The documents include mechanical drawings and specifications for a federal construction project to build out a Long Term Spinal Cord Injury center. The drawings show layouts for HVAC systems on different floors, including locations for air handling units, fan coil units, terminal units, ductwork, grilles and other mechanical equipment. The specifications reference HVAC legends, notes, and details to guide installation.
The related federal contract opportunity is a solicitation to provide construction services for the Long Term Spinal Cord Injury project located at the VA Medical Center in Dallas, Texas. The solicitation seeks bids for building out the 549,820 square foot facility in accordance with the mechanical drawings and specifications. The contracting agency is the Department of Veterans Affairs Office of Construction and Facilities Management.
View the file
Other files
Show 40 more
Latest 50 of 117 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UP
SHEET NOTES
DD.6
DD.6
J.6 J.6
I.6 I.6
I I
H.6 H.6
H H
8.3
8.3
CC.6
CC.6
CC
CC
BB.6
BB.6
12.3
J J
G.8 G.8
6.3
6.3
7.6
7.6
7.2
7.2
13.6
BB
BB
DD
DD
G.2 G.2
Z.8
Z.8
Z.2
Z.2
14.3
14.3
G G
J.8 J.8
Z
Z
DD.8
DD.8
6.2
6.2
12.2
6.6
6.6
12.6
83-UH-04
83-UH-05
83-FCU-05
83-FCU-22A
20/14
12x12 S-2
495 CFM
83-FCU-13A
83-FCU-14B
83-FCU-14A
83-FCU-13B
16/14
16/14
10/14
8"ø S-1
215 CFM
8"ø S-1
215 CFM
8"ø S-1
215 CFM
8"ø S-1
215 CFM
8"ø S-1
215 CFM
/1
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
/1
/1
T
T T
83-FCU-22C
14/14 20/14
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
/1
/1
T
T
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
/1
T
/1
/1
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
COIL THE SENSOR WIRING AND
ATTACH TO ALL THREAD USED TO
SUPPORT THE FAN COIL UNIT,
TYPICAL.
COIL THE SENSOR WIRING AND
ATTACH TO ALL THREAD USED TO
SUPPORT THE FAN COIL UNIT,
TYPICAL.
T
F
83-SA-FCU-07R
16/16
(2)14"ø R-1
750 CFM
16/16 18/14
10/14
83-FCU-07
12x12 S-2
640 CFM
12x12 S-2
640 CFM
8"ø S-1
200 CFM
ROUTE 6" O/A DUCT TO
RETURN OF 83-FCU-08.
BALANCE TO 40 CFM.
6ø
62/20
62/24
30/24M A
T C
H
LI
N E
S E
E
F
-M
H -1
B 1A
MATCHLINE
SEE /F6 83-MH-1B1A
MATCHLINE
SEE
F6
83-MH-1B1B
BALANCE TO 1,060 CFM.F S
/1
18/24
/1
14/14
F S
F
F
ELEC
CLOSET
B1C004
EXIT STAIR
(2)
B1C001
EXIT STAIR
(6)
B1C101
ELEC
CLOSET
B1C103
SCREENED
PATIO
B1C002
SCREENED
PATIO
B1C102
SUB POD C1
B1C104
SUB POD C0
B1C005
SUB POD C0
B1C005
RESIDENT
CORRIDOR
B1B002
FUTURE
EXPANSION
B1B009
SUB POD C0
B1C005
D A
T E
S
A M
P
Drawing Title
Approved Project Director:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
PSP 309070 Revisions Date
ARCHITECT/ENGINEERS: Office of
Construction and Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
FILE NAME
Project Abbreviation
F
E
D
C
B
A
F
IL
E N
A M
E
KEY PLAN
FULLY SPRINKLERED
(NOT TO SCALE)
Page Southerland Page, LLP.
