARING THRUST BLOCK AND UNDISTURBED EARTH. COMPACT FILL TO AT
LEAST 90% STANDARD PROCTOR DENSITY AND INCREASE BEARING AREA BY A
FACTOR OF 1.5.
3. MINUMUM THRUST BLOCK ANGLE INDICATED ABOVE.
4. TAKE CARE IN PLACING CONCRETE SO THAT PIPE AND FITTINGS ARE NOT ENCASED.
5. VERIFY SOIL BEARING STRENGTH WITH SOILS ENGINEER.
6. THRUST BLOCK MATERIAL: 3,000 PSI CONCRETE AT 28 DAYS.
7. REFER TO NFPA 24, ANNEX A.10.8.2 FOR ADDITIONAL DESIGN REQUIREMENTS.
RESTROOM TRAP PRIMER ALTERNATIVES
SCALE: NO SCALE
WATER SAVER TRAP
PRIMER
CONNECTION
NOTE:
1. REFER TO TRAP PRIMER DETAIL FOR
ADDITIONAL INFORMATION.
2. PROVIDE ESCUTCHEON PLATE AT WALL
PENETRATION.
3. DISTANCE "A" BELOW CRITICAL LINE:
PER MANUFACTURER'S INSTRUCTION AND
CODE REQUIRED MINIMUM.
WATER
CLOSET
FLUSH VALVE
FLUSH VALVE
HANDLE
TO FLOOR
DRAIN
CRITICAL LINE
DISTANCE "A"
WATER HAMMER ARRESTER SCHEDULE
12-32
A
1-11 61-11333-60
CB D E
114-154
F
155-330
WATER HAMMER ARRESTER (PDI SYMBOL)
TYP. BRANCH LINE
SUPPLY RISER
FIXTURE
UNIT RATING
PDI SYMBOL
WATER HAMMER ARRESTER
SCALE: NOT TO SCALE
NOTE:
1. INSTALL WATER HAMMER ARRESTERS AT THE END OF BRANCH LINE BETWEEN THE
LAST TWO FIXTURES SERVED.
2. ONE WATER HAMMER ARRESTER PER 20' LINE, AND ANOTHER FOR BRANCHES OVER
20' IN LENGTH.
3. THE SUM OF FIXTURE UNIT RATING FOR BOTH ARRESTERS SERVING A BRANCH OVER
20' IN LENGTH SHALL BE EQUAL TO OR GREATER THAN THE DEMAND OF THE ENTIRE
BRANCH.
4. FOR LONG RUNS SERVING SINGLE FIXTURE OR EQUIPMENT, SIZE WATER HAMMER
ARRESTER PER PDI STANDARD 201 TABLE IV.
5. PROVIDE STAINLESS STEEL ACCESS PANEL WHERE NOT ACCESSIBLE.
6. REFER TO APPLICABLE PLUMBING CODE FOR FIXTURE UNITS VALUES.
7. PROVIDE ISOLATION VALVE TO LARGE WATER HAMMER ARRESTER.
WHA-X
WHA-X
NOTE:
1. HUB DRAIN MAY BE WET-VENTED THROUGH SINK/LAVATORY STACK AS ALLOWED BY CODE.
2. PROVIDE TRAP PRIMER AND CONNECT IT TO WATER SUPPLY SERVING SINK/LAVATORY.
3. PROVIDE MINIMUM 1" AIR GAP AT ALL INDIRECT WASTES INTO HUB DRAIN.
4. COORDINATE LOCATION WITH ARCHITECT, CABINET MANUFACTURER AND WITH ANY
ADA CLEARANCE REQUIREMENTS.
5. HUB DRAIN MAY BE INSTALLED AS HIGH AS POSSIBLE AS LONG AS IT IS VISIBLE.
6. HUB DRAIN MAY BE ROTATED TO BE PARALLEL WITH WALL.
UNDERCOUNTER HUB DRAIN
SCALE: NO SCALE
CABINET
P-TRAP FOR
SINK/LAVATORY
2" HUB DRAIN FOR
INDIRECT WASTE
WATER SUPPLY
SERVING SINK/LAVATORY
FILE: BFP
UNDERCOUNTER-005.DWG
UPDATED: 6/2/2007
IT IS CRUCIAL TO
COORDINATE CABINET
CONFIGURATION
WITH ARCHITECT
1"
1"
NOTE:
1. CLEARANCES LISTED ABOVE ARE MINIMUM REQUIREMENTS. PROVIDE SUFFICIENT CLEARANCE FOR
MAINTENANCE AND INSPECTION. REFER TO AHJ AND BFP MANUFACTUER FOR ADDITIONAL
REQUIREMENTS.
