This solicitation is for renovation services at two primary care buildings at a Veterans Affairs medical center. Key requirements include architectural, structural, and MEP design and construction services to upgrade exam rooms, offices, waiting areas, and support spaces. Bidders must have experience in healthcare facility renovations. The work will be conducted in phases to minimize disruptions to ongoing medical operations. The award is a fixed-price contract with a one year period of performance. The solicitation includes specifications for various systems and components.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EWC

GFI

WP/GFI

WP/GFI

J

DH

J

M

"T-X"

PAN. " "

PAN. " "

SYMBOL DESCRIPTION

POWER LEGEND

20 AMP, 125 VOLT, DUPLEX GROUNDING TYPE RECEPTACLE. HUBBELL #HBLB300I (HOSPITAL GRADE). PROVIDE TAMPER RESISTANT RECEPTACLES HUBBELL #BL8300-SGLA IN ALL PEDIATRIC/ PSYCHIATRIC OR PUBLIC ACCESSIBLE AREAS (I.E. PATIENT ROOMS, CORRIDORS, NURSES STATIONS, WAITING ROOMS, ETC.). SEE SPECIFICATIONS TO DETERMINE WHERE EACH TYPE IS REQUIRED. MOUNT AT 18" AFF TO CENTERLINE UNLESS OTHERWISE NOTED. WHERE SUBSCRIPT "R" OCCURS, RECEPTACLE TO BE COLORED RED AND TO BE SERVED BY ESSENTIAL POWER. WHERE SUBSCRIPT "C" OCCURS, RECEPTACLE TO MOUNTED ABOVE COUNTERTOP.

20 AMP, 125 VOLT, DUPLEX GROUND FAULT INTERRUPTER TYPE RECEPTACLE FOR ELECTRIC WATER COOLER.

HUBBELL #GFR8300HILA (HOSPITAL GRADE). LOCATE PER WATER COOLER SUPPLIER'S SHOP DRAWINGS.

20 AMP, 125 VOLT, DUPLEX GROUND FAULT INTERRUPTER TYPE RECEPTACLE. HUBBELL #GFR8300HILA (HOSPITAL GRADE). PROVIDE TAMPER RESISTANT RECEPTACLES HUBBELL #HBL8300-SGLA IN IN ALL PEDIATRIC/ PSYCHIATRIC PATIENT OR PUBLIC ACCESSIBLE AREAS (I.E. PATIENT ROOMS, CORRIDORS, NURSES STATIONS, WAITING ROOMS, ETC.). SEE SPECIFICATIONS TO DETERMINE WHERE EACH TYPE IS REQUIRED. MOUNT AT 24" AFG TO CENTERLINE UNLESS OTHERWISE NOTED. WHERE SUBSCRIPT "R" OCCURS, RECEPTACLE TO BE COLORED RED AND TO BE SERVED BY ESSENTIAL POWER. WHERE SUBSCRIPT "C" OCCURS, RECEPTACLE TO MOUNTED ABOVE COUNTERTOP.

20 AMP, 125 VOLT, TAMPER RESISTANT DUPLEX GROUND FAULT INTERRUPTER TYPE RECEPTACLE. HUBBELL #GFTR201 (HOSPITAL GRADE). WITH WEATHERPROOF "IN-USE" COVERPLATE. MOUNT VERTICALLY AT 24" AFG TO CENTERLINE UNLESS OTHERWISE NOTED. WHERE SUBSCRIPT "R" OCCURS, RECEPTACLE TO BE COLORED RED

AND TO BE SERVED BY ESSENTIAL POWER.

DOT INDICATES NEW 20A, 125 VOLT, DUPLEX GROUNDING TYPE RECEPTACLE. HUBBELL #HBL5362I INSTALLED IN EXISTING RECESSED BOX. RECONNECT TO NEW OR EXISTING BRANCH CIRCUIT WIRING. PROVIDE NEW

COVERPLATE AS SPECIFIED.

TWO 20 AMP, 125 VOLT, DUPLEX GROUNDING TYPE RECEPTACLES. HUBBELL #HBL5362I (HOSPITAL GRADE).

PROVIDE TAMPER RESISTANT RECEPTACLES HUBBELL #HBL8300-SGLA IN ALL PEDIATRIC/ PSYCHIATRIC PATIENT OR PUBLIC ACCESSIBLE AREAS (I.E. PATIENT ROOMS, CORRIDORS, NURSES STATIONS, WAITING ROOMS, ETC.). SEE SPECIFICATIONS TO DETERMINE WHERE EACH TYPE IS REQUIRED. MOUNT IN COMMON BOX WITH COMMON PLATE AT 18" AFF TO CENTERLINE UNLESS OTHERWISE NOTED. WHERE SUBSCRIPT "R" OCCURS, RECEPTACLE TO BE COLORED RED AND TO BE SERVED BY ESSENTIAL POWER. WHERE SUBSCRIPT "C" OCCURS, RECEPTACLE TO

MOUNTED ABOVE COUNTERTOP.

20 AMP, 125 VOLT, DUPLEX GROUNDING TYPE RECEPTACLE. HUBBELL #HBL8300I (HOSPITAL GRADE). PROVIDE TAMPER RESISTANT RECEPTACLES HUBBELL #HBL8300-SGLA IN ALL PEDIATRIC/ PSYCHIATRIC OR PUBLIC ACCESSIBLE AREAS (I.E. PATIENT ROOMS, CORRIDORS, NURSES STATIONS, WAITING ROOMS, ETC.). SEE SPECIFICATIONS TO DETERMINE WHERE EACH TYPE IS REQUIRED. SURFACE MOUNT AT 18" AFF TO CENTERLINE UNLESS OTHERWISE NOTED. WHERE SUBSCRIPT "R" OCCURS, RECEPTACLE TO BE COLORED RED AND TO BE SERVED BY ESSENTIAL POWER. WHERE SUBSCRIPT "C" OCCURS, RECEPTACLE TO MOUNTED ABOVE

COUNTERTOP.

20 AMP, 125 VOLT, DUPLEX GROUND FAULT INTERRUPTER TYPE RECEPTACLE. HUBBELL #GFTR201 (HOSPITAL GRADE). WITH WEATHERPROOF "IN-USE" COVERPLATE. SURFACE MOUNT AT 18" AFF TO CENTERLINE UNLESS OTHERWISE NOTED. WHERE SUBSCRIPT "R" OCCURS, RECEPTACLE TO BE COLORED

RED AND TO BE SERVED BY ESSENTIAL POWER.

TWO 20 AMP, 125 VOLT, DUPLEX GROUNDING TYPE RECEPTACLES. HUBBELL #HBL8300I (HOSPITAL GRADE).

PROVIDE TAMPER RESISTANT RECEPTACLES HUBBELL #HBL8300-SGLA IN ALL PEDIATRIC/ PSYCHIATRIC OR PUBLIC ACCESSIBLE AREAS (I.E. PATIENT ROOMS, CORRIDORS, NURSES STATIONS, WAITING ROOMS, ETC.). SEE SPECIFICATIONS TO DETERMINE WHERE EACH TYPE IS REQUIRED. SURFACE MOUNT IN COMMON BOX WITH COMMON PLATE AT 18" AFF TO CENTERLINE UNLESS OTHERWISE NOTED. WHERE SUBSCRIPT "R" OCCURS, RECEPTACLE TO BE COLORED RED AND TO BE SERVED BY ESSENTIAL POWER. WHERE SUBSCRIPT "C" OCCURS, RECEPTACLE TO MOUNTED ABOVE COUNTERTOP.

SPECIAL PURPOSE OUTLET. REFER TO DRAWINGS FOR DESCRIPTION. VERIFY EXACT LOCATION WITH ARCHITECT PRIOR TO ROUGH-IN. WHERE SUBSCRIPT "R" OCCURS, RECEPTACLE TO BE COLORED RED AND TO BE SERVED BY ESSENTIAL POWER. WHERE SUBSCRIPT "C" OCCURS, RECEPTACLE TO MOUNTED ABOVE

COUNTERTOP.

STANDARD STEEL JUNCTION BOX WITH COVER. LOCATE AND CONNECT AS DIRECTED. SUBSCRIPT INDICATES

EQUIPMENT SERVED.

F - FURNITURE SYSTEM FEED (REFER TO TELECOM DETAILS)

LTG - LIGHTING

LTG/EM - EMERGENCY LIGHTING

SEC - SECURITY

PS - POWER SUPPLY

MAGNETIC DOOR HOLDER FURNISHED BY GENERAL TRADES CONTRACTOR BUT INSTALLED AND WIRED BY ELECTRICAL CONTRACTOR. TIE INTO FIRE ALARM SYSTEM AS DIRECTED BY EQUIPMENT SUPPLIER. VERIFY

EXACT LOCATION WITH ARCHITECT PRIOR TO ROUGH-IN.

POINT OF CONNECTION TO ELECTRIFIED EQUIPMENT. VERIFY EXACT LOCATION WITH RESPECTIVE

EQUIPMENT SUPPLIER PRIOR TO ROUGH-IN. SUBSCRIPT INDICATES EQUIPMENT SERVED.

MOTOR FURNISHED AND INSTALLED BY OTHERS, WIRED BY ELECTRICAL CONTRACTOR. CONNECT AS DIRECTED BY

MOTOR SUPPLIER. SUBSCRIPT INDICATES EQUIPMENT SERVED.

EF - EXHAUST FAN

MOD - MOTOR OPERATED DAMPER

SD - SMOKE DAMPER

FUSIBLE DISCONNECT SWITCH, HEAVY DUTY TYPE, (UNLESS NOTED OTHERWISE ON DRAWINGS) COMPLETE WITH FUSETRONS SIZED TO PROTECT MOTOR, EQUIPMENT OR CONDUCTORS (WHICHEVER IS APPLICABLE). SIZE, POLES, AND TYPE AS INDICATED. HORSEPOWER RATED, QUICK-MAKE, QUICK-BREAK.

PUSH BUTTON. REFER TO DRAWINGS AND/OR SPECIFICATIONS FOR DETAILS.

TRANSFORMER. SIZE AND TYPE AS NOTED ON DRAWINGS AND/OR TRANSFORMER SCHEDULE.

208/120V,3∅,4W PANELBOARD. REFER TO PANELBOARD SCHEDULE AND/OR SPECIFICATIONS FOR DETAILS.

480/277V,3∅,4W PANELBOARD. REFER TO PANELBOARD SCHEDULE AND/OR SPECIFICATIONS FOR DETAILS.

MANUAL MOTOR STARTER WITH NEON PILOT LIGHT. ALLEN-BRADLEY #600TQX216. MOUNT AT 46" AFF TO

CENTERLINE UNLESS OTHERWISE NOTED.

MANUAL MOTOR STARTER WITH NEON PILOT LIGHT. ALLEN-BRADLEY #600TAX216. SURFACE MOUNT IN 4" SQUARE BOX WITH EXPOSED WORK COVER AT 46" AFF TO CENTERLINE UNLESS OTHERWISE NOTED.

DOT INDICATES NEW 20 AMP SWITCH INSTALLED IN EXISTING RECESSED BOX. RECONNECT TO NEW OR EXISTING

BRANCH CIRCUIT WIRING. PROVIDE NEW COVERPLATE AS SPECIFIED.

