This document is a solicitation for the renovation of Primary Care PACT Buildings 340 and 341 located in Dayton, Ohio. The solicitation requires renovations to fire protection, plumbing, mechanical, and electrical systems including replacement of fire alarm, security, network, and medical equipment. Products and services must comply with industry standards and be provided by experienced contractors. The solicitation includes specifications for fire sprinklers, plumbing fixtures, HVAC equipment, electrical switches, medical imaging and records systems. Responses are due by June 7th, 2022 with award dates to be determined. The contract will be awarded by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FIRE PROTECTION NEW WORK GENERAL

NOTES

1. THE GENERAL NOTES LISTED HERE APPLY TO ALL FIRE PROTECTION DRAWINGS IN ADDITION TO ANY ADDITIONAL DRAWING NOTES ON

THE INDIVIDUAL DRAWINGS.

2. SEE CODED NOTES ON INDIVIDUAL DRAWING SHEETS FOR SPECIFIC INSTRUCTIONAL NOTES.

3. FIELD VERIFY EXISTING CONDITIONS PRIOR TO THE START OF CONSTRUCTION.

4. COORDINATE WITH GENERAL TRADES WORK, HVAC WORK, PLUMBING WORK, ELECTRICAL WORK AND OTHER WORK.

5. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS OF FIRE AND SMOKE WALLS AND RATED STRUCTURES. SEE DETAILS AND

SPECIFICATIONS FOR PIPE PENETRATION SEAL REQUIREMENTS.

6. REFER TO ARCHITECTURAL DRAWINGS FOR ROOM DESIGNATIONS INCLUDING ALL STORAGE AREAS. ALL STORAGE AREAS ARE TO BE

SPRINKLERED AS ORDINARY HAZARD PER N.F.P.A.

7. IT IS RECOGNIZED THAT DRAWINGS MAY BE PLOTTED AT DIFFERENT SCALES, SUCH THAT PLOTTED DRAWINGS MAY VARY FROM ACTUAL OR INTENDED DIMENSIONS. THEREFORE, DRAWINGS ARE DIAGRAMMATIC AND ARE NOT TO BE SCALED. SBM TAKES NO RESPONSIBILITY FOR ERRORS REGARDING DISCREPANCIES FROM THE ORIGINAL DRAWINGS DRAWN AT THE PROPER SCALE AND THOSE DRAWINGS THAT

HAVE BEEN PLOTTED.

8. THE FIRE PROTECTION DESIGN DRAWINGS ARE DIAGRAMMATIC AND ARE NOT INTENDED TO SHOW EXACT LOCATION OF EQUIPMENT AND PIPING UNLESS DIMENSIONS ARE GIVEN OR OTHERWISE IMPLIED FOR CLEARANCES, ETC. PIPING AND FIRE PROTECTION EQUIPMENT ARE TO BE INSTALLED ALONG THE GENERAL PLANS SHOWN ON THE DRAWINGS, BUT KEEPING IN MIND ACTUAL BUILDING CONDITIONS WHICH MUST BE CONFORMED WITH IN THE ACTUAL WORK. THIS CONTRACTOR TO BE AWARE OF LIMITED SPACE ABOVE CEILING FOR NEW WORK AND SHOULD MODIFY HIS WORK TO ACCOMMODATE OTHER TRADES. COORDINATE WORK WITH OTHER TRADES PRIOR TO MAKING THE FINAL INSTALLATION DRAWING OR SYSTEM INSTALLATION. THE CONTRACTORS IN THEIR BIDS ARE REQUIRED TO INCLUDE ALL LABOR AND MATERIALS AND OTHER RELATED WORK NECESSARY TO PROVIDE MINOR OFFSETS IN FIRE PROTECTION WORK AS REQUIRED TO AVOID CONFLICT WITH OTHER WORK ON THIS PROJECT, OR AS REQUIRED IN ORDER TO OBTAIN MAXIMUM HEAD ROOM OR EQUIPMENT ACCESS IN

SPACES.

9. THE FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR CUTTING, PATCHING, REMOVAL, AND RE-INSTALLATION OF WALL, CEILING, FLOORS, ETC. AND NEW MATERIALS FOR THE INSTALLATION OF THEIR RESPECTIVE WORK AS SHOWN ON THE DRAWINGS OR SPECIFICATIONS FOR AREAS OTHERWISE NOT INVOLVED IN THE GENERAL CONSTRUCTION WORK.

10. ALL SPRINKLER HEADS ARE TO BE QUICK RESPONSE TYPE.

11. ALL FIRE PROTECTION PIPING AND CONDUIT SHALL FOLLOW THE INSTALLATION REQUIREMENTS AS LISTED BELOW:

A. INSTALL TIGHT AGAINST BOTTOM OF ROOF AND FLOOR STRUCTURE.

B. INSTALL PARALLEL AND PERPENDICULAR TO BUILDING STRUCTURE.

C. INSTALL CONCEALED ABOVE CEILINGS OR INSIDE WALLS, UNLESS OTHERWISE NOTED.

12. SPRINKLER PIPING IS TO AVOID EQUIPMENT IN MECHANICAL ROOM. COORDINATE WITH H.C. AND E.C.

13. USE INTERMEDIATE LEVEL SPRINKLERS BELOW DUCTWORK AND STRUCTURAL MEMBERS, WHERE APPLICABLE.

14. GENERAL CONTRACTOR SHALL PAINT ALL EXPOSED FIRE PROTECTION PIPING INSIDE AND OUTSIDE BUILDING WITH COLOR AS

SELECTED BY ARCHITECT.

15. ALL VALVES, FLOW SWITCHES, AND ETC. ABOVE THE CEILING SHALL BE LABELED WITH ENGRAVED LAMINATE TAG ATTACHED TO CEILING GRID WITH PRESSURE SENSITIVE TAPE. THE (RED) LAMINATE TAG SHALL BE 1/2" WIDE WITH 1/4" HIGH ENGRAVED (WHITE)

LETTERS.

16. FIRE PROTECTION CONTRACTOR TO COORDINATE FINAL PLACEMENT OF SPRINKLER HEADS WITH REFLECTED CEILING PLANS.

SPRINKLER HEADS SHALL BE INSTALLED IN STRAIGHT AND PARALLEL LINES CENTERED IN A SYMMETRICAL AND UNIFORM PATTERN IN THE

CEILING TILES (TYP ALL HEADS).