2. SERVICE AND NON-SERVICE SIDES OF THE BFP CANNOT BE UBSTRUCTED BY PERMANENT ELEMENTS (IE. SINK, P-TRAP, GARBAGE DISPOSAL). A REMOVABLE PANEL IS ALLOWED. LABEL PANEL "BACKFLOW
PREVENTER ACCESS PANEL".
3. AVOID ROUTING PIPING THROUGH COUNTERTOP. ROUTE PIPING DOWNSTREAM OF BFP BACK INTO WALL
TOEQUIPMENT. PROVIDE ESCUTCHEON PLATE AT ALL WALL PENETRATIONS.
4. COORDINATE INSTALLATION WITH ARCHITECT AND CABINET MANUFACTURER PRIOR TO CONSTRUCTION.
WHERE MODIFYING THE CABINET IS NOT PRACTICAL, COORDINATE WITH ENGINEER FOR ALTERNATE INSTALLATION.
5. FOR HUB DRAIN, PROVIDE AS MUCH HEIGHT ON NECK AS POSSIBLE. P-TRAP MAY EXTEND BELOW CABINET BASE.
SEAL AROUND ANY PENETRATIONS THROUGH CABINET BASE.
6. REFER TO BACKFLOW PREVENTER DETAIL.
7. REFER TO UNDERCOUNTER HUB DRAIN DETAIL.
BACKFLOW PREVENTER UNDERCOUNTER
SCALE: NOT TO SCALE
UNUBSTRUCTED
SPACE WITHIN
CABINET
12" ABOVE
X 6" DEEP
CLEAR
12" AFF MINIMUM
TO BOTTOM OF
BFP
P-TRAP BELOW
CABINET BASE
AS NEEDED
PROVIDE CLEARANCES ON
SERVICE AND NON-
SERVICES
SIDES OF BFP
2" AIR GAP
BFP
UNUBSTRUCTED SPACE
WITHIN CABINET
SUPPORT BFP FROM
CABINET WALL
BFP UNDERCOUNTER
MINIMUM 24" WIDE
ACCESS TO BFP
12" DEEP MINIMUM
2x3 INCREASER
CENTERED
BELOW
BFP DRAIN
PLAN
SECTION
SECTION
EXTEND HUB
DRAIN NECK
6" MIN.
NOTE:
1. GRADE CLEANOUT COVER: HEAVY DUTY GALVANIZED CAST IRON TOP IN DRIVEWAY,
ROADWAY AND FINISH GRADE AREAS.
2. AT FINISH GRADE AREAS WITHOUT CONCRETE TOPPING, SET GRADE CLEANOUT
HOUSING IN 24"X24" OR 24"∅ BY 6" MINIMUM THICK CONCRETE COLLAR WITH #4 REBAR
ALL AROUND. SET FLUSH WITH GRADE.
GRADE CLEANOUT
SCALE: NOT TO SCALE
GRADE CLEANOUT COVER CONCRETE TOPPING
CLEANOUT HOUSING
MAINTAIN GAP BETWEEN
CONCRETE AND RISER
THREADED BRONZE
CLEANOUT PLUG
GASKET JOINT
DRAIN LINE WYE
DRAIN LINE BELOW
GRADE. SIZED AS
SHOWN ON
DRAWINGS
PIPE RISER TO GRADE
1/2" EXPANSION JOINT
THREADED BRONZE CLEANOUT PLUG
SIDEWALK OR
CONCRETE
PAVEMENT
GRADE CLEANOUT COVER
CONCRETE COLLAR
TURF
PIPE PENETRATION THROUGH FLOOR
SCALE: NO SCALE
RISER CLAMP WITH ALL
THREAD STAND OFF
PIPE INSULATION
SCHEDULE 40
STEEL SLEEVE
FIRE STOP SEALANT
MINERAL
WOOL
BACKING
BARE PIPE
THROUGH
FLOOR
INSULATED PIPE
THROUGH
FLOOR
1" MAX.
NOTE:
1. COORDINATE FINAL LOCATION OF FLOOR AND WALL CLEANOUT WITH ARCHITECT.
2. PROVIDE MINIMUM 12" TO ADJACENT WALLS, CABINETS, DOORS OR OTHER ADJACENT
OBSTRUCTIONS. IN RESTROOMS, COORDINATE LOCATION WITH PARTITIONS AND FIXTURES.
