262726.pdf

PDF 55 KB Posted

Attached to
Y1LZ--693-222 | Parking Structure Solicitation Amendment 2
Solicitation number
36C24420R0075
Issued by

About this file

This document contains a federal solicitation for the construction of a parking garage project at the Wilkes-Barre VA Medical Center. The solicitation seeks offers for all labor, materials, equipment, permits, testing and reports required to construct a new 435-space parking structure according to provided drawings and specifications. Offerors must meet requirements outlined in the attached statement of work, specifications, drawings and comply with all federal, state and local codes and VA rules. The project magnitude is between $10-20 million. It is a small business set-aside for verified service-disabled veteran-owned small businesses, to be evaluated using tiered procedures including large businesses. The contractor must properly classify worker titles and comply with applicable wage and hour laws. Pricing must be in whole dollars. The solicitation may be canceled before award if in the best interest of the government. The Department of Veterans Affairs Veterans Health Administration VISN 4 is the issuing agency.

View the file

Other files

File Type Posted
Parking Garage Arch Dwgs Add 1.pdf PDF
A6.2 Signage.pdf PDF
015000TempFacilitiesControls.pdf PDF
VMAC_Sketch_SKE-1.pdf PDF
084113 Aluminum Storefront Systems.pdf PDF
057200 Ornamental Fence and Gates.pdf PDF
097753 Living Wall System.pdf PDF
019100 Gen Commis.docx DOCX document
013526 Safety Requirements.docx DOCX document
S02 36C24420R0075 Amend 2.pdf PDF
S02 Q_A Parking Structure Solicit.pdf PDF
S02 Pricing Sheet.pdf PDF
36C24420R0075_6.docx DOCX document
010000 General.docx DOCX document
024100 Demolition.docx DOCX document
150002002 - VAMC Wilkes-Barre Parking Structure FINAL Geotechnical Report 11-30-15.pdf PDF
095113 Acoustical Panel Ceilings.pdf PDF
014535 Special Inspections.docx DOCX document
017419 Const Waste Mgmt.doc DOC document
022113 Site Surveys.docx DOCX document
087100 Door Hardware.pdf PDF
107300 Exterior Canopy System.pdf PDF
015719 Temp Envir Cont.doc DOC document
013323 Shop dwgs Product Data.docx DOCX document
015816 Temp Int Signage.docx DOCX document
042000 Unit Masonry Assemblies.pdf PDF
074515 Composite Wall Panel.pdf PDF
014219 Reference Standards.docx DOCX document
014500 Quality Control.docx DOCX document
S02 Solicitation 36C24420R0075 AMD 0001.pdf PDF
EXHIBIT D -SampleTransmittalLetter Past Performance Evaluation Questionnaire.docx DOCX document
36C24420R0075_5.docx DOCX document
EXHIBIT E PastPerformanceQuestionnaire.docx DOCX document
36C24420R0075_4.docx DOCX document
P03 JA Tyco SimplexGrinnell.pdf PDF
P03 JA Yale Lock.pdf PDF
S04 Site Visit Sign-in.pdf PDF
P03 JA Johnson Controls.pdf PDF
075323 EPDM Single-Ply Membrane Roofing.pdf PDF
014500.docx DOCX document
071113 Bituminous Dampproofing.pdf PDF
034133 Precast Structural Pretensioned Concrete.pdf PDF
264313.pdf PDF
017900 Warranties_Single Prime.pdf PDF
S02 Dwg S3-S5.pdf PDF
012700 Cutting and Patching_Single Prime.pdf PDF
061000 Rough Carpentry.pdf PDF
111200 Parking Control Equipment.pdf PDF
012800 Field Engineering_Single Prime.pdf PDF
210512.pdf PDF
Show 40 more

Latest 50 of 165 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Parking Garage Project Number 693-222 Department of Veterans Affairs Wilkes-Barre, Pennsylvania

262726 - 1

SECTION 26 27 26 - WIRING DEVICES

PART 1 - GENERAL

1.1 DESCRIPTION

A. This section specifies the furnishing, installation, connection, and testing of wiring devices.

1.2 RELATED WORK

A. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: General electrical requirements that are common to more than one section of Division 26.

