23 c Mechl DWGs 3of12sp.pdf

PDF 6 MB Posted

Attached to
Y1DA--LTSCI VA Dallas 549-820B Long Term Spinal Cord Injury
Solicitation number
36C10F22R0045
Issued by

About this file

This document package includes mechanical drawings and specifications for a federal construction project. The drawings show HVAC system layouts and details for Level B1 of the Long Term Spinal Cord Injury facility at the VA Medical Center in Dallas, Texas. Key project information includes solicitation number 36C10F22R0045; the scope involves HVAC work for areas A, B, and C of Level B1. Ductwork, air terminals, fan coil units, air handling units and related equipment are depicted. Notes provide design guidance, equipment schedules and coordination instructions. The contracting agency is the Department of Veterans Affairs Office of Construction and Facilities Management. The solicitation release and award dates are not specified.

View the file

Other files

File Type Posted
Part II of II RFI Response.pdf PDF
01 45 00 chart.pdf PDF
36C10F22R0045 0013.docx DOCX document
RE trailer plan REV.pdf PDF
sign IN-01.33.pdf PDF
RE Field Office REV.pdf PDF
ADD-02 SPECs.pdf PDF
ADD-02 DWGs.pdf PDF
36C10F22R0045 0012.docx DOCX document
LTSCI ADDDENDUM 01drawings RV.pdf PDF
36C10F22R0045 0011.docx DOCX document
Bldg 74 ACM Survey Report.pdf PDF
36C10F22R0045 0010.docx DOCX document
36C10F22R0045 0009.docx DOCX document
36C10F22R0045 0008.docx DOCX document
83-GL-101 VA-Attachment RFI.pdf PDF
36C10F22R0045 0007.docx DOCX document
36C10F22R0045 0006.docx DOCX document
36C10F22R0045 0005.docx DOCX document
1 17 RESIDENT ENGINEER FIeld Office.pdf PDF
LTSCI Pre-proposal visit Sign In Sheets.pdf PDF
1 17 RESIDENT ENGINEER RE FIeld Office.pdf PDF
36C10F22R0045 0004.docx DOCX document
36C10F22R0045 0003.docx DOCX document
36C10F22R0045 0002.docx DOCX document
36C10F22R0045 0001.docx DOCX document
23 b Mechl DWGs 2of12sp.pdf PDF
01_a Civil DWGs 1of4 tt1.pdf PDF
01_d Civil DWGs 4of4 oc.pdf PDF
23 d Mechl DWGs 4of12sp.pdf PDF
04 IRRIGATION DWGs 1of1.pdf PDF
22 a Plmbg DWGs 1of8 tt.pdf PDF
27_a TELECOM DWGs 1of1sp.pdf PDF
26_g Elecl DWGs 7of7g.pdf PDF
20_GENERAL Vol 3 DWGs tt.pdf PDF
LTSCI ProjMan VOL 01 part 1of2 div00-div08 tt1.pdf PDF
26_d Elecl DWGs 4of7sp.pdf PDF
09_f Archl DWGs 6of12sp.pdf PDF
08.0 a Structl DWGs 1of4 tt1.pdf PDF
LTSCI ProjMan VOL 01 part 2of2 div09-div14 tt.pdf PDF
83 LTSCI MES part 1of6.pdf PDF
09_l Archl DWGs 12of12sp.pdf PDF
23 f Mechl DWGs 6of12sp.pdf PDF
VA LTSCI Bid Pack B Suppl Info part 2of2 g.pdf PDF
09_j Archl DWGs 10of12sp.pdf PDF
09_h Archl DWGs 8of12sp.pdf PDF
22 f Plmbg DWGs 6of8 tt.pdf PDF
26_b Elecl DWGs 2of7 tt.pdf PDF
26_f Elecl DWGs 6of7 tt.pdf PDF
22 c Plmbg DWGs 3of8 tt1.pdf PDF
Show 40 more

Latest 50 of 117 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DN

DN

UP

UP

UP

UP

UP

UP

DN

UP

DN

DN

D.5

1 4

E

DD.6

J.6

F

F

D

I.6

I

H.6

H

8.3

CC.6

CC

BB.6

12.3

L

L.6

M

7.1

P.2

P.2

Q

Q

Q.6

Q.6

R

R

8.8

U.2

V

V.6

W

11.4

A.8

B.8 J

G.8

6.3

7.6 7.2

13.2

13.6

BB

DD

M.6

N

N.2

6.5

R.6

R.6

P1

P1

S.2

S.2

9.4

10.1

W.6

X

X.2

11.8

12.5

13.1

AA

G.2

Z.8

Z.2

14.3

N.8

K.2

S.8

S.8

X.8

G

O

P

S.9

S.9

U

Y

Z

DD.8

F.3 F.3

6.2

12.2

16.2

E.3

1.8

D.5

D.5

1.5

A.9

1.9

6.4 6.6

12.4

12.6

7.9

8.6

10.9

11.5

E.2

D.6

8.5

SHEET NOTES

D A

T E

S

A M

P

Drawing Title

Approved Project Director:

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

PSP 309070 Revisions Date

ARCHITECT/ENGINEERS: Office of

Construction and Facilities

Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

FILE NAME

Project Abbreviation

F

E

D

C

B

A

F

IL

E N

A M

E

KEY PLAN

FULLY SPRINKLERED

(NOT TO SCALE)

Page Southerland Page, LLP.