17. SPRINKLER HEADS TO BE PROVIDED IN TYPES AND FINISHES TO MATCH EXISTING AREAS.

18. ALL WORK IS TO COMPLY WITH DESIGN AND INSTALLATION REQUIREMENTS PER NATIONAL FIRE PROTECTION AGENCY 13, AND THE

OWNER'S INSURANCE COMPANY. THE MOST STRINGENT REQUIREMENTS SHALL APPLY.

19. FIRE PROTECTION CONTRACTOR SHALL PERFORM WATER FLOW TEST PRIOR TO PERFORMING HYDRAULIC CALCULATIONS AND SPRINKLER LAYOUT. TEST TO MEET N.F.P.A. REQUIREMENTS. CONTRACTOR SHALL COORDINATE WHEN TEST IS TO BE PERFORMED WITH

OWNER AND COPY TEST RESULTS TO PROJECT ENGINEER AND OWNER.

20. FIRE PROTECTION CONTRACTOR SHALL HYDRAULICALLY CALCULATE AUTOMATIC SPRINKLER SYSTEM AND INSTALL NEW SYSTEM AS REQUIRED BY NEW CALCULATIONS AND DESIGN. THE FIRE PROTECTION CONTRACTOR SHALL DESIGN THE SYSTEM, SUBMIT AND ETC. AS

LISTED BELOW:

A. COMPLETE AND RETURN A/E AND STATE OF OHIO, DEPARTMENT OF INDUSTRIAL RELATIONS A COPY OF THE AUTOMATIC SPRINKLER SYSTEM SUPPLEMENT FORM FB-13; THE SUBMITTED PLANS AND CALCULATIONS MUST ALSO INDICATE THE CERTIFIED INDIVIDUAL

INSTALLING THE SPRINKLER SYSTEM TO COMPLY WITH SECTION 4101:2-1-22(D);

B. PLANS FOR THE SPRINKLER SYSTEM SHALL CONTAIN THE FOLLOWING INFORMATION RELATIVE TO THE WATER SUPPLY:

1. THE PLANS SHALL SHOW THE WATER SUPPLY REQUIREMENTS FOR THE HYDRAULICALLY MOST DEMANDING AREA. THE DESIGN CALCULATIONS SHALL SUBSTANTIATE THAT THE AVAILABLE WATER SUPPLY WILL FULFILL THE SYSTEM REQUIREMENTS.

2. THE WATER SUPPLY REQUIREMENTS SHALL BE DETERMINED ACCORDING TO HAZARD CLASSIFICATION AS OUTLINED IN N.F.P.A. 13.

3. WHEN SPRINKLER SYSTEMS ARE CONNECTED TO CITY WATER MAINS, FLOW TEST RESULTS SHALL BE SUBMITTED. THE PLANS SHALL SHOW THE FOLLOWING INFORMATION ON WATER FLOW DATA WITH EXISTING OR PROPOSED WATER SUPPLY, DEAD END OR CIRCULATING:

a. LOCATION AND ELEVATION OF STATIC AND RESIDUAL TEST GAGE WITH RELATION TO THE RISER REFERENCE POINT.

b. FLOW LOCATION.

c. STATIC PRESSURE, PSI

d. RESIDUAL PRESSURE, PSI

e. FLOW, GPM

f. DATE

g. TIME

h. TEST CONDUCTED BY OR INFORMATION SUPPLIED BY

i. PLOTTED GRAPH SHOWING WATER SUPPLY CURVES AND SYSTEM REQUIREMENTS IN ACCORDANCE WITH SECTIONS 6-3, 6-2.4, AND A-7-2.1

OF N.F.P.A. 13, APPROVED ADDITION.

21. FIRE MAIN TO BE HYDRAULICALLY CALCULATED AND SIZED TO DESIGN INSTALLATION REQUIREMENTS AS PER N.F.P.A., SECTIONS 13, 14, AND 24.

22. ALL OCCUPIED AREAS OF THE BUILDING ARE TO HAVE A WET PIPE SPRINKLER SYSTEM, HYDRAULICALLY CALCULATED AND SIZED TO DESIGN INSTALLATION REQUIREMENTS OF N.F.P.A. SECTIONS 13, 14 AND 24 FOR LIGHT HAZARD OCCUPANCY UNLESS NOTED OTHERWISE.

23. IF THE FIRE PROTECTION CONTRACTOR REQUIRES ACCESS PANELS, THE FIRE PROTECTION CONTRACTOR SHALL FURNISH THE ACCESS PANELS WITH INSTALLATION COSTS ASSUMED BY THE FIRE PROTECTION CONTRACTOR, BUT INSTALLED BY THE GENERAL CONTRACTOR.

ANY ACCESS PANELS PURCHASED DURING CONSTRUCTION BY THE FIRE PROTECTION CONTRACTOR SHALL MATCH THOSE ALREADY

PURCHASED BY THE GENERAL CONTRACTOR.

24. PROVIDE MINIMUM 15 DAYS NOTICE OF ANY UTILITY IN ADVANCE WITH THE OWNER. ACCOMPLISH DRAIN DOWN AND RE-FILL OF PIPING

SYSTEMS AS REQUIRED.

25. PRIOR TO CONSTRUCTION, THE FIRE SUPPRESSION CONTRACTOR OF RECORD SHALL SUBMIT IN WRITING TO THE OWNER AND DESIGN TEAM THEIR MEANS AND METHODS OF CONSTRUCTION TO MAINTAIN OPERATION OF SPRINKLER SYSTEM WITHIN THE RENOVATION AREAS DURING CONSTRUCTION AND TO THE ADJACENT AREAS SERVED BY THIS SPRINKLER SYSTEM. THE REPORT SHALL INCLUDE BUT IS NOT LIMITED TO HOW TIE-INS SHALL INCUR AND THE TIME REQUIRED TO MAKE THESE CONNECTIONS, KEEPING IN MIND THAT DOWN TIME SHALL BE KEPT AT A MINIMUM. THE AUTOMATIC SPRINKLER SYSTEM SHALL REMAIN ACTIVE TO SERVE THIS AREA AT ALL TIMES EXCEPT AS ALLOWED BY THE FIRE MARSHALL AND OWNER FOR SYSTEM TIE-INS. CONTRACTOR IS RESPONSIBLE FOR:

A. COMPLETELY REMOVING EXISTING SYSTEM WITHIN PROJECT LIMITS (ALL FIRE MAINS, SPRINKLER PIPING, FITTINGS, SPRINKLER HEADS, HANGERS AND SUPPORTS, ETC.). THE OWNER SHALL HAVE SALVAGE RIGHTS TO ANY ITEM REMOVED FROM THE SYSTEM AND ALL OTHER

ITEMS SHALL BE REMOVED FROM SITE.

