233400.pdf
PDF 48 KB Posted
- Attached to
- Y1LZ--693-222 | Parking Structure Solicitation Amendment 2 Federal contract opportunity
- Solicitation number
- 36C24420R0075
About this file
This document includes a solicitation for a construction project and specifications for HVAC fans. The solicitation is for Project 693-222 to construct a new parking garage at the Wilkes-Barre VA Medical Center with a magnitude between $10 million and $20 million. It is set aside for verified service-disabled veteran-owned small businesses and will use a tiered evaluation process including large businesses. Offerors shall provide all labor, materials, equipment, permits, testing and reports to complete the project according to the drawings, specifications, and federal, state and local requirements. The specifications provide requirements for various HVAC fans to be used in the project, including centrifugal fans, power roof ventilators, and ceiling fans. Product standards, performance criteria, submittal requirements, quality assurance protocols, and installation instructions are delineated.
View the file
Other files for this federal contract opportunity
Show all 50
Y1LZ--693-222 | Parking Structure Solicitation Amendment 2 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Parking Garage Project Number 693-222 Department of Veterans Affairs Wilkes-Barre, Pennsylvania
233400 - 1
SECTION 23 34 00 - HVAC FANS
PART 1 - GENERAL
1.1 DESCRIPTION
A. Fans for heating, ventilating and air conditioning.
B. Product Definitions: AMCA Publication 99, Standard l-66.
1.2 RELATED WORK
A. Section 01 00 00, GENERAL REQUIREMENTS.
B. Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
C. Section 23 05 11, COMMON WORK RESULTS FOR HVAC AND STEAM
GENERATION.
D. Section 23 05 41, NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND
EQUIPMENT.
E. Section 23 05 93, TESTING, ADJUSTING, AND BALANCING FOR HVAC.
F. Section 23 09 23, DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC.
G. Section 23 82 16, AIR COILS.
1.3 QUALITY ASSURANCE
A. Refer to paragraph, QUALITY ASSURANCE, in Section 23 05 11, COMMON WORK
RESULTS FOR HVAC AND STEAM GENERATION.
B. Fans and power ventilators shall be listed in the current edition of AMCA 26l, and shall bear the AMCA performance seal.
C. Operating Limits for Centrifugal Fans: AMCA 99 (Class I, II, and III).
D. Fans and power ventilators shall comply with the following standards:
l. Testing and Rating: AMCA 2l0.
2. Sound Rating: AMCA 300.
E. Vibration Tolerance for Fans and Power Ventilators: Section 23 05 41, NOISE AND
VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT.
F. Performance Criteria:
Wilkes-Barre, Pennsylvania
233400 - 2
l. The fan schedule shall show the design air volume and static pressure. Select the fan motor HP by increasing the fan BHP by 10 percent to account for the drive losses and field conditions.
2. Select the fan operating point as follows:
a. Forward Curve and Axial Flow Fans: Right hand side of peak pressure point
b. Air Foil, Backward Inclined, or Tubular: At or near the peak static efficiency
G. Safety Criteria: Provide manufacturer's standard screen on fan inlet and discharge where exposed to operating and maintenance personnel.
1.4 SUBMITTALS
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, and SAMPLES.
B. Manufacturers Literature and Data:
l. Fan sections, motors and drives.
2. Centrifugal fans, motors, drives, accessories and coatings.
a. In-line centrifugal fans.
b. Up-blast kitchen hood exhaust fans.
3. Prefabricated roof curbs.
4. Power roof and wall ventilators.
5. Centrifugal ceiling fans.
6. Packaged hood make-up air units.
C. Certified Sound power levels for each fan.
D. Motor ratings types, electrical characteristics and accessories.
E. Roof curbs.
F. Belt guards.
G. Maintenance and Operating manuals in accordance with Section 01 00 00, GENERAL
REQUIREMENTS.
H. Certified fan performance curves for each fan showing cubic feet per minute (CFM) versus static pressure, efficiency, and horsepower for design point of operation.
1.5 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification to the extent referenced.
The publications are referenced in the text by the basic designation only.
B. Air Movement and Control Association International, Inc. (AMCA):
Wilkes-Barre, Pennsylvania
233400 - 3
99-86.....................................Standards Handbook
2l0-06....................................Laboratory Methods of Testing Fans for Aerodynamic
Performance Rating
26l-09....................................Directory of Products Licensed to bear the AMCA Certified
Ratings Seal - Published Annually
300-08...................................Reverberant Room Method for Sound Testing of Fans
C. American Society for Testing and Materials (ASTM):
B117-07a ..............................Standard Practice for Operating Salt Spray (Fog)
Apparatus
D1735-08 ..............................Standard Practice for Testing Water Resistance of
Coatings Using Water Fog Apparatus
D3359-08 ..............................Standard Test Methods for Measuring Adhesion by Tape
Test
G152-06................................Standard Practice for Operating Open Flame Carbon Arc
Light Apparatus for Exposure of Non-Metallic Materials
G153-04................................Standard Practice for Operating Enclosed Carbon Arc
Light Apparatus for Exposure of Non-Metallic Materials
D. National Fire Protection Association (NFPA):
NFPA 96-08 ..........................Standard for Ventilation Control and Fire Protection of
Commercial Cooking Operations
E. National Sanitation Foundation (NSF):
37-07.....................................Air Curtains for Entrance Ways in Food and Food Service
Establishments
F. Underwriters Laboratories, Inc. (UL):
181-2005...............................Factory Made Air Ducts and Air Connectors
1.6 EXTRA MATERIALS
A. Provide one additional set of belts for all belt-driven fans.
PART 2 - PRODUCTS
2.1 CENTRIFUGAL FANS
A. Standards and Performance Criteria: Refer to Paragraph, QUALITY ASSURANCE.
Record factory vibration test results on the fan or furnish to the Contractor.