1800 Main Street Suite 123
Dallas, TX 75201 pagethink.com
TEL
FAX
ARCHITECTURE / ENGINEERING / INTERIORS / CONSULTING
Austin / Dallas / Denver / Houston / Washington DC /
International Affiliate Offices
214 522 3900
214 522 4380
DWG
C
U se rs \b k in m a n \D o c u m e n ts
\3 b M
E -S
C I- R -C
E N
T R A L b k in m a n R K W
J .r v t
/2
/2
:0 :3
P
M
C:\Users\bkinman\Documents\309070b3ME-SCI-R18-CENTRAL_bkinmanR4KWJ.rvt
83-MH-1B1C
CONSTRUCTION
VA-LTSCI-D
RH
549-820B
KV
MECHANICAL - FLOOR PLAN - LEVEL B1 AREA C
LONG TERM SPINAL CORD INJURY
VA NORTH TEXAS HEALTH CARE SYSTEM
4500 S. LANCASTER RD. DALLAS, TX 75216OFFICE OF CONSTRUCTION AND FACILITIES
MANAGEMENT DIRECTOR , CENTRAL REGION
06 MAY 2021
BID PACKAGE B
BF
C
D
G
A
H
E
0' 16' 32'8' 64'
NORTH
PLAN
SCALE: 1/8" = 1'-0"F6 MECHANICAL - FLOOR PLAN - LEVEL B1 AREA C
1. REFER TO DRAWING 83-M-001 FOR HVAC LEGENDS, ABBREVIATIONS AND
GENERAL NOTES.
2. COORDINATE WORK ON THIS SHEET WITH ALL TRADES. WORK SHOWN ON
THIS SHEET IS INTENDED TO PROVIDE THE OVERALL ENGINEERING
DESIGN CONCEPT AND DOES NOT PROVIDE FOR RELOCATIONS, OFFSETS,
ETC., THAT ARE REQUIRED BY THE COORDINATION OF TRADES. THESE
SHALL BE PROVIDED BY THE CONTRACTOR AT NO ADDITIONAL COST TO
THE CONTRACT.
3. COORDINATE THE EXACT LOCATIONS OF ALL THE GRILLES, REGISTERS,
AND DIFFUSERS WITH THE ARCHITECTURAL REFLECTED CEILING PLAN.
4. ALL MECHANICAL EQUIPMENT REQUIRING ACCESS THAT IS LOCATED
ABOVE GYP. BOARD OR OTHERWISE INACCESSIBLE CEILING SHALL BE
PROVIDED WITH A CEILING ACCESS PANEL SUPPLIED AND INSTALLED BY
THE GENERAL CONTRACTOR. THE MECHANICAL CONTRACTOR SHALL
COORDINATE THE EXACT LOCATION OF THESE ACCESS PANELS WITH THE
GENERAL CONTRACTOR.
5. ALL DUCT RUNOUTS TO INDIVIDUAL DIFFUSERS, GRILLES AND REGISTERS
SHALL BE THE SAME AS THE DIFFUSER, GRILLE, REGISTER NECK SIZE
UNLESS NOTED OTHERWISE.
6. ALL MEDIUM PRESSURE DUCT RUNOUTS TO INDIVIDUAL VAV BOXES SHALL
BE THE SAME AS VAV BOX INLET SIZE UNLESS NOTED OTHERWISE. THE
LOW PRESSURE DUCT IMMEDIATELY DOWNSTREAM OF THE VAV BOX
SHALL BE THE SAME SIZE AS THE DISCHARGE OF THE VAV BOX UNLESS
NOTED OTHERWISE. IF NOTED DIFFERENT THAN DISCHARGE, PROVIDE
TRANSITION.
7. PROVIDE BALANCE DAMPERS IN SUPPLY, RETURN, AND EXHAUST DUCTS
AT ALL TAKE-OFFS TO INDIVIDUAL DIFFUSERS, GRILLES, AND REGISTERS.
IF A SINGLE DIFFUSER IS SERVED BY A DEDICATED VAV BOX THEN THE
BALANCE DAMPER AT THE TAKE-OFF MAY BE OMITTED.
8. ALL TAPS IN MEDIUM PRESSURE DUCT SHALL BE WITHOUT DAMPERS.
9. REFER TO DETAIL D8/83-M-501 FOR DUCT PRESSURE CLASSIFICATION
POINT OF CHANGE INFORMATION.
