36C10F19R0003-024.pdf

PDF 1 MB Posted

Attached to
Research Office Building (ROB) Connecting Bridge VAPHS, Pittsburgh, PA
Solicitation number
36C10F19R0003
Issued by

About this file

36C10F19R0003 COMBINED ELECTRICAL _ TELECOM.pdf

View the file

Other files

File Type Posted
36C10F19C0016-000.docx DOCX document
36C10F19R0003-0007000.docx DOCX document
36C10F19R0003-0007002.pdf PDF
36C10F19R0003-0007003.pdf PDF
36C10F19R0003-0007004.pdf PDF
36C10F19R0003-0007005.pdf PDF
36C10F19R0003-0007001.pdf PDF
36C10F19R0003-0006003.pdf PDF
36C10F19R0003-0006001.pdf PDF
36C10F19R0003-0006002.pdf PDF
36C10F19R0003-0006000.docx DOCX document
36C10F19R0003-0005000.docx DOCX document
36C10F19R0003-0005001.pdf PDF
36C10F19R0003-0005003.pdf PDF
36C10F19R0003-0005004.pdf PDF
36C10F19R0003-0005002.pdf PDF
36C10F19R0003-0004000.docx DOCX document
36C10F19R0003-0003000.docx DOCX document
36C10F19R0003-0002002.pdf PDF
36C10F19R0003-0002001.pdf PDF
36C10F19R0003-0002000.docx DOCX document
36C10F19R0003-0001001.pdf PDF
36C10F19R0003-0001000.docx DOCX document
36C10F19R0003-014.pdf PDF
36C10F19R0003-019.pdf PDF
36C10F19R0003-016.pdf PDF
36C10F19R0003-020.pdf PDF
36C10F19R0003-022.pdf PDF
36C10F19R0003-023.pdf PDF
36C10F19R0003-018.pdf PDF
36C10F19R0003-013.docx DOCX document
36C10F19R0003-017.pdf PDF
36C10F19R0003-021.pdf PDF
36C10F19R0003-015.pdf PDF
36C10F19R0003-000.docx DOCX document
36C10F19R0003.docx DOCX document
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DNUP

DN

F B

F B

F B

F B

C R

C R

DC

F

4 5 6

EXISTING BUILDING 1

2ND FLOOR

AREA W

EXISTING BUILDING 30

2ND FLOOR

NE

F

B

S

D

E

E.6

E.7 F

3.4

6.5

6.1

12.8 x.8x.7x.6x.5x.4 x.19 x.18 x.17 x.16 x.14 x.2 x.C

EA

x.J x.L x.N x.P x.3

J 11

D

D

F B

FULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

Office of

Facilities

Management o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t 4 o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

BIDDING DOCUMENTS - FEBRUARY 22, 2019

VA CARES CONSOLIDATION

VAMC, PITTSBURGH, PA

CONNECTING BRIDGE

ESD-801

646CA2500.23

AuthorChecker

ELECTRICAL DEMOLITION

PLAN

VAPHS UNIVERSITY DRIVE

1 & 30

1/8" = 1'-0"

ELECTRICAL DEMOLITION PLAN

Key Notes

EXISTING RECESSED LIGHTING, EXIT SIGNS, DUPLEX RECEPTACLES AND

FIRE ALARM DEVICES SHOWN HERE SHALL BE DE-ENERGIZED,

DISCONNECTED AND REMOVED BACK TO SOURCE, UNLESS NOTED

OTHERWISE. TYPICAL.

DISCONNECT AND REMOVE EXISTING CARD READERS. REWORK

EXISTING EQUIPMENT, WIRING, CIRCUITS, ETC. TO ACCOMMODATE NEW

CARD READER NEAR THIS LOCATION. SEE ET1-101 FOR NEW WORK.

EXISTING SURFACE MOUNTED FLUORESCENT FIXTURES MOUNTED UNDER

PASSAGE CORRIDOR IN SECOND FLOOR MECHANICAL ROOM SHALL BE

DE-ENERGIZED, DISCONNECTED AND REMOVED TO SOURCE. TYPICAL.

EXISTING PANELBOARD W2D2 SHALL BE DE-ENERGIZED, DISCONNECTED

AND REMOVED. SEE RISER DIAGRAM ON SHEET EP5-101 FOR ADDITIONAL

INFORMATION.

EXISTING PANELBOARD W2D1 SHALL BE DE-ENERGIZED, DISCONNECTED

AND REMOVED. SEE RISER DIAGRAM ON SHEET EP5-101 FOR ADDITIONAL

INFORMATION.

EXISTING PANELBOARD W2E SHALL BE DE-ENERGIZED, DISCONNECTED

AND REMOVED. SEE RISER DIAGRAM ON SHEET EP5-101 FOR ADDITIONAL

INFORMATION.

EXISTING DATA CABLES SERVING EXISTING LAB ARE TO BE DE-

ENERGIZED, DISCONNECTED AND REMOVED BACK TO EXISTING IT

CLOSET.

EXISTING 3/4" EMT CONDUIT WITH 6 #12 AWG CONDUCTOR SHALL BE

RELOCATED TO NEW CHASE. SEE DRAWING EP1-101 FOR ADDITIONAL

INFORMATION.

EXISTING STAIRWELL PAGING SPEAKER TO BE RELOCATED. SEE ET1-101

FOR NEW WIRING SCHEME.

EXISTING CABINET HEATER TO BE DE-ENERGIZED AND DISCONNECTED.

MAINTAIN EXISITNG 120 VOLT 20 AMP CIRCUIT FOR EXTENSION TO NEW

HEATER.

EXISTING STAIRWELL LIGHT FIXTURE TO BE RELOCATED. SEE EL1-101

FOR NEW LOCATION AND WIRING.

MAINTAIN EXISTING NORMAL/EMERGENCY CIRCUIT FOR EXTENSION TO

NEW PA AMPLIFIER IN NEW ELECTRICAL ROOM. SEE EP1-101 FOR NEW

LOCATION.

EXISTING SECURITY TRAC DURESS CEILING SENSOR TO REMAIN AND BE

REINSTALLED IN NEW CEILING. PROTECT FROM PHYSICAL DAMAGE AND

DUST DURING CONSTRUCTION. MAINTAIN EXISTING WIRING.

GENERAL DEMOLITION NOTES:

A. REMOVE ALL ELECTRICAL EQUIPMENT ON OR IN EXISTING WALLS,

CEILINGS AND PARTITIONS WHICH ARE TO BE DEMOLISHED. REMOVE

ALL EXPOSED PORTIONS OF BRANCH CIRCUIT AND CONTROL VOLTAGE

WIRING AND CONDUITS.

B. WHERE EXISTING WALLS ARE TO REMAIN, REMOVE ALL EXPOSED

RACEWAYS, SURFACE AND RECESSED OUTLET BOXES, ETC. WHICH

ARE NOT TO BE REUSED. WHERE NEW CONDUITS AND OUTLETS ARE

TO BE ADDED TO EXISTING WALLS IN FINISHED ROOMS, THEY SHALL

BE CONCEALED BY CUTTING AND PATCHING THE WALLS.