3. FOR WALL CLEANOUT, LOCATE COVER PLATE SO THAT IT IS NOT NECESSARY TO CUT
TILE AT COVED BASE.
4. PROVIDE MINIMUM CLEANOUT SIZE PER SCHEDULE BELOW. FOR WALL CLEANOUTS,
ALSO COORDINATE MINIMUM CLEAR SPACE INSIDE WALL WITH SIZE OF CLEANOUT FITTING.
PIPE SIZE CLEANOUT CLEAR
1 1/2" 2" 3"
2" 2" 3"
2 1/2" 3" 4"
3" 3" 4"
4" & LARGER 4" 5 1/2"
FLOOR AND WALL CLEANOUT
SCALE: NOT TO SCALE
FINISHED WALL
STAINLESS STEEL WALL
CLEANOUT COVER PLATE
SECURING SCREW
CLEANOUT FITTING
COVERED BASE
1/4" MINIMUM
CLEAR
SECTION: SUPPORT @ COLUMN
SECTION: SUPPORT @ COLUMN
SECTION: SUPPORT @ JOIST OR BEAM
SECTION: SUPPORT @ COLUMN
SECTION: SUPPORT @ BEAM
SECTION: SUPPORT @ COLUMN
PLAN: SUPPORT @ JOISTS OR BEAMS
NOTE:
1. SUPPORT PIPING 6" AND LARGER TO PREVENT HORIZONTAL MOVEMENT OF JOINTS IN ACCORDANCE WITH CISPI STANDARD 310. ABOVE
DETAILS SHOW SOME EXAMPLES OF SUPPORTING PIPING. NOTE THAT NOT ALL ARRANGEMENTS NECESSARY TO ACCOMPLISH THE WORK ARE
SHOWN. CONTRACTOR SHALL SUPPORT PIPING AT OTHER CONDITIONS SIMILAR TO ABOVE. ALL DETAILS SHALL BE SUBMITTED FOR APPROVAL
PRIOR TO WORK.
2. CONTRACTOR SHALL ENSURE THAT ALL SUPPORT ATTACHMENT METHODS CAN SUPPORT THE MAXIMUM ENCOUNTERED THRUST FROM
HYDROSTATIC LOADS.
HUBLESS PIPE SUPPORT FOR STEEL STRUCTURE
SCALE: NOT TO SCALE
1 RISER CLAMP
2 HANGER ROD AND HANGER
3 HEAVY DUTY DOUBLE BOLT PIPE CLAMP
4 STEEL BRACKET
5 WELD OR CLAMP TO BEAM/COLUMN
6 STRUCTURAL WELDING LUG
7 JOIST OR BEAM
DETAIL KEY
7 6
7 4
NOTES:
D A
A M
P
Drawing Title
Approved Project Director:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
PSP 309070 Revisions Date
ARCHITECT/ENGINEERS: Office of
Construction and
Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
FILE NAME
Project Abbreviation
F
E
D
C
B
A
F
IL
E N
A M
E
FULLY SPRINKLERED
Page Southerland Page, LLP.
1800 Main Street Suite 123
Dallas, TX 75201 pagethink.com
TEL
FAX
ARCHITECTURE / ENGINEERING / INTERIORS / CONSULTING
Austin / Dallas / Denver / Houston / Washington DC /
International Affiliate Offices
214 522 3900
214 522 4380
DWG
C
U se rs \b k in m a n \D o c u m e n ts
\3 b P -S
C I- R -C
E N
T R A L b k in m a n R K W
J .r v t
/2
/2
:3 :1
A
M
C:\Users\bkinman\Documents\309070b3P-SCI-R18-CENTRAL_bkinmanR4KWJ.rvt
83-PP-402
CONSTRUCTION
VA-LTSCIF-D
RCM
549-820B
EGH
PLUMBING - DETAILS
LONG TERM SPINAL CORD INJURY
VA NORTH TEXAS HEALTH CARE SYSTEM
4500 S. LANCASTER RD. DALLAS, TX 75216OFFICE OF CONSTRUCTION AND FACILITIES
MANAGEMENT DIRECTOR, CENTRAL REGION
06 MAY 2021
BID PACKAGE B
FLOOR
CEILING
FLOOR
ELEVATOR
HOISTWAY
B
A
FLOW
RATE
(GPM)
PIPE SIZE
(IN)
2.5
"A" "B"
5 3
PIT SIZE
H X W X L
(IN)
30 X 24 X 24
36 X 30 X 30
36 X 36 X 36
W L
H
SUMP PUMP:
MANUFACTURER
[NAME HERE]
[MODEL HERE]
[MODEL HERE]
[MODEL HERE]
28 29
52 7
# OF
ELEV.
