Solicitation No. VA 36C10F19R0003 VAPHS – University Drive Division
Research Office Building – Building 30
Connecting Bridge
Amendment No. 5 – May 3, 2019
01-01-16
08 71 00-1
SECTION 08 71 00
DOOR HARDWARE
PART 1 - GENERAL
1.1 DESCRIPTION
A. Door hardware and related items necessary for complete installation and operation of doors.
1.2 RELATED WORK
A. Caulking: Section 07 92 00 JOINT SEALANTS.
B. Application of Hardware:
1. Section 08 11 13, HOLLOW METAL DOORS AND FRAMES
2. Section 08 71 13, AUTOMATIC DOOR OPERATORS
C. Finishes: Section 09 06 00, SCHEDULE FOR FINISHES.
D. Painting: Section 09 91 00, PAINTING.
E. Card Readers: Section 28 13 11, PHYSICAL ACCESS CONTROL SYSTEMS.
1. Provided by Government under a separate contract.
F. Fire Detection: Section 28 31 00, FIRE DETECTION AND ALARM.
1.3 GENERAL
A. All hardware shall comply with UFAS, (Uniform Federal Accessible
Standards) unless specified otherwise.
B. Hardware for Labeled Fire Doors and Exit Doors: Conform to requirements of NFPA 80 for labeled fire doors and to NFPA 101 for exit doors, as well as to other requirements specified. Provide hardware listed by UL, except where heavier materials, large size, or better grades are specified herein under paragraph HARDWARE SETS. In lieu of UL labeling and listing, test reports from a nationally recognized testing agency may be submitted showing that hardware has been tested in accordance with UL test methods and that it conforms to NFPA requirements.
C. Hardware for application on metal and wood doors and frames shall be made to standard templates. Furnish templates to the fabricator of these items in sufficient time so as not to delay the construction.
D. The following items shall be of the same manufacturer, except as otherwise specified:
1. Mortise locksets.
2. Hinges for hollow metal and wood doors.
3. Surface applied overhead door closers.
4. Exit devices.
5. Floor closers.
Connecting Bridge
Amendment No. 5 – May 3, 2019
01-01-16
08 71 00-2
1.4 WARRANTY
A. Automatic door operators shall be subject to the terms of FAR Clause
52.246-21, except that the Warranty period shall be two years in lieu of one year for all items except as noted below:
1. Locks, latchsets, and panic hardware: 5 years.
2. Door closers and continuous hinges: 10 years.
1.5 MAINTENANCE MANUALS
A. In accordance with Section 01 00 00, GENERAL REQUIREMENTS Article titled "INSTRUCTIONS", furnish maintenance manuals and instructions on all door hardware. Provide installation instructions with the submittal documentation.
1.6 SUBMITTALS
A. Submittals shall be in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA AND SAMPLES. Submit 6 copies of the schedule per Section
01 33 23. Submit 2 final copies of the final approved schedules to VAMC
Locksmith as record copies (VISN Locksmith if the VAMC does not have a locksmith).
B. Hardware Schedule: Prepare and submit hardware schedule in the following form:
Hardware
Item
Quantity Size Reference
Publication
Type No.
Finish Mfr.
Name and
Catalog
No.
Key
Control
Symbols
UL Mark
(if fire rated and listed)
ANSI/BHMA
Finish
Designation
C. Samples and Manufacturers' Literature:
1. Samples: All hardware items (proposed for the project) that have not been previously approved by Builders Hardware Manufacturers
Association shall be submitted for approval. Tag and mark all items with manufacturer's name, catalog number and project number.
2. Samples are not required for hardware listed in the specifications by manufacturer's catalog number, if the contractor proposes to use the manufacturer's product specified.
Connecting Bridge
Amendment No. 5 – May 3, 2019
01-01-16
08 71 00-3
D. Certificate of Compliance and Test Reports: Submit certificates that hardware conforms to the requirements specified herein. Certificates shall be accompanied by copies of reports as referenced. The testing shall have been conducted either in the manufacturer's plant and certified by an independent testing laboratory or conducted in an independent laboratory, within four years of submittal of reports for approval.