B. INSTALLING TEMPORARY SYSTEM TO FULLY PROTECT AREA DURING CONSTRUCTION AND TIE-INS TO EXISTING SYSTEM OUTSIDE

PROJECT LIMITS.

C. INSTALLING NEW SYSTEM AND TIE-INS TO EXISTING SYSTEM OUTSIDE OF PROJECT LIMITS. THE NEW SPRINKLER SYSTEM SHALL CONSIST OF ALL NEW PIPING, FITTINGS, SPRINKLER HEADS, AND HANGERS AND SUPPORTS. COORDINATE EXTEND OF WORK WITH

ARCHITECTURAL CEILING PLANE.

26. REFER TO STRUCTURAL PLANS FOR SEISMIC DESIGN CATEGORY.

WALL SECTION

FLOOR SECTION

FURNISH AND INSTALL

FIRESTOP MATERIALS IN

ACCORDANCE WITH

APPROPRIATE U.L. SYSTEMS

TO MAINTAIN FIRE RESISTANCE

RATING

PIPE SLEEVE

DAMMING MATERIAL

(PER U.L. TESTED

SYSTEM DESIGN)

FLOOR SLAB; SEE

ARCHITECTURAL DRAWINGS

FOR FLOOR CONSTRUCTION

AND FIRE RATING

PIPE INSULATION WITH PVC

JACKET (WHERE SPECIFIED)

PIPING WITH FREEZE PROTECTION

SELF-REGULATING HEATING CABLE

(WHERE SPECIFIED)

FURNISH AND INSTALL FIRESTOP

MATERIALS IN ACCORDANCE WITH

APPROPRIATE U.L. SYSTEMS TO

MAINTAIN FIRE RESISTANCE RATING

PIPE SLEEVE (SLEEVE TO

EXTEND 2" ABOVE FLOOR

IN MECHANICAL EQUIPMENT

ROOMS.)

SEAL JOINT BETWEEN SLEEVE

AND FLOOR SLAB WITH MIN. 1/2"

BEAD FIRESTOP CAULK

SEE ARCHITECTURAL

DRAWINGS FOR WALL

CONSTRUCTION AND FIRE

RATING

PIPING WITH FREEZE PROTECTION

SELF-REGULATING HEATING CABLE

(WHERE SPECIFIED)

PIPE INSULATION WITH PVC

JACKET (WHERE SPECIFIED)

NOTES:

1. WHERE PIPES, DUCTS AND OTHER COMPONENTS PASS THROUGH FIRE OR SMOKE RATED WALLS OR FLOORS, PROVIDE NON-ASBESTOS SEAL ASSEMBLIES CLASSIFIED BY U.L. TO PROVIDE FIRE BARRIERS EQUAL TO OR GREATER THAN THE TIME RATING OF THE CONSTRUCTION BEING PENETRATED, WITH APPROPRIATE MATERIALS AND SYSTEMS THAT COMPLY WITH APPLICABLE CODES AND THAT HAVE BEEN

TESTED IN ACCORDANCE WITH U.L. 1479 OR ASTM E814.

2. GROUT, MORTAR OR GYPSUM BASED PRODUCTS SHALL NOT BE INSTALLED IN LIEU OF FIRESTOPPING

MATERIALS AND U.L. SYSTEMS.

3. FOR SLEEVED PENETRATIONS, FIRESTOP ANNULAR SPACE, IF ANY, BETWEEN SLEEVE AND ADJACENT

CONSTRUCTION TO MEET U.L. SYSTEM REQUIREMENTS. SEE NOTE 2 ABOVE.

4. THIS CONTRACTOR SHALL FIRESTOP ALL MISCELLANEOUS OPENINGS IN FIRE-RATED CONSTRUCTION

RESULTING FROM HIS WORK.

5. CONTRACTOR SHALL PROVIDE SUBMITTAL DRAWINGS TO ARCHITECT, INCLUDING U.L. RATED SYSTEM

NUMBER AND DETAIL FOR EACH TYPE OF PENETRATION AND CONFIGURATION.

6. THE FIRESTOPPING SYSTEMS ARE TO BE INSTALLED BY EXPERIENCED, MANUFACTURER TRAINED, AND

UL CERTIFIED OR FM CERTIFIED PERSONNEL.

7. ALL FIRESTOPPING MATERIAL IS TO BE PROVIDED FROM A SINGLE MANUFACTURER FOR ALL

APPLICATIONS.

8. CONTRACTOR SHALL CONSULT MANUFACTURER'S TECHNICAL EXPERTS FOR ASSISTANCE IN SELECTING

APPROPRIATE FIRESTOPPING SYSTEM FOR EACH APPLICATION.

THROUGH FIRE-RATED CONSTRUCTIONS

N.T.S.

FIRESTOPPING DETAIL FOR PENETRATIONS

HOSE ADAPTOR CONNECTION

WITH END CAP

1" SIGHT GLASS

INSPECTOR'S TEST VALVE

TO SPRINKLER SYSTEM

FLOW SWITCH

WIRE TO FIRE ALARM

PANEL (BY E.C.)

O.S. & Y. VALVE WITH

TAMPER SWITCH

SYSTEM RISER

SEE FLOOR PLAN

FOR EXACT LOCATION

OF PIPING

SPRINKLER CONNECTION DETAIL

N.T.S.

" M

IN

#57 COARSE AGGREGATE

4" Ø x 12" LONG

PVC LEG

BALL DRIP

18" x 18" x 18"

CONCRETE PAD

GRADE

SIDEWALK SIAMESE

SIDEWALK SIAMESE DETAIL

N.T.S.

