ROUND NECK CEILING DIFFUSER TAKE-OFF
SIDE VIEW
ROUND AND/OR SQUARE NECK CEILING DIFFUSER
TAKE-OFFS SIDE VIEW
MULTI-BLADE DAMPER FOR ROUND
NECK DIFFUSER & OPPOSED BLADE
DAMPER FOR SQUARE NECK DIFFUSER
CONTROL GRIDCEILING
SUPPLY DUCT
SPLITTER DAMPER WITH
CENTER ROD OPERATOR
SUPPLY DUCT
CEILING CONTROL GRID
NOTE:
1.
2.
DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR
FOR MULTI-BLADE DAMPERS & ROUND DAMPERS.
INSULATION
DAMPER BLADE
1/8" [6mm]
CLEARANCE
ALL AROUND
OUTSIDE END BEARING
INSIDE END BEARING
HANDLE WITH
LOCKING
QUADRANT
INSULATION
STAND-OFF
1/2" [15mm]
ROUND ROD PIN
DUCT
STIFFEN BLADE
AS REQUIRED
SIDE ELEVATION SECTION
VOLUME DAMPER DETAIL
VANE
VANE
NOTES:
1.
2.
THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
ALL STANDARD RADIUS ELBOWS SHOWN ON FLOOR PLANS MAY BE MADE SHORT
RADIUS ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL
BE CONSTRUCTED, SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.
R SHALL
EQUAL
OR BE
GREATER
THAN W.
R SHALL
EQUAL
OR BE
GREATER
THAN
1/3W.
W
R
2/3W
1/ 3W
R SHALL
EQUAL
OR BE
GREATER
THAN
1/6W.
SHORT RADIUS ELBOW
WITH ONE VANE
SHORT RADIUS ELBOW
WITH TWO VANES
W W
1/2W
1/ 3W
1/6W
W
STANDARD RADIUS
ELBOW
R R
NOTES:
1.
2.
3.
4.
ALL VANED ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY
SMACNA.
WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE VANE TYPE
REGARDLESS OF W DIMENSION.
ALL SINGLE VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm]
MAXIMUM SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.
WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL
BE DOUBLE VANE TYPE.
W
W1
ONE 1 [25] x 22 GA STRAP
QUANTITY/SIZEMAX. DUCT ∅
26 [650]
HANGER STRAPS OR RODS
MAX. LOAD
LBS. [kg]
260 [119]
MAX.
144 [3658]
IN. [mm]
SPACING
IN. [mm] IN. [mm]
BAND OF
SAME SIZE AS
HANGER STRAP
LOAD RATED
FASTENERS
NOTE:
TABULATED DATA FROM SMACNA
ALLOWS FOR DUCT REINFORCING AND
INSULATION, BUT NO EXTERNAL LOAD.
SUPPLY
TYPICAL FOR SUPPLY,
RETURN, AND
EXHAUST
A
IR
F
LO
W
TYPICAL FOR SUPPLY,
RETURN, AND
EXHAUST
A
IR
F
LO
W
A
IR
F
LO
W
45°
VOLUME
DAMPER
D/4
BRANCH
MAIN
CONICAL SPIN TAP COLLAR
WITH DAMPER
FLEXIBLE DUCT OR
RIGID ROUND
MECHANICAL CLAMP
MAIN
MAIN
ROUND OR
MITERED ELBOW WITH
TURNING VANES.
VOLUME DAMPER
VOLUME DAMPER
D
NOTES:
1. THE SUPPLY REGISTER TAKE-OFF MAY BE USED FOR
UP TO 25% OF THE MAIN DUCT CFM. THE BRANCH
DUCT TAKE-OFF MAY BE USED FOR UP TO 15% OF
THE MAIN DUCT CFM ANYTIME AND UP TO 40% WHEN
THE MAIN DUCT VELOCITY IS 1000 FPM (5 M/S) OR
LESS. THE AIR SPLIT DUCT TAKE-FF SHALL BE USED
IN ALL OTHER CASES AND MAY BE USED AT ANYTIME.
RADIANT PANEL
HWS
HWR
NO
UNION (TYP.)
P/T PORT (TYP.) 2-WAY ATC VALVE BALANCING VALVE
BALL VALVE (TYP.)
STRAINER
NOTE: 3" INSULATION BLANKET
I IB DENSITY
INSULATION
CAULKING
LOUVER
EXTERIOR
SHEETMETAL FASTENED 6" ON CENTER
TO LOUVER AT INTERMEDIATE SUPPORTS
AND FRAMES.
PITCH TO DRAIN
BIRD SCREEN
º
HVAC CASING
INTAKE/EXHAUST
PLENUM
DUCTWORK-REFER TO
FLOOR PLAN FOR SIZE
BREAK-AWAY "S" SLIP JOINT TO CONNECT
DUCTWORK TO SLEEVE, MAXIMUM OF 6"
FROM WALL (BOTH SIDES)
FIRE DAMPER ASSEMBLY (UL-555
APPROVED FOR VERTICAL INSTALLATION AND
INSTALL TO COMPLY WITH NFPA-90A), WITH
DYNAMIC TYPE DAMPER OUTSIDE OF AIR
STREAM.
