1737010dwg8of8VOL4.pdf
PDF 7 MB Posted
- Solicitation number
- N4008526R0020
About this file
Document Summary
This is a comprehensive set of construction drawings and specifications for a Forklift Charging Station at Naval Weapons Station Yorktown, Virginia (Project P171-1737010). The facility is a single-story, Type IIB noncombustible building measuring approximately 42 feet by 24 feet with a building height of 15 feet and roof height of 15 feet 4 inches. The project includes structural, architectural, mechanical, and electrical design documents prepared by NAVFAC Mid-Atlantic.
The facility is designed to support battery charging operations for forklifts using three charging stations, with provisions for hydrogen gas detection and exhaust systems. Key structural elements include a reinforced concrete slab-on-grade floor with 3/16-inch per 12-inch slope for drainage, reinforced concrete masonry unit (CMU) bearing walls (8-inch and 12-inch), continuous concrete footings, and a reinforced concrete roof slab with cantilevered overhang. The building features three overhead coiling doors (10 feet by 10 feet each) for equipment access, with metal panel exterior walls, standing seam metal roofing, and architectural precast concrete water table and band elements. Mechanical systems include two exhaust fans (one for hydrogen exhaust, one for general exhaust), an electric unit heater, gravity ventilator, and hydrogen gas detection control panel with interlock operation. Electrical infrastructure consists of a 250-amp, 208Y/120V panelboard with circuits for three battery chargers, overhead door motors, unit heater, exhaust fans, lighting, and emergency systems. The design complies with UFC 1-200-01, IBC 2018, NFPA 101 Life Safety Code, and includes lightning protection with air terminals, down conductors, and grounding systems per NFPA 780.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ROOM / ZONE AREA
OCCUPANCY,
ALLOWABLE AREA PER
OCCUPANT
OCCUPANCY LOAD (PEOPLE)
OCCUPANCY, TYPE
S - STORAGE
1500 SF
S 500
# : EXIT NUMBER
W: NET EXIT WIDTH (INCHES)
C: CAPACITY (PEOPLE)
P: EXIT WIDTH PER PERSON
A: ACTUAL EGRESS (PEOPLE)
SYMBOL DESCRIPTION
COMMON PATH OF TRAVEL
MAXIMUM TRAVEL DISTANCE
MTD = X'-XX"
DEAD -END CORRIDOR
DE = X'-XX"
FIRE EXTINGUISHER - ABC TYPE
EXIT LABEL#
W
C
P
A
CPT = X'-XX"
ABC
MTD1
32' - 6"
32 0.2
32 0.2
820 SF
S 500
MTD2
34' - 0"
ABCABC
APPLICABLE CODES, STANDARD, AND DESIGN CRITERIA
STANDARD TITLE REVISION DATE NOTES
UFC 1-200-01 GENERAL BUILDING REQUIREMENTS 01 OCTOBER 2020 --
UFC 3-600-01* FIRE PROTECTION ENGINEERING FOR FACILITIES --
IBC INTERNATIONAL BUILDING CODE 2018 APPLICABLE CHAPTERS PER UFC
1-200-01; MEANS OF EGRESS
SHALL BE BASED UPON THE LIFE
SAFETY CODE
NFPA 101 LIFE SAFETY CODE (LSC) 2018
* UFC 3-600-01 GENERALLY REQUIRES CONSTRUCTION ISSUES TO COMPLY WITH IBC CRITERIA AND LIFE SAFETY/EGRESS ISSUES TO MEET THE REQUIREMENTS OF LSC. CONFLICTS BETWEEN THE IBC AND LSC RELATED TO FIRE RESISTANCE ARE REQUIRED TO COMPLY WITH LSC
CRITERIA AND APPLICABLE PROVISIONS OF THE UFC CODE (UFC 3-600-01 § 2-1.1).
BUILDING DESCRIPTION
TYPE OF CONSTRUCTION IIB - NONCOMBUSTIBLE UNPROTECTED
NUMBER OF STORIES 1
BUILDING HEIGHT 15'-0"
NUMBER OF
STORIES
OCCUPANCY
AND USE
(A)
BLDG AREA PER
STORY (ACTUAL)
1 U
(B)
TABLE 506.2 AREA
(PER STORY)
(C)
AREA FOR FRONTAGE
INCREASE (100% OPEN)
(E)
ALLOWABLE AREA
825 8,500 6375 14,875 (PER STORY)
TOTAL -- 825 -- -- 14,875
ALLOWABLE AREA FOR NEW CONSTRUCTION (TYPE IIB)
ALLOWABLE HEIGHT (TYPE VB)
ALLOWABLE
(TABLE 504.3)
BUILDING HEIGHT 55'-0"
ACTUAL
15'-0"
NUMBER OF STORIES 2 1
FIRE RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS OF TYPE IIB
BUILDING BASED ON FIRE SEPARTION DISTANCE (IBC TABLE 602)
FIRE SEPARATION DISTANCE TO LOT LINE USE GROUP U
FSD < 5 FT
5FT ≥ FSD < 10FT
FSD ≥ 10FT
1 HR
1 HR
0 HR
NOTES
STRUCTURAL FRAME, INCLUDING COLUMNS,
GIRDERS, TRUSSES
BUILDING ELEMENT HOURLY RATING
REQ'D TYPE
VB
PROVIDED
BEARING WALLS
EXTERIOR
INTERIOR
NONBEARING WALLS AND PARTITIONS
EXTERIOR WALLS
*NOT LESS THAN THE FIRE RESISTANCE RATING BASED ON
THE FIRE SEPARATION DISTANCE FROM BUILDING 235
(SEE IBC TABLE 602)
*NOT LESS THAN THE FIRE RESISTANCE RATING BASED ON
THE FIRE SEPARATION DISTANCE FROM BUILDING 235
(SEE IBC TABLE 602)
FLOOR CONST. INCLUDING SUPPORTING
BEAMS AND JOISTS
ROOF CONSTRUCTION INCLUDING
SUPPORTING BEAMS AND JOISTS
EXIT ENCLOSURES
TYPE VB FIRE RESISTANCE RATINGS (IN HOURS) OF STRUCTURAL ELEMENTS
0 0
0 0
0 NA
0 0
0 0
0 0
1 NA
SHAFT ENCLOSURES 1 NA
OCCUPANCY CLASSIFICATIONS
FORK LIFT CHARGING
LSC
UTILITY
USE GROUP U
DESCRIPTION OF USE
IBC
LOW HAZARD STORAGE
(CHAPTER 42)
USE AND OCCUPANCY CLASSIFICATIONS
OCCUPANT LOAD FACTOR
(FT2/PER PERSON)
USE
STORAGE USE (IN OTHER OCCUPANCY) 500
APPLICABLE OCCUPANT LOAD FACTORS
NUMBER OF EXITS AND CAPACITY
FLOOR LEVEL
FIRST FLOOR
REQUIRED
EXIT CAPACITY
AVAILABLE
EXIT CAPACITY
NUMBER OF
EXITS REQUIRED
NUMBER OF
EXITS PROVIDED
2 2 - 36" WIDE DOORS
32" NET AVAIL EACH
1 2
COMMON PATH OF TRAVEL
• NONSPRINKLERED STORAGE OCCUPANCIES (LSC TABLE 42.2.5)
NOT LIMITED NONE
DEAD END PATH OF TRAVEL
• NONSPRINKLERED STORAGE OCCUPANCIES (LSC TABLE 42.2.5)
NOT LIMITED NONE
TOTAL TRAVEL DISTANCE
• NONSPRINKLERED STORAGE OCCUPANCIES (LSC TABLE 42.2.6)
NOT LIMITED 34'
BUILDING CODE AND LIFE SAFETY ANALYSIS
COMMON PATH, DEAD END, & TOTAL TRAVEL DISTANCE FOR STORAGE USE
REQUIRED ACTUALTRAVEL DISTANCE REQUIREMENT
05 JUNE 2021
AREA OF WORK
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/3
/2
:1
:2
A
M
C
U s e rs \d a v id
.h a d d o c k \D o c u m e n ts \P
-1
-F -R d a v id
.h a d d o c k .r v t
GI101B
F O
R K
L
IF
T C
H A
R G
IN
G
L
IF
E S
A F
E T
Y -C
O D
E -S
IT
E
P L A
N
SSR
12942149
KEK DMH
F O
R K
L
IF
T C
H A
R G
IN
G
S T
A T
IO
N
MMP/SLC
1737010
Y O
R K
T O
W N
V
IR
G
IN
IA
N A
V A
L W
E A
P O
N S
S T
A T
IO
N
JWJ
CGM
HPN
M
ID
L A
N T
D C
C O
R E
G I1
B
P W
E A
P O
N M
A G
A Z
IN
E
S
GENERAL NOTES
LIFE SAFETY LEGEND
GRAPHIC SCALE(S)
1/8" = 1' - 0" 0 5' 10' 15' 30'
TRAVEL DISTANCE SUMMARY
ID ACTUAL MAXIMUM
MTD1 32' - 6" NA
MTD2 34' - 0" NA
EXIT CAPACITY SCHEDULE#
EXIT
NUMBER
NET CLEAR
EXIT WIDTH
(INCHES)
EXIT WIDTH PER
PERSON (EGRESS
FACTOR)
EXIT
CAPACITY
(PEOPLE)
ACTUAL
PERSONS
USING EXIT
1 32 0.2 160 1
2 32 0.2 160 1
TOTAL 320 2
OCCUPANCY TABLE SUMMARY
USE
OCCUPIED
AREA
OCCUPANT LOAD
FACTOR (SF PER
OCCUPANT)
OCCUPANT
LOAD
1/8" = 1'-0" B3
LIFE SAFETY FLOOR PLAN - FORKLIFT CHARGING
S 820 500 2
SITE PLAN NOTES:
1. PER UFC 3-600-01 4-33.2.3 SPRINKLER AND
HYDRANT PROTECTION ARE NOT REQUIRED
FOR MUNITIONS STORAGE AREAS.
2. FORK LIFT STORAGE BLDG HAS BEEN
PROVIDED WITH MANUAL EXTINGUISHERS
AT EACH EXIT DOORWAY.
3. FORKLIFT CHARGING STATION IS MINIMUM
50 FT DIRECT LINE OF SIGHT FROM CLOSEST
MUNITION STORAGE AREA.
PLAN
NORTH
PLAN
NORTH
A. REFER TO DISCIPLINE SHEETS FOR EQUIPMENT LOCATIONS
AND CONSTRUCTION DETAILS.