1.7 DELIVERY AND MARKING
A. Deliver items of hardware to job site in their original containers, complete with necessary appurtenances including screws, keys, and instructions. Tag one of each different item of hardware and deliver to
Resident Engineer for reference purposes. Tag shall identify items by
Project Specification number and manufacturer's catalog number. These items shall remain on file in Resident Engineer's office until all other similar items have been installed in project, at which time the
Resident Engineer will deliver items on file to Contractor for installation in predetermined locations on the project.
1.8 PREINSTALLATION MEETING
A. Convene a preinstallation meeting not less than 30 days before start of installation of door hardware. Require attendance of parties directly affecting work of this section, including Contractor and Installer, Architect, Project Engineer and VA Locksmith, Hardware Consultant, and
Hardware Manufacturer’s Representative. Review the following:
1. Inspection of door hardware.
2. Job and surface readiness.
3. Coordination with other work.
4. Protection of hardware surfaces.
5. Substrate surface protection.
6. Installation.
7. Adjusting.
8. Repair.
9. Field quality control.
10. Cleaning.
1.9 INSTRUCTIONS
A. Hardware Set Symbols on Drawings: Except for protective plates, door stops, mutes, thresholds and the like specified herein, hardware requirements for each door are indicated on drawings by symbols.
Connecting Bridge
Amendment No. 5 – May 3, 2019
01-01-16
08 71 00-4
Symbols for hardware sets consist of letters (e.g., "HW") followed by a number. Each number designates a set of hardware items applicable to a door type.
B. Manufacturers' Catalog Number References: Where manufacturers' products are specified herein, products of other manufacturers which are considered equivalent to those specified may be used. Manufacturers whose products are specified are identified by abbreviations as follows:
Adams-Rite Adams Rite Mfg. Co. Glendale, CA
Glynn Johnson Glynn Johnson Co. Chicago, IL
LCN LCN Closers Princeton, IL
Firemark Rixon-Firemark Co. Chicago, IL
Hager Hager Hinge Company Saint Louis, MO
Stanley The Stanley Works New Britain, CT
Trimco Triangle Brass Mfg. Co. Los Angeles, CA
Unican Simplex Security Systems Collinsville, CT
Von Duprin Von Duprin Hardware Co. Indianapolis, IN
Zero Zero Weather Stripping Co. New York, NY
C. Keying: All cylinders shall be keyed into existing Grand Master Key
System. Provide removable core cylinders that are removable only with a special key or tool without disassembly of knob or lockset. Cylinders shall be 7 pin type. Keying information shall be furnished at a later date by the Resident Engineer.
D. Interchangeable Core and Key Part Numbers are: KABA-ILCO/Peaks.
1. 3850-25-1007 P3 50%
2. 3850-25-1007 P4 50%.
3. Elevator key switch – 7 pin SFIC
4. Electric panel covers – 7 pin SFIC.
5. Dealer code: A02 N01.
6. Key part number: 3850-00-0003.
E. Provide spare cores as follows:
P1 Keyway: 50%.
P2 Keyway: 40%.
P3 Keyway: 50%.
Connecting Bridge
Amendment No. 5 – May 3, 2019
01-01-16
08 71 00-5
P4 Keyway: 50%.
1.10 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. In text, hardware items are referred to by series, types, etc., listed in such specifications and standards, except as otherwise specified.
B. American Society for Testing and Materials (ASTM):
F883-04.................Padlocks
E2180-07................Standard Test Method for Determining the
Activity of Incorporated Antimicrobial Agent(s)
In Polymeric or Hydrophobic Materials
C. American National Standards Institute/Builders Hardware Manufacturers
Association (ANSI/BHMA):
A156.1-06...............Butts and Hinges
A156.2-03...............Bored and Pre-assembled Locks and Latches
A156.3-08...............Exit Devices, Coordinators, and Auto Flush
Bolts
A156.4-08...............Door Controls (Closers)
A156.5-14...............Cylinders and Input Devices for Locks.