C. UTILIZE EXISTING OUTLET BOXES AND RACEWAY SYSTEMS WHEREVER

PRACTICAL IN RENOVATION AREAS. WHERE SUCH EXISTING OUTLET

BOXES ARE USED, INSTALL NEW WIRING DEVICES, COVERPLATES, AND

WIRING. SPECIAL COVERPLATES MAY BE REQUIRED TO SUIT

CONDITIONS.

D. REARRANGE EXISTING CONDUITS AND WIRING TO ACCOMMODATE NEW

CIRCUIT ARRANGEMENTS INDICATED AND TO MAINTAIN CONTINUITY OF

EXISTING CIRCUITS FEEDING DEVICES THAT ARE TO REMAIN.

E. BE RESPONSIBLE TO REMOVE AND REINSTALL EXISTING ELECTRICAL

EQUIPMENT TO ACCOMMODATE THE WORK OF OR DISTURBED BY ALL

TRADES.

F. STOCKPILE REMOVED LUMINAIRES, POWER AND COMMUNICATION

DEVICES ON JOB SITE FOR REUSE UNTIL TIME OR PROJECT

CLOSEOUT, THEN REMOVE THOSE FROM SITE THAT THE OWNER DOES

NOT WISH TO SALVAGE.

G. EXISTING DEVICE LOCATIONS WERE INDENTIFIED AS COMPLETELY AS

POSSIBLE BY A SITE SURVEY AND BY RECORD DOCUMENTS AS

AVAILABLE. BE RESPONSIBLE FOR PROPER DEMOLITION AND REWORK

OF DEVICES NOT SHOWN ON DRAWINGS TO CONFORM WITH INTENT OF

DOCUMENTS.

H. MAINTAIN CONTINUOUS SERVICE TO ALL LIGHTING, POWER, AND

SIGNALING/ALARM CIRCUITS THAT ARE OUTSIDE OF THE RENOVATION

AREA BUT MAY BE AFFECTED BY THE WORK. CLOSELY COORDINATE

REQUIRED OUTAGES WITH THE VA AND SCHEDULE WORK TO MINIMIZE

DISRUPTION OF SERVICES.

1 AMENDMENT 3 01-31-17

RECESSED/SURFACE/PENDANT

MOUNTED LINEAR FIXTURE

Lighting Symbols

RECESSED/SURFACE

MOUNTED ROUND DOWNLIGHT

WALL/SURFACE MOUNTED FIXTURE

WALL MOUNTED EXIT SIGN - SINGLE

OR DOUBLE FACE AND CHEVRONS AS

SHOWN ON FLOOR PLANS

CEILING MOUNTED EXIT SIGN - SINGLE OR

DOUBLE FACE AND CHEVRONS AS

SHOWN ON FLOOR PLANS

F11

INDICATES

LUMINAIRE TYPE (F11)

INDICATES

CIRCUIT NUMBER(2) -

PANEL INDICATED AT

HOME RUN

LUMINAIRE

SYMBOL

1.

2. THE LIGHTING SYSTEM WIRING SHALL BE SIZED IN

ORDER TO LIMIT THE VOLTAGE DROP TO 3% FROM THE

LAST FIXTURE IN ANY CIRCUIT TO THE PANELBOARD.

3. ALL LIGHTING FIXTURE FINISHES SHALL BE COORDINATED

WITH ARCHITECT PRIOR TO INSTALLATION.

4. LIGHTING SHALL BE MOUNTED UTILIZING METHODS OF

ATTACHMENT IN ACCORDANCE WITH NEC, LATEST

APPLICABLE ARTICLE AND UL REQUIREMENTS.

CONTRACTOR IS RESPONSIBLE TO COORDINATE FIXTURE

INSTALLATION HARDWARE WITH CEILING TYPE.

6.

7.

8.

9.

10.

General Notes

THE ELECTRICAL POWER DISTRIBUTION SYSTEM

WILL PROVIDE A VOLTAGE DROP NOT TO EXCEED

5% BETWEEN THE TRANSFORMER SECONDARY AND

THE EQUIPMENT TO BE SERVED.

ALL EMPTY CONDUITS (ELECTRICAL, TELEPHONE,

DATA, TV, ETC.) SHALL HAVE A CONDUIT MEASURING

TAPE INSTALLED WITHIN THEM. THE TAPE SHALL BE

SUITABLE FOR USE AS A PULLING LINE. TAPE SHALL

BE RATED 130 LB. TENSILE STRENGTH (GREENLEE 435

OR EQUAL) SIZES 2 INCHES OR LARGER SHALL BE

SUPPLEMENTED WITH 200 LB. NYLON LINE, TIED AT

BOTH ENDS TO TAPE.

ALL PULL LINES SHALL BE IDENTIFIED LISTING ORIGIN,

INTERMEDIATE PULL POINTS AND TERMINATION,

SPECIFIC LOCATIONS OF ORIGIN, INTERMEDIATE PULL

POINTS AND TERMINATION. SPECIFIC LOCATIONS OF

ORIGIN, INTERMEDIATE PULL POINTS AND

TERMINATION SHALL BE INDICATED.

WHERE CONDUIT, CABLES, DUCTWORK, OR PIPING

PASSES THROUGH FIRE RATED FLOORS OR WALLS,

THE SLEEVES SHALL BE COMPLETELY SEALED WITH A

FIRESTOP MATERIAL THAT IS UL LISTED, AND

ACCEPTED BY THE BUILDING DEPARTMENT AND FIRE

DEPARTMENT AS BEING SUITABLE FOR THIS SERVICE

SUCH AS DOW CORNING CORP., SILICONE

ELASTOMER, DOW CORNING 3-6548 SILICONE TRV

FOAM, OR APPROVED EQUAL. THIS MATERIAL SHALL

BE INSTALLED IN ACCORDANCE WITH THE

REQUIREMENTS OF THE MANUFACTURER TO MAINTAIN

THE FIRE RATING OF THE PENETRATED WALL OR

FLOOR.

ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ONLY.

REFER TO ARCHITECTURAL DRAWINGS FOR EXACT

LOCATIONS OF DEVICES AND LIGHTING FIXTURE

LOCATIONS.

ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE

LATEST EDITION OF THE NATIONAL ELECTRICAL CODE

(NFPA 70) AND LOCAL APPLICABLE CODES.

PROVIDE PROPER ACCESS PANELS AS REQUIRED IN

WALLS AND GWB CEILINGS FOR ANY EQUIPMENT,

DEVICES, SWITCHES, CONTRACTORS, PULL AND

JUNCTION BOXES ETC. REQUIRING PANELS TO BE

PROVIDED BY TRADE CONTRACTOR FOR INSTALLATION

G.C.

Electrical Symbols

DUPLEX RECEPTACLE

QUAD RECEPTACLE

WEATHER-PROOF GROUND

FAULT ISOLATED DUPLEX

RECEPTACLE

GROUND FAULT ISOLATED DUPLEX RECEPTACLE

DUPLEX RECEPTACLE MOUNTED 6" ABOVE COUNTER

DUPLEX RECEPTACLE MOUNTED 48" AFF

WP/GFI

GFI

+48

SPECIAL RECEPTACLE NEMA TYPE AS SHOWN

MOTOR CONNECTION - THREE PHASE

MOTOR CONNECTION - SINGLE PHASE

BRANCH CIRCUIT -

(2)#12 AWG AND #12AWG G. IN 3/4" C. (EMT) U.N.O.