SHEET NOTES
L L
L.6 L.6
MM
7.1
7.1
P.2
P.2
Q
Q
Q.6
Q.6
R
R
8.8
8.8
M.6M.6
NN
N.2N.2
5.2
5.2
5.8
5.8
6.5
6.5
R.6
R.6
P1
P1
S.2
S.2
9.4
9.4
10.1
10.1
N.8N.8
K.2 K.2
S.8
S.8
OO
P
P
S.9
S.9
4.9 5.3
5.3
7.9
7.9
8.6
8.6
8.5
8.5
83-FCU-04
83-UH-01
83-UH-02
83-UH-03
10"ø S-1
250 CFM
10"ø S-1
250 CFM
83-FCU-22B
83-FCU-22D
20/14
12x12 S-2
495 CFM
12x12 S-2
495 CFM
83-FCU-12A
83-FCU-10A
83-FCU-10B
83-FCU-11B
83-FCU-11A
/1
/1
/1
10"ø S-1
250 CFM
F
12x12 S-2
495 CFM
12x12 S-2
495 CFM
12x12 S-2
495 CFM
12x12 S-2
495 CFM
20/1414/14
T
10x10 S-2
330 CFM
10x10 S-2
330 CFM
/1
T
T
/1
/1
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
T
T
/1
/1
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM 2
/1
/1
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2 330 CFM10x10 S-2
330 CFM
10x10 S-2 330 CFM10x10 S-2
330 CFM
10x10 S-2 330 CFM10x10 S-2
330 CFM
T
T
/1
/1
COIL THE SENSOR WIRING AND
ATTACH TO ALL THREAD USED TO
SUPPORT THE FAN COIL UNIT,
TYPICAL.
COIL THE SENSOR WIRING AND
ATTACH TO ALL THREAD USED TO
SUPPORT THE FAN COIL UNIT,
TYPICAL.
S
12"ø R-1
500 CFM
SF
14x14 S-2
640 CFM
14x14 S-9
640 CFM
MATCHLINE
SEE
/F6 83-MH-1B1B
MATCHLINE
SEE /F6 83-MH-1B1A
MATCHLINE
SEE
/F6 83-MH-1B1B
PROVIDE INTEGRAL
BALANCING DAMPERS ON
ALL EXPOSED GRILLES. TYP.
F S
F S
RESIDENT
CORRIDOR
B1A017
SUB POD D0
B1D005
SCREENED
PATIO
B1E004
SUB POD D1
B1D105
SCREENED
PATIO
B1E004
SUB POD D1
B1D105
FUTURE
EXPANSION
B1A013
FUTURE
EXPANSION
B1B009
ELEC
CLOSET
B1E002
EXIT STAIR
(5)
B1E001
D A
A M
P
Drawing Title
Approved Project Director:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
PSP 309070 Revisions Date
ARCHITECT/ENGINEERS: Office of
Construction and Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
FILE NAME
Project Abbreviation
F
E
D
C
B
A
F
IL
E N
A M
E
KEY PLAN
FULLY SPRINKLERED
(NOT TO SCALE)
Page Southerland Page, LLP.
1800 Main Street Suite 123
Dallas, TX 75201 pagethink.com
TEL
FAX
ARCHITECTURE / ENGINEERING / INTERIORS / CONSULTING
Austin / Dallas / Denver / Houston / Washington DC /
International Affiliate Offices
214 522 3900
214 522 4380
DWG
W
V A -L
T S C
IF
-D \3
B M
E -S
C I- R -b k in m a n .R
V T
/1
/2
:1
:2
A
M
W:\VA-LTSCIF-D\309070B3ME-SCI-R18-bkinman.RVT
83-MH-1B1D
CONSTRUCTION
VA-LTSCI-D
RH
549-820B
KV
MECHANICAL - FLOOR PLAN - LEVEL B1 AREA D
LONG TERM SPINAL CORD INJURY
VA NORTH TEXAS HEALTH CARE SYSTEM
4500 S. LANCASTER RD. DALLAS, TX 75216OFFICE OF CONSTRUCTION AND FACILITIES
MANAGEMENT DIRECTOR , CENTRAL REGION
06 MAY 2021
BID PACKAGE B
0' 16' 32'8' 64'
NORTH
PLAN
BF
C
D
G
A
H
E
SCALE: 1/8" = 1'-0"F6 MECHANICAL - FLOOR PLAN - LEVEL B1 AREA D
1. REFER TO DRAWING 83-M-001 FOR HVAC LEGENDS, ABBREVIATIONS AND
GENERAL NOTES.
2. COORDINATE WORK ON THIS SHEET WITH ALL TRADES. WORK SHOWN ON
THIS SHEET IS INTENDED TO PROVIDE THE OVERALL ENGINEERING
DESIGN CONCEPT AND DOES NOT PROVIDE FOR RELOCATIONS, OFFSETS,
ETC., THAT ARE REQUIRED BY THE COORDINATION OF TRADES. THESE
SHALL BE PROVIDED BY THE CONTRACTOR AT NO ADDITIONAL COST TO
THE CONTRACT.
3. COORDINATE THE EXACT LOCATIONS OF ALL THE GRILLES, REGISTERS,
AND DIFFUSERS WITH THE ARCHITECTURAL REFLECTED CEILING PLAN.