1800 Main Street Suite 123

Dallas, TX 75201 pagethink.com

TEL

FAX

ARCHITECTURE / ENGINEERING / INTERIORS / CONSULTING

Austin / Dallas / Denver / Houston / Washington DC /

International Affiliate Offices

214 522 3900

214 522 4380

DWG

C

U se rs \b k in m a n \D o c u m e n ts

\3 b M

E -S

C I- R -C

E N

T R A L b k in m a n R K W

J .r v t

/2

/2

:0 :1

P

M

C:\Users\bkinman\Documents\309070b3ME-SCI-R18-CENTRAL_bkinmanR4KWJ.rvt

83-MH-1B1

CONSTRUCTION

VA-LTSCI-D

RH

549-820B

KV

MECHANICAL - FLOOR PLAN - LEVEL B1 OVERALL

LONG TERM SPINAL CORD INJURY

VA NORTH TEXAS HEALTH CARE SYSTEM

4500 S. LANCASTER RD. DALLAS, TX 75216OFFICE OF CONSTRUCTION AND FACILITIES

MANAGEMENT DIRECTOR , CENTRAL REGION

06 MAY 2021

BID PACKAGE B

SCALE: 1/16" = 1'-0"F6 MECHANICAL OVERALL PLAN - LEVEL B1 0' 16' 32'8' 64'

NORTH

PLAN

BF

C

D

G

A

H

E

1. REFER TO DRAWING 83-M-001 FOR HVAC LEGENDS, ABBREVIATIONS AND

GENERAL NOTES.

2. COORDINATE WORK ON THIS SHEET WITH ALL TRADES. WORK SHOWN ON

THIS SHEET IS INTENDED TO PROVIDE THE OVERALL ENGINEERING

DESIGN CONCEPT AND DOES NOT PROVIDE FOR RELOCATIONS, OFFSETS,

ETC., THAT ARE REQUIRED BY THE COORDINATION OF TRADES. THESE

SHALL BE PROVIDED BY THE CONTRACTOR AT NO ADDITIONAL COST TO

THE CONTRACT.

3. COORDINATE THE EXACT LOCATIONS OF ALL THE GRILLES, REGISTERS,

AND DIFFUSERS WITH THE ARCHITECTURAL REFLECTED CEILING PLAN.

4. ALL MECHANICAL EQUIPMENT REQUIRING ACCESS THAT IS LOCATED

ABOVE GYP. BOARD OR OTHERWISE INACCESSIBLE CEILING SHALL BE

PROVIDED WITH A CEILING ACCESS PANEL SUPPLIED AND INSTALLED BY

THE GENERAL CONTRACTOR. THE MECHANICAL CONTRACTOR SHALL

COORDINATE THE EXACT LOCATION OF THESE ACCESS PANELS WITH THE

GENERAL CONTRACTOR.

5. ALL DUCT RUNOUTS TO INDIVIDUAL DIFFUSERS, GRILLES AND REGISTERS

SHALL BE THE SAME AS THE DIFFUSER, GRILLE, REGISTER NECK SIZE

UNLESS NOTED OTHERWISE.

6. ALL MEDIUM PRESSURE DUCT RUNOUTS TO INDIVIDUAL VAV BOXES SHALL

BE THE SAME AS VAV BOX INLET SIZE UNLESS NOTED OTHERWISE. THE

LOW PRESSURE DUCT IMMEDIATELY DOWNSTREAM OF THE VAV BOX

SHALL BE THE SAME SIZE AS THE DISCHARGE OF THE VAV BOX UNLESS

NOTED OTHERWISE. IF NOTED DIFFERENT THAN DISCHARGE, PROVIDE

TRANSITION.

7. PROVIDE BALANCE DAMPERS IN SUPPLY, RETURN, AND EXHAUST DUCTS

AT ALL TAKE-OFFS TO INDIVIDUAL DIFFUSERS, GRILLES, AND REGISTERS.

IF A SINGLE DIFFUSER IS SERVED BY A DEDICATED VAV BOX THEN THE

BALANCE DAMPER AT THE TAKE-OFF MAY BE OMITTED.