A-1 HOMERUN TO PANEL BOARD

BRANCH CIRCUIT NUMBER

PANEL DESIGNATION

GROUNDING ROD

PANELBOARD/RELAY LIGHTING CONTROL PANEL

INDICATES:

PANEL (B1)-

CIRCUIT NUMBER (3)B1-3

DEVICE SYMBOL

Electrical Abbreviations

Mounting Heights Schedule

6'-8" AFF (BOTTOM OF DEVICE) OR 6"

BELOW FINISHED CEILING, (TOP OF

DEVICE) WHICH EVER IS LOWER

REFERENCE LUMINAIRE

SCHEDULE FOR MOUNTING

REQUIREMENTS

6'-6"

6'-0"

5'-0"

3'-10"

(CENTER OF DEVICE)

3'-6'

(TOP OF DEVICES)

2'-0"

1'-6"

FIRE ALARM HORNS /

STROBES

PENDANT MOUNTED

LUMINARIES

TOP OF PANELBOARDS,

CABINETS

TOP OF DISCONNECT

SWITCHES, STARTERS,

AND CONTACTORS

LIGHTS SWITCHES, FIRE ALARM

PULL STATIONS, MANUAL

MOTOR STARTERS, FIREMAN'S

TELEPHONES, NURSE CALL

PULL CHORD, PUSH BUTTON,

DUTY STATIONS AND PANIC

BUTTONS

WALL MOUNTED

HANDICAPPED

TELEPHONE OUTLETS

ELECTRICAL

RECEPTACLES IN

MECHANICAL /

ELECTRICAL ROOMS &

ELEVATOR MACHINE

ROOMS

ELECTRICAL RECEPTACLES

(U.N.O.) COMMUNICATIONS /

DATA OUTLETS (U.N.O.)

0'-0" FINISHED

FLOOR

NOTE;

1. CTR - MOUNTED 6" ABOVE COUNTER OR BACKSPLASH.

12. THE ELECTRICAL CONTRACTOR SHALL VERIFY ALL

LOCATIONS OF ELECTRICAL DEVICES PRIOR TO

INSTALLATION. THE ELECTRICAL CONTRACTOR IS

RESPONSIBLE FOR ALL MEANS AND METHODS OF

INSTALLATION OF THE FOLLOWING ELECTRICAL

DEVICES BUT IS NOT LIMITED TO ALL POKE

THROUGH'S, RECEPTACLES, COMMUNICATION ROUGH-

INS, JUNCTION BOXES, ETC. ALL ROUTING AND

INSTALLATION OF RACEWAY FEEDING ELECTRICAL

DEVICES SHALL BE INSTALLED NEAT AND FLUSH TO

SURFACE (WHERE NOT IN DRYWALL) AND SHALL BE

CONCEALED FROM VIEW IN DRYWALL WHERE APPLIED.

PULL BOXPB

JUNCTION BOXJ

DUPLEX RECEPTACLE ON NORMAL / EMERGENCY CIRCUIT

QUAD RECEPTACLE ON NORMAL / EMERGENCY CIRCUIT

SINGLE RECEPTACLE

NORMAL EMERGENCY

SITE LIGHTING BOLLARD

LUMINAIRE TYPES

Electrical Abbreviations

PRI PRIMARY

PRN PRESENT LIGHTING FIXTURE,

SWITCH, DEVICE, ETC., TO BE

REMOVED AND REPLACED WITH

NEW

PRR PRESENT LIGHTING FIXTURE,

SWITCH, DEVICE,, ETC., SHOWN AT

NEW LOCATION

PRX PRESENT LIGHTING FIXTURE,

SWITCH, DEVICE, ETC., TO BE

REMOVED AND OUTLET BOX

EXTENSION INSTALLED FOR

SURFACE CONDUIT OR SMR AND

WIRE EXTENSION TO NEW OUTLET

SHOWN. REINSTALL PRESENT

LIGHTING FIXTURE, SWITCH,

DEVICE, ETC.

PWR POWER

REC/RECPT RECEPTACLE

REQ'D REQUIRED

RGS RIGID GALVANIZED STEEL

RMC RIGID GALVANIZED METAL

CONDUIT

RPC REMOVE PRESENT FIXTURE,

SWITCH, DEVICE, ETC., AND CAP

OUTLET

RPP REMOVE PRESENT FIXTURE,

SWITCH, DEVICE, ETC., PATCH THE

PLASTER IF IN PLASTER: CAP IF IN

METAL OR WOOD

RPX REMOVED PRESENT FIXTURE,

WITCH, DEVICE, ETC., WIRE AND

ALL RELATED EXPOSED RACEWAY

INSOFAR AS IS POSSIBLE. ALL

DAMAGED SURFACES TO BE

REPAIRED

SEC SECONDARY

SM SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

TEL / TELE TELEPHONE

TL TWIST LOCK

TP TAMPER PROOF

TV TELEVISION

TYP TYPICAL

UC UNDER COUNTER

UCR UNDER COUNTER REFRIGERATOR

RECEPTACLE

UH UNIT HEATER

UL UNDERWRITERS' LABORATORIES,

INC.

UNO UNLESS NOTED OTHERWISE

V VOLTAGE

VT VAPOR TIGHT

W WATT OR WIRE

W/ WITH

W/GRD WITH GROUND WIRE

W/O WITHOUT

WP WEATHER PROOF ENCLOSURE

WT WATER TIGHT

XA EXISTING TO BE REMOVED

COMPLETELY

XR EXISTING TO BE REMOVED AND

RELOCATED

XRN EXISTING TO BE REMOVED AND

REPLACED WITH NEW DEVICE

XRR RELOCATED EXISTING EQUIPMENT

Y STAR OR WYE DISTRIBUTION

SYSTEM

NE NORMAL / EMERGENCY POWER

5.

A/AMP AMPERE

AFCI ARC FAULT INTERRUPTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AL ALUMINUM

AWG AMERICAN WIRE GAUGE

BKR BREAKER

C CONDUIT

CB CIRCUIT BREAKER

CC COMMUNICATION / NETWORK

CONTRACTOR

CCT/CKT CIRCUIT

CLG CEILING

CO CONVENIENCE OUTLET

CONN CONNECTION

CTR COUNTER

CU COPPER

DISC DISCONNECT

DN DOWN

DS DISCONNECT SWITCH

DWG DRAWING

E/EM EMERGENCY OR EMERGENCY

SYSTEM

EA EACH

EC ELECTRICAL CONTRACTOR

EF EXHAUST FAN

EH ELECTRIC HEAT

ELEC ELECTRICAL

EMT ELECTRIC METALLIC TUBING

EQ/EQUIP EQUIPMENT

EUH ELECTRIC UNIT HEATER

EWC ELECTRIC WATER COOLER

EX EXISTING

F FIXTURE

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FBO FURNISHED BY OTHERS WITH ALL