CABS
2" A
A
SAN
3" 40
43 44
OIL INTERCEPTOR
NOTES:
1. SUMP PUMP SHALL BE FULLY AUTOMATIC AND SHALL NOT REQUIRE HUMAN INTERVENTION TO OPERATE.
2. REFER TO FLOOR PLANS FOR ROUTING AND ADDITIONAL INFO.
3. ELEVATOR SUMP PUMP, POWER AND LABELING SHALL BE PER THE LATEST VERSION OF ASME A17.1/CSA
B44, THE STATE ELEVATOR LICENSING AND REGULATION AGENCY AND LOCAL AHJ REQUIREMENTS.
4. SUMP PUMP DISCHARGE PIPING: LABEL: "NON-POTABLE WATER. ELEVATOR SUMP PUMP DRAINAGE". FOR
PIPING FROM MULTIPLE ELEVATORS, INDICATE ELEVATOR NUMBER AND/OR LOCATION. REFER TO PLANS
FOR LOCATION OF SAMPLING PORT.
FORCE MAIN: HARD PIPED. TYPE K COPPER PIPE AND FITTINGS. NO PVC ALLOWED. SUPPORT HORIZONTAL AND VERTICAL PIPING 36" MIN. ON CENTER. ROUTE AROUND THE PERIMETER OF HOISTWAY. EXTEND UP ALONG THE SIDE OF THE HOISTWAY LADDER. COORDINATE ROUTING WITH ELEVATOR MANUFACTURER
PRIOR TO CONSTRUCTION.
GRAVITY LINE: SANITARY WASTE PIPING PER SPECIFICATION. ROUTE AS HIGH AS POSSIBLE. RISE TO AN ELEVATION 12" ABOVE THE LOCAL 100 YEAR FLOOD PLAIN MIN. BEFORE DRAINING BY GRAVITY. SLOPE AT
1/4" PER FOOT DOWNSTREAM OF HIGH POINT.
5. SUMP PIT: LOCATE OPPOSITE SIDE OF ELEVATOR SHAFT FROM DOOR. REMOVABLE CAST IRON OR ALUMINUM GRATE (BY STRUCTURE) WITH REINFORCED OPENINGS FOR POWER, CONTROLS, DISCHARGE PIPING, ETC. GRATE MUST BE FLUSH WITH ELEVATOR PIT FLOOR. COORDINATE CONSTRUCTION, LOCATION, PIT SIZE AND GRATING WITH ARCHITECT, ELEVATOR MANUFACTURER AND STRUCTURAL
ENGINEER.
6. SUMP PUMP CONTROL PANEL: METAL ENCLOSURE. REMOTELY LOCATED. CANNOT BE LOCATED IN ELEVATOR SHAFT OR IN ELEVATOR MACHINE ROOM. REFER TO PLAN FOR PROPOSED LOCATION. REFER
TO ELECTRICAL. COORDINATE CABLE LENGTH REQUIREMENTS WITH MANUFACTURER.
7. SUMP PUMP: 40 FT HD MIN OR AS NOTED IN PUMP SCHEDULE. PROVIDE MEANS OF EASILY REMOVING
PUMP.
8. CHECK VALVE: INSTALL UPPER CHECK VALVE AT HIGHEST POINT IN PIPING BEFORE GRAVITY DRAINAGE.
9. HIGH LEVEL ALARM: RED WARNING LIGHT, AUDIBLE ALARM, PUSH-TO-TEST ALARM SWITCH, LOCAL HORN
SILENCE SWITCH/BUTTON. MUST BE READILY VISIBLE AT ALL TIMES. COORDINATE LOCATION WITH ARCHITECT, OWNER AND BUILDING MAINTENANCE. MAY BE INTEGRAL/INCLUDED WITH SUMP PUMP
CONTROL PANEL. BASIS OF DESIGN: HYDROMATIC Q-ALERT XT OR EQUAL.
10. OIL/WATER PROBE: WHERE REQUIRED. NON-OPTICAL BASED SENSOR. MAY BE A COMPONENT OF SUMP
PUMP.