A156.6-05...............Architectural Door Trim
A156.8-05...............Door Controls-Overhead Stops and Holders
A156.13-05..............Mortise Locks and Latches Series 1000
A156.14-07 .............Sliding and Folding Door Hardware
A156.15-06..............Release Devices-Closer Holder, Electromagnetic and Electromechanical
A156.16-08..............Auxiliary Hardware
A156.17-04 .............Self-Closing Hinges and Pivots
A156.18-06..............Materials and Finishes
A156.20-06 .............Strap and Tee Hinges, and Hasps
A156.21-09..............Thresholds
A156.22-05..............Door Gasketing and Edge Seal Systems
A156.23-04..............Electromagnetic Locks
A156.24-03..............Delayed Egress Locking Systems
A156.25-07 .............Electrified Locking Devices
A156.26-06..............Continuous Hinges
A156.28-07 .............Master Keying Systems
Connecting Bridge
Amendment No. 5 – May 3, 2019
01-01-16
08 71 00-6
A156.29-07 .............Exit Locks and Alarms
A156.30-03 .............High Security Cylinders
A156.31-07 .............Electric Strikes and Frame Mounted Actuators
A156.36-10..............Auxiliary Locks
A250.8-03...............Standard Steel Doors and Frames
D. National Fire Protection Association (NFPA):
80-10...................Fire Doors and Other Opening Protectives
101-09..................Life Safety Code
E. Underwriters Laboratories, Inc. (UL):
Building Materials Directory (2008)
PART 2 - PRODUCTS
2.1 BUTT HINGES
A. ANSI A156.1. Provide only three-knuckle hinges, except five-knuckle where the required hinge type is not available in a three-knuckle version (e.g., some types of swing-clear hinges). The following types of butt hinges shall be used for the types of doors listed, except where otherwise specified:
1. Interior Doors: Type A8112/A5112 for doors 900 mm (3 feet) wide or less and Type A8111/A5111 for doors over 900 mm (3 feet) wide.
Hinges for doors exposed to high humidity areas (shower rooms, toilet rooms, kitchens, janitor rooms, etc. shall be of stainless steel material.
2. Labeled Wood Fire Doors: Type 8411 or Type 8412.
B. Provide quantity and size of hinges per door leaf as follows:
1. Doors up to 1210 mm (4 feet) high: 2 hinges.
2. Doors 1210 mm (4 feet) to 2260 mm (7 feet 5 inches) high: 3 hinges minimum.
3. Doors greater than 2260 mm (7 feet 5 inches) high: 4 hinges.
4. Doors up to 900 mm (3 feet) wide, standard weight: 114 mm x 114 mm
(4-1/2 inches x 4-1/2 inches) hinges.
5. Doors over 900 mm (3 feet) to 1065 mm (3 feet 6 inches) wide, standard weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).
6. Doors over 1065 mm (3 feet 6 inches) to 1210 mm (4 feet), heavy weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).
7. Provide heavy-weight hinges where specified.
8. At doors weighing 330 kg (150 lbs.) or more, furnish 127 mm (5 inch) high hinges.
Connecting Bridge
Amendment No. 5 – May 3, 2019
01-01-16
08 71 00-7
C. See Articles "MISCELLANEOUS HARDWARE" and "HARDWARE SETS" for pivots and hinges other than butts specified above and continuous hinges specified below.
2.3 DOOR CLOSING DEVICES
A. Closing devices shall be products of one manufacturer for each type specified.
2.4 ELECTROMAGNETIC LOCKS
A. ANSI/BHMA A156.23; electrically powered, of strength and configuration indicated; with electromagnet attached to frame and armature plate attached to door. Listed under Category E in BHMA's "Certified Product
Directory."
1. Type: Full exterior or full interior, as required by application indicated.
2. Strength Ranking: 1500 lbf (6672 N)
3. Inductive Kickback Peak Voltage: Not more than 53V.
4. Residual Magnetism: Not more than 4 lbf (18 N) to separate door from magnet.
B. Delayed-Egress Locks: BHMA A156.24. Listed under Category G in BHMA's
"Certified Product Directory".
1. Means of Egress Doors: Lock releases within 15 seconds after applying a force not more than 15 lbf (67 N) for not more than 3 seconds, as required by NFPA 101.