RELATED ELECTRICAL WORK BY

ELECTRICAL CONTRACTOR

FC FOOTCANDLES

FDR FEEDER

FH FUME HOOD

FL FLOOR

FLA FULL LOAD AMPERE

FLUOR FLUORESCENT

GRN/GND GROUND

GC GENERAL CONTRACTOR

GFI GROUND FAULT INTERRUPTER

HC HEATING, VENTILATION, AIR

CONDITIONING CONTRACTOR

HID HIGH INTENSITY DISCHARGE

HP HORSEPOWER

HPF HIGH POWER FACTOR

HTR HEATER

HVAC HEATING, VENTILATION, AIR

CONDITIONING

HZ HERTZ

IN INCH

JB/JBOX JUNCTION BOX

K THOUSAND

KVA KILO-VOLT AMPERES

KW KILOWATT

LED LIGHT EMITTING DIODE

LCP LIGHTING CONTROL PANEL

LTG LIGHTING

LRP LIGHTING REPLAY PANEL

LV LOW VOLTAGE

MC MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

MDP MAIN DISTRIBUTION PANEL

MFR MANUFACTURER

MH MANHOLE

MLO MAIN LUGS ONLY

MSW MAIN SWITCH AND FUSE

MTD MOUNTED

MTG MOUNTING

MTG HT MOUNTING HEIGHT

N/A NON APPLICABLE

NEC NATIONAL ELECTRIC CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN THIS CONTRACT

NL NIGHT LIGHT

NO / # NUMBER

NTS NOT TO SCALE

OC ON CENTER

OEM ORIGINAL EQUIPMENT

MANUFACTURER

OSHA OCCUPATIONAL SAFETY AND HEALTH

ADMINISTRATION

P POLE

PB PUSH BUTTON

PBOX PULL BOX

PC PLUMBING CONTRACTOR

PH / Ø PHASE

PNL PANELBOARD

POS POSITION

PR PRESENT LIGHTING FIXTURE, SWITCH,

DEVICE, ETC., TO REMAIN

PENDANT/SURFACE MOUNTED LINEAR

INDUSTRIAL FIXTURE

Fire Alarm Symbols

Communications Symbols

S

Security Symbols

Access Symbols

RECESSED CEILING PAGING SPEAKER WITH GRILLE

EMERGENCY WALL PHONE ROUGH-IN ONLY. PROVIDE A 4"/16"

SQUARE OUTLET BOX WITH A SINGLE GANG DEVICE RING AND A

1" EMT CONDUIT TO NEAREST ACCESSIBLE CEILING (UNLESS

INDICATED OTHERWISE).

ADDRESSABLE FIRE ALARM CONTROL PANEL

COMBO SYNCHRONIZED SPEAKER/STROBE UNIT

ADDRESSABLE CONTROL MODULE

FACP

CM

HD

SD

HEAT DETECTOR

SMOKE DETECTOR

MANUAL PULL STATIONF

DC

CR

DOOR CHIME

CARD READER ROUGH-IN ONLY. PROVIDE A 4- 11/16"

SQUARE OUTLET BOX WITH A SINGLE GANG DEVICE

RING AND A 1" EMT CONDUIT TO NEAREST

ACCESSIBLE CEILING (UNLESS INDICATED

OTHERWISE).

F B

W

SECURITY TRAC DURESS CEILING SENSORD

R-59

CONTROL RELAY NUMBER

WIRE BASKET CABLE TRAY

SINGLE POLE SWITCH, 3'-8" AFF

WALL MOUNTED LINE VOLTAGE

OCCUPANCY SENSOR, 3'-8" AFFOS

LIGHTING FIXTURE SCHEDULE

FIXTURE

TYPE

LAMPING

MOUNTING MANUFACTURERLUMENS WATTSVOLTAGE

BALLAST/

DRIVER

DESCRIPTION

NUMBER LAMP

F01 RECESSED

CEILING

CORELITE # R2XWO2L351CUNV22X2583 277 2'x2' RECESSED LED FIXTURE WITH SMOOTH OPAL ACRYLIC LENS1 LED

F02 1664 2771 LED

F03 SURFACE WALL4462 2771 LED - -

- DIMMABLE

- DIMMABLE

PORTFOLIO # LD4A13DO1OTE -

ERW4A13835 - 4LW1L1

MCGRAW EDISION

#IST-F02-LED-E1-BL3-BZ-P

4" DIAMETER LED DOWNLIGHT FIXTURE WITH SIMI-SPECULAR ALZAK REFLECTOR.

WALL MOUNTED LED LIGHT FIXTURE WITH PHOTO CELL,

WET LOCATION LISTED

RECESSED

CEILING

FO4

EX-2

LED

LED -

EX-1 UNIVERSAL TOP,

END BACK

- 2771 LED - - MULE # ARS-A-1-R-AA SINGLE FACE LED EXIT SIGN FIXTURE WITH EXTRUDED ALUMINUM HOUSING

AND UNIVERSAL MOUNTING.

2786 SURFACE 28 - METALUX #

2-WNLED-LD4-28SL-UNX-L835-X-1

2' LED SURFACE MOUNTED FIXTURE WITH WRAP LENS

UNIVERSAL TOP,

END, BACK

277 - - MULE # ARS-A-2-R-AA DOUBLE FACE LED EXIT SIGN FIXTURE WITH EXTRUDED ALUMINUM HOUSING

AND UNIVERSAL MOUNTING

FULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

Office of

Facilities

Management o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t 4 o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

BIDDING DOCUMENTS - FEBRUARY 22, 2019

VA CARES CONSOLIDATION

VAMC, PITTSBURGH, PA

CONNECTING BRIDGE

EG0-001

646CA2500.23

AuthorChecker

SYMBOLS & LIGHTING

FIXTURE SCHEDULE

VAPHS UNIVERSITY DRIVE

1 & 30

6.5

FE

D x.G x.J x.L x.5 x.6

E.7

EA

x.12

FO1

NE

FO1

NE

FO1 19

NE

FO1

NE

FO1

NE

FO1

NE

FO1

NE

FO1

NE

FO1

NE

FO1

NE

FO1

NE

FO1

NE

FO1

FO1

FO1

FO1

FO1

FO1

FO1

FO1

FO1

FO1

FO1

FO1 FO1 FO1 FO1 FO1 FO1

FO1 FO1

R-59

R-59

R-59

R-59

R-59

R-59

R-59

R-59

R-59

R-59

R-59

R-10

R-10

R-10

R-10

R-10

NE

R-10

FO2

R-59

FO2

NE

FO2

41R-59

FO2

R-59

FO2

NE

FO2

9 R-1011

NE

EX-1

EX-1

NE

EX-1 NE

EX-1

NE 19

EX-1 NE

EX-1

NE

EX-1

NE

EX-1

NE

EX-1

NE

EL2A-11

LS2HA-19

2HA-41

1 3

LP2-9

D

E

E.6

E.7 F

6.5

6.1

12.8 x.8x.7x.6x.5x.4 x.19x.18x.17x.16x.14 x.2 x.1 x.C

EA

x.L x.N x.P x.3

FO3

FO3

EX-2

NE

os

9FO4

FO1

R-10

FULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

Office of

Facilities

Management o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t 4 o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

BIDDING DOCUMENTS - FEBRUARY 22, 2019

VA CARES CONSOLIDATION

VAMC, PITTSBURGH, PA

CONNECTING BRIDGE

EL1-101

646CA2500.23

AuthorChecker

BRIDGE LIGHTING PLAN

VAPHS UNIVERSITY DRIVE

1 & 30

Key Notes

1/8" = 1'-0"

BRIDGE LIGHTING PLAN

RELOCATE EXISTING STAIRWELL LIGHT FIXTURE. PROVIDE JUNCTION

BOXES AND ALL WIRING/ RACEWAY MODIFICATION AS REQUIRED.