11. POWER: ON SAME POWER TYPE (IE. NORMAL, EMERGENCY, CRITICAL) AS THE ELEVATOR. SUMP PUMP MAY NOT SHARE THE SAME ELECTRICAL CIRCUIT AS ANY OTHER COMPONENTS (IE. CONTROL PANEL, HIGH LEVEL ALARM). REFER TO ELECTRICAL.
DUPLEX OUTLET: GFCI. DEDICATED CIRCUIT. LABEL: "SUMP PUMP ONLY". COORDINATE EXACT LOCATION IN FIELD. LOCATE WITHIN ELEVATOR HOISTWAY PER LOCAL AHJ REQUIREMENTS/RESTRICTIONS.
12. SEAL ALL PIPING PENETRATIONS BELOW GRADE WATERTIGHT. SEAL ALL PIPING PENETRATIONS THROUGH HOISTWAY WALL PER ARCHITECTURAL DRAWINGS OR 2-HOUR FIRE/SMOKE RATING AT MIN..
13. ALL PIPE LABELING PER 2015 UPC 601.3/2015 IPC 608.8
14. PER CITY OF AUSTIN: PROVIDE SAMPLING PORT ON DISCHARGE PIPING FIRST PREFERENCE: WITHIN THE
PROPERTY LINE (SEE KEYED NOTE #5) OR SECOND PREFERENCE: INSIDE (SEE KEYED NOTE #55). REFER
TO TDLR FOR APPROVED LOCATIONS.
15. PER CITY OF TAMPA:
HYDRAULIC ELEVATOR: PROVIDE OIL SENSOR TO TURN OFF PUMP UPON DETECTION OF OIL.
NON-HYDRAULIC ELEVATOR: ROUTE TO OIL INTERCEPTOR.
PREFAB OIL INTERCEPTOR. FLOW RATE: 200
GPM. HOLDING CAPACITY: 265 GAL. MIN..
BASIS OF DESIGN: ZURN Z1188 OR EQUAL.
HOUSEKEEPING PAD.
FLOW RESTRICTOR WHERE REQUIRED BY
INTERCEPTOR MANUFACTURER. SET TO
FLOW RATE TO MATCH INTERCEPTOR FLOW
RATE. PROVIDE VENT IF NEEDED.
2" AIR GAP.
ELEVATOR SUMP PUMP DISCHARGE
SERVING HYDRAULIC ELEVATOR.
ELEVATOR SUMP PUMP DISCHARGE
SERVING NON-HYDRAULIC ELEVATOR.
PROVIDE SUFFICIENT CLEARANCE ABOVE
AND AROUND UNIT FOR MAINTENANCE.
DRAW-OFF CONNECTION. EXTEND CAP MIN.
12" ABOVE INTERCEPTOR.
HIGH LEVEL ALARM FLOAT. SET AT 18" AS
MEASURED ABOVE PIT FLOOR.
HIGH LEVEL ALARM.
OIL SUMP. 10 GAL. HOLDING CAPACITY.
FROM TRAP PRIMER. REFER TO DETAIL.
SINGLE RISER 2-WAY CLEANOUT OR TWO
1-WAY CLEANOUTS.
LIMIT LINE LENGTH BETWEEN SUMP PUMP AND
JUNCTION BOX TO 60" OR PER
MANUFACTURER RECOMMENDATION.
ROUTE CONTROL, FLOAT/ALARM AND
ELECTRICAL WIRING IN SEPARATE 1" MIN.
CONDUITS.
POWER CONNECTION.
OIL/WATER PROBE
FLOATS. MAY BE FLOAT (SINGLE OR MULTIPLE
FLOATS) OR DISCRIMINATING TYPE. PUMP ON
SET AT 12" AND PUMP OFF SET AT 3" BOTH AS
MEASURED ABOVE PIT FLOOR
POWER/CONTROL/ALARM JUNCTION BOX
MOUNTED ON INTERIOR OF HOISTWAY WALL.
COORDINATE LOCATION AND LINE LENGTH PER
MANUFACTURER REQUIREMENTS.
SUMP PUMP CONTROL PANEL.
HOISTWAY WALL RATED PENETRATION.
FORCE MAIN.
GRAVITY PIPING.
REMOVABLE GRATE.
PIPE INCREASER
MAINTENANCE VALVE (LOCKED OPEN) IN
ACCESSIBLE LOCATION. LABEL: "ELEVATOR
SUMP PUMP MAINTENANCE VALVE"
SUMP PUMP PIT.
