This solicitation is for a renovation project at Primary Care PACT Buildings 340 and 341 located in Dayton, Ohio. Key requirements include mechanical, electrical, and plumbing work along with fire protection and architectural services. The solicitation involves replacing plumbing fixtures and piping, installing new HVAC equipment, upgrading the electrical system including switches and cabling, installing a fire alarm and security system, and renovating patient exam rooms. The work will be completed in phases to minimize disruptions to ongoing medical services. The solicitation is issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10. Responses are due by June 7th, 2022 with work expected to be completed within 365 days of award.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PLUMBING DEMOLITION GENERAL NOTES

1. THE GENERAL NOTES LISTED HERE APPLY TO ALL DEMOLITION DRAWINGS IN ADDITION TO ANY

ADDITIONAL DEMOLITION DRAWING NOTES ON THE INDIVIDUAL DEMOLITION DRAWINGS.

2. IT IS RECOGNIZED THAT DRAWINGS MAY BE PLOTTED AT DIFFERENT SCALES, SUCH THAT

PLOTTED DRAWINGS MAY VARY FROM ACTUAL OR INTENDED DIMENSIONS. THEREFORE,

DRAWINGS ARE DIAGRAMMATIC AND ARE NOT TO BE SCALED. SBM TAKES NO RESPONSIBILITY

FOR ERRORS REGARDING DISCREPANCIES FROM THE ORIGINAL DRAWINGS DRAWN AT THE

PROPER SCALE AND THOSE DRAWINGS THAT HAVE BEEN PLOTTED.

3. WALLS SHOWN IN DASHED ARE BEING REMOVED. WALLS SHOWN TO BE REMOVED MAY

CONTAIN PLUMBING PIPING TO FIXTURES THAT ARE TO REMAIN. THIS PIPING IS TO BE

PROTECTED DURING WORK.

4. DARK, DASHED LINES INDICATE PIPING AND EQUIPMENT TO BE REMOVED.

5. UNLESS NOTED OTHERWISE, ALL PIPING TO BE DEMOLISHED SHALL BE REMOVED BACK TO THE

MAIN AND CAPPED.

6. CAP ALL REMAINING PIPING WITH SIMILAR MATERIALS. PIPE ENDS INDICATED TO BE CAPPED ARE

NOT TO BE CRIMPED. ALL DCW, DHW, & RDHW PIPING SHOWN TO BE REMOVED AND NOT

INDICATED TO BE EXTENDED WITH NEW WORK, THE CAPPED ENDS ARE TO BE INSULATED WITH

MATERIALS SPECIFIED FOR NEW WORK.

7. NEW INSULATION IS TO BE INSTALLED ON ANY EXPOSED SECTIONS OF PIPING THAT WAS

PREVIOUSLY INSULATED PRIOR TO THE START OF DEMOLITION WORK. THIS INCLUDES CAPPED

ENDS OF PIPING.

8. PROVIDE HANGERS TO SUPPORT ANY REMAINING PIPING OR EQUIPMENT.

9. REMOVE ALL HANGERS AND SUPPORTS FOR PIPING AND EQUIPMENT BEING DEMOLISHED.

10. OWNER SHALL HAVE SALVAGE RIGHTS TO ANY EQUIPMENT OR MATERIALS BEING REMOVED.

ANY EQUIPMENT OR MATERIALS REFUSED BY THE OWNER SHALL BE REMOVED FROM THE SITE.

SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

11. SEE SPECIFICATIONS FOR ALL CUTTING AND PATCHING REQUIREMENTS REQUIRED UNDER

DEMOLITION AND ALSO INDICATED ON DRAWINGS.

12. THIS CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO START OF

CONSTRUCTION.

13. THE PLUMBING CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE EXACT LOCATION AND

ELEVATION OF ALL EXISTING UNDERGROUND UTILITIES PRIOR TO COMMENCING WORK. THE

PLUMBING CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGES WHICH OCCURS BY HIS FAILURE TO

LOCATE OR PRESERVE THE UNDERGROUND CONDITIONS.

14. IF DURING CONSTRUCTION OPERATIONS, THE PLUMBING CONTRACTOR ENCOUNTERS UTILITIES

OTHER THAN THOSE LOCATIONS SHOWN IN THE PLANS, HE SHALL IMMEDIATELY NOTIFY THE

ENGINEER AND TAKE THE NECESSARY STEPS TO PROTECT THE FACILITY AND ASSURE THE

CONTINUANCE OF SERVICE.

15. AN ATTEMPT HAS BEEN MADE TO SHOW ALL ITEMS TO BE REMOVED AND/OR RELOCATED.

FIELD VERIFY EXISTING CONDITIONS INCLUDING LOCATIONS AND INVERTS AND REMOVE OR

RELOCATE ALL PLUMBING PIPING THAT INTERFERES WITH NEW CONSTRUCTION PRIOR TO START

OF WORK.

16. ANY DISRUPTION OF ANY EXISTING SERVICE THAT SERVES THE BUILDING SHALL BE

COORDINATED WITH THE OWNER PRIOR TO DISRUPTION. WORK ASSOCIATED WITH THIS SERVICE

SHALL BE PERFORMED AT A TIME REQUESTED BY OWNER WHICH COULD BE PERFORMED OFF

STANDARD WORKING HOURS AT NO ADDITIONAL COST TO OWNER FOR TIME OF WORK. COST TO

BE INCLUDED UNDER BASE BID FOR PROJECT.

17. WHERE PLUMBING PIPING HAS BEEN REMOVED AND/OR CAPPED, THE PLUMBING CONTRACTOR

IS TO PATCH FLOOR/WALL TO MATCH EXISTING CONDITIONS.

18. THE PLUMBING CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING OF EXISTING

WALLS, CEILINGS, AND FLOORS THAT REQUIRES PLUMBING WORK AND IS OUTSIDE THIS PROJECT.

PATCHING IS TO MATCH EXISTING CONSTRUCTION AND FINISH.

19. REMOVAL AND REINSTALLATION OF CEILINGS NOT INDICATED TO BE REMOVED AND

REINSTALLED ON THE ARCHITECTURAL DRAWINGS TO BE PERFORMED BY THIS CONTRACTOR FOR

DEMOLITION OR INSTALLATION OF NEW PIPING OR EQUIPMENT OUTSIDE THE PROJECT AREA.

REMOVAL OF PLUMBING PIPING IN CEILING SPACE IS TO BE COORDINATED WITH THE NEW WORK

PLAN TO MINIMIZE DISTURBANCE TO ADJACENT SPACES.

20. P.C. TO REROUTE/RECONNECT ALL ACTIVE VENT PIPE REMOVED DURING CONSTRUCTION DUE TO DEMOLITION OF INTERIOR WALLS. VENT PIPING SHALL BE ROUTED IN NEW FURRED COLUMN

SPACE OR NEW WALL STUD SPACE AS REQUIRED.

21. THE PLUMBING CONTRACTOR SHALL REMOVE PLUMBING PIPING IN WALLS TO BE REMOVED

AND RE-PIPE ALL ITEMS OUTSIDE THE DEMOLITION LIMITS AND RESTORE TO ORIGINAL WORKING

CONDITION.

22. WHERE EXISTING PIPING IS MAINTAINED AT WALLS SHOWN TO BE DEMOLISHED, CONTRACTOR

TO REMOVE ABANDONED SLEEVES ASSEMBLIES AND ANY ASSOCIATED FIRESTOPPING MATERIALS

ON PIPING. PIPING INSULATION WITHIN AND AROUND THE SLEEVE ASSEMBLY IS TO BE REMOVED

AND REPLACED WITH SIMILAR INSULATION MATERIALS, MATCHING EXISTING.

PLUMBING NEW WORK GENERAL NOTES

1. THE GENERAL NOTES LISTED HERE APPLY TO ALL PLUMBING DRAWINGS IN ADDITION TO ANY

ADDITIONAL DRAWING NOTES ON THE INDIVIDUAL DRAWINGS.

2. SEE CODED NOTES ON INDIVIDUAL DRAWING SHEETS FOR SPECIFIC INSTRUCTIONAL NOTES.

3. FIELD VERIFY EXISTING CONDITIONS PRIOR TO THE START OF CONSTRUCTION.

4. THE PLUMBING CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE EXACT LOCATION AND

ELEVATION OF ALL EXISTING UNDERGROUND UTILITIES PRIOR TO COMMENCING WORK. THE

PLUMBING CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGES WHICH OCCURS BY HIS FAILURE TO

LOCATE OR PRESERVE THE UNDERGROUND CONDITIONS.

5. IF DURING CONSTRUCTION OPERATIONS, THE PLUMBING CONTRACTOR ENCOUNTERS UTILITIES

OTHER THAN THOSE LOCATIONS SHOWN IN THE PLANS, HE SHALL IMMEDIATELY NOTIFY THE

ENGINEER AND TAKE THE NECESSARY STEPS TO PROTECT THE FACILITY AND ASSURE THE

CONTINUANCE OF SERVICE.

6. COORDINATE WITH GENERAL TRADES WORK, HVAC WORK, FIRE PROTECTION WORK,

ELECTRICAL WORK AND OTHER WORK.

7. IT IS RECOGNIZED THAT DRAWINGS MAY BE PLOTTED AT DIFFERENT SCALES, SUCH THAT

PLOTTED DRAWINGS MAY VARY FROM ACTUAL OR INTENDED DIMENSIONS. THEREFORE,

DRAWINGS ARE DIAGRAMMATIC AND ARE NOT TO BE SCALED. SBM TAKES NO RESPONSIBILITY

FOR ERRORS REGARDING DISCREPANCIES FROM THE ORIGINAL DRAWINGS DRAWN AT THE

PROPER SCALE AND THOSE DRAWINGS THAT HAVE BEEN PLOTTED.

8. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS OF FIRE AND SMOKE WALLS AND RATED

STRUCTURES. SEE DETAILS AND SPECIFICATIONS FOR PIPE PENETRATION SEAL REQUIREMENTS.

