This file is a building code analysis and life safety design document for segregation facilities at Naval Weapons Station Yorktown, Virginia, prepared as part of Design-Bid-Build Project P171 Weapons Magazines. The document establishes applicable codes, standards, and design criteria for a single-story Type II-A construction facility with a building height of 24'-8" and total area of 9,244 square feet.
The facility must comply with UFC 1-200-01, UFC 3-600-01, ICC International Building Code 2018, NFPA 13 (sprinkler systems), NFPA 72 (fire alarm), and NFPA 70 (electrical code). Fire resistance ratings require 1-hour protection for structural frames, bearing walls, and floor/roof construction. The building houses high-hazard industrial use (Group H-1) segregation areas along with business use (Group B) office and collaboration spaces, requiring a 2-hour occupancy separation per UFC 3-600-01. The facility is designed for a calculated occupant load of 32 persons with maximum probable occupancy of 14 persons in high-hazard areas and 5 persons in business areas. Life safety egress analysis confirms eight exits with total capacity of 800 persons, exceeding required capacity. Travel distance requirements are satisfied with common path of travel at 59'-6" to 67'-0" (maximum allowable 100 feet) and total travel distances of 54'-0" to 71'-0" (maximum allowable 75 feet). The design incorporates sprinklered systems allowing reduced travel distances per Life Safety Code requirements. The document also references ammunition and explosives safety standards (NAVSEA OP-5 and DES REG 6055.09) and includes detailed specifications for concrete construction, reinforcement, and structural materials.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPLICABLE CODES, STANDARDS, AND DESIGN CRITERIA
STANDARD TITLE REVISION DATE NOTES
UFC 1-200-01 GENERAL BUILDING REQUIREMENTS 01 OCTOBER 2020 --
UFC 3-600-01* FIRE PROTECTION ENGINEERING FOR FACILITIES 12 AUGUST 2020 --
ICC INTERNATIONAL BUILDING CODE(IBC) 2018 APPLICABLE CHAPTERS PER UFC
1-200-01; MEANS OF EGRESS MUST
BE BASED UPON THE LIFE SAFETY
CODE
NFPA 13 STANDARD FOR THE INSTALLATION OF SPRINKLER
SYSTEMS
2019 --
--NFPA 72 NATIONAL FIRE ALARM SIGNALING CODE 2019
NFPA 70 NATIONAL ELECTRICAL CODE (NEC) 2020
NOTES
STRUCTURAL FRAME, INCLUDING COLUMNS,
GIRDERS, TRUSSES
BUILDING ELEMENT HOURLY RATING
REQ'D
TYPE II-A
PROVIDED
EXTERIOR BEARING WALLS
INTERIOR BEARING WALLS
NONBEARING WALLS AND PARTITIONS
EXTERIOR WALLS
*NOT LESS THAN THE FIRE RESISTANCE
RATING BASED ON THE FIRE SEPARATION
DISTANCE FROM BUILDING 235
(SEE IBC TABLE 602)
*NOT LESS THAN THE FIRE RESISTANCE
RATING BASED ON THE FIRE SEPARATION
DISTANCE FROM BUILDING 235
(SEE IBC TABLE 602)
FLOOR CONST. INCLUDING SUPPORTING
BEAMS AND JOISTS
ROOF CONSTRUCTION INCLUDING
SUPPORTING BEAMS AND JOISTS
EXIT ENCLOSURES NOT APPLICABLE
TYPE II-A FIRE RESISTANCE RATINGS (IN HOURS) OF STRUCTURAL ELEMENTS
1 1
1 1
1 1
0 0
1 1
1 1
1 1
SHAFT ENCLOSURES 1 1
ADDITIONAL FIRE RESISTIVE RATED CONSTRUCTION REQUIREMENTS
NOTESBUILDING
ELEMENT/HAZARD
DESCRIPTION
HOURLY RATING
REQ'D ICC PROVIDED
OCCUPANCY CLASSIFICATIONS
SEGREGATION AREA
LSC
HIGH HAZARD
USE GROUP H-1
DESCRIPTION OF AREA
IBC
HIGH HAZARD-INDUSTRIAL
(CHAPTER 40)
OCCUPANCY CLASSIFICATIONS
OCCUPANT LOAD FACTOR
(FT2/PER PERSON)
150 GROSS
USE
BUSINESS
INDUSTRIAL - SPECIAL PURPOSE, HIGH HAZARD MAXIMUM PROBABLE NUMBER - TABLE 7.3.1.2 - "MP"
APPLICABLE OCCUPANT LOAD FACTORS - LSC TABLE 7.3.1.2
OFFICE
PLANNING ROOM
BUSINESS
INDUSTRIAL - SPECIAL
PURPOSE - HIGH HAZARD
MAXIMUM PROBABLE
NUMBER
LSC CALCULATED BUILDING OCCUPANT LOAD 32
AREA OCCUPANCY APPROX. AREA OCCUPANT LOAD
FACTOR
OCCUPANT LOAD
FIRST FLOOR
NUMBER OF EXITS AND CAPACITY
FLOOR LEVEL
FIRST FLOOR
REQUIRED
EXIT CAPACITY
AVAILABLE
EXIT CAPACITY
NUMBER OF
EXITS REQUIRED
NUMBER OF
EXITS PROVIDED
28" 4 - 36" WIDE DOORS
CLEAR WIDTH - 32"
TOTAL - 128"
2 (LSC- 7.11.4) 4
CALCULATED OCCUPANT LOADS PER LSC - SECTION 7.3.1
FLOOR, ROOM OR
SPACE DESIGNATION
MINIMUM
NUMBER OF EXITS
TRAVEL DISTANCE
FIRST FLOOR
(BUSINESS)
REQUIRED SHOWN
ON PLAN
ALLOWABLE TRAVEL
DISTANCE (LSC)
ARRANGEMENT MEANS
OF EGRESS
ACTUAL TRAVEL
DISTANCE SHOWN ON
PLANS
REQ'D DISTANCE
BETWEEN EXIT
DOORS
ACTUAL DISTANCE
SHOWN ON PLANS
1 1 100 FT 60 FT ONE EXIT - N/A
LSC - 38.2.4.2
N/A
2 4 100 FT 57 FT 127'/3=43 FT 74 FT & 52 FT
COMMON PATH OF TRAVEL
• SPRINKLERED BUSINESS OCCUPANCIES (LSC 38.2.5)
• SPRINKLERED HIGH HAZARD INDUSTRIAL (LSC 40.2.5.1)
100 FEET
NOT PERMITTED
60 FEET
NONE
DEAD END PATH OF TRAVEL
• SPRINKLERED BUSINESS OCCUPANCIES (LSC 38.2.5)
• SPRINKLERED HIGH HAZARD INDUSTRIAL (LSC 40.2.5.1 & 7.11.4)
50 FEET
NOT PERMITTED
18.5 FEET
NONE
TOTAL TRAVEL DISTANCE
• SPRINKLERED BUSINESS OCCUPANCIES (LSC 38.2.4.2)-SINGLE EXIT
• SPRINKLERED HIGH HAZARD INDUSTRIAL STORAGE (LSC 40.2.5.1)
100 FEET
75 FEET
60 FEET
57 FEET
BUILDING CODE AND LIFE SAFETY ANALYSIS
COMMON PATH, DEAD END, & TOTAL TRAVEL DISTANCE ANALYSISREQUIRED ACTUAL
TRAVEL DISTANCE REQUIREMENT
MEANS OF EGRESS SUMMARY
NFPA 10 PORTABLE FIRE EXTINGUISHERS 2018 --
NFPA 101 LIFE SAFETY CODE (LSC) 2018NFPA 90A STANDARD FOR THE INSTALLATION OF AIR-
CONDITIONING AND VENTILATING SYSTEMS
NFPA 101 LIFE SAFETY CODE (LSC) 2018
NOT APPLICABLE
FIRST FLOOR
(HIGH HAZARD)
SEGREGATION
214 30 8
500 GROSSSTORAGE, ORDINARY HAZARD
OFFICE BUSINESS
USE GROUP B
BUSINESS
(CHAPTER 32)
H-1 / B OCCUPANCY SEPARATION 2 HR UFC 3-600-01 - 4-5.4.32 HR
NAVSEA OP-5 AMMUNITION AND EXPLOSIVES SAFETY ASHORE EIGHTH REVISION10 MARCH 2023
DES REG 6055.09 DEFENSE EXPLOSIVES SAFETY REGULATION EDITION 1JANUARY 13, 2019
* UFC 3-600-01 GENERALLY REQUIRES CONSTRUCTION ISSUES TO COMPLY WITH IBC CRITERIA AND LIFE SAFETY/EGRESS ISSUES TO MEET THE REQUIREMENTS OF LSC. CONFLICTS BETWEEN THE IBC AND LSC RELATED TO FIRE RESISTANCE ARE REQUIRED TO COMPLY WITH LSC
CRITERIA AND APPLICABLE PROVISIONS OF THE UFC CODE (UFC 3-600-01 § 2-1.1).