4. ALL MECHANICAL EQUIPMENT REQUIRING ACCESS THAT IS LOCATED
ABOVE GYP. BOARD OR OTHERWISE INACCESSIBLE CEILING SHALL BE
PROVIDED WITH A CEILING ACCESS PANEL SUPPLIED AND INSTALLED BY
THE GENERAL CONTRACTOR. THE MECHANICAL CONTRACTOR SHALL
COORDINATE THE EXACT LOCATION OF THESE ACCESS PANELS WITH THE
GENERAL CONTRACTOR.
5. ALL DUCT RUNOUTS TO INDIVIDUAL DIFFUSERS, GRILLES AND REGISTERS
SHALL BE THE SAME AS THE DIFFUSER, GRILLE, REGISTER NECK SIZE
UNLESS NOTED OTHERWISE.
6. ALL MEDIUM PRESSURE DUCT RUNOUTS TO INDIVIDUAL VAV BOXES SHALL
BE THE SAME AS VAV BOX INLET SIZE UNLESS NOTED OTHERWISE. THE
LOW PRESSURE DUCT IMMEDIATELY DOWNSTREAM OF THE VAV BOX
SHALL BE THE SAME SIZE AS THE DISCHARGE OF THE VAV BOX UNLESS
NOTED OTHERWISE. IF NOTED DIFFERENT THAN DISCHARGE, PROVIDE
TRANSITION.
7. PROVIDE BALANCE DAMPERS IN SUPPLY, RETURN, AND EXHAUST DUCTS
AT ALL TAKE-OFFS TO INDIVIDUAL DIFFUSERS, GRILLES, AND REGISTERS.
IF A SINGLE DIFFUSER IS SERVED BY A DEDICATED VAV BOX THEN THE
BALANCE DAMPER AT THE TAKE-OFF MAY BE OMITTED.
8. ALL TAPS IN MEDIUM PRESSURE DUCT SHALL BE WITHOUT DAMPERS.
9. REFER TO DETAIL D8/83-M-501 FOR DUCT PRESSURE CLASSIFICATION
1 QAQC 01 JAN 2023
SHEET NOTES
U.2
U.2
V
V
V.6
V.6
W
W
11.4
11.4
W.6
W.6
X
X
X.2
X.2
11.8
11.8
12.5
12.5
13.1
13.1
X.8
X.8
U
U
Y
Y
10.9
10.9
11.5
11.5
83-UH-03
83-FCU-12A
83-FCU-12B
12x12 S-2
495 CFM
14/1
T
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
20/14
12/12
T
20/14
COIL THE SENSOR WIRING AND ATTACH TO
ALL THREAD USED TO SUPPORT THE FAN
COIL UNIT, TYPICAL.
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
10x10 S-2
330 CFM
12/12
MATCHLIN
E
SEE
F6
83-M H-1
B1B
14x14 S-2
640 CFM
F S
14/14
SCREENED
PATIO
B1E004
SUB POD E0
B1E105
SCREENED
PATIO
B1E004
ELEC
CLOSET
B1E002
EXIT STAIR
(5)
B1E001
FUTURE
EXPANSION
B1B009
D A
A M
P
Drawing Title
Approved Project Director:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
PSP 309070 Revisions Date
ARCHITECT/ENGINEERS: Office of
Construction and Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
FILE NAME
Project Abbreviation
F
E
D
C
B
A
F
IL
E N
A M
E
KEY PLAN
FULLY SPRINKLERED
(NOT TO SCALE)
Page Southerland Page, LLP.
1800 Main Street Suite 123
Dallas, TX 75201 pagethink.com
TEL
FAX
ARCHITECTURE / ENGINEERING / INTERIORS / CONSULTING
Austin / Dallas / Denver / Houston / Washington DC /
International Affiliate Offices
214 522 3900
214 522 4380
DWG
C
U se rs \b k in m a n \D o c u m e n ts
\3 b M
E -S
C I- R -C
E N
T R A L b k in m a n R K W
J .r v t
/2
/2
:0 :4
P
M
C:\Users\bkinman\Documents\309070b3ME-SCI-R18-CENTRAL_bkinmanR4KWJ.rvt
83-MH-1B1E
CONSTRUCTION
VA-LTSCI-D
RH
549-820B
KV
MECHANICAL - FLOOR PLAN - LEVEL B1 AREA E
LONG TERM SPINAL CORD INJURY
VA NORTH TEXAS HEALTH CARE SYSTEM
4500 S. LANCASTER RD. DALLAS, TX 75216OFFICE OF CONSTRUCTION AND FACILITIES
MANAGEMENT DIRECTOR , CENTRAL REGION
06 MAY 2021
BID PACKAGE B
0' 16' 32'8' 64'
NORTH
PLAN
BF
C
D
G
A
H
E
SCALE: 1/8" = 1'-0"F6 MECHANICAL - FLOOR PLAN - LEVEL B1 AREA E
1. REFER TO DRAWING 83-M-001 FOR HVAC LEGENDS, ABBREVIATIONS AND
GENERAL NOTES.