CHECK VALVE IN ACCESSIBLE LOCATION.
SUMP PUMP.
LEVEL B1
519' - 3"
32.5
LEVEL B1
519' - 2"
3"CV
83-ESP-2
ELEV: 513' - 7"
3"GV
3"SSPD
SUMP PUMP FLOAT
SWITCH
ELEVATOR HOISTWAY
UNION
HIGH WATER ALARM AT
36" ABOVE PIT BOTTOM
UNION
83-ESP-1
3"SSPD
4"SSPD
SUMP PUMP FLOAT
SWITCH
HIGH WATER ALARM AT
36" ABOVE PIT BOTTOM
LOCAL CONTROL PANEL
INTERLOCKED WITH BAS SYSTEM
JUNCTION BOX
ROUTE ALL WIRING IN
1" MINIMUM CONDUIT
3"GV
3"CV
LEVEL B1
519' - 3"
LEVEL B1
519' - 2"
SUMP PUMP FLOAT
SWITCH
HIGH WATER ALARM AT
36" ABOVE PIT BOTTOM
LOCAL CONTROL PANEL
INTERLOCKED WITH
JUNCTION BOX
ROUTE ALL WIRING
IN 1" MIN. CONDUIT
ELEVATOR HOISTWAY
UNION
BEYOND
3"SSPD
4"SSPD
BEYOND
83-ESP-3
3"CV
GENERAL NOTES:
1. SUMP PUMPS SHALL BE FULLY AUTOMATIC AND SHALL NOT REQUIRE HUMAN INTERVENTION.
2. SUMP PUMP IS SIZED AT 100 GPM TO MEET THE STATE MINIMUM REQUIREMENT OF 3000
GALLONS PER HOUR PER ELEVATOR CAR.
3. ESP-3 FLOAT VALVE TO BE SET AT 18" ABOVE THE BOTTOM OF THE ELEVATOR HOISTWAY SUMP.
4. SET HIGH WATER ALARM AT 36" ABOVE THE BOTTOM OF THE ELEVATOR HOISTWAY SUMP.
5. COORDINATE THE FINAL LOCATION OF THE CONTROL PANEL, JUNCTION BOX, CONDUIT AND
PIPING WITH THE ELEVATOR EQUIPMENT CUT SHEETS.
6. REFER TO FLOOR PLAN AND RISER DIAGRAM FOR ADDITIONAL INFORMATION.
7. REFER TO SPECIFICATION SECTION 221436 FOR ADDITIONAL INFORMATION.
3" S
S P
D
LEVEL 01
535' - 3"
LEVEL B1
519' - 3"
17.1 16.6
LEVEL 01
535' - 2"
LEVEL B1
519' - 2"
BYPASS VALVE (NC)
INLET VALVE (NO)
BYPASS VALVE (NC)
RETURN VALVE (NO)
INLET VALVE (NO)
STRAINER
PRESSURE REGULATOR
1" F
O S
1" F
O R
6"FOV
6" F
O V
2" F
O V
ELEVATOR SUMP AND OIL SEPARATOR PIPING DETAIL
SCALE: NO SCALE
D A
A M
P
Drawing Title
Approved Project Director:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
PSP 309070 Revisions Date
ARCHITECT/ENGINEERS: Office of
Construction and
Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
FILE NAME
Project Abbreviation
F
E
D
C
B
A
F
IL
E N
A M
E
FULLY SPRINKLERED
Page Southerland Page, LLP.
