This document is a solicitation for the renovation of Primary Care PACT Buildings 340 and 341 located in Dayton, Ohio. The solicitation is issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10. Renovation work includes architectural, structural, fire protection, plumbing, mechanical, and electrical upgrades. The solicitation requires renovations to mechanical systems including installation of a new rooftop air handling unit and associated ductwork, piping, controls, and terminal units. Electrical work includes upgrades to switches, video systems, patient access and clinical systems. The response date is not provided, however the wage determination is included as an attachment.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HVAC DEMOLITION GENERAL NOTES
1. THE GENERAL NOTES LISTED HERE APPLY TO ALL HVAC DEMOLITION DRAWINGS IN ADDITION TO
ANY ADDITIONAL DEMOLITION DRAWING NOTES ON THE INDIVIDUAL DEMOLITION DRAWINGS.
2. SEE CODED NOTES ON INDIVIDUAL DRAWING SHEETS FOR SPECIFIC INSTRUCTIONAL NOTES.
3. FIELD VERIFY EXISTING CONDITIONS.
4. COORDINATE WITH GENERAL TRADES WORK, PLUMBING WORK, FIRE PROTECTION WORK,
ELECTRICAL WORK AND OTHER WORK.
5. IT IS RECOGNIZED THAT DRAWINGS MAY BE PLOTTED AT DIFFERENT SCALES, SUCH THAT
PLOTTED DRAWINGS MAY VARY FROM ACTUAL OR INTENDED DIMENSIONS. THEREFORE, DRAWINGS ARE DIAGRAMMATIC AND ARE NOT TO BE SCALED. SBM TAKES NO RESPONSIBILITY FOR ERRORS
REGARDING DISCREPANCIES FROM THE ORIGINAL DRAWINGS DRAWN AT THE PROPER SCALE AND
THOSE DRAWINGS THAT HAVE BEEN PLOTTED.
6. PHASING - SEE DIVISION 1 PROJECT SPECIFICATION PHASING DOCUMENTS FOR SPECIFIC
PHASING INSTRUCTIONS. COORDINATE SHUT-DOWN OF ANY UTILITY IN ADVANCE WITH THE
OWNER. ACCOMPLISH DRAIN DOWN AND RE-FILL OF PIPING SYSTEMS AS REQUIRED. UNLESS
OTHERWISE SPECIFICALLY INDICATED, EXISTING CHILLED WATER SYSTEMS SHALL NOT BE
DISRUPTED DURING THE COOLING SEASON, AND HEATING SYSTEMS SHALL NOT BE DISRUPTED
WHEN REQUIRED FOR OCCUPANT COMFORT OR BUILDING FREEZE PROTECTION.
7. DARK, DASHED LINES INDICATE PIPING, DUCTWORK AND EQUIPMENT TO BE REMOVED.
8. SEE SPECIFICATIONS FOR GENERAL CUTTING AND PATCHING REQUIREMENTS REQUIRED UNDER
DEMOLITION. ALSO SEE DRAWINGS FOR MORE SPECIFIC REQUIREMENTS.
9. SEE SPECIFICATIONS FOR SALVAGE RIGHTS TO ANY EQUIPMENT OR MATERIALS BEING REMOVED.
10. REMOVE ALL HANGERS AND SUPPORTS SERVING PIPING, DUCTWORK AND EQUIPMENT BEING
DEMOLISHED. PROVIDE AND/OR ADJUST EXISTING HANGERS TO SUPPORT ANY REMAINING PIPING, DUCTWORK, OR EQUIPMENT ADJACENT TO DEMOLISHED.
11. CAP ALL REMAINING ACTIVE PIPING WITH SIMILAR MATERIALS TO MATCH EXISTING WATERTIGHT.
PIPE ENDS INDICATED TO BE CAPPED ARE NOT TO BE CRIMPED. INSULATED PIPING SHALL BE
INSULATED AT CAP WITH MATERIALS SPECIFIED FOR NEW WORK.
12. CAP ALL REMAINING ACTIVE DUCTWORK WITH SIMILAR MATERIALS TO MATCH EXISTING AND
SEALED AIRTIGHT. INSULATED DUCTWORK SHALL BE INSULATED AT CAP WITH MATERIALS
SPECIFIED FOR NEW WORK.
13. SEE SPECIFICATIONS FOR SPECIFIC REQUIREMENTS FOR DEMOLITION OF REFRIGERANT
CONTAINING MATERIALS OR EQUIPMENT.
14. REMOVE ALL THERMOSTATS, TEMPERATURE CONTROL WIRING AND PIPING FROM DEMOLISHED EQUIPMENT BACK TO (MAIN SOURCE/WALL) AND CAP CONTROL AIR PIPING AIRTIGHT. CRIMPING
SHALL NOT BE CONSIDERED ADEQUATE.
15. WHERE EXISTING PIPING IS MAINTAINED AT WALLS SHOWN TO BE DEMOLISHED, CONTRACTOR
TO REMOVE ABANDONED SLEEVES ASSEMBLIES AND ANY ASSOCIATED FIRESTOPPING MATERIALS
ON PIPING. PIPING INSULATION WITHIN AND AROUND THE SLEEVE ASSEMBLY IS TO BE REMOVED
AND REPLACED WITH SIMILAR INSULATION MATERIALS, MATCHING EXISTING.
HVAC NEW WORK GENERAL NOTES
1. THE GENERAL NOTES LISTED HERE APPLY TO ALL HVAC DRAWINGS IN ADDITION TO ANY
ADDITIONAL DRAWING NOTES ON THE INDIVIDUAL DRAWINGS.
2. REFER ALSO TO DUCTWORK MATERIAL SCHEDULE AND NOTES FOR ADDITIONAL GENERAL NOTES
APPLICABLE TO DUCTWORK.
3. SEE CODED NOTES ON INDIVIDUAL DRAWING SHEETS FOR SPECIFIC INSTRUCTIONAL NOTES.
4. FIELD VERIFY EXISTING CONDITIONS.
5. COORDINATE WITH GENERAL TRADES WORK, PLUMBING WORK, FIRE PROTECTION WORK,
ELECTRICAL WORK AND OTHER WORK.
6. IT IS RECOGNIZED THAT DRAWINGS MAY BE PLOTTED AT DIFFERENT SCALES, SUCH THAT
PLOTTED DRAWINGS MAY VARY FROM ACTUAL OR INTENDED DIMENSIONS. THEREFORE, DRAWINGS ARE DIAGRAMMATIC AND ARE NOT TO BE SCALED. SBM TAKES NO RESPONSIBILITY FOR ERRORS
REGARDING DISCREPANCIES FROM THE ORIGINAL DRAWINGS DRAWN AT THE PROPER SCALE AND
THOSE DRAWINGS THAT HAVE BEEN PLOTTED.
7. THE MECHANICAL DESIGN DRAWINGS ARE DIAGRAMMATIC AND ARE NOT INTENDED TO SHOW
EXACT LOCATION OF EQUIPMENT, PIPING AND DUCTWORK UNLESS DIMENSIONS ARE GIVEN OR
OTHERWISE IMPLIED FOR CLEARANCES, ETC. PIPING, DUCTWORK AND MECHANICAL EQUIPMENT
ARE TO BE INSTALLED ALONG THE GENERAL PLANS SHOWN ON THE DRAWINGS, BUT KEEPING IN
MIND ACTUAL BUILDING CONDITIONS WHICH MUST BE CONFORMED WITH IN THE ACTUAL WORK.
CONTRACTORS IN THEIR BIDS ARE REQUIRED TO INCLUDE ALL LABOR AND MATERIALS AND OTHER RELATED WORK NECESSARY TO PROVIDE MINOR OFFSETS IN MECHANICAL WORK AS REQUIRED TO AVOID CONFLICT WITH OTHER WORK ON THIS PROJECT, OR AS REQUIRED IN ORDER TO OBTAIN
MAXIMUM HEAD ROOM OR EQUIPMENT ACCESS IN SPACES.
8. PHASING - SEE DIVISION 1 PROJECT SPECIFICATION PHASING DOCUMENTS FOR SPECIFIC
PHASING INSTRUCTIONS. COORDINATE SHUT-DOWN OF ANY UTILITY IN ADVANCE WITH THE
OWNER. ACCOMPLISH DRAIN DOWN AND RE-FILL OF PIPING SYSTEMS AS REQUIRED. UNLESS
OTHERWISE SPECIFICALLY INDICATED, EXISTING CHILLED WATER SYSTEMS SHALL NOT BE
DISRUPTED DURING THE COOLING SEASON, AND HEATING SYSTEMS SHALL NOT BE DISRUPTED
WHEN REQUIRED FOR OCCUPANT COMFORT OR BUILDING FREEZE PROTECTION.
9. MAINTAIN REQUIRED RIGGING ACCESS CLEARANCES. COORDINATE CLEARANCE REQUIREMENTS
WITH OTHER TRADES.
10. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS OF FIRE AND SMOKE WALLS AND RATED
STRUCTURES. SEE DETAILS AND SPECIFICATIONS FOR PIPE PENETRATION SEAL REQUIREMENTS.
11. H.C. IS TO COORDINATE ALL MASONRY PENETRATION LOCATIONS AND SIZES WITH G.C.
12. DO NOT ROUTE DUCTWORK OR PIPING OVER ELECTRICAL EQUIPMENT.
13. UNLESS OTHERWISE INDICATED, ALL PIPING TO RUN GENERALLY BELOW DUCTWORK FOR
ACCESS TO VALVING. DO NOT OBSTRUCT EQUIPMENT OR ACCESS DOORS. AVOID DUCTWORK OVER
LIGHTS WHEREVER POSSIBLE.
14. EQUIPMENT CONNECTION ARRANGEMENTS, FLANGES, UNIONS, VALVING, ETC. ARE NOT
TYPICALLY SHOWN ON PLAN VIEWS. REFER TO DETAILS AND FLOW DIAGRAMS FOR REQUIREMENTS.
INSTALL ALL VALVES AND OTHER ITEMS REQUIRING OR FACILITATING MAINTENANCE IN ACCESSIBLE
LOCATIONS, AND SO AS TO NOT OBSTRUCT MAINTENANCE ON EQUIPMENT SERVED.
15. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE SO THERE
WILL BE COUNTER FLOW BETWEEN WATER AND AIR.
16. NOT ALL AIR VENTS AND DRAINS HAVE BEEN SHOWN ON PIPING AS THEIR REQUIRED LOCATION
DEPENDS ON THE PIPING INSTALLATION. REFER TO SPECIFICATION SECTION 23 FOR
REQUIREMENTS OF PIPING AIR VENTS AND DRAINS. PROVIDE AIR VENTS IN ALL HIGH POINTS AND
DRAIN VALVES AT ALL LOW POINTS IN PIPING SYSTEM.