6"

DESCRIPTIONABBREVIATION SYMBOL

AS

F

FIRE SUPPRESSION SYMBOL LEGEND

AS AUTOMATIC SPRINKLER LINE

FIRE LINE

FLOW SWITCH - AUTOMATIC SPRINKLERS

VALVE WITH TAMPER SWITCH (SEE SPECIFICATIONS FOR TYPE)

PIPE SLEEVE (SEE SPECIFICATIONS FOR ADDIT. REQUIREMENTS)

VIBRATION CONNECTION (SEE SPECIFICATIONS)

PRESSURE GAUGE WITH GAUGE COCK (WATER)

PRESSURE GAUGE WITH BALL VALVE (WATER)

E.C. E.C. ELECTRICAL CONTRACTOR

F.S.C. F.S.C. FIRE SUPPRESSION CONTRACTOR

G.C. G.C. GENERAL CONTRACTOR

H.C. H.C. HVAC CONTRACTOR

P.C. P.C. PLUMBING CONTRACTOR

MFR. MFR. MANUFACTURER

N.C. N.C. NORMALLY CLOSED

TYP. TYP. TYPICAL

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

RE G IS T E RE

D

E-62197

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

CONSTRUCTION - ISSUED FOR

BID

Project Number

Building Number

Drawing Number

340, 341

VA Building 340, 341 Project Title

Location

Issued Date Checked Drawn

Drawing Title Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

SCHEESER BUCKLEY MAYFIELD

1540 CORPORATE WOODS PARKWAY

UNIONTOWN, OHIO 44685

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

Approved:

PHILIP P. KIRK

CHIEF ENGINEER

2/

/2

2:

: 5

PM

C :\U se rs

\J Bi lin s k i\D oc um en ts \1

_M E

P_ C

EN

TR

A L

FI

LE

_j bi lin sk i@ sb m ce

.c om

.rv t

FJ-100

552-20-104

CJS JMB

RENOVATE PRIMARY CARE FOR

PACT BLDG 340, BLDG 341

02/09/2021

4100 WEST THIRD STREET, DAYTON, OH 45428

FIRE SUPPRESSION GENERAL NOTES,

SYMBOL LEGEND AND DETAILS

02/09/2021

FIRE DEPARTMENT

CONNECTION NEW FREESTANDING FIRE DEPARMENT CONNECTION TO MATCH EXISTING INLET THREAD TYPE AND STYLE. COORDINATE WITH LOCAL FIRE DEPARTMENT.

SUPERVISORY SWITCH PROVIDE SIZES AND TYPES WHICH MATE AND MATCH PIPING AND CONNECTIONS, UL-LISTED.

FLOW SWITCH PROVIDE SIZES AND TYPES WHICH MATE AND MATCH PIPING AND CONNECTIONS, UL-LISTED.

DESCRIPTION REMARKS

FIRE PROTECTION SCHEDULE

Revisions Date

CONSTRUCTION - ISSUED FOR BID 02/09/2021

PLAN NOTES

A. SEE SHEET FJ-100 FOR GENERAL NOTES AND SYMBOL LEGEND.

B. EXISTING PIPING AND EQUIPMENT SHOWN WITH LIGHT LINES.

C. EXISTING PIPING AND EQUIPMENT TO BE REMOVED SHOWN WITH DARK DASHED LINES.

D. REFER TO ARCHITECTURAL PLANS FOR PHASING AND SUB-PHASING AREAS OF WORK.

E. ACCESS TO ALL AREAS OUTSIDE OF PHASE AND SUB-PHASE CONSTRUCTION AREAS

INDICATED TO BE FULLY ACCESSIBLE TO STAFF AND PATIENTS THROUGH OUT NORMAL WORKING HOURS. ALL LIMITED SCOPE SUPPORTING ACTIVITIES TO BE COORDINATED WITH THE VA COR.

ALL WORK DEEMED DISRUPTIVE BY COR TO BE CONDUCTED OUTSIDE NORMAL WORKING HOURS

(7:30 AM TO 5:00 PM).

CODED NOTES

1. EXISTING FIRE DEPARTMENT CONNECTION TO BE REMOVED. DISCONNECT AND REMOVE

ASSOCIATED FIRE PIPING BACK TO MAIN FOR RECONNECTION UNDER NEW WORK.

2. EXISTING DRAIN TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED DRAIN PIPING

BACK TO MAIN FOR RECONNECTION UNDER NEW WORK.

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

RE G IS T E RE

D

E-62197

0' 1'

2'

1/ 2"

' 0

0' 1'

3'

3/ 8"

' 0

0' 2'

4'

1/ 4"

' 0

0' 3'

6' 1'

3/

' 0

0' 4'

8' 2'1/

8"

' 0

0' 3'

3/

' 0

6' 0'

8'

4'1/

' 0

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

CONSTRUCTION - ISSUED FOR

BID

Project Number

Building Number

Drawing Number

340, 341

VA Building 340, 341 Project Title

Location

Issued Date Checked Drawn

Drawing Title Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

SCHEESER BUCKLEY MAYFIELD

1540 CORPORATE WOODS PARKWAY

UNIONTOWN, OHIO 44685

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

Approved:

PHILIP P. KIRK

CHIEF ENGINEER

2/

/2

1:

: 2

PM

C :\U se rs

\J Bi lin s k i\D oc um en ts \1

_M E

P_ C

EN

TR

A L

FI

LE

_j bi lin sk i@ sb m ce

.c om

.rv t

FD-100

552-20-104

CJS JMB

RENOVATE PRIMARY CARE FOR

PACT BLDG 340, BLDG 341

02/09/2021

4100 WEST THIRD STREET, DAYTON, OH 45428

DEMOLITION - FIRST FLOOR PLAN - FIRE

PROTECTION

02/09/2021

N 1/8" = 1'-0"

DEMOLITION - FIRST FLOOR PLAN - FIRE SUPPRESSION PHASE 1

121121A120119

EX-185

EX-186

PAC121

C-1-11

190 191 192

C-1-12

EX-183a

EX-183 EX-122

EX-121 EX-120

EX-119 1

EX-138

EX-137

EX-136

EX-182

EX-181

EX-180

EX-179

EX-184

EX-123

EX-124

EX-125

EX-131

EX-130

EX-129

EX-132

EX-133

EX-134

EX-178

EX-177

EX-176

EX-175

EX-174

EX-173

EX-187 EX-126A EX-126

EX-188

EX-128

EX-127

EX-167a

EX-155 EX-154 EX-153

EX-189

EX-152

EX-190

EX-151

EX-191

EX-192 EX-193

EX-156

EX-157

EX-158

EX-161

EX-160

EX-159

EX-163

EX-164

EX-148 EX-147 EX-146 EX-145

EX-144 EX-143

EX-142

EX-101

EX

-1

611 11

CODED NOTES

1. 4" FIRE LINE. TIE INTO EXISTING FIRE LINE SERVING FIRE DEPARTMENT CONNECTION AT POINT

INDICATED.