9. THE PLUMBING DESIGN DRAWINGS ARE DIAGRAMMATIC AND ARE NOT INTENDED TO SHOW

EXACT LOCATION OF EQUIPMENT AND PIPING UNLESS DIMENSIONS ARE GIVEN OR OTHERWISE

IMPLIED FOR CLEARANCES, ETC. PIPING AND PLUMBING EQUIPMENT ARE TO BE INSTALLED ALONG

THE GENERAL PLANS SHOWN ON THE DRAWINGS, BUT KEEPING IN MIND ACTUAL BUILDING

CONDITIONS WHICH MUST BE CONFORMED WITH IN THE ACTUAL WORK. CONTRACTORS IN THEIR

BIDS ARE REQUIRED TO INCLUDE ALL LABOR AND MATERIALS AND OTHER RELATED WORK

NECESSARY TO PROVIDE MINOR OFFSETS IN PLUMBING WORK AS REQUIRED TO AVOID CONFLICT

WITH OTHER WORK ON THIS PROJECT OR AS REQUIRED IN ORDER TO OBTAIN MAXIMUM HEAD

ROOM OR EQUIPMENT ACCESS IN SPACES.

10. THE PLUMBING CONTRACTOR IS TO COORDINATE ALL PIPING WITH OTHER TRADES PRIOR TO ROUTING PIPING AND SHALL MAKE OFFSETS AND ADJUST PIPE ROUTING AS REQUIRED TO HANDLE

CONFLICTS IN FIELD. THE PLUMBING CONTRACTOR SHALL ALSO BE REQUIRED TO OFFSET

VERTICAL SANITARY AND VENT LINES AROUND STRUCTURAL MEMBERS AS REQUIRED AND SHALL

INCLUDE IN THEIR BASE BID THE ASSOCIATED COST FOR ADDITIONAL FITTINGS, PIPING, AND MAN

HOURS TO ACCOMMODATE CONFLICTS.

11. SEE ARCHITECTURAL PLANS FOR EXACT LOCATION AND ELEVATION OF PLUMBING FIXTURES.

12. ALL COLD WATER AND HOT WATER PIPING TO INDIVIDUAL SINKS AND INDIVIDUAL LAVATORIES

TO BE 1/2", UNLESS OTHERWISE INDICATED.

13. ALL COLD WATER AND HOT WATER PIPING SERVING 3 OR LESS SINKS OR LAVS ARE TO BE 3/4"

UNLESS NOTED OTHERWISE.

14. FINAL COLD WATER PIPING CONNECTIONS TO WATER CLOSETS TO BE 1-1/4".

15. UNLESS OTHERWISE NOTED SEE PLUMBING FIXTURE SCHEDULE FOR FIXTURE DRAIN, VENT, DCW AND DHW PIPE SIZES.

16. P.C. TO FURNISH WALL FLANGES AROUND ALL PIPING EXPOSED BELOW CEILING AND

CASEWORK.

17. P.C. TO COORDINATE ALL COUNTERTOP SINKS WITH CASEWORK TO ENSURE PROPER

INSTALLATION AND CLEARANCE REQUIREMENTS PRIOR TO ORDERING AND INSTALLATION.

COORDINATE ANY CHANGE IN SIZE OR CONFIGURATION WITH PROJECT ENGINEER AND ARCHITECT.

18. SEE PLUMBING ISOMETRICS FOR SANITARY PIPE SIZES NOT INDICATED ON FLOOR PLANS.

19. UNLESS OTHERWISE INDICATED, ALL PIPING TO RUN GENERALLY BELOW DUCTWORK FOR

ACCESS TO VALVING. DO NOT OBSTRUCT EQUIPMENT OR ACCESS DOORS.

20. SEE PROJECT SPECIFICATIONS FOR CUTTING AND PATCHING RESPONSIBILITIES.

21. FINAL FLOOR DRAIN ELEVATIONS ARE TO BE SET BY THE PLUMBING CONTRACTOR.

COORDINATE EXACT POSITIONING OF FLOOR DRAINS WITH HVAC CONTRACTOR TO SERVE HVAC

EQUIPMENT AS INTENDED, AND TO AVOID TRIPPING HAZARDS WITH ABOVE FLOOR DRAIN PIPING.

22. PLUMBING FIXTURE NUMBERS ARE SHOWN ON WASTE PLANS AND REFERS TO PLUMBING

FIXTURE SCHEDULE.

23. ACCESS PANELS ARE TO BE FURNISHED AND INSTALLED BY THE PLUMBING CONTRACTOR. THE

PLUMBING CONTRACTOR IS TO COORDINATE LOCATION AND INSTALLATION OF VALVES, SHOCK

STOPS, AND CLEANOUTS ABOVE ACCESS PANEL WITH G.C. AND ARCHITECTURAL DRAWINGS TO

MINIMZE SIZE OF PANELS.

24. EQUIPMENT CONNECTION ARRANGEMENTS, FLANGES, UNIONS, VALVING, ETC. ARE NOT

TYPICALLY SHOWN ON PLAN VIEWS. REFER TO DETAILS AND FLOW DIAGRAMS FOR

REQUIREMENTS. INSTALL ALL VALVES AND OTHER ITEMS REQUIRING OR FACILITATING

MAINTENANCE IN ACCESSIBLE LOCATIONS, AND SO AS TO NOT OBSTRUCT MAINTENANCE ON

EQUIPMENT SERVED.

DESCRIPTIONABBREVIATION SYMBOL

US

SAN

UST

DS

DCW

DHW

RDHW

PLUMBING SYMBOL LEGEND

US SANITARY SEWER BELOW FLOOR OR GRADE

SAN SANITARY SEWER ABOVE FLOOR

SANITARY VENT

UST STORM SEWER BELOW FLOOR OR GRADE

DS DOWNSPOUT ABOVE FLOOR (WITHIN BUILDING SPACE)

DCW DOMESTIC COLD WATER

DHW DOMESTIC HOT WATER

RDHW RECIRCULATED DOMESTIC HOT WATER

SHOCK STOP IN HORIZONTAL

BALL VALVE

BALANCE VALVE (SEE SPECIFICATIONS)

C.O. CLEANOUT

FW/FCO FLUSH WITH FLOOR CLEANOUT

FW/WCO FLUSH WITH WALL CLEANOUT

P__-__ PLUMBING FIXTURE (SEE SCHEDULE)

E.C. E.C. ELECTRICAL CONTRACTOR

F.S.C. F.S.C. FIRE SUPPRESSION CONTRACTOR

G.C. G.C. GENERAL CONTRACTOR

H.C. H.C. HVAC CONTRACTOR

P.C. P.C. PLUMBING CONTRACTOR

A.D. A.D. ACCESS DOOR

A.F.F. A.F.F. ABOVE FINISHED FLOOR

MFR. MFR. MANUFACTURER

TYP. TYP. TYPICAL

INDICATES TIE INTO EXISTING

INDICATES REMOVE TO POINT FOR RECONNECTION

INDICATES REMOVE TO POINT AND CAP

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

RE G IS T E RE

D

E-62197

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

CONSTRUCTION - ISSUED FOR

BID

Project Number

Building Number

Drawing Number

340, 341

VA Building 340, 341 Project Title

Location

Issued Date Checked Drawn

Drawing Title Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

SCHEESER BUCKLEY MAYFIELD

1540 CORPORATE WOODS PARKWAY

UNIONTOWN, OHIO 44685

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

Approved:

PHILIP P. KIRK

CHIEF ENGINEER

2/

/2

1:

: 3

PM

C :\U se rs

\J Bi lin s k i\D oc um en ts \1

_M E

P_ C

EN

TR

A L

FI

LE

_j bi lin sk i@ sb m ce

.c om

.rv t

PJ-100

552-20-104

CJS JMB

RENOVATE PRIMARY CARE FOR

PACT BLDG 340, BLDG 341

02/09/2021

4100 WEST THIRD STREET, DAYTON, OH 45428

PLUMBING GENERAL NOTES, SYMBOL

LEGEND AND SCHEDULES

02/09/2021 a1. "SLOAN" 111 ESS HARDWIRED SENSOR FLUSH VALVE, 1.28 GPF. PROVIDE WITH 120VAC/24VAC TRANSFORMER.

a2. "CHICAGO FAUCETS" 116.103 SENSOR FAUCET, GOOSENECK SPOUT, LAMINAR FLOW OUTLET, PROVIDE WITH HARD-WIRE TRANSFORMER.

b1."AMERICAN STANDARD" NO. 7723.018 OFFSET DRAIN ASSEMBLY b2."JUST" NO. J-35 GRID STRAINER.

c1.1-1/4" CHROME PLATED CAST BRASS P-TRAP W/ CLEANOUT c2.1-1/2" CHROME PLATED CAST BRASS P-TRAP W/ CLEANOUT d1."CHICAGO FAUCET" NO. 1017 LOOSE KEY ANGLE STOPS AND 3/8" O.D. FLEXIBLE RISERS AND WALL FLANGE d2. "BROCAR" PIPING WRAP ON EXPOSED PIPING.

NOTE: CONTRACTOR TO PROGRAM ALL FAUCETS, COORDINATE FAUCET RUN TIMES WITH OWNER.

NOTES:

PLUMBING FIXTURE SCHEDULE

MARK NO. DESCRIPTION MAKE OR APPROVED

EQUAL MODEL SIZE TRIM DRANINAGE WATER CARRIER REMARKSW.P. V.P. CW HW

P-103 WATER CLOSET (ADA) AMERICAN STANDARD "AFWALL" 3351.128 a1 4" 2" 1-1/4" - "WADE" 300 SERIES WALL MOUNT BACK OUTLET, VITREOUS CHINA, 17" RIM HEIGHT, DIRECT-FED SIPHON JET ACTION, ELONGATED BOWL, FULLY-GLAZED 2" BALLPASS TRAPWAY, 1-1/2" TOP SPUD. PROVIDE WITH CHURCH

#9500C OPEN FRONT SEAT, LESS COVER WITH CHECK HINGES.

P-418 LAVATORY (ADA) AMERICAN STANDARD "LUCERNE" 0356.421 21"x18" a2, b1, c1, d1, d2 1-1/2" 1-1/2" 1/2" 1/2" "WADE" W-520-07 VITREOUS CHINA, FRONT OVERFLOW, D-SHAPED BOWL, FAUCET LEDGE, SELF DRAINING DECK AREA WITH

CONTOURED BACK AND SIDE SPLASH AREAS AND SINGLE FAUCET HOLE

P-528 SINK JUST SL-17519-A-GR 19"x17.5" a2, b2, c2, d1 1-1/2" 1-1/2" 1/2" 1/2" 18 GA. 302 STAINLESS STEEL, SINGLE COMPARTMENT, UNDERCOUNTER MOUNTED, SELF-RIMMING, UNDERCOATED.