BUILDING DESCRIPTION
TYPE OF CONSTRUCTION II-A
NUMBER OF STORIES 1
BUILDING HEIGHT 24'-8"
NUMBER OF
STORIES
OCCUPANCY
AND USE
(A)
BLDG AREA PER
STORY (ACTUAL)
1 H-1
(B)
TABLE 506.2 AREA
(PER STORY)
(C)
AREA FOR FRONTAGE
INCREASE (100% OPEN)
(E)
ALLOWABLE AREA
9,244 11,000 8,250 19,250 (PER STORY)
TOTAL -- 9,244 -- -- 19,250
ALLOWABLE AREA FOR NEW CONSTRUCTION (TYPE II-A)
ALLOWABLE HEIGHT (TYPE II-A)
ALLOWABLE
(TABLE 504.3)
BUILDING HEIGHT 65'-0"
ACTUAL
24'-8"
NUMBER OF STORIES 1 1
FIRE RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS OF TYPE II-A
BUILDING BASED ON FIRE SEPARATION DISTANCE (IBC TABLE 602)
FIRE SEPARATION DISTANCE (FSD) TO LOT
LINE
USE GROUP H-1
FSD < 5 FT
5 FT ≥ FSD < 10 FT
10 FT ≥ FSD < 30 FT
2 HR
3 HR
1 HR
FSD ≥ 30FT 0 HR
30 GROSSBUSINESS COLLABORATION ROOM ( ≤ 450 FT²)
SECURE STORAGE
BUSINESS/
COLLABORATION
STORAGE 447 500 1
MECH/ELEC SUPPORT UNOCCUPIED 517 4
MECHANICAL, TELECOM, ELECTRICAL SUPPORT MAXIMUM PROBABLE NUMBER - TABLE 7.3.1.2 - "MP"
MAXIMUM PROBABLE
NUMBER
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
CUI
CUI
C U
I
/3
/2
:2
:3
A
M
C
U s e rs \d a v id
.h a d d o c k \D o c u m e n ts
\P
-1
-F
-R
-S
E G d a v id
.h a d d o c k .r v t
GI001A
B U
IL
D
IN
G
C O
D E
A N
A L Y
S
IS
SSR
12942039
KEK DMH
S E
G R
E G
A T
IO
N
F A
C
IL
IT
IE
S
MMP/SLC
1737010
Y O
R K
T O
W N
V
IR
G
IN
IA
N A
V A
L W
E A
P O
N S
S T
A T
IO
N
JWJ
CGM
HPN
M
ID
L A
N T
D C
C O
R E
G I0
A
P W
E A
P O
N M
A G
A Z
IN
E
S
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
ACTIVITY
Approved by LCDR VINCE DEL
GRECO, ROICC with PWD YORKTOWN, via Email, U.C.
Wine
REF.
ROOM / ZONE AREA (SF)
OCCUPANCY, ALLOWABLE
AREA PER OCCUPANT OCCUPANCY LOAD (PEOPLE)
OCCUPANCY, TYPE
SEE OCCUPANCY HATCH
LEGEND
1500 B
150 10
2 HOUR FIRE BARRIER
SYMBOL DESCRIPTION
COMMON PATH OF TRAVEL
TRAVEL DISTANCE
TD
XX' - XX"
DEAD -END CORRIDOR
DE
XX' - XX"
34 0.2
CP
XX' - XX"
EXIT WIDTH PER PERSON
ACTUAL EGRESS (PEOPLE)
EXIT ID NUMBER
MAX EXIT CAPACITY (PEOPLE)
NET EXIT WIDTH (INCHES)
B
A
1 2 5 6 8
C
D
E
F
TD4
69' - 6"
CP2
67' - 0"
TD1
70' - 6"
TD5
71' - 0"
TD2
54' - 0"
TD3
67' - 0"
CP1
59' - 6"
32 0.2
32 0.4
32 0.4
32 0.4
B
MP
SP-1
MP
UO
A B
C
ABC
A B
C
ABC
ABCABC
A B
C
ABC
ABC ABC ABC ABC
OPEN OFFICE
SHOP LEAD
104 CORRIDOR
MOTHERS
ROOM
TOILET
TOILET
109 PLANNING ROOM
VESTIBULE
OPEN
SEGREGATION
AREA B
SEGREGATION
CELL B
SEGREGATION
CELL A
CONTAINER
TRANSFER
BAY A
SPRINKLER
ROOM
MECHANICAL
ROOM
ELECTRICAL
ROOM
AIR
FORKLIFT
CHARGING
SECURE TOOL
ROOM B
GENERAL
STORAGE
STOR.
DE1
18' - 6"
CUSTODIAN
SERVER
GENERAL
STORAGE
SECURE TOOL
ROOM A
S
B/C
32 0.4
64 0.4
32 0.4
32 0.4
73' - 6"
126' - 10"
51' - 10"
OCCUPANCY HATCH LEGEND
OCCUPANCY USEMARK
BUSINESS (B)
SPECIAL PURPOSE -
INDUSTRIAL * (SP-I)
STORAGE - ORDINARY (S)
* CLASS II, DIV 1 ELECTRICAL CLASSIFICATION
BUSINESS -
COLLABORATION (B-C)
UO = UNOCCUPIED
MP = MAXIMUM PROBABLE
NUMBER
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
CUI
CUI
C U
I
/3
/2
:2
:3
A
M
C
U s e rs \d a v id
.h a d d o c k \D o c u m e n ts
\P
-1
-F
-R
-S
E G d a v id
.h a d d o c k .r v t
GI101A
F L O
O R
P L A
N
L
IF
E S
A F
E T
Y
SSR
12942041
KEK DMH
S E
G R
E G
A T
IO
N
F A
C
IL
IT
IE
S
MMP/SLC
1737010
Y O
R K
T O
W N
V
IR
G
IN
IA
N A
V A
L W
E A
P O
N S
S T
A T
IO
N
JWJ
CGM
HPN
M
ID
L A
N T
D C
C O
R E
G I1
A
P W
E A
P O
N M
A G
A Z
IN
E
S
GENERAL NOTES
LIFE SAFETY LEGEND
KEY NOTES
GRAPHIC SCALE(S)
1/8" = 1' - 0" 0 5' 10' 15' 30'
TRAVEL DISTANCE SUMMARY
ID ACTUAL MAXIMUM
CP1 59' - 6" 100'
CP2 67' - 0" 100'
DE1 18' - 6" 50'
TD1 70' - 6" 75'
TD2 54' - 0" 75'
TD3 67' - 0" 75'
TD4 69' - 6" 75'
TD5 71' - 0" 75'
EXIT CAPACITY SCHEDULE
EXIT
NUMBER
NET CLEAR
EXIT WIDTH
(INCHES)
EXIT WIDTH PER
PERSON (EGRESS
FACTOR)
EXIT
CAPACITY
(PEOPLE)
ACTUAL
PERSONS
USING EXIT
1 32 0.2 160 22
2 32 0.4 80 2
3 32 0.4 80 2
4 32 0.4 80 1
5 64 0.4 160 1
6 32 0.4 80 1
7 32 0.4 80 1
8 32 0.4 80 2
TOTAL 800 32
1/8" = 1'-0" A1
FLOOR PLAN - LIFE SAFETY
A. FOR BUILDING CODE ANALYSIS REFER TO G001A
B. FOR CODE COMPLIANCE SITE PLAN REFER TO G100A
C. INFORMATION PROVIDED APPLIES TO BOTH SEGREGATION BUILDING
LOCATIONS
1. FACU
PLAN
NORTH
PLAN
NORTH
BLDG 1 BLDG 2
ABC
DRY CHEMICAL EXTINGUISHER - ABC TYPE
4A:80B:C UL RATED 10 LB EXTINGUISHER
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
CBAAXBB CONCRETE BEAM MARK
AA=WIDTH
BB=DEPTH
CPCAAXBB CONTINUOUS PILE CAP MARK
AA=WIDTH
BB=DEPTH
CCAAXBB CONCRETE COLUMN MARK
AA=WIDTH
BB=DEPTH
CWXX CONCRETE WALL MARK
XX=WALL WIDTH
PCX PILE CAP MARK
X=NUMBER OF PILES
TYP TYPICAL
X GRID MARK
WORK NOTE
TOSYY X' - X" TOP OF SLAB
CAST-IN-PLACE CONCRETE
COMPACTED SUBGRADE
POROUS FILL / STONE
BASE COURSE
XXX
XXX-TPY
PILE LOCATION
XXX=PILE NUMBER
TEST PILE LOCATION
XXX=PILE NUMBER
Y=TEST PILE NUMBER
GROUND FLOOR SLAB
JOINT - TYPE INDICATED
ON PLAN
TOPYY X' - X" TOP OF PARAPET
MASONRY VENEER
YY = HR FOR HIGH ROOF SLAB/PARAPET
YY = LR FOR LOW ROOF SLAB/PARAPET
YY = CR FOR CANOPY ROOF
DPX DROP PANEL MARK
X = WIDTH IN FEET
UNO UNLESS NOTED OTHERWISE
OC ON CENTER
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/7
/2
:3
:3
A M
C U s e rs
\d a v id
.s a m m o n s
\D o c u m e n ts \R e v it L o c a l F ile s \P
-1
-S
-R
-S
E G d a v id
.s a m m o n s
.r v t
S-001A
G E
N E
R A
L N
O T
E S
A N
D L
E G
E N
D
WCT
12942044
DMS DMS
03/26/2026
S E
G R
E G
A T
IO
N
F A
C
IL
IT
IE
S
MME/WJW
1737010
Y O
R K
T O
W N
V
IR
G
IN
IA
N A
V A
L W
E A
P O
N S
S T
A T
IO
N
JWJ
CGM
HPN
M
ID
L A
N T
D C
C O
R E
S -0
A
P W
E A
P O
N M
A G
A Z
IN
E
S
Approved by LCDR VINCE DEL GRECO, ROICC with PWD
YORKTOWN, via Email.