8. ALL TAPS IN MEDIUM PRESSURE DUCT SHALL BE WITHOUT DAMPERS.

9. REFER TO DETAIL D8/83-M-501 FOR DUCT PRESSURE CLASSIFICATION

POINT OF CHANGE INFORMATION.

UP

F

D

D

B.8 B.8

F.3 F.3

E.3

1.81.51.9

E.2

D.6

83-TU-4-31

83-FCU-04

83-TU-4-18

-T U

-4 -2

83-TU-4-25

83-TU-4-24

83-TU-4-22

83-TU-4-21

83-TU-4-17

83-TU-4-15

83-TU-4-19

83-TU-4-26

83-TU-4-23

83-TU-4-27

-T U

-4 -2

83-TU-4-32

-T U

-4 -2

83-TU-4-30

6"ø S-1

100 CFM

6"ø S-1

100 CFM

6"ø S-1

120 CFM

8"ø S-1

180 CFM

12"ø S-1

340 CFM

8"ø R-1

180 CFM

8"ø R-1

205 CFM

6"ø S-1

100 CFM

8"ø S-1

170 CFM

8"ø S-1

200 CFM

6"ø S-3

50 CFM

8"ø E-3

150 CFM

8"ø S-1

180 CFM

10"ø E-1

260 CFM

10"ø E-1

260 CFM

8"ø S-1

180 CFM

8"ø R-1

180 CFM

6"ø S-1

90 CFM

8"ø R-1

210 CFM

12"ø R-1

430 CFM

6"ø S-1

135 CFM

6"ø S-1

135 CFM

16"ø E-1

600 CFM

10"ø S-1

245 CFM

10"ø S-1

245 CFM

8" S-7

240 CFM

8" S-7

240 CFM

12"ø S-1

340 CFM

8"ø S-1

200 CFM

6"ø S-1

100 CFM

6"ø S-1

100 CFM

6"ø S-3

50 CFM

6"ø S-3

50 CFM

16"ø R-1

580 CFM

12"ø R-1

375 CFM

12"ø R-1

390 CFM

12"ø R-1

430 CFM

8"ø E-3

175 CFM

8"ø E-3

150 CFM

6"ø S-4

120 CFM

12"ø S-1

425 CFM

6"ø S-1

150 CFM

8"ø S-1

180 CFM

8"ø S-1

160 CFM

8"ø S-1

180 CFM

16x16 R-5

600 CFM

16x16 S-9

600 CFM

10"ø S-1

250 CFM

10"ø S-1

250 CFM

10"ø S-1

250 CFM

8"ø S-1

210 CFM

12"ø R-1

500 CFM

6"ø S-1

140 CFM

12"ø R-1

410 CFM

12"ø S-1

425 CFM

6"ø S-1

150 CFM

8" S-7

220 CFM

8" S-7

220 CFM

8" S-7

220 CFM

8" S-7

220 CFM

16"ø R-1

375 CFM

16"ø R-1

375 CFM

/1

/1

/2

12/10

/1

24/18

42/24

/2

/2

/2

38/22

/1

/1

/1

/1

16/14

36/18

36/18 14/14

22/16

12/10

34/22

12/10 12/10

12/12

/1

10/10

10/10

10/10

/1

/1

/1

22/22

/1

22/20

/1

16/14

22/16

48/18

60/30

/1

12/18

/1

83-FCU-02

83-FCU-03

83-CRC-01

F F

F

F

F

F

F

F

F

F

F

F

F

F

F

F

T

T T

T

T

T

T T

T

T T

T

T

/1

T

CO2

F

T

83-FCU-22A

83-FCU-22B

83-FCU-22D

20/1414/14

20/14

14/14

12x12 S-2

495 CFM

12x12 S-2

495 CFM

12x12 S-2

495 CFM

12x12 S-2

495 CFM

12x12 S-2

495 CFM

12x12 S-2

495 CFM

12x12 S-2

495 CFM

12x12 S-2

495 CFM

/1

/1

10/14

/1

10"ø S-1

250 CFM

F

12x12 S-2

495 CFM

12x12 S-2

495 CFM

12x12 S-2

495 CFM

12x12 S-2

495 CFM

20/14

14/14

T

T

T

T

T

COIL THE SENSOR WIRING AND

ATTACH TO ALL THREAD USED TO

SUPPORT THE FAN COIL UNIT, TYPICAL.

COIL THE SENSOR WIRING AND

ATTACH TO ALL THREAD USED TO

SUPPORT THE FAN COIL UNIT, TYPICAL.

83-FCU-22C

12x12 S-2

495 CFM

12x12 S-2

495 CFM

12x12 S-2

495 CFM

14/14

20/14

12x12 S-2

495 CFM

S

F S

F

F

/1

FLOOR GRILLES FED FROM LEVEL B2.