COORDINATE EXACT LOCATION WITH RELOCATED CABINET HEATER

TO ENSURE PROPER CLEARANCES PER MANUFACTURER'S

RECOMMENDATIONS.

EXISTING LIGHT FIXTURES AND CONTROLS IN UNOCCUPIED SPACE

TO REMAIN AND BE MODIFIED TO ACCOMMODATE NEW CORRIDOR

WALL AND RELOCATION OF DUCT SHAFT. SHIFT EXISTING FIXTURES

THAT ARE IN CONFLICT WITH NEW PARTITIONS TO ADJACENT

CEILING TILES WITHIN THE UNOCCUPIED SPCE AND EXTEND

EXISTING CIRCUITS/CONTROLS TO NEW FIXTURE LOCATION.

PROVIDE NEW SWITCHING ADJACENT TO DOOR FOR CONTROL OF

EXISTING UNOCCUPIED SPACE LIGHTING. INTERCEPT & EXTEND

EXISTING BRANCH CIRCUIT WIRE TO CONTROL UNOCCUPIED AREA

EXISTING LIGHTING.

TO EXISTING BUILDING #1 LIFE SAFETY PANELBOARD EL2A CIRCUIT #

11 LOCATED APPROXIMATELY 100' AWAY. PROVIDE A 20 AMP SINGLE

POLE CIRCUIT BREAKER IN EXISTING SPACE.

WIRE TO EXISTING SPARE 20A-1P CIRCUIT BREAKER IN PANELBOARD

LP2 CIRCUIT #9 LOCATED IN BUILDING #1 ELECTRICAL ROOM 2W130.

CIRCUIT IS TO BE CONTROLLED VIA EXISTING SPARE RELAY #10 IN

LIGHTING CONTROL PANEL '2BT' WHICH IS ALSO LOCATED IN THE

SAME ELECTRICAL ROOM. PROVIDE ALL SOFTWARE MODIFICATIONS

AS REQUIRED TO EXSTING LIGHTING CONTROL PANEL FOR CONTROL

OF CORRIDOR LIGHTING FIXTURES. ROOM W2130 IS

APPROXIMATELY 220' AWAY.

WIRE TO EXISTING SPARE 20A-1P CIRCUIT BREAKER IN PANELBOARD

LS2HA CIRCUIT #19 LOCATED ON THE SECOND FLOOR OF BUILDING #

30 ELECTRICAL ROOM 2A109 APPROXIMATELY 180' AWAY.

WIRE TO EXISTING SPARE 20A-1P CIRCUIT BREAKER IN PANELBOARD

2HA CIRCUIT #41 LOCATED IN BUILDING #30 ELECTRICAL ROOM

2A123. CIRCUIT IS TO BE CONTROLLED VIA EXISTING SPARE RELAY #

59 IN THE LIGHTING CONTROL PANEL WHICH IS ALSO LOCATED IN THE

SAME ELECTRICAL ROOM. PROVIDE ALL SOFTWARE MODIFICATIONS

AS REQUIRED TO EXISTING LIGHTING CONTROL PANEL FOR

CONTROL OF CORRIDOR LIGHTING FIXTURES. ROOM 2A123 IS

APPROXIMATELY 100' AWAY.

EXTERIOR LIGHT FIXTURE TO BE SERVED VIA PANEL LP2 CIRCUIT 9

WITHOUT LIGHTING RELAY CONTROL. FIXTURE IS OPERATED FROM

DUSK TO DAWN VIA INTERNAL FIXTURE PHOTO CELL.

J

J

J

J

J

J

CABINET

HEATER

EXISTING BUILDING 1

2ND FLOOR

AREA W

EXISTING BUILDING 30

2ND FLOOR

W2D2-21

W2D2-23

D

E E.7

F

6.5

6.1

12.8 x.11x.10 x.8x.7x.6x.5x.4 x.19x.18x.17x.16x.14x.2 x.C

EA

x.D x.E x.F x.G x.J x.L x.N

FULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

Office of

Facilities

Management o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t 4 o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

BIDDING DOCUMENTS - FEBRUARY 22, 2019

VA CARES CONSOLIDATION

VAMC, PITTSBURGH, PA

CONNECTING BRIDGE

EP1-101

646CA2500.23

AuthorChecker

BRIDGE POWER PLAN

VAPHS UNIVERSITY DRIVE

1 & 30

PROVIDE CONNECTION TO POWER OPERATED DOOR WITH CARD READER.

CARD READER SHALL ACTUATE THE DOOR FOR ENTRY FROM THE

UNSECURED SIDE.

NEW PANELBOARD W2D2 - 208/120V 3Ø,4W.

NEW PANELBOARD W2D1 - 208/120V 3Ø 4W.

NEW PANELBOARD W2E - 208/120V 3Ø 4W.

RELOCATED 3/4" EMT CONDUIT WITH 6 #12 AWG CONDUCTORS PROVIDE

JUNCTION BOXES AND ALL WIRING/RACEWAY MODIFICATIONS AS

REQUIRED. COORDINATE RELOCATOIN AND CIRCUIT OUTRAGE WITH

OWNER.

TO EXISTING PANELBOARD LS2LA, CIRCUIT #38 LOCATED APPROX. 300'

AWAY ON THE SECOND FLOOR OF BUILDING 30. PROVIDE #10 AWG WIRE

TO COMPENSATE FOR VOLTAGE DROP.

TO EXISTING PANELBOARD 2LC, CIRCUIT #42 LOCATED APPROX. 100'

AWAY ON THE SECOND FLOOR OF BUILDING 30.

FLOOR IN THIS AREA IS RAISED 14" AND IS TO RAMP DOWN FROM WEST TO

EAST. ALL NEW AND EXISTING ELECTRICAL SERVICES SHALL BE

COORDINATED WITH ALL OTHER TRADES TO MAINTAIN REQUIRED CEILING

HEIGHT.

HANDS FREE DOOR ACTUATOR EMPTY RACEWAY SYSTEM.

EXISTING CABINET HEATER TO BE REPLACED WITH NEW. INTERCEPT

EXISTING 120V 20AMP CIRCUIT CURRENTLY SERVING UNIT AND EXTEND TO

NEW UNIT AS REQUIRED.

PA AMPLIFIER. PROVIDE WALL-MOUNTED SHELF AT 6'-6" AFF AND OF

AMPLE DEPTH FOR NEW AMPLIFIER AND ASSOCIATED WIRING THAT

CONNECTS TO THE BACK OF THE UNIT. PROVIDE RECEPTACLE ADJACENT

TO SHELF AT 6'-6" AFF.

EXTEND EXISTING 120 VOLT, 20 AMP EMERGENCY LIFE SAFETY CIRCUIT

THAT PREVIOUSLY FED CORRIDOR RECEPTACLE (SEE ESD-801) TO NEW

RECEPTACLE FOR PA AMPLIFER AND POWERED DOOR CONNECTION.