L-1 - LIFT

P-103 - ELECTRONIC FLUSH VALVE. REFER TO MECHANICAL DRAWINGS AND ELECTRONIC TOILET/SINK DETAIL

FOR MORE INFORMATION.

P-418 - ELECTRONIC FAUCET. REFER TO MECHANICAL DRAWINGS AND ELECTRONIC TOILET/SINK DETAIL FOR

MORE INFORMATION.

P-528 - ELECTRONIC FAUCET. REFER TO MECHANICAL DRAWINGS AND ELECTRONIC TOILET/SINK DETAIL FOR

MORE INFORMATION.

AD-1 - AUTOMATIC SLIDING DOOR (120V).

A

A

FX

E

N

S

SR

S

SYMBOL DESCRIPTION

GENERAL LEGEND

EXPOSED BRANCH CIRCUIT HOMERUN. FOR NORMAL BRANCH CIRCUIT WIRING, CONTRACTOR MAY COMBINE UP TO THREE HOMERUNS IN ONE RACEWAY ON A WYE SYSTEM AND TWO HOMERUNS IN ONE RACEWAY ON A DELTA SYSTEM. QUANTITY OF MARKS INDICATE NUMBER OF CONDUCTORS. #12 AWG MINIMUM SIZE CONDUCTORS UNLESS NOTED OTHERWISE. ALL RACEWAYS TO CONTAIN SEPARATE EQUIPMENT GROUNDING CONDUCTOR. ALL BRANCH CIRCUITS SHALL HAVE SEPARATE NEUTRAL CONDUCTOR. NEUTRAL CONDUCTOR SHALL NOT BE SHARED BETWEEN

CIRCUITS. REFER TO SPECIFICATIONS FOR RACEWAY TYPE.

CONCEALED BRANCH CIRCUIT HOMERUN. FOR NORMAL BRANCH CIRCUIT WIRING, CONTRACTOR MAY COMBINE UP TO THREE HOMERUNS IN ONE RACEWAY ON A WYE SYSTEM AND TWO HOMERUNS IN ONE RACEWAY ON A DELTA SYSTEM. QUANTITY OF MARKS INDICATE NUMBER OF CONDUCTORS. #12 AWG MINIMUM SIZE CONDUCTORS UNLESS NOTED OTHERWISE. ALL RACEWAYS TO CONTAIN SEPARATE EQUIPMENT GROUNDING CONDUCTOR. ALL BRANCH CIRCUITS SHALL HAVE SEPARATE NEUTRAL CONDUCTOR. NEUTRAL CONDUCTOR SHALL NOT BE SHARED BETWEEN

CIRCUITS. REFER TO SPECIFICATIONS FOR RACEWAY TYPE.

RACEWAY UP. QUANTITY OF MARKS INDICATE NUMBER OF CONDUCTORS. #12 AWG MINIMUM SIZE CONDUCTOR UNLESS NOTED OTHERWISE. ALL RACEWAYS TO CONTAIN SEPARATE EQUIPMENT GROUNDING CONDUCTOR.

ALL BRANCH CIRCUITS SHALL HAVE SEPARATE NEUTRAL CONDUCTOR. NEUTRAL CONDUCTOR SHALL NOT BE

SHARED BETWEEN CIRCUITS. REFER TO SPECIFICATIONS FOR RACEWAY TYPE.

RACEWAY DOWN. QUANTITY OF MARKS INDICATE NUMBER OF CONDUCTORS. #12 AWG MINIMUM SIZE CONDUCTOR UNLESS NOTED OTHERWISE. ALL RACEWAYS TO CONTAIN SEPARATE EQUIPMENT GROUNDING CONDUCTOR. ALL BRANCH CIRCUITS SHALL HAVE SEPARATE NEUTRAL CONDUCTOR. NEUTRAL CONDUCTOR

SHALL NOT BE SHARED BETWEEN CIRCUITS. REFER TO SPECIFICATIONS FOR RACEWAY TYPE.

FLEXIBLE METAL CONDUIT OR LIQUIDTIGHT FLEXIBLE METAL CONDUIT (REFER TO SPECIFICATIONS) AND WIRING.

QUANTITY OF MARKS INDICATE NUMBER OF CONDUCTORS. #12 AWG MINIMUM SIZE CONDUCTOR UNLESS OTHERWISE NOTED. ALL RACEWAYS TO CONTAIN SEPARATE EQUIPMENT GROUNDING CONDUCTOR. ALL BRANCH CIRCUITS SHALL HAVE SEPARATE NEUTRAL CONDUCTOR. NEUTRAL CONDUCTOR SHALL NOT BE

SHARED BETWEEN CIRCUITS. REFER TO SPECIFICATIONS FOR RACEWAY TYPE.

RACEWAY AND CONDUCTORS CONCEALED ABOVE CEILING OR IN WALL AT ELECTRICAL CONTRACTOR'S OPTION.

QUANTITY OF MARKS INDICATE NUMBER OF CONDUCTORS. #12 AWG MINIMUM SIZE CONDUCTOR UNLESS OTHERWISE NOTED. ALL RACEWAYS TO CONTAIN SEPARATE EQUIPMENT GROUNDING CONDUCTOR. ALL BRANCH CIRCUITS SHALL HAVE SEPARATE NEUTRAL CONDUCTOR. NEUTRAL CONDUCTOR SHALL NOT BE

SHARED BETWEEN CIRCUITS. REFER TO SPECIFICATIONS FOR RACEWAY TYPE.

RACEWAY AND CONDUCTORS RUN EXPOSED ON CEILINGS OR WALLS. QUANTITY OF MARKS INDICATE NUMBER OF CONDUCTORS. #12 AWG MINIMUM SIZE CONDUCTOR UNLESS OTHERWISE NOTED. ALL RACEWAYS TO CONTAIN SEPARATE EQUIPMENT GROUNDING CONDUCTOR. ALL BRANCH CIRCUITS SHALL HAVE SEPARATE NEUTRAL CONDUCTOR. NEUTRAL CONDUCTOR SHALL NOT BE SHARED BETWEEN CIRCUITS. REFER TO

SPECIFICATIONS FOR RACEWAY TYPE.

EMERGENCY POWER SYSTEM CONDUIT AND WIRING. QUANTITY OF MARKS INDICATE NUMBER OF CONDUCTORS. # 12 AWG MINIMUM SIZE CONDUCTOR UNLESS OTHERWISE NOTED. ALL RACEWAYS TO CONTAIN SEPARATE EQUIPMENT GROUNDING CONDUCTOR. ALL BRANCH CIRCUITS SHALL HAVE SEPARATE NEUTRAL CONDUCTOR.

NEUTRAL CONDUCTOR SHALL NOT BE SHARED BETWEEN CIRCUITS. REFER TO SPECIFICATIONS FOR RACEWAY

TYPE.

NURSES CALL SYSTEM CONDUIT AND WIRING. REFER TO NURSE CALL SYSTEM CABLE LEGEND FOR WIRE AND

CABLE DETAILS. REFER TO SPECIFICATIONS FOR RACEWAY TYPE.

SPEAKER OR SOUND SYSTEM CONDUIT AND WIRING. REFER TO SPEAKER OR SOUND SYSTEM CABLE LEGEND

FOR WIRE AND CABLE DETAILS. REFER TO SPECIFICATIONS FOR RACEWAY TYPE.

SURFACE METAL RACEWAY. QUANTITY OF MARKS INDICATE NUMBER OF CONDUCTORS, #12 AWG MINIMUM SIZE CONDUCTOR UNLESS OTHERWISE NOTED. ALL BRANCH CIRCUITS SHALL HAVE SEPARATE NEUTRAL CONDUCTOR. NEUTRAL CONDUCTOR SHALL NOT BE SHARED BETWEEN CIRCUITS. ALL RACEWAYS TO CONTAIN

SEPARATE EQUIPMENT GROUNDING CONDUCTOR.

BRANCH CIRCUIT UNDER FLOOR SLAB, UNDERGROUND OR ABOVE ACCESSIBLE CEILING OF FLOOR BELOW.

QUANTITY OF MARKS INDICATES NUMBER OF CONDUCTORS. ALL BRANCH CIRCUITS SHALL HAVE SEPARATE NEUTRAL CONDUCTOR. NEUTRAL CONDUCTOR SHALL NOT BE SHARED BETWEEN CIRCUITS. ALL RACEWAYS TO

CONTAIN SEPARATE EQUIPMENT GROUNDING CONDUCTORS.

ALL ITEMS SHOWN DASHED ON DEMOLITION PLANS TO BE REMOVED (UNLESS OTHERWISE NOTED).

CONDUIT SLEEVE. SIZE AND QUANTITY AS NOTED.

INDICATES POINT WHERE CONDUIT RUN TURNS UPWARD. OBSERVE CONDUIT BEND RADIUS AND OTHER REQUIREMENTS

OUTLINED IN DETAILS AND SPECIFICATIONS. SIZE AS NOTED.

INDICATES POINT WHERE CONDUIT RUN TURNS DOWNWARD. OBSERVE CONDUIT BEND RADIUS AND OTHER

REQUIREMENTS OUTLINED IN DETAILS AND SPECIFICATIONS. SIZE AS NOTED.

M M

FACP

TS

J

FS

J

SYMBOL DESCRIPTION

FIRE ALARM LEGEND

MANUAL FIRE ALARM SENDING STATION. REFER TO SPECIFICATIONS FOR DETAILS. MOUNT AT 46" AFF

TO CENTERLINE UNLESS OTHERWISE NOTED.

FIRE ALARM SYSTEM AUTOMATIC DETECTOR. REFER TO SPECIFICATIONS FOR DETAILS. SUBSCRIPT INDICATES TYPE.

SMD - SMOKE DETECTOR, DUCT TYPE COMPLETE WITH SAMPLING TUBES AND REMOTE KEY TEST SWITCH INDICATOR LIGHT. INSTALL IN AIR HANDLING UNIT OR DUCT AS RECOMMENDED BY RESPECTIVE MANUFACTURER AND

COORDINATE INSTALLATION WITH MECHANICAL CONTRACTOR.

SMP - SMOKE DETECTOR, PHOTOELECTRIC TYPE, CEILING MOUNTED.

FIRE ALARM SYSTEM ALARM SPEAKER WITH STROBE LIGHT. REFER TO SPECIFICATIONS FOR DETAILS. MOUNT AT 82" AFF TO CENTERLINE UNLESS OTHERWISE NOTED. SUBSCRIPT "V" INDICATES VISUAL ONLY ALARM SIGNAL.

FIRE ALARM SYSTEM ZONE ADDRESSABLE MODULE (MONITOR TYPE). REFER TO SPECIFICATIONS FOR DETAILS.

FIRE ALARM SYSTEM CONTROL PANEL. REFER TO SPECIFICATIONS FOR DETAILS.

SPRINKLER SYSTEM TAMPER SWITCH. FURNISHED AND INSTALLED BY FIRE PROTECTION CONTRACTOR, CONNECTED TO FIRE ALARM SYSTEM BY ELECTRICAL CONTRACTOR. VERIFY LOCATION WITH EQUIPMENT

SUPPLIER PRIOR TO ROUGH-IN.

SPRINKLER SYSTEM FLOW SWITCH. FURNISHED AND INSTALLED BY FIRE PROTECTION CONTRACTOR, CONNECTED TO FIRE ALARM SYSTEM BY ELECTRICAL CONTRACTOR. VERIFY LOCATION WITH EQUIPMENT

SUPPLIER PRIOR TO ROUGH-IN.