REF. SHEET 83-MH-1B2A FOR

DISTRIBUTION, TYPICAL OF 7

T

T

T T

T

T

T

T

T T

T

TO 83-TU-4-62

REF. 83-MH-102a

TO 83-TU-4-01

REF. 83-MH-1B2A

TO 83-TU-4-64

REF. 83-MH-102A

TO 83-TU-4-02

REF. 83-MH-1B2A

8"ø S-7

220 CFM

8"ø S-7

220 CFM

8"ø S-7

220 CFM

48x6 S-6

600 CFM

48x6 S-6

600 CFM

48x6 S-6

600 CFM

48x6 S-6

600 CFM

24x6 S-6

300 CFM

24x6 S-6

300 CFM

36x6 S-6

450 CFM

83-TU-4-16

F F

S S

/1

16x16 S-9

490 CFM

16x16 R-5

490 CFM

16x16 S-9

1000 CFM

16x16 R-5

1000 CFM

F F

F F F

F

F

83-SA-FCU-02S

83-SA-FCU-02R

83-SA-FCU-03R

83-SA-FCU-03S

83-SA-CRC-01R

83-SA-CRC-01S

(2)14"ø R-1

750 CFM

6"ø S-1

155 CFM

ø

/2 ø

8/10

/1

/1

/1

/1

/1

/1

MVD

RATED GYP BOARD

ENCLOSURE BENEATH LEVEL

1 FLOORSLAB

SD

SD

SD

SD

/1

/2

/1

F ø 16/16

18/14 34/22

16/1410/18

S

S

S

S

S

SD

SD

SD

S

S

SD

S S

SD

S

SD

S

SD

S

SD

S

SD

S

SD

SD

SD

SD

S

S

S

S

SD

SD

S

F S

SD

MVD

MVD

MVD

MVD

MVD

MVD

12"ø R-1

500 CFM

SF

12ø

12ø

12ø

12ø

REFER TO SPECIFICATION

SECTION 23 07 11 FOR

INSULATION REQUIREMENTS.

TYPICAL ALL SHEETS.

CONNECT 8" OUTDOOR AIR

DUCT TO 16/14 RETURN

DUCT SERVING 83-FCU-04.

BALANCE TO 100 CFM.

12x12 S-2

640 CFM

14x14 S-2

640 CFM

8x8 S-9

40 CFM

8x8 S-9

40 CFM

8x8 S-9

40 CFM

60/30

24/12

26/16

16/14

24/18

/1

16/14

8ø

/1

12/12

AFMS

62/30 46/24

62/24

32/52

M A

T C

H

LI

N E

R E

F

F

-M

H -1

B 1B

MATCHLINE

SEE /F6 83-MH-1B1F

S

F F

F

BALANCE TO 1,100 CFM

PROVIDE INTEGRAL

BALANCING DAMPERS ON

ALL EXPOSED GRILLES. TYP.

PROVIDE INTEGRAL

BALANCING DAMPERS ON

ALL EXPOSED GRILLES. TYP.

PROVIDE INTEGRAL

BALANCING DAMPERS ON

ALL EXPOSED GRILLES. TYP.

F S

F S

D7

83-M-305

F

F

6ø

8ø

14/14

RESIDENT

ELEVATOR

LOBBY

B1B001

FUTURE

EXPANSION

B1A013

STAFF TLT

B1F009

ELEC

B1A014

TELE COMM

B1A016

EXAM ROOM

B1F023

FEMALE

PUBLIC

TOILETS

B1F045

MALE PUBLIC

TOILETS

B1F044

CLEAN

UTILITY

B1F022

SOILED

UTILITY

B1F024

PUBLIC

LOBBY

B1A002

RECEPTION

B1F003

CLINIC

SEATING

B1F002

SERVICE

ELEVATOR

LOBBY

B1A012

EXIT STAIR

(1)

B1A007

INFORMATION

DESK

B1A006

PATIENT

TOILET

B1F007

VESTIBULE

B1A001

PUBLIC

ELEVATOR

CAB (P1)

B1A009B

SERVICE

ELEVATOR

CAB (S3)

B1A010B

RESIDENT

ELEVATOR

CAB (P6)

1B001B

PUBLIC

CORRIDOR

B1A005

CHECK-IN

ALCOVE

B1F001

RESIDENT

CORRIDOR

B1B004

SERVICE

CORRIDOR

B1A011

SERVICE

CORRIDOR

B1F046

CLINIC

CORRIDOR

B1F006A

CLINIC

CORRIDOR

B1F006

CLINIC

CORRIDOR

B1F020

RESIDENT

CORRIDOR

B1A017

NEURO EXAM

CONSULT

B1F008

STAFF

LOUNGE

B1F025

SECURITY

B1A015

W|M ALCOVE

B1F005

AREAWAY

EXHAUST

N|A

PUBLIC

ELEVATOR

LOBBY

B1A008

CHECK-OUT

ALCOVE

B1F004

RESIDENT

ELEVATOR

CAB (P5)