1" = 80'-0" A3
CODE COMPLIANCE PLAN - FORKLIFT CHARGING
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
A N
E W
D R
A W
IN
G
A
D D
C H
A R
G
IN
G S
T A
/2 /2
D W
N
ACTIVITY
Approved by LCDR VINCE DEL
GRECO, ROICC with PWD YORKTOWN, via Email, -X"
X
TOP OF SLAB ELEVATION
FROM REFERENCE
ELEVATION 0'-0"
WALL GRID MARK
NEW WORK KEY NOTE
X = N FOR FOUNDATION NOTE
X = R FOR ROOF FRAMING NOTE
Y = NOTE NUMBER
XY
SLAB STEP / CHANGE
IN ELEVATION
STEPPED FOOTINGWF-X WALL FOOTING MARK
WX WALL MARK
CONCRETE MASONRY
UNIT WALL
CAST-IN-PLACE
CONCRETE
SLAB-ON-GRADE
DOWELED JOINT
TOF TOP OF FOOTING
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/3
/2
:0
:2
P
M
C U s e rs \m ig u e l.
w a lk e r\
D o c u m e n ts \P
-1
-S -R
-F O
R K
L
IF
T m ig u e l.
w a lk e r.
rv t
S-001B
S T
R U
C T
U R
A L N
O T
E S
A N
D L
E G
E N
D
CWJ
12942152
DOB MTW
03/26/2026
F O
R K
L
IF
T C
H A
R G
IN
G
S T
A T
IO
N
MMP/SLC
1737010
Y O
R K
T O
W N
V
IR
G
IN
IA
N A
V A
L W
E A
P O
N S
S T
A T
IO
N
JWJ
NEK
HPN
M
ID
L A
N T
D C
C O
R E
S -0
B
P W
E A
P O
N M
A G
A Z
IN
E
S
Approved by LCDR VINCE DEL GRECO, ROICC with PWD
YORKTOWN, via Email.
GENERAL NOTES
LEGEND
2. THIS PROJECT IS SUBJECT TO IBC 2021 SPECIAL INSPECTION REQUIREMENTS
AS MODIFIED BY UFC 3-301-01. THE STATEMENT AND SCHEDULE OF SPECIAL
INSPECTIONS, INCLUDED WITH THE PROJECT SPECIFICATIONS, DEFINE THE
SCOPE OF SPECIAL INSPECTIONS.
3. THIS PROJECT IS NOT SUBJECT TO IBC 2021 STRUCTURAL OBSERVATION
REQUIREMENTS.
4. THE STRUCTURES ASSOCIATED WITH THIS PROJECT DO NOT MEET THE
OCCUPANCY LEVELS OF INHABITED BUILDINGS. THEREFORE, THE STRUCTURES
ARE EXEMPT FROM UFC 4-010-01 ANTITERRORISM PROVISIONS.
5. COORDINATE STRUCTURAL WORK WITH WORK SHOWN ON OTHER DRAWINGS.
6. CONTRACT DOCUMENTS REPRESENT THE FINISHED STRUCTURE. PROVIDE
MEANS AND METHODS OF CONSTRUCTION INCLUDING, BUT NOT LIMITED TO,
SHORING AND TEMPORARY BRACING TO MAINTAIN THE STRUCTURE IN A SAFE
AND STABLE CONDITION AT ALL TIMES. THE CONTRACTOR IS SOLELY
RESPONSIBLE TO DETERMINE ERECTION PROCEDURES AND SEQUENCE OF
CONSTRUCTION. UNDERTAKE NECESSARY MEASURES TO ENSURE SAFETY OF
PERSONS AND STRUCTURES AT THE SITE AND ADJACENT TO THE SITE. VISITS
TO THE SITE BY THE CONTRACTING OFFICER OR CONTRACTING OFFICER'S
REPRESENTATIVE DO NOT RELIEVE THE CONTRACTOR OF SUCH
RESPONSIBILITY.
7. IF CERTAIN FEATURES ARE NOT FULLY SHOWN OR CALLED FOR ON THE
CONTRACT DRAWINGS OR SPECIFICATIONS, THEIR CONSTRUCTION MUST BE
OF THE SAME CHARACTER AS FOR SIMILAR CONDITIONS THAT ARE SHOWN OR
CALLED FOR SUBJECT TO THE APPROVAL OF THE CONTRACTING OFFICER.
WHERE SECTIONS VARY, PROVIDE FOR SMOOTH TRANSITIONS BETWEEN THEM,
UNLESS NOTED OTHERWISE.
8. REPORT DIMENSIONAL DISCREPANCIES BETWEEN DRAWINGS TO THE
CONTRACTING OFFICER PRIOR TO BEGINNING WORK IN AFFECTED AREAS.
9. CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES AND
SUPERVISION OF THE WORK ARE THE SOLE RESPONSIBILITY OF THE
CONTRACTOR.
10. DETAILS TITLED OR NOTED AS TYPICAL OR STANDARD APPLY NOT ONLY
WHERE SPECIFICALLY INDICATED OR REFERENCED BUT ALSO IN OTHER CASES
WHERE THE NATURE OF THE CONSTRUCTION REQUIRES THEIR USE.
DETERMINE APPLICABILITY OF TYPICAL AND STANDARD DETAILS FROM
DESCRIPTIVE TITLES OR FROM THE SIMILARITY OF A CONSTRUCTION
CONDITION WITH ANOTHER CONDITION WHERE THE DETAIL IS SPECIFICALLY
INDICATED OR REFERENCED.
1. MASONRY DESIGN FOR STRENGTH CONFORMS TO THE STRENGTH DESIGN
METHODOLOGY.
2. USE MASONRY ASSEMBLIES WITH THE FOLLOWING PROPERTIES:
A. UNITS: ASTM C90, MINIMUM NET AREA COMPRESSIVE STRENGTH = 1900
PSI
B. MINIMUM DESIGN MASONRY ASSEMBLAGE STRENGTH, f'm = 1900 PSI
C. WEIGHT CLASSIFICATION: NORMAL WEIGHT
D. MORTAR: ASTM C270, TYPE M OR S
3. AGGREGATE FOR MORTAR: ASTM C144. AGGREGATE FAILING TO COMPLY
WITH THE ASTM C144 GRADATION REQUIREMENTS MAY BE USED PROVIDED
THE MORTAR CAN BE PREPARED TO COMPLY WITH THE ASTM C270 PROPERTY
SPECIFICATION REQUIREMENTS FOR LABORATORY PREPARED MORTAR.
4. REINFORCING STEEL:
A. BARS: ASTM A615 GRADE 60. SHOP FABRICATE BENT BARS AND BARS
WITH HOOKS.
B. MINIMUM CLEAR DISTANCE TO ANY FACE OF MASONRY UNIT OR FORMED
SURFACE: 1/2"
C. LAP CONTINUOUS HORIZONTAL AND VERTICAL REINFORCING 60 BAR
DIAMETERS.
D. PROVIDE REINFORCING STEEL DOWELS WITH STANDARD 90 DEGREE
HOOKS OF THE SAME SIZE AND SPACING AS VERTICAL REINFORCING
FROM THE SUPPORTING STRUCTURE.
E. USE STANDARD LADDER TYPE HORIZONTAL JOINT REINFORCING AT
EVERY OTHER COURSE (16 INCHES ON CENTER MAXIMUM SPACING).
BEGIN AT TOP OF FIRST BLOCK COURSE. IN ADDITION, PROVIDE
HORIZONTAL JOINT REINFORCING IN TWO JOINTS IMMEDIATELY ABOVE
AND BELOW OPENINGS. EXTEND JOINT REINFORCING 2 FEET MINIMUM
BEYOND THE OPENING JAMB ON EACH SIDE OF THE OPENING.
5. GROUT:
A. PROPERTIES: COARSE GROUT PER ASTM C476, MINIMUM COMPRESSIVE
STRENGTH = 2000 PSI, SLUMP = 8" TO 11"
B. FULLY GROUT CELLS BELOW GRADE, CELLS THAT CONTAIN REINFORCING
STEEL AND CELLS THAT CONTAIN PLATES, BOLTS OR OTHER EMBEDDED
ITEMS.
C. PROVIDE MASONRY UNITS WITH MINIMUM SPACE IN CELLS TO RECEIVE
GROUT OF 3"x 3" AND ALIGN THESE CELLS TO PROVIDE UNOBSTRUCTED
OPENINGS.
DESIGN LOADS & CRITERIA
1. RISK CATEGORY: II PER UFC 3-301-01 TABLE 2-2.
2. LIVE LOADS PER UFC 3-301-01 TABLE G-1
3. GROUND FLOOR SLAB:
A. GARAGE STORAGE UNIFORM LOAD: 100 PSF
B. UNLOADED FORKLIFT WHEEL LOAD (BASED ON DREXEL MODEL SL120
SWINGMAST): 16,710 POUNDS (1/2 AXLE LOAD)
4. ROOFS: 20 PSF UNIFORM LOAD
5. UNIFORM AND CONCENTRATED LIVE LOADS HAVE NOT BEEN APPLIED
CONCURRENTLY. WHERE BOTH UNIFORM AND CONCENTRATED LOADS ARE
INDICATED, THE SUPPORTING STRUCTURE HAS BEEN DESIGNED FOR THE LOAD
THAT PRODUCES THE GREATER LOAD EFFECTS.
6. ROOF SNOW LOAD DATA
A. GROUND SNOW LOAD: Pg = 15 PSF B. FLAT-ROOF SNOW LOAD: Pf = 12 PSF C. SNOW EXPOSURE FACTOR: Ce = 1.0 FOR PARTIALLY EXPOSED AT TERRAIN
CATEGORY B
D. SNOW LOAD IMPORTANCE FACTOR: IS = 1.00
E. THERMAL FACTOR: Ct = 1.0
7. WIND DESIGN DATA
A. BASIC DESIGN WIND SPEED: 115 MPH
B. ALLOWABLE STRESS DESIGN WIND SPEED: 89 MPH
C. WIND EXPOSURE CATEGORY: C
D. INTERNAL PRESSURE COEFFICIENT: +/- 0.55
E. ENCLOSURE CLASSIFICATION: PARTIALLY ENCLOSED
F. TOPOGRAPHIC FACTOR: 1.0
G. REFER TO COMPONENTS AND CLADDING PRESSURE NOTES ON S-002B FOR
BASIC DESIGN WIND PRESSURES APPLIED TO EXTERIOR COMPONENT AND
CLADDING MATERIALS NOT SPECIFICALLY DESIGNED BY THE REGISTERED
DESIGN PROFESSIONAL RESPONSIBLE FOR THE DESIGN OF THE
STRUCTURE.
8. EARTHQUAKE DESIGN DATA (PER THE GEOTECHNICAL REPORT)
A. SEISMIC IMPORTANCE FACTOR: IE = 1.00
B. MAPPED SPECTRAL RESPONSE ACCELERATION PARAMETERS:
SS = 0.109g, S1 = 0.0425g
C.SITE CLASS: D
D.SHORT-PERIOD SITE COEFFICIENT: Fa = 1.6 E.LONG-PERIOD SITE COEFFICIENT: Fv = 2.4
F. DESIGN SPECTRAL RESPONSE ACCELERATION PARAMETERS:
SDS = 0.116g, SD1 = 0.068g
G.SEISMIC DESIGN CATEGORY: A
H.BASIC SEISMIC FORCE-RESISTING SYSTEM: BEARING WALL SYSTEM WITH
ORDINARY REINFORCED MASONRY SHEAR WALLS
I. DESIGN BASE SHEAR: XXXX KIPS
J. SEISMIC RESPONSE COEFFICIENT: Cs = 0.057
K.RESPONSE MODIFICATION COEFFICIENT: R = 2
L. ANALYSIS PROCEDURE USED: EQUIVALENT LATERAL FORCE ANALYSIS
M.THE ASCE 7-16 SEISMIC DESIGN REQUIREMENTS FOR BUILDINGS DO NOT
APPLY TO THIS BUILDING SINCE IT HAS BEEN ASSIGNED TO SEISMIC
DESIGN CATEGORY A.