17. SEE TEMPERATURE CONTROL DRAWINGS AND COORDINATE WITH TEMPERATURE CONTROL
CONTRACTORS FOR INSTRUMENTATION DEVICES REQUIRED TO BE INSTALLED IN PIPING AND
DUCTWORK, TOGETHER WITH NECESSARY CLEARANCES FOR SAME.
18. ALL HWS AND HWR BRANCH CONNECTIONS TO HEATING EQUIPMENT, TERMINAL UNITS AND
RADIANT PANELS TO BE 3/4" UNLESS OTHERWISE NOTED.
19. NO "BULL-HEAD" TEES ARE PERMITTED IN PIPING. FLOW IS NOT PERMITTED TO BE IN OPPOSING
DIRECTIONS IN THE SAME TEE FITTING.
20. ALL AIR TERMINAL UNITS, HEATING TERMINALS AND REHEAT COILS SHALL BE PROVIDED WITH
WALL-MOUNTED THERMOSTATS UNLESS NOTED ON THE PLANS OR SPECIFICATIONS TO BE
EQUIPPED WITH INTEGRAL THERMOSTATS. REFER TO PLANS FOR APPROXIMATE THERMOSTAT
LOCATIONS - COORDINATE WITH OTHER TRADES. IF A THERMOSTAT IS NOT SHOWN ON THE PLANS, COORDINATE LOCATION WITH ENGINEER. CONTRACTOR SHALL SUBMIT A FLOOR PLAN WITH
APPROXIMATE LOCATIONS OF ALL THERMOSTATS.
DESCRIPTIONABBREVIATION SYMBOL
HWS
HWR
CD
MIN. GPM
MIN. CFM
MIN. GPM
MIN. CFM
1.5
XXX
CFM
A.D.A.D.
TERMINAL UNIT WITH MIN. CFM SETTING (SEE DUCT DWG.)
HVAC SYMBOL LEGEND
HWS HEATING WATER SUPPLY
HWR HEATING WATER RETURN
CD A/C CONDENSATE DRAIN
BALL VALVE
BALANCE VALVE (SEE SPECIFICATIONS)
CHECK VALVE (SWING)
TWO WAY CONTROL VALVE
THERMOSTAT
DIFFUSER, REGISTER OR GRILLE (SEE SCHEDULE)
DUCTWORK INSULATION AND MATERIAL (SEE SCHEDULE)
TERMINAL UNIT W/HEATING COIL GPM SETTING (SEE PIPING DWG.)
CODED NOTE (SEE SCHEDULE)
ME__-__ MECHANICAL EQUIPMENT (SEE SCHEDULE)
E.C. E.C. ELECTRICAL CONTRACTOR
F.P.C. F.P.C. FIRE PROTECTION CONTRACTOR
G.C. G.C. GENERAL CONTRACTOR
H.C. H.C. HVAC CONTRACTOR
P.C. P.C. PLUMBING CONTRACTOR
T.C.C. T.C.C. TEMPERATURE CONTROL SUB-CONTRACTOR
A.D. A.D. ACCESS DOOR
A.F.F. A.F.F. ABOVE FINISHED FLOOR
A.L. A.L. ACTIVE LENGTH
MFR. MFR. MANUFACTURER
N.O. N.O. NORMALLY OPEN
N.C. N.C. NORMALLY CLOSED
TYP. TYP. TYPICAL
E.A. E.A. EXHAUST AIR
R.A. R.A. RETURN AIR
S.A. S.A. SUPPLY AIR
FLOW DIRECTION INDICATOR (VAPOR)
FLOW DIRECTION INDICATOR (LIQUID)
FLOW DIRECTION INDICATOR (VAPOR) W/ CFM QUANTITY GIVEN
ACCESS DOOR IN BOTTOM OF DUCT OR SIDE OF DUCT
90° ELBOW WITH TURNING VANES
SQUARE-TO-ROUND DUCT TRANSITION
TERMINAL UNIT WITH FLEXIBLE CONNECTION AND REHEAT COIL
MANUAL BALANCING DAMPER
AUTOMATIC CONTROL DAMPER
INDICATES TIE INTO EXISTING
INDICATES REMOVE TO POINT FOR RECONNECTION
INDICATES REMOVE TO POINT AND CAP
DATESIGNATURE
SCHOONOVER
C. J.
ST
AT
E OF O
H IO
P R O F E
SS IO N
AL EN
G
IN
E E R
RE G IS T E RE
D
E-62197
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
CONSTRUCTION - ISSUED FOR
BID
Project Number
Building Number
Drawing Number
340, 341
VA Building 340, 341 Project Title
Location
Issued Date Checked Drawn
Drawing Title Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
SCHEESER BUCKLEY MAYFIELD
1540 CORPORATE WOODS PARKWAY
UNIONTOWN, OHIO 44685
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
Approved:
PHILIP P. KIRK
CHIEF ENGINEER
2/
/2
1:
: 4
PM
C :\U se rs
\J Bi lin s k i\D oc um en ts \1
_M E
P_ C
EN
TR
A L
FI
LE
_j bi lin sk i@ sb m ce
.c om
.rv t
MJ-100
552-20-104
CJS JMB
RENOVATE PRIMARY CARE FOR
PACT BLDG 340, BLDG 341
02/09/2021
4100 WEST THIRD STREET, DAYTON, OH 45428
MECHANICAL GENERAL NOTES AND SYMBOL
LEGEND
02/09/2021
Revisions Date
CONSTRUCTION - ISSUED FOR BID 02/09/2021
NOTES:
FLOOR SECTION
WALL SECTION
PIPE INSULATION
(WHERE SPECIFIED)
1. WHERE PIPES, DUCTS AND OTHER COMPONENTS PASS THROUGH FIRE OR SMOKE RATED WALLS OR FLOORS, PROVIDE NON-ASBESTOS SEAL ASSEMBLIES CLASSIFIED BY U.L. TO PROVIDE FIRE BARRIERS EQUAL TO OR GREATER THAN THE TIME RATING OF THE CONSTRUCTION BEING PENETRATED, WITH APPROPRIATE MATERIALS AND SYSTEMS THAT COMPLY WITH APPLICABLE CODES AND THAT HAVE BEEN TESTED IN
ACCORDANCE WITH U.L. 1479 OR ASTM E814.
2. GROUT, MORTAR OR GYPSUM BASED PRODUCTS SHALL NOT BE INSTALLED IN LIEU OF FIRESTOPPING
MATERIALS AND U.L. SYSTEMS.
3. FOR SLEEVED PENETRATIONS, FIRESTOP ANNULAR SPACE, IF ANY, BETWEEN SLEEVE AND ADJACENT
CONSTRUCTION TO MEET U.L. SYSTEM REQUIREMENTS. SEE NOTE 2 ABOVE.
4. THIS CONTRACTOR SHALL FIRESTOP ALL MISCELLANEOUS OPENINGS IN FIRE-RATED CONSTRUCTION
RESULTING FROM HIS WORK.
5. CONTRACTOR SHALL PROVIDE SUBMITTAL DRAWINGS TO ENGINEER, INCLUDING U.L. RATED SYSTEM
NUMBER AND DETAIL FOR EACH TYPE OF PENETRATION AND CONFIGURATION.
PENETRATING COMPONENT
SEE ARCHITECTURAL DRAWINGS
FOR WALL CONSTRUCTION AND
FIRE RATING
SEAL JOINT BETWEEN SLEEVE
AND FLOOR SLAB WITH MIN.
1/2" BEAD FIRESTOP CAULK
PIPE SLEEVE (SLEEVE TO
EXTEND 2" ABOVE FLOOR IN
MECHANICAL EQUIPMENT ROOMS)
FURNISH AND INSTALL FIRESTOP
MATERIALS IN ACCORDANCE
WITH APPROPRIATE U.L.
SYSTEMS TO MAINTAIN FIRE
RESISTANCE RATING
FURNISH AND INSTALL FIRESTOP
MATERIALS IN ACCORDANCE
WITH APPROPRIATE U.L.
SYSTEMS TO MAINTAIN FIRE
RESISTANCE RATING
DAMMING MATERIAL
(PER U.L. TESTED
SYSTEM DESIGN)
PIPE SLEEVE
PENETRATING COMPONENT
FLOOR SLAB; SEE
ARCHITECTURAL DRAWINGS FOR
FLOOR CONSTRUCTION AND
FIRE RATING
PIPE INSULATION
(WHERE SPECIFIED)
FIRESTOPPING DETAIL FOR PENETRATIONS
THROUGH FIRE-RATED CONSTRUCTIONS
N.T.S.
NOTE:
PIPE CL
STRUCTURAL FRAMING NOTE:
SUPPLY ADDITIONAL
SUPPORT STEEL AS REQUIRED
HEX NUTS (4 REQUIRED)
THREADED ROD (SEE
SPECIFICATIONS FOR
DIAMETER)
ADJUSTABLE CLEVIS HANGER
PIPE WITH INSULATION AND
JACKET (AS APPLICABLE).
SEE SPECIFICATIONS FOR
REQUIREMENTS.
SADDLE (SEE SPECIFICATIONS)
INSULATE VOID SPACE
BETWEEN SADDLE AND PIPE
REFER TO HANGER SPECIFICATIONS
FOR ADDITIONAL REQUIREMENTS.
BEAM CLAMP
AMBIENT TEMPERATURE)
(FOR MEDIUM HIGHER THAN
CLEVIS HANGER PIPE SUPPORT
N.T.S.
CONCRETE INSERT
STRUCTURAL
CONCRETE
SINGLE LINE REPRESENTATION - PLAN VIEWS
DETAILED REPRESENTATION - PLAN VIEWS
TOP DISCHARGE SIDE DISCHARGE
SINGLE/DOUBLE LINE REPRESENTATION - PLAN VIEWS
FASTEN FLEXIBLE DUCTWORK TO DIFFUSER
NECK AND SUPPLY DUCT WITH DRAWBAND
AND WITH THREE SHEET METAL SCREWS.
SHEET METAL SCREWS TO HAVE WASHERS
CRIMPED OVER TOP ON FLEX DUCT SUPPORT
WIRE.
1.5A
3" .5A X
6' MAX.
(MINIMUM)
A = DIFFUSER NECK DIA.
X = 3" + 2A
15"
6"
10"
12"
8"
14"
35"
15"
27"
23"
19"
31"
SQUARE TO ROUND TRANSITION
WHERE MAIN DUCT DEPTH IS LESS
THAN RUNOUT DUCT DIAMETER
DIFF. NECK
DIA. A X
3" .5A
1.5A
X
MAIN SUPPLY DUCT SPIN IN FITTING WHERE
RUNOUT DUCT DIAMETER IS
LESS THAN MAIN DUCT DEPTH
MAIN SUPPLY DUCT
SUPPLY DIFFUSER
SUPPLY DIFFUSER
MAIN SUPPLY DUCT
SUPPLY DIFFUSER
DUCT SIZE TO BE SAME SIZE AS
NECK OF DIFFUSER UNLESS NOTED
OTHERWISE
24 GA. SNAP LOCK W/
EXTERNAL WRAP INSULATION, SEE
SPECS.