GENERAL NOTES
1. UNIFIED FACILITIES CRITERIA UFC 1-200-01 - DOD BUILDING CODE (01
SEPTEMBER 2022 CHANGE 2, 12 JUNE 2023) IS THE OVERARCHING DOCUMENT
FOR THE DESIGN OF THE STRUCTURAL SYSTEM FOR THIS PROJECT. BELOW
ARE CORE UNIFIED FACILITIES CRITERIA, CONSENSUS BUILDING CODES AND
STANDARDS DIRECTED BY UFC 1-200-01 FOR USE IN THE DESIGN OF THE
STRUCTURAL SYSTEM:
A. CORE UNIFIED FACILITIES CRITERIA:
a. UFC 3-301-01 (11 APRIL 2023): STRUCTURAL ENGINEERING
B. CONSENSUS BUILDING CODES AND STANDARDS:
a. GENERAL:
• IBC 2021: INTERNATIONAL BUILDING CODE
• ASCE 7-16, WITH SUPPLEMENT 1: AMERICAN SOCIETY OF CIVIL
ENGINEERS, MINIMUM DESIGN LOADS FOR BUILDINGS AND
OTHER STRUCTURES
b. CONCRETE:
• ACI 318-19: AMERICAN CONCRETE INSTITUTE, BUILDING CODE
REQUIREMENTS FOR STRUCTURAL CONCRETE
c. METALS:
• ANSI/AISC 360-16: AMERICAN INSTITUTE OF STEEL
CONSTRUCTION, SPECIFICATION FOR STRUCTURAL STEEL
BUILDINGS
• AWS D1.1-2015: AMERICAN WELDING SOCIETY, STRUCTURAL
WELDING CODE – STEEL
• ANSI/NAAMM MBG 531-17: NATIONAL ASSOCIATION OF
ARCHITECTURAL METAL MANUFACTURERS, METAL BAR GRATING
MANUAL
2. THIS PROJECT IS SUBJECT TO IBC 2021 SPECIAL INSPECTION REQUIREMENTS
AS MODIFIED BY UFC 3-301-01 AND UFC 3-600-01. THE STATEMENT AND
SCHEDULE OF SPECIAL INSPECTIONS, INCLUDED WITH THE PROJECT
SPECIFICATIONS, DEFINE THE SCOPE OF SPECIAL INSPECTIONS.
3. THIS PROJECT IS SUBJECT TO IBC 2021 STRUCTURAL OBSERVATION
REQUIREMENTS FOR STRUCTURES. THE PROJECT SPECIFICATIONS DEFINE
THE SCOPE OF STRUCTURAL OBSERVATIONS.
4. THE STRUCTURAL SYSTEM HAS NOT BEEN DESIGNED TO RESIST
PROGRESSIVE COLLAPSE IN ACCORDANCE WITH UFC 4-023-03.
5. THE STRUCTURES ASSOCIATED WITH THIS PROJECT DO NOT MEET THE
OCCUPANCY LEVELS OF INHABITED BUILDINGS. THEREFORE, THE
STRUCTURES ARE EXEMPT FROM UFC 4-010-01 ANTITERRORISM PROVISIONS.
6. COORDINATE STRUCTURAL WORK WITH WORK SHOWN ON OTHER
DRAWINGS.
7. CONTRACT DOCUMENTS REPRESENT THE FINISHED STRUCTURE. PROVIDE
MEANS AND METHODS OF CONSTRUCTION INCLUDING, BUT NOT LIMITED TO,
SHORING AND TEMPORARY BRACING TO MAINTAIN THE STRUCTURE IN A
SAFE AND STABLE CONDITION AT ALL TIMES. THE CONTRACTOR IS SOLELY
RESPONSIBLE TO DETERMINE ERECTION PROCEDURES AND SEQUENCE OF
CONSTRUCTION. UNDERTAKE NECESSARY MEASURES TO ENSURE SAFETY
OF PERSONS AND STRUCTURES AT THE SITE AND ADJACENT TO THE SITE.
VISITS TO THE SITE BY THE CONTRACTING OFFICER OR CONTRACTING
OFFICER'S REPRESENTATIVE DO NOT RELIEVE THE CONTRACTOR OF SUCH
RESPONSIBILITY.
8. WHERE CERTAIN FEATURES ARE NOT FULLY SHOWN OR CALLED FOR ON THE
CONTRACT DRAWINGS OR SPECIFICATIONS, CONSTRUCT OF THE SAME
CHARACTER AS FOR SIMILAR CONDITIONS THAT ARE SHOWN OR CALLED FOR
SUBJECT TO THE APPROVAL OF THE CONTRACTING OFFICER. WHERE
SECTIONS VARY, PROVIDE FOR SMOOTH TRANSITIONS BETWEEN THEM,
UNLESS NOTED OTHERWISE.
9. REPORT DIMENSIONAL DISCREPANCIES BETWEEN DRAWINGS TO THE
CONTRACTING OFFICER PRIOR TO BEGINNING WORK IN AFFECTED AREAS.
10. CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES AND
SUPERVISION OF THE WORK ARE THE SOLE RESPONSIBILITY OF THE
CONTRACTOR.
11. DETAILS TITLED OR NOTED AS TYPICAL OR STANDARD APPLY NOT ONLY
WHERE SPECIFICALLY INDICATED OR REFERENCED BUT ALSO IN OTHER
CASES WHERE THE NATURE OF THE CONSTRUCTION REQUIRES THEIR USE.
DETERMINE APPLICABILITY OF TYPICAL AND STANDARD DETAILS FROM
DESCRIPTIVE TITLES OR FROM THE SIMILARITY OF A CONSTRUCTION
CONDITION WITH ANOTHER CONDITION WHERE THE DETAIL IS SPECIFICALLY
INDICATED OR REFERENCED.
12. ELEVATIONS SHOWN ON THE STRUCTURAL DRAWINGS ARE RELATIVE TO A
REFERENCE ELEVATION OF 0'-0" THAT CORRESPONDS TO THE FOLLOWING
ELEVATIONS ABOVE SEA LEVEL BASED ON THE VIRGINIA NORTH AMERICAN
VERTICAL DATUM, 1988 (NAVD88):
A. SEGREGATION BUILDING 1: 52.65
B. SEGREGATION BUILDING 2: 50.50
DESIGN LOADS AND CRITERIA
1. RISK CATEGORY: III
2. LIVE LOADS:
A. UNIFORM:
a. CONTAINER TRANSFER, SEGREGATION AND CHARGING: 250 PSF
b. MECHANICAL, ELECTRICAL, SPRINKLER AND AIR: 150 PSF
c. MECHANICAL CATWALK: 40 PSF
d. OTHER AREAS: 125 PSF
e. ROOF: 20 PSF MINIMUM OR SNOW DRIFT
B. CONCENTRATED:
a. GROUND FLOOR SLAB: 2,000 LBS UNIFORMLY DISTRIBUTED OVER AN
AREA 2.5 FEET BY 2.5 FEET
b. ROOF: 300 LBS
C. VEHICLE (REFER TO S-901A FOR FORKLIFT AXLE LOADS.):
a. CONTAINER TRANSFER AND SEGREGATION: LOADED FORKLIFT
b. FORKLIFT CHARGING: UNLOADED FORKLIFT
c. CONTAINER TRANSFER: TRACTOR TRAILER WITH 80,000 LBS GROSS
VEHICLE WEIGHT (TRACTOR AND TRAILER) AND WB-67 WHEEL BASE
WITH THE FOLLOWING AXLE LOADS:
SINGLE DRIVE AXLE: 16 KIPS/12 KIPS
TANDEM DRIVE AXLE: 32 KIPS/34 KIPS (19'-6" FROM STEER AXLE)
TANDEM TRAILER AXLE: 32 KIPS/34 KIPS (45'-6" FROM DRIVE AXLE)
3. UNIFORM, CONCENTRATED AND VEHICLE LIVE LOADS HAVE NOT BEEN
APPLIED CONCURRENTLY. WHERE UNIFORM, CONCENTRATED AND VEHICLE
LOADS ARE INDICATED, THE SUPPORTING STRUCTURE HAS BEEN DESIGNED
FOR THE LOAD THAT PRODUCES THE GREATER LOAD EFFECTS.
4. LIVE LOADS FOR FLOOR AND ROOF FRAMING HAVE NOT BEEN REDUCED.
5. BOLLARDS: 6,000 LB CONCENTRATED LOAD APPLIED HORIZONTALLY IN ANY
DIRECTION AT 2'-3" ABOVE THE FLOOR SURFACE AS NON-CRASH AND NON-
ATTACK-RESISTANT BOLLARDS.
6. HANDRAIL AND GUARDRAIL SYSTEMS:
A. TOP RAIL:
a. CONCENTRATED LOAD: 200 LB APPLIED IN ANY DIRECTION AT ANY
POINT ON THE TOP RAIL
b. UNIFORM LOAD: 50 PLF APPLIED IN ANY DIRECTION ALONG TOP RAIL
AND NOT ACTING CONCURRENTLY WITH THE CONCENTRATED LOAD
B. INTERMEDIATE RAILS:
a. CONCENTRATE LOAD: 50 LBS APPLIED HORIZONTALLY AND NORMAL
TO THE RAILING ON AN AREA NOT EXCEEDING 12-INCH BY 12-INCH
AND NOT ACTING CONCURRENTLY WITH THE TOP RAIL
CONCENTRATED AND UNIFORM LOADS.
7. FIXED LADDERS:
A. LADDER: 300 LB APPLIED AT ANY POINT TO PRODUCE MAXIMUM LOAD
EFFECT ON ELEMENT CONSIDERED WITH NUMBER AND POSITION OF
ADDITIONAL CONCENTRATED LOAD UNITS OF 1 UNIT OF 300 LB FOR
EVERY 10 FEET OF LADDER HEIGHT.
B. SIDE RAIL EXTENSION: 100 LB SINGLE CONCENTRATED LIVE LOAD
APPLIED IN ANY DIRECTION AT ANY HEIGHT UP TO THE TOP OF THE SIDE
RAIL EXTENSION.