9. ROOF RAIN LOAD DATA
RAIN INTENSITY: i = 3.5 INCH/HOUR FOR 60-MINUTE DURATION / 100-YEAR
RETURN PERIOD STORM
10.NOTIONAL LOADS FOR GENERAL STRUCTURAL INTEGRITY:
LOAD PATH CONNECTIONS: 5% OF THE CONNECTED PORTION'S WEIGHT
LATERAL FORCES: DESIGN LATERAL FORCE APPLIED AT A STORY EQUAL
TO 1% OF THE PORTION OF THE TOTAL DEAD LOAD OF THE STRUCTURE
LOCATED OR ASSIGNED TO A LEVEL.
CONNECTION TO SUPPORTS: 5% OF THE UNFACTORED DEAD LOAD PLUS
LIVE LOAD REACTION IMPOSED BY THE SUPPORTED MEMBER ON THE
SUPPORTING MEMBER.
ANCHORAGE OF STRUCTURAL WALLS: STRENGTH LEVEL HORIZONTAL
FORCE PERPENDICULAR TO THE PLANE OF THE WALL EQUAL TO 20% OF
THE WEIGHT OF THE WALL TRIBUTARY TO THE CONNECTION, BUT NOT
LESS THAN 5 PSF.
UNIT MASONRY
CAST-IN-PLACE CONCRETE
1. CONCRETE: NORMAL WEIGHT WITH A 4000 PSI MINIMUM 28-DAY COMPRESSIVE
STRENGTH.
2. FORMWORK:
A. COORDINATE CONCRETE WORK WITH THE PLACEMENT OF PIPING,
INSERTS, FLOOR DRAINS, CHAMFER STRIPS, REGLETS AND OTHER
EMBEDDED ITEMS.
B. ACCURATELY PLACE, SUPPORT AND SECURE EMBEDDED ITEM SUCH AS
ANCHOR RODS AND WELD PLATES BEFORE PLACING CONCRETE TO
PREVENT DISPLACEMENT OF EMBEDDED ITEM BEYOND PERMITTED
TOLERANCES.
C. SLEEVE PIPING OR UTILITIES PASSING THROUGH CONCRETE TO MAINTAIN
1" CLEAR ALL AROUND, UNLESS NOTED OTHERWISE. REFER TO OTHER
DISCIPLINE DRAWINGS FOR SLEEVE DETAILS. PROVIDE MEASURES TO
ENSURE THAT SLEEVES REMAIN FREE OF DEBRIS AND WATER DURING
CONSTRUCTION.
D. PROVIDE 3/4" CHAMFER STRIPS ON EDGES OF EXPOSED CONCRETE,
UNLESS NOTED OTHERWISE.
E. WITH THE EXPLICIT PRIOR APPROVAL IN WRITING OF THE CONTRACTING
OFFICER, FOOTINGS FOR SHALLOW FOUNDATIONS MAY BE EARTH-FORMED
USING UNDISTURBED NATIVE SOIL. PROVIDE A MINIMUM EXCAVATION
WIDTH 4" GREATER THAN INDICATED.
1. SHALLOW FOUNDATION SETTLEMENT LIMIT: NOT TO EXCEED AN ANGULAR
DISTORTION OF 1/500 DIFFERENTIAL OR 1-INCH TOTAL.
2. CONCRETE ROOF FRAMING DEFLECTION LIMIT:
A. L/180 FOR IMMEDIATE DEFLECTION DUE TO LIVE LOAD.
3. BUILDING LATERAL DRIFT: H/480 BASED ON AN ALLOWABLE STRESS DESIGN
WIND SPEED WITH A 10 YEAR MEAN RECURRENCE INTERVAL (0.42 TIMES THE
BASIC COMPONENT AND CLADDING LOADS):
4. WIND INDUCED DEFLECTION LIMITS FOR FRAMING SUPPORTING EXTERIOR
WALL FINISHES BASED ON AN ALLOWABLE STRESS DESIGN WIND SPEED
WITH A 10 YEAR MEAN RECURRENCE INTERVAL (0.42 TIMES THE BASIC
COMPONENT AND CLADDING LOADS):
A. L/240 FOR INSULATED METAL PANEL
B. L/600 DEFLECTION LIMIT FOR MASONRY VENEER SKIRT DOES NOT
CONTROL
SERVICEABILITY LIMITS
GEOTECHNICAL INFORMATION
1. THE INFORMATION PROVIDED IN THE REPORT TITLED 'FINAL GEOTECHNICAL
REPORT MILCON PROJECT P-171 WON 1737010 WEAPONS MAGAZINES, PHASE 3
YORKTOWN NAVAL WEAPONS STATION, YORKTOWN, VA', PREPARED BY
NAVFAC MIDLANT, AND DATED SEPTEMBER 18, 2023 HAS BEEN USED FOR THE
DESIGN OF THE FOUNDATIONS.
2. SITE PREPARATION
A. EXCAVATE, FILL, AND BACKFILL IN ACCORDANCE WITH THE CONTRACT
DRAWINGS AND SPECIFICATIONS.
B. DO NOT INSTALL FOUNDATION WORK UNTIL IT HAS BEEN COORDINATED
WITH ADJACENT UNDERGROUND UTILITIES. SLEEVE OR LOWER FOOTINGS
WHERE REQUIRED. INSTALL UTILITIES PERPENDICULAR TO WALL
FOOTINGS.
C. DO NOT PLACE BACKFILL IN AN UNBALANCED MANNER AGAINST
FOUNDATION WALLS UNLESS WALLS ARE SECURELY BRACED AGAINST
OVERTURNING, EITHER BY TEMPORARY CONSTRUCTION BRACING OR BY
PERMANENT CONSTRUCTION.
D. PROVIDE A 6 INCH LAYER OF VDOT NO. 57 STONE BELOW THE FOOTINGS.
3. SOIL AND SITE CHARACTERISTICS
A. MODULUS OF SUBGRADE REACTION: 100 PCI FOR GROUND LEVEL SLAB
UPON FIRM NATURAL SOIL OR WELL-COMPACTED STRUCTURAL FILL
MATERIAL
4. SHALLOW FOUNDATIONS
A. NET ALLOWABLE SOIL BEARING PRESSURE: 1,500 PSF
B. FACTOR OF SAFETY: 2.0 FOR SLIDING AND OVERTURNING STABILITY
C. PRIOR TO PLACING FOUNDATION CONCRETE AND REINFORCEMENT, ALLOW
SPECIAL INSPECTOR/GEOTECHNICAL ENGINEER TO INSPECT FOUNDATION
EXCAVATIONS TO EXPLORE THE EXTENT OF ANY POSSIBLE LOOSE, SOFT,
EXPANSIVE, OR OTHERWISE GEOTECHNICALLY UNSUITABLE SUBGRADE
CONDITIONS AND TO VERIFY THE DESIGN BEARING PRESSURE.
GEOTECHNICAL ENGINEER WILL PROVIDE DIRECTION TO CORRECT
UNSUITABLE SUBGRADE SUBJECT TO REVIEW AND APPROVAL BY THE
CONTRACTING OFFICER.
D. FROST PENETRATION DEPTH IS 9 INCHES BELOW FINISH SITE GRADES.
SUBJECT TO REVIEW AND APPROVAL OF THE CONTRACTING OFFICER,
LOWER FOOTINGS BASED ON ACTUAL SITE CONDITIONS TO MAINTAIN
BOTTOM OF EXTERIOR FOUNDATIONS A MINIMUM OF 9 INCHES BELOW
FINAL SITE GRADES.
1. UFC 1-200-01 (01 SEPTEMBER 2022), DOD BUILDING CODE, IS THE
FOUNDATIONAL DOCUMENT FOR THE DESIGN OF THE STRUCTURAL SYSTEM
FOR THIS PROJECT. BELOW ARE CORE UFC, CONSENSUS BUILDING CODES
AND STANDARDS USED FOR THE DESIGN OF THE STRUCTURAL SYSTEM:
CORE UNIFIED FACILITIES CRITERIA:
UFC 3-301-01 (1 OCTOBER 2019 CHANGE 1, 4 FEBRUARY 2022):
STRUCTURAL ENGINEERING
UFC 3-320-06A (1 MARCH 2005): CONCRETE FLOOR SLABS ON GRADE
SUBJECTED TO HEAVY LOADS
CONSENSUS BUILDING CODES AND STANDARDS:
GENERAL:
IBC 2021: INTERNATIONAL BUILDING CODE
ASCE 7-16, WITH SUPPLEMENT 1: AMERICAN SOCIETY OF CIVIL
ENGINEERS, MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER
STRUCTURES
CONCRETE:
ACI 318-19: AMERICAN CONCRETE INSTITUTE, BUILDING CODE
REQUIREMENTS FOR STRUCTURAL CONCRETE
MASONRY
TMS 402-2022: BUILDING CODE FOR MASONRY STRUCTURES
TMS 602-2022: SPECIFICATION FOR MASONRY STRUCTURES
METALS:
ANSI/AISC 360-22: AMERICAN INSTITUTE OF STEEL CONSTRUCTION,
SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS
AWS D1.1-2015: AMERICAN WELDING SOCIETY, STRUCTURAL
WELDING CODE – STEEL
CAST-IN-PLACE CONCRETE CONTINUED
3. REINFORCING STEEL:
A. BARS: ASTM A615 GRADE 60. SHOP FABRICATE BENT BARS AND BARS WITH
HOOKS.
B. WELDED WIRE REINFORCEMENT: ASTM A1064, SHEET TYPE. DO NOT USE
ROLL TYPE.
C. DETAIL AND PLACE REINFORCEMENT IN ACCORDANCE WITH THE
AMERICAN CONCRETE INSTITUTE ACI SP-66, ACI 301 AND ACI 318, AND THE
CONCRETE REINFORCING STEEL INSTITUTE CRSI MANUAL OF STANDARD
PRACTICE.
D. UNLESS NOTED OTHERWISE, USE THE FOLLOWING MINIMUM CONCRETE
CLEAR COVER OVER REINFORCEMENT:
a. CONCRETE CAST AGAINST EARTH OR EXPOSED TO EARTH OR
WEATHER: 3"
b. ELEVATED SLABS: 1"
E.UNLESS NOTED OTHERWISE, USE A 44 BAR DIAMETER EMBEDMENT AND
LAP SPLICE LENGTH.
F. MINIMUM STANDARD HOOK EMBEDMENT LENGTHS: 16 BAR DIAMETERS
G.HOOK EMBEDMENT IS THE MINIMUM STRAIGHT LINE DISTANCE FROM THE
CRITICAL SECTION OF THE BAR TO THE FARTHEST EDGE OF THE HOOK.