MAIN SUPPLY DUCT
SUPPLY DIFFUSER
SUPPLY DIFFUSER
MAIN SUPPLY DUCT
MAIN SUPPLY DUCT
TOP DISCHARGE
BALANCING DAMPER
24 GA. SNAP LOCK
W/ EXTERNAL WRAP
INSULATION, SEE SPECS.
SUPPLY DIFFUSER
BALANCING DAMPER
24 GA. SNAP LOCK
MAIN SUPPLY
DUCT
SUSPENDED CEILING
SUPPLY DIFFUSERSUPPLY DIFFUSER
SUSPENDED
CEILING
FLEX DUCT, 6' MAX
MAIN SUPPLY
DUCT
24 GA. SNAP LOCK
W/EXTERNAL WRAP
INSULATION, SEE
SPECS.
BALANCING DAMPER
DUCT RUNOUT SIZE
SHALL BE THE SAME
SIZE AS THE DIFFUSER
NECK SIZE UNLESS
NOTED OTHERWISE
(TYP).
FLEX DUCT, 6' MAX
FLEX DUCT, 6' MAX
FLEX DUCT, 6' MAX
BALANCING DAMPER
SUPPLY DIFFUSER CONNECTION DETAIL
N.T.S.
SECTION "A-A"
"A"
"A"
GASKET
DUCT
ACCESS PANEL
N.T.S.
1. DELETE INSULATION STAND-OFF ON DUCTWORK
WITHOUT EXTERIOR INSULATION.
2. DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER
INSTALLATION SHALL BE SIMILAR FOR MULTI-BLADE
DAMPERS & ROUND DAMPERS.
DUCT
INSULATION
OUTSIDE END BEARING
1/8" (6 MM) CLEARANCE
ALL AROUND
DAMPER BLADE
SECTION
1/2" (15 MM)
ROUND ROD PIN
INSULATION
STAND-OFF
HANDLE WITH
LOCKING
QUADRANT
INSIDE END
BEARING
NOTE:
SIDE ELEVATION
VOLUME DAMPER DETAIL
N.T.S.
INSULATION STIFFEN BLADE
AS REQUIRED
DAMPER BLADE
HANDLE WITH
LOCKING QUADRANT
DUCT
SEE PLANS FOR ACTUAL
DUCTWORK CONFIGURATION
LEAVING BOTTOM OF UNIT.
STRUCTURE BY G.C.
COORDINATE LOCATION OF
OPENINGS AND SUPPORTS.
NEOPRENE CONNECTION
CURB WEATHER SEAL.
CURB MOUNTED ALUMINUM
SPRING VIBRATION BASE IN
CUTAWAY VIEW.
COMPLETELY FILL VOID
BETWEEN ROOF DECK AND UNIT
WITH ACOUSTIC FIBERGLASS
BATT INSULATION.
6" FLEXIBLE CONNECTION
IN VERTICAL (TYP.)
FLASHING TO EXTERIOR OF
CURB BASE BY G.C.
ROOF LINE
SECURE UNIT TO CURB
FOR WEATHERTIGHT
INSTALLATION PER CURB
MFR.'S RECOMMENDATIONS.
ROOFTOP AIR CONDITIONING UNIT;
SEE PLANS AND SPECIFICATIONS
FOR OPTIONS AND
CONFIGURATION.
WITH CURB MOUNTED SPRING VIBRATION BASE
ROOFTOP AIR CONDITIONING UNIT DETAIL
N.T.S.
PLACE (4) 1/2" SHEETS OF
DRYWALL FOR TOTAL OF 2" OF
DRYWALL IN CURB
3/4" DRAIN VALVE
HWS
HWR
STRAIGHT LENGTH FLEXIBLE
CONNECTION (6" LONG
MINIMUM, 24" LONG MAXIMUM
UNLESS OTHERWISE INDICATED)
CONTROL ASSEMBLY
BALL VALVE
UNION (TYP.)
2-WAY CONTROL VALVE
BALANCE VALVE
RECTANGULAR TO ROUND
TRANSITION WHERE INDICATED
SUPPLY AIR DUCT
SECURE WITH BAND AND
COVER EXPOSED INSULATION
WITH DUCT TAPE (TYP.)
REHEAT COIL SIZED TO MATCH
TERMINAL UNIT UNLESS
OTHERWISE INDICATED
LOW VELOCITY SUPPLY
AIR DUCT
NOTES:
1. ALL PIPING AND VALVING SIZES TO MATCH RUNOUT
SIZE INDICATED ON PLANS.
2. SUSPEND COIL LEVEL AND PLUMB TO PERMIT FULL
DRAINAGE.
3. PIPING TO BE RUN ABOVE BOTTOM OF UNIT CASING
UNLESS OTHERWISE INDICATED.
4. LOCATE HANGERS TO SUPPORT TERMINAL
UNIT AND PIPING INDEPENDENTLY.
5. LOCATE AIR VENTS IN HIGH POINTS OF MAIN
PIPING.
6. ARRANGE UNIT DISCHARGE TO AVOID BLOWING
INTO OBSTRUCTIONS.
VAV TERMINAL UNIT DETAIL
N.T.S.
WITH REHEAT COIL AND 2-WAY CONTROL VALVE
ACCESS DOOR
DAMPER - SEE SPECIFICATIONS AND/
OR TEMPERATURE CONTROL
DRAWINGS FOR REQUIREMENTS.
BIRD SCREEN
DUCTCONDUIT (BY E.C.)
WOOD NAILER STRIP
BY H.C.
ROOF LINE
SECURE ALL AROUND
12" O.C. AT CAP AND
BASE
PREFABRICATED CURB
WITH INSULATION BY FAN
MANUFACTURER
ROOFING UP UNDER
METAL CAP
FOAM RUBBER GASKET
APPLIED TO UNDERSIDE
OF FAN CURB CAP.
DISCONNECT SWITCH
ROOF CENTRIFUGAL EXHAUST FAN
N.T.S.
NOTES:
1. SHIM CURB AND VENTILATOR AS NECESSARY TO
MOUNT EXHAUST FAN DEAD LEVEL.
2. SIZE ROOF OPENING IN ACCORDANCE WITH MFR'S
APPROVED SHOP DRAWINGS. COORDINATE LOCATION
WITH G.C.
3. CONDUIT TO BE RUN IN CORNER, INSIDE CURB BY E.C.
UNLESS OTHERWISE INDICATED.6" M
IN.
6" M
IN.
PRESSURE AND
TEMPERATURE GAUGE
CONNECTOR PLUG (TYPICAL).
1. SEE SPECIFICATIONS FOR SLIP AND DRIVE OR
FLANGED REHEAT COIL TYPE.
2. MOUNT MULTIPLE ROW COILS FOR COUNTER FLOW
ARRANGEMENT.
3. ALL PIPING AND VALVING SIZES TO MATCH RUNOUT
SIZE INDICATED ON PLANS.
4. SUSPEND COIL LEVEL AND PLUMB TO PERMIT FULL
COIL DRAINAGE.
5. SEE PLANS FOR COIL HAND CONNECTIONS.
6. LOCATE HANGERS TO SUPPORT COIL AND PIPING
INDEPENDENTLY.
7. LOCATE AIR VENTS IN HIGH POINTS OF MAIN PIPING.
2-WAY CONTROL VALVE
BALANCE VALVE
UNION (TYPICAL)
3/4" DRAIN VALVE
BALL VALVE
ACCESS DOOR, BOTH SIDES
OF DUCT (TYP.)
SUPPLY AIR DUCT
HWS
HWR
TRANSITION DUCT TO COIL
DIMENSIONS PER SMACNA
REQUIREMENTS
HEATING COIL
NOTES:
HYDRONIC WITH 2-WAY CONTROL VALVE
DUCT HEATING COIL
N.T.S.
DATESIGNATURE
SCHOONOVER
C. J.
ST
AT
E OF O
H IO
P R O F E
SS IO N
AL EN
G
IN
E E R
RE G IS T E RE
D
E-62197
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
CONSTRUCTION - ISSUED FOR
BID
Project Number
Building Number
Drawing Number
340, 341
VA Building 340, 341 Project Title
Location
Issued Date Checked Drawn
Drawing Title Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
SCHEESER BUCKLEY MAYFIELD
1540 CORPORATE WOODS PARKWAY
UNIONTOWN, OHIO 44685
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
Approved:
PHILIP P. KIRK
CHIEF ENGINEER
2/
/2
1:
: 4
PM
C :\U se rs
\J Bi lin s k i\D oc um en ts \1
_M E
P_ C
EN
TR
A L
FI
LE
_j bi lin sk i@ sb m ce
.c om
.rv t
MJ-101
552-20-104
CJS JMB
RENOVATE PRIMARY CARE FOR
PACT BLDG 340, BLDG 341
02/09/2021
4100 WEST THIRD STREET, DAYTON, OH 45428
MECHANICAL DETAILS
02/09/2021
PITCH DN. TOWARD DRAIN
DIELECTRIC UNION
B
UNIT DRAIN PAN
A
ROUTE TO NEAREST ROOF DRAIN
PLUGGED TEE CLEANOUT (TYP.)
PIPE OPEN TO ATMOSPHERE
UNIT TYPE A B
DRAW THROUGH X/2"
BLOW THROUGH
WHERE X = POSITIVE VALUE OF STATIC PRESSURE
DIFFERENCE BETWEEN PAN SECTION AND TRAP LOCATION
X"+1"
X"+2"
1" MINIMUM
NOTES:
1. LOCATE TRAP AS CLOSE AS POSSIBLE TO AHU DRAIN OUTLET WITH BOTTOM BELOW
SUPPORT STRUCTURE.
2. SIZE OF TRAP PIPING TO BE LARGER OF
EQUIPMENT OUTLET SIZE OR DIMENSION ON PLANS.
3. SEE SPECIFICATIONS FOR INSULATION REQUIREMENTS
4. NOTIFY ENGINEER BEFORE FABRICATING IF PHYSICAL CONDITIONS PROHIBIT
INSTALLATION OF DEPTH SHOWN.
AIR HANDLING UNIT
STANDARD A/C CONDENSATE TRAP DETAIL
N.T.S.
A
AIR HANDLER PIPE
A
RTU-1 1-1/4"
PLENUM
CEILING
RETURN AIR
REGISTER (SEE
SCHEDULE)
CEILING
INTERIOR
ACOUSTICAL LINING
(4)#10 GAUGE SHEET
METAL STRAP HANGERS
HANG FROM STRUCTURE
ABOVE
SEE GRILLE SCHEDULE FOR
SHEET METAL DUCT SIZES
18" MIN.