P-608 WATER COOLER (ADA) OASIS PG8EBFSL 1-1/2" 1-1/2" 1/2" - WALL HUNG, TWO-LEVEL WHEELCHAIR ACCESS MODEL WITH BOTTLE FILLER AND FILTER. 8.0 GPH

CAPACITY, 1/4 HP COMPRESSOR, 115 V/1 P, 4.6 FLA.

P-800 FROSTPROOF PEDESTAL

HYDRANT

MAPA PRODUCTS 1" FROSTPROOF PEDESTAL HYDRANT WITH BLACK POWDER COATED CAST ALUMINUM WEATHER GUARD, DOME HANDLE, TYPE 304 S.S. SHROUD WITH FLANGE, BUILT-IN VACUUM BREAKER AND RESERVOIR.

SHOCK ABSORBER PPP 1-1/4", FIXTURE CAPACITY: 61-113 (PDI "D")

SHOCK ABSORBER PPP 1", FIXTURE CAPACITY: 33-60 (PDI "C")

SHOCK ABSORBER PPP 3/4", FIXTURE CAPACITY: 12-32 (PDI "B")

SHOCK ABSORBER PPP 1/2", FIXTURE CAPACITY: 1-11 (PDI "A")

DESCRIPTION MANUFACTURE REMARKS

SHOCK ABSORBER SCHEDULE

NOTES:

DRAINS AND CLEANOUTS SCHEDULE

MARK. NO. DESCRIPTION MAKE/MODEL/SIZE REMARKS

C.O.

FW/FCO FLUSH WITH FLOOR

CLEANOUT

WADE NO. W-6000 CAST IRON FLOOR CLEANOUT WITH SPIGOT OUTLET FOR "NO-HUB" OR "TY-SEAL" CONNECTION, THREADED ADJUSTIBLE HOUSING, FLANGED FERRULE WITH PLUG AND ROUND SECURED NICKEL

BRONZE TOP. TOP TO MATCH FINISHED FLOOR AREA.

RD-1 OVERFLOW ROOF DRAIN WADE NO. 300SD SERIES CAST IRON ROOF DRAIN WITH FLANGE, FLASHING RING WITH GRAVEL STOP, CAST IRON MUSHROOM

DOME, UNDERDECK CLAMP, ADJUSTABLE EXTENSIONS, AND 6" DIAMETER PLASTIC STANDPIPE.

Revisions Date

CONSTRUCTION - ISSUED FOR BID 02/09/2021

WALL SECTION

FLOOR SECTION

FURNISH AND INSTALL

FIRESTOP MATERIALS IN

ACCORDANCE WITH

APPROPRIATE U.L. SYSTEMS

TO MAINTAIN FIRE RESISTANCE

RATING

PIPE SLEEVE

DAMMING MATERIAL

(PER U.L. TESTED

SYSTEM DESIGN)

FLOOR SLAB; SEE

ARCHITECTURAL DRAWINGS

FOR FLOOR CONSTRUCTION

AND FIRE RATING

PIPE INSULATION

(WHERE SPECIFIED)

PENETRATING COMPONENT

FURNISH AND INSTALL FIRESTOP

MATERIALS IN ACCORDANCE WITH

APPROPRIATE U.L. SYSTEMS TO

MAINTAIN FIRE RESISTANCE RATING

PIPE SLEEVE (SLEEVE TO

EXTEND 2" ABOVE FLOOR

IN MECHANICAL EQUIPMENT

ROOMS.)

SEAL JOINT BETWEEN SLEEVE

AND FLOOR SLAB WITH MIN. 1/2"

BEAD FIRESTOP CAULK

SEE ARCHITECTURAL

DRAWINGS FOR WALL

CONSTRUCTION AND FIRE

RATING

PENETRATING COMPONENT

PIPE INSULATION

(WHERE SPECIFIED)

NOTES:

1. WHERE PIPES, DUCTS AND OTHER COMPONENTS PASS THROUGH FIRE OR SMOKE RATED WALLS OR FLOORS, PROVIDE NON-ASBESTOS SEAL ASSEMBLIES CLASSIFIED BY U.L. TO PROVIDE FIRE BARRIERS EQUAL TO OR GREATER THAN THE TIME RATING OF THE CONSTRUCTION BEING PENETRATED, WITH APPROPRIATE MATERIALS AND SYSTEMS THAT COMPLY WITH APPLICABLE CODES AND THAT HAVE BEEN

TESTED IN ACCORDANCE WITH U.L. 1479 OR ASTM E814.

2. GROUT, MORTAR OR GYPSUM BASED PRODUCTS SHALL NOT BE INSTALLED IN LIEU OF FIRESTOPPING

MATERIALS AND U.L. SYSTEMS.

3. FOR SLEEVED PENETRATIONS, FIRESTOP ANNULAR SPACE, IF ANY, BETWEEN SLEEVE AND ADJACENT

CONSTRUCTION TO MEET U.L. SYSTEM REQUIREMENTS. SEE NOTE 2 ABOVE.

4. THIS CONTRACTOR SHALL FIRESTOP ALL MISCELLANEOUS OPENINGS IN FIRE-RATED CONSTRUCTION

RESULTING FROM HIS WORK.

5. CONTRACTOR SHALL PROVIDE SUBMITTAL DRAWINGS TO ARCHITECT, INCLUDING U.L. RATED SYSTEM

NUMBER AND DETAIL FOR EACH TYPE OF PENETRATION AND CONFIGURATION.

6. THE FIRESTOPPING SYSTEMS ARE TO BE INSTALLED BY EXPERIENCED, MANUFACTURER TRAINED, AND

UL CERTIFIED OR FM CERTIFIED PERSONNEL.

7. ALL FIRESTOPPING MATERIAL IS TO BE PROVIDED FROM A SINGLE MANUFACTURER FOR ALL

APPLICATIONS.

8. CONTRACTOR SHALL CONSULT MANUFACTURER'S TECHNICAL EXPERTS FOR ASSISTANCE IN SELECTING

APPROPRIATE FIRESTOPPING SYSTEM FOR EACH APPLICATION.

THROUGH FIRE-RATED CONSTRUCTIONS

N.T.S.

FIRESTOPPING DETAIL FOR PENETRATIONS

CLEVIS HANGER PIPE SUPPORT

N.T.S.

NOTE:

REFER TO HANGER SPECIFICATIONS

FOR ADDITIONAL REQUIREMENTS.

PIPE ℄

TYPICAL FOR

UN-INSULATED PIPE

TYPICAL FOR

INSULATED PIPE

STRUCTURAL FRAMING

NOTE: SUPPLY ADDITIONAL

SUPPORT STEEL AS

REQUIRED

BEAM CLAMP

HEX NUTS (4 REQUIRED)

THREADED ROD (SEE

SPECIFICATIONS FOR DIAMETER)

ADJUSTABLE CLEVIS HANGER

PIPE WITH INSULATION AND

JACKET (AS APPLICABLE).

SEE SPECIFICATIONS FOR

REQUIREMENTS.

180 DEG. INSULATION PROTECTION

SHIELD, 14 GA., GALVANIZED BY 18"

LONG FOR PIPING 8" AND OVER.

SEE SPECIFICATIONS FOR 6" AND

UNDER.

SUPPORT BLOCK (SEE

SPECIFICATIONS)

INTERIOR DRAIN CLEANOUT DETAIL

N.T.S.

"Y" BRANCH

FINISHED GRADE

ADJUSTABLE HOUSING

6" C.I. ENCASED IN IN CONCRETE

6" THICK ON EACH SIDE OF PIPE

6" C.I.

P.C. TO COORDINATE WITH ROOM FINISH SCHEDULE

AND PLUMBING FIXTURE SCHEDULE, PROVIDE

CARPET MARKERS WHERE APPLICABLE.

COORDINATE LOCATIONS WITH CARPET INSTALLER.

P.C. TO FURNISH COVER LIDS TO MATCH TYPE OF

FLOOR FINISH.

M A

X

8 "

10 3/4"

FAUCET

LAMINAR FLOW

CONTROL DEVICE

LOOSE KEY

ANGLE STOP

OFFSET WASTE

TRAP PARALLEL TO

WALL

ESCUTCHEON

FINISHED FLOOR

TYPICAL WHEELCHAIR LAVATORY DETAIL

N.T.S.

SEE DRAWINGS FOR SIZES

UNDERDECK CLAMP

P.C. TO INSTALL ALL

NECESSARY SUPPORT

BRACING PLATE AROUND

OPENING AS REQUIRED TO

INSTALL ROOF DRAIN.

FLASHING AND COUNTER

FLASHING BY ROOFING

CONTRACTOR. P.C. TO

COORDINATE AND SECURE

ROOFING MEMBRANE TO ROOF

DRAIN.

OVERFLOW DAM

ROOF MEMBRANE

INSULATION

INSULATE ALL VERTICAL AND

HORIZONTAL SECTIONS OF

DOWNSPOUT, SEE

DOWNSPOUT DETAIL

METAL DECK

TYPICAL OVERFLOW ROOF DRAIN

N.T.S.

CHASE WALL

STORM DRAIN

DOWNSPOUT NOZZLE

WITH SCREEN.

MOUNT 6" ABOVE

FINISHED GRADE.

COORDINATE INSTALLATION

OF NOZZLE WITH WALL

WORK. GROUT ALL OPEN

AREAS AROUND EXTERIOR

FLANGE. SECURE TO WALL

WITH STAINLESS STEEL

FASTENERS.

PLUMBING CHASE

EXTERIOR WALL

GRADE

CONCRETE SPLASH BLOCK.CAULK REMAINING AREA

WEATHERTIGHT

INSTALL THROUGH

SMOOTH BORE HOLE BY

CORE DRILLING

EXTERIOR BLOCK

DOWNSPOUT NOZZLE DETAIL

N.T.S.

WALL CLEANOUT DETAIL

N.T.S.

TEST TEE

THREADED

CLEANOUT PLUG

ACCESS COVER

AND FRAME

FINISHED WALL

AND SURFACE

FREEZE-PROOF PEDESTAL HYDRANT DETAIL

N.T.S.