FAAP FIRE ALARM ANNUNCIATOR PANEL. REFER TO SPECIFICATIONS FOR DETAILS.

FAEP FIRE ALARM EXTENDER/BOOSTER PANEL. REFER TO SPECIFICATIONS FOR MORE INFORMATION.

N SP

N B

N D

N ST

NCMS

NCMS

RM

SYMBOL DESCRIPTION

NURSE CALL LEGEND

NURSE CALL SYSTEM SINGLE PATIENT STATION. REFER TO SPECIFICATIONS FOR DETAILS.

NURSE CALL SYSTEM BED INTERFACE UNIT. REFER TO SPECIFICATIONS FOR DETAILS.

NURSE CALL SYSTEM DUTY STATION. MOUNT AT 60" AFF TO CENTERLINE UNLESS OTHERWISE NOTED. REFER

TO SPECIFICATIONS FOR DETAILS.

NURSE CALL SYSTEM STAFF STATION. MOUNT AT 60" AFF TO CENTERLINE UNLESS OTHERWISE NOTED. REFER

TO SPECIFICATIONS FOR DETAILS.

NURSE CALL SYSTEM MASTER STATION. REFER TO SPECIFICATIONS FOR DETAILS.

NURSE CALL SYSTEM REMOTE MASTER STATION. REFER TO SPECIFICATIONS FOR DETAILS.

NURSE CALL CORRIDOR DOME FOR EXAM ROOM. PROVIDE 4-11/16" SQUARE BOX WITH 2-GANG

PLASTER RING MOUNTED IN THE ACCESSIBLE CEILING TILE ABOVE THE ROOM DOOR. REFER TO DRAWINGS

AND/OR SPECIFICATIONS FOR DETAILS. "Z" DESIGNATION INDICATES ZONE INDICATION.

N T NURSE CALL SYSTEM TOILET STATION. MOUNT AT 48" AFF TO CENTERLINE UNLESS OTHERWISE NOTED. REFER TO

SPECIFICATIONS FOR DETAILS.

S

S3

S

OC

A

SYMBOL DESCRIPTION

LIGHTS/SWITCHES LEGEND

EXTRA HEAVY DUTY 20 AMP, SINGLE POLE SWITCH. HUBBELL #HBL1221. MOUNT AT 46" AFF TO CENTERLINE UNLESS OTHERWISE NOTED. WHERE SUBSCRIPT "R" OCCURS, SWITCH TO BE RED IN COLOR HUBBELL

#HBL1221R.

EXTRA HEAVY DUTY 20 AMP, THREE-WAY SWITCH. HUBBELL #HBL1223. MOUNT AT 46" AFF TO CENTERLINE

UNLESS OTHERWISE NOTED.

SINGLE-LEVEL SWITCH TYPE OCCUPANCY SENSOR. MOUNT AT 46" AFF TO CENTERLINE UNLESS

OTHERWISE NOTED. REFER LIGHTING CONTROL DIAGRAM DETAIL FOR MORE INFORMATION.

LIGHTING CONTROL REFERENCE TAG. REFER TO LIGHTING CONTROL DETAILS.

LED LIGHTING FIXTURES. REFER TO LIGHTING FIXTURE SCHEDULE FOR DETAILS.

EXISTING LIGHT FIXTURES TO BE REINSTALLED IN NEW LOCATIONS. REFER TO FLOOR PLANS FOR

ADDITIONAL INFORMATION.

CEILING OR WALL MOUNTED SINGLE FACE EXIT SIGN. SHADED AREA INDICATES LOCATION OF FACE(S).

ARROWS INDICATE CHEVRONS.

CEILING MOUNTED OCCUPANCY SENSOR. REFER TO LIGHTING CONTROL DIAGRAM FOR MORE INFORMATION.OC1

DIMMER SWITCH. REFER TO LIGHTING CONTROL DETAIL FOR MORE INFORMATION.

SOCD

SINGLE-LEVEL SWITCH TYPE OCCUPANCY SENSOR WITH DIMMER. MOUNT AT 46" AFF TO CENTERLINE UNLESS OTHERWISE NOTED. REFER LIGHTING CONTROL DIAGRAM DETAIL FOR MORE INFORMATION.

CEILING MOUNTED OCCUPANCY SENSOR. REFER TO LIGHTING CONTROL DIAGRAM FOR MORE INFORMATION.OC2

20 AMP, SINGLE POLE SWITCH. HUBBELL #HBL1221LA. SURFACE MOUNT IN 4" SQUARE BOX WITH EXPOSED

WORK COVER AT 46" AFF TO CENTERLINE UNLESS OTHERWISE NOTED.

S

CR

SYMBOL DESCRIPTION

SECURITY AND PA SYSTEMS LEGEND

PA SYSTEM CEILING SPEAKER (VALCOM V-1020C) WITH BACKCAN/BRIDGE (VALCOM V-9916M). CONNECT TO TELECOM ROOM WITH HOME-RUN CAT3 CABLE (DO NOT DAISY-CHAIN SPEAKERS) TERMINATED ON WALL-MOUNTED

66-BLOCK. COORDINATE CONNECTION TO SYSTEM WITH OWNER'S OIT DEPT.

PHYSICAL ACCESS CONTROL (PACS) CARD READER. REFER TO PACS SPECIFICATIONS AND DETAILS.

VIDEO SURVEILLANCE SYSTEM (VSS) CEILING-MOUNTED INTERIOR CAMERA:

1. CAMERAS IN ACCESSIBLE CEILINGS REQUIRE NO CONDUIT/BOX ROUGH-IN UNLESS NOTED OTHERWISE.

2. FOR LOCATIONS IN INACCESSIBLE CEILING, PROVIDE FLUSH ROUND CEILING BACK BOX (COORDINATE EXACT

LOCATION WITH VSS SYSTEM VENDOR). EXTEND 1"C FROM OUTLET TO NEAREST ACCESSIBLE AREA ABOVE

FINISHED CEILING.

3. DEVICE PROVIDED AND INSTALLED BY SECURITY VENDOR. REFER TO VSS SYSTEM DETAILS, SYSTEMS FLOOR

PLANS AND SPECIFICATIONS FOR REQUIREMENTS PER SUBSCRIPT.

4. CABLING/OUTLET TO BE INSTALLED BY TELECOM CONTRACTOR. REFER TO TELECOM SYMBOL LEGEND, FLOOR PLANS, AND DETAILS FOR CABLING REQUIREMENTS.

5. ARROW INDICATES APPROXIMATE CENTER OF FIELD OF VIEW

6. SUBSCRIPT INDICATES CAMERA TYPE AS FOLLOWS (REFER TO WRITTEN SPECIFICATIONS FOR BASIS OF

DESIGN FOR EACH CAMERA TYPE):

SUBSCRIPT DESCRIPTION

2MP 2MP INTERIOR DOME

C #MP

SURFACE MOUNTED CAMERA.C

GENERAL NOTES

1. EC TO REFER TO FLOOR PLANS FOR PHASING OF WORK.

2. REFER TO TELECOM DRAWINGS FOR ADDITIONAL INFORMATION.

SYMBOL DESCRIPTION

ABBREVIATION LEGEND

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

"C" SUBSCRIPT "C" INDICATES DEVICE TO BE MOUNTED 8" ABOVE COUNTERTOP TO CENTERLINE.

CLG CEILING

EC ELECTRICAL CONTRACTOR

EM EMERGENCY

EMT GALVANIZED ELECTRIC METALLIC TUBING (THINWALL), UL LISTED

FBO FURNISHED BY OTHER TRADES, BUT INSTALLED AND WIRED BY ELECTRICAL CONTRACTOR.

FM FLUSH MOUNTED

FPC FIRE PROTECTION CONTRACTOR

GC GENERAL CONTRACTOR

GFI GROUND FAULT INTERRUPTER

GRC GALVANIZED, RIGID, HEAVY WALL CONDUIT, UL LISTED

LS LIFE SAFETY BRANCH CIRCUIT

MC MECHANICAL CONTRACTOR (HVAC)

MICRO MICROWAVE

MON MONITOR

N NORMAL BRANCH CIRCUIT

NIC NOT IN CONTRACT

NL NIGHT LIGHT

PAN PANELBOARD

PC PLUMBING CONTRACTOR

PVC CARLON PLASTIC CONDUIT, HEAVY WALL TYPE, POLYVINYL CHLORIDE, UL LISTED, SCHEDULE 40 UNLESS

NOTED OTHERWISE.

"R" SUBSCRIPT "R" INDICATES RED DEVICE CONNECTED TO EMERGENCY POWER.

REF REFRIGERATOR

TR TAMPER RESISTANT

UCF UNDERCOUNTER FREEZER

WP WEATHERPROOF

"X" SUBSCRIPT "X" BY SYMBOL INDICATES EXISTING ITEM TO REMAIN.

CR CRITICAL BRANCH CIRCUIT

AFC ABOVE FINISHED CEILING

UON UNLESS OTHERWISE NOTED

VAV VARIABLE AIR VOLUME

X

WAP

SYMBOL DESCRIPTION

TELECOM LEGEND

TELECOM OUTLET TO BE REMOVED DURING DEMOLITION PHASE. REMOVE FACE PLATE, JACK MODULES, AND

ASSOCIATED CABLES BACK TO TERMINATION PANEL IN TELECOM ROOM.

EXISTING TELECOM OUTLET TO REMAIN THROUGH PHASE. PROTECT JACK MODULES FROM CONSTRUCTION DUST

AND DEBRIS.

FLUSH TELECOM OUTLET. USE 5" SQUARE X 2-7/8" DEEP BACK BOX WITH REDUCER RING. REFER TO TELECOM OUTLET ROUGH-IN DETAIL. REDUCER RING SIZE, BOX MOUNTING HEIGHT, AND CONDUIT SIZE PER SUBSCRIPT AS

NOTED BELOW:

SUBSCRIPT #1 GANG/MOUNTING HEIGHT CONDUIT

W 1-GANG/48" AFF 1"C

2D THRU 4D 2-GANG/18" AFF 1-1/4"C

TV 2-GANG/ADJACENT TO TV PWR 1-1/4"C

SB-I 1-GANG/ADJACENT PC PWR 1-1/4"C

SB-O 1-GANG/ADJACENT TO SB PWR 1-1/4"C

SUBSCRIPT #2 (WHERE APPLICABLE):

##" OUTLET HEIGHT AFF TO CENTERLINE IN INCHES. THIS SUPERSEDES HEIGHT CITED FOR SUBSCRIPT #1

C INDICATES OUTLET TO BE LOCATED AT 8" ABOVE COUNTERTOP HEIGHT.

WIRELESS ACCESS POINT TELECOM OUTLET:

• FOR LOCATIONS IN ACCESSIBLE CEILINGS, "FLOAT" OUTLET ABOVE CEILING AT LOCATION INDICATED.

• FOR LOCATIONS IN INACCESSIBLE CEILING, PROVIDE FLUSH 2-GANG TELECOM TYPE BACK BOX WITH 2"

EXTENSION RING (FOR PLACING WAP OUTLET WITHIN) IN CEILING. EXTEND 1"C FROM OUTLET TO NEAREST

ACCESSIBLE AREA ABOVE FINISHED CEILING.