8. ROOF SNOW LOAD DATA:
A. GROUND SNOW LOAD: pg = 15 PSF B. FLAT-ROOF SNOW LOAD: pf = 12 PSF C. SNOW EXPOSURE FACTOR: Ce = 1.0 FOR PARTIALLY EXPOSED AT TERRAIN
CATEGORY B
D. SNOW LOAD IMPORTANCE FACTOR: Is = 1.10 E. THERMAL FACTOR: Ct = 1.0 AND SLOPE FACTOR: Cs = 1.0 F. DRIFT SURCHARGE LOAD: pd = 54 PSF G. WIDTH OF SNOW DRIFT: w = 13.5 FEET
9. WIND DESIGN DATA:
A. BASIC DESIGN WIND SPEED: 124 MPH
B. ALLOWABLE STRESS DESIGN WIND SPEED: 96 MPH
C. WIND EXPOSURE CATEGORY: C
D. INTERNAL PRESSURE COEFFICIENTS: +/- 0.18.
E. ENCLOSURE CLASSIFICATION: ENCLOSED
F. TOPOGRAPHIC FACTOR: 1.0
G. THE BUILDING LOCATION IS NOT A HURRICANE-PRONE REGION SINCE THE
BASIC DESIGN WIND SPEED FOR RISK CATEGORY II IS NOT GREATER
THAN 115 MPH.
H. THE BUILDING LOCATION IS NOT A WIND-BORNE DEBRIS REGION SINCE
THE BASIC DESIGN WIND SPEED IS NOT EQUAL TO OR GREATER THAN 130
MPH.
I. REFER TO COMPONENTS AND CLADDING PRESSURE NOTES ON S-901A
FOR BASIC DESIGN WIND PRESSURES APPLIED TO EXTERIOR
COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY DESIGNED BY
THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR THE DESIGN
OF THE STRUCTURE.
10. ROOF RAIN LOAD DATA: 100-YEAR RAIN INTENSITY: i = 3.5 INCH/HOUR
11. NOTIONAL LOADS FOR GENERAL STRUCTURAL INTEGRITY: IN ACCORDANCE
WITH ASCE 7-16 SECTION 1.4.
MISCELLANEOUS METAL FABRICATIONS,
LADDERS AND METAL RAILINGS
SERVICEABILITY LIMITS
1. PILE FOUNDATION AND DRILLED SHAFT SETTLEMENT LIMIT: 1/2 INCH TOTAL
FOR INDIVIDUAL PILES OR PILE GROUPS OR AN ANGULAR DISTORTION OF 1/500.
2. CONCRETE FLOOR AND ROOF DEFLECTION LIMITS FOR THAT PART OF THE
TOTAL DEFLECTION OCCURRING AFTER ATTACHMENT OF NONSTRUCTURAL
ELEMENTS, WHICH IS THE SUM OF THE TIME-DEPENDENT DEFLECTION DUE TO
ALL SUSTAINED LOADS AND THE IMMEDIATE DEFLECTION DUE TO ANY
ADDITIONAL LIVE LOAD (FOR TWO-WAY SLABS, L = SLAB PANEL LARGEST
CLEAR SPAN DIMENSION):
A. ROOFS: L/240 (INTERIOR NON-LOAD BEARING PARTITIONS REQUIRE
DEFLECTION TRACK TO ALLOW FOR ROOF SLAB DEFLECTION OF 1-INCH)
B. FLOORS AT ADMINISTRATIVE AREA: L/480
3. FLOORS OTHER THAN ADMINISTRATIVE AREA: L/360 FOR IMMEDIATE
DEFLECTION DUE TO LIVE LOAD SINCE THESE FLOOR AREAS DO NOT SUPPORT
OR HAVE NONSTRUCTURAL ELEMENTS ATTACHED TO THEM THAT ARE LIKELY
TO BE DAMAGED BY LARGE DEFLECTIONS.
4. HANDRAIL AND GUARDRAIL SYSTEM: SUM OF THE RAIL HEIGHT DIVIDED BY 24
PLUS THE EFFECTIVE RAIL LENGTH DIVIDED BY 96 (H/24 + L/96).
5. WIND INDUCED LATERAL DRIFT AND DEFLECTION LIMITS BASED ON 0.42 TIMES
THE APPLICABLE BASIC MAIN WIND FORCE-RESISTING SYSTEM OR
COMPONENT AND CLADDING LOADS (ALLOWABLE STRESS DESIGN WIND SPEED
WITH A 10-YEAR MEAN RETURN INTERVAL):
A. BUILDING LATERAL DRIFT: H/480
B. WALL FRAMING DEFECTION: H/240
DELEGATED ENGINEERED SYSTEMS
1. DESIGN RESPONSIBILITY FOR THE FOLLOWING STRUCTURAL ENGINEERED
SYSTEMS AND COMPONENT PARTS IS DELEGATED TO A QUALIFIED
DELEGATED REGISTERED PROFESSIONAL ENGINEER SELECTED BY THE
CONTRACTOR. THIS LIST DOES NOT INCLUDE NON-STRUCTURAL ELEMENTS.
A. PRECAST/PRESTRESSED CONCRETE PILES
2. REFER TO THIS SHEET FOR APPLICABLE DESIGN STANDARDS, LOADS,
CRITERIA, AND SERVICEABILITY LIMITS.
3. INCLUDE SIGNED SEALS FOR WORK DESIGNED BY THE DELEGATED ENGINEER.
4. DO NOT START FABRICATION OF THE DELEGATED SYSTEM OR COMPONENT
PART OR FIELD CONSTRUCTION AFFECTED BY THE SYSTEM OR COMPONENT
PART WITHOUT SUBMITTAL APPROVAL BY THE CONTRACTING OFFICER.
PRECAST/PRESTRESSED CONCRETE PILES
12. FLOOD DESIGN DATA:
A. FLOOD DESIGN CLASS 2 ASSIGNED ACCORDING TO ASCE 24 TABLE 1-1
B. ELEVATION OF THE PROPOSED LOWEST FLOOR AND ELEVATION TO
WHICH BUILDING IS DRY FLOODPROOFED: BUILDING 1: 52.65 AND BUILDING
2: 48.50
C. ELEVATION OF THE BOTTOM OF THE LOWEST HORIZONTAL STRUCTURAL
MEMBER OF THE LOWEST FLOOR: BUILDING 1: 48.32 AND BUILDING 2: 44.17
13. EARTHQUAKE DESIGN DATA:
A. SEISMIC IMPORTANCE FACTOR: Ie = 1.25
B. MAPPED SPECTRAL RESPONSE ACCELERATION PARAMETERS:
SS = 0.109g, S1 = 0.0425g
C. SITE CLASS: D
D. DESIGN SPECTRAL RESPONSE ACCELERATION PARAMETERS:
SDS = 0.116g, SD1 = 0.068g
SEISMIC DESIGN CATEGORY: A
E. BASIC SEISMIC FORCE-RESISTING SYSTEM: BEARING WALL SYSTEM WITH
ORDINARY REINFORCED CONCRETE SHEAR WALLS
F. DESIGN BASE SHEAR (DUE TO ASD WIND LOADING):
a. PLAN NORTH-SOUTH DIRECTION: 114 KIPS
b. PLAN EAST-WEST DIRECTION: 108 KIPS
G. SEISMIC RESPONSE COEFFICIENT: Cs = 0.03625
H. RESPONSE MODIFICATION COEFFICIENT: R = 4
I. ANALYSIS PROCEDURE USED: EQUIVALENT LATERAL FORCE ANALYSIS
J. THE ASCE 7-16 SEISMIC DESIGN REQUIREMENTS FOR BUILDINGS DO NOT
APPLY TO THIS BUILDING SINCE IT HAS BEEN ASSIGNED TO SEISMIC
DESIGN CATEGORY A.
1. THE INFORMATION PROVIDED IN THE REPORT TITLED 'FINAL GEOTECHNICAL
REPORT MILCON PROJECT P-171 WON 1737010 WEAPONS MAGAZINES, PHASE
3 YORKTOWN NAVAL WEAPONS STATION, YORKTOWN, VA', PREPARED BY
NAVFAC MIDLANT, AND DATED SEPTEMBER 18, 2023 HAS BEEN USED FOR THE
DESIGN OF THE FOUNDATIONS..
2. SHALLOW FOUNDATIONS (EXTERIOR MECHANICAL EQUIPMENT PADS): 500 PSF
NET ALLOWABLE BEARING PRESSURE WITH 9" FROST PROTECTION DEPTH
3. ALLOWABLE (SERVICE-LEVEL) PILE DESIGN CAPACITIES ARE AS FOLLOWS:
A. AXIAL COMPRESSION: 48 TONS
B. AXIAL TENSION: 0 TONS. PILES ARE NOT SUBJECT TO AXIAL TENSION
C. LATERAL: 4.5 TONS FOR 1/4-INCH DEFLECTION WITH A FREE-END PILE
HEAD FIXITY CONDITION
GEOTECHNICAL INFORMATION
1. CONCRETE: NORMAL WEIGHT WITH A MINIMUM 28-DAY COMPRESSIVE
STRENGTH OF 5000 PSI FOR SLABS AND 4000 PSI FOR OTHER CONCRETE.
2. FORMWORK:
A. COORDINATE CONCRETE WORK WITH THE PLACEMENT OF PIPING,
INSERTS, FLOOR DRAINS, CHAMFER STRIPS, REGLETS AND OTHER
EMBEDDED ITEMS.
B. DO NOT EMBED MECHANICAL, ELECTRICAL, PLUMBING AND OTHER
UTILITIES IN CONCRETE SLABS AND WALLS.
C. ACCURATELY PLACE, SUPPORT AND SECURE EMBEDDED ITEM SUCH AS
ANCHOR RODS AND WELD PLATES BEFORE PLACING CONCRETE TO
PREVENT DISPLACEMENT OF EMBEDDED ITEM BEYOND PERMITTED
TOLERANCES.
D. SLEEVE PIPING OR UTILITIES PASSING THROUGH CONCRETE TO
MAINTAIN 1" CLEAR ALL AROUND, UNLESS NOTED OTHERWISE. REFER TO
OTHER DISCIPLINE DRAWINGS FOR SLEEVE DETAILS. PROVIDE
MEASURES TO ENSURE THAT SLEEVES REMAIN FREE OF DEBRIS AND
WATER DURING CONSTRUCTION. DO NOT SLEEVE THROUGH PILE CAPS.
E. PROVIDE 3/4" CHAMFER STRIPS ON EDGES OF EXPOSED CONCRETE,
UNLESS NOTED OTHERWISE.