4. JOINTS:
A.LOCATE CONSTRUCTION, CONTRACTION, ISOLATION, EXPANSION, AND
OTHER JOINTS AS INDICATED OR SPECIFIED, OR OTHERWISE APPROVED BY
THE CONTRACTING OFFICER.
B.CLEAN SURFACES OF HORIZONTAL AND VERTICAL CONSTRUCTION JOINTS
TO REMOVE LAITANCE AND EXPOSE CLEAN COARSE AGGREGATE SOLIDLY
EMBEDDED IN MORTAR MIX. THOROUGHLY CLEAN AND WET SURFACE OF
CONSTRUCTION JOINTS JUST PRIOR TO DEPOSITING CONCRETE.
POST INSTALLED ANCHORS
1. ALL ADHESIVE ANCHOR INSTALLATIONS WILL COMPLY WITH MANUFACTURER’S
WRITTEN INSTRUCTIONS AND SPECIFICATIONS, INCLUDING ICC-ES REPORTS.
THE FOLLOWING INSTRUCTIONS ARE MINIMUM REQUIREMENTS AND DO NOT
SUPERSEDE ANY INSTRUCTIONS OR REQUIREMENTS FROM THE CONTRACTOR’S
SELECTED MANUFACTURER. CONTRACTOR TO SUBMIT SELECTED ANCHOR
PRODUCT FOR REVIEW AND APPROVAL.
2. DUST WILL BE BLOWN FROM THE HOLE WITH COMPRESSED AIR TO ENSURE
PROPER ANCHOR SEATING DEPTH AND TO PROVIDE A CLEAN BONDING
SURFACE. ADDITIONALLY, THE HOLE WILL BE BRUSHED WITH A NYLON BRUSH
THEN BLOWN AGAIN WITH COMPRESSED AIR.
3. ADHESIVE WILL ONLY BE APPLIED TO DRY SURFACES.
4. BASE MATERIAL TEMPERATURE MUST BE IN ACCORDANCE WITH
MANUFACTURER INSTRUCTIONS AT TIME OF INSTALLATION.
5. WHEN INSTALLING EPOXY ANCHORS INTO MASONRY, ANCHORS WILL BE
INSTALLED IN SOLID GROUTED CELLS ONLY. CONTRACTOR TO AVOID
DAMAGING REINFORCING DURING INSTALLATION.
6. CHEMICAL ANCHOR SYSTEMS:
a. CONCRETE: USE ONLY ADHESIVE ANCHOR SYSTEMS THAT HAVE BEEN
ISSUED AN ICC-ES REPORT IN ACCORDANCE WITH PROVISIONS OF ICC-ES
AC308. ANCHOR SYSTEM SHOULD BE APPROVED FOR USE IN CRACKED
CONCRETE AND SEISMIC DESIGN CATEGORIES A-F PER SECTION 2.0 OF THE
ICC-ES EVALUATION SERVICES REPORT. ANCHOR SYSTEM WILL BE INSTALL
PER REQUIREMENTS OF THE ICC-ES EVALUATION SERVICES REPORT FOR
SPECIFIC ANCHOR, AND AS REQUIRED BY THE MANUFACTURER.
b. GROUT-FILLED MASONRY UNITS: USE ONLY ADHESIVE ANCHOR SYSTEMS
THAT HAVE BEEN ISSUED AN ICC-ES REPORT IN ACCORDANCE WITH
PROVISIONS OF ICC-ES AC58. ANCHOR SYSTEMS WILL BE INSTALLED PER
REQUIREMENTS OF ICC-ES EVALUATION SERVICES REPORT FOR THE
SPECIFIC ANCHOR, AND AS REQUIRED BY THE MANUFACTURER.
7. REMOVE GREASE, OIL, RUST, AND ANY OTHER LAITANCE FROM RODS AND
DOWELS PRIOR TO INSTALLATION.
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
SLOPED CONCRETE
SLAB-ON-GRADE
REINFORCED CONCRETE
MASONRY UNIT WALL
BACKING UP INSULATED
METAL WALL PANELS
OVERHEAD DOOR OPENING
OVERHEAD DOOR OPENING
OVERHEAD DOOR OPENING
REINFORCED CONTINUOUS
CONCRETE WALL FOOTING
TURNED DOWN SLAB
EDGE AT DOOR OPENINGS
SOLID GROUTED
CONCRETE MASONRY UNIT
FOUNDATION WALL UNDER
MASONRY VENEER.
INSULATION NOT SHOWN
PERSONNEL DOOR OPENING
STEP AT
OVERHEAD DOOR
BOLLARD
CONCRETE
EQUIPMENT PAD
SLOPED REINFORCED
CONCRETE ROOF SLAB
REINFORCED CONCRETE
MASONRY UNIT WALL
BACKING UP INSULATED
METAL WALL PANELS
CANTILEVERED SLAB
OVERHANG AROUND
ROOF PERIMETER
ROOF OPENING FOR
MECHANICAL VENT
ROOF OPENING FOR
MECHANICAL VENT
STEP TOP OF WALL
FOR ROOF SLOPE
DESIGN WIND PRESSURES FOR ROOF COMPONENTS (PSF)
COMPONENT TRIBUTARY AREA (SQFT)
ROOF
ZONE
DESIGN WIND PRESSURES FOR WALL COMPONENTS (PSF)
COMPONENT TRIBUTARY AREA (SQFT)WALL
ZONE
+20
1. USE WIND PRESSURES BELOW FOR THE DESIGN OF COMPONENTS AND
CLADDING ELEMENTS OR RETAIN A PROFESSIONAL ENGINEER TO
DETERMINE WIND PRESSURES FOR SPECIFIC EFFECTIVE WIND AREAS.
2. REFER TO DESIGN LOADS AND CRITERIA NOTES ON S-001 FOR WIND LOAD
DESIGN CRITERIA.
3. WIND PRESSURES ARE STRENGTH LEVEL VALUES BASED ON THE BASIC
DESIGN WIND SPEED (WIND LOAD FACTOR = 1.0). MULTIPLY PRESSURES
BY 0.6 WHEN USING ALLOWABLE STRESS DESIGN METHODOLOGY.
4. PRESSURE ARE GROSS VALUES, DO NOT INCLUDE DEAD LOADS AND ARE
TABULATED IN POUNDS PER SQUARE FOOT (PSF).
5. FOR ROOFS AND WALLS, PLUS AND MINUS SIGNS SIGNIFY PRESSURES
ACTING TOWARD AND AWAY FROM THE SURFACES, RESPECTIVELY.
6. DESIGN COMPONENTS AND CLADDING FOR THE MAXIMUM POSITIVE AND
NEGATIVE WIND PRESSURES.
7. FOR COMPONENTS AND CLADDING NOT AFFECTED BY INTERNAL
PRESSURE SUCH AS METAL WALL PANELS ATTACHED TO THE EXTERIOR
SURFACES OF CONCRETE WALLS, DEDUCT 5 PSF INTERNAL PRESSURE
FROM THE ABSOLUTE PRESSURE VALUES TABULATED BELOW EXCEPT DO
NOT REDUCE BELOW 16 PSF.
8. LINEAR INTERPOLATION IS PERMITTED FOR INTERMEDIATE EFFECTIVE
WIND AREAS.
9. BUILDING ZONES ARE DEFINED IN ASCE 7-16 FIGURES 30.3-1 FOR WALLS,
30.3-5B FOR ROOFS.
10. FOR DESIGN OF DEFLECTION-CONTROLLED COMPONENTS AND CLADDING,
MULTIPLY DESIGN WIND PRESSURES BY 0.42 TO CONVERT LOADING TO
ALLOWABLE STRESS DESIGN VALUES FOR A 10-YEAR MEAN RETURN
INTERVAL.
-38
+20 -44
+20 -71
+18 -35
+18 -38
+18 -58
+17 -34
+17 -36
+17 -52
+17 -34
+17 -36
+17 -52
+32 -34
+32 -40
+28 -30
+28 -33
+27 -29
+27 -31
+26 -28
+26 -26
WHEEL BASE
89" STEER WHEEL
UNLOADED = 12,460 LBS
LOADED = 15,050 LBS
DRIVE AXLE
UNLOADED = 4,800 LBS
LOADED = 14,210 LBS
NOTES:
1. LOADS BASED ON COMBILIFT FORKLIFT MODEL C12000ET
2. RATED CAPACITY = 12,000 LBS
3. OVERALL WIDTH (WIDE TREAD) = 90.4"
4. FRONT WHEEL LOAD = 1/2 AXLE LOAD
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/3
/2
:0
:2
P
M
C U s e rs \m ig u e l.
w a lk e r\
D o c u m e n ts \P
-1
-S -R
-F O
R K
L
IF
T m ig u e l.
w a lk e r.
rv t
S-002B
D
R E
P R
E S
E N
T A
T
IO
N
CWJ
12942153
DOB MTW
03/26/2026
F O
R K
L
IF
T C
H A
R G
IN
G
S T
A T
IO
N
MMP/SLC
1737010
Y O
R K
T O
W N
V
IR
G
IN
IA
N A
V A
L W
E A
P O
N S
S T
A T
IO
N
JWJ
NEK
HPN
M
ID
L A
N T
D C
C O
R E
S -0
B
P W
E A
P O
N M
A G
A Z
IN
E
S
Approved by LCDR VINCE DEL GRECO, ROICC with PWD
YORKTOWN, via Email.
A. REFER TO S-001B FOR GENERAL NOTES AND LEGEND.
B. THE 3D REPRESENTATION IS FOR GENERAL INFORMATION ONLY AND
DOES NOT REPRESENT A COMPLETE AND DETAILED REPRESENTATION OF
THE STRUCTURE. REFER TO FOUNDATION AND FRAMING PLANS,
ENLARGED SECTIONS AND DETAILS AND MISCELLANEOUS DETAILS FOR
MORE DETAILED INFORMATION NOT SHOWN IN THE 3D REPRESENTATION.
C. ARCHITECTURAL AND OTHER NON-STRUCTURAL ELEMENTS ARE NOT
SHOWN IN THE 3D REPRESENTATION.
3D REPRESENTATION GENERAL NOTES
NOT TO SCALE
A1
3D REPRESENTATION
COMPONENTS AND CLADDING PRESSURES
FORKLIFT AXLE LOADS AND GEOMETRY
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
A. REFER TO S-001B FOR GENERAL NOTES AND PLAN LEGEND AND S-501B
FOR TYPICAL SLAB-ON-GRADE AND FOUNDATION DETAILS.
B. ELEVATIONS SHOWN ON THE STRUCTURAL DRAWINGS ARE RELATIVE TO
A REFERENCE ELEVATION OF 0'-0" REFER TO CIVIL DRAWINGS FOR
CORRESPONDING ELEVATION.
C. TOP OF FOOTING ELEVATIONS ARE 1'-4" BELOW REFERENCE ELEVATION
0'-0" UNLESS NOTED OTHERWISE.
D. PROVIDE TERMITE TREATMENT DIRECTLY ON THE EXPOSED COMPACTED
BUILDING PAD SUBGRADE SOIL.
A
B
A1 S-401B
WF3.0
WF3.0
W F
3.
W F
3.