2. 4" FIRE LINE DOWN TO BELOW GRADE.

3. REMOVE EXISTING SPRINKLER HEAD AND INSTALL NEW SPRINKLER HEAD AS REQUIRED FOR

REMOVAL OF EXISTING CEILING AND INSTALLATION OF NEW CEILING WITHIN HATCHED AREA.

REMOVE/EXTEND EXISTING AS PIPING AS REQUIRED FOR NEW HEAD LOCATION.

4. PRIOR TO CONSTRUCTION, THE FIRE PROTECTION CONTRACTOR OF RECORD SHALL SUBMIT

IN WRITING TO THE OWNER AND DESIGN TEAM THEIR MEANS AND METHODS OF CONSTRUCTION

TO MAINTAIN OPERATION OF THE SPRINKLER SYSTEM WITHIN THIS RENOVATION AREA DURING

CONSTRUCTION AND TO THE ADJACENT AREAS SERVED BY THIS SPRINKLER SYSTEM. THE

REPORT SHALL INCLUDE BUT IS NOT LIMITED TO HOW TIE-INS SHALL INCUR AND THE TIME

REQUIRED TO MAKE THESE CONNECTIONS, KEEPING IN MIND THAT DOWN TIME SHALL BE KEPT

AT A MINIMUM. THE AUTOMATIC SPRINKLER SYSTEM SHALL REMAIN ACTIVE TO SERVE THIS AREA

AT ALL TIMES EXCEPT AS ALLOWED BY THE FIRE MARSHAL AND OWNER FOR SYSTEM TIE-INS.

CONTRACTOR IS RESPONSIBLE FOR:

A. COMPLETELY REMOVING EXISTING SYSTEM WITHIN PROJECT LIMITS (ALL FIRE MAINS,

SPRINKLER PIPING, FITTINGS, SPRINKLER HEADS, HANGERS AND SUPPORTS, ETC.) THE OWNER SHALL HAVE SALVAGE RIGHTS TO ANY ITEM REMOVED FROM THE SYSTEM AND ALL OTHER ITEMS

SHALL BE REMOVED FROM THE SITE.

B. INSTALLING TEMPORARY SYSTEM TO FULLY PROTECT AREA DURING CONSTRUCTION AND TIE-

INS TO EXISTING SYSTEMS OUTSIDE OF PROJECT LIMITS. CONTRACTOR TO REFER TO

ARCHITECTURAL PLANS FOR LOCATIONS OF TEMPORARY CONSTRUCTION BARRIERS.

C. INSTALLING NEW SYSTEM AND TIE-INS TO EXISTING SYSTEMS OUTSIDE OF PROJECT LIMITS.

THE NEW SPRINKLER SYSTEM SHALL CONSIST OF ALL NEW PIPING, FITTINGS, SPRINKLER HEADS, AND HANGERS AND SUPPORTS. THE NEW SYSTEM IS TO BE HYDRAULICALLY CALCULATED AND

SIZED FOR WET PIPE SYSTEM. DESIGN AND INSTALL IN ACCORDANCE WITH N.F.P.A. 13 (2019

EDITION LIGHT HAZARD OCCUPANCY (UNLESS NOTED OTHERWISE). COORDINATE EXTENT OF

WORK WITH ARCHITECTURAL REFLECTED CEILING PLAN.

5. EXTEND AUTOMATIC SPRINKLER SYSTEM TO WITHIN HATCHED AREA. INSTALL NEW

SPRINKLER HEADS IN NEW CEILINGS. SYSTEM IS TO BE HYDRAULICALLY CALCULATED AND SIZED

FOR WET PIPE SYSTEM IN ACCORDANCE WITH NFPA 13 (2019 EDITION).

6. TIE NEW AS PIPING INTO EXISTING AS PIPING AT POINT INDICATED.

7. FIRE DEPARTMENT CONNECTION, SEE DETAIL.

8. TIE NEW DRAIN LINE INTO EXISTING DRAIN LINE IN EXISTING ROOM, MATCH EXISTING LINE SIZE.

9. EXTEND DRAIN LINE DOWN ALONG WALL, ROUTE PIPING TO OUTDOORS. TERMINATE PIPING

12" ABOVE GRADE WITH TURNED DOWN ELBOW AND DISCHARGE ONTO SPLASH BLOCK.

10. SPRINKLER ZONE BOUNDRY.

11. ORDINARY HAZARD GROUP 2.

12. NO WORK THIS ROOM.

PLAN NOTES

A. SEE SHEET FJ-100 FOR GENERAL NOTES, SYMBOL LEGEND AND DETAILS.

B. EXISTING PIPING AND EQUIPMENT SHOWN WITH LIGHT LINES.

C. NEW PIPING AND EQUIPMENT SHOWN WITH DARK LINES.

D. REFER TO ARCHITECTURAL PLANS FOR PHASING AND SUB-PHASING AREAS OF WORK.

E. ACCESS TO ALL AREAS OUTSIDE OF PHASE AND SUB-PHASE CONSTRUCTION AREAS

INDICATED TO BE FULLY ACCESSIBLE TO STAFF AND PATIENTS THROUGH OUT NORMAL WORKING HOURS. ALL LIMITED SCOPE SUPPORTING ACTIVITIES TO BE COORDINATED WITH THE VA COR.

ALL WORK DEEMED DISRUPTIVE BY COR TO BE CONDUCTED OUTSIDE NORMAL WORKING HOURS

(7:30 AM TO 5:00 PM).