PROVIDE GROUND CONNECTION TO NEAREST TELECOMMUNICATIONS

GROUNDING BUS, WIRE SIZE SHALL BE #10G.

PROVIDE GROUND BOND TO NEW STEEL STRUCTURE AT EACH END OF THE

BRIDGE. EXTEND 250KCMIL COPPER CONDUCTOR AND BOND TO EXISTING

BUILDING STRUCTURAL STEEL.

PROVIDE CONNECTION TO NEW POWERED DOOR OPERATOR TO BE

INSTALLED ON EXISTING DOOR. UTILIZE NEXT AVAILABLE SPARE CIRCUIT

FROM THE NEAREST LIFE SAFETY PANELBOARD. UPDATE PANELBOARD

SCHEDULE AS REQUIRED. REFER TO ARCHITECTURAL DRAWINGS FOR

PUSH PLATE ROUGH-IN LOCATIONS. PROVIDE/INSTALL ALL

INTERCONNECTING WIRING AS REQUIRED PER MANUFACTURER'S

INSTALLATION INSTRUCTIONS.

Key Notes

1/8" = 1'-0"

BRIDGE POWER PLAN

4#4/0+1#2G - 2 1/2"C

PB

PANELBOARD W2D1

208/120V, 3Ø, 4W

PANELBOARD W2D2

208/120V, 3Ø, 4W

PANELBOARD W2E

208/120V, 3Ø, 4W

PB

EXISTING

PANELBOARD W2F

208/120V, 3Ø, 4W

(TO REMAIN)

EXISTING

PANELBOARD W2E

208/120V, 3Ø, 4W

(42 POLE)

EXISTING

PANELBOARD W2D1

208/120V, 3Ø, 4W

(42 POLE)

EXISTING

PANELBOARD W2D2

208/120V, 3Ø, 4W

(36 POLE)

EXISTING DIST

BOARD DPW2

208/120V, 3Ø, 4W, 600A

(TO REMAIN)

4#3 +1#8G -1 1/4"C EXISTING 4 #3 +1#8G -1 1/4"C

EXISTING 4#4/0 +1#2G -2 1/2"C

EXISTING PANEL FEEDERS TO BE DE-

ENERGIZED AND REMOVED

FEEDER PULLBOX WITH SPLICE

CONNECTION AS APPLICABLE. SIZE BOX

AS PER NEC REQUIREMENTS (TYPICAL).

111222

EXISTING MAIN HEAD END

EQUIPMENT RACK LOCATED

IN THE BASEMENT MDF ROOM

4 CONDUCTOR 18 AWG - 3/4"C. EC TO

VERIFY CABLE REQUIREMENTS WITH

MANUFACTURER PRIOR TO ROUGH-IN.

BASEMENT

120V,20A

NE PWR

CKT # PER PLANS

S S ~

PA - 100W AMPLIFIER/ CABINET

BOGEN #C100 W/ UPS

4 CONDUCTOR 18 AWG - 3/4"C (TYP). EC

TO VERIFY CABLE REQUIREMENTS WITH

MANUFACTURER PRIOR TO ROUGH-IN.

TYPICAL CORRIDOR PA SPEAKER

GROUND FLOOR

FIRST FLOOR

SECOND FLOOR

FACP

FS FS

FSDHDTO NEXT

DEVICE

TO NEXT

DEVICE

CM SD SD

AS REQ'D

BY NFPA 72

FIRE ALARM RISER KEYNOTES (THIS DETAIL)

EXISTING ADDRESSABLE FIRE ALARM CONTROL PANEL. PROVIDE

ADDITIONAL ADDRESSABLE DEVICE CARDS AS REQUIRED. SYSTEM

MAY REQUIRE ADDITIONAL PROVISIONS TO BE MADE TO ADD CARDS.

OTHER EXISTING

DEVICES

OUTPUT

INPUT

NOTIFY NECESSARY STAFF

FOR RESPONSE FOR HEALTH

CARE AND HIGH RISE BUILDING

ONLY (ALARM SIGNAL MAY BE

DIFFERENT ON DIFFERENT

FLOORS)

NOTIFY FIRE

DEPARTMENT

INITIATE SUPERVISORY

SIGNAL TO A 24-HOUR

MANNED POINT FOR

IMMEDIATE RESPONSE

CLOSE ASSOCIATE

SMOKE BARRIER

DOORS ON THE

FLOOR

CLOSE DAMPERS

ON FAN PROXIMATE

TO DETECTOR.

SHUT DOWN AIR

HANDLER SERVED

BY THE DETECTOR

RECALL

ELEVATOR

OPEN LOCKED

EGRESS DOORS

ON FLOOR TO

FIRE ORIGIN

DUCT SMOKE DETECTOR

AREA SMOKE DETECTOR

DOOR RELEASE SMOKE DETECTOR

MANUAL PULL STATION

SPRINKLER WATERFLOW / PRESSURE

SWITCH

WATER CONTROL VALVE TAMPER

HIGH/LOW PRESSURE DRY - PIPE SPRINKLER

SYSTEM

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

FULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

Office of

Facilities

Management o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t 4 o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

BIDDING DOCUMENTS - FEBRUARY 22, 2019

VA CARES CONSOLIDATION

VAMC, PITTSBURGH, PA

CONNECTING BRIDGE

EP5-101

646CA2500.23

AuthorChecker

ELECTRICAL SINGLE-LINE

DIAGRAMS

VAPHS UNIVERSITY DRIVE

1 & 30

N.T.S.

ELECTRICAL SINGLE-LINE DIAGRAM

PA SYSTEM RISER DIAGRAM - BUILDING 1

N.T.S.

TYPICAL FIRE ALARM CONNECTION

DIAGRAM

NTS3

FIRE ALARM SYSTEM MATRIX

KEYED NOTES :

1.

PROVIDE NEW PANELBOARDS TO REPLACE EXISTING PANELBOARDS WHICH ARE TO BE REMOVED. INSTALL NEW PANELBOARDS AND TAP EXISTING FEEDERS AS SHOWN. CLOSELY COORDINATE REQUIRED SHUT-DOWNS WITH THE VA TO MINIMIZE DOWNTIME OF EXISTING CIRCUITS. REFER TO PANELBOARD SCHEDULES FOR

ADDITIONAL INFORMATION.

2.

DISCONNECT EXISTING BRANCH CIRCUITS WHICH ARE TO REMAIN FROM THIS PANELBOARD AND REROUTE TO THE NEW PANELBOARD WITH THE SAME DESIGNATION (E.G. - CIRCUITS CURRENTLY FED FROM EXISTING PANELBOARD 'W2D2' WILL BE REFED FROM NEW PANELBOARD 'W2D2'). CLOSELY COORDINATE THIS WORK WITH THE VA TO MINIMIZE DISRUPTION TO EXISTING CIRCUITS AND CUT BRANCH CIRCUITS OVER ONE AT A TIME; NOTE THAT THESE CIRCUITS MAY EXTEND BEYOND THE RENOVATION AREA. AVOID CHANGING THE CIRCUIT NUMBER OF THE EXISTING CIRCUITS. SPLICE AND EXTEND EXISTING BRANCH CIRCUIT WIRING WITH SIMILAR

CONDUCTORS TO THE EXISTING CIRCUITS AS REQUIRED.