RETURN AIR BOOT
N.T.S.
COIL DRAIN
FULL SIZED
BYPASS LINE
TRANSITION PIPING TO
COIL CONNECTION SIZE
AS NEEDED.
3/4" VENT WITH BALL
VALVE AND CAP
(TYPICAL)
TEMPERATURE
SENSOR
PRESSURE GAUGE
(TYPICAL)
FULL SIZED BYPASS
LINE WITH SILENT
CHECK
RETURN HEADER PIPE
THREE-WAY MIXING
CONTROL VALVE (N.O. TO
COIL)
HEATING COIL
H W
R
H W
S
AIR
FLOW
AIR VENT AT HIGH
POINT
3/4" DRAIN WITH HOSE
ADAPTER AND CAP
(TYPICAL)
UNION OR FLANGE (TYPICAL)
HWR
IN-LINE CENTRIFUGAL PUMP.
SUPPORT
INDEPENDENTLY FROM PIPING.
SEE PLANS AND SCHEDULE
FOR ADDITIONAL
INFORMATION.
BALL VALVE FOR PIPE SIZES
2" AND UNDER, BUTTERFLY
VALVE FOR PIPE SIZES
2-1/2" AND ABOVE.
PRESSURE GAUGE WITH
GAUGE COCK (TYP.)
FULL SIZED BYPASS LINE
WITH SILENT CHECK
THERMOMETER OR
TEMPERATURE GAUGE (SEE
SPECIFICATIONS - TYPICAL)
REDUCER/INCREASER (TYP.)
BALANCE VALVE (TYPICAL)
SUPPLY HEADER PIPE
REDUCER - IF REQUIRED
HWS
1. PIPING INSTALLATION SHALL ALLOW FOR EQUIPMENT ACCESS AND COIL PULL.
2. SCHEMATIC IS APPLICABLE TO UNITS WITH ONE COIL. IF THE UNIT HAS MULTIPLE COILS:
HEADER PIPING SHALL BE FULL SIZE; EACH COIL SHALL HAVE UNIONS OR FLANGES; EACH
COIL SHALL HAVE SHUT-OFF VALVES ON THE COIL INLET AND BALANCE VALVES ON THE COIL
OUTLET; EACH COIL SHALL HAVE THERMOMETERS AND PRESSURE GAUGES ON THE COIL
INLET AND OUTLET.
3. SEE PLANS FOR PIPING DROPS AND COIL CONNECTION LOCATIONS.
NOTES:
AIR HANDLING UNIT - 3-WAY VALVE WITH PUMP
HEATING WATER COIL PIPING SCHEMATIC - SINGLE COIL
N.T.S.
A
A
A
A
A
AIR HANDLER PIPE
A
RTU-1 1-1/2"
PIPING/EQUIPMENT
LOCATED WITHIN
CEILING SPACE
DATESIGNATURE
SCHOONOVER
C. J.
ST
AT
E OF O
H IO
P R O F E
SS IO N
AL EN
G
IN
E E R
RE G IS T E RE
D
E-62197
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
CONSTRUCTION - ISSUED FOR
BID
Project Number
Building Number
Drawing Number
340, 341
VA Building 340, 341 Project Title
Location
Issued Date Checked Drawn
Drawing Title Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
SCHEESER BUCKLEY MAYFIELD
1540 CORPORATE WOODS PARKWAY
UNIONTOWN, OHIO 44685
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
Approved:
PHILIP P. KIRK
CHIEF ENGINEER
2/
/2
1:
: 4
PM
C :\U se rs
\J Bi lin s k i\D oc um en ts \1
_M E
P_ C
EN
TR
A L
FI
LE
_j bi lin sk i@ sb m ce
.c om
.rv t
MJ-102
552-20-104
CJS JMB
RENOVATE PRIMARY CARE FOR
PACT BLDG 340, BLDG 341
02/09/2021
4100 WEST THIRD STREET, DAYTON, OH 45428
MECHANICAL DETAILS
02/09/2021
NO.
MAKE OR
APPROVED
EQUAL
MODEL CONTROL
TYPE
SIZE INLET DIA
(IN.) RATING CFM MFR. MIN.
CFM
MAX NC @
RATING CFM
MAX. APD
(TERMINAL ONLY)
IN. H2O
COIL MBH
COIL MBH
@ 120°F
EWT
COIL
GPM
MAX. COIL
WPD
FT. H20
MAX. COIL APD
IN. H20
RE-HEAT COIL
1 OR 2 ROWS,
STANDARD (SC) OR
HIGH CAPACITY (HC)
REMARKS
NOTES:
SINGLE DUCT SUPPLY VAV TERMINAL UNIT SCHEDULE
6 PRICE SDV DIGITAL 6 400 66 27 0.15" 15.3 9.21 1.0 0.2 0.35" 2-ROW, HC
8 PRICE SDV DIGITAL 8 700 132 28 0.05" 24.7 14.9 2.0 0.8 0.5" 2-ROW, SC
10 PRICE SDV DIGITAL 10 1000 221 26 0.05" 36.2 21.8 2.0 1.0 0.55" 2-ROW, HC
12 PRICE SDV DIGITAL 12 1400 304 29 0.05" 52.9 31.9 4.0 3.9 0.5" 2-ROW, SC
14 PRICE SDV DIGITAL 14 2200 439 31 0.05" 80.0 48.2 6.0 4.5 0.57" 2-ROW, SC
16 PRICE SDV DIGITAL 16 2600 568 30 0.05" 92.6 55.8 6.0 4.8 0.55" 2-ROW, SC
24 PRICE SDV DIGITAL 24x16 4000 1187 35 0.05" 131.4 79.2 6.0 6.0 0.52" 2-ROW, SC
1. SEE DRAWINGS FOR INDIVIDUAL TERMINAL UNIT MAXIMUM AND MINIMUM CFM SETPOINTS. MAXIMUM CFM SETPOINTS SHALL BE THE SUM OF THE CONNECTED DIFFUSERS UNLESS OTHERWISE INDICATED. MINIMUM CFM SETPOINTS SHALL BE ZERO UNLESS OTHERWISE INDICATED. "MFR. MIN. CFM" ON SCHEDULE REFERS TO THE MANUFACTURER'S RECOMMENDED MINIMUM CONTROLLABLE CFM FOR THE TERMINAL UNIT AND SHALL NOT BE USED FOR AIR BALANCE.
2. ALL TERMINAL UNITS SHALL CONSUME NO MORE THAN 0.2" OF AIR PRESSURE DROP THROUGH THE TERMINAL UNIT WITH DAMPER FULLY OPEN AT MAXIMUM RATING CFM.
3. MAXIMUM N.C. IS DISCHARGE AIRBORNE NOISE CALCULATED FROM A 10 DB REDUCTION IN REVERBERANT ROOM SOUND POWER LEVELS WITH A TERMINAL STATIC PRESSURE DROP OF 1.5"
4. ALL HOT WATER COILS SHALL BE TWO ROW UNLESS OTHERWISE INDICATED.
5. REHEAT COIL PERFORMANCE BASED ON ENTERING AIR TEMPERATURE OF 55°F AND AN ENTERING WATER TEMPERATURE OF 160°F.
6. ALL TERMINALS WITH REHEAT COILS SHALL BE PROVIDED WITH INSULATED ACCESS DOORS WITH QUARTER TURN DOOR LATCHES UPSTREAM OF REHEAT COILS.
7. TERMINAL UNITS SHALL BE FULLY INSULATED; SECTIONS NOT INSULATED BY THE MANUFACTURER SHALL BE INSULATED TO MATCH THE DUCTWORK DOWNSTREAM (ROOM SIDE) OF THE TERMINAL FOR AT LEAST 6" BEYOND THE UN-INSULATED SECTION IN EACH DIRECTION, INCLUDING REHEAT COIL AND REHEAT COIL PIPING HEADERS.
DATESIGNATURE
SCHOONOVER
C. J.
ST
AT
E OF O
H IO
P R O F E
SS IO N
AL EN
G
IN
E E R
RE G IS T E RE
D
E-62197
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
CONSTRUCTION - ISSUED FOR
BID
Project Number
Building Number
Drawing Number
340, 341
VA Building 340, 341 Project Title
Location
Issued Date Checked Drawn
Drawing Title Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
SCHEESER BUCKLEY MAYFIELD
1540 CORPORATE WOODS PARKWAY
UNIONTOWN, OHIO 44685
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
Approved:
PHILIP P. KIRK
CHIEF ENGINEER
2/
/2
1:
: 4
PM
C :\U se rs
\J Bi lin s k i\D oc um en ts \1
_M E
P_ C
EN
TR
A L
FI
LE
_j bi lin sk i@ sb m ce
.c om
.rv t
MJ-103
552-20-104
CJS JMB
RENOVATE PRIMARY CARE FOR
PACT BLDG 340, BLDG 341
02/09/2021
4100 WEST THIRD STREET, DAYTON, OH 45428
MECHANICAL SCHEDULES
02/09/2021
1. MOUNTING FRAME TYPES SHALL BE COORDINATED WITH THE ARCHITECTURAL REFLECTED CEILING PLAN.
2. FURNISH ALL DIFFUSERS, REGISTERS AND GRILLES IN STANDARD WHITE FINISH UNLESS OTHERWISE NOTED.
3. THE SYMBOL ON THE DUCTWORK PLANS INDICATES THE MARK, AND THE AIR BALANCE IN CFM. THE DIFFUSER, REGISTER, OR GRILLE NECK SIZE WILL BE DETERMINED FROM THIS SCHEDULE GIVEN THE MARK (A,B,C, ETC.) AND THE CORRESPONDING CFM. MANUFACTURERS NOT LISTED MUST CONFORM TO SCHEDULED CHARACTERISTICS (INCLUDING FOUR DIFFUSING CONES FOR MODEL 1400). IF LARGER NECK SIZES ARE REQUIRED TO OBTAIN AIR QUANTITIES WITH MAXIMUM NOISE CRITERIA (NC) SCHEDULED, INSTALLING CONTRACTOR MUST INCLUDE ALL COSTS ASSOCIATED WITH CHANGES OF THIS NATURE IN HIS BID. IN NO CASE
WILL SMALLER NECK SIZES THAN SCHEDULED BE PERMITTED.
4. 2 SLOT, 1" SLOT WIDTH. PROVIDE WITH SUPPLY AIR PLENUM.