2. Security Grade: Activated from secure side of door by initiating device.
3. Movement Grade: Activated by door movement as initiating device.
4. The lock housing shall not project more than 4-inches (101mm) from the underside of the frame head stop.
C. Manufacturers:
1. Door Controls International.
2. Doorguard Systems, Inc.
3. Dortronics Systems, Inc.
4. DynaLock Corp.
5. Locknetics; an Ingersoll-Rand Company.
6. Rutherford Controls Int'l. Corp.
7. SARGENT Manufacturing Company; an ASSA ABLOY Group company.
8. Securitron Magnalock Corporation; an ASSA ABLOY Group company.
9. Security Door Controls.
Connecting Bridge
Amendment No. 5 – May 3, 2019
01-01-16
08 71 00-8
2.4 CARD READERS AND REQUEST TO EXIT DEVICES
A. Card readers and overhead request to exit devices are provided and installed under a separate contract. Locations are indicated on
Architectural drawings. These locations are inclusive of conduit for electric strikes and power for magnetic locks as required. Coordinate with electrical Drawings. Refer to Section 28 05 33 RACEWAY AND BOXES
FOR ELECTRONIC SAFETY AND SECURITY for card reader installation requirements and coordination.
2.5 ELECTRIC STRIKES
A. ANSI/ BHMA A156.31 Grade 1.
B. General: Use fail-secure electric strikes at fire-rated doors.
C. Manufacturers:
1. Adams Rite Manufacturing Co.
2. Folger Adam Security Inc.; an ASSA ABLOY Group company.
3. HES, Inc.; an ASSA ABLOY Group company.
4. Locknetics; an Ingersoll-Rand Company.
5. Precision Hardware, Inc.
6. Von Duprin; an Ingersoll-Rand Company.
2.6 ARMOR PLATES, KICK PLATES, MOP PLATES AND DOOR EDGING
A. Conform to ANSI Standard A156.6.
B. Provide protective plates and door edging as specified below:
1. Kick plates, mop plates and armor plates of metal, Type J100 series.
2. Provide kick plates and mop plates for both sides of each door, except where noted as not required. Kick-mop plates shall be 200 mm
(8 inches). Both kick and mop plates shall be minimum 1.27 mm (0.050 inches) thick. Provide kick and mop plates beveled on all 4 edges
(B4E). On push side of doors where jamb stop extends to floor, make kick plates 38 mm (1-1/2 inches) less than width of door, except pairs of metal doors which shall have plates 25 mm (1 inch) less than width of each door. Extend all other kick and mop plates to within 6 mm (1/4 inch) of each edge of doors. Kick and mop plates shall butt astragals. For jamb stop requirements, see specification sections pertaining to door frames.
3. Kick plates and/or mop plates are not required on following door sides:
Connecting Bridge
Amendment No. 5 – May 3, 2019
01-01-16
08 71 00-9
a. Armor plate side of doors;
b. Exterior side of exterior doors;
c. Closet side of closet doors;
d. Both sides of aluminum entrance doors.
4. Armor plates for doors are listed under Article "Hardware Sets".
Armor plates shall be thickness as noted in the hardware set, 875 mm
(35 inches) high and 38 mm (1-1/2 inches) less than width of doors, except on pairs of metal doors. Provide armor plates beveled on all
4 edges (B4E). Plates on pairs of metal doors shall be 25 mm (1 inch) less than width of each door. Where top of intermediate rail of door is less than 875 mm (35 inches) from door bottom, extend armor plates to within 13 mm (1/2 inch) of top of intermediate rail.
On doors equipped with panic devices, extend armor plates to within
13 mm (1/2 inch) of panic bolt push bar.
2.7 EXIT DEVICES
A. Conform to ANSI Standard A156.3. Exit devices shall be Grade 1; type and function are specified in hardware sets. Provide flush with finished floor strikes for vertical rod exit devices in interior of building. Trim shall have lever handles of design similar to locksets, unless otherwise specified.
B. Exit devices for fire doors shall comply with Underwriters
Laboratories, Inc., requirements for Fire Exit Hardware. Submit proof of compliance.
2.8 FLUSH BOLTS (AUTOMATIC)
A. Conform to ANSI A156.3. Dimension of flush bolts shall conform to ANSI
A115. Bolts shall conform to Underwriters Laboratories, Inc., requirements for fire door hardware. Flush bolts shall automatically latch and unlatch. Furnish dustproof strikes conforming to ANSI A156.16 for bottom flushbolt. Face plates for dustproof strike shall be rectangular and not less than 38 mm by 90 mm (1-1/2 by 3-1/2 inches).