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

RE G IS T E RE

D

E-62197

0' 1'

2'

1/ 2"

' 0

0' 1'

3'

3/ 8"

' 0

0' 2'

4'

1/ 4"

' 0

0' 3'

6' 1'

3/

' 0

0' 4'

8' 2'1/

8"

' 0

0' 3'

3/

' 0

6' 0'

8'

4'1/

' 0

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

CONSTRUCTION - ISSUED FOR

BID

Project Number

Building Number

Drawing Number

340, 341

VA Building 340, 341 Project Title

Location

Issued Date Checked Drawn

Drawing Title Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

SCHEESER BUCKLEY MAYFIELD

1540 CORPORATE WOODS PARKWAY

UNIONTOWN, OHIO 44685

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

Approved:

PHILIP P. KIRK

CHIEF ENGINEER

2/

/2

1:

: 3

PM

C :\U se rs

\J Bi lin s k i\D oc um en ts \1

_M E

P_ C

EN

TR

A L

FI

LE

_j bi lin sk i@ sb m ce

.c om

.rv t

FX-100

552-20-104

CJS JMB

RENOVATE PRIMARY CARE FOR

PACT BLDG 340, BLDG 341

02/09/2021

4100 WEST THIRD STREET, DAYTON, OH 45428

FIRST FLOOR PLAN - FIRE SUPPRESSION

PHASE 1

02/09/2021

N 1/8" = 1'-0"

FIRST FLOOR PLAN - FIRE SUPPRESSION PHASE 1

ROOM LEGEND

Number Name

1 TEMP. LOCKERS 1

2 TEMP. LOCKERS 2

070 T.R.

071 T.R.

072 VENDING

100 VESTIBULE

118 STAFF T.R.

119 HEALTH BEHAV. COORD.

120 DIETICIAN

121 TVC/FLOAT

121A STAFF T.R.

133 MSA SUPERVISOR

134 WAITING

135 EXISTING WAITING AREA

136 KIOSK

137 EX. VESTIBULE

140 SCALES

141 EXAM

171 EXAM

172 EXAM

173 EXAM

174 T.R.

175 SUPPLY

188 MSA

189 PACT

190 STAFF T.R.

191 SOIL

192 CLEAN

193 MED

C-1-4 CORRIDOR

C-1-11 CORRIDOR

C-1-12 CORRIDOR

EX-100 MECH

EX-101 OFFICE

EX-119 OFFICE

EX-120 STORE

EX-121 PSYCH

EX-122 PSYCH

EX-123 EXAM 17

EX-124 EXAM 18

EX-125 EXAM 19

EX-126 CLOSET

EX-126A CLOSET

EX-127 STORAGE

EX-128 SOILED LINEN/UTIL.

EX-129 EXAM 14

EX-130 EXAM 15

EX-131 EXAM 16

EX-132 EXAM 11

EX-133 EXAM 12

EX-134 EXAM 13

EX-136 EXAM 1

EX-137 EXAM 2

EX-138 EXAM 3

EX-142 EXAM

EX-143 EXAM

EX-144 EXAM

EX-145 EXAM

EX-146 EXAM

EX-147 EXAM

EX-148 EXAM

EX-151 TLT.

EX-152 EXAM

EX-153 CLEAN LINEN

EX-154 PT

EX-155 TELE. TRIAGE

EX-156 EXAM

EX-157 EXAM

EX-158 EXAM

EX-159 EXAM

EX-160 EXAM

EX-161 EXAM

EX-163 EXAM

EX-164 EXAM

EX-167a NURSE STATION

EX-173 M.D. OFFICE

EX-174 M.D. OFFICE

EX-175 M.D. OFFICE

EX-176 M.D. OFFICE

EX-177 OFFICE

EX-178 CLOSET

EX-179 MD OFFICE

EX-180 MD OFFICE

EX-181 MD OFFICE

EX-182 OFFICE

EX-183 SEC.

EX-183a CHIEF'S OFFICE

EX-184 PROGRAM SUPPORT

EX-185 OFFICE

EX-186 MD OFFICE

EX-187 CLOSET

EX-188 STORAGE

EX-189 N.P. OFFICE

EX-190 M.D. OFFICE

EX-191 NURSE MANAGER

EX-192 STAFF

EX-193 STAFF

PAC121 RECEPTION

118117116115114 113112

C-1-6

C-1-8

145146

155 165

153 163

C-1-5

C-1-7

C-1-9

C-1-2

120 121A 121 EX-125

EX-100E

EX-104

EX-103

EX-138

EX-132

EX-133

EX-134

EX-137

EX-136

192 193

EX-163

EX-164

EX-157

EX-160

EX-158

EX-159

C-1-11

C-1-12

EX-148

X-147 EX-146 EX-145 EX-144 EX-143 EX-142

EX-101

EX

-1

PAC121

CODED NOTES

1. PRIOR TO CONSTRUCTION, THE FIRE PROTECTION CONTRACTOR OF RECORD SHALL SUBMIT

IN WRITING TO THE OWNER AND DESIGN TEAM THEIR MEANS AND METHODS OF CONSTRUCTION

TO MAINTAIN OPERATION OF THE SPRINKLER SYSTEM WITHIN THIS RENOVATION AREA DURING

CONSTRUCTION AND TO THE ADJACENT AREAS SERVED BY THIS SPRINKLER SYSTEM. THE

REPORT SHALL INCLUDE BUT IS NOT LIMITED TO HOW TIE-INS SHALL INCUR AND THE TIME

REQUIRED TO MAKE THESE CONNECTIONS, KEEPING IN MIND THAT DOWN TIME SHALL BE KEPT

AT A MINIMUM. THE AUTOMATIC SPRINKLER SYSTEM SHALL REMAIN ACTIVE TO SERVE THIS AREA

AT ALL TIMES EXCEPT AS ALLOWED BY THE FIRE MARSHAL AND OWNER FOR SYSTEM TIE-INS.

CONTRACTOR IS RESPONSIBLE FOR:

A. COMPLETELY REMOVING EXISTING SYSTEM WITHIN PROJECT LIMITS (ALL FIRE MAINS,

SPRINKLER PIPING, FITTINGS, SPRINKLER HEADS, HANGERS AND SUPPORTS, ETC.) THE OWNER SHALL HAVE SALVAGE RIGHTS TO ANY ITEM REMOVED FROM THE SYSTEM AND ALL OTHER ITEMS

SHALL BE REMOVED FROM THE SITE.

B. INSTALLING TEMPORARY SYSTEM TO FULLY PROTECT AREA DURING CONSTRUCTION AND TIE-

INS TO EXISTING SYSTEMS OUTSIDE OF PROJECT LIMITS. CONTRACTOR TO REFER TO

ARCHITECTURAL PLANS FOR LOCATIONS OF TEMPORARY CONSTRUCTION BARRIERS.