NOTES:
DIFFUSER, REGISTER & GRILLE SCHEDULE
NO. MAKE MODEL DAMPER MOUNTING NOMINAL
FACE SIZE MAX NC REMARKS50 75 100 125 150 175 200 225 250 275 300 325 350 375 400 425 450 475 500 525 550 575 600 625 650 675 700 725 750 775 800 825 850 875 900 950 1000
A PRICE SPD NONE NOTE #1 24"x24" 25 6" 6" 6" 8" 8" 8" 8" 10" 10" 10" 10" 10" 10" 10" 12" 12" 12" 12" B PRICE PDDR NONE NOTE #1 12"x24" 25 6"X6" 6"X6" 6"X6" 6"X6" 6"X6" 6"X6" C PRICE PDDR NONE NOTE #1 24"x24" 25 6"X6" 6"X6" 6"X6" 6"X6" 6"X6" 6"X6" 6"X6" 6"X6" 6"X6" 8"X8" 8"X8" 8"X8" 8"X8" 8"X8" 8"X8" 8"X8" 8"X8" 10"X10" 10"X10" 10"X10" 10"X10" 10"X10" 10"X10" 10"X10" 10"X10" 10"X10" 10"X10" 12"X12" 12"X12" 12"X12" 12"X12" 12"X12" 12"X12" 12"X12" 12"X12" 12"X12" 12"X12"
D PRICE TBD3 NONE NOTE #1 2' LONG 25 8" 8" NOTE #4
E PRICE 520 NONE 25 10"X8" 10"X8" 10"X8" 10"X8"
A. PRESSURE CLASSIFICATIONS SCHEDULED ARE IN ACCORDANCE WITH THE LATEST EDITION OF THE SMACNA "HVAC DUCT CONSTRUCTION STANDARDS". REFER ALSO TO SPECIFICATIONS.
B. ALL DUCTWORK RUN OUTS TO TERMINAL UNITS TO BE THE INLET SIZE OF THE TERMINAL UNIT, UNLESS NOTED OTHERWISE.
C. THE FIRST FIGURE OF DUCT SIZE INDICATES THE DIMENSION OF THE FACE SHOWN OR INDICATED.
D. REFER TO THE ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF CEILING OUTLETS AND INLETS.
E. ALL SUPPLY AIR DUCTWORK UPSTREAM OF TERMINAL UNITS TO BE TYPE 1 UNLESS OTHERWISE NOTED.
F. ALL SUPPLY AIR DUCTWORK DOWNSTREAM OF TERMINAL UNITS TO BE TYPE 2 UNLESS OTHERWISE NOTED.
G. ALL SUPPLY AIR DUCTWORK SERVING RTU-1 TO BE TYPE 3 UNLESS OTHERWISE NOTED.
H. ALL RETURN AIR DUCTWORK TO BE TYPE 4 UNLESS OTHERWISE NOTED.
I. ALL GENERAL EXHAUST AIR DUCTWORK TO BE TYPE 4 UNLESS OTHERWISE NOTED.
J. FOR LOW PRESSURE DUCTWORK (SMACNA CLASSIFICATION 2" W.G. AND LESS) - MINIMUM SIZE OF THE ACCESS PANEL IN THE DUCTWORK FOR FUSIBLE LINK REPAIR SHALL BE 2" LESS THAN WIDTH OF THE DUCT BY 12" IN LENGTH, UP TO A MAXIMUM OF 18" WIDE, UNLESS OTHERWISE NOTED ON DRAWINGS. ACCESS DOORS SHALL BE HINGED IN MECHANICAL ROOMS WHERE DOOR SWING CLEARANCE PERMITS, OTHERWISE CAM LOCK TYPE.
K. FOR MEDIUM AND HIGH PRESSURE DUCTWORK (SMACNA CLASSIFICATION 3" W.G. AND GREATER) - MINIMUM SIZE OF THE ACCESS PANEL IN THE FUSIBLE LINK REPAIR SHALL BE 8" WIDE BY 12" LONG FOR ROUND DUCTS 5" TO 12" IN DIAMETER AND FLAT OVAL DUCTS 8" TO 16" WIDE; PANEL TO BE 12" WIDE BY 12" LONG FOR ROUND DUCTS 13" TO 18" IN DIAMETER AND FLAT OVAL DUCTS 17" TO 24" WIDE; PANEL TO BE 14" WIDE BY 12" LONG FOR ROUND DUCTS 19" IN DIAMETER AND HIGHER AND FLAT OVAL DUCTS 25" AND HIGHER. ACCESS PANELS IN MEDIUM AND HIGH PRESSURE RECTANGULAR DUCTWORK SHALL BE THE SAME SIZES AS REQUIRED FOR LOW PRESSURE DUCTWORK.
L. ALL RETURN AND EXHAUST AIR DUCT PRESSURE CLASSES TO BE NEGATIVE.
NOTES:
4 2" GALVANIZED STEEL NONE
3 4" GALVANIZED STEEL EXTERNAL (WRAP OR RIGID - SEE SPECIFICATIONS)
2 2" GALVANIZED STEEL EXTERNAL (WRAP OR RIGID - SEE SPECIFICATIONS)
1 6" GALVANIZED STEEL EXTERNAL (WRAP OR RIGID - SEE SPECIFICATIONS)
TYPE
NO.
SMACNA PRESSURE
CLASSIFICATION DUCT MATERIAL INSULATION
DUCT MATERIAL SCHEDULE
1. ALL PUMPS TO BE SELECTED FOR THE MAXIMUM NON-OVERLOADING (N/O) BRAKE HORSEPOWER SCHEDULED. 2. ALL PUMP CASINGS SHALL BE CAPABLE OF ACCEPTING ONE LARGER IMPELLER SIZE.
2. SEE VIBRATION ISOLATION SPECIFICATION FOR ISOLATION REQUIRED FOR EACH PUMP TYPE.
NOTES:
HYDRONIC PUMP SCHEDULE
NO. MAKE MODEL TYPE SERVICE GPM HEAD PRESS
(FT) H20 RPM MAX BHP MHP VOLTS / PHASE REMARKS
HWP-1 TACO IL112 IN-LINE RTU-1 HEATING COIL 14 15 3,450 0.326 1/3 120/1
1. FOR TYPE FAN, AF = AIRFOIL.
2. ROOFTOP UNIT EXTERNAL STATIC PRESSURE (ESP) INCLUDES ALL DUCTWORK AND ACCESSORY LOSSES UPSTREAM AND DOWNSTREAM OF DUCTWORK CONNECTIONS TO ROOFTOP UNIT. ALL OTHER STATIC PRESSURE IS INTERNAL. ENTRANCE AND EXIT LOSSES ARE CONSIDERED INTERNAL.
3. MINIMUM OUTDOOR AIR (OA) REQUIREMENT IS TO BE MET BY OA DAMPERS GOING TO A MINIMUM POSITION.
4. SEE SPECIFICATIONS FOR REQUIRED ACCESSORIES.
5. COOLING CAPACITY SCHEDULED INCLUDES EFFECT OF FAN MOTOR HEAT.
6. TOTAL COOLING/HEATING MAXIMUM KWS INCLUDE COMPRESSOR AND CONDENSER ENERGY AT RATED CONDITIONS.
NOTES:
ROOFTOP AIR CONDITIONING UNIT SCHEDULE
NO. MODEL
MAKE OR
APPROVED
EQUAL
VOLTS/PHASE MIN. OA CFM
SUPPLY FAN INTERNAL EXHAUST FAN COOLING SYSTEM HEATING COILS (HOT WATER) FILTRATION
REMARKSCFM ESP TSP TYPE RPM MAX. BHP MHP CFM ESP TYPE RPM MAX. BHP MHP EDB DEG. F EWB DEG. F LDB DEG. F LWB DEG. F SENS MBH TOT MBH AMB DEG. F MIN. AMB DEG. F EAT DEG. F TOT MBH EWT DEG. F GPM MAX APD MAX WPD MIN. EFF MAX FPM APD (IN W.C.)
RTU-1 DPS012A DAIKIN 460/3 1,200 4,000 1.25" 2.3" AF 1,293 2.28 4.0 4,000 0.75" AF 2,072 1.44 4.0 80 67 55 54 109 150 95 49 214 200 14 0.30" 3.1' MERV 8/11 222 0.30"
1. SEE SPECIFICATIONS FOR REQUIRED ACCESSORIES.
2. TOTAL PRESSURE (TP) FOR VANEAXIAL FANS INCLUDES EXTERNAL STATIC PRESSURE (ESP) ADDED TO SPECIFIED FAN'S VELOCITY PRESSURE AT CFM INDICATED. FANS SUBMITTED WITH LOWER VELOCITY PRESSURE SHOULD ADJUST TP ACCORDINGLY.
NOTES:
FAN SCHEDULE
NO.
MAKE OR
APPROVED
EQUAL
MODEL SERVICE DESCRIPTION DRIVE
TYPE CFM ESP (IN.
W.C.) MAX BHP MHP FAN RPM VOLTS / PHASE
MAX FAN DISCHARGE SOUND LEVELS
REMARKS 63 Hz 125 Hz 250 Hz 500 Hz 1 KHz 2 KHz 4 KHz 8 KHz EF-1 GREENHECK GB-080-VG GENERAL ROOF MOUNTED - CENT. DIRECT 325 0.5" 0.07 1/10 1,725 120/1 69 75 72 65 62 60 55 49
1. SEE SPECIFICATIONS FOR REQUIRED ACCESSORIES.
2. MAXIMUM COIL FIN DENSITY IS SCHEDULED FINS PER INCH (FPI) UNLESS OTHERWISE INDICATED.
NOTES:
DUCT MOUNTED HEATING COIL SCHEDULE
NO. MAKE OR
APPROVED EQUAL MODEL FINNED LENGTH
(IN)
FINNED HEIGHT
(IN)
DUCT SIZE
W"xH"
RATING
CFM
HEATING COILS (HOT WATER) REMARKSEAT DEG. F LAT DEG. F TOT MBH EWT DEG. F LWT DEG. F. GPM MAX. WPD ROWS/FPI MAX. FPM MAX. APD
RHC-1 DAIKIN 12"X10" 500 65 95 16.2 200 170 1.1
THE ROOM TEMPERATURE SENSOR WITH LOCALLY ADJUSTABLE SETPOINT SHALL SEND TEMPERATURE AND SETPOINT SIGNALS TO THE UNIT'S DIGITAL CONTROLLER. THE DIGITAL CONTROLLER SHALL OPERATE THE MODULATING ELECTRIC TERMINAL UNIT OPERATOR THROUGH THE FLOW CONTROLLER IN A PRESSURE INDEPENDENT MANNER IN SEQUENCE WITH THE REHEAT ELECTRIC MODULATING VALVE
TO CONTROL AIRFLOW AND SPACE TEMPERATURE. UPON A DROP IN SPACE TEMPERATURE BELOW
THE TEMPERATURE SENSOR COOLING SETPOINT, THE UNIT DIGITAL CONTROLLER SHALL REDUCE THE AIRFLOW AS REQUIRED (DOWN TO THE TERMINAL UNIT'S MINIMUM SCHEDULED AIRFLOW) TO MAINTAIN TEMPERATURE SETPOINT. UPON A FURTHER DROP IN SPACE TEMPERATURE BELOW THE TEMPERATURE SENSOR HEATING SETPOINT, THE UNIT DIGITAL CONTROLLER SHALL MODULATE VALVE VE-1 AT THE
MINIMUM SCHEDULED CONSTANT AIRFLOW TO MAINTAIN TEMPERATURE SETPOINT. THE DIGITAL
CONTROLLER SHALL LIMIT THE DISCHARGE AIR TEMPERATURE NO GREATER THAN 15 DEG. F. ABOVE THE ROOM AIR TEMPERATURE. THE SYSTEM SHALL HAVE THE CAPABILITY OF REPORTING LOCAL TEMPERATURES BACK TO THE GLOBAL SYSTEM, AND THE SYSTEM SHALL HAVE THE CAPABILITY OF
OVERRIDING THE LOCAL TEMPERATURE SETPOINT FROM
THE GLOBAL SYSTEM FOR SETBACK OR OTHER ENERGY MANAGEMENT STRATEGIES.