B. At interior doors, provide auto flush bolts less bottom bolt, unless otherwise specified, except at wood pairs with fire-rating greater than
20 minutes; provide fire pins as required by auto flush bolt and door fire labels.
2.30 FINISHES
A. Exposed surfaces of hardware shall have ANSI A156.18, finishes as specified below. Finishes on all hinges, pivots, closers, thresholds, Connecting Bridge
Amendment No. 5 – May 3, 2019
01-01-16
08 71 00-10 etc., shall be as specified below under "Miscellaneous Finishes." For field painting (final coat) of ferrous hardware, see Section 09 91 00, PAINTING.
B. 630: All surfaces on exterior and interior of buildings, except where other finishes are specified.
C. Miscellaneous Finishes:
1. Hinges --interior doors: 652 or 630.
2. Door Closers: Factory applied paint finish. Satin Aluminum color.
3. Cover plates for floor hinges and pivots: 630.
4. Other primed steel hardware: 652.
D. Hardware Finishes for Existing Buildings: U.S. Standard finishes shall match finishes of hardware in (similar) existing spaces except where otherwise specified.
E. Color of Plastic Items: See Section 09 06 00, SCHEDULE FOR FINISHES.
Where colors other than chocolate brown or black are specified, color of core material may be different than color of face.
2.31 BASE METALS
A. Apply specified U.S. Standard finishes on different base metals as following:
Finish Base Metal
652 Steel
626 Brass or bronze
630 Stainless steel
PART 3 - EXECUTION
3.1 HARDWARE HEIGHTS
A. For existing buildings locate hardware on doors at heights to match existing hardware. The Contractor shall visit the site, verify location of existing hardware and submit locations to VA Resident Engineer for approval.
B. For new buildings locate hardware on doors at heights specified below, with all hand-operated hardware centered within 864 mm (34 inches) to
1200 mm (48 inches), unless otherwise noted:
C. Hardware Heights from Finished Floor:
1. Exit devices centerline of strike (where applicable) 1024 mm (40-
5/16 inches).
Connecting Bridge
Amendment No. 5 – May 3, 2019
01-01-16
08 71 00-11
2. Locksets and latch sets centerline of strike 1024 mm (40-5/16 inches).
3. Deadlocks centerline of strike 1219 mm (48 inches).
4. Centerline of door pulls to be 1016 mm (40 inches).
5. Push plates and push-pull shall be 1270 mm (50 inches) to top of plate.
6. Push-pull latch to be 1024 mm (40-5/16 inches) to centerline of strike.
7. Centerline of deadlock strike to be 840 mm (33 inches) when used with push-pull latch.
8. Locate other hardware at standard commercial heights. Locate push and pull plates to prevent conflict with other hardware.
3.2 INSTALLATION
A. Closer devices, including those with hold-open features, shall be equipped and mounted to provide maximum door opening permitted by building construction or equipment. Closers shall be mounted on side of door inside rooms, inside stairs, and away from corridors. Where closers are mounted on doors they shall be mounted with sex nuts and bolts; foot shall be fastened to frame with machine screws.
B. Substitute parallel arm or top jamb mounting for regular arm mounting where the following conditions occur:
1. Where door swing, in full open position, would be limited to less than 90 degrees due to partition construction and closer location.
2. Where door to room opens outward into corridor.
3. Where exterior doors open outward.
C. Hinge Size Requirements:
Door Thickness Door Width Hinge Height
45 mm (1-3/4 inch) 900 mm (3 feet) and less 113 mm (4-1/2 inches)
45 mm (1-3/4 inch) Over 900 mm (3 feet) but not more than 1200 mm (4 feet)
125 mm (5 inches)
D. Hinge leaves shall be sufficiently wide to allow doors to swing clear of door frame trim and
E. Hinges Required Per Door:
Doors 1500 mm (5 ft) or less in height 2 butts
Connecting Bridge
Amendment No. 5 – May 3, 2019
01-01-16
08 71 00-12
Doors over 1500 mm (5 ft) high and not over 2280 mm
(7 ft 6 in) high
3 butts
Doors over 2280 mm (7 feet 6 inches) high 4 butts
Dutch type doors 4 butts
Doors with spring hinges 1370 mm (4 feet 6 inches) high or less
2 butts
Doors with spring hinges over 1370 mm (4 feet 6 inches) 3 butts
F. Fastenings: Suitable size and type and shall harmonize with hardware as to material and finish. Provide machine screws and lead expansion shields to secure hardware to concrete, ceramic or quarry floor tile, or solid masonry. Fiber or rawl plugs and adhesives are not permitted.