C. INSTALLING NEW SYSTEM AND TIE-INS TO EXISTING SYSTEMS OUTSIDE OF PROJECT LIMITS.

THE NEW SPRINKLER SYSTEM SHALL CONSIST OF ALL NEW PIPING, FITTINGS, SPRINKLER HEADS, AND HANGERS AND SUPPORTS. THE NEW SYSTEM IS TO BE HYDRAULICALLY CALCULATED AND

SIZED FOR WET PIPE SYSTEM. DESIGN AND INSTALL IN ACCORDANCE WITH N.F.P.A. 13 (2019

EDITION LIGHT HAZARD OCCUPANCY (UNLESS NOTED OTHERWISE). COORDINATE EXTENT OF

WORK WITH ARCHITECTURAL REFLECTED CEILING PLAN.

2. SPRINKLER ZONE BOUNDRY.

3. REMOVE EXISTING SPRINKLER HEAD AND INSTALL NEW SPRINKLER HEAD AS REQUIRED FOR

REMOVAL OF EXISTING CEILING AND INSTALLATION OF NEW CEILING WITHIN HATCHED AREA.

REMOVE/EXTEND EXISTING AS PIPING AS REQUIRED FOR NEW HEAD LOCATION.

PLAN NOTES

A. SEE SHEET FJ-100 FOR GENERAL NOTES, SYMBOL LEGEND AND DETAILS.

B. REFER TO ARCHITECTURAL PLANS FOR PHASING AND SUB-PHASING AREAS OF WORK.

C. ACCESS TO ALL AREAS OUTSIDE OF PHASE AND SUB-PHASE CONSTRUCTION AREAS

INDICATED TO BE FULLY ACCESSIBLE TO STAFF AND PATIENTS THROUGH OUT NORMAL WORKING HOURS. ALL LIMITED SCOPE SUPPORTING ACTIVITIES TO BE COORDINATED WITH THE VA COR.

ALL WORK DEEMED DISRUPTIVE BY COR TO BE CONDUCTED OUTSIDE NORMAL WORKING HOURS

(7:30 AM TO 5:00 PM).

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

RE G IS T E RE

D

E-62197

0' 1'

2'

1/ 2"

' 0

0' 1'

3'

3/ 8"

' 0

0' 2'

4'

1/ 4"

' 0

0' 3'

6' 1'

3/

' 0

0' 4'

8' 2'1/

8"

' 0

0' 3'

3/

' 0

6' 0'

8'

4'1/

' 0

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

CONSTRUCTION - ISSUED FOR

BID

Project Number

Building Number

Drawing Number

340, 341

VA Building 340, 341 Project Title

Location

Issued Date Checked Drawn

Drawing Title Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

SCHEESER BUCKLEY MAYFIELD

1540 CORPORATE WOODS PARKWAY

UNIONTOWN, OHIO 44685

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

Approved:

PHILIP P. KIRK

CHIEF ENGINEER

2/

/2

1:

: 3

PM

C :\U se rs

\J Bi lin s k i\D oc um en ts \1

_M E

P_ C

EN

TR

A L

FI

LE

_j bi lin sk i@ sb m ce

.c om

.rv t

FX-101

552-20-104

CJS JMB

RENOVATE PRIMARY CARE FOR

PACT BLDG 340, BLDG 341

02/09/2021

4100 WEST THIRD STREET, DAYTON, OH 45428

FIRST FLOOR PLAN - FIRE SUPPRESSION

PHASE 2

02/09/2021

N 1/8" = 1'-0"

FIRST FLOOR PLAN - FIRE SUPPRESSION PHASE 2

ROOM LEGEND

Number Name

139 NURSE MANAGER

C-1-10 CORRIDOR

070 T.R.

071 T.R.

072 VENDING

100 VESTIBULE

111 CHIEF

112 ASST. CHIEF

113 ADMIN. OFFICER

114 CHIEF NURSE

115 DIABETES ED

116 NURSE PRACT./ DIABET.

117 NURSE PRACT./ DIABET.

118 STAFF T.R.

119 HEALTH BEHAV. COORD.

120 DIETICIAN

121 TVC/FLOAT

121A STAFF T.R.

122 HAC

123 ELECT.

124 DATA

126 CONFERENCE/BREAK

127 LOCKERS

128 STAFF T.R.

129 KITCHEN

130 PRIMARY CARE CALL CENTER

131 TELEPHONE NURSE TRIAGE

132 MSA SUPERVISOR

133 MSA SUPERVISOR

134 WAITING

135 EQUIP/SUPPLY STORAGE

135 EXISTING WAITING AREA

136 ADMIN OPEN

137 NURSE MANAGER

138 NURSE MANAGER

139 NURSE MANAGER

140 SCALES

141 EXAM

142 T.R.

143 PROCEDURE

144 EQUIP/SUPPLY STORAGE

145 T.R.

146 T.R.

147 MENTAL HEALTH

148 MENTAL HEALTH

149 MENTAL HEALTH

152 EXAM

153 EXAM

154 EXAM

155 EXAM

156 PHARMACY

157 PHARMACY

158 MENTAL HEALTH

162 T.R.

163 EXAM

164 EXAM

165 EXAM

171 EXAM

172 EXAM

173 EXAM

174 T.R.

175 SUPPLY

188 MSA

189 PACT

190 STAFF T.R.

191 SOIL

192 CLEAN

193 MED

C-1-2 CORRIDOR

C-1-5 CORRIDOR

C-1-6 CORRIDOR

C-1-7 CORRIDOR

C-1-8 CORRIDOR

C-1-9 CORRIDOR

C-1-11 CORRIDOR

C-1-12 CORRIDOR

EX-100 MECH

EX-100E VESTIBULE

EX-101 OFFICE

EX-103 WOMEN

EX-104 MEN

EX-125 OFFICE

EX-132 EXAM 11

EX-133 EXAM 12

EX-134 EXAM 13

EX-136 EXAM 1

EX-137 EXAM 2

EX-138 EXAM 3

EX-142 EXAM

EX-143 EXAM

EX-144 EXAM

EX-145 EXAM

EX-146 EXAM

EX-148 EXAM

EX-157 EXAM

EX-158 EXAM

EX-159 EXAM

EX-160 EXAM

EX-163 EXAM

EX-164 EXAM

PAC121 RECEPTION

X-147 EXAM

100E

100D

C-1-1

C-1-2

C-1-7

C-1-3

124 EX-103

EX-104

C-1-5

C-1-10

C-1-4

169159

C-1-9

180 181

182 183 184 185

C-1-12

112 113 114

117 118 119 120 121A

EX-125 108

EX-109

EX-110

193192191190

162152

153 163

165155

C-1-6127

C-1-8

135 146

141138

139 140 188

C-1-11

PAC121

CODED NOTES

1. REMOVE EXISTING SPRINKLER HEAD AND INSTALL NEW SPRINKLER HEAD AS REQUIRED FOR

REMOVAL OF EXISTING CEILING AND INSTALLATION OF NEW CEILING WITHIN HATCHED AREA.