1B001A

SERVICE

ELEVATOR

CAB (S4)

B1A010A

PUBLIC

ELEVATOR

CAB (P2)

B1A009A

SEATING

B1A003 SEATING

B1A004

FUTURE

EXPANSION

B1A013

FUTURE

EXPANSION

B1A013

FUTURE

EXPANSION

B1A013

SHEET NOTES

KEY NOTES

DESCRIPTIONNUMBER

D A

A M

P

Drawing Title

Approved Project Director:

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

PSP 309070 Revisions Date

ARCHITECT/ENGINEERS: Office of

Construction and Facilities

Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

FILE NAME

Project Abbreviation

F

E

D

C

B

A

F

IL

E N

A M

E

KEY PLAN

FULLY SPRINKLERED

(NOT TO SCALE)

Page Southerland Page, LLP.

1800 Main Street Suite 123

Dallas, TX 75201 pagethink.com

TEL

FAX

ARCHITECTURE / ENGINEERING / INTERIORS / CONSULTING

Austin / Dallas / Denver / Houston / Washington DC /

International Affiliate Offices

214 522 3900

214 522 4380

DWG

W

V A -L

T S C

IF

-D \3

B M

E -S

C I- R -b k in m a n .R

V T

/1

/2

:1

:1

A

M

W:\VA-LTSCIF-D\309070B3ME-SCI-R18-bkinman.RVT

83-MH-1B1A

CONSTRUCTION

VA-LTSCI-D

FG

549-820B

KV

MECHANICAL - FLOOR PLAN - LEVEL B1 AREA A

LONG TERM SPINAL CORD INJURY

VA NORTH TEXAS HEALTH CARE SYSTEM

4500 S. LANCASTER RD. DALLAS, TX 75216OFFICE OF CONSTRUCTION AND FACILITIES

MANAGEMENT DIRECTOR , CENTRAL REGION

06 MAY 2021

BID PACKAGE B

SCALE: 1/8" = 1'-0"F6 MECHANICAL - FLOOR PLAN - LEVEL B1 AREA A 0' 16' 32'8' 64'

NORTH

PLAN

BF

C

D

G

A

H

E

1 COMBINATION FIRE/SMOKE DAMPER INSTALLED IN LEVEL 01 FLOOR SLAB,

TYPICAL ALL DUCT PENETRATIONS THROUGH SLAB. INSTALL 120V

DAMPER ACTUATORS AT LEVEL 01 FLOOR. COORDINATE CHASE ACCESS

PANEL LOCATION WITH GENERAL CONTRACTOR, AND ACTUATOR

LOCATIONS WITH ELECTRICAL CONTRACTOR. EXTEND SUPPLY, RETURN,

AND EXHAUST DUCTS 6" BELOW FLOOR SLAB AND CAP TO PREVENT

LEAKAGE. TRUNKS WILL BE EXTENDED AS PART OF THE FUTURE LEVEL

B1 FINISH OUT PROJECT.

2 CONTRACTOR TO INSTALL 2" GALVANIZED STEEL POULTRY NETTING.

ACROSS FACE OF BOTH SUPPLY AND RETURN GRILLE IN ALL TELECOM,

IT, AND SECURITY ROOMS. FOLD CLOTH BEHIND GRILLE BORDER PRIOR

TO GRILLE ATTACHMENT TO WALL SO NETTING CANNOT BE PULLED OFF.

1. REFER TO DRAWING 83-M-001 FOR HVAC LEGENDS, ABBREVIATIONS AND

GENERAL NOTES.

2. COORDINATE WORK ON THIS SHEET WITH ALL TRADES. WORK SHOWN ON

THIS SHEET IS INTENDED TO PROVIDE THE OVERALL ENGINEERING

DESIGN CONCEPT AND DOES NOT PROVIDE FOR RELOCATIONS, OFFSETS,

ETC., THAT ARE REQUIRED BY THE COORDINATION OF TRADES. THESE

SHALL BE PROVIDED BY THE CONTRACTOR AT NO ADDITIONAL COST TO

THE CONTRACT.

3. COORDINATE THE EXACT LOCATIONS OF ALL THE GRILLES, REGISTERS,

AND DIFFUSERS WITH THE ARCHITECTURAL REFLECTED CEILING PLAN.