B. Section 26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS: Conduit and boxes.

C. Section 26 05 19, LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES: Cables and wiring.

D. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS:

Requirements for personnel safety and to provide a low impedance path to ground for possible ground fault currents.

E. Section 26 51 00, INTERIOR LIGHTING: LED drivers for use with manual dimming controls.

1.3 QUALITY ASSURANCE

A. Refer to Paragraph, QUALIFICATIONS (PRODUCTS AND SERVICES), in Section 26

05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS.

1.4 SUBMITTALS

A. Submit six copies of the following in accordance with Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS.

1. Shop Drawings:

a. Submit sufficient information to demonstrate compliance with drawings and specifications.

b. Include electrical ratings, dimensions, mounting details, construction materials, grade, and termination information.

2. Manuals:

Wilkes-Barre, Pennsylvania

262726 - 2

a. Submit, simultaneously with the shop drawings, companion copies of complete maintenance and operating manuals, including technical data sheets and information for ordering replacement parts.

b. If changes have been made to the maintenance and operating manuals originally submitted, submit updated maintenance and operating manuals two weeks prior to the final inspection.

3. Certifications: Two weeks prior to final inspection, submit the following.

a. Certification by the manufacturer that the wiring devices conform to the requirements of the drawings and specifications.

b. Certification by the Contractor that the wiring devices have been properly installed and adjusted.

1.5 APPLICABLE PUBLICATIONS

A. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by basic designation only.

B. National Fire Protection Association (NFPA):

70-11 .....................................National Electrical Code (NEC)

99-12 .....................................Health Care Facilities

C. National Electrical Manufacturers Association (NEMA):

WD 1-10 ................................General Color Requirements for Wiring Devices

WD 6-08 ...............................Wiring Devices – Dimensional Specifications

D. Underwriter’s Laboratories, Inc. (UL):

5-11 .......................................Surface Metal Raceways and Fittings

20-10 .....................................General-Use Snap Switches

231-07 ...................................Power Outlets

467-07 ...................................Grounding and Bonding Equipment

498-07 ...................................Attachment Plugs and Receptacles

943-11 ...................................Ground-Fault Circuit-Interrupters

1449-07 .................................Surge Protective Devices

1472-96 .................................Solid State Dimming Controls

Wilkes-Barre, Pennsylvania

262726 - 3

PART 2 - PRODUCTS

2.1 RECEPTACLES

A. General: All receptacles shall comply with NEMA, NFPA, UL, and as shown on the drawings.

1. Mounting straps shall be plated steel, with break-off plaster ears and shall include a self-grounding feature. Terminal screws shall be brass, brass plated or a copper alloy metal.

2. Receptacles shall have provisions for back wiring with separate metal clamp type terminals (four minimum) and side wiring from four captively held binding screws.

B. Duplex Receptacles: single phase, 20 ampere, 120 volts, 2-pole, 3-wire, NEMA 5-20R, with break-off feature for two-circuit operation.

1. Bodies shall be ivory in color.

2. Switched duplex receptacles shall be wired so that only the top receptacle is switched. The lower receptacle shall be unswitched.

3. Duplex Receptacles on Emergency Circuit:

a. In rooms without emergency powered general lighting, the emergency receptacles shall be of the self-illuminated type.

4. Ground Fault Interrupter Duplex Receptacles: Shall be an integral unit, hospital-grade, suitable for mounting in a standard outlet box, with end-of-life indication and provisions to isolate the face due to improper wiring.

a. Ground fault interrupter shall consist of a differential current transformer, solid state sensing circuitry and a circuit interrupter switch. Device shall have nominal sensitivity to ground leakage current of 4-6 milliamperes and shall function to interrupt the current supply for any value of ground leakage current above five milliamperes (+ or – 1 milliampere) on the load side of the device. Device shall have a minimum nominal tripping time of 0.025 second.