SUBSCRIPT #1

SUBSCRIPT #2

VIDEO SURVEILLANCE SYSTEM (VSS) CAMERA TELECOM OUTLET:

• REFER TO SYSTEM FLOOR PLANS FOR ASSOCIATED VSS CAMERA LOCATIONS.

• OUTLET TO "FLOAT" IN CEILING AT CAMERA LOCATION.

• FOR CAMERAS REQUIRING CONDUIT/BOX ROUGH-IN, PLACE OUTLET IN ACCESSIBLE CEILNG AT CONDUIT STUB

LOCATION.

REFER TO TELECOM DETAILS FOR CABLING REQUIREMENTS PER SUBSCRIPTS

VSS

TGB TELECOMMUNICATIONS GROUNDING BUSBAR (TGB). E.C. TO INSTALL PER DETAILS AND WRITTEN SPECIFICATIONS.

X

EXISTING TELECOM OUTLET TO BE DEMOLISHED IN A LATER PHASE.

FURNITURE SYSTEM TELECOM OUTLET. TELECOM OUTLET TO BE INSTALLED IN OPENING PROVIDED IN

FURNITURE SYSTEM AND DOES NOT REQUIRE CONDUIT/BOX ROUGH-IN.

FURNITURE SYSTEM TELECOM CABLING FEED-THRU BOX. USE 2-GANG OPEN BOX FRAME. EXTEND 2"C FROM BOX FRAME TO CEILING CABLE PATHWAY. MOUNTING HEIGHT TO MATCH ADJACENT FURNITURE SYSTEM POWER OUTLET

HEIGHT WHERE PRACTICABLE UON.

F J

SIGNATURE DATE

HATHAWAY

ST

ATE OF O

H IO

P R

O F

ESS IO N

AL E N G

IN

E E

R

R E G I S T E RE D

E-61777

MARLON

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

CONSTRUCTION - ISSUED FOR

BID

Project Number

Building Number

Drawing Number

340, 341

VA Building 340, 341 Project Title

Location

Issued Date Checked Drawn

Drawing Title Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

SCHEESER BUCKLEY MAYFIELD

1540 CORPORATE WOODS PARKWAY

UNIONTOWN, OHIO 44685

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

Approved:

PHILIP P. KIRK

CHIEF ENGINEER

2/

/2

2:

: 5

PM

C :\U se rs

\M Ky ag ab a\ D oc um en ts

\1

_M

EP

_C

E N

TR

AL

F

IL

E_ m ky ag ab a@ sb m c e

.c om

.rv t

EJ-100

552-20-104

MCH MSK

RENOVATE PRIMARY CARE FOR

PACT BLDG 340, BLDG 341

02/09/2021

4100 WEST THIRD STREET, DAYTON, OH 45428

ELECTRICAL GENERAL NOTES AND SYMBOL

LEGEND

02/09/2021

Revisions Date

CONSTRUCTION - ISSUED FOR BID 02/09/2021

LIGHTING CONTROL GENERAL NOTES

1. REFER TO FLOOR PLANS FOR QUANTITIES, WIRING AND SWITCHING ARRANGEMENTS.

2. REFER TO OCCUPANCY SENSOR MANUFACTURER'S WIRING DIAGRAMS FOR INSTALLATION

DRAWINGS.

3. FOR ALL OCCUPANCY SENSORS, TIME DELAY DIP SWITCH SETTINGS SHALL BE FOR 15

MINUTES, UNLESS DIRECTED OTHERWISE. WALL MOUNTED DEVICES SHALL HAVE DIP SWITCH

SETTINGS FOR MANUAL ON.

4. OCCUPANCY SENSORS SHALL BE PROVIDED AS SPECIFIED BY SENSOR SWITCH. EQUALS

SHALL BE MANUFACTURED BY WATTSTOPPER, TOUCHÉ CONTROLS, OR LEVITON. ALL

EQUIVALENT SYSTEMS SHALL PROVIDE ALL DEVICES, WIRING, AND COMPONENTS FOR A

COMPLETE INSTALLATION COMPARABLE TO SENSOR SWITCH.

5. EC IS RESPONSIBLE FOR PROPER COMMISSIONING OF ALL OCCUPANCY SENSORS.

COMMISSIONING SHALL BE PERFORMED ONCE ALL SPACES ARE OCCUPIED AND HVAC SYSTEM IS

PROPERLY BALANCED FOR AIR FLOW AND TEMPERATURE. COMMISSIONING SHALL INCLUDE A

ROOM-BY-ROOM 100% TEST OF EACH SENSOR IN A SHORT TIME-OUT TEST MADE TO ENSURE

SENSOR DETECTS HUMAN MOVEMENTS, NO AIR INTERFERENCE IS PRESENT, AND SENSOR

CANNOT DETECT MOVEMENT OUTSIDE OF CONTROLLED SPACE. INCLUDE ALL ADJUSTMENTS TO

SETTINGS AND MINOR RELOCATION OF DEVICES.

A

LIGHTING CONTROL TAG DETAIL

LIGHTING CONTROL

TAG FOR ROOM OR

SPACE.

PANEL

CIRCUIT #

N.T.S.

OR

Refer to floor plans for exact quantity and types of switches required.

A

LIGHTING CONTROL DIAGRAM #1

Lighting Load

Neutral White

Unswitched Hot Black

Lighting Load

Unswitched Hot Black

N.T.S.

LIGHTING CONTROL DIAGRAM #2

N.T.S.

SYMBOL " "

B

277V

WHITE

GROUND

NEUTRAL

NEUTRAL

GREEN

RED

BLACK

WHITE

(SEE INSTALLATION

INSTRUCTIONS)

120V GROUND

OC

Primary Load

SENSORSWITCH: PASSIVE

INFRARED WALL SWITCH

SENSOR #WSX-PDT.

OCD

Class 2 0-10V Control Wiring

LIGHTING CONTROL DIAGRAM #3

0-10V dimming driver required

White

Green

Black

Yellow

Ground

Neutral White

Unswitched Hot Black

Red

Gry Vio

Lighting Load

C

SENSORSWITCH: DUAL

TECHNOLOGY WALL

SWITCH SENSOR #WSX-

PDT-D-WH.

N.T.S.

LIGHTING CONTROL DIAGRAM #4

D

BLK

WHT

277V

NEUTRAL

CAT 6

RED/EM 277V

YLW/EM 120V

BLU/EM MVOLT

WHT-RED/EM NEUTRAL

VLT DIM COMMON

GRY DIM POSITIVE

BLU LINE OUTGRN

CAT 6

CAT 6 CAT 6

nCM-PDT-10

OCCUPANCY SENSOR

SENSOR SWITCH

J nCM-PDT-10

OCCUPANCY SENSOR

SENSOR SWITCH

FOR ADDITIONAL

POWER PACKS (IF

REQUIRED) IN WORK

SPACE, SEE PLANS

SYMBOL

SENSORSWITCH:

#nPP16-D POWER

PACK WITH MVOLT

INPUT.

SS

SENSORSWITCH:

#nPODM-DX-WH

SINGLE CHANNEL

DIMMER SWITCH.

OC1OC1

PP

N.T.S.

BLK

WHT

120V

NEUTRAL

RED/EM 277V

YLW/EM 120V

BLU/EM MVOLT

WHT-RED/EM NEUTRAL

VLT DIM COMMON

GRY DIM POSITIVE

BLU LINE OUTGRN

CAT 6

LIGHTING CONTROL DIAGRAM #5

N.T.S.

J

SYMBOL " "

E

SENSORSWITCH:

#nPODM-DX-WH

SINGLE CHANNEL

DIMMER SWITCH.

SYMBOL

SENSORSWITCH:

#nPP16-D POWER

PACK WITH MVOLT

INPUT.

SS

PP

BLK

WHT

277V

NEUTRAL

CAT 6

RED/EM 277V

YLW/EM 120V

BLU/EM MVOLT

WHT-RED/EM NEUTRAL

RED/EM

YLW/EM

BLU/EM

WHT-RED/EM

VLT DIM COMMON

GRY DIM POSITIVE

BLU LINE OUT

VLT DIM COMMON

GRY DIM POSITIVE

BLUGRN

GRN

CAT 6

CAT 6

CAT 6

CAT 6 CAT 6

LIGHTING CONTROL DIAGRAM #6

N.T.S.

F

J

J

OCCUPANCY SENSOR

SENSOR SWITCH

nCM-PDT-10

OCCUPANCY SENSOR

SENSOR SWITCH

nCM-PDT-10

SYMBOL

SENSORSWITCH:

#nPP16-D POWER

PACK WITH MVOLT

INPUT.

SS

SYMBOL

SENSORSWITCH:

#nPP16-D POWER

PACK WITH MVOLT

INPUT.

SS FOR ADDITIONAL

POWER PACKS (IF

REQUIRED) IN WORK

SPACE, SEE PLANS

OC1 OC1

PP

PP

SENSORSWITCH:

#nPODM-DX-WH

SINGLE CHANNEL

DIMMER SWITCH.

SENSORSWITCH:

#nPODM-DX-WH

SINGLE CHANNEL

DIMMER SWITCH.

LIGHTING CONTROL DIAGRAM #7

G

3 4 3

N.T.S.

GREY COMMON

3-#16,1/2"C

BL

K

YELLOW

VIOLET

BL

U

R

ED

LINE

NEUTRAL

J

OC2

GREY

YELLOW

VIOLET

SYMBOL " " . SENSOR SWITCH POWER PACK

#PP16 (277V). INSTALL ABOVE ACCESSIBLE

CEILING NEAR LIGHT SWITCHES.

TO LIGHT FIXTURE WITH

DESIGNATION EM OR

NL.

C

IR

C U

IT

7V (1

V)

CONTROL

OUTPUT

CONTROL +

24VDC

TO LIGHT FIXTURES IN

ROOM OR SPACE.

LOCAL SWITCH.

(IF APPLICABLE)

SYMBOL

SENSOR SWITCH ULTRASONIC

OCCUPANCY SENSOR #CM-PDT-10.

MOUNT ON CEILING AT LOCATION

RECOMMENDED AND DIRECTED

BY MANUFACTURER.

FOR ADDITIONAL SENSORS, SEE

PLANS. ADD ADDITIONAL

POWER PACKS AS REQUIRED.

PP

GREY COMMON

3-#16,1/2"C

BL

K

YELLOW

VIOLET

BL

U

R

ED

OC2

GREY

YELLOW

VIOLET

CONTROL

OUTPUT

CONTROL +

24VDC

SYMBOL

SENSOR SWITCH ULTRASONIC

OCCUPANCY SENSOR #CM-PDT-10.

MOUNT ON CEILING AT LOCATION

RECOMMENDED AND DIRECTED

BY MANUFACTURER.

FOR ADDITIONAL SENSORS, SEE

PLANS. ADD ADDITIONAL

POWER PACKS AS REQUIRED.

ADDITIONAL POWER PACKS

AS REQUIRED.

SS

SS

BLK

WHT

277V

NEUTRAL

CAT 6

RED/EM 277V

YLW/EM 120V

BLU/EM MVOLT

WHT-RED/EM NEUTRAL

RED/EM

YLW/EM

BLU/EM

WHT-RED/EM

VLT DIM COMMON

GRY DIM POSITIVE

BLU LINE OUT

VLT DIM COMMON

GRY DIM POSITIVE

BLUGRN

GRN

CAT 6

CAT 6

a,b

LIGHTING CONTROL DIAGRAM #8

N.T.S.