4. ALL MECHANICAL EQUIPMENT REQUIRING ACCESS THAT IS LOCATED

ABOVE GYP. BOARD OR OTHERWISE INACCESSIBLE CEILING SHALL BE

PROVIDED WITH A CEILING ACCESS PANEL SUPPLIED AND INSTALLED BY

THE GENERAL CONTRACTOR. THE MECHANICAL CONTRACTOR SHALL

COORDINATE THE EXACT LOCATION OF THESE ACCESS PANELS WITH THE

GENERAL CONTRACTOR.

5. ALL DUCT RUNOUTS TO INDIVIDUAL DIFFUSERS, GRILLES AND REGISTERS

SHALL BE THE SAME AS THE DIFFUSER, GRILLE, REGISTER NECK SIZE

UNLESS NOTED OTHERWISE.

6. ALL MEDIUM PRESSURE DUCT RUNOUTS TO INDIVIDUAL VAV BOXES SHALL

BE THE SAME AS VAV BOX INLET SIZE UNLESS NOTED OTHERWISE. THE

LOW PRESSURE DUCT IMMEDIATELY DOWNSTREAM OF THE VAV BOX

SHALL BE THE SAME SIZE AS THE DISCHARGE OF THE VAV BOX UNLESS

NOTED OTHERWISE. IF NOTED DIFFERENT THAN DISCHARGE, PROVIDE

TRANSITION.

7. PROVIDE BALANCE DAMPERS IN SUPPLY, RETURN, AND EXHAUST DUCTS

AT ALL TAKE-OFFS TO INDIVIDUAL DIFFUSERS, GRILLES, AND REGISTERS.

IF A SINGLE DIFFUSER IS SERVED BY A DEDICATED VAV BOX THEN THE

BALANCE DAMPER AT THE TAKE-OFF MAY BE OMITTED.

8. ALL TAPS IN MEDIUM PRESSURE DUCT SHALL BE WITHOUT DAMPERS.

9. REFER TO DETAIL D8/83-M-501 FOR DUCT PRESSURE CLASSIFICATION

1 QAQC 01 JAN 2023

DN

12'x11' EMERGENCY GENERATOR ROOM DISCHARGE

LOUVER WITH ATTACHED120V MOTORIZED DAMPERS.

DAMPERS TO MATCH LOUVER SIZE. COORDINATE

SHEET METAL TRANSITION AND CONNECTION TO

RADIATOR WITH ACTUAL GENERATOR TO BE

INSTALLED.

27'-7"x11' EMERGENCY GENERATOR

ROOM

INTAKE LOUVER WITH ATTACHED

120 V MOTORIZED DAMPERS MATCHING

LOUVER SIZE

E

F

D

16.2

83-UH-04

10"ø S-1

250 CFM

10"ø S-1

250 CFM

8"ø S-1

210 CFM

12"ø R-1

500 CFM

83-FCU-05

T

T

T

T

83-FCU-08 83-CRC-03

83-FCU-06

83-CRC-02

T

83-FCU-13A

83-FCU-12A

83-FCU-13B

16/14

16/1

/1

8"ø S-1

215 CFM

8"ø S-1

215 CFM

8"ø S-1

215 CFM

8"ø S-1

215 CFM

8"ø S-1

215 CFM

83-FCU-12B

8"ø S-1

215 CFM

10/14

/1

16x16 R-5

1000 CFM

16x16 S-9

1000 CFM

83-FCU-23B

83-FCU-23A

16x16 R-5

490 CFM

16x16 S-9

490 CFM

16x16 R-5

600 CFM

16x16 S-9

600 CFM

16x16 R-5

300 CFM

16x16 S-9

300 CFM

T

12x12 S-2

495 CFM

12x12 S-2

495 CFM

12x12 S-2

495 CFM

12x12 S-2

495 CFM

14/14

20/14

12x12 S-2

495 CFM

12x12 S-2

495 CFM

12x12 S-2

495 CFM

12x12 S-2

495 CFM

14/1

20/1

10x10 S-2

330 CFM

10x10 S-2

330 CFM

10x10 S-2

330 CFM

10x10 S-2

330 CFM

10x10 S-2

330 CFM

10x10 S-2

330 CFM

20/14

12/12

T

T

10x10 S-2

330 CFM

10x10 S-2

330 CFM

10x10 S-2

330 CFM

10x10 S-2

330 CFM

10x10 S-2

330 CFM

10x10 S-2

330 CFM

20/14

12/12

T

20/14

T

T

COIL THE SENSOR WIRING AND ATTACH TO

ALL THREAD USED TO SUPPORT THE FAN

COIL UNIT, TYPICAL.

COIL THE SENSOR WIRING AND ATTACH TO

ALL THREAD USED TO SUPPORT THE FAN

COIL UNIT, TYPICAL.