A2 S-401B
A3 S-401B
A4 S-401B
3' - 8" 10' - 8" 1' - 4" 10' - 8" 1' - 4" 10' - 8" 3' - 8"
42' - 0"
3'
4" 3'
4"
W1
W2
TYP
W1
W1
A4 S-401B
W2
-2 5/8" -2 5/8"
-2 5/8"
-3 1/2"
3/
/ 1
2"
-3 1/2" -2 5/8" -3 1/2" -2 5/8"
-4 1/4" -4 1/4"
TYP
TYP
6 6
TYP
10"
-4"-3 1/2"
8" 1'
8"
10" 1' - 4"
1'
4"
1' - 4"
S-502B A3
0" 0" 0"0"
S-502B A3
SIM
-2 5/8"
-2 5/8"
-3 1/4"-3 1/4"
-3 1/4"-3 1/4"
-3 1/4"-3 1/4"
-4 1/4" -4 1/4" -4 1/4" -4 1/4"
-3 1/2"
S-502B A3
SIM
2'
5"
3' - 2"
1'
1'
5' - 4"
2'
5"
3' - 6"
[TOF -3'-4"]
[TOF -4'-8"]
[TOF -3'-4"]
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/3
/2
:0
:2
P
M
C U s e rs \m ig u e l.
w a lk e r\
D o c u m e n ts \P
-1
-S -R
-F O
R K
L
IF
T m ig u e l.
w a lk e r.
rv t
S-101B
F O
U N
D A
T
IO
N A
N D
G R
O U
N D
F L O
O R
P L A
N
CWJ
12942154
DOB MTW
03/26/2026
F O
R K
L
IF
T C
H A
R G
IN
G
S T
A T
IO
N
MMP/SLC
1737010
Y O
R K
T O
W N
V
IR
G
IN
IA
N A
V A
L W
E A
P O
N S
S T
A T
IO
N
JWJ
NEK
HPN
M
ID
L A
N T
D C
C O
R E
S -1
B
P W
E A
P O
N M
A G
A Z
IN
E
S
Approved by LCDR VINCE DEL GRECO, ROICC with PWD
YORKTOWN, via Email.
1 8-INCH CONCRETE SLAB-ON-GRADE REINFORCED WITH #5 BARS 16 OC
SPACING EACH WAY ON VAPOR RETARDER AND 12-INCH DEEP POROUS
FILL.
SLAB SLOPE VALUES ARE NOMINAL. ACTUAL SLOPE VALUES ARE VALUES
RESULTING FROM THE ACTUAL TOP OF SLAB ELEVATIONS INDICATED.
2 SLAB-ON-GRADE DOWELED JOINT. REFER TO DETAILS ON S-501B.
3 GRID LINE AND FACE OF MASONRY VENEER.
4 FREE STANDING INTERIOR CONCRETE EMBEDDED BOLLARD - REFER TO
TYPICAL BOLLARD DETAIL ON S-502B. REFER TO ARCHITECTURAL
DRAWINGS FOR BOLLARD LOCATION WITHIN BUILDING LIMITS.
COORDINATE BOLLARD PLACEMENT WITH BUILDINGS FOUNDATIONS AND
PAVEMENT.
5 BOLLARD AT OVERHEAD DOORS - REFER TO TYPICAL BOLLARD DETAIL ON
S-502B. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS WITHIN
BUILDING LIMITS. COORDINATE BOLLARD PLACEMENT WITH BUILDINGS
FOUNDATIONS.
6 CONCRETE EQUIPMENT PAD. REFER TO S-501B FOR DETAIL.
7 STEP WALL FOOTING TO AN ELEVATION LOWER THAN ELECTRICAL DUCT
BANK. REFER TO B1/S-501B, TYPICAL FOOTING DETAILS AND C3/S-502B,
TYPICAL CONCRETE MASONRY BOND BEAM LINTEL DETAIL. REFER TO
ELECTRICAL SITEWORK DRAWINGS FOR DUCT BANK LOCATION.
GENERAL SHEET NOTES
3/8" = 1'-0" A1
FOUNDATION AND GROUND FLOOR PLAN
PLAN
NORTH
0' 2' 4' 6'
WALL FOOTING SCHEDULE
MARK
DIMENSIONS
REINFORCINGWIDTH DEPTH
WF3.0 3' - 0" 1' - 2" (5)-#5 CONTINUOUS TOP AND BOTTOM WITH #4 TIES AT 1'-6" ON
CENTER
MASONRY WALL SCHEDULE
MARK CMU WIDTH
REINFORCING
NOTESVERTICAL HORIZONTAL
W1 8" #5 AT 4'-0" OC (2)-#5 CONTINUOUS AT LOCATIONS INDICATED. 1
W2 12" #5 AT 1'-4" OC (2)-#5 CONTINUOUS AT LOCATIONS INDICATED. 1, 2 AND 3
NOTES:
1. AT SIDE AND REAR WALLS, PLACE TOP OF CONTINUOUS BOND BEAMS AT ELEVATIONS 2'-0", 6'-0", AND 10'-0".
AT SIDE WALLS, PLACE STEPPED BOND BEAM AT TOP OF STEPPED WALL. REFER TO SECTION FOR DETAILS.
2. PLACE TOP OF CONTINUOUS BOND BEAMS AT ELEVATIONS 2'-0" AND 15'-4" AND PLACE 24" DEEP CONTINUOUS BOND BEAM LINTEL AT HEAD OF OVERHEAD DOOR OPENINGS. REFER TO SECTIONS FOR DETAILS.
3. AT 1'-4" LONG SECTIONS OF WALLS, AT EACH SIDE OF OVERHEAD DOOR OPENINGS, PLACE (2) #5 BAR VERTICAL
REINFORCING BARS IN EACH CELL. REFER TO DETAIL 4 ON S-502B.
KEYNOTES
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
A. REFER TO S-001B FOR GENERAL NOTES AND PLAN LEGEND AND S-501B
FOR TYPICAL WALL AND ROOF SLAB DETAILS.
A
B
A1 S-401B
A3 S-401B
A4 S-401B
A4 S-401B
1 2
3"
A2 S-401B
6"
2'
6"
3' - 8"
MASONRY LINTEL OPENING
10' - 8" 1' - 4"
MASONRY LINTEL OPENING
10' - 8" 1' - 4"
MASONRY LINTEL OPENING
10' - 8" 3' - 8"
6" 42' - 0" 6"
3'
4"
3'
4"
TYP
TYP
3'
4" 3'
4"
2'
0" 3'
4"
2'
0" 3'
4"
2'
0"
16' - 8"
6' - 4"
REINFORCED CMU WALL BENEATH
ROOFING ASSEMBLY LAYOUT CENTERLINE
EQUAL EQUAL
2'
0" 4'
0"
DIAGONAL STACK BRACE
CONNECTOR ANCHORED TO
REINFORCED CONCRETE
SLAB. SEE DETAIL C5/A-502B
3' - 2" 3' - 2"
15' - 4"
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/3
/2
:0
:3
P
M
C U s e rs \m ig u e l.
w a lk e r\
D o c u m e n ts \P
-1
-S -R
-F O
R K
L
IF
T m ig u e l.
w a lk e r.
rv t
S-102B
F R
A M
IN
G
P L A
N
R O
O F
CWJ
12942155
DOB MTW
03/26/2026
F O
R K
L
IF
T C
H A
R G
IN
G
S T
A T
IO
N
MMP/SLC
1737010
Y O
R K
T O
W N
V
IR
G
IN
IA
N A
V A
L W
E A
P O
N S
S T
A T
IO
N
JWJ
NEK
HPN
M
ID
L A
N T
D C
C O
R E
S -1
B
P W
E A
P O
N M
A G
A Z
IN
E
S
Approved by LCDR VINCE DEL GRECO, ROICC with PWD
YORKTOWN, via Email.
GENERAL SHEET NOTES
3/8" = 1'-0" A1
FRAMING PLAN - ROOF
1 8-INCH CONCRETE SLAB REINFORCED WITH #5 AT 12" ON CENTER EACH
DIRECTION TOP AND BOTTOM. TERMINATE TOP REINFORCING WITH
STANDARD 90-DEGREE HOOKS EACH END. PLACE REINFORCING PARALLEL
TO NUMBERED GRID LINES IN OUTER LAYER.
2 COORDINATE SIZE AND UNDERSLAB SUPPORT WITH MECHANICAL
OPENING FOR MECHANICAL VENT. REFER TO S-501B FOR SLAB OPENING
REINFORCING DETAIL.
3 EDGE OF CONCRETE ROOF SLAB OVERHANG.
4 FACE OF METAL WALL PANEL BELOW.
5 MASONRY WALL STEPS AT WALLS PARALLEL TO ROOF SLAB SLOPE. TURN
DOWN ROOF SLAB TO TOP OF STEPPED WALL.
6 8" DEEP BOND BEAM LINTEL AT HEAD OF DOOR OPENING. REINFORCED
WITH (2) #5 BOTTOM. BEAR LINTEL 8" EACH END.
PLAN
NORTH
0' 2' 4' 6'
KEYNOTES
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
GROUND FLOOR
0' - 0"
ROOF LOW BEARING
10' - 0"
B
ROOF - HIGH BEARING
15' - 4"
ROOF SLAB EDGE GRID LINE /
EXTERIOR FACE OF
MASONRY VENEER
INTERIOR FACE
OF CMU WALL
CONTINUOUS 8" DEEP BOND
BEAMS REINFORCED WITH (2)
#4 CONTINUOUS BOTTOM
12" REINFORCED
CMU WALL
VERTICAL WALL
REINFORCING
TOP OF OVERHEAD
DOOR ROUGH
OPENING
CONCRETE WALL
FOOTING
VAPOR RETARDER
POROUS FILL
COMPACTED
SUBGRADE
CONCRETE
SLAB-ON-GRADE
SLOPE
GALVANIZED
L2 1/2 X 2 1/2 X 1/4 WITH
1/2"Ø X 4" LONG
HEADED STUDS AT 24"
ON CENTER ALONG
DOOR SILL
TURNED DOWN
SLAB EDGE AT DOOR
CONTINUE VAPOR RETARDER
UNDER SLAB EDGE
WALL BEYOND
OVERHEAD DOOR
ROOF FINISH
MASONRY
VENEER BEYOND
PRECAST
BAND BEYOND
METAL WALL
PANEL BEYOND
METAL WALL PANEL
2' - 6"
SITE PAVEMENT
CONTINUOUS 24" DEEP BOND
BEAM LINTEL REINFORCED
WITH (2) #5 TOP AND BOTTOM
FULL LENGTH OF FRONT WALL
6"
EDGE OF
STEP / ANGLE
REINFORCED
CONCRETE
ROOF SLAB
3/4"
CHAMFER
1"
WORKING POINT AT
UNDERSIDE OF SLAB
AND FACE OF CMU
BOLLARD BEYOND
NOTE:
REFER TO OTHER SECTIONS ON THIS SHEET FOR
NOTES NOT SHOWN INCLUDING NON-GEOTEXTILE
AND STONE BASE BENEATH ALL WALL FOOTINGS TYP.