NOTES:

1. COMPOSITION:

BLACK POWDER COATED CAST ALUMINUM

WEATHER-GUARD DOME HANDLE

GRADE 304 STAINLESS STEEL SHROUD WITH WELDED

STAINLESS STEEL FLANGE

125 LB. 1" BRONZE GLOBE ANGLE VALVE/MALE HOSE

FITTING/QUICK DISCONNECT WITH BUILT-IN VACUUM

BREAKER

STAINLESS STEEL RESERVOIR

2. INSULATION:

R-8 RATED/THERMO-CELL INSULATION

3. MOUNTING HARDWARE:

BLACK POWDER COATED UNDER-DECK SUPPORT

FLANGE WITH HARDWARE

UNDER DECK

FLANGE

STAINLESS SHROUD

1" GALVANIZED

NIPPLE

STAINLESS SHROUD

BRASS VALVE FLOAT

ASSEMBLY

CONTINUOUS WELDED

SEAM

ROOF MEMBRANE

ROOF INSULATION

ROOF DECKING

ANGLE FRAMING

1/4" FLANGE NUT

1/4"x1-1/2" SET SCREW

SUPPLY TUBING

1" DCW LINE FOM

DOMESTIC WATER

SUPPLY

24"

10"

10"

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

RE G IS T E RE

D

E-62197

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

CONSTRUCTION - ISSUED FOR

BID

Project Number

Building Number

Drawing Number

340, 341

VA Building 340, 341 Project Title

Location

Issued Date Checked Drawn

Drawing Title Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

SCHEESER BUCKLEY MAYFIELD

1540 CORPORATE WOODS PARKWAY

UNIONTOWN, OHIO 44685

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

Approved:

PHILIP P. KIRK

CHIEF ENGINEER

2/

/2

1:

: 3

PM

C :\U se rs

\J Bi lin s k i\D oc um en ts \1

_M E

P_ C

EN

TR

A L

FI

LE

_j bi lin sk i@ sb m ce

.c om

.rv t

PJ-101

552-20-104

CJS JMB

RENOVATE PRIMARY CARE FOR

PACT BLDG 340, BLDG 341

02/09/2021

4100 WEST THIRD STREET, DAYTON, OH 45428

PLUMBING DETAILS

02/09/2021

91110 9

US

USUS

US

USTUSTUST

U S

U S

US US US

U S

U S

U S

D S

U S

U S

USTUSTUST

U

ST

US

U

ST

14131313

CODED NOTES

1. EXISTING LAVATORY / SINK TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED

SANITARY DOWN TO BELOW GRADE AND CAP WATER TIGHT. DISCONNECT AND REMOVE

ASSOCIATED VENT PIPING AS SHOWN. PATCH FLOOR AS REQUIRED TO MATCH EXISTING

CONDITIONS.

2. EXISTING WATER CLOSET TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED

SANITARY DOWN TO BELOW GRADE AND CAP WATER TIGHT. DISCONNECT AND REMOVE

ASSOCIATED VENT PIPING AS SHOWN. PATCH FLOOR AS REQUIRED TO MATCH EXISTING

CONDITIONS.

3. REMOVE EXISTING VENT PIPING BACK TO POINT INDICATED AND CAP AIR TIGHT.

4. EXISTING SINK TO BE RELOCATED. DISCONNECT AND REMOVE ASSOCIATED SANITARY AND

VENT PIPING AS REQUIRED FOR NEW SINK LOCATION.

5. EXISTING MOP BASIN TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED SANITARY

DOWN TO BELOW GRADE AND CAP WATER TIGHT. DISCONNECT AND REMOVE ASSOCIATED VENT

PIPING AS SHOWN. PATCH FLOOR AS REQUIRED TO MATCH EXISTING CONDITIONS.

6. REMOVE EXISTING VENT PIPING BACK TO POINT INDICATED FOR RECONNECTION UNDER NEW

WORK.

7. REMOVE EXISTING DS PIPING BACK TO POINT INDICATED FOR RECONNECTION UNDER NEW

WORK.

8. REMOVE EXISTING DS PIPING DOWN TO BELOW GRADE AND CAP WATER TIGHT. PATCH FLOOR

AS REQUIRED TO MATCH EXISTING CONDITIONS.

9. EXISTING LAVATORY / SINK TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED

SANITARY DOWN TO BELOW GRADE AND CAP WATER TIGHT. DISCONNECT AND REMOVE

ASSOCIATED VENT PIPING BACK TO MAIN AND CAP AIR TIGHT. PATCH FLOOR AS REQUIRED TO

MATCH EXISTING CONDITIONS.

10. EXISTING WATER CLOSET TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED

SANITARY AND VENT PIPING AS REQUIRED FOR CONNECTION TO NEW WATER CLOSET.

11. EXISTING LAV/SINK TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED SANITARY AND

VENT PIPING AS REQUIRED FOR CONNECTION TO NEW WATER CLOSET.

12. EXISTING LAVATORY / SINK TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED INTO

WALL FOR RECONNECTION UNDER NEW WORK.

13. EXISTING LAVATORY / SINK TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED

SANITARY AS REQUIRED FOR EXTENSION TO NEW SINK. DISCONNECT AND REMOVE ASSOCIATED

VENT PIPING AS SHOWN.

14. EXISTING LAVATORY / SINK TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED

SANITARY DOWN TO BELOW GRADE AND CAP WATER TIGHT. DISCONNECT AND REMOVE

ASSOCIATED VENT BACK TO MAIN AND CAP AIR TIGHT. PATCH FLOOR AS REQUIRED TO MATCH

EXISTING CONDITIONS.

PLAN NOTES

A. SEE SHEET PJ-100 FOR GENERAL NOTES AND SYMBOL LEGEND.

B. EXISTING PIPING AND EQUIPMENT TO REMAIN SHOWN WITH LIGHT LINES.

C. EXISTING PIPING AND EQUIPMENT TO BE REMOVED SHOWN WITH DARK DASHED LINES.

D. REFER TO ARCHITECTURAL PLANS FOR PHASING AND SUB-PHASING AREAS OF WORK.

E. ACCESS TO ALL AREAS OUTSIDE OF PHASE AND SUB-PHASE CONSTRUCTION AREAS

INDICATED TO BE FULLY ACCESSIBLE TO STAFF AND PATIENTS THROUGH OUT NORMAL WORKING HOURS. ALL LIMITED SCOPE SUPPORTING ACTIVITIES TO BE COORDINATED WITH THE VA COR.

ALL WORK DEEMED DISRUPTIVE BY COR TO BE CONDUCTED OUTSIDE NORMAL WORKING HOURS

(7:30 AM TO 5:00 PM).

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

RE G IS T E RE

D

E-62197

0' 1'

2'

1/ 2"

' 0

0' 1'

3'

3/ 8"

' 0

0' 2'

4'

1/ 4"

' 0

0' 3'

6' 1'

3/

' 0

0' 4'

8' 2'1/

8"

' 0

0' 3'

3/

' 0

6' 0'

8'

4'1/

' 0

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

CONSTRUCTION - ISSUED FOR

BID

Project Number

Building Number

Drawing Number

340, 341

VA Building 340, 341 Project Title

Location

Issued Date Checked Drawn

Drawing Title Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

SCHEESER BUCKLEY MAYFIELD

1540 CORPORATE WOODS PARKWAY

UNIONTOWN, OHIO 44685

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

Approved:

PHILIP P. KIRK

CHIEF ENGINEER

2/

/2

1:

: 0

PM

C :\U se rs

\J Bi lin s k i\D oc um en ts \1

_M E

P_ C

EN

TR

A L

FI

LE

_j bi lin sk i@ sb m ce

.c om

.rv t

PD-100

552-20-104

CJS JMB

RENOVATE PRIMARY CARE FOR

PACT BLDG 340, BLDG 341

02/09/2021

4100 WEST THIRD STREET, DAYTON, OH 45428

DEMOLITION - FIRST FLOOR PLAN -

PLUMBING (SANITARY) PHASE 1

02/09/2021

N 1/8" = 1'-0"

DEMOLITION - FIRST FLOOR PLAN - PLUMBING (SANITARY) PHASE 1

3 4

1110 1

DHW

DCW

DHW

D H

W

DCW

DHW

D H

W

DCW

DHW

DCW

DHW

DCW

DHW

DHW

D H

W

DHW

D H

W

DHW

RDHW

R D

H W

RDHW RDHW

R D

H W

D H

W

12 12

CODED NOTES

1. EXISTING LAVATORY / SINK TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED DCW

AND DHW PIPING AS SHOWN.

2. EXISTING WATER CLOSET TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED DCW AS

SHOWN.

3. REMOVE EXISTING DCW AND DHW PIPING BACK TO POINTS INDICATED AND CAP WATER TIGHT.

4. EXISTING SINK TO BE RELOCATED. DISCONNECT AND REMOVE ASSOCIATED DCW AND DHW

PIPING AS REQUIRED FOR NEW SINK LOCATION.

5. EXISTING MOP BASIN TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED DCW AND

DHW PIPING AS SHOWN.

6. EXISTING LAVATORY / SINK TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED DCW

AND DHW PIPING BACK TO MAINS AND CAP WATER TIGHT.

7. REMOVED EXISTING DCW AND DHW PIPING BACK TO POINTS INDICATED FOR RECONNECTION

UNDER NEW WORK.

8. EXISTING HOSE BIB TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED DCW PIPING AS

SHOWN.

9. REMOVE EXISTING DCW PIPING BACK TO POINT INDICATED AND CAP WATER TIGHT.

10. EXISTING WATER CLOSET TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED DCW

AND DHW PIPING AS REQUIRED FOR CONNECTION TO NEW WATER CLOSET.

11. EXISTING LAV/SINK TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED DCW AND DHW

PIPING AS REQUIRED FOR CONNECTION TO NEW LAV/SINK.

12. EXISTING LAV/SINK TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED DCW AND DHW

PIPING BACK TO MAIN AND CAP WATER TIGHT.

PLAN NOTES

A. SEE SHEET PJ-100 FOR GENERAL NOTES AND SYMBOL LEGEND.

B. EXISTING PIPING AND EQUIPMENT TO REMAIN SHOWN WITH LIGHT LINES.

C. EXISTING PIPING AND EQUIPMENT TO BE REMOVED SHOWN WITH DARK DASHED LINES.

D. REFER TO ARCHITECTURAL PLANS FOR PHASING AND SUB-PHASING AREAS OF WORK.

E. ACCESS TO ALL AREAS OUTSIDE OF PHASE AND SUB-PHASE CONSTRUCTION AREAS

INDICATED TO BE FULLY ACCESSIBLE TO STAFF AND PATIENTS THROUGH OUT NORMAL WORKING HOURS. ALL LIMITED SCOPE SUPPORTING ACTIVITIES TO BE COORDINATED WITH THE VA COR.