T

10x10 S-2

330 CFM

22/14

83-FCU-26

10x10 S-2

350 CFM

10x10 S-2

350 CFM

10x10 S-2

350 CFM

10x10 S-2

350 CFM

10x10 S-2

350 CFM

10x10 S-2

350 CFM

SD

83-UH-11

EMERGENCY GENERATOR

T

83-FCU-09

F

F

F

F

F

F

F

F

83-SA-FCU-06R

83-SA-FCU-06S

83-SA-FCU-07S

83-SA-CRC-02S

83-SA-CRC-02R

83-SA-FCU-08R

83-SA-FCU-08S

83-SA-FCU-07R

16/16

16x14 R-5

500 CFM

/8

F

/1

10/8

10/8

T

83-FCU-30

8x6 S-2

90 CFM

8x6 S-2

90 CFM

8x6 S-2

90 CFM

8x6 S-2

90 CFM

(2)14"ø R-1

750 CFM

T

16/16

18/14

GENERATOR MUFFLER SUSPENDED

FROM OVERHEAD CONSTRUCTION

16/16

16/16

/1

/8

16/16

/1

16/16

16/16

/1

/1

83-FCU-07

(3)12x12ø S-2

660 CFM

8x6 S-2

90 CFM

RETURN AIR PLENUM

S

F S

SD

SD

SD

RETURN AIR

PLENUM

LOCATE HVAC EQUIPMENT

OVER AISLES, NOT OVER

ELECTRICAL EQUIPMENT

OR PANELS.

12x12 S-2

640 CFM

8"ø S-1

200 CFM

14x14 S-9

640 CFM

ROUTE 6" O/A DUCT TO

RETURN OF 83-FCU-08.

BALANCE TO 40 CFM.

6/6

6ø

6ø

ROUTE 6" O/A DUCT TO

RETURN OF 83-FCU-30.

BALANCE TO 80 CFM.

8x6 S-9

40 CFM

83-FCU-31

F1

83-M-303

62/20

62/24

30/24

M A

T C

H

LI

N E

S E

E

F

-M

H -1

B 1A

MATCHLIN

E

SEE

F6

83-M H-1B1E

M

ATCHLI

NE

SEE

F6

-M

H-1 B1C

14x14 S-2

640 CFM

BALANCE TO 1,060 CFM.

F S

14/1

14/14

16/14

10/1

18/2

14/14

14/1

F S

F

F

8x8 S-2

100 CFM

F

T

MATCHLINE

SEE

F6

83-MH-1B1D

F

F S

S

RESIDENT

ELEVATOR

LOBBY

B1B001

EXIT STAIR

(6)

B1C101

ELEC

CLOSET

B1C103

SCREENED

PATIO

B1C102

ELEC

CLOSET

B1B003

SUB POD C1

B1C104

RESIDENT

ELEVATOR

CAB (P6)

1B001B

RESIDENT

CORRIDOR

B1B004

RESIDENT

CORRIDOR

B1A017

RESIDENT

ELEVATOR

CAB (P5)

1B001A

RESIDENT

CORRIDOR

B1B002

FUTURE

EXPANSION

B1B009

ELEC

B1B010

TELE COMM

B1B006

EXIT STAIR

(7)

B1B011

ELECTRICAL

GENERATOR

B1B013

NORMAL

POWER

SWITCHGEAR

B1B012

EMERGENCY

POWER

SWITCHGEAR

B1B014

SECURITY

B1B007

FIRE PUMP

ROOM

B1B015

MDF

B1B016

MECH CHASE

N|A

SUB POD E0

B1E105

FUTURE

EXPANSION

B1B009

FUTURE

EXPANSION

B1B009

SHEET NOTES

KEY NOTES

DESCRIPTIONNUMBER

D A

A M

P

Drawing Title

Approved Project Director:

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

PSP 309070 Revisions Date

ARCHITECT/ENGINEERS: Office of

Construction and Facilities

Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

FILE NAME

Project Abbreviation

F

E

D

C

B

A

F

IL

E N

A M

E

KEY PLAN

FULLY SPRINKLERED

(NOT TO SCALE)

Page Southerland Page, LLP.

1800 Main Street Suite 123

Dallas, TX 75201 pagethink.com

TEL

FAX

ARCHITECTURE / ENGINEERING / INTERIORS / CONSULTING

Austin / Dallas / Denver / Houston / Washington DC /

International Affiliate Offices

214 522 3900

214 522 4380

DWG

W

V A -L

T S C

IF

-D \3

B M

E -S

C I- R -b k in m a n .R

V T

/1

/2

:1

:2

A

M

W:\VA-LTSCIF-D\309070B3ME-SCI-R18-bkinman.RVT

83-MH-1B1B

CONSTRUCTION

VA-LTSCI-D

FG

549-820B

KV

MECHANICAL - FLOOR PLAN - LEVEL B1 AREA B

LONG TERM SPINAL CORD INJURY

VA NORTH TEXAS HEALTH CARE SYSTEM

4500 S. LANCASTER RD. DALLAS, TX 75216OFFICE OF CONSTRUCTION AND FACILITIES

MANAGEMENT DIRECTOR , CENTRAL REGION

06 MAY 2021

BID PACKAGE B

SCALE: 1/8" = 1'-0"F6 MECHANICAL - FLOOR PLAN - LEVEL B1 AREA B

0' 16' 32'8' 64'