WALL SLEEVE-SIZE AS REQUIRED. WELD OR
BOLT AIR TIGHT TO ANGLES (BOTH SIDES
OF WALL)
1/8" MAXIMUM CLEARANCE FOR ALL FOUR
SIDES. DO NOT FILL OR SEAL WITH FIRE
CAULK OR FIRE STOP MATERIALS
INTERIOR WALL CONSTRUCTION. REFER TO
ARCHITECTURAL DRAWINGS FOR THICKNESS,
TYPE, AND FIRE RATING
1-1/2" x 1-1/2" x 14 GAUGE RETAINING ANGLES FOR NEW WALL CONSTRUCTION AND 2" x 1" x 14 GAUGE RETAINING ANGLES FOR EXISTING WALL CONSTRUCTION. SECURE
ANGLES TO DAMPER SLEEVE ON ALL FOUR SIDES AND ON BOTH SIDES OF WALL.
ANGLES
TO BE TIGHT TO WALL CONSTRUCTION WITHOUT ATTACHING DIRECTLY TO WALL
CONSTRUCTION. USE 1/4" x 20 x 3/4" LONG ROUND HEAD STOVE BOLTS @12" O.C.
MAXIMUM OR WELD
LOCATE FIRE DAMPER ACCESS DOOR IN BOTTOM OF DUCT AT
AN ACCESSIBLE LOCATION. DOOR SIZE AS REQUIRED TO
PROPERLY SERVICE DAMPER. ALTERNATE LOCATION #1: SIDE
OF DUCT. ALTERNATE LOCATION #2: (LEAST PREFERRED) TOP
OF DUCT
FACTORY SUPPLIED DAMPER SLEEVE, 16 GAUGE FOR DAMPERS
NOT EXCEEDING 36" WIDE OR 24" HIGH. 14 GAUGE FOR
DAMPERS LARGER THAN 36" WIDE OR 24" HIGH
AIR FLOW
FUSIBLE LINK - 165°F TEMPERATURE
RATING, UNLESS OTHERWISE NOTED
2. LABEL THE ACCESS DOORS: "FIRE DAMPER ACCESS".
3. WHERE ACCESS DOORS ARE INSTALLED ON THE SIDE OF A
DUCT, PROVIDE A LABEL OR SIGN AT THE BOTTOM OF THE DUCT
WITH AN ARROW AND "FIRE/SMOKE DAMPER ACCESS DOOR" TEXT
POINTING TO THE ACCESS DOOR. WHERE ACCESS DOORS ARE
INSTALLED ON THE TOP OF THE DUCT, PROVIDE A LABEL OR SIGN
AT THE BOTTOM OF THE DUCT WITH "FIRE/SMOKE DAMPER ACCESS
DOOR ON TOP OF DUCT."
5. REFER TO FIRE DAMPER SCHEDULE FOR FURTHER INFORMATION.
1. FOLLOW THIS DETAIL, UNLESS THE DAMPER MANUFACTURER'S
INSTALLATION DETAILS AND INSTRUCTIONS (AS TESTED AND
APPROVED BY UL) OR THE PROJECT SPECIFICATION IS MORE
STRINGENT.
A. FIRE DAMPER MODE: HIGH TEMPERATURE MELTS FUSIBLE LINK,
CLOSING FIRE DAMPER.
4. SEQUENCE OF OPERATION:
NOTES:
LPC
LPS
N.C. BYPASS VALVE
F & T TRAP
TO LOW PRESSURE
CONDENSATE
RETURN
M
IN
NOTE: PROVIDE STEAM MAIN DRIPS AT:
1. END OF MAINS
2. BASE OF RISERS
3. BEFORE CONTROL VALVES
4. LOW POINTS IN MAINS
5. 100 FT. INCREMENTS
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. ofRevisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of
Facilities
Management o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t 4 o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
BIDDING DOCUMENTS - FEBRUARY 22, 2019
VA CARES CONSOLIDATION
VAMC, PITTSBURGH, PA
CONNECTING BRIDGE
MH0-701
646CA2500.23
AuthorChecker
HVAC DETAILS &
SCHEDULES
VAPHS UNIVERSITY DRIVE
1 & 30
NTS1
SUPPLY DIFFUSER TAKE-OFF DETAIL
NTS3
VOLUME DAMPER DETAIL
NTS4
RADIUS ELBOW DETAIL
NTS5
MITERED ELBOW DETAIL
NTS6
PIPE HANGER DETAIL
NTS2
SUPPLY DUCTWORK TAKE-OFFS DETAIL
NTS7
INSULATED RADIANT HEAT PANEL PIPING
DETAIL
NTS8
INTAKE/EXHAUST PLENUM TO LOUVER
CONNECTION
NTS
FIRE DAMPER
1 AMENDMENT 7 05-23-19
NTS
STEAM MAIN DRIP DETAIL - LOW PRESSURE
| Sheets |
| MD0-100 - SECOND FLOOR DEMO DUCTWORK PLAN |
| MH0-100 - SECOND FLOOR NEW DUCTWORK PLAN |
| MH0-301 - ENLARGED SECTIONS |
| MH0-701 - HVAC DETAILS & SCHEDULES |