All fastenings exposed to weather shall be of nonferrous metal.
G. After locks have been installed; show in presence of Resident Engineer that keys operate their respective locks in accordance with keying requirements. (All keys, Master Key level and above shall be sent
Registered Mail to the Medical Center Director along with the bitting list. Also a copy of the invoice shall be sent to the Resident Engineer for his records.) Installation of locks which do not meet specified keying requirements shall be considered sufficient justification for rejection and replacement of all locks installed on project.
3.3 FINAL INSPECTION
A. Installer to provide letter to VA Resident/Project Engineer that upon completion, installer has visited the Project and has accomplished the following:
1. Re-adjust hardware.
2. Evaluate maintenance procedures and recommend changes or additions, and instruct VA personnel.
3. Identify items that have deteriorated or failed.
4. Submit written report identifying problems.
3.4 DEMONSTRATION
A. Demonstrate efficacy of mechanical hardware and electrical, and electronic hardware systems, including adjustment and maintenance procedures, to satisfaction of Resident/Project Engineer and VA
Locksmith.
Connecting Bridge
Amendment No. 5 – May 3, 2019
01-01-16
08 71 00-13
3.5 HARDWARE SETS
A. Following sets of hardware correspond to hardware symbols shown on drawings. Only those hardware sets that are shown on drawings will be required. Disregard hardware sets listed in specifications but not shown on drawings.
HW 1 Rated (Bridge) Pair - Door A-02 and Door A-09
2 Continuous Hinges INTEGRAL HINGE GUARD CHANNEL
ADJUSTA-SCREWS
2 Armor Plates J101 X 1.275 MM (0.050 inch)
1 2 Exit Devices with vertical rods
TYPE 7 or 8 F01, less bottom rod
1 Self Adhesive Astragal ROY14
1 2 Touchless Actuators 8310-13 LCN
1 Set Auto Flush Bolts TYPE 25
2 Sets Self-Adhesive Seals R0E154
1 Door Status Contact (By Security Vendor)
1 Threshold Saddle Type Aluminum
1 Power Supply
H 1 Card Reader (By Security Vendor)
1 Power Supply for Reader (By Security Vendor)
1 Automatic Door Operator; see Section 08 71 13
Notes:
Following functional description corresponds to hardware set:
1. Doors are closed and unlocked during business hours and are activated by touchless activators.
2. Doors are closed and secured by electromagnetic locks after hours.
3. Emergency release will be installed to release magnetic locks upon control failure.
4. Electric latch Latch held open under normal operation.
5. After hours, vValid card (readers & wiring by Security Vendor) presented from west side of door from Building 1 side (Door A-02) or from Building 30 side (Door A-09) will release magnetic locks, initiate automatic door operation and open door. Automatic sensors for door “1A” will be masked so that door “1A” will not operate. Touchless activator operates door from bridge side of door.
ELECTRIC HARDWARE ABBREVIATIONS LEGEND:
ADO = Automatic Door Operator
EMCH = Electro-Mechanical Closer-Holder
MHO = Magnetic Hold-Open (wall- or floor-mounted)
Connecting Bridge
Amendment No. 5 – May 3, 2019
01-01-16
08 71 00-14
6. Door status contacts in magnetic locks will monitor door position for security system.
7. Door status contacts in door operator system will monitor door position and interlock functionality.
8. In a fire alarm event:
a. Electric latch Vertical rods will engage and positively latch door.
b. Magnetic locks will release.
c. Automatic door operation will disengage.