DIGITAL VAV TERMINAL UNIT
WITH HYDRONIC REHEAT CONTROL DIAGRAM
N.T.S.
T-3
VE-1
HWR
N.O. HWS
C
H
SEQUENCE OF OPERATION:
COMMUNICATION BUS
BACK TO SUPPLY AIR
HANDLER DIGITAL
CONTROL PANEL.
24VAC FROM 24VAC
SOURCE (BY T.C.C.)
UNIT DIGITAL
CONTROLLER
VAV
TERMINAL
UNIT
SUPPLY AIR
T-1
INSTALL DUCT TEMPERATURE
SENSOR MINIMUM 5 FEET
DOWNSTREAM OF REHEAT COIL
IF POSSIBLE
ROOFTOP AIR HANDLING UNIT SEQUENCE OF OPERATIONS
DESCRIPTION: THE ROOFTOP AIR HANDLING UNIT IS VARIABLE AIR VOLUME WITH A HYDRONIC HEATING COIL, DX COOLING COIL, SUPPLY FAN AND RELIEF FAN.
ALL SETPOINTS AND DELAYS SHALL BE USER ADJUSTABLE.
UNIT IS NORMALLY STARTED AND STOPPED BY THE BAS OR MANUALLY AT THE UNIT.
THE UNIT SHALL BE OFF DURING ANY UNOCCUPIED CYCLE.
WHEN THE UNIT IS OFF, THE OUTSIDE AIR DAMPER SHALL BE CLOSED AND THE RETURN DAMPER SHALL BE OPEN.
UNOCCUPIED MODE OPERATION:
THE UNIT’S CONTROLLER SHALL MONITOR SPACE TEMPERATURE AND HUMIDITY. THE SPACE TEMPERATURE/HUMIDITY SHALL BE RESET TO 78OF/60% (ADJ.) RH DURING SUMMER OPERATION AND 65OF (ADJ.) DURING WINTER OPERATION. THE UNITS CONTROLLER SHALL MODULATE THE OUTDOOR AIR, RETURN AIR, AND RELIEF AIR DAMPERS (IF ECONOMIZER OPERATION IS WARRANTED), HEATING WATER CONTROL VALVE AND COMPRESSORS AS REQUIRED TO MAINTAIN THE UNOCCUPIED SPACE TEMPERATURE AND HUMIDITY SETTINGS.
OCCUPIED MODE OPERATION:
FAN CONTROL:
THE UNIT'S SUPPLY AND RELIEF FANS SHALL RUN CONTINUOUSLY DURING ANY OCCUPIED CYCLE.
SUPPLY FAN AIRFLOW CONTROL: THE SUPPLY AIR FLOW SHALL BE CONTROLLED BY THE DDC SYSTEM MODULATING THE SUPPLY FAN VARIABLE FREQUENCY DRIVE (VFD) TO
MAINTAIN THE SPACE TEMPERATURE SETPOINT.
RELIEF FAN AIRFLOW CONTROL: THE RELIEF AIRFLOW SHALL BE CONTROLLED BY THE UNITS CONTROLLER BY MODULATING THE RELIEF FAN VFD TO MAINTAIN SPACE PRESSURE.
INTIAL SPACE PRESSURE SETPOINT TO BE SET TO 0.02" W.C.
COOLING/HEATING CONTROL:
THE UNIT’S CONTROLLER SHALL MODULATE THE UNIT’S DAMPERS (IF ECONOMIZER OPERATION IS WARRANTED), GAS FURNACE, ELECTRIC RE-HEAT COIL, HOT-GAS RE-HEAT COIL, AND DIGITAL SCROLL COMPRESSORS AS REQUIRED TO MAINTAIN SPACE TEMPERATURE.
ECONOMIZER MODE: THE RETURN AND OUTSIDE AIR DAMPERS SHALL OPERATE IN A DRY BULB ECONOMIZER OPERATION AS REQUIRED TO MAINTAIN THE UNIT DISCHARGE AIR
TEMPERATURE SET POINT.
UPON A DROP IN THE SPACE TEMPERATURE BELOW THE TEMPERATURE SENSOR COOLING SETPOINT, THE UNITS DIGITAL CONTROLLER SHALL REDUCE THE AIRFLOW AS REQUIRED WHILE MAINTAINING A CONSTANT DISCHARGE AIR TEMPERATURE OF 55 DEG. F (DOWN TO THE UNITS MINIMUM AIRFLOW OF 3,200 CFM) TO MAINTAIN TEMPERATURE SETPOINT. UPON A FURTHER DROP IN SPACE TEMPERATURE BELOW THE TEMPERATURE SENSOR HEATING SETPOINT, THE UNITS CONTROLLER SHALL RESET THE DISCHARGE AIR TEMPERATURE BY BY MODULATING GAS FURNACE AT THE MINIMUM SCHEDULED AIRFLOW TO MAINTAIN TEMPERATURE SETPOINT. UPON A FURTHER DROP IN SPACE TEMPERATURE BELOW THE TEMPERATURE SENSORS HEATING SETPOINT, THE UNIT’S CONTROLLER SHALL MAINTAIN A DISCHARGE AIR TEMPERATURE OF 90 DEG. F BY MODULATING THE GAS FURNACE AND MODULATE THE SUPPLY AIRFLOW AS REQUIRED TO MAINTAIN THE SPACE TEMPERATURE SETPOINT.
WHEN THE OUTDOOR CONDITIONS ARE BEYOND DESIGN CONDITIONS AND THE UNIT CAN NO LONGER MAINTAIN SPACE TEMPERATURE, THE UNIT’S CONTROLLER SHALL START TO CLOSE THE OUTDOOR AIR DAMPER AS REQUIRED UNTIL THE SPACE TEMPERATURE IS SATISFIED.
FREEZE PROTECTION:
IF THE OUTDOOR AIR TEMPERATURE FALLS BELOW 40 DEG F, THE FREEZE PROTECTION HEATING WATER PUMP SHALL BE COMMANDED TO START, INDEPENDENT OF AIR HANDLING UNIT OPERATION. THE HEATING CONTROL VALVE SHALL MODULATE TO MAINTAIN COIL HEATING WATER RETURN TEMPERATURE OF 45 DEG F. HEATING COIL MODULATION TO MAINTAIN SUPPLY AIR TEMPERATURE SHALL TAKE PRECEDENCE OVER COIL HEATING WATER RETURN TEMPERATURE MAINTENANCE.
IF THE TEMPERATURE AT THE FREEZESTAT FALLS BELOW 40 DEG F, THE UNIT SUPPLY FAN SHALL SHUT DOWN AND A CRITICAL ALARM SHALL BE INDICATED AT THE WORKSTATION.
THE DDC SYSTEM, USING HIGH PRESSURE SWITCH LOCATED DOWNSTREAM OF THE AIR HANDLING UNIT SHALL PREVENT THE SUPPLY FAN FROM DEVELOPING OVER THE DUCTWORK MAXIMUM PRESSURE CLASSIFICATION. IF STATIC PRESSURE IS EXCEEDED, THE SYSTEM SHALL "SHUTOFF" THE SUPPLY FAN AND ALARM THE DDC SYSTEM.
OPTIMUM START SEQUENCE (MORNING WARM-UP/COOL-DOWN):
WHEN THIS SEQUENCE IS ENABLED VIA THE BAS, THE OUTSIDE AIR AND RELIEF DAMPERS SHALL CLOSE AND THE RETURN AIR DAMPER SHALL OPEN. THE UNITS CONTROLLER SHALL SHALL MAINTAIN A DISCHARGE TEMPERATURE OF 55 DEG F (ADJ.) IN COOLING SEASON AND 100 DEG F. (ADJ.) IN HEATING SEASON.
SMOKE DETECTION:
WHEN SMOKE IS DETECTED, THE SUPPLY AND RELIEF FANS SHALL SHUT OFF AND AN ALARM SHALL BE TRANSMITTED TO THE FIRE ALARM SYSTEM AND RELAY ALARM SIGNAL TO
THE BAS.
PROGRAM AT MINIMUM THE FOLLOWING ALARMS:
DIRTY FILTER
SMOKE DETECTOR ALARM
HIGH SUPPLY AIR TEMPERATURE
LOW SUPPLY AIR TEMPERATURE
HIGH SPACE TEMPERATURE
LOW SPACE TEMPERATURE
SUPPLY FAN HIGH STATIC CUTOUT
PUMP FAILURE
ROOFTOP AIR HANDLING UNIT CONTROL DIAGRAM
N.T.S.
SUPPLY AIR RETURN AIR
SPS-3 FSD-1 BY
E.C.
(RTU-1)
SPS-1 TLL-1
ROOFTOP UNIT
N.O.
HWR
HWS
NOTES:
1. PROVIDE CONTROL WIRING BETWEEN SENSORS AND ROOFTOP UNIT
PER RTU MANUFACTURER'S REQUIREMENTS. PROVIDE WIRING
BETWEEN ROOFTOP UNITS AND BUILDING AUTOMATIC SYSTEM.
2. OUTDOOR TEMPERATURE AND HUMIDITY SHALL BE RETRIEVED FROM
INTEGRAL OUTDOOR AIR TEMPERATURE AND HUMIDITY SENSORS, SEE
SPECIFICATIONS.
3. RTU-1 SHALL BE PROVIDED WITH BACNET CARD AND ALL AVAILABLE
POINTS SHALL BE INTEGRATED INTO BAS.