NORTH

PLAN

BF

C

D

G

A

H

E

1 COMBINATION FIRE/SMOKE DAMPER INSTALLED IN LEVEL 01 FLOOR SLAB,

TYPICAL ALL DUCT PENETRATIONS THROUGH SLAB. INSTALL 120V

DAMPER ACTUATORS AT LEVEL 01 FLOOR. COORDINATE CHASE ACCESS

PANEL LOCATION WITH GENERAL CONTRACTOR, AND ACTUATOR

LOCATIONS WITH ELECTRICAL CONTRACTOR. EXTEND SUPPLY, RETURN,

AND EXHAUST DUCTS 6" BELOW FLOOR SLAB AND CAP TO PREVENT

LEAKAGE. TRUNKS WILL BE EXTENDED AS PART OF THE FUTURE LEVEL

B1 FINISH OUT PROJECT.

2 CONTRACTOR TO INSTALL 2" GALVANIZED STEEL POULTRY NETTING.

ACROSS FACE OF BOTH SUPPLY AND RETURN GRILLE IN ALL TELECOM,

IT, AND SECURITY ROOMS. FOLD CLOTH BEHIND GRILLE BORDER PRIOR

TO GRILLE ATTACHMENT TO WALL SO NETTING CANNOT BE PULLED OFF.

1. REFER TO DRAWING 83-M-001 FOR HVAC LEGENDS, ABBREVIATIONS AND

GENERAL NOTES.

2. COORDINATE WORK ON THIS SHEET WITH ALL TRADES. WORK SHOWN ON

THIS SHEET IS INTENDED TO PROVIDE THE OVERALL ENGINEERING

DESIGN CONCEPT AND DOES NOT PROVIDE FOR RELOCATIONS, OFFSETS,

ETC., THAT ARE REQUIRED BY THE COORDINATION OF TRADES. THESE

SHALL BE PROVIDED BY THE CONTRACTOR AT NO ADDITIONAL COST TO

THE CONTRACT.

3. COORDINATE THE EXACT LOCATIONS OF ALL THE GRILLES, REGISTERS,

AND DIFFUSERS WITH THE ARCHITECTURAL REFLECTED CEILING PLAN.

4. ALL MECHANICAL EQUIPMENT REQUIRING ACCESS THAT IS LOCATED

ABOVE GYP. BOARD OR OTHERWISE INACCESSIBLE CEILING SHALL BE

PROVIDED WITH A CEILING ACCESS PANEL SUPPLIED AND INSTALLED BY

THE GENERAL CONTRACTOR. THE MECHANICAL CONTRACTOR SHALL

COORDINATE THE EXACT LOCATION OF THESE ACCESS PANELS WITH THE

GENERAL CONTRACTOR.

5. ALL DUCT RUNOUTS TO INDIVIDUAL DIFFUSERS, GRILLES AND REGISTERS

SHALL BE THE SAME AS THE DIFFUSER, GRILLE, REGISTER NECK SIZE

UNLESS NOTED OTHERWISE.

6. ALL MEDIUM PRESSURE DUCT RUNOUTS TO INDIVIDUAL VAV BOXES SHALL

BE THE SAME AS VAV BOX INLET SIZE UNLESS NOTED OTHERWISE. THE

LOW PRESSURE DUCT IMMEDIATELY DOWNSTREAM OF THE VAV BOX

SHALL BE THE SAME SIZE AS THE DISCHARGE OF THE VAV BOX UNLESS

NOTED OTHERWISE. IF NOTED DIFFERENT THAN DISCHARGE, PROVIDE

TRANSITION.

7. PROVIDE BALANCE DAMPERS IN SUPPLY, RETURN, AND EXHAUST DUCTS

AT ALL TAKE-OFFS TO INDIVIDUAL DIFFUSERS, GRILLES, AND REGISTERS.

IF A SINGLE DIFFUSER IS SERVED BY A DEDICATED VAV BOX THEN THE

BALANCE DAMPER AT THE TAKE-OFF MAY BE OMITTED.

8. ALL TAPS IN MEDIUM PRESSURE DUCT SHALL BE WITHOUT DAMPERS.

9. REFER TO DETAIL D8/83-M-501 FOR DUCT PRESSURE CLASSIFICATION

1 QAQC 01 JAN 2023

83-MH-1B1
83-MH-1B1A
83-MH-1B1B