ALL WORK DEEMED DISRUPTIVE BY COR TO BE CONDUCTED OUTSIDE NORMAL WORKING HOURS

(7:30 AM TO 5:00 PM).

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

RE G IS T E RE

D

E-62197

0' 1'

2'

1/ 2"

' 0

0' 1'

3'

3/ 8"

' 0

0' 2'

4'

1/ 4"

' 0

0' 3'

6' 1'

3/

' 0

0' 4'

8' 2'1/

8"

' 0

0' 3'

3/

' 0

6' 0'

8'

4'1/

' 0

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

CONSTRUCTION - ISSUED FOR

BID

Project Number

Building Number

Drawing Number

340, 341

VA Building 340, 341 Project Title

Location

Issued Date Checked Drawn

Drawing Title Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

SCHEESER BUCKLEY MAYFIELD

1540 CORPORATE WOODS PARKWAY

UNIONTOWN, OHIO 44685

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

Approved:

PHILIP P. KIRK

CHIEF ENGINEER

2/

/2

1:

: 0

PM

C :\U se rs

\J Bi lin s k i\D oc um en ts \1

_M E

P_ C

EN

TR

A L

FI

LE

_j bi lin sk i@ sb m ce

.c om

.rv t

PD-101

552-20-104

CJS JMB

RENOVATE PRIMARY CARE FOR

PACT BLDG 340, BLDG 341

02/09/2021

4100 WEST THIRD STREET, DAYTON, OH 45428

DEMOLITION - FIRST FLOOR PLAN -

PLUMBING (WATER) PHASE 1

02/09/2021

N 1/8" = 1'-0"

DEMOLITION - FIRST FLOOR PLAN - PLUMBING (WATER) PHASE 1

2 2

1 1

3 3

1 1 1

UST

US

U

ST

US

UST

US

USTUS

U S

U S

U S

U S

USTUST

U

ST

U S

US US US

U S

D S

D S

US US

CODED NOTES

1. EXISTING LAVATORY / SINK TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED

SANITARY DOWN TO BELOW GRADE AND CAP WATER TIGHT. DISCONNECT AND REMOVE

ASSOCIATED VENT PIPING AS SHOWN. PATCH FLOOR AS REQUIRED TO MATCH EXISTING

CONDITIONS.

2. EXISTING WATER CLOSET TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED

SANITARY DOWN TO BELOW GRADE AND CAP WATER TIGHT. DISCONNECT AND REMOVE

ASSOCIATED VENT PIPING AS SHOWN. PATCH FLOOR AS REQUIRED TO MATCH EXISTING

CONDITIONS.

3. REMOVE EXISTING VENT PIPING BACK TO POINT INDICATED AND CAP AIR TIGHT.

4. EXISTING SINK TO BE RELOCATED. DISCONNECT AND REMOVE ASSOCIATED SANITARY AND

VENT PIPING AS REQUIRED FOR NEW SINK LOCATION.

5. EXISTING MOP BASIN TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED SANITARY

DOWN TO BELOW GRADE AND CAP WATER TIGHT. DISCONNECT AND REMOVE ASSOCIATED VENT

PIPING AS SHOWN.

6. REMOVE EXISTING VENT PIPING BACK TO POINT INDICATED FOR RECONNECTION UNDER NEW

WORK.

7. REMOVE EXISTING DS PIPING BACK TO POINT INDICATED FOR RECONNECTION UNDER NEW

WORK.

8. REMOVE EXISTING DS PIPING DOWN TO BELOW GRADE AND CAP WATER TIGHT.

9. EXISTING FLOOR DRAIN TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED SANITARY

DOWN TO BELOW GRADE AND CAP WATER TIGHT. PATCH FLOOR AS REQUIRED TO MATCH

EXISTING CONDITIONS.

10. EXISTING LAVATORY / SINK TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED

SANITARY BACK INTO WALL AS REQUIRED FOR RECONNECTION UNDER NEW WORK.

DISCONNECT AND REMOVE ASSOCIATED VENT PIPING AS SHOWN.

PLAN NOTES

A. SEE SHEET PJ-100 FOR GENERAL NOTES AND SYMBOL LEGEND.

B. EXISTING PIPING AND EQUIPMENT TO REMAIN SHOWN WITH LIGHT LINES.

C. EXISTING PIPING AND EQUIPMENT TO BE REMOVED SHOWN WITH DARK DASHED LINES.

D. REFER TO ARCHITECTURAL PLANS FOR PHASING AND SUB-PHASING AREAS OF WORK.

E. ACCESS TO ALL AREAS OUTSIDE OF PHASE AND SUB-PHASE CONSTRUCTION AREAS

INDICATED TO BE FULLY ACCESSIBLE TO STAFF AND PATIENTS THROUGH OUT NORMAL WORKING HOURS. ALL LIMITED SCOPE SUPPORTING ACTIVITIES TO BE COORDINATED WITH THE VA COR.

ALL WORK DEEMED DISRUPTIVE BY COR TO BE CONDUCTED OUTSIDE NORMAL WORKING HOURS

(7:30 AM TO 5:00 PM).

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

RE G IS T E RE

D

E-62197

0' 1'

2'

1/ 2"

' 0

0' 1'

3'

3/ 8"

' 0

0' 2'

4'

1/ 4"

' 0

0' 3'

6' 1'

3/

' 0

0' 4'

8' 2'1/

8"

' 0

0' 3'

3/

' 0

6' 0'

8'

4'1/

' 0

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

CONSTRUCTION - ISSUED FOR

BID

Project Number

Building Number

Drawing Number

340, 341

VA Building 340, 341 Project Title

Location

Issued Date Checked Drawn

Drawing Title Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

SCHEESER BUCKLEY MAYFIELD

1540 CORPORATE WOODS PARKWAY

UNIONTOWN, OHIO 44685

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

Approved:

PHILIP P. KIRK

CHIEF ENGINEER

2/

/2

1:

: 1

PM

C :\U se rs

\J Bi lin s k i\D oc um en ts \1

_M E

P_ C

EN

TR

A L

FI

LE

_j bi lin sk i@ sb m ce

.c om

.rv t

PD-102

552-20-104

CJS JMB

RENOVATE PRIMARY CARE FOR

PACT BLDG 340, BLDG 341

02/09/2021

4100 WEST THIRD STREET, DAYTON, OH 45428

DEMOLITION - FIRST FLOOR PLAN -

PLUMBING (SANITARY) PHASE 2

02/09/2021

N 1/8" = 1'-0"

DEMOLITION - FIRST FLOOR PLAN - PLUMBING (SANITARY) PHASE 2

1 11

4 4

DCW

DHW

DHW

DCW

D H

W

DHW

DCW

DHW

RDHW

D H

W R

D H

W

RDHW

DHW

DHW

DCW

DHW

DCW

DCW

DHW

D H

W D

C W

D H

W D

C W

D C

W D

H W

D C

W

D C

W

CODED NOTES

1. EXISTING LAVATORY / SINK TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED DCW

AND DHW PIPING AS SHOWN.

2. EXISTING WATER CLOSET TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED DCW AS

SHOWN.

3. REMOVED EXISTING DCW AND DHW PIPING BACK TO POINTS INDICATED AND CAP WATER

TIGHT.

4. REMOVED EXISTING DCW PIPING BACK TO POINT INDICATED AND CAP WATER TIGHT.

5. REMOVED EXISTING DHW PIPING BACK TO POINT INDICATED AND CAP WATER TIGHT.

6. REMOVED EXISTING DCW PIPING BACK TO POINT INDICATED FOR RECONNECTION UNDER NEW

WORK.

7. REMOVED EXISTING DHW PIPING BACK TO POINT INDICATED FOR RECONNECTION UNDER NEW

WORK.

PLAN NOTES

A. SEE SHEET PJ-100 FOR GENERAL NOTES AND SYMBOL LEGEND.

B. EXISTING PIPING AND EQUIPMENT TO REMAIN SHOWN WITH LIGHT LINES.

C. EXISTING PIPING AND EQUIPMENT TO BE REMOVED SHOWN WITH DARK DASHED LINES.

D. REFER TO ARCHITECTURAL PLANS FOR PHASING AND SUB-PHASING AREAS OF WORK.

E. ACCESS TO ALL AREAS OUTSIDE OF PHASE AND SUB-PHASE CONSTRUCTION AREAS

INDICATED TO BE FULLY ACCESSIBLE TO STAFF AND PATIENTS THROUGH OUT NORMAL WORKING HOURS. ALL LIMITED SCOPE SUPPORTING ACTIVITIES TO BE COORDINATED WITH THE VA COR.

ALL WORK DEEMED DISRUPTIVE BY COR TO BE CONDUCTED OUTSIDE NORMAL WORKING HOURS

(7:30 AM TO 5:00 PM).

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

RE G IS T E RE

D

E-62197

0' 1'

2'

1/ 2"

' 0

0' 1'

3'

3/ 8"

' 0

0' 2'

4'

1/ 4"

' 0

0' 3'

6' 1'

3/

' 0

0' 4'

8' 2'1/

8"

' 0

0' 3'

3/

' 0

6' 0'

8'

4'1/

' 0

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

CONSTRUCTION - ISSUED FOR

BID

Project Number

Building Number

Drawing Number

340, 341

VA Building 340, 341 Project Title

Location

Issued Date Checked Drawn

Drawing Title Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

SCHEESER BUCKLEY MAYFIELD

1540 CORPORATE WOODS PARKWAY

UNIONTOWN, OHIO 44685

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

Approved:

PHILIP P. KIRK

CHIEF ENGINEER

2/

/2

1:

: 2

PM

C :\U se rs

\J Bi lin s k i\D oc um en ts \1

_M E

P_ C

EN

TR

A L

FI

LE

_j bi lin sk i@ sb m ce

.c om

.rv t

PD-103

552-20-104

CJS JMB

RENOVATE PRIMARY CARE FOR

PACT BLDG 340, BLDG 341

02/09/2021

4100 WEST THIRD STREET, DAYTON, OH 45428

DEMOLITION - FIRST FLOOR PLAN -

PLUMBING (WATER) PHASE 2

02/09/2021

N 1/8" = 1'-0"

DEMOLITION - FIRST FLOOR PLAN - PLUMBING (WATER) PHASE 2

UST

US

U

ST

UST

USUS

US US

U S

U

ST

UST

U S

UST UST

U S

U S

US US US

O

D S O

D S

U S

U S

U

ST

U S

CODED NOTES

1. EXISTING LAVATORY / SINK TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED

SANITARY AS REQUIRED FOR EXTENSION TO NEW SINK. DISCONNECT AND REMOVE ASSOCIATED

VENT PIPING AS SHOWN.