3.

AFTER ALL EXISTING BRANCH CIRCUITS WHICH ARE TO REMAIN HAVE BEEN RELOCATED TO THE NEW PANEL, DISCONNECT AND REMOVE EXISTING PANELBOARD.

DEMOLISH EXISTING FEEDER BACK TO THE POINT WHERE THE NEW FEEDER WAS TAPPED. REWORK TAPS AND PROVIDE PERMANENT SPLICES TO THE NEW FEEDERS.

CKT CIRCUIT DESCRIPTION TRIP POLESPOLES A

NOTES: FEED THROUGH LUGS. CIRCUITS NOTED AS "EXISTING LOADS" ARE TO BE RELOCATED FROM EXISTING PANEL "W2D1". MAINTAIN PREVIOUS CIRCUIT NUMBERS.

1 20 A 1

B C

TRIP

20 A

CIRCUIT DESCRIPTION CKT

3 20 A 1 1 20 A

5 20 A 1 1 20 A

7 20 A 1 1 20 A

9 20 A 1 1 20 A

11 20 A 1 1 20 A

13 20 A 1 1 20 A

15 20 A 1 1 20 A

17 20 A 1 1 20 A

19 20 A 1 1 20 A

21 20 A 1 1 20 A

23 20 A 1 1 20 A

25 20 A 1 2 30 A

27 20 A 1

29 15 A 2 2 40 A

31 --- ---

33 20 A 2 2 50 A

35 --- ---

37 30 A 3 3 30 A

39 --- --- --- ---

41 --- --- --- ---

16.5 17.2 17.7TOTAL LOAD:

51.4 KVA

TOTAL LOAD:

Branch Panel: W2D1 (NEW)

LOCATION: 2ND FL BLDG 1

SUPPLY FROM: DPW2

MOUNTING: SURFACE

ENCLOSURE: NEMA 1

VOLTS: 208Y/120V

PHASES: 3

WIRES: 4

A.I.C. Rating: 22,000

Mains Type: MCB

Mains Rating: 225A

MCB Rating: 225A-3P

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

.8 .8

.8 .8

.8 .8

.8 .8

.8 .8

.8 .8

.8 .8

.8 .8

.8 .8

.8 .8

.8 .8

.8 .8

.8 1.5

.8 1.5

.8 2.0

.8 2.0

1.0 2.5

1.0 2.5

2.5 2.5

2.5 2.5

2.5 2.5

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

CKT CIRCUIT DESCRIPTION TRIP POLESPOLES A

NOTES: CIRCUITS NOTED AS "EXISTING LOADS" ARE TO BE RELOCATED FROM EXISTING PANEL "W2D2". MAINTAIN PREVIOUS CIRCUIT NUMBERS.

1 20 A 1

B C

TRIP

20 A

CIRCUIT DESCRIPTION CKT

3 20 A 1 1 20 A

5 20 A 1 1 20 A

7 20 A 1 1 20 A

9 20 A 1 1 20 A

11 20 A 1 1 20 A

13 20 A 1 1 20 A

15 20 A 1 1 20 A

17 20 A 1 1 20 A

19 20 A 1 1 20 A

21 20 A 1 1 20 A

23 20 A 1 1 20 A

25 20 A 1 1 20 A

27 20 A 1 1 20 A

29 20 A 1 1 20 A

31 20 A 1 1 20 A

33 20 A 1 1 20 A

35 20 A 1 1 20 A

37 20 A 1 1 20 A

39 20 A 1 1 20 A

41 20 A 1 1 20 A

8.1 6.6 6.8TOTAL LOAD:

21 KVA

TOTAL LOAD:

Branch Panel: W2D2 (NEW)

LOCATION: 2ND FL BLDG 1

SUPPLY FROM: W2D1

MOUNTING: SURFACE

ENCLOSURE: NEMA 1

VOLTS: 208Y/120V

PHASES: 3

WIRES: 4

A.I.C. Rating: 22,000

Mains Type:

Mains Rating: 225A

MCB Rating: -----

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

REC - CORRIDOR

SPARE

SPARE

REC - LAB

REC - LAB

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

REC - LAB

REC - LAB

1.2 .5

.8 .8

.8 .8

.8 .8

.8 .8

.8 .8

.8 .8

.8 .8

.8 .8

.8 .8

.8 .8

.6 1.2

.8 1.2

SPARE

MLO

Branch Panel: W2E (NEW)

CKT CIRCUIT DESCRIPTION TRIP POLES

LOCATION: 2ND FL BLDG 1

SUPPLY FROM: DPW2

MOUNTING: SURFACE

ENCLOSURE: NEMA 1

VOLTS: 208Y/120V

PHASES: 3

WIRES: 4

A.I.C. Rating: 22,000

Mains Type: MCB

Mains Rating: 225A

MCB Rating: 225A-3P

POLES A

NOTES: CIRCUITS NOTED AS "EXISTING LOADS" ARE TO BE RELOCATED FROM EXISTING PANEL "W2E". MAINTAIN PREVIOUS CIRCUIT NUMBERS.

1 EXISTING LOADS 20 A 1 0.8 0.8

B C

TRIP

20 A

CIRCUIT DESCRIPTION

EXISTING LOADS

CKT

3 20 A 1 1 20 A

5 20 A 1 1 20 A

7 20 A 1 1 20 A

9 20 A 1 1 20 A

11 20 A 1 1 20 A

13 20 A 1 1 20 A

15 20 A 1 1 20 A

17 20 A 1 1 20 A

19 20 A 1 1 20 A

21 20 A 1 1 20 A

23 20 A 1 1 20 A

25 20 A 1 1 20 A

27 20 A 1 1 20 A

29 20 A 1 1 20 A

31 20 A 1 1 20 A

33 20 A 1 1 20 A

35 20 A 1 1 20 A

37 20 A 1 3 70 A EXISTING PANELBOARD W2F

39 20 A 2 - - ----

41 - - - - ----

--- 7.2

1.0 7.2

1.0 7.2

13.6 14.6 13TOTAL LOAD:

41.2 KVA

TOTAL LOAD:

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

EXISTING LOADS

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

0.8 0.8

0.8 0.8

0.8 0.8

0.8 0.8

0.8 0.8

0.8 0.8

0.8 0.8

0.8 0.8

0.8 0.8

0.8 0.8

FULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

Office of

Facilities

Management o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t 4 o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

BIDDING DOCUMENTS - FEBRUARY 22, 2019

VA CARES CONSOLIDATION

VAMC, PITTSBURGH, PA

CONNECTING BRIDGE

EP6-101

646CA2500.23

AuthorChecker

PANELBOARD SCHEDULES

VAPHS UNIVERSITY DRIVE

1 & 30

CR

CM

CR

S

S

S

S

S

S

S

S

S S S

S

S

S

S

S

CM

F B

F B

F B

F B

F B

F B

F B

PB

F

EXISTING BUILDING 1

2ND FLOOR

AREA W

EXISTING BUILDING 30

2ND FLOOR

S

D

F B

D

F B

F B

F B

SD

SDSD

W W

W

W

SDSD

D

E

E.6

E.7 F

3.4

6.5

6.1

12.8 x.11x.10 x.8x.7x.6x.5x.4 x.19x.18x.17x.16x.14 x.2 x.C

EA

x.D x.E x.F x.G x.J x.L x.N

TW112

FULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg. ofRevisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

Office of

Facilities

Management o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t 4 o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Department of Veterans Affairs

BIDDING DOCUMENTS - FEBRUARY 22, 2019

VA CARES CONSOLIDATION

VAMC, PITTSBURGH, PA

CONNECTING BRIDGE

ET1-101

646CA2500.23

AuthorChecker

BRIDGE SYSTEMS PLAN

VAPHS UNIVERSITY DRIVE

1 & 30

3 - 4" EMT CONDUITS WITH DRAGWIRE FOR FUTURE TELECOMMUNICATION

CABLING.