EXTENDED
FOOTING FOR
BOLLARDS BEYOND
EXTENDED
FOOTING FOR
BOLLARDS BEYOND
1' - 8"
B
CONTINUOUS 8" DEEP BOND
BEAMS REINFORCED WITH (2)
#4 CONTINUOUS BOTTOM
12" REINFORCED
CMU JAMB
VERTICAL WALL
REINFORCING OVERHEAD DOOR BEYOND
METAL WALL PANEL
ROOF FINISH
MASONRY VENEER
PRECAST BAND AND
GALVANIZED
L4 X 4 X 3/8" X 1'-0" LONG
SUPPORT ANGLE, REFER
TO ARCHITECTURAL
DRAWINGS
METAL WALL PANEL
ROOF SLAB EDGE
SITE PAVEMENT
CONCRETE
WALL FOOTING
GROUT VENEER
AND CAVITY
SOLID BELOW 0'-0"
REINFORCED
CONCRETE
ROOF SLAB
1"
WORKING POINT AT
UNDERSIDE OF SLAB
AND FACE OF CMU
PREMOLDED
JOINT FILLER
DOWELS SAME SIZE
AND SPACING AS
VERTICAL REINFORCING
GRID LINE /
EXTERIOR FACE OF
MASONRY VENEER
INTERIOR FACE
OF CMU WALL
2' - 6"
VAPOR RETARDER
POROUS FILL
CONCRETE
SLAB-ON-GRADE
SLOPE
CONTINUOUS 8" DEEP
BOND BEAMS
REINFORCED WITH (2) #4
CONTINUOUS BOTTOM
GROUT COURSE SOLID
ABOVE BOND BEAM AT
PRECAST BAND
CONTINUOUS 24" DEEP BOND
BEAM LINTEL REINFORCED
WITH (2) #5 TOP AND BOTTOM
FULL LENGTH OF FRONT WALL
3/4"
CHAMFER
NOTE:
REFER TO A1/S-502B FOR TYPICAL BOLLARD DETAILS.
REFER TO OTHER SECTIONS ON THIS SHEET FOR
NOTES NOT SHOWN INCLUDING NON-GEOTEXTILE
AND STONE BASE BENEATH ALL WALL FOOTINGS TYP.
BOLLARD AT
OVERHEAD DOOR
TYP
1' - 8"
A
0"
WORKING POINT AT
UNDERSIDE OF SLAB
AND FACE / TOP OF CMU
CONTINUOUS 8" DEEP BOND
BEAMS REINFORCED WITH (2)
#4 CONTINUOUS BOTTOM
8" REINFORCED
CMU WALL
VERTICAL WALL
REINFORCING
ROOF SLAB EDGE
DOWELS SAME SIZE
AND SPACING AS
VERTICAL REINFORCING
GRID LINE /
EXTERIOR FACE OF
MASONRY VENEER
MASONRY VENEER
PRECAST BAND AND GALVANIZED
L4 X 4 X 3/8" X 1'-0" LONG
SUPPORT ANGLE, REFER TO
ARCHITECTURAL DRAWINGS
METAL WALL PANEL
CONCRETE
WALL FOOTING
GROUT VENEER AND
CAVITY SOLID
BELOW 0'-0"
SLOPE
PREMOLDED
JOINT FILLER
INTERIOR FACE
OF CMU WALL
ROOF FINISH
REINFORCED
CONCRETE ROOF SLAB
1' - 4" 6"
CONTINUOUS 8" DEEP BOND
BEAMS REINFORCED WITH
(2) #4 CONTINUOUS BOTTOM
GROUT COURSE SOLID
ABOVE BOND BEAM AT
PRECAST BAND
CONCRETE
EQUIPMENT PAD
(EQUIPMENT
NOT SHOWN)
TOP OF CMU /
UNDERSIDE OF SLAB
NOTE:
REFER TO OTHER SECTIONS ON THIS SHEET FOR
NOTES NOT SHOWN INCLUDING NON-GEOTEXTILE
AND STONE BASE BENEATH ALL WALL FOOTINGS TYP.
BOLLARD BEYOND
GROUND FLOOR
0' - 0"
ROOF - HIGH BEARING
15' - 4"
NOTE:
REFER TO OTHER
SECTIONS ON THIS SHEET
FOR NOTES NOT SHOWN.
STEP CMU BOND BEAM AT
TOP OF WALL TO ALLOW
ROOF SLAB TO TURN DOWN
TO TOP OF WALL. REFER TO
PLAN FOR DIMENSIONS OF
WALL STEP LENGTHS. LAP
BOND BEAMS 2'-0" AT STEPS.
ROOF SLAB TURN
DOWN DEPTH
REINFORCED
CONCRETE
ROOF SLAB
1' - 4"6"
INTERIOR FACE
OF CMU WALL
GRID LINE /
EXTERIOR FACE OF
MASONRY VENEER
ROOF SLAB
ELEVATION VARIES
2' - 0"
2'-0" THICK NO 57 STONE
BASE COURSE BENEATH
ALL WALL FOOTINGS TYP
NON-WOVEN GEOTEXTILE
TYP
T Y
P
2' - 0"
TYP
1/
2"
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/3
/2
:0
:3
P
M
C U s e rs \m ig u e l.
w a lk e r\
D o c u m e n ts \P
-1
-S -R
-F O
R K
L
IF
T m ig u e l.
w a lk e r.
rv t
S-401B
E N
L A
R G
E D
S E
C T
IO
N
S
CWJ
12942156
DOB MTW
03/26/2026
F O
R K
L
IF
T C
H A
R G
IN
G
S T
A T
IO
N
MMP/SLC
1737010
Y O
R K
T O
W N
V
IR
G
IN
IA
N A
V A
L W
E A
P O
N S
S T
A T
IO
N
JWJ
NEK
HPN
M
ID
L A
N T
D C
C O
R E
S -4
B
P W
E A
P O
N M
A G
A Z
IN
E
S
Approved by LCDR VINCE DEL GRECO, ROICC with PWD
YORKTOWN, via Email.
1" = 1'-0" (S-101B) A1
SECTION AT FRONT WALL
1" = 1'-0" (S-101B)
A2
SECTION AT FRONT WALL
1" = 1'-0" (S-101B) A3
SECTION AT REAR WALL
1" = 1'-0" (S-101B)
A4
SECTION AT SIDE WALL
AT OVERHEAD DOOR BETWEEN OVERHEAD DOORS
1' 2'0' 6"1' 2'0' 6" 1' 2'0' 6" 1' 2'0' 6"
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
D /3
D /3
D /3
D
NEW POURPREVIOUS POUR
WIDTH OF FOOTING
1 1/2" KEY FULL
BOTTOM REINFORCEMENT
CONTINUOUS THRU JOINT
4"4"
TO
P
2" C
LE
A
R
TIE BAR EACH SIDE OF
CONSTRUCTION JOINT
CONTINUOUS FOOTING CONSTRUCTION JOINT
WALL FOOTING AT UTILITY LINES
STEPPED CONTINUOUS FOOTING (SF)
M
A X
8" M
IN
M A
X
8" M
IN
8" STEP
16" MIN
16" STEP
32" MIN
3" CLEAR
12" MIN
LAP (TYPICAL)
36 BAR DIAMETER
CONTINUOUS WALL
FOOTING REINFORCEMENT
CONTINUOUS WALL
FOOTING
REINFORCEMENT
'Z' BARS SAME SIZE
AND NUMBER AS
CONTINUOUS FOOTING
REINFORCEMENT,
BEND AS SHOWN
UTILITY PERPENDICULAR TO AND THROUGH FOOTING
NON-CORROSIVE METAL
PIPE SLEEVE (INSIDE Ø =
OUTSIDE PIPE Ø + 2" MIN)
ADDED BARS SAME
SIZE AND NUMBER AS
CONTINUOUS
REINFORCEMENT
CONTINUOUS
BOTTOM
REINFORCEMENT,
CUT AT PIPE SLEEVE
AS REQUIRED
6" M
IN
(TYPICAL)
2" C
LEAR
M
IN
12" MIN
#4 AT 12" OC
(1) #4
(1) #4
STANDARD 90°
HOOK (TYPICAL)
3" C
LE
A
R
(T Y
P
IC
A L)
2" C
LE
A
R
CONTINUOUS WALL
FOOTING, REFER TO
PLAN
TOP OF SLEEVE WITHIN
FOOTING OR LESS THAN 4"
FROM BOTTOM OF FOOTING
CONTINUOUS FOOTING REINFORCEMENT
10"
9 3/8"
PLAN AT CORNER
9 3/8"9 3/8"
PLAN AT INTERSECTION
NOTE:
1. WHERE THREE OR MORE BARS
OCCUR, MIDDLE BAR(S) SHALL BE
TREATED AS INNER FACE BAR.
2. TRANSVERSE BARS NOT SHOWN
FOR CLARITY.
BARS (TYPICAL)
0" BETWEEN
TYPICAL FOOTING
REINFORCEMENT
TOP REINFORCEMENT
CONTINUOUS THRU JOINT
SLAB AT EXTERIOR OPENINGS
REFER TO ARCHITECTURAL DRAWINGS
WALL OPENING
#4 A
T
2" O
C
CLEAR
2"
1'
- 4
1' - 0" TYPICAL
PLAN
CONCRETE
SLAB-ON-GRADE
(1) #4 AT RE-ENTRANT
CORNER, MIDDLE OF
SLAB, EACH SIDE
NOTE:
WALL REINFORCEMENT
NOT SHOWN FOR CLARITY.
WALL
(1) #4 CONTINUOUS
EDGE OF SLAB (EOS)
SECTION
T Y
P
3' - 0"
STANDARD
90° HOOK
6" LAYER OF VDOT NO. 57 STONE
#5 AT 32" OC, MINIMUM
(2) PER OPENING
[8"] CMU GROUTED SOLID[REFER TO PLAN]
TOP OF FOOTING
[6"] SOLID CMU
PAVING OR FINISHED
GRADE, REFER TO
CIVIL DRAWINGS
RADIUSED
TOOLED EDGE
BEYOND
WALL
(1) #4 CONTINUOUS
#4 AT 12" OC
C
LE
A R
3/ 4"
INTERIOR CONCRETE SLAB-ON-GRADE EQUIPMENT PAD
4"
MIN.
6"
FACE OF EQUIPMENT
1/2" PREMOLDED
JOINT FILLER
(TYPICAL)
CONCRETE
SLAB-ON-GRADE
#4 AT 1'-0" OC EACH WAY
EQUIPMENT PAD
3/4" CHAMFER (TYPICAL)
2" C
LE
A
R
INTERIOR CONCRETE EQUIPMENT PAD
MIN.
6"
FACE OF EQUIPMENT
ROUGHEN SURFACE
TO 1/8" AMPLITUDE,
AND APPLY BONDING
AGENT
CONCRETE
SLAB-ON-GRADE
#4 AT 1'-0" OC EACH WAY
EQUIPMENT PAD
3/4" CHAMFER
(TYPICAL)
2" C
LE
A
R
4"
NOTES:
1. SLAB-ON-GRADE SHOWN. DETAIL SIMILAR AT ELEVATED SLAB.
2. IN LIEU OF ROUGHENING SURFACE AND APPLYING EPOXY BONDING AGENT,
CONTRACTOR MAY DRILL AND EPOXY #4 DOWELS AT 16" OC AROUND
PERIMETER EDGE OF PAD. DO NOT CUT SLAB-ON-GRADE REINFORCEMENT.