2. EXISTING VENT PIPING TO BE REMOVED BACK TO POINT INDICATED FOR RECONNECTION

UNDER NEW WORK.

3. EXISTING LAVATORY / SINK TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED

SANITARY DOWN TO BELOW GRADE AND CAP WATER TIGHT. DISCONNECT AND REMOVE

ASSOCIATED VENT BACK TO MAIN AND CAP AIR TIGHT. PATCH FLOOR AS REQUIRED TO MATCH

EXISTING CONDITIONS.

4. REMOVE EXISTING VENT PIPING BACK TO POINT INDICATED AND CAP AIR TIGHT.

PLAN NOTES

A. SEE SHEET PJ-100 FOR GENERAL NOTES AND SYMBOL LEGEND.

B. EXISTING PIPING AND EQUIPMENT TO REMAIN SHOWN WITH LIGHT LINES.

C. EXISTING PIPING AND EQUIPMENT TO BE REMOVED SHOWN WITH DARK DASHED LINES.

D. NO WORK SHALL BE COMPLETED IF ALTERNATE 5 IS ACCEPTED.

E. REFER TO ARCHITECTURAL PLANS FOR PHASING AND SUB-PHASING AREAS OF WORK.

F. ACCESS TO ALL AREAS OUTSIDE OF PHASE AND SUB-PHASE CONSTRUCTION AREAS

INDICATED TO BE FULLY ACCESSIBLE TO STAFF AND PATIENTS THROUGH OUT NORMAL WORKING HOURS. ALL LIMITED SCOPE SUPPORTING ACTIVITIES TO BE COORDINATED WITH THE VA COR.

ALL WORK DEEMED DISRUPTIVE BY COR TO BE CONDUCTED OUTSIDE NORMAL WORKING HOURS

(7:30 AM TO 5:00 PM).

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

RE G IS T E RE

D

E-62197

0' 1'

2'

1/ 2"

' 0

0' 1'

3'

3/ 8"

' 0

0' 2'

4'

1/ 4"

' 0

0' 3'

6' 1'

3/

' 0

0' 4'

8' 2'1/

8"

' 0

0' 3'

3/

' 0

6' 0'

8'

4'1/

' 0

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

CONSTRUCTION - ISSUED FOR

BID

Project Number

Building Number

Drawing Number

340, 341

VA Building 340, 341 Project Title

Location

Issued Date Checked Drawn

Drawing Title Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

SCHEESER BUCKLEY MAYFIELD

1540 CORPORATE WOODS PARKWAY

UNIONTOWN, OHIO 44685

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

Approved:

PHILIP P. KIRK

CHIEF ENGINEER

2/

/2

1:

: 2

PM

C :\U se rs

\J Bi lin s k i\D oc um en ts \1

_M E

P_ C

EN

TR

A L

FI

LE

_j bi lin sk i@ sb m ce

.c om

.rv t

PD-104

552-20-104

CJS JMB

RENOVATE PRIMARY CARE FOR

PACT BLDG 340, BLDG 341

02/09/2021

4100 WEST THIRD STREET, DAYTON, OH 45428

DEMOLITION - FIRST FLOOR PLAN -

PLUMBING (SANITARY) PHASE 3

02/09/2021

N 1/8" = 1'-0"

DEMOLITION - FIRST FLOOR PLAN - PLUMBING (SANITARY) PHASE 3

2 2

DHW

DCW

R D

H W

D H

W

DHW

DCW

DHW

RDHW

DHW

DHW

RDHW

RDHW

DHW

DHW

DHW

DCW

D H

W

D H

W D

C W

D H

W D

C W

DHWDHW

D H

W D

C W

DCW

DHW

D H

W

D C

W

DCW

D H

W

1 1 2

CODED NOTES

1. EXISTING LAVATORY / SINK TO BE REMOVED. DISCONNECT AND REMOVE ASSOCIATED DCW

AND DHW PIPING AS SHOWN.

2. REMOVED EXISTING DCW AND DHW PIPING BACK TO POINTS INDICATED FOR RECONNECTION

UNDER NEW WORK.

PLAN NOTES

A. SEE SHEET PJ-100 FOR GENERAL NOTES AND SYMBOL LEGEND.

B. EXISTING PIPING AND EQUIPMENT TO REMAIN SHOWN WITH LIGHT LINES.

C. EXISTING PIPING AND EQUIPMENT TO BE REMOVED SHOWN WITH DARK DASHED LINES.

D. NO WORK SHALL BE COMPLETED IF ALTERNATE 5 IS ACCEPTED.

E. REFER TO ARCHITECTURAL PLANS FOR PHASING AND SUB-PHASING AREAS OF WORK.

F. ACCESS TO ALL AREAS OUTSIDE OF PHASE AND SUB-PHASE CONSTRUCTION AREAS

INDICATED TO BE FULLY ACCESSIBLE TO STAFF AND PATIENTS THROUGH OUT NORMAL WORKING HOURS. ALL LIMITED SCOPE SUPPORTING ACTIVITIES TO BE COORDINATED WITH THE VA COR.

ALL WORK DEEMED DISRUPTIVE BY COR TO BE CONDUCTED OUTSIDE NORMAL WORKING HOURS

(7:30 AM TO 5:00 PM).

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

RE G IS T E RE

D

E-62197

0' 1'

2'

1/ 2"

' 0

0' 1'

3'

3/ 8"

' 0

0' 2'

4'

1/ 4"

' 0

0' 3'

6' 1'

3/

' 0

0' 4'

8' 2'1/

8"

' 0

0' 3'

3/

' 0

6' 0'

8'

4'1/

' 0

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

CONSTRUCTION - ISSUED FOR

BID

Project Number

Building Number

Drawing Number

340, 341

VA Building 340, 341 Project Title

Location

Issued Date Checked Drawn

Drawing Title Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

SCHEESER BUCKLEY MAYFIELD

1540 CORPORATE WOODS PARKWAY

UNIONTOWN, OHIO 44685

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

Approved:

PHILIP P. KIRK

CHIEF ENGINEER

2/

/2

1:

: 3

PM

C :\U se rs

\J Bi lin s k i\D oc um en ts \1

_M E

P_ C

EN

TR

A L

FI

LE

_j bi lin sk i@ sb m ce

.c om

.rv t

PD-105

552-20-104

CJS JMB

RENOVATE PRIMARY CARE FOR

PACT BLDG 340, BLDG 341

02/09/2021

4100 WEST THIRD STREET, DAYTON, OH 45428

DEMOLITION - FIRST FLOOR PLAN -

PLUMBING (WATER) PHASE 3

02/09/2021

N 1/8" = 1'-0"

DEMOLITION - FIRST FLOOR PLAN - PLUMBING (WATER) PHASE 3

P-418P-103

P-103

P-418

P-418 P-103

P-528

P-528

P-528

P-528

1/

2" V

E N

T 2"

FW/FCO

4" U

S

4" U

S

1/

2"

5 8

P-103 P-418

11 12

P-608

P-608

4" ODS

C.O.

C.O.

C.O.

4" O

D S

6" O

D S

US US

UST

US

UST

US

UST

US

US

U S

U S

U S

UST

U

ST

UST

U S

U S

US US US

U S

U S

U S

D S

U

ST

U

ST

C.O.

FW/FCO

FW/FCO

FW/FCO

4" US

121121A 120119

EX-185

EX-186

PAC121

C-1-11

192 193

C-1-12

EX-183a

EX-183 EX-122

EX-121 EX-120

EX-119

1 2

EX-138

EX-137

EX-136

EX-182

EX-181

EX-180

EX-179

EX-184 EX-123

EX-124

EX-125

EX-131

EX-130

EX-129

EX-132

EX-133

EX-134

EX-178

EX-177

EX-176

EX-175

EX-174

EX-173

EX-187 EX-126A EX-126

EX-188

EX-128 EX-127

EX-167a

EX-155 EX-154 EX-153

EX-189

EX-152

EX-190 EX-151

EX-191

EX-192 EX-193

EX-156

EX-157

EX-158

EX-161

EX-160

EX-159

EX-163

EX-164

EX-148 EX-147 EX-146 EX-145

EX-144 EX-143 EX-142

EX-101

EX-100

1 4 1 4 2 4

P-528 P-528 P-528 P-528 P-528P-528

P-528

P-528

CODED NOTES

1. 2" US PIPING, TIE INTO EXISTING US PIPING AT POINT INDICATED.

2. 4" US PIPING, TIE INTO EXISTING US PIPING AT POINT INDICATED.

3. 2" VENT PIPING. TIE INTO EXISTING VENT PIPING AT POINT INDICATED.

4. 1-1/2" VENT PIPING. TIE INTO EXISTING VENT PIPING AT POINT INDICATED.

5. 4" DS PIPING. TIE INTO EXISTING 4" DS PIPING AT POINT INDICATED.

6. 6" DS PIPING. TIE INTO EXISTING 6" DS PIPING AT POINT INDICATED.

7. 6" DS PIPING DOWN TO BELOW GRADE, INSTALL CLEANOUT 12" A.F.F.

8. 6" UST PIPING. TIE INTO EXISTING DS PIPING AT POINT INDICATED.

9. RELOCATED SINK. REWORK/EXTEND EXISTING SANITARY AND VENT PIPING AS REQUIRED FOR

NEW LOCATION. PATCH FLOOR AS REQUIRED TO MATCH EXISTING CONDITIONS.

10. 2-1/2" VENT PIPING. TIE INTO EXISTING VENT PIPING AT POINT INDICATED.

11. NEW WATER CLOSET, CONNECT TO EXISTING SANITARY AND VENT PIPING AS REQUIRED.

12. NEW LAV/SINK, CONNECT TO EXISTING SANITARY AND VENT PIPING AS REQUIRED.

13. 4" ODS PIPING UP TO RD-1.