H

J

J

SENSORSWITCH:

#nPODM-2P-DX-WH

TWO

CHANNEL DIMMER

SWITCH.

SYMBOL

SENSORSWITCH:

#nPP16-D POWER

PACK WITH

MVOLT

INPUT.

FOR ADDITIONAL

POWER PACKS (IF

REQUIRED) IN WORK

SPACE, SEE PLANS

BLK

WHT

120V

NEUTRAL

NORMAL CRITICAL

277V

120V

MVOLT

NEUTRAL

SIGNATURE DATE

HATHAWAY

ST

ATE OF O

H IO

P R

O F

ESS IO N

AL E N G

IN

E E

R

R E G I S T E RE D

E-61777

MARLON

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

CONSTRUCTION - ISSUED FOR

BID

Project Number

Building Number

Drawing Number

340, 341

VA Building 340, 341 Project Title

Location

Issued Date Checked Drawn

Drawing Title Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

SCHEESER BUCKLEY MAYFIELD

1540 CORPORATE WOODS PARKWAY

UNIONTOWN, OHIO 44685

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

Approved:

PHILIP P. KIRK

CHIEF ENGINEER

2/

/2

2:

: 5

PM

C :\U se rs

\M Ky ag ab a\ D oc um en ts

\1

_M

EP

_C

E N

TR

AL

F

IL

E_ m ky ag ab a@ sb m c e

.c om

.rv t

EJ-101

552-20-104

MCH MSK

RENOVATE PRIMARY CARE FOR

PACT BLDG 340, BLDG 341

02/09/2021

4100 WEST THIRD STREET, DAYTON, OH 45428

LIGHTING FIXTURE SCHEDULE AND DETAILS

02/09/2021

1. "NL" SUBSCRIPT INDICATES THAT THE FIXTURE IS CONNECTED TO AN UNSWITCHED CIRCUIT FOR "NIGHT LIGHT"

ILLUMINATION.

2. "EM" SUBSCRIPT INDICATES THAT THE FIXTURE IS CONNECTED TO AN EMERGENCY POWER SOURCE FOR EMERGENCY

ILLUMINATION.

3. VERIFY CEILING TYPE WITH ARCHITECTURAL REFLECTED CEILING PLAN. PROVIDE MOUNTING TYPE AS REQUIRED TO ACCOMMODATE THE CEILING. (i.e. FLANGE OR GRID MOUNT).

4. CONFIRM ALL MOUNTING HEIGHTS WITH ARCHITECT.

5. PROVIDE LUMINAIRE DISCONNECT SWITCH, POWER PLUG OR EQUAL IN ACCORDANCE WITH NEC 410.103.

NOTES:

LIGHTING FIXTURE SCHEDULE

SYMBOL CATALOG NUMBER DESCRIPTION MOUNTING LAMP(S)

POWER

REQUIREMENT

D1 LDN4-35/10-L04-AR-LSS-MVOLT-EZ1 LITHONIA: 11 3/16"x 9 7/16" x 5 11/16" DEEP LED FIXTURE WITH 4" APERATURE, 3500K, 1085.2 LUMEN OUTPUT, MVOLT, WHITE

FINISH AND ONE (1) 0-10V DIMMING LED DRIVER.

RECESSED INTEGRAL 13 VA

D2 LDN4-35/25-L04-AR-LSS-MVOLT-EZ1 LITHONIA: 11 3/16"x 9 7/16" x 5 11/16" DEEP LED FIXTURE WITH 4" APERATURE, 3500K, 2551 LUMEN OUTPUT, 26.1W, MVOLT, WHITE FINISH AND ONE (1) 0-10V DIMMING LED DRIVER.

RECESSED INTEGRAL 26 VA

P1 695-A90-645-35-10-00-01-01-952-01-01

-01-LCS-277

SENSO: 12.4"x'x14.3" DEEP LED PENDANT FIXTURE WITH ALUMINUM CONSTRUCTION, 1000 LUMEN OUTPUT, MVOLT, 3500K COLOR TEMPERATURE, 9.3W, WHITE FINISH AND (1) LED DRIVER. EC TO PROVIDE EMERGENCY BATTERY PACK WHERE "EM" IS

INDICATED ON FLOOR PLANS AND PROVIDE AIRCRAFT CABLING.

PENDANT INTEGRAL 9 VA

P2 4L-P-ID-STD-06-SOF-C1-35K-I030-D10

0-D01-2C-UNV-FA1

LITECONTROL: 4.25"x6'x4.5" DEEP LED PENDANT INDIRECT/DIRECT FIXTURE WITH ALUMINUM CONSTRUCTION, ACRYLIC LENS, 1000 LUMEN/FT DIRECT, 12.1W/FT DIRECT, 300 LUMEN/FT INDERECT, 2.4W/FT INDIRECT, 3500K, MVOLT, WHITE FINISH AND ONE

(1) LED DIMMING DRIVER

RECESSED INTEGRAL 58 VA

P3 N/A HALPER LIGHTING SOLUTIONS: LINEAR PENDANT/DOWN AMERICAN FLAG LIGHTING FIXTURE SYSTEM, 2400W DOWNLIGHT(S), RGBW 1800W, DIMMABLE LED DRIVER, RGBW 120/277 TO 24V CONTROLS/OPERATION, EC TO COORDINATE WITH

MANUFACTURER FOR EXACT HEIGHT AND LOCATION OF LIGHTING SYSTEM AND PROVIDE ALL APPLICABLE COMPONENTS, AC/DC/DIMMING WIRING AND ASSOCIATED DEVICES FOR A COMPLETE INSTALLATION. REFER TO INTERIOR LIGHTING

SPECIFICATION FOR ADDITIONAL INFORMATION.

PENDANT INTEGRAL 58 VA

R3 2BLT2-48LHE-ADP-EZ1-LP835 LITHONIA: 2'x2'x2-3/4" DEEP LED FIXTURE WITH ALUMINUM FRAME HOUSING, ACRLYIC LENS, 4780.4 LUMEN OUTPUT, 3500K, 82CRI, 37.85WATTS, WHITE FINISH WITH ONE UNIVERSAL VOLTAGE 0-10V DIMMING DRIVER.

RECESSED INTEGRAL 38 VA

R4 2BLT2-33L-ADP-EZ1-LP835 LITHONIA: 2'x2'x2-3/4" DEEP LED FIXTURE WITH ALUMINUM FRAME HOUSING, ACRLYIC LENS, 3332 LUMEN OUTPUT, 3500K, 82CRI, 26.67WATTS, WHITE FINISH WITH ONE UNIVERSAL VOLTAGE 0-10V DIMMING DRIVER.

RECESSED INTEGRAL 26 VA

R5 4L-LG-D-06-SOF-C1-35K-D100-D01-1C

-UNV

LITECONTROL: 4.25"x6'x4.5" DEEP LED FIXTURE WITH ALUMINUM CONSTRUCTION, ACRYLIC LENS, 1000 LUMEN/FT DIRECT, 9W/FT

DIRECT, 3500K, MVOLT, WHITE FINISH AND ONE (1) LED DIMMING DRIVER

RECESSED INTEGRAL 54 VA

R6 EP44-RVN SKYFACTORY: 4'x4' LUMINOUS SKYCEILING LIGHT FXITURE WITH ALUMINUM HOUSING, POLYCARBONATE LENS, 6500K COLOR TEMPERATURE; 37.4W, WHITE POWDER-COATED (NON-FERROUS) FINISH, AND ONE (1) SKY FACTORY 24PS HLG POWER

SYSTEM. EC TO COORDINATE WITH MANUFACTURER AND PROVIDE ALL ADDITIONAL AC/DC/DIMMING WIRING AND ASSOCIATED

DEVICES FOR A COMPLETE INSTALLATION.

CEILING RECESSED INTEGRAL 92 VA

R7 LX4RT-R-30-L8/835-F/J-A-ASY-LX4RV9

0R-DIM-UNV

HE WILLIAM: 4"x30'x5-5/16" DEEP LED DRYWALL COVE FIXTURE WITH ALUMINUM HOUSING, ASYMMETRIC ACRYLIC LENS, 3500K, 800LM/FT OUTPUT, 62W AND ONE (1) 0-10 LED DRIVER.

CEILING RECESSED INTEGRAL 248 VA

R8 2TL2-40L-FW-A12-EZ1-LP835 LITHONIA: 2'x2'x3-3/4" DEEP LED FIXTURE WITH STEEL CONSTUCTION, ACRLYIC LENS, 3892.7 LUMEN OUTPUT, 3500K, 82CRI, 35WATTS, WHITE FINISH WITH ONE UNIVERSAL VOLTAGE 0-10V DIMMING DRIVER.

RECESSED INTEGRAL 35 VA

R9 2TL2-33L-FW-A12-EZ1-LP835 LITHONIA: 2'x2'x3-3/4" DEEP LED FIXTURE WITH STEEL CONSTUCTION, ACRLYIC LENS, 3317 LUMEN OUTPUT, 3500K, 82CRI, 29WATTS, WHITE FINISH WITH ONE UNIVERSAL VOLTAGE 0-10V DIMMING DRIVER.

RECESSED INTEGRAL 29 VA

R10 MMAC22-G-4-9-FA-45L35K-DCC-DV-A

MF

KENALL: 23.75"x23.75"x6.10" DEEP LED FIXTURE WITH DIE-FORMED PRIME GRADE HOUSING, POLYCARBONATE LENS, 4131 LUMEN OUTPUT, 3500K, 82CRI, 49WATTS, ANTIMICROBIAL FINISH WITH ONE UNIVERSAL VOLTAGE 0-10V DIMMING DRIVER.

RECESSED INTEGRAL 49 VA

R11 CSEDI-22-90T-27/65K9-ATW-DV-PAF-P

AH-SYM-AMF

KENALL: 2'x2'x3-3/4" DEEP LED FIXTURE WITH ALUMINUM CONSTUCTION, ACRLYIC LENS, 8035 LUMEN OUTPUT, TUNABLE WHITE LED, 82CRI, 92WATTS, ANTIMICROBIAL WHITE FINISH WITH ONE UNIVERSAL VOLTAGE 0-10V DIMMING DRIVER.

RECESSED INTEGRAL 68 VA

R12 2BLT2-48L-ADP-EZ1-LP835 LITHONIA: 2'x2'x2-3/4" DEEP LED FIXTURE WITH ALUMINUM FRAME HOUSING, ACRLYIC LENS, 4800 LUMEN OUTPUT, 3500K, 82CRI, 43.67WATTS, WHITE FINISH WITH ONE UNIVERSAL VOLTAGE 0-10V DIMMING DRIVER.

RECESSED INTEGRAL 44 VA

R13 HSTL-2X2-G-MVOLT-STD-ALM-3000L

M-35K-80CRI-ZT-MIN10-IAW-GWAM

HEALTHCARE LIGHTING: 2'x2'x2-3/4" DEEP LED FIXTURE WITH STEEL CONSTRUCTION, ACRLYIC LENS, 3269 LUMEN OUTPUT, 3500K, 80CRI, 27WATTS, WHITE ANTIMICROBIAL FINISH WITH ONE UNIVERSAL VOLTAGE 0-10V DIMMING DRIVER.