2. COORDINATE WORK ON THIS SHEET WITH ALL TRADES. WORK SHOWN ON
THIS SHEET IS INTENDED TO PROVIDE THE OVERALL ENGINEERING
DESIGN CONCEPT AND DOES NOT PROVIDE FOR RELOCATIONS, OFFSETS,
ETC., THAT ARE REQUIRED BY THE COORDINATION OF TRADES. THESE
SHALL BE PROVIDED BY THE CONTRACTOR AT NO ADDITIONAL COST TO
THE CONTRACT.
3. COORDINATE THE EXACT LOCATIONS OF ALL THE GRILLES, REGISTERS,
AND DIFFUSERS WITH THE ARCHITECTURAL REFLECTED CEILING PLAN.
4. ALL MECHANICAL EQUIPMENT REQUIRING ACCESS THAT IS LOCATED
ABOVE GYP. BOARD OR OTHERWISE INACCESSIBLE CEILING SHALL BE
PROVIDED WITH A CEILING ACCESS PANEL SUPPLIED AND INSTALLED BY
THE GENERAL CONTRACTOR. THE MECHANICAL CONTRACTOR SHALL
COORDINATE THE EXACT LOCATION OF THESE ACCESS PANELS WITH THE
GENERAL CONTRACTOR.
5. ALL DUCT RUNOUTS TO INDIVIDUAL DIFFUSERS, GRILLES AND REGISTERS
SHALL BE THE SAME AS THE DIFFUSER, GRILLE, REGISTER NECK SIZE
UNLESS NOTED OTHERWISE.
6. ALL MEDIUM PRESSURE DUCT RUNOUTS TO INDIVIDUAL VAV BOXES SHALL
BE THE SAME AS VAV BOX INLET SIZE UNLESS NOTED OTHERWISE. THE
LOW PRESSURE DUCT IMMEDIATELY DOWNSTREAM OF THE VAV BOX
SHALL BE THE SAME SIZE AS THE DISCHARGE OF THE VAV BOX UNLESS
NOTED OTHERWISE. IF NOTED DIFFERENT THAN DISCHARGE, PROVIDE
TRANSITION.
7. PROVIDE BALANCE DAMPERS IN SUPPLY, RETURN, AND EXHAUST DUCTS
AT ALL TAKE-OFFS TO INDIVIDUAL DIFFUSERS, GRILLES, AND REGISTERS.
IF A SINGLE DIFFUSER IS SERVED BY A DEDICATED VAV BOX THEN THE
BALANCE DAMPER AT THE TAKE-OFF MAY BE OMITTED.