RELOCATED SURFACE MOUNTED PAGING SPEAKER.

EXISTING SECURITY TRAC DURESS CEILING SENSOR TO BE

REMOVED FROM CEILING AND SUPPORTED ABOVE CEILING FOR

REINSTALLATION BY SECURTY VENDOR.

FIRE ALARM SPEAKER STROBE LOCATED IN BRIDGE SHALL BE

PROGRAMMED TO OPERATE FROM BOTH BUILDING #30 AND BUILDING #1

FIRE ALARM SYSTEMS.

TO NEW PA AMPLIFIER LOCATED IN ELECTRICAL ROOM.

TO NEAREST FIRE ALARM NOTIFICATION APPLIANCE PANEL AND AMPLIFIER

LOCATED IN BUILDING #1. CONTRACTOR TO PROVIDE A NEW BOOSTER

PANEL FOR APPLIANCE DEVICES IF REQUIRED. IF NEW PANEL IS ADDED,

PROVIDE SMOKE DETECTOR AT THIS LOCATION AS REQUIRED.

TO NEAREST FIRE ALARM NOTIFICATION APPLIANCE PANEL AND AMPLIFIER

LOCATED IN BUILDING #30. CONTRACTOR TO PROVIDE A NEW BOOSTER

PANEL FOR APPLIANCE DEVICES IF REQUIRED. IF NEW PANEL IS ADDED,

PROVIDE SMOKE DETECTOR AT THIS LOCATION AS REQUIRED.

TO NEAREST PAGING SYSTEM AMP LOCATED IN BUILDING #30.

PA 100W AMPLIFIER/ CABINET

120V 1 PHASE NE PWR,

BOGEN #C100

CONTACT: NICK WASKIEWICZ FROM DSX AT

412-848-8326

TO NEAREST EXISTING FIRE ALARM TERMINAL CABINET IN BUILDING #1.

PROVIDE NEW CABINET, EXPANSION CARDS, ETC. AS REQUIRED TO

SUPPORT NEW DEVICES.

TO NEAREST EXISTING FIRE ALARM TERMINAL CABINET IN BUILDING #30.

PROVIDE NEW CABINET, EXPANSION CARDS, ETC. AS REQUIRED TO

SUPPORT NEW DEVICES.

EXISTING TELECOMMUNICATIONS ROOM. PROVIDE FOUR (4) 4" SLEEVES

WITH FIRESTOPPING THROUGH WALL FOR FUTURE ACCESS TO NEW CABLE

TRAY.

LOCATE NEW FIRE ALARM PANELS WITHIN EXISTING ELECTRICAL ROOM

2W106. ROUTE NEW BACKBONE CABLING TO EXISTING FA PANEL LOCATED

IN ROOM 1C101 IN BUILDING 29.

Key Notes

1/8" = 1'-0"

BRIDGE SYSTEMS PLAN

NEW FIRE ALARM DEVICES TO BE SERVED FROM THE

EXISTING SIMPLEX BUILDING #30 AND BUILDING #1 FIRE ALARM

CONTROL PANELS. PROVIDE ALL NECESSARY SOFTWARE

MODIFICATION REQUIRED.

1.

General Notes

1 AMENDMENT 3 01-31-17

ESD-801 - ELECTRICAL DEMOLITION PLAN
Sheets
EG0-001 - SYMBOLS & LIGHTING FIXTURE SCHEDULE
EL1-101 - BRIDGE LIGHTING PLAN
EP1-101 - BRIDGE POWER PLAN
EP5-101 - ELECTRICAL SINGLE-LINE DIAGRAMS
EP6-101 - PANELBOARD SCHEDULES
ESD-801 - ELECTRICAL DEMOLITION PLAN
ET1-101 - BRIDGE SYSTEMS PLAN
EG0-001 - SYMBOLS & LIGHTING FIXTURE SCHEDULE
Sheets
EG0-001 - SYMBOLS & LIGHTING FIXTURE SCHEDULE
EL1-101 - BRIDGE LIGHTING PLAN
EP1-101 - BRIDGE POWER PLAN
EP5-101 - ELECTRICAL SINGLE-LINE DIAGRAMS
EP6-101 - PANELBOARD SCHEDULES
ESD-801 - ELECTRICAL DEMOLITION PLAN
ET1-101 - BRIDGE SYSTEMS PLAN
EL1-101 - BRIDGE LIGHTING PLAN
Sheets
EG0-001 - SYMBOLS & LIGHTING FIXTURE SCHEDULE
EL1-101 - BRIDGE LIGHTING PLAN
EP1-101 - BRIDGE POWER PLAN
EP5-101 - ELECTRICAL SINGLE-LINE DIAGRAMS
EP6-101 - PANELBOARD SCHEDULES
ESD-801 - ELECTRICAL DEMOLITION PLAN
ET1-101 - BRIDGE SYSTEMS PLAN
EP1-101 - BRIDGE POWER PLAN_updated
Sheets
EP1-101 - BRIDGE POWER PLAN
ET1-101 - BRIDGE SYSTEMS PLAN
EP5-101 - ELECTRICAL SINGLE-LINE DIAGRAMS
Sheets
EG0-001 - SYMBOLS & LIGHTING FIXTURE SCHEDULE
EL1-101 - BRIDGE LIGHTING PLAN
EP1-101 - BRIDGE POWER PLAN
EP5-101 - ELECTRICAL SINGLE-LINE DIAGRAMS
EP6-101 - PANELBOARD SCHEDULES
ESD-801 - ELECTRICAL DEMOLITION PLAN
ET1-101 - BRIDGE SYSTEMS PLAN
EP6-101 - PANELBOARD SCHEDULES
Sheets
EG0-001 - SYMBOLS & LIGHTING FIXTURE SCHEDULE
EL1-101 - BRIDGE LIGHTING PLAN
EP1-101 - BRIDGE POWER PLAN
EP5-101 - ELECTRICAL SINGLE-LINE DIAGRAMS
EP6-101 - PANELBOARD SCHEDULES
ESD-801 - ELECTRICAL DEMOLITION PLAN
ET1-101 - BRIDGE SYSTEMS PLAN
ET1-101 - BRIDGE SYSTEMS PLAN_updated
Sheets
EP1-101 - BRIDGE POWER PLAN
ET1-101 - BRIDGE SYSTEMS PLAN

File details come from the government source that posted it.