45°
4" 1"
NOTE '2'
CONTINUOUS WALL FOOTING
T Y
P
IC
A L
2'
0"
BETWEEN BARS, TYP
3" OC SPACINGSLAB OR WALL
REINFORCEMENT, REFER
TO PLAN OR SCHEDULE
1-#5 EACH FACE FOR
WALLS, 1-#5 TOP AND
BOTTOM FOR SLABS
1-#5 EACH FACE FOR WALLS, 1-#5
TOP AND BOTTOM FOR SLABS
AT EACH SIDE OF SLAB OR
WALL OPENING ADD 1/2 OF
REINFORCEMENT INTERRUPTED
BY OPENING
ADDED REINFORCEMENT AT OPENINGS
IN CONCRETE SLAB OR WALL WHERE
MAIN REINFORCING IS NOT INTERRUPTED
ADDED REINFORCEMENT AT OPENINGS
IN CONCRETE SLAB OR WALL WHERE
MAIN REINFORCEMENT IS INTERRUPTED
SLAB OR WALL REINFORCEMENT
INTERRUPTED BY OPENING
NOTES:
1. COORDINATE OPENING SIZE AND
LOCATION WITH ARCHITECTURAL,
MECHANICAL, AND ELECTRICAL
DWGS.
2. NO SPECIAL REINFORCEMENT
REQUIRED FOR OPENINGS 4" OR
LESS.
3. REINFORCEMENT FOR ROUND
OPENINGS SIMILAR.
TYPICAL
2" CLEAR,
TY
P
IC
A
L 2"
C
LE
A R
TYPIC
AL2'
- 0
LA
P
T Y
P
IC
A L
C
LA
S S
'B
2" CLEAR
TYPICAL
2' - 0"
AT CONSTRUCTION JOINTS AT SAWCUT JOINTS
PREVIOUS POUR SUBSEQUENT POUR
JOINT CENTERLINE
END OF REINFORCING
1/8" WIDE X T/4 DEEP INITIAL
SAWCUT BEFORE SUBSEQUENT
CUT FOR JOINT FILLER
CRACK ALONG SAWCUT
1.
2.
NOTES:
JOINT DETAILS ARE SHOWN FOR CONSTANT THICKNESS NON-SLOPING SLAB. DETAILS ARE SIMILAR AT AREAS WITH VARIABLE THICKNESS AND SLOPING SLABS.
JOINT FILLER: SAWCUT GAP ALONG DOWELED JOINTS TO CREATE JOINT FILLER GAP 1/4" MINIMUM TO 3/8" MAXIMUM WIDE X DEPTH REQUIRED FOR FILLER.
AFTER SAW CUTTING, APPLY THIN LAYER OF CLEAN DRY SILICA SAND AT BOTTOM OF GAP TO PREVENT RUN OUT FROM CRACKS AT BOTTOM OF JOINTS. FILL REMAINDER OF SAWCUT GAPS WITH SEMI-RIGID EPOXY JOINT FILLER. STRIKE OFF LEVEL WITH TOP OF SLAB.
SAWCUT GAP FILLED WITH
JOINT FILLER / SEALANT
SAWCUT GAP FILLED WITH
JOINT FILLER / SEALANT
T /4
T
1/
2" C
O V
E R
U
N O
APPLY CURING COMPOUND
TO FACES OF PREVIOUS
POUR TO PREVENT BONDING
2" 2"
1-1/4" DIA X 1'-6" LONG SMOOTH,
GREASED STEEL DOWEL AT 12" ON
CENTER. LOCATE CENTERLINE OF
FIRST DOWEL 6" FROM END OF JOINT.
2" 2"
END OF REINFORCING
JOINT CENTERLINE
1-1/4" DIA X 1'-6" LONG SMOOTH,
GREASED STEEL DOWEL AT 12" ON
CENTER. LOCATE CENTERLINE OF
FIRST DOWEL 6" FROM END OF JOINT.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/3
/2
:0
:3
P
M
C U s e rs \m ig u e l.
w a lk e r\
D o c u m e n ts \P
-1
-S -R
-F O
R K
L
IF
T m ig u e l.
w a lk e r.
rv t
S-501B
T Y
P
IC
A L D
E T
A
IL
S
CWJ
12942157
DOB MTW
03/26/2026
F O
R K
L
IF
T C
H A
R G
IN
G
S T
A T
IO
N
MMP/SLC
1737010
Y O
R K
T O
W N
V
IR
G
IN
IA
N A
V A
L W
E A
P O
N S
S T
A T
IO
N
JWJ
NEK
HPN
M
ID
L A
N T
D C
C O
R E
S -5
B
P W
E A
P O
N M
A G
A Z
IN
E
S
Approved by LCDR VINCE DEL GRECO, ROICC with PWD
YORKTOWN, via Email.
NOT TO SCALE
B1
TYPICAL FOOTING DETAILS
NOT TO SCALE
A1
TYPICAL SLAB-ON-GRADE DETAILS
NOT TO SCALE
B3
TYPICAL CONCRETE SLAB AND WALL OPENING
NOT TO SCALE
C3
DOWELED JOINTS
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
CORNER
CONTROL JOINTOPENING - WALL TERMINATION
CONTROL JOINT, REFER TO
[ARCHITECTURAL] DRAWINGS
FOR LOCATIONS AND DETAILS
VERTICAL WALL
REINFORCEMENT,
SAME SIZE AS TYPICAL
VERTICAL WALL
REINFORCEMENT,
SAME SIZE AS TYPICAL
TYPICAL WALL SEGMENT
TO PLAN OR SCHEDULE
TYPICAL SPACING, REFER
TYPICAL VERTICAL
REINFORCEMENT,
REFER TO PLAN OR
SCHEDULE FOR
SIZE
VERTICAL WALL
REINFORCEMENT,
SAME SIZE AS
TYPICAL
NOTES:
1. REINFORCEMENT IS CONTINUOUS
FOR FULL HEIGHT OF WALL, UNLESS
OTHERWISE NOTED.
2. REINFORCEMENT SHOWN IS THE
MINIMUM AT EACH GIVEN LOCATION.
REFER TO PLANS, SECTIONS, AND
OTHER DETAILS FOR ADDITIONAL
REINFORCEMENT, IF REQUIRED.
3. REINFORCEMENT IS CENTERED IN
CELLS UNLESS OTHERWISE NOTED.
4. HORIZONTAL JOINT AND BOND BEAM
REINFORCEMENT IS NOT SHOWN FOR
CLARITY.
NOT AT CONTROL JOINT
LINTEL, REFER TO
SCHEDULE FOR SIZE
AND REINFORCING
(D=16" SHOWN)
WALL REINFORCEMENT
AT OPENING
0' ― 3' - 4"
BOND BEAM LINTEL SCHEDULE
8" (2) #48"
SECTION ('D' = 8")
TYPICAL VERTICAL
REINFORCEMENT
BEYOND IN FULLY
GROUTED CELLS
ABOVE OPENING (IF
SPACING IS LESS
THAN CLEAR SPAN)
BOTTOM
REINFORCEMENT IN
FULLY GROUTED
LINTEL BLOCK
CLEAR SPAN
DEPTH
'D'
REINFORCEMENTWIDTH
'W'
3' - 5" ― 6' - 4" 16" (2) #48"
6' - 5" ― 10' - 8" 24" (2) #512"
KNOCK-OUT
WEB BLOCK
BOTTOM TOP
N/A
(2) #4
(2) #5
[REFER TO ARCH]
BOTTOM OF LINTEL
NOTE:
VENEER MASONRY AND
SUPPORT NOT SHOWN
FOR CLARITY.
SECTION ('D' > 8")
TOP REINFORCEMENT
IN 8" HIGH KNOCK-OUT
WEB BLOCK AT TOP OF
LINTEL
BOTTOM
REINFORCEMENT IN 8"
HIGH LINTEL BLOCK
FIRST COURSE ABOVE
OPENING
KNOCK-OUT WEB
BLOCK BETWEEN TOP
AND BOTTOM
COURSES (SLOT
LENGTH HALF DEPTH
MINIMUM)
C
LE
A R
1/
2"
'W'
'D
'W'
G R
O U
T S
O
LI
D 'D
C
LE
A R
1/
2"
FREE STANDING
HSS6.625X0.280, FILL
BOLLARD WITH 4000
PSI CONCRETE
CONCRETE FOOTING3'
6" 4'
0"
3'
0"
18" DIA MIN
1" CROWN AT EXTERIOR
BOLLARDS ONLY
PAINTED YELLOW
FINISH GRADE
PLAN
2"
SQUARE
1' - 2"
1/4
HSS BOLLARD
BASE PL1 WITH STANDARD HOLES
FOR (4) POST-INSTALLED ANCHORS
BASE PLATE / HSS
CENTERLINES
ANCHOR
CENTERLINES
NOTE:
POST-INSTALLED ANCHORS ARE
1"Ø THREADED RODS SET IN
CONCRETE WITH ADHESIVE.
2" TYP
M
IN
1'
0"
4'
0"
GALVANIZED HSS6.625X0.280
FILLED WITH CONCRETE
GROUND FLOOR SLAB OR
SITE PAVEMENT
CONCRETE FOUNDATION -
REINFORCING NOT SHOWN
1/
2"
DOME TOP OF CONCRETE FILL
BOLLARD CENTERLINE -
REFER TO PLAN
TOP OF HSS
NOTE:
COORDINATE FOUNDATION
REINFORCING PLACEMENT TO
AVOID CUTTING REINFORCING
DURING POST-INSTALLED
ANCHOR INSTALLATION.
POST-INSTALLED
ANCHORS
NOTE:
SLAB AND PAVEMENT
REINFORCING NOT SHOWN.
ADJUST REINFORCING
PLACEMENT TO MAINTAIN
CONCRETE COVER AND AVOID
INTERRUPTING REINFORCING.
AT OVERHEAD DOORS (INTERIOR AND EXTERIOR)
1/
2"
DOME TOP OF
CONCRETE FILL
M
IN6"
MIN
1' - 0"
EDGE OF FOOTING
1"
3" C
LR
3"
C
LR
C
M U
1' - 4"
(2) #5 VERTICAL BARS
EACH FACE WITH
MATCHING DOWELS
OVERHEAD DOOR
C
M U
3" 3"
C
LR
(2) #5 VERTICAL BARS
EACH FACE WITH
MATCHING DOWELS
OVERHEAD DOOR
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/3
/2
:0
:3
P
M
C U s e rs \m ig u e l.
w a lk e r\
D o c u m e n ts \P
-1
-S -R
-F O
R K
L
IF
T m ig u e l.
w a lk e r.
rv t
S-502B
T Y
P
IC
A L D
E T
A
IL
S
CWJ
12942158
DOB MTW
03/26/2026
F O
R K
L
IF
T C
H A
R G
IN
G
S T
A T
IO
N
MMP/SLC
1737010
Y O
R K
T O
W N
V
IR
G
IN
IA
N A
V A
L W
E A
P O
N S
S T
A T
IO
N
JWJ
NEK
HPN
M
ID
L A
N T
D C
C O
R E
S -5
B
P W
E A
P O
N M
A G
A Z
IN
E
S
Approved by LCDR VINCE DEL GRECO, ROICC with PWD
YORKTOWN, via Email.