8. ALL TAPS IN MEDIUM PRESSURE DUCT SHALL BE WITHOUT DAMPERS.
DN
DN
DN
DN
SHEET NOTES
STORAGE
B1F041
SHARED OFFICE
PHYSICIANS
B1F033
OFFICE PSYCH
B1F032
OFFICE
CLINICIAN
B1F030
WORKROOM
B1F013
CLINIC
CORRIDOR
B1F015
CLINIC
CORRIDOR
B1F020
CLINIC
CORRIDOR
B1F035
UROLOGY EXAM
ROOM 5
B1F019
HAC
B1F027
CLINIC
CORRIDOR
B1F010
HALLWAY
B1F029
EXAM ROOM 2
B1F014
CYSTO
CONTROL
B1F042
PATIENT TOILET
B1F017
SCRUB ALCOVE
B1F039
A.8
B.8
A.9
83-TU-5-03
83-TU-5-01
83-TU-5-07
-T U
-4 -1
83-TU-4-14
83-TU-4-11
83-TU-4-18
-T U
-4 -2
83-TU-4-09
83-TU-4-08
83-TU-5-05
83-TU-4-25
83-TU-4-24
83-TU-4-22
83-TU-4-21
83-TU-5-06
83-TU-5-02
83-TU-4-17
83-TU-4-15
83-TU-4-12
83-TU-4-05
83-TU-4-04
83-TU-4-03
83-TU-4-07
83-TU-4-19
83-TU-5-04
83-TU-4-23
83-TU-4-13
83-TU-4-06
6"ø S-1
150 CFM
8"ø S-1
200 CFM
12"ø R-1
400 CFM
8"ø S-1
190 CFM
8"ø S-1
190 CFM
8"ø R-1
190 CFM
8"ø R-1
190 CFM
6"ø S-1
120 CFM
6"ø R-1
120 CFM
6"ø S-1
110 CFM
6"ø R-1
110 CFM
8"ø S-1
215 CFM
8"ø S-1
215 CFM
8"ø S-1
200 CFM
8"ø S-1
180 CFM
8"ø R-1
200 CFM
8"ø R-1
180 CFM
6"ø S-1
95 CFM
6"ø S-1
100 CFM
6"ø S-1
100 CFM
6"ø S-1
120 CFM
6"ø S-1
90 CFM
8"ø S-1
180 CFM
12"ø S-1
340 CFM
8"ø R-1
180 CFM
8"ø R-1
205 CFM
6"ø S-1
100 CFM
8"ø S-1
170 CFM
8"ø S-1
200 CFM
8"ø S-1
200 CFM
6"ø S-1
90 CFM
6"ø S-1
150 CFM
(2)12"ø S-1
505 CFM
8"ø E-3
150 CFM
6"ø S-3
50 CFM
6"ø S-1
60 CFM
6"ø S-1
90 CFM
8"ø S-1
175 CFM
8"ø S-1
170 CFM
8"ø R-1
170 CFM
6"ø S-3
50 CFM
8"ø E-3
150 CFM
6"ø S-1
135 CFM
6"ø S-3
50 CFM
8"ø E-3
175 CFM
8"ø S-1
180 CFM
10"ø E-1
260 CFM
10"ø E-1
260 CFM
8"ø S-1
180 CFM
6"ø S-1
135 CFM
6"ø E-3
125 CFM
8"ø S-1
180 CFM
8"ø S-1
180 CFM
8"ø S-1
180 CFM
8"ø R-1
180 CFM
8"ø R-1
180 CFM
8"ø R-1
180 CFM
6"ø S-1
90 CFM
8"ø S-1
210 CFM
8"ø R-1
190 CFM
8"ø R-1
180 CFM
8"ø R-1
210 CFM
12"ø R-1
430 CFM
10"ø S-1
320 CFM
(2)12"ø R-1
505 CFM
6"ø R-1
90 CFM
10"ø R-1
320 CFM
6"ø S-1
135 CFM
16"ø E-1
600 CFM
10"ø S-1
245 CFM
10"ø S-1
245 CFM
8" S-7
240 CFM
8" S-7
240 CFM
12"ø S-1
340 CFM
6"ø S-1
155 CFM
8x6 S-9
150 CFM
8"ø S-1
200 CFM
8"ø R-1
175 CFM
8"ø S-1
200 CFM
8"ø S-1
200 CFM
6"ø S-1
100 CFM
6"ø S-1
100 CFM
6"ø S-3
50 CFM
6"ø S-3
50 CFM
12x24 E-2
550 CFM
12x24 E-2
550 CFM
16"ø R-1
580 CFM
12"ø R-1
375 CFM
12"ø R-1
390 CFM
10"ø R-1
270 CFM
8x6 R-5
150 CFM
12"ø R-1
430 CFM
12"ø E-1
400 CFM
8"ø E-3
175 CFM
(6)10" S-8
240 CFM
8"ø E-3
150 CFM
24/18
42/24
/2
/2
/2
38/22
/1
/1
/1
/1
16/14
36/18
36/18 14/14
22/16
12/10
34/22
12/10 12/10
12/12
/1
10/10
10/10
10/10
22/22
/1
22/20
/1
/1
/1
26/16
24/12
/1
26/18 16/10
12/10
10/10
10/10
/1
20/14
/1
12/10
/1
14/16
22/14
26/16
14/14
/1
/1
T
/1
16/14
22/16
48/18
60/30
12/18
/1
F F
F
F
F
F
F
F
F
F
F
F
F
T
T T
T
T
T
T T
/1
T
T
T
T
T
T T
T
T
T
T
T
T
T
T
T
CO2
F
/1
/1
12/1010/10
/1
S
F S
F
F
/1
S
SF
F
/1
16/14 ø
/1
8ø
10/10
T
THE HVAC SYSTEM FOR THE CYSTO SUITE
WILL BE TAILORED TO THE REQUIREMENTS OF
THE FINAL CYSTO SUITE MEDICAL EQUIPMENT,
ONCE THAT EQUIPMENT HAS BEEN DETERMINED
BY THE VA. A SIEMENS SYSTEM WAS USED FOR
THE BASIS OF THIS DESIGN.