RECESSED INTEGRAL 27 VA

R14 HSTL-2X2-G-MVOLT-STD-ALM-7000L

M-35K-80CRI-ZT-MIN10-IAW-GWAM

HEALTHCARE LIGHTING: 2'x2'x2-3/4" DEEP LED FIXTURE WITH STEEL CONSTRUCTION, ACRLYIC LENS, 6735 LUMEN OUTPUT, 3500K, 80CRI, 58WATTS, WHITE ANTIMICROBIAL FINISH WITH ONE UNIVERSAL VOLTAGE 0-10V DIMMING DRIVER.

RECESSED INTEGRAL 58 VA

W1 070442-40K-PHC PERFORMANCE IN LIGHTING: 8.9"x8.6" LED EXTERIOR WALL MOUNT FIXTURE, ALUMINUM HOUSING, 4000K COLOR TEMPERATURE, TYPE 3 DISTRIBUTION, 18.5W, ALUMINUM METALLIC FINISH, INTEGRAL PHOTOCELL AND ONE (1) 0-10V LED

DIMMING DRIVER. FIXTURE TO BE MOUNTED 10' AFF UNLESS SPECIFIED OTHERWISE BY ARCHITECT.

WALL MOUNT INTEGRAL 19 VA

X1 EDGR-R LITHONIA: 13"x8"x1-3/4" DEEP LED EXIT SIGN WITH ACRYLIC HOUSING WITH BRUSHED ALUMINUM FACE, RED LETTERS DUAL VOLTAGE, NICKEL CADMIUM BATTERY AND MOUNTING, FACES & CHEVRONS AS INDICATED ON PLANS.

UNIVERSAL INTEGRAL 3 VA

FX

CONNECTION TYPE 2 DIAGRAM

N.T.S

STANDARD

FEEDER

DESIGNATIO

N. SEE

STANDARD

FEEDER

SCHEDULE

MOTOR

RATED

TOGGLE

SWITCH

FX

CONNECTION TYPE 1 DIAGRAM

N.T.S

STANDARD

FEEDER

DESIGNATION.

SEE

STANDARD

FEEDER

SCHEDULE

INTEGRAL

WITH

EQUIPMENT

SIGNATURE DATE

HATHAWAY

ST

ATE OF O

H IO

P R

O F

ESS IO N

AL E N G

IN

E E

R

R E G I S T E RE D

E-61777

MARLON

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

CONSTRUCTION - ISSUED FOR

BID

Project Number

Building Number

Drawing Number

340, 341

VA Building 340, 341 Project Title

Location

Issued Date Checked Drawn

Drawing Title Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

SCHEESER BUCKLEY MAYFIELD

1540 CORPORATE WOODS PARKWAY

UNIONTOWN, OHIO 44685

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

Approved:

PHILIP P. KIRK

CHIEF ENGINEER

2/

/2

2:

: 5

PM

C :\U se rs

\M Ky ag ab a\ D oc um en ts

\1

_M

EP

_C

E N

TR

AL

F

IL

E_ m ky ag ab a@ sb m c e

.c om

.rv t

EJ-102

552-20-104

MCH MSK

RENOVATE PRIMARY CARE FOR

PACT BLDG 340, BLDG 341

02/09/2021

4100 WEST THIRD STREET, DAYTON, OH 45428

MECHANICAL EQUIPMENT AND

PANELBOARD SCHEDULE

02/09/2021

300 300 350 4 2-1/2" 3" 3"

250 250 250 4 2" 2-1/2" 2-1/2"

225 225 4/0 4 2" 2" 2"

200 200 3/0 6 1-1/2" 2" 2"

175 175 2/0 6 1-1/2" 2" 2"

150 150 1/0 6 1-1/2" 1-1/2" 2"

125 125 1 6 1-1/2" 1-1/2" 1-1/2"

110 110 2 6 1" 1-1/2" 1-1/2"

100 100 2 8 1" 1-1/2" 1-1/2"

90 90 3 8 1" 1-1/2" 1-1/2"

80 80 4 8 1" 1" 1-1/2"

70 70 4 8 1" 1" 1-1/2"

60 60 6 10 3/4" 3/4" 1"

50 50 8 10 3/4" 3/4" 3/4"

45 45 8 10 3/4" 3/4" 3/4"

40 40 8 10 3/4" 3/4" 3/4"

35 35 8 10 3/4" 3/4" 3/4"

30 30 10 10 3/4" 3/4" 3/4"

25 25 10 10 3/4" 3/4" 3/4"

20 20 12 12 3/4" 3/4" 3/4"

15 15 12 12 3/4" 3/4" 3/4"

CU CU CU CU CU

W/G W/G W/G

PHASE/

NEUTRAL GROUND 2C 3C 4C

A B C

FEEDER NO.

WIRE SIZE AMPS

NOMINAL FEEDER SIZE

(AMPS)

CONDUCTOR SIZE (AWG) CONDUIT SIZE

STANDARD FEEDER SCHEDULE

1. SEE STANDARD FEEDER SCHEDULE FOR MORE INFORMATION.

2. WHERE THE DISCONNECT IS LISTED AS "INTEGRAL", THE UNIT IS BEING SUPPLIED WITH AN "INTEGRAL" DISCONNECTING MEANS. WHERE A SIZE, TYPE, ETC. IS SHOWN; IT IS TO BE PROVIDED BY THE E.C.

3. WHERE THE STARTER IS LISTED AS "INTEGRAL", THE UNIT IS BEING SUPPLIED WITH AN "INTEGRAL" STARTER. WHERE A STARTER DESIGNATION IS SHOWN; IT IS TO BE PROVIDED BY THE E.C. SEE THE MOTOR STARTER SCHEDULE FOR MORE INFORMATION.

4. SEE CONNECTION TYPE DIAGRAMS FOR MORE INFORMATION.

NOTES:

MECHANICAL EQUIPMENT SCHEDULE

Mechanical Equipment Designation

DESCRIPTION

FLOOR LEVEL ROOM

APPARENT POWER HP VOLTAGE PHASE (NUMBER OF

POLES) WIRE/CONDUIT (NOTE 1) PANEL CIRCUIT(S) DISCONNNECT

DESIGNATION DISCONNECT DESCRIPTION (NOTE 2) DISCONNECT LOCATION

STARTER

DESCRIPTION

(NOTE 3)

CONNECTION TYPE

(NOTE 4) REMARKS

HWP-1 HEATING WATER PUMP FIRST FLOOR C-1-11 864 VA 1/3 120 V 1 20A 340-1-4-3 38 - - - MANUAL MOTOR

STARTER - EC TO PROVIDE RELAY-IN-A-BOX. SEE DETAIL.

VAV-1 VAV TERMINAL UNIT

FIRST FLOOR 188

100 VA - 120 V 1 20A 340-1-4-2 40 DS-VAV-1 TOGGLE SWITCH - INTEGRAL 2

TOGGLE SWITCH ABOVE CEILING SPACE. EC TO

COORDINATE WITH MC FOR EXACT LOCATION WITHIN LINE

OF SIGHT OF VAV

VAV-2 VAV TERMINAL UNIT

FIRST FLOOR 189

100 VA - 120 V 1 20A 340-1-4-2 40 DS-VAV-2 TOGGLE SWITCH - INTEGRAL 2

TOGGLE SWITCH ABOVE CEILING SPACE. EC TO

COORDINATE WITH MC FOR EXACT LOCATION WITHIN LINE

OF SIGHT OF VAV

VAV-3 VAV TERMINAL UNIT

FIRST FLOOR 191

100 VA - 120 V 1 20A 340-1-4-2 40 DS-VAV-3 TOGGLE SWITCH - INTEGRAL 2

TOGGLE SWITCH ABOVE CEILING SPACE. EC TO

COORDINATE WITH MC FOR EXACT LOCATION WITHIN LINE

OF SIGHT OF VAV

VAV-4 VAV TERMINAL UNIT

FIRST FLOOR C-1-5

100 VA - 120 V 1 20A 340-1-4-2 40 DS-VAV-4 TOGGLE SWITCH - INTEGRAL 2

TOGGLE SWITCH ABOVE CEILING SPACE. EC TO

COORDINATE WITH MC FOR EXACT LOCATION WITHIN LINE

OF SIGHT OF VAV

VAV-5 VAV TERMINAL UNIT

FIRST FLOOR

100 VA - 120 V 1 20A 340-1-4-2 40 DS-VAV-5 TOGGLE SWITCH - INTEGRAL 2

TOGGLE SWITCH ABOVE CEILING SPACE. EC TO

COORDINATE WITH MC FOR EXACT LOCATION WITHIN LINE

OF SIGHT OF VAV

EF-1 EXHAUST FAN T.O. STEEL 696 VA 1/4 120 V 1 20A 340-1-4-2 42 - - - MANUAL MOTOR

STARTER - EC TO PROVIDE RELAY-IN-A-BOX. SEE DETAIL.

RTU-1 ROOFTOP UNIT T.O. STEEL 20369 VA - 480 V 3 30B 340-1-5 33,35,37 INTEGRAL - - INTEGRAL 1

11619 VA 9848 VA 6790 VA

41 SPACE -- -- -- 0 VA / 0 VA -- -- -- SPACE 42

39 SPACE -- -- -- 0 VA / 0 VA -- -- -- SPACE 40

37 -- -- -- -- 6790 VA / 0 VA -- -- -- SPACE 38

35 -- -- -- -- 6790 VA / 0 VA -- -- -- SPACE 36

33 ROOFTOP RTU-1 30 A 3 6790 VA / 0 VA -- -- -- SPACE 34

31 SPARE 20 A 1 0 VA / 0 VA 1 20 A SPARE 32

29 EXISTING LOAD STREET LIGHTS 20 A 1 0 VA / 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA / 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA / 0 VA 1 20 A SPARE 26

23 SPARE 20 A 1 0 VA / 0 VA 1 20 A SPARE 24

21 LIGHTING 2 20 A 1 266 VA / 3016 VA 1 20 A 2 LIGHTING 22

19 LIGHTING 2 20 A 1 2490 VA / 2635 VA 1 20 A 2 LIGHTING 20

17 EXISTING LOAD RM 100, 100E, C-1-1, C-1-8, C-1-9, C-1-10 20 A 1 0 VA / 0 VA 1 20 A EXISTING NURSES STATION CAN LIGHTS 18

15 EXISTING RM 108, 109, 110 20 A 1 0 VA / 0 VA 1 20 A EXISTING LOAD LOBBY CAN LIGHTS 16

13 EXISTING LOAD RM 106, 106, 107, 109A 20 A 1 0 VA / 0 VA 1 20 A EXISTING LOAD LOBBY CAN LIGHTS, MECHANICAL ROM

LIGHTS 14

11 EXISTING LOAD RM 129, 130, 131, 132, 133, 134 20 A 1 0 VA / 0 VA 1 20 A EXISTING LOAD RM 156, 157, 158, 159, 160, 161 12

9 EXISTING LOAD RM 135, 136, 167, (OLD 114) 20 A 1 0 VA / 0 VA 1 20 A EXISTING LOAD RM 100, 101, 142, 143, 144, 145, 146, 147, 148 10

7 EXISTIN LOAD RM C-1-2, C-1-3, C-2-4, C-2-5, C-2-11,

C-2-12, RM 137, 138, 139, 140, 141 20 A 1 0 VA / 0 VA 1 20 A EXISTING LOAD RM 162, 163, 164, 165, 166 8

5 EXISTING LOAD RM 123, 124, 12,5, 126, 127, 128, 184,

185, 186, 187, 188 20 A 1 0 VA / 0 VA 1 20 A EXISTING LOAD RM 149, 150, 151, 152, 153, 154, 155, 190, 191, 192, 193 6

3 EXISTING LOAD RM 121, 122, 180, 181, 182, 183, 183A 20 A 1 0 VA / 0 VA 1 20 A EXISTING LOAD C-1-6, C-1-7, RM 168, 169, 170, 171 4

1 EXISTING LOAD RM 112, 113, 114, 115, 116, 117, 118, 119,

120 20 A 1 0 VA / 0 VA 1 20 A EXISTING LOAD RM 172, 173, 174, 175, 176, 177, 178, 179 2

CCT Load Name NOTES TRIP POLES A B C POLES TRIP NOTES Load Name CCT

1. EC TO PROVIDE NEW TYPED PANELBOARD SCHEDULE. ALL EXISTING CIRCUIT BREAKERS MADE SPARE AFTER DEMOLITION PHASE AND NOT NOTED SHALL BE CALLED SPARE IN NEW

TYPED SCHEDULE. EC TO VERIFY.