14. 4" ODS PIPING TO PENETRATE BUILDING LOW ON WALL, SEE "DOWNSPOUNT NOZZLE DETAIL".

15. 6" ODS PIPING UP TO RD-1.

16. 6" ODS PIPING TO PENETRATE BUILDING LOW ON WALL, SEE "DOWNSPOUNT NOZZLE DETAIL".

17. EXTEND 1-1/2" SAN AND 1-1/2" VENT PIPING FROM NEW SINK AND TIE INTO EXISTING SAN AND

VENT PIPING IN WALL SERVING SINK THAT WAS REMOVED.

PLAN NOTES

A. SEE SHEET PJ-100 FOR GENERAL NOTES, SYMBOL LEGEND AND SCHEDULES.

B. SEE SHEET PJ-101 FOR DETAILS.

C. EXISTING PIPING AND EQUIPMENT TO REMAIN SHOWN WITH LIGHT LINES.

D. EXISTING PIPING AND EQUIPMENT TO BE REMOVED SHOWN WITH DARK DASHED LINES.

E. CONTRACTOR SHALL BE RESPONSIBLE FOR CUTTING AND PATCHING OF FLOOR TO MATCH

EXISTING CONDITIONS AS REQUIRED FOR INSTALLATION OF NEW SANITARY PIPING.

F. REFER TO ARCHITECTURAL PLANS FOR PHASING AND SUB-PHASING AREAS OF WORK.

G. ACCESS TO ALL AREAS OUTSIDE OF PHASE AND SUB-PHASE CONSTRUCTION AREAS

INDICATED TO BE FULLY ACCESSIBLE TO STAFF AND PATIENTS THROUGH OUT NORMAL WORKING HOURS. ALL LIMITED SCOPE SUPPORTING ACTIVITIES TO BE COORDINATED WITH THE VA COR.

ALL WORK DEEMED DISRUPTIVE BY COR TO BE CONDUCTED OUTSIDE NORMAL WORKING HOURS

(7:30 AM TO 5:00 PM).

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

RE G IS T E RE

D

E-62197

0' 1'

2'

1/ 2"

' 0

0' 1'

3'

3/ 8"

' 0

0' 2'

4'

1/ 4"

' 0

0' 3'

6' 1'

3/

' 0

0' 4'

8' 2'1/

8"

' 0

0' 3'

3/

' 0

6' 0'

8'

4'1/

' 0

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

CONSTRUCTION - ISSUED FOR

BID

Project Number

Building Number

Drawing Number

340, 341

VA Building 340, 341 Project Title

Location

Issued Date Checked Drawn

Drawing Title Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

SCHEESER BUCKLEY MAYFIELD

1540 CORPORATE WOODS PARKWAY

UNIONTOWN, OHIO 44685

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

Approved:

PHILIP P. KIRK

CHIEF ENGINEER

2/

/2

1:

: 4

PM

C :\U se rs

\J Bi lin s k i\D oc um en ts \1

_M E

P_ C

EN

TR

A L

FI

LE

_j bi lin sk i@ sb m ce

.c om

.rv t

PL-100

552-20-104

CJS JMB

RENOVATE PRIMARY CARE FOR

PACT BLDG 340, BLDG 341

02/09/2021

4100 WEST THIRD STREET, DAYTON, OH 45428

SANITARY - FIRST FLOOR PLAN - PLUMBING

PHASE 1

02/09/2021

N 1/8" = 1'-0"

SANITARY - FIRST FLOOR PLAN - PLUMBING PHASE 1

ROOM LEGEND

Number Name

1 TEMP. LOCKERS 1

2 TEMP. LOCKERS 2

070 T.R.

071 T.R.

072 VENDING

100 VESTIBULE

118 STAFF T.R.

119 HEALTH BEHAV. COORD.

120 DIETICIAN

121 TVC/FLOAT

121A STAFF T.R.

133 MSA SUPERVISOR

134 WAITING

135 EXISTING WAITING AREA

136 KIOSK

137 EX. VESTIBULE

140 SCALES

141 EXAM

171 EXAM

172 EXAM

173 EXAM

174 T.R.

175 SUPPLY

188 MSA

189 PACT

190 STAFF T.R.

191 SOIL

192 CLEAN

193 MED

C-1-4 CORRIDOR

C-1-11 CORRIDOR

C-1-12 CORRIDOR

EX-100 MECH

EX-101 OFFICE

EX-119 OFFICE

EX-120 STORE

EX-121 PSYCH

EX-122 PSYCH

EX-123 EXAM 17

EX-124 EXAM 18

EX-125 EXAM 19

EX-126 CLOSET

EX-126A CLOSET

EX-127 STORAGE

EX-128 SOILED LINEN/UTIL.

EX-129 EXAM 14

EX-130 EXAM 15

EX-131 EXAM 16

EX-132 EXAM 11

EX-133 EXAM 12

EX-134 EXAM 13

EX-136 EXAM 1

EX-137 EXAM 2

EX-138 EXAM 3

EX-142 EXAM

EX-143 EXAM

EX-144 EXAM

EX-145 EXAM

EX-146 EXAM

EX-147 EXAM

EX-148 EXAM

EX-151 TLT.

EX-152 EXAM

EX-153 CLEAN LINEN

EX-154 PT

EX-155 TELE. TRIAGE

EX-156 EXAM

EX-157 EXAM

EX-158 EXAM

EX-159 EXAM

EX-160 EXAM

EX-161 EXAM

EX-163 EXAM

EX-164 EXAM

EX-167a NURSE STATION

EX-173 M.D. OFFICE

EX-174 M.D. OFFICE

EX-175 M.D. OFFICE

EX-176 M.D. OFFICE

EX-177 OFFICE

EX-178 CLOSET

EX-179 MD OFFICE

EX-180 MD OFFICE

EX-181 MD OFFICE

EX-182 OFFICE

EX-183 SEC.

EX-183a CHIEF'S OFFICE

EX-184 PROGRAM SUPPORT

EX-185 OFFICE

EX-186 MD OFFICE

EX-187 CLOSET

EX-188 STORAGE

EX-189 N.P. OFFICE

EX-190 M.D. OFFICE

EX-191 NURSE MANAGER

EX-192 STAFF

EX-193 STAFF

PAC121 RECEPTION

4 5

DHW

DCW

DCW

DHW

D C

W D

H W

D C

W D

H W

DCW

DHW

DCW

DHW

DHW

D H

W

DCW

DHW

D H

W

1A

EX-185

EX-186

PAC121

C-1-11

190 191 192 193

C-1-12

EX-183a

EX-183 EX-122

EX-121 EX-120

EX-119 1

EX-138

EX-137

EX-136

EX-182

EX-181

EX-180

EX-179

EX-184

EX-123

EX-124

EX-125

EX-131

EX-130

EX-129

EX-132

EX-133

EX-134

EX-178

EX-177

EX-176

EX-175

EX-174

EX-173

EX-187 EX-126A EX-126

EX-188 EX-128

EX-127

EX-167a

EX-155 EX-154 EX-153

EX-189

EX-152

EX-190

EX-151

EX-191

EX-192 EX-193

EX-156

EX-157

EX-158

EX-161

EX-160

EX-159

EX-163

EX-164

EX-148 EX-147 EX-146 EX-145 EX-144 EX-143 EX-142 EX-101

EX-100

2"

6 6

CODED NOTES

1. RELOCATED LAV. REWORK/EXTEND EXISTING DCW AND DHW PIPING AS REQUIRED FOR NEW

LCOATION. PATCH WALL AS REQUIRED TO MATCH EXISTING CONDITIONS.

2. 1/2" DCW AND 1/2" DHW PIPING. TIE INTO EXISTING DCW AND DHW PIPING AT POINTS

INDICATED.

3. 1-1/4" DCW AND 1/2" DHW PIPING. TIE INTO EXISTING DCW AND DHW PIPING AT POINTS

INDICATED.

4. 1-1/4" DCW PIPING DOWN IN WALL TO WATER CLOSET (TYP.).

5. 1/2" DCW AND 1/2" DHW PIPING DOWN IN WALL TO LAV/SINK (TYP.).

6. 1/2" DCW AND 1/2" DHW PIPING DOWN IN WALL. EXTEND 1/2" DCW AND 1/2" DHW PIPING TO

EACH SINK.

7. 1/2" DCW PIPING. TIE INTO EXISTING DCW PIPING AT POINT INDICATED.

8. 1/2" DCW PIPING DOWN IN WALL TO WATER COOLER.

9. SHOCK ABSORBER, SEE SCHEDULE (TYP.).

10. NEW WATER CLOSET, CONNECT TO EXISTING DCW PIPING AS REQUIRED.

11. NEW LAV/SINK, CONNECT TO EXISTING DCW AND DHW PIPING AS REQUIRED.

12. 1" DCW PIPING. TIE INTO EXISTING DCW PIPING AT POINT INDICATED.

13. 1" DCW PIPING UP P-800, TO SEE "FREEZE-PROOF PEDESTAL HYDRANT DETAIL".

14. 2" DCW PIPING. TIE INTO EXISTING DCW PIPING AT POINT INDICATED.

15. VALVE AND CAP 2" DCW PIPING FOR EXTENSION UNDER PHASE 2.

PLAN NOTES

A. SEE SHEET PJ-100 FOR GENERAL NOTES, SYMBOL LEGEND AND SCHEDULES.

B. SEE SHEET PJ-101 FOR DETAILS.

C. EXISTING PIPING AND EQUIPMENT TO REMAIN SHOWN WITH LIGHT LINES.

D. EXISTING PIPING AND EQUIPMENT TO BE REMOVED SHOWN WITH DARK DASHED LINES.

E. REFER TO ARCHITECTURAL PLANS FOR PHASING AND SUB-PHASING AREAS OF WORK.

F. ACCESS TO ALL AREAS OUTSIDE OF PHASE AND SUB-PHASE CONSTRUCTION AREAS

INDICATED TO BE FULLY ACCESSIBLE TO STAFF AND PATIENTS THROUGH OUT NORMAL WORKING HOURS. ALL LIMITED SCOPE SUPPORTING ACTIVITIES TO BE COORDINATED WITH THE VA COR.

ALL WORK DEEMED DISRUPTIVE BY COR TO BE CONDUCTED OUTSIDE NORMAL WORKING HOURS

(7:30 AM TO 5:00 PM).