NOT TO SCALE
C1
TYPICAL CONCRETE MASONRY WALL VERTICAL REINFORCEMENT
NOT TO SCALE
C3
TYPICAL CONCRETE MASONRY BOND BEAM LINTEL
NOT TO SCALE
A1
TYPICAL BOLLARD DETAILS
NOT TO SCALE (S-101B)
A3
REINFORCING AT FRONT DOOR JAMBS
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
DOOR NUMBER
(REFER TO DOOR SCHEDULE)
DOOR TAG
ARCHITECTURAL SYMBOLS
WINDOW TYPE LETTER
WINDOW TYPE TAG
SPECIALITY ITEM NUMBER
SPECIALITY ITEM TAG
PARTITION TYPE DESIGNATION
(REFER TO PARTITION SCHEDULE)
PARTITION TYPE TAG
PARTITION IN PLAN
ROOM
A1 A-301
ROOM TAG
DETAIL NUMBER
SHEET WHERE DRAWN
DETAIL TAG
ROOM NAME
ROOM NUMBER
A-401 INTERIOR ELEVATION
TAG
INTERIOR ELEVATION NUMBER
SHEET WHERE DRAWN
EXTERIOR ELEVATION
TAG
ELEVATION NUMBER
DIRECTION OF VIEW
SHEET WHERE DRAWN
A1 A-301
WALL / PARTIAL
BUILDING SECTION
TAG
SECTION NUMBER
SHEET WHERE DRAWN
A1 A-301
BUILDING SECTION
TAG
SECTION NUMBER
SHEET WHERE DRAWN
A1 A-301
BUILDING
KEYNOTE TAG
KEYNOTE NUMBER
A-901 PHOTOGRAPH TAG
PHOTOGRAPH NUMBER
SHEET WHERE SHOWN
A1
A-501
A1
A1
A1
B
A1
PLAN
NORTH
GRID NORTH
MATERIALS LEGEND
CONCRETE MASONRY UNIT (CMU)
CAST-IN-PLACE CONCRETE
STEEL
RIGID INSULATION
WOOD - ROUGH
WOOD BLOCKING
CMU
SECTION ELEVATION
EARTH / COMPACT FILL
POROUS FILL / GRAVEL
ALUMINUM
FACING MASONRY
PLYWOOD
SAND / MORTAR / PLASTER
CONCRETE
CMU, GROUT SOLID
NON-COMBUSTIBLE BOARD INSULATION
CONCRETE, CEMENT GROUT
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D
EP
AR
TM
EN
T
O F
TH
E
N
AV
Y N
AV
AL
F
AC
IL
IT
IE
S
EN
G
IN
EE
R
IN
G S
YS
TE
M S
C O
M M
AN
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L F
AC
ILI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
MS
C
OM
MA
ND
MI
D-
AT
LA
NT
IC
N
AV
AL
S
TA
TI
O N
N
O R
FO
LK
, V A
AS NOTED
4/ 1/
2:
:4
PM
C :\R ev it
Lo ca l F ile s\ P1
-1
-A
-R
-F O
R
KL
IF
T_ ga re th .ra tti .rv t
A-001B
AR
C
H
IT
EC
TU
R
AL
, A
BB
R
EV
IA
TI
O N
S, N
O
TE
S
AN
D S
YM
BO
LS
JEL
12942161
GJR GJR
03/26/2026
FO
R
KL
IF
T C
H
AR
G
IN
G S
TA
TI
O N
MME/WJW
1737010
YO
R
KT
O
W N
, V
IR
G
IN
IA
N
AV
AL
W
EA
PO
N
S
ST
AT
IO
N
JWJ
DJD
HPN
M
ID
LA
N
T D
C C
O R
E
A-
1B
P1
W
EA
PO
N
M
AG
AZ
IN
ES
Approved by LCDR VINCE DEL GRECO, ROICC with PWD
YORKTOWN, via Email, SIM SIMILAR
SPC SUSPENDED PLASTER CEILING
SPEC SPECIFICATION
SQ SQUARE
STD STANDARD
STOR STORAGE
STR STRAIGHT STRIKE / STRINGERS
SUSP SUSPENDED
T&B TOP AND BOTTOM
TEL TELEPHONE
THRES THRESHOLD
THRU THROUGH
TOS TOP OF SLAB / STEEL
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
V VOLT
VAR VARIATION
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VENT VENTILATION / VENTILATOR
VERT VERTICAL
VEST VESTIBULE
VS VENT STACK
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W WASTE / WATT / WEST / WIDE
W/ WITH
W/O WITHOUT
WC WATER CLOSET / WALL COVERING
WD WOOD
WH WATER HEATER
WP WATERPROOFING / WEATHERPROOF / WORKING
POINT
WSCT WAINSCOT
WT WEIGHT
WWF WELDED WIRE FABRIC
XRMR TRANSFORMER
OC ON CENTER
OD OUTSIDE DIAMETER / DIMENSION
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OPT OPTIONAL
PCT PERCENT
PEJ PREMOLDED EXPANSION JOINT
PL PROPERTY LINE
PLAS PLASTER / PLASTIC
PLYWD PLYWOOD
PNL PANEL
PRELIM PRELIMINARY
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT
QT QUARRY TILE
R RADUIS / RISER
RA RETURN AIR
RAD RETURN AIR DUCT
RB RESILIENT BASE
RD ROOF DRAIN / ROAD
REFL REFLECT
REFR REFRIGERATION
REINF REINFORCE
REQD REQUIRED
REV REVISION
RF RESILIENT FLOORING
RL ROOF LEADER
RM ROOM
RND ROUND
RO ROUGH OPENING
RS ROUGH SAWN
RT RIGHT
S SOUTH
SAPC SUSPENDED ACOUSTICAL PANEL CEILING
SCHED SCHEDULE
SECT SECTION
SF SQUARE FOOT
SH SHINGLES / SINGLE HUNG
GA GAUGE
GALV GALVANIZED
GFCI GOVERNMENT FURNISHED CONTRACTOR INSTALLED
GL GLASS / GROUND LEVEL
GR GROSS
GSU GLAZED STRUCTURAL UNIT
GYP GYPSUM
H HIGH
HB HOSE BIB
HDW HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HT HEIGHT
HVY HEAVY
ID INSIDE DIAMETER
INSUL INSULATION / INSULATED
INT INTERIOR
J-BOX JUNCTION BOX
JAN JANITOR CLOSET
LAV LAVATORY
LB POUND
LT LIGHT
MACH MACHINE
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFG MANUFACTURING
MIN MINIMUM / MINUTE
MISC MISCELLANEOUS
ML MATCH LINE
MO MASONRY OPENING / MOTOR OPERATED
MTD MOUNTED
MTG MOUNTING / MEETING
MTL METAL
MWP MEMBRANE WATERPROOFING
N NORTH
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OUTSIDE AIR
CPT CARPET / COMMON PATH OF TRAVEL
CT CERAMIC TILE
CTR CENTER
D DEPTH / DEEP
DEG DEGREE
DEMO DEMOLITION
DET DETAIL
DIA DIAMETER
DIM DIMENSION
DR DRAIN
DS DOWNSPOUT
DW DISHWASHER
DWG DRAWING
E EAST
EA EACH
EIFS EXTERIOR INSULATION & FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRIC / ELECTRICAL
EPDM ETHLENE PROPYLENE DIEN MONOMER
EQ EQUAL
EQUIP EQUIPMENT
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXH EXHAUST
EXIST EXISTING
EXP EXPANSION / EXPOSED / EXPAND
EXT EXTERIOR
FD FLOOR DRAIN
FDTN FOUNDATION
FF FINISH FACE
FG FIGURE
FHC FIRE HOUSE CABINET
FIN FLR FINISHED FLOOR
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF STUB / FACE OF SLAB
FR FRAME / FIRE RATING / FIRE RESISTANT
FT FOOT, FEET
FTG FOOTING
AB ANCHOR BOLT
ACS PNL ACCESS PANEL
ADJ ADJUST
ALT ALTERNATE, ALTITUDE
ALUM ALUMINUM
ANOD ANODIZED
APPROX APPROXIMATE
ARCH ARCHITECT
ASPH ASPHALT
ATC ACOUSTICAL TILE CEILING
BD BOARD
BLDG BUILDING
BLW BELOW
BM BEAM
BOS BOTTOM OF SLAB / STEEL
BOT BOTTOM
BRG BEARING
BSMT BASEMENT
BTWN BETWEEN
C TO C CENTER TO CENTER
CAB CABINET
CEM CEMENT
CER CERAMIC
CI CAST IRON
CIP CAST IRON PIPE
CJ CONTROL / CONSTRUCTION JOINT
CLG CEILING
CLG REG CEILING REGISTER
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CND CONDUIT
CNDS CONDENSATE
CNSTR CONSTRUCTION
CNTR CNTR
CO CLEANOUT
COL COLUMN
CONC CONCRETE
CONN CONNECT
CONT CONTINUE / CONTINUOUS
CORR CORRIDOR
ARCHITECTURAL ABBREVIATIONS
GENERAL NOTES
A. ITEMS INDICATED TO BE REMOVED MUST BE DISPOSED OF OFF SITE
UNLESS OTHERWISE NOTED.
B. PROVIDE NEW MATERIALS UNLESS SPECIFICALLY NOTED EXISTING,
FURNISHED BY THE GOVERNMENT, OR PROVIDED BY THE GOVERNMENT.
C. WOOD BLOCKING AND MISCELLANEOUS STEEL SHOWN IN DETAILS AND
SECTIONS MUST BE CONTINUOUS UNLESS SPECIFICALLY NOTED
OTHERWISE.
D. VERIFY FIELD CONDITIONS AND DIMENSIONS PRIOR TO PROCEEDING
WITH THE WORK. PROVIDE IMMEDIATE WRITTEN NOTIFICATION TO THE
CONTRACTING OFFICER OF ANY DISCREPANCIES.
E. DEMOLITION OF PLUMBING, MECHANICAL AND ELECTRICAL ITEMS
INDICATED ON THE ARCHITECTURAL DRAWINGS IS NOT INTENDED TO
INCLUDE ALL NECESSARY DEMOLITION WORK FOR THESE ITEMS. REFER
TO PLUMBING, MECHANICAL AND ELECTRICAL DEMOLITION DRAWINGS
FOR ADDITIONAL INFORMATION.
F. DIMENSIONS INDICATED FOR THE WORK ARE TO FACE OF STUD, FACE OF
MASONRY OR FACE OF EXISTING SURFACES…
This is the start of the file's text. The full file is on GovTribe.