2. WHERE "2" IS SHOWN ON NOTES, EXISTING CIRCUIT BREAKER TO REMAIN AND MADE SPARE AFTER DEMOLITION PHASE.

NOTES:

MCB RATING:

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 250 A

SUPPLIED FROM: PHASE: 3 MAINS TYPE: MLO

LOCATION: ELECT. 123 VOLTAGE: 480/277 NP A.I.C. RATING: 22000

PANEL NAME: 340-1-5

522 VA 0 VA 0 VA

41 SPACE -- -- -- 0 VA / 0 VA -- -- -- SPACE 42

39 SPACE -- -- -- 0 VA / 0 VA -- -- -- SPACE 40

37 SPACE -- -- -- 0 VA / 0 VA -- -- -- SPACE 38

35 SPACE -- -- -- 0 VA / 0 VA -- -- -- SPACE 36

33 SPACE -- -- -- 0 VA / 0 VA -- -- -- SPACE 34

31 SPACE -- -- -- 0 VA / 0 VA -- -- -- SPACE 32

29 SPACE -- -- -- 0 VA / 0 VA -- -- -- SPACE 30

27 SPACE -- -- -- 0 VA / 0 VA -- -- -- SPACE 28

25 SPACE -- -- -- 0 VA / 0 VA -- -- -- SPACE 26

23 SPACE -- -- -- 0 VA / 0 VA -- -- -- SPACE 24

21 EXISTING LOAD 20 A 1 0 VA / 0 VA -- -- -- SPACE 22

19 EXISTING LOAD 20 A 1 0 VA / 0 VA 1 20 A SPARE 20

17 EXISTING LOAD 20 A 1 0 VA / 0 VA 1 20 A SPARE 18

15 EXISTING LOAD 20 A 1 0 VA / 0 VA 1 20 A SPARE 16

13 EXISTING LOAD 20 A 1 0 VA / 0 VA 1 20 A SPARE 14

11 EXISTING LOAD 20 A 1 0 VA / 0 VA 1 20 A SPARE 12

9 EXISTING LOAD 20 A 1 0 VA / 0 VA 1 20 A SPARE 10

7 EXISTING LOAD 20 A 1 0 VA / 522 VA 1 20 A WAITING ROOM(S) 134 &135, KIOSK 136, CORRIDOR

C-1-12 AND VESITBULE 100 8

5 EXISTING LOAD LIGHTS 20 A 1 0 VA / 0 VA -- -- -- -- 6

3 EXISTING LOAD LIGHTS 20 A 1 0 VA / 0 VA -- -- -- -- 4

1 EXISTING LOAD LIGHTS 20 A 1 0 VA / 0 VA 3 60 A EXISTING XFMR T-340-2 2

CCT Load Name NOTES TRIP POLES A B C POLES TRIP NOTES Load Name CCT

1. EC TO PROVIDE NEW TYPED PANELBOARD SCHEDULE. ALL EXISTING CIRCUIT BREAKERS MADE SPARE AFTER DEMOLITION PHASE AND NOT NOTED SHALL BE CALLED SPARE IN NEW

TYPED SCHEDULE. EC TO VERIFY.

NOTES:

MCB RATING:

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 250 A

SUPPLIED FROM: PHASE: 3 MAINS TYPE: MLO

LOCATION: ELECT. 123 VOLTAGE: 480/277 LS A.I.C. RATING: 22000

PANEL NAME: LLS1

1500 VA 2500 VA 3924 VA

41 SPACE -- -- 0 VA / 0 VA -- -- SPACE 42

39 SPACE -- -- 0 VA / 0 VA -- -- SPACE 40

37 SPACE -- -- 0 VA / 0 VA -- -- SPACE 38

35 SPACE -- -- 0 VA / 0 VA -- -- SPACE 36

33 SPACE -- -- 0 VA / 0 VA -- -- SPACE 34

31 TELECOM ROOM 139 NCTC 3 20 A 1 0 VA / 0 VA -- -- SPACE 32

29 VESTIBULE 100-A AD-1 3 20 A 1 1000 VA / 0 VA 1 20 A 3 TELECOM ROOM 139 FAEP 30

27 DOOR 126-B SECURITY 3 20 A 1 500 VA / 500 VA 1 20 A 3 DOOR C-1-8-A SECURITY 28

25 DOOR 134-B SECURITY 3 20 A 1 500 VA / 500 VA 1 20 A 3 DOOR 101-A SECURITY 26

23 EXISTING DOOR C-1-1A SECURITY 3 20 A 1 500 VA / 500 VA 1 20 A 3 DOOR 134-A SECURITY 24

21 DOOR 189-B SECURITY 3 20 A 1 500 VA / 500 VA 1 20 A 3 DOOR 189-C SECURITY 22

19 -- -- -- 0 VA / 0 VA -- -- -- 20

17 EXISTING LOAD 20 A 2 0 VA / 0 VA 2 30 A EXISTING LOAD RM 139 UPS 18

15 -- -- -- 0 VA / 500 VA 1 20 A DOOR 189-A SECURITY 16

13 EXISTING CATALYST 4500 20 A 2 0 VA / 500 VA 1 20 A DOOR C-1-11-A SECURITY 14

11 VESTIBULE 100-C AD-1 20 A 1 1000 VA / 1000 VA 1 20 A VESTIBULE 100-B AD-1 12

9 EXISTING LOAD OUTDOOR RECEPT A/C 20 A 1 0 VA / 0 VA 1 20 A EXISTING LOAD REFRIGERATOR 10

7 -- -- -- 0 VA / 0 VA 1 20 A EXISTING LOAD CRASH CART 8

5 EXISTING LOAD A/C OUTSIDE UNIT FOR RM IE100 20 A 2 0 VA / 0 VA 1 20 A EXISTING COMPUTER RECEPTION DESK 6

3 EXISTING LOAD RM 139 20 A 1 0 VA / 0 VA 1 20 A EXISTING FIRE ALARM PANEL 4

1 EXISTING LOAD RM 140 20 A 1 0 VA / 0 VA 1 20 A EXISTING LOAD NURSE CALL 2

CCT Load Name NOTES TRIP POLES A B C POLES TRIP NOTES Load Name CCT

1. EC TO PROVIDE NEW TYPED PANELBOARD SCHEDULE. ALL EXISTING CIRCUIT BREAKERS MADE SPARE AFTER DEMOLITION PHASE AND NOT NOTED SHALL BE CALLED SPARE IN NEW

TYPED SCHEDULE. EC TO VERIFY.

2. WHERE "2" IS SHOWN ON NOTES, EXISTING CIRCUIT BREAKER TO REMAIN AND MADE SPARE AFTER DEMOLITION PHASE.

3. EC TO PROVIDE NEW CIRCUIT BREAKER IN EXISTING SPACE. NEW CIRCUIT BREAKER TO MATCH IN EXISTING TYPE, MANUFACTURER AND AIC RATING.

NOTES:

MCB RATING:

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 125 A

SUPPLIED FROM: PHASE: 3 MAINS TYPE: MCB

LOCATION: ELECT. 123 VOLTAGE: 120/208 LS A.I.C. RATING: 22000

PANEL NAME: RLS1

5100 VA 4775 VA 5954 VA

41 ROOM 114 RECEPTACLE 2 20 A 1 1000 VA / 696 VA 1 20 A 2 ROOFTOP EF-1 42

39 EXISTING LOAD RM 110 2X2 LIGHTS 20 A 1 0 VA / 500 VA 1 20 A 2 ROOM 188 VAV-1 40

37 EXISTING LOAD ACH2 20 A 1 0 VA / 1080 VA 1 20 A 2 ROOM 189 RECEPTACLES 38

35 EXISTING LOAD RM 109A 20 A 1 0 VA / 0 VA 1 20 A EXISTING LOAD DRINKING FOUNTAINS 36

33 EXISTING LOAD RM 107, 109A 20 A 1 0 VA / 0 VA 1 20 A EXISTING LOAD RM 112 34

31 EXISTING LOAD RM 106, 107 20 A 1 0 VA / 0 VA 1 20 A EXISTING LOAD C-1-5, MAIN HALL 32

29 EXISTING LOAD RM 109 20 A 1 0 VA / 0 VA 1 20 A EXISTING LOAD RM 104, 110 30

27 EXISTING LOAD RM 109 20 A 1 0 VA / 0 VA 1 20 A EXISTING LOAD RM 110 28

25 EXISTING LOAD RM 109 20 A 1 0 VA / 0 VA 1 20 A EXISTING LOAD RM 110 26

23 EXISTING LOAD DISPLAY CASE 20 A 1 0 VA / 0 VA 1 20 A EXISTING LOAD RM 105, 108 24

21 EXISTING LOAD 20 A 1 0 VA / 0 VA 1 20 A EXISTING LOAD RM 105, 108, MAIN HALL 22

19 ROOM 189 RECEPTACLES 2 20 A 1 1080 VA / 0 VA 1 20 A EXISTING LOAD RM 105, 108 20

17 ROOM 189 RECEPTACLES 2 20 A 1 1080 VA / 0 VA 1 20 A EXISTING LOAD RM 112 18

15 ROOM 189 RECEPTACLES 2 20 A 1 1080 VA / 0 VA 1 20 A EXISTING LOAD RM 112 16

13 EXISTING LOAD RM 157B 20 A 1 0 VA / 1080 VA 1 20 A 2 ROOM 189 RECEPTACLES 14

11 EXISTING LOAD RM 157B 20 A 1 0 VA / 1080 VA 1 20 A 2 ROOM 189 RECEPTACLES 12

9 EXISTING LOAD RM 157B 20 A 1 0 VA / 1080 VA 1 20 A 2 ROOM 189 RECEPTACLES 10

7 EXISTING LOAD RM 157B 20 A 1 0 VA / 1080 VA 1 20 A 2 ROOM 189 RECEPTACLES 8

5 ROOM 189 RECEPTACLES 2 20 A 1 1080 VA / 1080 VA 1 20 A 2 ROOM 189 RECEPTACLES 6

3 ROOM 189 RECEPTACLES 2 20 A 1 1080 VA / 1080 VA 1 20 A 2 ROOM 189 RECEPTACLES 4

1 ROOM(S) 189, 190, 191, 192, AND 193 2 20 A 1 780 VA / 0 VA 1 20 A EXISTING LOAD RM 157B 2

CCT Load Name NOTES TRIP POLES A B C POLES TRIP NOTES Load Name CCT

1. EC TO PROVIDE NEW TYPED PANELBOARD SCHEDULE. ALL EXISTING CIRCUIT BREAKERS MADE SPARE AFTER DEMOLITION PHASE AND NOT NOTED SHALL BE CALLED SPARE IN NEW

TYPED SCHEDULE. EC TO VERIFY.