F. DO NOT EARTH-FORM FOUNDATIONS.
G. LOCATE CONSTRUCTION, CONTRACTION, ISOLATION, EXPANSION, AND
OTHER JOINTS AS INDICATED OR SPECIFIED, OR OTHERWISE APPROVED.
3. REINFORCING STEEL:
A. BARS: ASTM A615 GRADE 60. SHOP FABRICATE BENT AND HOOKED BARS.
B. HEADED DEFORMED BARS: ASTM A970 INCLUDING ANNEX A1
REQUIREMENTS FOR CLASS HA HEAD DIMENSIONS.
C. WELDED WIRE REINFORCEMENT: ASTM A1064, SHEET TYPE ONLY.
D. DETAIL AND PLACE REINFORCEMENT IN ACCORDANCE WITH THE
AMERICAN CONCRETE INSTITUTE ACI SP-66, ACI 301 AND ACI 318, AND
THE CONCRETE REINFORCING STEEL INSTITUTE CRSI MANUAL OF
STANDARD PRACTICE.
E. REINFORCING BAR SUPPORTS: CONFORM TO CRSI RB4.1. USE WIRE OR
COMPOSITE BAR SUPPORTS. PRECAST CONCRETE BAR SUPPORTS ARE
ACCEPTABLE FOR FOUNDATIONS BUT NOT SLABS AND OTHER
CONCRETE ELEMENTS. FOR PRECAST BAR SUPPORTS, USE SUPPORTS
SPECIFICALLY MANUFACTURED FOR REINFORCING SUPPORT WITH A
MINIMUM CONCRETE COMPRESSIVE STRENGTH EQUAL TO OR GREATER
THAN CONCRETE ELEMENT INTO WHICH IT IS PLACED. DO NOT PLACE
PRECAST CONCRETE BAR SUPPORTS ON TOP OF OR CLOSER THAN 18-
INCHES FROM PILES.
F. CONCRETE CLEAR COVER: UNLESS NOTED OTHERWISE, USE THE
FOLLOWING MINIMUM CONCRETE CLEAR COVER OVER REINFORCEMENT:
a. CAST AGAINST AND PERMANENTLY IN CONTACT WITH GROUND: 3"
b. EXPOSED TO WEATHER OR IN DIRECT CONTACT WITH GROUND: 2"
c. NOT EXPOSED TO WEATHER OR IN DIRECT CONTACT WITH GROUND:
• ROOF SLABS AND WALLS (EXCEPT AT ROOF SLAB SOFFIT/WALL
SURFACES AT UTILITY ROOMS): 3/4"
• ROOF SLAB SOFFIT/WALL SURFACES AT UTILITY ROOMS: 1 1/2"
• GROUND FLOOR SLABS: TOP = 1" AND BOTTOM = 1 1/2"
• BEAMS AND COLUMNS: 1 1/2" TO STIRRUPS AND TIES
1. PROVIDE MATERIALS CONFORMING TO THE FOLLOWING:
A. SHAPES (OTHER THAN W AND WT), PLATES, MISCELLANEOUS SHAPES
AND THREADED RODS: ASTM A36, Fy = 36 KSI
B. WIDE FLANGE SHAPES AND TEES: ASTM A992, Fy = 50 KSI C. PIPE: ASTM A53, TYPE E OR S, GRADE B, Fy=35 KSI D. HOLLOW STRUCTURAL SECTIONS: ASTM A1085, GRADE A, Fy = 50 KSI
E. WELDING: AWS D1.1 USING E70 ELECTRODES WITH LOW HYDROGEN
WHERE REQUIRED
F. HEADED STUD CONNECTORS: AWS D1.1, TYPE B MADE FROM ASTM A108
MATERIAL WITH Fu=65 KSI
G. STRUCTURAL BOLTS: ASTM A325, TYPE 1 WITH DIRECT TENSION
INDICATOR WASHERS OR ASTM F1852, TYPE 1 TENSION CONTROL BOLTS
H. CARBON STEEL BOLTS: ASTM A307, GRADE A
I. POST-INSTALLED ANCHORS: USE ANCHORS WITH CHARACTERISTICS
MEETING OR EXCEEDING THOSE IN REFERENCED ESR AS FOLLOWS.
a. CONCRETE SCREW ANCHORS: CASE HARDENED CARBON STEEL
SCREW BOLT WITH HEX HEAD AND SIZE INDICATED. EVALUATION
SERVICE REPORT ESR-3889 WAS USED FOR THE BASIS OF DESIGN.
b. ADHESIVE ANCHORS: CARBON STEEL ASTM F1554, GRADE 36
THREADED RODS OF SIZE INDICATED AND SET WITH ADHESIVE.
EVALUATION SERVICE REPORT ESR-4868 WAS USED FOR THE BASIS
OF DESIGN.
J. ANCHOR RODS: ASTM F1554 GRADE 36
K. GROUT: ASTM C1107 CEMENTITIOUS NONSHRINK
L. STEEL BAR GRATING: CONSTRUCTION TYPE, BAR SIZE AND FINISH AS
INDICATED AND MANUFACTURED IN ACCORDANCE WITH NATIONAL
ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS (NAAMM)
METAL BAR GRATING (MBG) 531.
2. USE STRUCTURAL BOLTS FOR MISCELLANEOUS METAL FABRICATION BOLTED
CONNECTIONS EXCEPT WHERE SPECIFICALLY NOTED OTHERWISE. FULLY
PRETENSION STRUCTURAL BOLTS.
3. LOCATE ANCHOR RODS, STEEL PLATES WITH HEADED STUD CONNECTORS
AND OTHER EMBEDDED ITEMS ACCURATELY, SET WITH TEMPLATES, AND
SECURELY HELD IN POSITION PRIOR TO AND WHILE PLACING CONCRETE.
PROTECT EMBEDDED ITEMS FROM CONSTRUCTION ACTIVITY. DO NOT INSERT
EMBEDDED ITEMS INTO FRESH OR PARTIALLY HARDENED CONCRETE. DO NOT
SUBSTITUTE POST-INSTALLED ANCHORS FOR EMBEDDED ANCHOR RODS OR
OTHER EMBEDDED ANCHORS.
4. HOT-DIP GALVANIZE MISCELLANEOUS METAL FABRICATIONS, LADDERS AND
METAL RAILINGS AFTER FABRICATION.
LEGEND
1. USE 12-INCH SQUARE PRECAST/PRESTRESSED CONCRETE PILES
COMPLYING WITH THE PRECAST CONCRETE INSTITUTE MNL-116. AND WITH
THE FOLLOWING MATERIAL PROPERTIES:
A. BASE BID LENGTH: DETERMINE USING FOLLOWING MINIMUM PILE TIP
ELEVATIONS REFERENCING NAVD88, ROUNDING UP TO NEAREST
WHOLE FOOT FOR EACH PILE AND ADDING 10 FEET FOR TEST PILES:
a. SEGREGATION BUILDING 1 = 3.0 FEET
b. SEGREGATION BUILDING 2 = -1.0 FEET
B. CONCRETE: f'c = 5000 PSI (MINIMUM)
C. PRESTRESSING STEEL: ASTM A416, GRADE 270 SEVEN-WIRE STRESS
RELIEVED OR LOW RELAXATION STRANDS
D. REINFORCING STEEL: ASTM A615, Fy = 60 KSI
E. SPIRAL TIES: ASTM A1064
2. DESIGN PILES FOR THE FOLLOWING FACTORED LOAD COMBINATIONS
WHERE PU = FACTORED CONCENTRIC AXIAL FORCE, MU = FACTORED
BENDING MOMENT AND VU = FACTORED SHEAR IN THE PILE AND THE POINT
OF FIXITY IS 8.7 FEET BELOW TOP OF PILE:
A. 1.2D+1.0L+1.0W: PU = 135 KIPS, MU = 24 FT-KIPS AND VU = 15 KIPS
3. DRIVE (5) TEST (INDICATOR) PILES AT LOCATIONS SHOWN ON THE
FOUNDATION PLAN AS DIRECTED BY THE GOVERNMENT GEOTECHNICAL
ENGINEER AND CONTRACTING OFFICER.
4. DRIVE PILES WITH A VARIATION OF NOT MORE THAN THE FOLLOWING
WITHIN LOCATION/ELEVATION/ORIENTATION INDICATED. WHERE INDIVIDUAL
PILES OR PILE GROUPS EXCEED THESE TOLERANCES, PROVIDE
CORRECTIVE ACTION TO ENSURE PILE CAPACITIES ARE NOT EXCEEDED.
A. LONGITUDINAL AXIS: 2 PERCENT FROM VERTICAL
B. PLAN ROTATION: 10 DEGREES
C. PLAN OFFSET:
a. INDIVIDUAL PILE BUTTS: +/-3" IN TWO PERPENDICULAR DIRECTIONS
b. PILE GROUP CENTER OF GRAVITY:
• P-4 PILE CAPS/PARALLEL TO CONTINUOUS PILE CAP AXIS: +/-2"
• PERPENDICULAR TO CONTINUOUS PILE CAP AXIS: +/-1"
D. PILE BUTT ELEVATION: +0"/-2"
CAST-IN-PLACE CONCRETE
DESIGN LOADS AND CRITERIA CONTINUED CAST-IN-PLACE CONCRETE CONTINUED
G. SPLICE AND DEVELOPMENT LENGTHS: PROVIDE REINFORCING WITH
GREATEST LENGTHS PRACTICAL TO MINIMIZE SPLICES. DO NOT SPLICE WALL
AND COLUMN VERTICAL REINFORCING. WHERE WALL HORIZONTAL
REINFORCING SPLICES ARE REQUIRED, SPLICE BETWEEN AND NOT OVER
OPENINGS AND STAGGER SPLICES 5'-0" MINIMUM. WHERE SLAB REINFORCING
SPLICES ARE REQUIRED, SPLICE BOTTOM BARS OVER SUPPORTS AND TOP
BARS MIDWAY BETWEEN SUPPORTS. UNLESS NOTED OTHERWISE, USE THE
FOLLOWING EMBEDMENT AND LAP SPLICE LENGTHS FOR REINFORCING
STEEL BARS ROUNDED UP TO THE NEAREST WHOLE INCH:
a. MINIMUM STRAIGHT EMBEDMENT AND SPLICE LENGTHS: 48 BAR Ø
b. MINIMUM STANDARD HOOK EMBEDMENT LENGTHS: 15 BAR Ø
c. HOOK EMBEDMENT IS MINIMUM STRAIGHT LINE DISTANCE FROM
CRITICAL SECTION OF BAR TO FARTHEST EDGE OF HOOK.