T
T T
8"ø S-7
220 CFM
8"ø S-7
220 CFM
8"ø S-7
220 CFM
83-TU-4-16
F F
S S
/1
16/16
/1
6"ø S-1
155 CFM
ø
6"ø S-1
95 CFM
/1
/2 ø
8/10
MVD
SD
SD
SD
SD
/1
/2
/1
F
SD
SD
26/14
34/22
16/1410/18
120V COMBINATION FIRE/SMOKE DAMPER,
TYP.
COORDINATE INSTALLATION WITH FIRE
ALARM
AND ELECTRICAL CONTRACTORS
S dPT
S
SD
SD
SD
S
S
SD
S S
SD
S
SD
S
SD
S
SD
S
SD
S
SD
SD
SD
SD
S
S
S
S
SD
SD
MVD
MVD
MVD
MVD
MVD
MVD
MVD
MVD
MVD
MVD
12ø
12ø
12ø
12ø
60/30
24/12
26/16
16/14
24/18
MATCHLINE
SEE /F6 83-MH-1B1A
H 6ø
F
F
F
F F
F
12/12
12/10
10/10
10ø ø
/1
STAFF TLT
B1F009
EXAM ROOM
B1F023
FEMALE
PUBLIC
TOILETS
B1F045
MALE PUBLIC
TOILETS
B1F044
CLEAN
UTILITY
B1F022
SOILED
UTILITY
B1F024
RECEPTION
B1F003
CLINIC
SEATING
B1F002
PATIENT
TOILET
B1F007
CHECK-IN
ALCOVE
B1F001
SERVICE
CORRIDOR
B1F046
CLINIC
CORRIDOR
B1F006A
CLINIC
CORRIDOR
B1F006
CLINIC
CORRIDOR
B1F020
NEURO EXAM
CONSULT
B1F008
STAFF
LOUNGE
B1F025
W|M ALCOVE
B1F005
AREAWAY
EXHAUST
N|A
CHECK-OUT
ALCOVE
B1F004
PHYSICAL
EXAM ROOM
B1F021
EXAM ROOM
B1F011
PHYSICAL
EXAM ROOM
B1F018
EXAM ROOM
B1F016
ELEC
B1F026
OFFICE CASE
MANAGER
B1F031
CYSTO
B1F040
INSTRUMENT
CLEANING
B1F043
OFFICE
UROLOGY
B1F034
SERVICE
CORRIDOR
B1F028
NURSE
STATION
B1F012
CLEAN
UTILITY
B1F038
DRESSING
B1F036
CLINIC
CORRIDOR
B1F035
PATIENT
TOILET
B1F037
KEY NOTES
DESCRIPTIONNUMBER
D A
A M
P
Drawing Title
Approved Project Director:
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
PSP 309070 Revisions Date
ARCHITECT/ENGINEERS: Office of
Construction and Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
FILE NAME
Project Abbreviation
F
E
D
C
B
A
F
IL
E N
A M
E
KEY PLAN
FULLY SPRINKLERED
(NOT TO SCALE)
Page Southerland Page, LLP.
1800 Main Street Suite 123
Dallas, TX 75201 pagethink.com
TEL
FAX
ARCHITECTURE / ENGINEERING / INTERIORS / CONSULTING
Austin / Dallas / Denver / Houston / Washington DC /
International Affiliate Offices
214 522 3900
214 522 4380
DWG
W
V A -L
T S C
IF
-D \3
B M
E -S
C I- R -b k in m a n .R
V T
/3
/2
:5 :3
A
M
W:\VA-LTSCIF-D\309070B3ME-SCI-R18-bkinman.RVT
83-MH-1B1F
CONSTRUCTION
VA-LTSCI-D
FG
549-820B
KV
MECHANICAL - FLOOR PLAN - LEVEL B1 AREA F
LONG TERM SPINAL CORD INJURY
VA NORTH TEXAS HEALTH CARE SYSTEM
4500 S. LANCASTER RD. DALLAS, TX 75216OFFICE OF CONSTRUCTION AND FACILITIES
MANAGEMENT DIRECTOR , CENTRAL REGION
06 MAY 2021
BID PACKAGE B
0' 16' 32'8' 64'
NORTH
PLAN
BF
C
D
G
A
H
E
SCALE: 1/8" = 1'-0"F6 MECHANICAL - FLOOR PLAN - LEVEL B1 AREA F
1 COMBINATION FIRE/SMOKE DAMPER INSTALLED IN LEVEL 01 FLOOR SLAB,
TYPICAL ALL DUCT PENETRATIONS THROUGH SLAB. INSTALL 120V
DAMPER ACTUATORS AT LEVEL 01 FLOOR. COORDINATE CHASE ACCESS
PANEL LOCATION WITH GENERAL CONTRACTOR, AND ACTUATOR
LOCATIONS WITH ELECTRICAL CONTRACTOR.