C. Receptacles; 20, 30, and 50 ampere, 250 Volts: Shall be complete with appropriate cord grip plug.

D. Weatherproof Receptacles: Shall consist of a duplex receptacle, mounted in box with a gasketed, weatherproof, cast metal cover plate and cap over each receptacle opening.

The cap shall be permanently attached to the cover plate by a spring-hinged flap. The weatherproof integrity shall not be affected when heavy duty specification or hospital grade attachment plug caps are inserted. Cover plates on outlet boxes mounted flush in the wall shall be gasketed to the wall in a watertight manner.

Wilkes-Barre, Pennsylvania

262726 - 4

2.2 TOGGLE SWITCHES

A. Toggle switches shall be totally enclosed tumbler type with nylon bodies. Handles shall be ivory in color unless otherwise specified or shown on the drawings.

1. Switches installed in hazardous areas shall be explosion-proof type in accordance with the NEC and as shown on the drawings.

2. Shall be single unit toggle, butt contact, quiet AC type, heavy-duty general-purpose use with an integral self grounding mounting strap with break-off plasters ears and provisions for back wiring with separate metal wiring clamps and side wiring with captively held binding screws.

3. Switches shall be rated 20 amperes at 120-277 Volts AC.

2.3 WALL PLATES

A. Wall plates for switches and receptacles shall be type smooth nylon. Oversize plates are not acceptable.

B. Color shall be ivory unless otherwise specified.

C. For receptacles or switches mounted adjacent to each other, wall plates shall be common for each group of receptacles or switches.

E. Duplex Receptacles on Emergency Circuit: Wall plates shall be red nylon with the word "EMERGENCY" engraved in 1/4 inch white letters

5. Fire Rating: Unit is listed and labeled for fire rating of floor-ceiling assembly.

6. Cover plate shall be metal with finish selected by the architect.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Installation shall be in accordance with the NEC and as shown as on the drawings.

B. Install wiring devices after wall construction and painting is complete.

C. The ground terminal of each wiring device shall be bonded to the outlet box with an approved green bonding jumper, and also connected to the branch circuit equipment grounding conductor.

D. Outlet boxes for toggle switches and manual dimming controls shall be mounted on the strike side of doors.

E. Provide barriers in multigang outlet boxes to comply with the NEC.

F. Coordinate the electrical work with the work of other trades to ensure that wiring device flush outlets are positioned with box openings aligned with the face of the surrounding

Wilkes-Barre, Pennsylvania

262726 - 5 finish material. Pay special attention to installations in cabinet work, and in connection with laboratory equipment.

G. Exact field locations of floors, walls, partitions, doors, windows, and equipment may vary from locations shown on the drawings. Prior to locating sleeves, boxes and chases for roughing-in of conduit and equipment, the Contractor shall coordinate exact field location of the above items with other trades.

H. Install wall switches 46 inches above floor, with the toggle OFF position down.

I. Install wall dimmers 46 inches above floor.

J. Install receptacles 18 inches above floor, and 6 inches above counter backsplash or workbenches. Install specific-use receptacles at heights shown on the drawings.

K. Install vertically mounted receptacles with the ground pin up. Install horizontally mounted receptacles with the ground pin to the right.

L. When required or recommended by the manufacturer, use a torque screwdriver. Tighten unused terminal screws.

M. Label device plates with a permanent adhesive label listing panel and circuit feeding the wiring device.

3.2 ACCEPTANCE CHECKS AND TESTS

A. Perform manufacturer’s required field checks in accordance with the manufacturer's recommendations. In addition, include the following:

1. Visual Inspection and Tests:

a. Inspect physical and electrical condition.

b. Vacuum-clean surface metal raceway interior. Clean metal raceway exterior.

c. Test wiring devices for damaged conductors, high circuit resistance, poor connections, inadequate fault current path, defective devices, or similar problems using a portable receptacle tester. Correct circuit conditions, remove malfunctioning units and replace with new, and retest as specified above.

d. Test GFCI receptacles.

- - - END OF SECTION - - -

File details come from the government source that posted it. Updated .