TO EXHAUST
AND SUPPLY
FAN SAFETY
CIRCUIT
TO EXHAUST
AND SUPPLY
FAN SAFETY
CIRCUIT
TO BUILDING
AUTOMATION SYSTEM
TO EXHAUST
AND SUPPLY
FAN SAFETY
CIRCUIT
TO FIRE ALARM
(SEE ELECTRICAL
DRAWINGS)
DUCT STATIC PRESSURE
SENSOR, SEE PLANS FOR
LOCATION
SPACE DIFFERENTIAL PRESSURE
SENSOR. INSTALLED IN LOCATION
AS DIRECTED BY ENGINEER
NUMBER OF WIRES
AS REQUIRED (TYP)
SUPPLY AIR
TEMPERATURE SENSOR
CSR TO BUILDING
AUTOMATION SYSTEM
CSR
SEQUENCE OF OPERATION:
AIR
EXHAUST
1. EXHAUST FAN SHALL RUN CONTINUOUSLY DURING OCCUPIED PERIOD.
2. UPON A SIGNAL FROM THE DIGITAL CONTROL PANEL THE FAN SHALL START.
3. UPON A SIGNAL FROM THE DIGITAL CONTROL PANEL THE FAN SHALL STOP.
4. IF THE FAN FAILS TO START AN ALARM SHALL BE SENT TO THE BAS.
EXHAUST FAN CONTROL DIAGRAM
N.T.S.
TO BUILDING
AUTOMATION SYSTEM
START/STOP SIGNAL
FROM BUILDING
AUTOMATION SYSTEM
REMARKSABBREVIATION DESCRIPTION
FSD-1
SPS-1
SPS-3
T-1
T-3
TLL-1
VE-1
N.C.
N.O.
TEMPERATURE CONTROL SYMBOL LEGEND
DUCT SMOKE DETECTOR WITH AUXILIARY CONTACT BY E.C.
NORMALLY CLOSED
NORMALLY OPEN
STATIC PRESSURE SENSOR FOR AIRFLOW (ANALOG)
STATIC PRESSURE SENSOR FOR AIRFLOW - HIGH LIMIT - (ANALOG)
DUCT TEMPERATURE SENSOR
ROOM TEMPERATURE SENSOR (WITH LOCAL ADJUSTABLE SET POINT)
FREEZESTAT WITH AUXILIARY CONTACTS AND LOCAL MANUAL RESET
NORMALLY OPEN (N.O.) ELECTRIC MODULATING TWO-WAY HYDRONIC
CONTROL VALVE
T-3
SEQUENCE OF OPERATION:
HOT WATER REHEAT CONTROL DIAGRAM
N.T.S.
NEW SPACE TEMPERATURE
SENSOR WITH ROOM SETPOINT
ADJUSTMENT.
THE ROOM TEMPERATURE SENSOR WITH LOCALLY ADJUSTABLE SETPOINT SHALL SEND TEMPERATURE AND SETPOINT SIGNALS TO THE UNIT'S DIGITAL CONTROLLER. THE DIGITAL CONTROLLER SHALL OPERATE THE MODULATING REHEAT ELECTRIC HEATING WATER VALVE TO MAINTAIN THE SPACE TEMPERATURE SETPOINT. THE SYSTEM SHALL HAVE THE CAPABILITY OF REPORTING LOCAL TEMPERATURES AND SUPPLY AIR BACK TO THE GLOBAL SYSTEM, AND THE SYSTEM SHALL HAVE THE CAPABILITY OF OVERRIDING THE LOCAL TEMPERATURE SETPOINT FROM THE GLOBAL
SYSTEM FOR SETBACK OR OTHER ENERGY MANAGEMENT STRATEGIES.
POWER BY E.C.
BAS COMMUNICATION
BUS
UNIT DIGITAL
CONTROLLER
HWS
HWRN.O.
SUPPLY
AIR
H
C
VE-1
DATESIGNATURE
SCHOONOVER
C. J.
ST
AT
E OF O
H IO
P R O F E
SS IO N
AL EN
G
IN
E E R
RE G IS T E RE
D
E-62197
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
CONSTRUCTION - ISSUED FOR
BID
Project Number
Building Number
Drawing Number
340, 341
VA Building 340, 341 Project Title
Location
Issued Date Checked Drawn
Drawing Title Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
SCHEESER BUCKLEY MAYFIELD
1540 CORPORATE WOODS PARKWAY
UNIONTOWN, OHIO 44685
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
Approved:
PHILIP P. KIRK
CHIEF ENGINEER
2/
/2
1:
: 4
PM
C :\U se rs
\J Bi lin s k i\D oc um en ts \1
_M E
P_ C
EN
TR
A L
FI
LE
_j bi lin sk i@ sb m ce
.c om
.rv t
MI-100
552-20-104
CJS JMB
RENOVATE PRIMARY CARE FOR
PACT BLDG 340, BLDG 341
02/09/2021
4100 WEST THIRD STREET, DAYTON, OH 45428
MECHANICAL TEMPERATURE CONTROLS
02/09/2021
T
T
T
T
T
TT
TT
T
T T
T T
T T
T
T
T T
T
T T
T
T
T
T
T
T
TT
T
T
T
T
8 14
20 20 20
19191919
19 19 19 19
20 20
CODED NOTES
1. EXISTING TERMINAL UNIT TO BE REMOVED. DISCONNECT AND REMOVE ALL ASSOCIATED S.A.
DUCTWORK AND DIFFUSERS DOWNSTREAM OF UNIT. DISCONNECT AND REMOVE ASSOCIATED
S.A. DUCTWORK OF UNIT AS SHOWN.
2. REMOVE EXISTING S.A. DUCTWORK TO POINT INDICATED AND CAP AIR TIGHT.
3. EXISTING R.A. GRILLE TO BE REMOVED. DISCONNECT EXISTING R.A. DUCTWORK AS SHOWN.
4. REMOVE EXISTING R.A. DUCTWORK TO POINT INDICATED AND CAP AIR TIGHT.
5. EXISTING E.A. GRILLE TO BE REMOVED. DISCONNECT EXISTING R.A. DUCTWORK AS SHOWN.
6. REMOVE EXISTING E.A. DUCTWORK TO POINT INDICATED AND CAP AIR TIGHT.
7. EXISTING FAN ON ROOF TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED E.A.
DUCTWORK AS SHOWN.
8. EXISTING S.A. DIFFUSER TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED S.A.
DUCTWORK BACK TO MAIN AND CAP AIR TIGHT.
9. EXISTING THERMOSTAT TO BE REMOVED. DISCONNECT AND REMOVE ALL ASSOCIATED
TERMPERATURE CONTROL WIRING.
10. EXISTING E.A. GRILLE TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED E.A.
DUCTWORK BACK TO MAIN AND CAP AIR TIGHT.
11. EXISTING THERMOSTAT TO BE RELOCATED, SEE NEW WORK PLANS FOR LOCATION.
12. EXISTING R.A. GRILLE TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED R.A.
DUCTWORK BACK TO MAIN AND CAP AIR TIGHT.
13. REMOVE EXISTING S.A. DUCTWORK BACK TO POINT INDICATED FOR RECONNECTION UNDER
NEW WORK.
14. EXISTING R.A. GRILLE TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED R.A.
DUCTWORK BACK TO MAIN AND CAP AIR TIGHT.
15. EXISTING S.A. DIFFUSER TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED S.A.
DUCTWORK BACK TO POINT INDICATED FOR RECONNECTION UNDER NEW WORK.
16. PRE-RECORD EXISTING AIRFLOW PRIOR TO DEMOLITION WORK.
17. EXISTING AIR CURTAIN TO BE REMOVED.
18. EXISTING E.A. GRILLE TO BE REMOVED. DISCONNECT EXISTING E.A. DUCTWORK AS
REQUIRED FOR CONNECTION TO NEW E.A. GRILLE.
19. EXISTING S.A. DIFFUSER TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED S.A.
DUCTWORK AS REQUIRED FOR CONNECTION TO NEW DIFFUSER.
20. EXISTING R.A. GRILLE TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED R.A.
DUCTWORK AS REQUIRED FOR CONNECTION TO NEW GRILLE.
21. EXISTING S.A. GRILLE TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED S.A.
DUCTWORK AS SHOWN.
22. REMOVE EXISTING S.A. DUCTWORK BACK TO POINT INDICATED AND CAP AIR TIGHT.
PLAN NOTES
A. SEE SHEET MJ-100 FOR GENERAL NOTES AND SYMBOL LEGEND.
B. EXISTING DUCTWORK AND EQUIPMENT SHOWN WITH LIGHT LINES.
C. EXISTING DUCTWORK AND EQUIPMENT TO BE REMOVED SHOWN WITH DARK DASHED LINES.
D. REFER TO ARCHITECTURAL PLANS FOR PHASING AND SUB-PHASING AREAS OF WORK.
E. ACCESS TO ALL AREAS OUTSIDE OF PHASE AND SUB-PHASE CONSTRUCTION AREAS
INDICATED TO BE FULLY ACCESSIBLE TO STAFF AND PATIENTS THROUGH OUT NORMAL WORKING HOURS. ALL LIMITED SCOPE SUPPORTING ACTIVITIES TO BE COORDINATED WITH THE VA COR.
ALL WORK DEEMED DISRUPTIVE BY COR TO BE CONDUCTED OUTSIDE NORMAL WORKING HOURS
(7:30 AM TO 5:00 PM).
DATESIGNATURE
SCHOONOVER
C. J.
ST
AT
E OF O
H IO
P R O F E
SS IO N
AL EN
G
IN
E E R
RE G IS T E RE
D
E-62197
0' 1'
2'
1/ 2"
' 0
0' 1'
3'
3/ 8"
' 0
0' 2'
4'
1/ 4"
' 0
0' 3'
6' 1'
3/
' 0
0' 4'
8' 2'1/
8"
' 0
0' 3'
3/
' 0
6' 0'
8'
4'1/
' 0
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
CONSTRUCTION - ISSUED FOR
BID
Project Number
Building Number
Drawing Number
340, 341
VA Building 340, 341 Project Title
Location
Issued Date Checked Drawn
Drawing Title Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
SCHEESER BUCKLEY MAYFIELD
1540 CORPORATE WOODS PARKWAY
UNIONTOWN, OHIO 44685
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
Approved:
PHILIP P. KIRK
CHIEF ENGINEER
2/
/2
1:
: 5
PM
C :\U se rs
\J Bi lin s k i\D oc um en ts \1
_M E
P_ C
EN
TR
A L
FI
LE
_j bi lin sk i@ sb m ce
.c om
.rv t
MD-100
552-20-104
CJS JMB
RENOVATE PRIMARY CARE FOR
PACT BLDG 340, BLDG 341
02/09/2021
4100 WEST THIRD STREET, DAYTON, OH 45428
DEMOLITION - FIRST FLOOR PLAN - HVAC
(DUCTWORK) PHASE 1
02/09/2021
N 1/8" = 1'-0"
DEMOLITION - FIRST FLOOR PLAN - HVAC (DUCTWORK) PHASE 1
2 1/2" HWS
1" HWR
2 1/2" HWS
1 1/4" HWR
2" H
W S
2" H
W R
1/
2" H
W R
2" H
W S
2" HWR
2" HWS
2" HWR
2" HWS
2" H
W R
2" H
W S
1/
4" H
W S
2" H
W R
2 1/2" HWR
1" HWS
3" HWR
1" HWS
1" H
W S
3" H
W R
1" HWR
1" HWS
1" HWR
1" HWS
3/ 4"
H W
S 3/
4" H
W R
1 1
CODED NOTES
1. EXISTING TERMINAL UNIT TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED HWS AND
HWR PIPING BACK TO MAINS AND CAP WATER TIGHT.