REMOVE/EXTEND EXISTING AS PIPING AS REQUIRED FOR NEW HEAD LOCATION.

2. SPRINKLER ZONE BOUNDRY.

PLAN NOTES

A. SEE SHEET FJ-100 FOR GENERAL NOTES, SYMBOL LEGEND AND DETAILS.

B. NO WORK SHALL BE COMPLETED IF ALTERNATE 5 IS ACCEPTED.

C. REFER TO ARCHITECTURAL PLANS FOR PHASING AND SUB-PHASING AREAS OF WORK.

D. ACCESS TO ALL AREAS OUTSIDE OF PHASE AND SUB-PHASE CONSTRUCTION AREAS

INDICATED TO BE FULLY ACCESSIBLE TO STAFF AND PATIENTS THROUGH OUT NORMAL WORKING HOURS. ALL LIMITED SCOPE SUPPORTING ACTIVITIES TO BE COORDINATED WITH THE VA COR.

ALL WORK DEEMED DISRUPTIVE BY COR TO BE CONDUCTED OUTSIDE NORMAL WORKING HOURS

(7:30 AM TO 5:00 PM).

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

RE G IS T E RE

D

E-62197

0' 1'

2'

1/ 2"

' 0

0' 1'

3'

3/ 8"

' 0

0' 2'

4'

1/ 4"

' 0

0' 3'

6' 1'

3/

' 0

0' 4'

8' 2'1/

8"

' 0

0' 3'

3/

' 0

6' 0'

8'

4'1/

' 0

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

CONSTRUCTION - ISSUED FOR

BID

Project Number

Building Number

Drawing Number

340, 341

VA Building 340, 341 Project Title

Location

Issued Date Checked Drawn

Drawing Title Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

SCHEESER BUCKLEY MAYFIELD

1540 CORPORATE WOODS PARKWAY

UNIONTOWN, OHIO 44685

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

Approved:

PHILIP P. KIRK

CHIEF ENGINEER

2/

/2

1:

: 4

PM

C :\U se rs

\J Bi lin s k i\D oc um en ts \1

_M E

P_ C

EN

TR

A L

FI

LE

_j bi lin sk i@ sb m ce

.c om

.rv t

FX-102

552-20-104

CJS JMB

RENOVATE PRIMARY CARE FOR

PACT BLDG 340, BLDG 341

02/09/2021

4100 WEST THIRD STREET, DAYTON, OH 45428

FIRST FLOOR PLAN - FIRE SUPPRESSION

PHASE 3

02/09/2021

N 1/8" = 1'-0"

FIRST FLOOR PLAN - FIRE SUPPRESSION PHASE 3

ROOM LEGEND

Number Name

070 T.R.

071 T.R.

072 VENDING

100 VESTIBULE

100D VESTIBULE

100E VESTIBULE

101 VENDING

102 ROTUNDA / CONF.

103 CLASSROOM / CONF.

104 VESTIBULE

105 VENDING

108 OFFICE

111 CHIEF

112 ASST. CHIEF

113 ADMIN. OFFICER

114 CHIEF NURSE

115 DIABETES ED

116 NURSE PRACT./ DIABET.

117 NURSE PRACT./ DIABET.

118 STAFF T.R.

119 HEALTH BEHAV. COORD.

120 DIETICIAN

121 TVC/FLOAT

121A STAFF T.R.

122 HAC

123 ELECT

124 DATA

126 CONFERENCE/BREAK

127 LOCKERS

128 STAFF T.R.

129 KITCHEN

130 PRIMARY CARE CALL CENTER

131 TELEPHONE NURSE TRIAGE

132 MSA SUPERVISOR

133 MSA SUPERVISOR

134 WAITING

135 EQUIP/SUPPLY STORAGE

135 EXISTING WAITING AREA

136 ADMIN OPEN

137 NURSE MANAGER

138 NURSE MANAGER

139 NURSE MANAGER

140 SCALES

141 EXAM

142 T.R.

143 PROCEDURE

144 EQUIP/SUPPLY STORAGE

145 T.R.

146 T.R.

147 MENTAL HEALTH

148 MENTAL HEALTH

149 MENTAL HEALTH

150 EXAM

151 EXAM

152 EXAM

153 EXAM

154 EXAM

155 EXAM

156 PHARMACY

157 PHARMACY

158 MENTAL HEALTH

159 EXAM

160 EXAM

161 SUPPLY

162 T.R.

163 EXAM

164 EXAM

165 EXAM

166 EXAM

167 EXAM

168 EXAM

169 WPAFB

170 WPAFB

171 EXAM

172 EXAM

173 EXAM

174 T.R.

175 SUPPLY

176 EXAM

177 EXAM

178 EXAM

179 EXAM

180 EXAM

181 EXAM

182 EXAM

183 EXAM

184 EXAM

185 SOCIAL WORK

186 IMAGING TECH

187 MECH.

188 MSA

189 PACT

190 STAFF T.R.

191 SOIL

192 CLEAN

193 MED

C-1-1 CORRIDOR

C-1-2 CORRIDOR

C-1-3 CORRIDOR

C-1-4 CORRIDOR

C-1-5 CORRIDOR

C-1-6 CORRIDOR

C-1-7 CORRIDOR

C-1-8 CORRIDOR

C-1-9 CORRIDOR

C-1-10 CORRIDOR

C-1-11 CORRIDOR

C-1-12 CORRIDOR

EX-103 WOMEN

EX-104 MEN

EX-109 OFFICE

EX-110 EYE

EX-125 EXAM

PAC121 RECEPTION