HW 2 - Rated Door A-01 - Rated
1 Continuous Transfer Hinge x INTEGRAL HINGE GUARD CHANNEL
X ADJUSTA-SCREWS x 4-THRUWIRE TRANSFER x
IN-HINGE ACCESS PANEL
1 Electrified Lock F13-MOD x RIGID OUTSIDE LEVER X NO INSIDE
TURN X KEY RETRACTS LATCHBOLT AND
DEADBOLT (E01-REX, E06) 24VDC
1 Power Supply (By Security Vendor)
1 Closer C02011/C02021
1 Edge Guard (@ Wood Doors) J208M / J211 (VERIFY), CUT: HARDWARE
1 Floor Stop L02121 x 3 FASTENERS
1 Set Self-Adhesive Seals R0Y154
1 Alarm Contact
1 Card Reader (By Security Vendor)
120VAC POWER, CONDUIT, AND WIRING BY DIVISION 26.
CARD READER BY DIVISION 28.
Connecting Bridge
Amendment No. 5 – May 3, 2019
01-01-16
08 71 00-15
HW 2 Door A-01
Storefront Assembled System
1 Push Plate Switch (Frame Mounted)
2 Pivot Sets CO6011
2 Intermediate Pivots CO7321
2 Push/Pull Bar Sets J209P/J212
21 Overhead Stops CO1541 - Adjustable
2 Automatic Door Operator; see Section 08 71 13
HW 3 –Rated Door A-03 - Rated
Hinges QUANTITY & TYPE AS REQUIRED
Continuous Hinge INTEGRAL HINGE GUARD CHANNEL
ADJUSTA-SCREWS
1 Exit Device TYPE 1 F13 LEVER
1 Key Cylinder TYPE AS REQUIRED
1 Closer C02011/C02021
1 Floor Stop L02121 x 3 FASTENERS
1 Set Self-Adhesive Seals R0Y154
HW 4 Door A-04 Door A-08 - Rated
ADJUSTA-SCREWS
1 Storeroom Lock F07
1 Closer C02011/C02021
1 Armor Plate J101 x 1.275 MM (0.050 INCH) 1
1 Edge Guard (@ Wood Doors) J208M / J211 (VERIFY), CUT: 1
1 Set Self-Adhesive Seals R0Y154
HW 5 Door A-05 and A-06
1.5 Hinges QUANTITY & TYPE AS REQUIRED
1 Office Lock F04
1 Floor Stop L02121 x 3 FASTENERS
1 Set Self-Adhesive Seals R0Y154
1 Coat Hook L03121
OMIT COAT HOOK WHERE GLASS LITE PREVENTS INSTALLATION.
HW 6 Door A-07
ADJUSTA-SCREWS
1 Storeroom Lock F07
1 Armor Plate J101 x 1.275 MM (0.050 INCH) 1
1 Edge Guard (@ Wood Doors) J208M / J211 (VERIFY), CUT: 1
Connecting Bridge
Amendment No. 5 – May 3, 2019
01-01-16
08 71 00-16
Notes:
Following functional description correspond to hardware set:
9. Doors are closed and secured by electromagnetic locks.
10. Emergency release will be installed to release magnetic locks upon control failure.
11. Electric latch held open under normal operation.
12. Valid card (readers & wiring by Security Vendor) presented from west side of door will release magnetic locks, initiate automatic door operation and open door. Automatic sensors for door “1A” will be masked so that door “1A” will not operate.
13. Door status contacts in magnetic locks will monitor door position for security system.
14. Door status contacts in door operator system will monitor door position and interlock functionality.
15. In a fire alarm event:
d. Electric latch will engage and positively latch door.
e. Magnetic locks will release.
f. Automatic door operation will disengage.
16. Doors are closed and secured by electromagnetic locks.
17. Emergency release will be installed to release magnetic locks upon control failure.
18. Electric latch held open under normal operation.
19. Valid card (readers & wiring by Security Vendor) presented from west side of door will release magnetic locks, initiate automatic door operation and open door. Automatic sensors for door “1A” will be masked so that door “1A” will not operate.
20. Door status contacts in magnetic locks will monitor door position for security system.
21. Door status contacts in door operator system will monitor door position and interlock functionality.
22. In a fire alarm event:
a. Electric latch will engage and positively latch door.
b. Magnetic locks will release.
c. Automatic door operation will disengage.
- - - E N D - - -