2. EXISTING AIR CURTAIN TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED HWS AND
HWR PIPING BACK TO POINT INDICATED.
PLAN NOTES
A. SEE SHEET MJ-100 FOR GENERAL NOTES AND SYMBOL LEGEND.
B. EXISTING PIPING AND EQUIPMENT SHOWN WITH LIGHT LINES.
C. EXISTING PIPING AND EQUIPMENT TO BE REMOVED SHOWN WITH DARK DASHED LINES.
D. REFER TO ARCHITECTURAL PLANS FOR PHASING AND SUB-PHASING AREAS OF WORK.
E. ACCESS TO ALL AREAS OUTSIDE OF PHASE AND SUB-PHASE CONSTRUCTION AREAS
INDICATED TO BE FULLY ACCESSIBLE TO STAFF AND PATIENTS THROUGH OUT NORMAL WORKING HOURS. ALL LIMITED SCOPE SUPPORTING ACTIVITIES TO BE COORDINATED WITH THE VA COR.
ALL WORK DEEMED DISRUPTIVE BY COR TO BE CONDUCTED OUTSIDE NORMAL WORKING HOURS
(7:30 AM TO 5:00 PM).
DATESIGNATURE
SCHOONOVER
C. J.
ST
AT
E OF O
H IO
P R O F E
SS IO N
AL EN
G
IN
E E R
RE G IS T E RE
D
E-62197
0' 1'
2'
1/ 2"
' 0
0' 1'
3'
3/ 8"
' 0
0' 2'
4'
1/ 4"
' 0
0' 3'
6' 1'
3/
' 0
0' 4'
8' 2'1/
8"
' 0
0' 3'
3/
' 0
6' 0'
8'
4'1/
' 0
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
CONSTRUCTION - ISSUED FOR
BID
Project Number
Building Number
Drawing Number
340, 341
VA Building 340, 341 Project Title
Location
Issued Date Checked Drawn
Drawing Title Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
SCHEESER BUCKLEY MAYFIELD
1540 CORPORATE WOODS PARKWAY
UNIONTOWN, OHIO 44685
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
Approved:
PHILIP P. KIRK
CHIEF ENGINEER
2/
/2
1:
: 5
PM
C :\U se rs
\J Bi lin s k i\D oc um en ts \1
_M E
P_ C
EN
TR
A L
FI
LE
_j bi lin sk i@ sb m ce
.c om
.rv t
MD-101
552-20-104
CJS JMB
RENOVATE PRIMARY CARE FOR
PACT BLDG 340, BLDG 341
02/09/2021
4100 WEST THIRD STREET, DAYTON, OH 45428
DEMOLITION - FIRST FLOOR PLAN - HVAC
(PIPING) PHASE 1
02/09/2021
N 1/8" = 1'-0"
DEMOLITION - FIRST FLOOR PLAN - HVAC (PIPING) PHASE 1
T
T
T
T
TT
TT
T
T T
T T
T T
T
T
T T
T
TT
T
T
T T
T
T
T
T
T
10 12 10 12
2 1
11 5
5 6
16 3
3 3 4
181818
19 19
CODED NOTES
1. EXISTING TERMINAL UNIT TO BE REMOVED. DISCONNECT AND REMOVE ALL ASSOCIATED S.A.
DUCTWORK AND DIFFUSERS DOWNSTREAM OF UNIT. DISCONNECT AND REMOVE ASSOCIATED
S.A. DUCTWORK OF UNIT AS SHOWN.
2. REMOVE EXISTING S.A. DUCTWORK BACK TO POINT INDICATED AND CAP AIR TIGHT.
3. EXISTING R.A. GRILLE TO BE REMOVED. DISCONNECT EXISTING R.A. DUCTWORK AS SHOWN.
4. REMOVE EXISTING R.A. DUCTWORK BACK TO POINT INDICATED AND CAP AIR TIGHT.
5. EXISTING E.A. GRILLE TO BE REMOVED. DISCONNECT EXISTING E.A. DUCTWORK AS SHOWN.
6. REMOVE EXISTING E.A. DUCTWORK BACK TO POINT INDICATED AND CAP AIR TIGHT.
7. EXISTING E.A. FAN ON ROOF ABOVE TO BE ABANDONED. DISCONNECT AND REMOVE ALL
ASSOCIATED E.A. DUCTWORK TO GRILLE. CAP E.A. DUCTWORK JUST BELOW ROOF DECK.
8. EXISTING S.A. DIFFUSER TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED S.A.
DUCTWORK BACK TO MAIN AND CAP AIR TIGHT.
9. EXISTING THERMOSTAT TO BE REMOVED. DISCONNECT AND REMOVE ALL ASSOCIATED
TERMPERATURE CONTROL WIRING.
10. EXISTING S.A. DIFFUSER TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED S.A.
DUCTWORK BACK TO POINT INDICATED FOR RECONNECTION UNDER NEW WORK.
11. EXISTING THERMOSTAT TO BE RELOCATED, SEE NEW WORK PLANS FOR LOCATION.
12. EXISTING R.A. GRILLE TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED R.A.
DUCTWORK BACK TO MAIN AND CAP AIR TIGHT.
13. REMOVE EXISTING R.A. DUCTWORK BACK TO POINT INDICATED FOR RECONNECTION UNDER
NEW WORK.
14. REMOVE EXISTING S.A. DUCTWORK BACK TO POINT INDICATED FOR RECONNECTION UNDER
NEW WORK.
15. REMOVE EXISTING E.A. DUCTWORK BACK TO POINT INDICATED FOR RECONNECTION UNDER
NEW WORK.
16. EXISTING S.A. DIFFUSER TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED S.A.
DUCTWORK AS SHOWN.
17. EXISTING R.A. GRILLE TO BE REMOVED. DISCONNECT EXISTING R.A. DUCTWORK AS SHOWN.
PRE-RECORD EXISTING AIRFLOW PRIOR TO DEMOLITION.
18. EXISTING S.A. DIFFUSER TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED S.A.
DUCTWORK AS REQUIRED FOR CONNECTION TO NEW DIFFUSER.
19. EXISTING R.A. GRILLE TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED R.A.
DUCTWORK AS REQUIRED FOR CONNECTION TO NEW GRILLE.
PLAN NOTES
A. SEE SHEET MJ-100 FOR GENERAL NOTES AND SYMBOL LEGEND.
B. EXISTING DUCTWORK AND EQUIPMENT SHOWN WITH LIGHT LINES.
C. EXISTING DUCTWORK AND EQUIPMENT TO BE REMOVED SHOWN WITH DARK DASHED LINES.
D. REFER TO ARCHITECTURAL PLANS FOR PHASING AND SUB-PHASING AREAS OF WORK.
E. ACCESS TO ALL AREAS OUTSIDE OF PHASE AND SUB-PHASE CONSTRUCTION AREAS
INDICATED TO BE FULLY ACCESSIBLE TO STAFF AND PATIENTS THROUGH OUT NORMAL WORKING HOURS. ALL LIMITED SCOPE SUPPORTING ACTIVITIES TO BE COORDINATED WITH THE VA COR.
ALL WORK DEEMED DISRUPTIVE BY COR TO BE CONDUCTED OUTSIDE NORMAL WORKING HOURS
(7:30 AM TO 5:00 PM).
DATESIGNATURE
SCHOONOVER
C. J.
ST
AT
E OF O
H IO
P R O F E
SS IO N
AL EN
G
IN
E E R
RE G IS T E RE
D
E-62197
0' 1'
2'
1/ 2"
' 0
0' 1'
3'
3/ 8"
' 0
0' 2'
4'
1/ 4"
' 0
0' 3'
6' 1'
3/
' 0
0' 4'
8' 2'1/
8"
' 0
0' 3'
3/
' 0
6' 0'
8'
4'1/
' 0
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
CONSTRUCTION - ISSUED FOR
BID
Project Number
Building Number
Drawing Number
340, 341
VA Building 340, 341 Project Title
Location
Issued Date Checked Drawn
Drawing Title Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
SCHEESER BUCKLEY MAYFIELD
1540 CORPORATE WOODS PARKWAY
UNIONTOWN, OHIO 44685
MECHANICAL ENGINEER
ELECTRICAL ENGINEER
Approved:
PHILIP P. KIRK
CHIEF ENGINEER
2/
/2
1:
: 0
PM
C :\U se rs
\J Bi lin s k i\D oc um en ts \1
_M E
P_ C
EN
TR
A L
FI
LE
_j bi lin sk i@ sb m ce
.c om
.rv t
MD-102
552-20-104
CJS JMB
RENOVATE PRIMARY CARE FOR
PACT BLDG 340, BLDG 341
02/09/2021
4100 WEST THIRD STREET, DAYTON, OH 45428
DEMOLITION - FIRST FLOOR PLAN - HVAC
(DUCTWORK) PHASE 2
02/09/2021
N 1/8" = 1'-0"
DEMOLITION - FIRST FLOOR PLAN - HVAC (DUCTWORK) PHASE 2
1 1
1 1/4" HWR
2 1/2" HWS
1" HWR
2 1/2" HWR
1" HWS
3" HWR
1" HWS
2" H
W R
1/
4" H
W S
2" H
W R
2" H
W S
2" HWR
2" HWS
2" HWR
2" HWS
2" H
W S
2" H
W R
2" H
W S
1/
2" H
W R
CODED NOTES
1. EXISTING TERMINAL UNIT TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED HWS AND
HWR PIPING BACK TO POINTS INDICATED FOR RECONNECTION UNDER NEW WORK.
PLAN NOTES
A. SEE SHEET MJ-100 FOR GENERAL NOTES AND SYMBOL LEGEND.
B. EXISTING PIPING AND EQUIPMENT SHOWN WITH LIGHT LINES.
C. EXISTING PIPING AND EQUIPMENT TO BE REMOVED SHOWN WITH DARK DASHED LINES.
D. REFER…