H. AT CONSTRUCTION JOINTS BETWEEN WALL/COLUMN AND FOUNDATION/SLAB
ELEMENTS, PROVIDE CLEAN SURFACE FREE OF LAITANCE AND
INTENTIONALLY ROUGHENED TO A FULL AMPLITUDE OF APPROXIMATELY 1/4". S
Y M
D E
S C
R
IP
T
IO
N D
A T
E A
P
CONCRETE COLUMNS
CONTINUOUS PILE CAP
AT CONCRETE WALLS
PRECAST/PRESTRESSED
CONCRETE PILES
CONCRETE WALLS
MASONRY VENEER
PILE CAPS
AT COLUMNS
PILE SUPPORTED GROUND
FLOOR SLAB SHOWN
PARTIALLY TRANSPARENT
PERSONNEL
DOOR OPENINGS
OPENING
OVERHEAD DOOR
INTERIOR
CONCRETE
EQUIPMENT PAD
EQUIPMENT
CATWALK
FIXED
LADDER
LIGHTNING
PROTECTION MAST
FOUNDATION
EXTERIOR
CONCRETE
EQUIPMENT PAD
CONCRETE FILLED
STEEL BOLLARDS
CATWALK
BRACING
SAFETY
GATE
OPENINGLOUVER
SLAB SLOPES TO
EXTERIOR AT
CHARGING STATION
COLUMN
PROTECTION
SYSTEM
FIXED
LADDER
CONCRETE WALLS
CONCRETE ROOF SLAB
SHOWN PARTIALLY
TRANSPARENT
ROOF SLAB
OPENING
CONCRETE
COLUMNS BELOW
CONCRETE
COLUMN BELOW
CONCRETE WALLS
ROOF PRIMARY AND
OVERFLOW DRAIN
SCUPPER OPENINGS
EQUIPMENT
CATWALK
CONCRETE
COLUMNS BELOW
FIXED
LADDER
CATWALK
BRACING
CONCRETE
ROOF BEAM
FIXED
LADDER
A. REFER TO S-001A FOR GENERAL NOTES AND LEGEND.
B. THE 3D REPRESENTATION IS FOR GENERAL INFORMATION ONLY AND
DOES NOT REPRESENT A COMPLETE AND DETAILED REPRESENTATION OF
THE STRUCTURE. REFER TO PLANS, SECTIONS AND DETAILS FOR
DETAILED INFORMATION NOT SHOWN IN THE 3D REPRESENTATION.
C. ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND OTHER NON-
STRUCTURAL ELEMENTS ARE NOT SHOWN IN THE 3D REPRESENTATION.
DESIGN WIND PRESSURES FOR ROOF COMPONENTS (PSF)
COMPONENT TRIBUTARY AREA (SQFT)
ROOF
ZONE
DESIGN WIND PRESSURES FOR WALL COMPONENTS (PSF)
COMPONENT TRIBUTARY AREA (SQFT)WALL
ZONE
+16
1. USE WIND PRESSURES BELOW FOR THE DESIGN OF COMPONENTS AND
CLADDING ELEMENTS OR RETAIN A PROFESSIONAL ENGINEER TO
DETERMINE WIND PRESSURES FOR SPECIFIC EFFECTIVE WIND AREAS.
2. REFER TO DESIGN LOADS AND CRITERIA NOTES ON S-001A FOR WIND
LOAD DESIGN CRITERIA.
3. WIND PRESSURES ARE STRENGTH LEVEL VALUES BASED ON THE BASIC
DESIGN WIND SPEED (WIND LOAD FACTOR = 1.0). MULTIPLY PRESSURES
BY 0.6 WHEN USING ALLOWABLE STRESS DESIGN METHODOLOGY.
4. PRESSURES ARE GROSS VALUES, DO NOT INCLUDE DEAD LOADS AND ARE
TABULATED IN POUNDS PER SQUARE FOOT (PSF).
5. FOR ROOFS AND WALLS, PLUS AND MINUS SIGNS SIGNIFY PRESSURES
ACTING TOWARD AND AWAY FROM THE SURFACES, RESPECTIVELY. FOR
PARAPETS, PRESSURES ACT IN DIRECTION SHOWN IN ASCE 7-16 FIGURE
30.6-1.
6. DESIGN COMPONENTS AND CLADDING FOR THE MAXIMUM POSITIVE AND
NEGATIVE WIND PRESSURES.
7. FOR COMPONENTS AND CLADDING NOT AFFECTED BY INTERNAL
PRESSURE SUCH AS METAL WALL PANELS ATTACHED TO THE EXTERIOR
SURFACES OF CONCRETE WALLS, DEDUCT 5 PSF INTERNAL PRESSURE
FROM THE ABSOLUTE PRESSURE VALUES TABULATED BELOW EXCEPT DO
NOT REDUCE BELOW 16 PSF.
8. LINEAR INTERPOLATION IS PERMITTED FOR INTERMEDIATE EFFECTIVE
WIND AREAS.
9. BUILDING ZONES ARE DEFINED IN ASCE 7-16 FIGURES 30.3-1 FOR WALLS,
30.3-3 FOR ROOFS AND 30.6-1 FOR PARAPETS.
10. DETERMINE PARAPET PRESSURES IN ACCORDANCE WITH ASCE 7-16
FIGURE 30.6-1 USING THE WALL AND ROOF PRESSURES TABULATED
BELOW.
11. FOR DESIGN OF DEFLECTION-CONTROLLED COMPONENTS AND CLADDING,
MULTIPLY DESIGN WIND PRESSURES BY 0.42 TO CONVERT LOADING TO
ALLOWABLE STRESS DESIGN VALUES FOR A 10-YEAR MEAN RETURN
INTERVAL.
-59
+34 -78
+34 -78
+16 -50
+30 -66
+30 -66
+16 -41
+27 -56
+27 -56
+16 -37
+25 -50
+25 -50
+34 -37
+34 -45
+29 -32
+29 -35
+27 -30
+27 -32
+25 -28
+25 -28
WHEEL BASE
54.2" STEER AXLE
UNLOADED = 2,361 LBS
LOADED = 6,769
DRIVE AXLE
UNLOADED = 4,474 LBS
LOADED = 14,882 LBS
NOTES:
1. LOADS BASED ON HYSTER COMPANY FORKLIFT MODEL E60XN
2. RATED CAPACITY = 6,000 LBS
3. OVERALL WIDTH (WIDE TREAD) = 48.2"
4. WHEEL LOAD = 1/2 AXLE LOAD
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/7
/2
:3
:3
A M
C U s e rs
\d a v id
.s a m m o n s
\D o c u m e n ts \R e v it L o c a l F ile s \P
-1
-S
-R
-S
E G d a v id
.s a m m o n s
.r v t
S-002A
D
R E
P R
E S
E N
T A
T
IO
N A
N D
C O
M P
O N
E N
T S
A N
D C
L A
D D
IN
G
P R
E S
S U
R E
S
WCT
12942045
DMS DMS
03/26/2026
S E
G R
E G
A T
IO
N
F A
C
IL
IT
IE
S
MME/WJW
1737010
Y O
R K
T O
W N
V
IR
G
IN
IA
N A
V A
L W
E A
P O
N S
S T
A T
IO
N
JWJ
CGM
HPN
M
ID
L A
N T
D C
C O
R E
S -0
A
P W
E A
P O
N M
A G
A Z
IN
E
S
Approved by LCDR VINCE DEL GRECO, ROICC with PWD
YORKTOWN, via Email.
SCALE: NOT TO SCALE
A1
3D REPRESENTATION
GENERAL SHEET NOTES
COMPONENTS AND CLADDING PRESSURES
FORKLIFT AXLE LOADS AND GEOMETRY
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
A. REFER TO S-001A FOR GENERAL NOTES AND LEGEND, SB501A AND SB502A
FOR FOUNDATION DETAILS AND SF501A FOR CONCRETE COLUMN AND
WALL DETAILS.
B. GROUND FLOOR SLABS ARE NOT SHOWN ON FOUNDATION PLAN. REFER
TO SB102A FOR GROUND FLOOR SLAB PLAN.
C. COLUMN AND WALL MARKS ARE NOT SHOWN ON FOUNDATION PLAN.
REFER TO SB102A FOR MARKS.
D. COORDINATE BELOW GRADE UTILITIES CROSSING FOUNDATIONS SO THAT
UTILITIES ARE ABOVE OR BELOW PILE CAPS, DO NOT PENETRATE
THROUGH PILE CAPS AND ARE AT LEAST 1'-0" AWAY FROM FACE OF PILES.
E. PROVIDE 6-INCH DEPTH NO. 67 STONE BASE COURSE BENEATH
FOUNDATIONS.