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

RE G IS T E RE

D

E-62197

0' 1'

2'

1/ 2"

' 0

0' 1'

3'

3/ 8"

' 0

0' 2'

4'

1/ 4"

' 0

0' 3'

6' 1'

3/

' 0

0' 4'

8' 2'1/

8"

' 0

0' 3'

3/

' 0

6' 0'

8'

4'1/

' 0

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

CONSTRUCTION - ISSUED FOR

BID

Project Number

Building Number

Drawing Number

340, 341

VA Building 340, 341 Project Title

Location

Issued Date Checked Drawn

Drawing Title Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

SCHEESER BUCKLEY MAYFIELD

1540 CORPORATE WOODS PARKWAY

UNIONTOWN, OHIO 44685

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

Approved:

PHILIP P. KIRK

CHIEF ENGINEER

2/

/2

1:

: 5

PM

C :\U se rs

\J Bi lin s k i\D oc um en ts \1

_M E

P_ C

EN

TR

A L

FI

LE

_j bi lin sk i@ sb m ce

.c om

.rv t

PL-101

552-20-104

CJS JMB

RENOVATE PRIMARY CARE FOR

PACT BLDG 340, BLDG 341

02/09/2021

4100 WEST THIRD STREET, DAYTON, OH 45428

WATER - FIRST FLOOR PLAN - PLUMBING

PHASE 1

02/09/2021

N 1/8" = 1'-0"

WATER - FIRST FLOOR PLAN - PLUMBING PHASE 1

ROOM LEGEND

Number Name

1 TEMP. LOCKERS 1

2 TEMP. LOCKERS 2

070 T.R.

071 T.R.

072 VENDING

100 VESTIBULE

118 STAFF T.R.

119 HEALTH BEHAV. COORD.

120 DIETICIAN

121 TVC/FLOAT

121A STAFF T.R.

133 MSA SUPERVISOR

134 WAITING

135 EXISTING WAITING AREA

136 KIOSK

137 EX. VESTIBULE

140 SCALES

141 EXAM

171 EXAM

172 EXAM

173 EXAM

174 T.R.

175 SUPPLY

188 MSA

189 PACT

190 STAFF T.R.

191 SOIL

192 CLEAN

193 MED

C-1-4 CORRIDOR

C-1-11 CORRIDOR

C-1-12 CORRIDOR

EX-100 MECH

EX-101 OFFICE

EX-119 OFFICE

EX-120 STORE

EX-121 PSYCH

EX-122 PSYCH

EX-123 EXAM 17

EX-124 EXAM 18

EX-125 EXAM 19

EX-126 CLOSET

EX-126A CLOSET

EX-127 STORAGE

EX-128 SOILED LINEN/UTIL.

EX-129 EXAM 14

EX-130 EXAM 15

EX-131 EXAM 16

EX-132 EXAM 11

EX-133 EXAM 12

EX-134 EXAM 13

EX-136 EXAM 1

EX-137 EXAM 2

EX-138 EXAM 3

EX-142 EXAM

EX-143 EXAM

EX-144 EXAM

EX-145 EXAM

EX-146 EXAM

EX-147 EXAM

EX-148 EXAM

EX-151 TLT.

EX-152 EXAM

EX-153 CLEAN LINEN

EX-154 PT

EX-155 TELE. TRIAGE

EX-156 EXAM

EX-157 EXAM

EX-158 EXAM

EX-159 EXAM

EX-160 EXAM

EX-161 EXAM

EX-163 EXAM

EX-164 EXAM

EX-167a NURSE STATION

EX-173 M.D. OFFICE

EX-174 M.D. OFFICE

EX-175 M.D. OFFICE

EX-176 M.D. OFFICE

EX-177 OFFICE

EX-178 CLOSET

EX-179 MD OFFICE

EX-180 MD OFFICE

EX-181 MD OFFICE

EX-182 OFFICE

EX-183 SEC.

EX-183a CHIEF'S OFFICE

EX-184 PROGRAM SUPPORT

EX-185 OFFICE

EX-186 MD OFFICE

EX-187 CLOSET

EX-188 STORAGE

EX-189 N.P. OFFICE

EX-190 M.D. OFFICE

EX-191 NURSE MANAGER

EX-192 STAFF

EX-193 STAFF

PAC121 RECEPTION

P-528

P-418 P-103

P-528

P-418

P-418

P-528 P-528

P-528

P-528

P-528P-528

P-528

P-418 P-103

4" U

S

1/

2" V

E N

T

2"2"

4" US

C.O.

FW/FCO

2"

1/

2" V

E N

T

1/

2"

1/ 2"

1/

2"

P-103 P-103

UST

US

U

ST

US

UST

US

USTUS

US US

U S

U S

U S

U

ST

UST UST UST

US

U S

US

U S U

S

US

U S

U S

U S

U S

P-608

117116115114113112111

C-1-6

C-1-8

164154

153 163

C-1-5

C-1-7

C-1-9

C-1-2

121A 121 EX-125

EX-100E

EX-104

EX-103

EX-138

EX-132

EX-133

EX-134

EX-137

EX-136 190

192 193

EX-163

EX-164

EX-157 EX-160

EX-158 EX-159 188

C-1-11

C-1-12

EX-148

X-147 EX-146 EX-145 EX-144 EX-143 EX-142

EX-101

EX-100

PAC121

CODED NOTES

1. 2-1/2" VENT PIPING. TIE INTO EXISTING VENT PIPING AT POINT INDICATED.

2. 4" US PIPING, TIE INTO EXISTING US PIPING AT POINT INDICATED.

3. 6" UST PIPING. TIE INTO EXISTING DS PIPING AT POINT INDICATED.

4. 6" DS PIPING DOWN TO BELOW GRADE, INSTALL CLEANOUT 12" A.F.F.

5. 4" DS PIPING. TIE INTO EXISTING 4" DS PIPING AT POINT INDICATED.

6. 4" US PIPING DOWN TO BELOW GRADE.

7. 2" US PIPING. TIE INTO EXISTING US PIPING AT POINT INDICATED.

PLAN NOTES

A. SEE SHEET PJ-100 FOR GENERAL NOTES, SYMBOL LEGEND AND SCHEDULES.

B. SEE SHEET PJ-101 FOR DETAILS.

C. EXISTING PIPING AND EQUIPMENT TO REMAIN SHOWN WITH LIGHT LINES.

D. EXISTING PIPING AND EQUIPMENT TO BE REMOVED SHOWN WITH DARK DASHED LINES.

E. CONTRACTOR SHALL BE RESPONSIBLE FOR CUTTING AND PATCHING OF FLOOR TO MATCH

EXISTING CONDITIONS AS REQUIRED FOR INSTALLATION OF NEW SANITARY PIPING.

E. REFER TO ARCHITECTURAL PLANS FOR PHASING AND SUB-PHASING AREAS OF WORK.

F. ACCESS TO ALL AREAS OUTSIDE OF PHASE AND SUB-PHASE CONSTRUCTION AREAS

INDICATED TO BE FULLY ACCESSIBLE TO STAFF AND PATIENTS THROUGH OUT NORMAL WORKING HOURS. ALL LIMITED SCOPE SUPPORTING ACTIVITIES TO BE COORDINATED WITH THE VA COR.

ALL WORK DEEMED DISRUPTIVE BY COR TO BE CONDUCTED OUTSIDE NORMAL WORKING HOURS

(7:30 AM TO 5:00 PM).

DATESIGNATURE

SCHOONOVER

C. J.

ST

AT

E OF O

H IO

P R O F E

SS IO N

AL EN

G

IN

E E R

RE G IS T E RE

D

E-62197

0' 1'

2'

1/ 2"

' 0

0' 1'

3'

3/ 8"

' 0

0' 2'

4'

1/ 4"

' 0

0' 3'

6' 1'

3/

' 0

0' 4'

8' 2'1/

8"

' 0

0' 3'

3/

' 0

6' 0'

8'

4'1/

' 0

VA FORM 08 - 6231

F

E

D

C

B

A

987654321 10

F

E

D

C

B

A

987654321 10

CONSTRUCTION - ISSUED FOR

BID

Project Number

Building Number

Drawing Number

340, 341

VA Building 340, 341 Project Title

Location

Issued Date Checked Drawn

Drawing Title Phase

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMPARCHITECT / ENGINEER OF RECORD

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

CONSULTANT

SCHEESER BUCKLEY MAYFIELD

1540 CORPORATE WOODS PARKWAY

UNIONTOWN, OHIO 44685

MECHANICAL ENGINEER

ELECTRICAL ENGINEER

Approved:

PHILIP P. KIRK

CHIEF ENGINEER

2/

/2

1:

: 5

PM

C :\U se rs

\J Bi lin s k i\D oc um en ts \1

_M E

P_ C

EN

TR

A L

FI

LE

_j bi lin sk i@ sb m ce

.c om

.rv t

PL-102

552-20-104

CJS JMB

RENOVATE PRIMARY CARE FOR

PACT BLDG 340, BLDG 341

02/09/2021

4100 WEST THIRD STREET, DAYTON, OH 45428

SANITARY - FIRST FLOOR PLAN - PLUMBING

PHASE 2

02/09/2021

N 1/8" = 1'-0"

SANITARY - FIRST FLOOR PLAN - PLUMBING PHASE 2

ROOM LEGEND

Number Name

139 NURSE MANAGER

C-1-10 CORRIDOR

070 T.R.

071 T.R.

072 VENDING

100 VESTIBULE

111 CHIEF

112 ASST. CHIEF

113 ADMIN. OFFICER

114 CHIEF NURSE

115 DIABETES ED

116 NURSE PRACT./ DIABET.

117 NURSE PRACT./ DIABET.

118 STAFF T.R.

119 HEALTH BEHAV. COORD.

120 DIETICIAN

121 TVC/FLOAT

121A STAFF T.R.

122 HAC

123 ELECT.

124 DATA

126 CONFERENCE/BREAK

127 LOCKERS

128 STAFF T.R.

129 KITCHEN

130 PRIMARY CARE CALL CENTER

131 TELEPHONE NURSE TRIAGE

132 MSA SUPERVISOR

133 MSA SUPERVISOR

134 WAITING

135 EQUIP/SUPPLY STORAGE

135 EXISTING WAITING AREA

136 ADMIN OPEN

137 NURSE MANAGER

138 NURSE MANAGER

139 NURSE MANAGER

140 SCALES

1…