1800 Main Street Suite 123
Dallas, TX 75201 pagethink.com
TEL
FAX
ARCHITECTURE / ENGINEERING / INTERIORS / CONSULTING
Austin / Dallas / Denver / Houston / Washington DC /
International Affiliate Offices
214 522 3900
214 522 4380
DWG
C
U se rs \b k in m a n \D o c u m e n ts
\3 b P -S
C I- R -C
E N
T R A L b k in m a n R K W
J .r v t
/2
/2
:3 :1
A
M
C:\Users\bkinman\Documents\309070b3P-SCI-R18-CENTRAL_bkinmanR4KWJ.rvt
83-PP-403
CONSTRUCTION
VA-LTSCIF-D
RCM
549-820B
EGH
PLUMBING - DETAILS
LONG TERM SPINAL CORD INJURY
VA NORTH TEXAS HEALTH CARE SYSTEM
4500 S. LANCASTER RD. DALLAS, TX 75216OFFICE OF CONSTRUCTION AND FACILITIES
MANAGEMENT DIRECTOR, CENTRAL REGION
06 MAY 2021
BID PACKAGE B
SCALE: 1/2" = 1'-0"1 SUMP PIT PUMPS AT ELEVATORS P1-P2 &S3-S4
SCALE: 1/2" = 1'-0"2 SUMP PIT PUMP AT ELEVEATORS P5 & P6
SCALE: 1/2" = 1'-0"3 EMERGENCY GENERATOR FUEL OIL SUPPLY AND VENTING DETAIL
LEVEL B1
519' - 3"
LEVEL B2
501' - 3"
SOLENOID VALVES (N+1)
FOR TANK FILL
SHUT-OFF VALVES (N+1)
DOUBLE CHECK BACKFLOW
PREVENTERS (N+1)
83-BP-1
4" MIN THICK HOUSEKEEPING
PAD - COORDINATE DEPTH OF PAD WITH
ANTI-VORTEX PLATE TO MAINTAIN 6" CLEAR
AT PUMP SUCTION
FLOW THROUGH HYDRO PNEUMATIC TANK -
REF: SPECIFICATIONS
4" PUMP SUPPLY BY-PASS
FROM CITY SUPPLY
(NORMALLY CLOSED)
NO
NO NO
NO NO
4" DOMESTIC WATER TANK
FILL - TERMINATE AT 9'-9"
4" DOMESTIC WATER SUPPLY
FROM STREET
4" DCW
4" DCW
4" DCW
4" DCW
4" DCW
4" DCW
4" DCW
EMERGENCY SHUT-OFF
SOLENOID VALVE
DD.6DD.8
NC
DOMESTIC WATER PUMP
SUCTION AT STORAGE TANK
4" OVERFLOW DRAIN
ELEV: 509' - 6"
8"X4"
REDUCER
4"SAN
8" TANK OVER-
PRESSURIZATION VENT TO
PENTHOUSE ROOF
4" DCW 4" DCW
4" DCW
2" V
2" V
4" DCW
NO
4" V
4" SAN
4"SAN
4"SAN
LEVEL B2
501' - 3"
83-PP-404
13 13.6
LEVEL B2
501' - 2"
3"DCW
3"NPW
3" STRAINER
2 1/2" REDUCED PRESSURE
BACKFLOW PREVENTER
4 "FD-B
/2
2"V
2"V
4"SAN
COLUMN
LEVEL B2
501' - 3"
4"V2"V
4"SAN
4"SAN 4" FD-J
" LIQUID LEVEL SENSOR -
SET ALARM LEVEL AT 4"
ABOVE BOTTOM OF
ALARM ENCLOSURE
6" DIAMETER
STAINLESS STEEL
ALARM ENCLOSURE
1/2" FLEXIBLE &
WATERPROOF CONDUIT
WITH WATER-TIGHT
FITTINGS
AIR GAP FITTING
4"X8" INCREASER
"LOOSE" FITTING STAINLESS STEEL
CAP
(ALLOWS WATER TO ESCAPE IF HEAVY
LEAKS ARE PRESENT)
3" DIAMETER CLEAR BOROSILICATE SITE
GLASS, 3/16" THICK WITH NEOPRENE
GASKETS (TOP & BOTTOM) MOUNTED TO CAP
36" DIAMETER PIT - PROVIDE WITH
SOLID TOP AND "HAND-HOLE"
ACCESS OVER ALARM ENCLOSURE
6" OVERFLOW
LEAK DETECTION CONTROL PANEL
WITH LOCAL ALARM INTERLOCKED
WITH BAS SYSTEM
1/2" RIGID CONDUIT ABOVE PIT
6" SLEEVE
LEVEL 02
552' - 9"
LEVEL 02
552' - 8"
1 1/2" STRAINER WITH
MIN. 120 MESH SCREEN
(2) 1/2" BALL VALVE CONTROL
VALVES WITH FLOATING NON-
SPRING RETURN ACTUATORS
FOR 1ST FLOOR ROOF GARDEN
IRRIGATION
(2) 1/2" BALL VALVE CONTROL
VALVES WITH FLOATING NON-
SPRING RETURN ACTUATORS
FOR 2ND FLOOR ROOF GARDEN
IRRIGATION
(1) 3/4" & (1) 1/2" STUB-OUT 4"
ABOVE 2ND LEVEL SLAB WITH AND
BALL DRIPS - CAPPED FOR
IRRIGATION CONTRACTOR
UNION - TYPICAL OF (4)
N P
W N
P W
N P
W
N P
W
N P
W
N P
W
1 1/4" BALL VALVE FOR SHUT-OFF
1"NPW
3/4"NPW
D A
A M
P
Drawing Title
Approved Project Director:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
PSP 309070 Revisions Date
ARCHITECT/ENGINEERS: Office of
Construction and
Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
FILE NAME
Project Abbreviation
F
E
D
C
B
A
F
IL
E N
A M
E
FULLY SPRINKLERED
Page Southerland Page, LLP.