2. WHERE "2" IS SHOWN ON NOTES, EXISTING CIRCUIT BREAKER TO REMAIN AND MADE SPARE AFTER DEMOLITION PHASE.

NOTES:

MCB RATING:

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 250 A

SUPPLIED FROM: PHASE: 3 MAINS TYPE: MLO

LOCATION: ELECT. 123 VOLTAGE: 120/208 NP A.I.C. RATING: 22000

PANEL NAME: 340-1-4-2

6300 VA 5580 VA 4320 VA

41 EXISTING LOAD RM 115 20 A 1 0 VA / 900 VA 1 20 A 4 ROOM 111 RECEPTACLES 42

39 EXISTING LOAD RM 113 20 A 1 0 VA / 0 VA 1 20 A EXISTING LOAD C-1-2 40

37 EXISTING LOAD RM 114 20 A 1 0 VA / 0 VA 1 20 A EXISTING LOAD 38

35 SPARE 20 A 1 0 VA / 0 VA 1 20 A SPARE 36

33 EXISTING LOAD RM 118, C-1-2 20 A 1 0 VA / 0 VA 1 20 A EXISTING LOAD RM 112, 113, 115 34

31 SPARE 20 A 1 0 VA / 0 VA 1 20 A EXISTING LOAD 32

29 SPARE 20 A 1 0 VA / 0 VA 1 20 A SPARE 30

27 SPARE 20 A 1 0 VA / 0 VA 1 20 A SPARE 28

25 SPARE 20 A 1 0 VA / 0 VA 1 20 A SPARE 26

23 CORRIDOR C-1-2 RECEPTACLES 3 20 A 1 360 VA / 0 VA 1 20 A EXISTING LOAD RM 129, 134, C-1-12 24

21 ROOM 135 RECEPTAQLES 3 20 A 1 720 VA / 360 VA 1 20 A 3 ROOM 130 RECEPTACLES 22

19 ROOM 132 RECEPTACLES 3 20 A 1 900 VA / 900 VA 1 20 A 3 ROOM 133 RECEPTACLES 20

17 ROOM 136 RECEPTACLES 3 20 A 1 360 VA / 900 VA 1 20 A 3 ROOM 137 RECEPTACLES 18

15 ROOM 148 RECEPTACLES 3 20 A 1 900 VA / 900 VA 1 20 A 3 ROOM 147 RECEPTACLES 16

13 EXISTING LOAD RM 137, 138, XRAY VIEWER 20 A 1 0 VA / 900 VA 1 20 A 3 ROOM 149 RECEPTACLES 14

11 EXISTING LOAD RM 126, 138, 137 20 A 1 0 VA / 0 VA 1 20 A EXISTING LOAD RM 127, C-1-9 12

9 ROOM 157 RECEPTACLES 3 20 A 1 900 VA / 900 VA 1 20 A 3 ROOM 156 RECEPTACLES 10

7 ROOM 115 RECEPTACLES 3 20 A 1 900 VA / 900 VA 1 20 A 3 ROOM 158 RECEPTACLES 8

5 ROOM 117 RECEPTACLES 3 20 A 1 900 VA / 900 VA 1 20 A 3 ROOM 116 RECEPTACLES 6

3 ROOM 112 RECEPTACLES 3 20 A 1 900 VA / 0 VA 1 20 A EXISTING LOAD RM 183, C-1-2 4

1 ROOM 114 RECEPTACLES 2 20 A 1 900 VA / 900 VA 1 20 A 2 ROOM 113 RECEPTACLES 2

CCT Load Name NOTES TRIP POLES A B C POLES TRIP NOTES Load Name CCT

1. EC TO PROVIDE NEW TYPED PANELBOARD SCHEDULE. ALL EXISTING CIRCUIT BREAKERS MADE SPARE AFTER DEMOLITION PHASE AND NOT NOTED SHALL BE CALLED SPARE IN NEW

TYPED SCHEDULE. EC TO VERIFY.

2. EXISTING SPARE CIRCUIT BREAKER.

3. WHERE "3" IS SHOWN ON NOTES, EXISTING CIRCUIT BREAKER TO REMAIN AND MADE SPARE AFTER DEMOLITION PHASE 2 FOR REUSE.

NOTES:

MCB RATING:

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 250 A

SUPPLIED FROM: PHASE: 3 MAINS TYPE: MLO

LOCATION: ELECT. 123 VOLTAGE: 120/208 NP A.I.C. RATING: 22000

PANEL NAME: 340-1-4-1

7627 VA 8980 VA 8800 VA

41 EXISTING ELECTRIC DOOR 20 A 1 0 VA / 0 VA 1 20 A EXISTING UNDER PANEL RECEPTACLE 42

39 EXISTING ACH1 20 A 1 0 VA / 0 VA 1 20 A EXISTING ACH1 40

37 SPARE 20 A 1 0 VA / 864 VA 1 20 A CORRIDOR C-1-11 HWP-1 38

35 ROOM PAC121 RECEPTACLE 20 A 1 500 VA / 1080 VA 1 20 A WAITING ROOM 134 RECEPTACLES 36

33 ROOM PAC 121 RECEPTACLES 20 A 1 900 VA / 720 VA 1 20 A ROOM PAC121 RECEPTACLES 34

31 ROOM 172 RECEPTACLES 20 A 1 1080 VA / 900 VA 1 20 A ROOM 171 RECEPTACLES 32

29 EXISTING ROOM 161, C-1-11 20 A 1 0 VA / 1100 VA 1 20 A ROOM 189 RECEPTACLES 30

27 ROOM 150 RECEPTACLES 2 20 A 1 720 VA / 500 VA 1 20 A ROOM 188 RECEPTACLES 28

25 ROOM 151 RECEPTACLES 2 20 A 1 720 VA / 0 VA 1 20 A EXISTING C-1-8 26

23 ROOM 160 RECEPTACLES 2 20 A 1 720 VA / 720 VA 1 20 A ROOM 159 RECEPTACLES 24

21 ROOM 180 RECEPTACLES 2 20 A 1 720 VA / 720 VA 1 20 A 2 ROOM 179 RECEPTACLES 22

19 ROOM 182 RECEPTACLES 2 20 A 1 720 VA / 720 VA 1 20 A 2 ROOM 181 RECEPTACLES 20

17 ROOM 184 RECEPTACLES 2 20 A 1 720 VA / 720 VA 1 20 A 2 ROOM 183 RECEPTACLES 18

15 ROOM 188 RECEPTACLES 2 20 A 1 1080 VA / 900 VA 1 20 A 2 ROOM 185 RECEPTACLES 16

13 EXISTING RECEPT. C-1-10, C-1-6 SOUTH WAITING AREA 20 A 1 0 VA / 900 VA 1 20 A 3 ROOM 139 RECEPTACLES 14

11 ROOM(S) 188 & 189 RECEPTACLES 20 A 1 1260 VA / 900 VA 1 20 A 2 ROOM 186 RECEPTACLES 12

9 ROOM 189 RECEPTACLES 20 A 1 1080 VA / 560 VA 1 20 A 2 ROOM 169 RECEPTACLES 10

7 EXISTING CANOPY LIGHTS 20 A 1 0 VA / 720 VA 1 20 A 2 ROOM 170 RECEPTACLES 8

5 EXISTING LOAD 20 A 1 0 VA / 1080 VA 1 20 A ROOM 189 RECEPTACLES 6

3 EXISTING EF-4 20 A 1 0 VA / 1080 VA 1 20 A ROOM 189 RECEPTACLES 4

1 EXISTING UNIT HEATER 20 A 1 0 VA / 1080 VA 1 20 A ROOM 189 RECEPTACLES 2

CCT Load Name NOTES TRIP POLES A B C POLES TRIP NOTES Load Name CCT

1. EC TO PROVIDE NEW TYPED PANELBOARD SCHEDULE. ALL EXISTING CIRCUIT BREAKERS MADE SPARE AFTER DEMOLITION PHASE AND NOT NOTED SHALL BE CALLED SPARE IN NEW

TYPED SCHEDULE. EC TO VERIFY.

2. WHERE "2" IS SHOWN ON NOTES, EXISTING CIRCUIT BREAKER TO REMAIN AND MADE SPARE AFTER DEMOLITION PHASE 1.

3. WHERE "3" IS SHOWN ON NOTES, EXISTING CIRCUIT BREAKER TO REMAIN AND MADE SPARE AFTER DEMOLITION PHASE 2.

NOTES:

MCB RATING:

MOUNTING: FLUSH WIRES: 4 MAINS RATING: 250 A

SUPPLIED FROM: PHASE: 3 MAINS TYPE: MLO

LOCATION: CORRIDOR C-1-11 VOLTAGE: 120/208 NP A.I.C. RATING: 22000

PANEL NAME: 340-1-4-3

EXISTING EXISTING EXISTING

EXISTINGEXISTING EXISTING

SIGNATURE DATE

HATHAWAY

ST

ATE OF O

H IO

P R

O F

ESS IO N

AL E N G

IN

E E

R

R E G I S T E RE D

E-61777

MARLON

0' 1'

2'

1/ 2"

' 0

0' 1'

3'

3/ 8"

' 0

0' 2'

4'

1/ 4"

' 0

0' 3'

6' 1'

3/

' 0

0' 4'

8' 2'1/

8"

' 0

0' 3'

3/

' 0

6' 0'

8'

4'1/

' 0

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

CONSTRUCTION - ISSUED FOR

BID

Project Number

Building Number

Drawing Number

340, 341

VA Building 340, 341 Project Title

Location

Issued Date Checked Drawn

Drawing Title Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

SCHEESER BUCKLEY MAYFIELD

1540 CORPORATE WOODS PARKWAY

UNIONTOWN, OHIO 44685

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

Approved:

PHILIP P. KIRK

CHIEF ENGINEER

2/

/2

2:

: 2

PM

C :\U se rs

\M Ky ag ab a\ D oc um en ts

\1

_M

EP

_C

E N

TR

AL

F

IL

E_ m ky ag ab a@ sb m c e

.c om

.rv t

EJ-103

552-20-104

Checker Designer

RENOVATE PRIMARY CARE FOR

PACT BLDG 340, BLDG 341

02/09/2021

4100 WEST THIRD STREET, DAYTON, OH 45428

PANELBOARD SCHEDULES

02/09/2021

10402 VA 10403 VA 7997 VA

83 SPARE 20 A 1 0 VA / 0 VA 1 20 A SPARE 84

81 SPARE 20 A 1 0 VA / 0 VA 1 20 A SPARE 82

79 SPARE 20 A 1 0 VA / 0 VA 1 20 A SPARE 80

77…