B
AA
2 5
CC
D
E
F
1' - 8" 21' - 4" 20' - 4" 25' - 5" 27' - 7" 1' - 8"
17' - 7" 16' - 2" 24' - 0" 24' - 0" 12' - 11"
CPC70X28 (TYP UNO)
3' - 9"
5 5
4'
8"
6' - 4" 3' - 8" 3' - 8" 8' - 2"
2' - 4"2' - 4"
6' - 8"
TYP
2' - 11 1/2" 14' - 9" 14' - 11 1/2" 14' - 10" 20' - 8" 8' - 10" 8' - 4" 12' - 8"
4'
8"
32' - 8" 65' - 4"
98' - 0"
1'
8"
1'
8"
2'
4" 9'
0"
8' - 2"
4'
8"
6' - 4" 6' - 4" 6' - 4"
A1
SB401A
C1
SB401A
A1
SB402A
A1
SB401A
SIM
A1
SB401A
SIM
TYP
11' - 9" 11' - 9"
10' - 1" 12' - 9" 12' - 8" 13' - 8" 13' - 11"
10' - 2" 10' - 2" 5'
9"
6'
4'
6"
90 91
16' - 4" (2 SPACES AT 8' - 2")
5'
8" 5'
9"
3'
0"
6" TYP
6" T
Y P
5' - 2"
1'
8"
1' - 8"
6" TYP
6" T
Y P
4'
4"
4'
6" 6'
5' - 2"
3'
9"
6' - 8" 52' - 0" (8 SPACES AT 6' - 6")
(8 S
P A
C E
S A
T 5'
8"
9 9 9
95 98 99 100 101 103102 104 105
115 120 125
126 128-TP5 129 130
139 140
145 147 148 149
70 74 76 78 80 82 84
62 60 58 56 54-TP4
26 29 31 34 36-TP3
(5 S
P A
C E
S A
T 5'
0"
6'
3"
73 75 77 81 83
5557596163
33 35
(9 S
P A
C E
S A
T 5'
4"
(9 S
P A
C E
S A
T 5'
4"
3'
(5 S
P A
C E
S A
T 5'
0"
3'
(4 S
P A
C E
S A
T 6'
0"
27' - 6" (5 SPACES AT 5' - 6")
71' - 6" (13 SPACES AT 5' - 6")
24' - 0" (4 SPACES AT 6' - 0")5' - 4" 16' - 0" (4 SPACES AT 4' - 0") 6' - 4"
24 25
96 97
131 132 135 136 141 142
133 134 137 138 143 144
116 117
118 119
121 122
123 124
1-TP1
93 94
23 27
17-TP2
PC4PC4
TYP
65 67 6968
C P
C
X
C P
C
X
C P
C
X
C P
C
X
PC4 PC4 PC4
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/7
/2
:3
:4
A M
C U s e rs
\d a v id
.s a m m o n s
\D o c u m e n ts \R e v it L o c a l F ile s \P
-1
-S
-R
-S
E G d a v id
.s a m m o n s
.r v t
SB101A
P L A
N
F O
U N
D A
T
IO
N
WCT
12942046
DMS DMS
03/26/2026
S E
G R
E G
A T
IO
N
F A
C
IL
IT
IE
S
MME/WJW
1737010
Y O
R K
T O
W N
V
IR
G
IN
IA
N A
V A
L W
E A
P O
N S
S T
A T
IO
N
JWJ
CGM
HPN
M
ID
L A
N T
D C
C O
R E
S B
A
P W
E A
P O
N M
A G
A Z
IN
E
S
Approved by LCDR VINCE DEL GRECO, ROICC with PWD
YORKTOWN, via Email.
1/8" = 1' - 0" 0 5' 10' 15' 30'
GENERAL SHEET NOTES
GRAPHIC SCALE
KEYNOTES#
1 PROJECT BASE POINT/WORK POINT ORIGIN (0,0) DEFINED BY
INTERSECTION OF PLAN SOUTH AND WEST WALL EXTERIOR FINISHED
FACES.
2 CONCRETE WALL CENTERLINE DIMENSIONS.
3 FACE OF CONCRETE WALL DIMENSIONS.
4 FACE OF MASONRY VENEER DIMENSIONS.
5 PILE CENTERLINES DIMENSIONS ALONG CONTINUOUS PILE CAP.
6 GRID LINE AND/OR CONCRETE WALL CENTERLINE DIMENSIONS.
7 TOP OF CONTINUOUS PILE CAP ELEVATION IS 2'-0" BELOW TOP OF
REFERENCED GROUND FLOOR SLAB ELEVATION 0'-0" UNLESS NOTED
OTHERWISE.
8 TOP OF PILE CAP ELEVATION IS 1'-2" BELOW TOP OF REFERENCED
GROUND FLOOR SLAB ELEVATION 0'-0" UNLESS NOTED OTHERWISE.
9 ALIGN PILE CENTERLINE WITH CONCRETE WALL CENTERLINE.
10 CONCRETE FILLED STEEL HSS BOLLARDS AT OVERHEAD DOORS. REFER
TO SB502A FOR DETAILS AND SB102A FOR LOCATIONS.
11 PRECAST CONCRETE PILE - REFER TO GROUND FLOOR SLAB PLAN FOR
SLAB DROP PANELS CAST MONOLITHIC WITH SLAB AT PILES SUPPORTING
SLAB BETWEEN COLUMNS AND WALLS.
12 LIGHTNING MAST DRILLED SHAFT FOUNDATION - COORDINATE
FOUNDATION LOCATION WITH THE CIVIL AND ELECTRICAL PLANS. REFER
TO SB502A FOR DETAIL. LOCATE THE CLOSEST OUTSIDE EDGE OF THE
DRILLED SHAFT FOUNDATIONS A MINIMUM OF 3 FEET HORIZONTALLY
FROM THE OUTSIDE EDGE OF THE BUILDING FOUNDATION. PROVIDE THE
DRILLED SHAFT FOUNDATIONS AFTER CONSTRUCTING THE BUILDING
PILES AND FOUNDATIONS AND PRIOR TO CONSTRUCTING THE BUILDING
SUPERSTRUCTURE. PROVIDE DRILLED SHAFTS WITH TEMPORARY STEEL
CASING AND DRILLING SLURRY TO MITIGATE CONSTRUCTABILITY
CONCERNS AND POTENTIAL IMPACTS TO THE BUILDING FOUNDATIONS.
SCALE: 1/8" = 1'-0"
A1
PLAN - FOUNDATION
PLAN
NORTH
PLAN
NORTH
BLDG 1 BLDG 2
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
B
A
1 2 5 6 8
C
D
E
F
1'
8"
1'
8"
1' - 8" 21' - 4" 20' - 4" 25' - 5" 27' - 7" 1' - 8"
14' - 11 1/2" 14' - 10" 20' - 8" 8' - 10" 9' - 0" 12' - 0"
17' - 7" 16' - 2" 24' - 0" 24' - 0" 12' - 11"
3' - 9"
PC4 PC4 PC4
PC4PC4
TYP
CC24
X24
CC24
X24
CC24
X24
CC20
X20
CC20
X20
CW8 CW8
TYP
36' - 8" 7' - 4" 32' - 8"
3'
0"
4'
8"
32' - 8" 65' - 4"
2'
4" 9'
0"
CW12 (TYP UNO)
98' - 0"
TYP
21' - 4"
A1
SB401A
C1
SB401A
A1
SB401A
SIM
A1
SB402A
A1
SB401A
SIM
C4
SB401A
A1
SB402A
SIM
A1
SB402A
SIM
TYP AT
INTERIOR
DOORS
TYP
2'
4" 4'
0"
2'
8"
2' - 4"
O V
E R
H E
A D
D O
O R
O P
E N
IN
G
9'
3/
4"
2' - 11 1/2"
OVERHEAD DOOR OPENING
14' - 9"
2' - 11 1/2"
OVERHEAD DOOR OPENING
14' - 9"
1' - 6 1/2"
CW12A
CW8 TOS -2"
SLOPE
TYP
TYP
T Y
P
1'
0"
T Y
P
1'
6"
TYP
1' - 6"
TYP
1' - 6"
0" TYP
0" T
Y P
11 11 11
TYP
(7) #6T x 30' - 0"
(7
#6 T x
5'
0"
DP4.5 DP4.5 DP4.5
DP4.5DP4.5
DP4.5
DP4.5
DP4.5
8' - 0"
5'
0"
TYP
DP6.0
DP6.0
DP6.0
DP6.0 DP6.0
DP6.0 DP6.0 DP6.0
(7) #5T
(7
#5 T x
4'
0"
(7
#5 T x
4'
0"
(7
#5 T x
4'
0"
(7
#5 T x
4'
0"
(7
#5 T x
4'
0"
TYP
2" T
YP
(7) #6T x 30' - 0"
(7) #6T x 30' - 0"
(7
#6 T x
5'
0"
TYP
1'
8"
1' - 8"
A. REFER TO S-001A FOR GENERAL NOTES AND LEGEND, SB502A FOR
GROUND FLOOR SLAB DETAILS AND SF501A FOR COLUMN/WALL DETAILS.
B. REFER TO FOUNDATION PLAN ON SB101A FOR DIMENSIONS AND
FOUNDATION ELEMENTS NOT SHOWN OR ANNOTATED ON GROUND FLOOR
SLAB PLAN.
C. GROUND FLOOR SLAB IS 10-INCH THICK CONCRETE SLAB PLACED OVER
VAPOR BARRIER AND 8-INCH DEPTH OF POROUS FILL ON PREPARED
SUBGRADE AND REINFORCED WITH UNIFORMLY SPACED TOP AND
BOTTOM BARS EACH DIRECTION AS FOLLOWS:
CONTAINER TRANSFER/SEGREGATION AREAS: #6 AT 12" ON CENTER
MAXIMUM WITH OUTER LAYERS PARALLEL TO LETTERED GRID LINES.
OTHER AREAS: #5 AT 12" ON CENTER MAXIMUM WITH OUTER LAYERS
PARALLEL TO NUMBERED GRID LINES.
REFER TO SECTION A1/SB401A FOR REINFORCING PLACEMENT DETAILS.
AT LOCATIONS SHOWN ON PLAN, PLACE ADDED TOP BARS BETWEEN
UNIFORMLY SPACED REINFORCING SO THEY EXTEND EQUAL DISTANCE
EACH SIDE OF PILE/PILE CAP CENTERLINE.