1800 Main Street Suite 123
Dallas, TX 75201 pagethink.com
TEL
FAX
ARCHITECTURE / ENGINEERING / INTERIORS / CONSULTING
Austin / Dallas / Denver / Houston / Washington DC /
International Affiliate Offices
214 522 3900
214 522 4380
DWG
C
U se rs \b k in m a n \D o c u m e n ts
\3 b P -S
C I- R -C
E N
T R A L b k in m a n R K W
J .r v t
/2
/2
:3 :2
A
M
C:\Users\bkinman\Documents\309070b3P-SCI-R18-CENTRAL_bkinmanR4KWJ.rvt
83-PP-404
CONSTRUCTION
VA-LTSCIF-D
RCM
549-820B
EGH
PLUMBING - DETAILS
LONG TERM SPINAL CORD INJURY
VA NORTH TEXAS HEALTH CARE SYSTEM
4500 S. LANCASTER RD. DALLAS, TX 75216OFFICE OF CONSTRUCTION AND FACILITIES
MANAGEMENT DIRECTOR, CENTRAL REGION
06 MAY 2021
BID PACKAGE B
SCALE: 3/8" = 1'-0"1 DOMESTIC WATER PUMPS & TANK FILL DETAIL
SCALE: 3/8" = 1'-0"2 NON-POTABLE BACKFLOW PREVENTER DETAIL
SCALE: 1/2" = 1'-0"5 OVER-FLOW PIT DETAIL
SCALE: 1/2" = 1'-0"4 LEVEL 2 IRRIGATION CONTROL DETAIL
SCALE: 1/2" = 1'-0"3 SECTION AT DOWNSPOUT
1 ADDENDUM 1 17 MAY 2023
Drawing Title
Approved Project Director:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions Date
ARCHITECT/ENGINEERS:
Office of
Construction and Facilities
Management o n e e i g h t h i n c h o n e f o o t t h r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
FILE NAME
Project Abbreviation
F
E
D
C
B
A
Page Southerland Page, LLP.
1800 Main Street Suite 123
Dallas, TX 75201 pagethink.com
TEL
FAX
ARCHITECTURE / ENGINEERING / INTERIORS / CONSULTING
Austin / Dallas / Denver / Houston / Washington DC /
International Affiliate Offices
214 522 3900
214 522 4380
CONSTRUCTION FULLY SPRINKLERED
VA-LTSCIF-D
549-820B
LONG TERM SPINAL CORD INJURY
VA NORTH TEXAS HEALTH CARE SYSTEM
4500 S. LANCASTER RD. DALLAS, TX 75216OFFICE OF CONSTRUCTION AND FACILITIES
MANAGEMENT DIRECTOR, CENTRAL REGION
06 MAY 2021
BID PACKAGE B
F I L E
N
A M
E
D A
T E
S T
A M
P :9
E d w g p m
83-E-002
LIGHTING FIXTURE SCHEDULE
WH DR1 ADDENDUM 2 31 MAY 2023
FIRM
#15868
31MAY2023
| 01 83-FX-B1 - FIRE PROTECTION FLOOR PLAN LEVEL B1 |
| 02 83-FX-102 - FIRE PROTECTION OVERALL FLOOR PLAN LEVEL 2 |
| 03 83-PP-1B1b - PLUMBING SYSTEMS - FLOOR PLAN - LEVEL B1 AREA B |
| 04 83-PL-202 - PLUMBING WASTE, DRAIN AND VENT - ISOMETRICS |
| 05 83-PP-201 - PLUMBING - ENLARGED PLANS |
| 06 83-PP-402 - PLUMBING - DETAILS |
| 07 83-PP-403 - PLUMBING - DETAILS |
| 08 83-PP-404 - PLUMBING - DETAILS |
| 09 83-PP-501 - PLUMBING SCHEDULES |
| 10 83-E-002 - LIGHTING FIXTURES SCHEDULE |
File details come from the government source that posted it. Updated .