2 CONTRACTOR FABRICATED, EXTERNALLY INSULATED SHEETMETAL
PLENUMS SERVING FLOOR GRILLE ABOVE. REFER TO SHEET 83-MH-101F.
REF. D6/83-M-502 FOR TYPICAL FLOOR GRILLE INSTALLATION DETAIL.
3 2 HOUR RATED ENCLOSURE ENCLOSING THE FLOOR GRILLE PLENUM.
REFER TO ARCHITECTURAL PLANS FOR ENCLOSURE DETAILS.
4 PROVIDE DIFFERENTIAL PRESSURE TRANSMITTER, READING
DIFFERENTIAL PRESSURE BETWEEN CYSTO ROOM AND SCRUB ALCOVE
B1F039. TRANSMITTER SHALL INTERFACE WITH BAS AS OUTLINED IN
SEQUENCE OF OPERATION FOR CYSTO FROM TERMINAL UNITS.
1. REFER TO DRAWING 83-M-001 FOR HVAC LEGENDS, ABBREVIATIONS AND
GENERAL NOTES.
2. COORDINATE WORK ON THIS SHEET WITH ALL TRADES. WORK SHOWN ON
THIS SHEET IS INTENDED TO PROVIDE THE OVERALL ENGINEERING
DESIGN CONCEPT AND DOES NOT PROVIDE FOR RELOCATIONS, OFFSETS,
ETC., THAT ARE REQUIRED BY THE COORDINATION OF TRADES. THESE
SHALL BE PROVIDED BY THE CONTRACTOR AT NO ADDITIONAL COST TO
THE CONTRACT.
3. COORDINATE THE EXACT LOCATIONS OF ALL THE GRILLES, REGISTERS,
AND DIFFUSERS WITH THE ARCHITECTURAL REFLECTED CEILING PLAN.
4. ALL MECHANICAL EQUIPMENT REQUIRING ACCESS THAT IS LOCATED
ABOVE GYP. BOARD OR OTHERWISE INACCESSIBLE CEILING SHALL BE
PROVIDED WITH A CEILING ACCESS PANEL SUPPLIED AND INSTALLED BY
THE GENERAL CONTRACTOR. THE MECHANICAL CONTRACTOR SHALL
COORDINATE THE EXACT LOCATION OF THESE ACCESS PANELS WITH THE
GENERAL CONTRACTOR.
5. ALL DUCT RUNOUTS TO INDIVIDUAL DIFFUSERS, GRILLES AND REGISTERS
SHALL BE THE SAME AS THE DIFFUSER, GRILLE, REGISTER NECK SIZE
UNLESS NOTED OTHERWISE.
6. ALL MEDIUM PRESSURE DUCT RUNOUTS TO INDIVIDUAL VAV BOXES SHALL
BE THE SAME AS VAV BOX INLET SIZE UNLESS NOTED OTHERWISE. THE
LOW PRESSURE DUCT IMMEDIATELY DOWNSTREAM OF THE VAV BOX
SHALL BE THE SAME SIZE AS THE DISCHARGE OF THE VAV BOX UNLESS
NOTED OTHERWISE. IF NOTED DIFFERENT THAN DISCHARGE, PROVIDE
TRANSITION.
7. PROVIDE BALANCE DAMPERS IN SUPPLY, RETURN, AND EXHAUST DUCTS
AT ALL TAKE-OFFS TO INDIVIDUAL DIFFUSERS, GRILLES, AND REGISTERS.
IF A SINGLE DIFFUSER IS SERVED BY A DEDICATED VAV BOX THEN THE
BALANCE DAMPER AT THE TAKE-OFF MAY BE OMITTED.
8. ALL TAPS IN MEDIUM PRESSURE DUCT SHALL BE WITHOUT DAMPERS.
| 83-MH-1B1C |
| 83-MH-1B1D |
| 83-MH-1B1E |
| 83-MH-1B1F |
| 83-MH-1B1G |