Wilkes-Barre, Pennsylvania
233400 - 4
B. Construction: Wheel diameters and outlet areas shall be in accordance with AMCA standards.
l. Housing: Low carbon steel, arc welded throughout, braced and supported by structural channel or angle iron to prevent vibration or pulsation, flanged outlet, inlet fully streamlined. Provide lifting clips, and casing drain. Provide manufacturer's standard access door. Provide 12.5 mm (1/2 inches) wire mesh screens for fan inlets without duct connections.
2. Wheel: Steel plate with die formed blades welded or riveted in place, factory balanced statically and dynamically.
3. Shaft: Designed to operate at no more than 70 percent of the first critical speed at the top of the speed range of the fans class.
4. Bearings: Heavy duty ball or roller type sized to produce a Bl0 life of not less than
50,000 hours, and an average fatigue life of 200,000 hours. Extend filled lubrication tubes for interior bearings or ducted units to outside of housing.
5. Belts: Oil resistant, non-sparking and non-static.
6. Belt Drives: Factory installed with final alignment belt adjustment made after installation.
7. Motors and Fan Wheel Pulleys: Adjustable pitch for use with motors through 15HP, fixed pitch for use with motors larger than 15HP. Select pulleys so that pitch adjustment is at the middle of the adjustment range at fan design conditions.
8. Motor, adjustable motor base, drive and guard: Furnish from factory with fan. Refer to Section 23 05 11, COMMON WORK RESULTS FOR HVAC AND STEAM
GENERATION for specifications. Provide protective sheet metal enclosure for fans located outdoors.
9. Furnish variable speed fan motor controllers where shown on the drawings. Refer to
Section, MOTOR STARTERS. Refer to Section 23 05 11, COMMON WORK
RESULTS FOR HVAC AND STEAM GENERATION for controller/motor combination requirements.
2.2 POWER ROOF VENTILATOR
A. Standards and Performance Criteria: Refer to Paragraph, QUALITY ASSURANCE.
Wilkes-Barre, Pennsylvania
233400 - 5
B. Type: Centrifugal fan, backward inclined blades. Provide down-blast or up-blast type as indicated.
C. Construction: Steel or aluminum, completely weatherproof, for curb mounting, exhaust cowl or entire drive assembly readily removable for servicing, aluminum bird screen on discharge, UL approved safety disconnect switch, conduit for wiring, vibration isolators for wheel, motor and drive assembly. Provide self acting back draft damper. //Provide electric motor operated damper where indicated.//
D. Motor and Drive: Refer to Section 23 05 11, COMMON WORK RESULTS FOR HVAC
AND STEAM GENERATION. Bearings shall be pillow block ball type with a minimum L-
50 life of 200,000 hours. Motor shall be located out of air stream.
E. Prefabricated Roof Curb: As specified in paragraph 2.3 of this section.
F. Up-blast Type: Top discharge exhauster, motor out of air stream. For kitchen hood exhaust applications, provide grease trough on base and threaded drain. The mounting height of the kitchen up-blast exhaust fan shall be in compliance with NFPA 96.
(Provide vented curb extension if required to maintain required clearances.)
2.5 CENTRIFUGAL CEILING FANS (SMALL CABINET FAN)
A. Standards and Performance Criteria: Refer to Paragraph, QUALITY ASSURANCE.
B. Steel housing, baked enamel finish, direct connected fan assembly, attached grille.
Provide gravity back draft assembly, aluminum wall cap and bird or insect screen.
C. Acoustical Lining: 12.5 mm (1/2 inch) thick mineral fiber, dark finish. Comply with UL
181 for erosion.
D. Motor: Shaded pole or permanent split capacitor, sleeve bearings, supported by steel brackets in combination with rubber isolators.
E. Ceiling Grille, (Where indicated): White plastic egg crate design, 80 percent free area.
F. Control: Provide solid state speed control (located at unit) for final air balancing.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Install fan, motor and drive in accordance with manufacturer's instructions.
B. Align fan and motor sheaves to allow belts to run true and straight.
C. Bolt equipment to curbs with galvanized lag bolts.
D. Install vibration control devices as shown on drawings and specified in Section 23 05 41, NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT.
Wilkes-Barre, Pennsylvania
233400 - 6
3.2 PRE-OPERATION MAINTENANCE
A. Lubricate bearings, pulleys, belts and other moving parts with manufacturer recommended lubricants.
B. Rotate impeller by hand and check for shifting during shipment and check all bolts, collars, and other parts for tightness.
C. Clean fan interiors to remove foreign material and construction dirt and dust.
3.3 START-UP AND INSTRUCTIONS
A. Verify operation of motor, drive system and fan wheel according to the drawings and specifications.
B. Check vibration and correct as necessary for air balance work.
C. After air balancing is complete and permanent sheaves are in place perform necessary field mechanical balancing to meet vibration tolerance in Section 23 05 41, NOISE AND
VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT.
- - - E N D - - -
File details come from the government source that posted it. Updated .