COORDINATE REINFORCING STEEL PLACEMENT WITH FLOOR DRAINS AND
OTHER EMBEDDED ITEMS TO AVOID INTERRUPTING REINFORCING. OFFSET
REINFORCING BARS TO CLEAR EMBEDDED ITEMS. COORDINATE
REINFORCING STEEL PLACEMENT WITH POST INSTALLED ANCHOR
LOCATIONS TO AVOID CUTTING REINFORCING STEEL DURING ANCHOR
INSTALLATION. UNDER NO CIRCUMSTANCE IS IT ACCEPTABLE TO CUT
REINFORCING STEEL.
PLACE FLOOR SLABS MONOLITHICALLY BETWEEN JOINTS SHOWN. DO NOT
ADD CONSTRUCTION JOINTS WITHOUT CONTRACTING OFFICER APPROVAL.
COORDINATE SUPPORT FROM FLOOR SLABS FOR BELOW SLAB UTILITIES
WITH MECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION AND
OTHER REQUIREMENTS.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/7
/2
:3
:4
A M
C U s e rs
\d a v id
.s a m m o n s
\D o c u m e n ts \R e v it L o c a l F ile s \P
-1
-S
-R
-S
E G d a v id
.s a m m o n s
.r v t
SB102A
P L A
N
G R
O U
N D
F L O
O R
S L A
B
WCT
12942047
DMS DMS
03/26/2026
S E
G R
E G
A T
IO
N
F A
C
IL
IT
IE
S
MME/WJW
1737010
Y O
R K
T O
W N
V
IR
G
IN
IA
N A
V A
L W
E A
P O
N S
S T
A T
IO
N
JWJ
CGM
HPN
M
ID
L A
N T
D C
C O
R E
S B
A
P W
E A
P O
N M
A G
A Z
IN
E
S
Approved by LCDR VINCE DEL GRECO, ROICC with PWD
YORKTOWN, via Email.
1/8" = 1' - 0" 0 5' 10' 15' 30'
GENERAL SHEET NOTES
GRAPHIC SCALE
KEYNOTES#
SCALE: 1/8" = 1'-0"
A1
PLAN - GROUND FLOOR SLAB
1 FACE OF MASONRY VENEER.
2 CONCRETE WALL OPENING. REFER TO ARCHITECTURAL DRAWINGS FOR
SIZE AND LOCATION.
3 CONSTRUCTION JOINT WITH JOINT SEALANT AT PERSONNEL DOORS
THROUGH INTERIOR CONCRETE WALLS.
4 DOWELED CONSTRUCTION JOINT WITH SEMI-RIGID JOINT FILLER.
5 1/2-INCH PREMOLDED EXPANSION JOINT MATERIAL FULL DEPTH OF SLAB
BETWEEN SLAB EDGE AND FACE OF WALL.
6 (2) #5 X 4'-0" LONG AT REENTRANT SLAB CORNERS. PLACE DIRECTLY
BELOW SLAB TOP REINFORCING. TERMINATE WITH STANDARD HOOK
WHERE REINFORCING CANNOT BE PLACED SYMMETRIC ABOUT CORNER.
7 ADDED SLAB TOP REINFORCING OF QUANTITY, SIZE AND LENGTH
INDICATED. REFER TO GENERAL SHEET NOTES THIS SHEET FOR
REINFORCING PLACEMENT AND OTHER REQUIREMENTS.
8 SLAB DROP PANEL - REFER TO DETAIL ON SB501A.
9 CONCRETE FILLED STEEL HSS BOLLARDS AT OVERHEAD DOORS AND
FORKLIFT CHARGING ROOM. REFER TO SB502A FOR DETAILS.
10 SITE CONCRETE EMBEDDED STEEL BOLLARDS - REFER TO CIVIL
DRAWINGS FOR LOCATIONS AND DETAILS.
11 COLUMN PROTECTION SYSTEM - REFER TO ARCHITECTURAL DRAWINGS
FOR DETAILS.
12 FIXED LADDER. REFER TO DETAIL ON SF402A.
13 CONCRETE EQUIPMENT PAD AT EXTERIOR EQUIPMENT. REFER TO SB502A
FOR DETAIL. REFER TO MECHANICAL, ELECTRICAL AND PLUMBING
DRAWINGS FOR EQUIPMENT.
14 CONCRETE EQUIPMENT PAD AT INTERIOR EQUIPMENT. REFER TO SB502A
FOR DETAIL. REFER TO MECHANICAL, ELECTRICAL AND PLUMBING
DRAWINGS FOR EQUIPMENT.
15 BATTERY CHARGER EQUIPMENT PAD DIMENSIONS.
16 FLOOR DRAIN OR CLEANOUT - COORDINATE WITH PLUMBING.PLAN
NORTH
PLAN
NORTH
BLDG 1 BLDG 2
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
GROUND FLOOR TOS
0' - 0"
DEF
CONCRETE WALL
GROUND
FLOOR SLAB
SLAB TOP AND BOTTOM
REINFORCING - OUTER LAYER
CONCRETE
COLUMN BEYOND
GRID LINE /
INTERIOR FACE OF
CONCRETE WALL
GRID LINE /
CONCRETE COLUMN /
PILE CAP CENTERLINE
WALL VERTICAL
REINFORCING
WALL FINISH
SLAB UNIFORMLY
SPACED TOP AND
BOTTOM REINFORCING
BETWEEN COLUMN AND
WALL - INNER LAYER
WALL HORIZONTAL
REINFORCING
EXTERIOR FACE OF
CONCRETE WALL
STANDARD 180-
DEGREE HOOK EACH
END OF SLAB TOP
REINFORCING
GRID LINE /
INTERIOR FACE OF
CONCRETE WALL
INTERIOR FACE OF
CONCRETE WALL
PILES BEYOND
PILE CAP
BEYOND
PILES BEYOND
1' - 0"1' - 0"
CONTINUOUS
PILE CAP
WALL / CONTINUOUS
PILE CAP CENTERLINE
6" 6"
8"
COMPACTED
SUBGRADE
PILES
WIDEN WALL BELOW
SLAB FOR SLAB SUPPORT
WIDEN WALL BELOW
SLAB FOR SLAB SUPPORT
CONCRETE WALL
WALL VERTICAL
REINFORCING
WALL HORIZONTAL
REINFORCING
WALL / CONTINUOUS
PILE CAP CENTERLINE
6" 6"
NOTE:
REFER TO SB501A FOR PILE
CAP, CONTINUOUS PILE CAP
AND FLOOR SLAB DETAILS.
R E
FE
R
T O
P
LA
N
T O
P O
F P
IL
E
C A
P
1/2" JOINT FILLER AND
SEALANT BETWEEN
SLAB EDGES AND WALLS
CONTINUOUS
PILE CAP BEYOND
SITE GRADE
VAPOR BARRIER
POROUS FILL
WIDEN WALL BELOW
SLAB FOR SLAB SUPPORT
CONTINUE VAPOR
BARRIER ACROSS
TOP OF WALL
PERIMETER INSULATION
GROUTED CAVITY
BELOW GRADE
MASONRY
VENEER
8" 8"
CONTINUOUS
PILE CAP
STONE BASE COURSE ON
COMPACTED SUBGRADE
STONE BASE COURSE ON
COMPACTED SUBGRADE
T Y
P
6"
SLAB ADDED TOP
REINFORCING PLACED
MIDWAY BETWEEN
UNIFORMLY SPACED
REINFORCING
4"
6" 6"
FIRST SLAB REINFORCING
SPACE FROM FACE OF WALL
4" 4"
BEGIN SLAB UNIFORMLY
SPACED REINFORCING
AT 6" EACH SIDE OF PILE /
PILE CAP CENTERLINE
SLAB REINFORCING PLACEMENT NOTES:
1. REFER TO PLAN FOR ADDED REINFORCING
QUANTITIES, SIZE AND LOCATIONS.
2. PLACEMENT WIDTH IS AS REQUIRED FOR ADDED
REINFORCING BAR QUANTITY.
3. UNIFORMLY SPACED AND ADDED SLAB
REINFORCING PLACEMENT REQUIREMENTS ARE
SHOWN IN THIS SECTION BETWEEN GRID LINES D
AND F. THESE REQUIREMENTS ALSO APPLY FOR
OTHER SLAB AREAS AND SPAN DIRECTIONS.
4. BEGIN UNIFORMLY SPACED REINFORCING
PLACEMENT FROM PILES / PILE CAPS AND
PROGRESSING TOWARDS WALLS / ADJACENT PILES
/ PILE CAPS WITH BAR PLACEMENT STARTING AT 6"
EACH SIDE OF PILE / PILE CAP CENTERLINES.
ADDED TOP REINFORCING PLACEMENT WIDTH
EQUAL+/- EQUAL+/-
MAXIMUM
1'-0"
BA
CONCRETE WALL
GROUND
FLOOR SLAB
GRID LINE /
INTERIOR FACE OF
CONCRETE WALL
WALL VERTICAL
REINFORCING
WALL FINISH
WALL HORIZONTAL
REINFORCING
EXTERIOR FACE OF
CONCRETE WALL GRID LINE /
INTERIOR FACE OF
CONCRETE WALL
INTERIOR FACE OF
CONCRETE WALL
MASONRY
VENEER
CONTINUOUS
PILE CAP
PILES BEYOND PILES BEYOND
1' - 0"
CONTINUOUS
PILE CAP
WALL / CONTINUOUS
PILE CAP CENTERLINE
6" 6"
VAPOR BARRIER
POROUS FILL
WIDEN WALL BELOW
SLAB FOR SLAB SUPPORT
CONTINUE VAPOR
BARRIER ACROSS
TOP OF WALL COMPACTED
SUBGRADE
WIDEN WALL BELOW
SLAB FOR SLAB SUPPORT
WIDEN WALL BELOW
SLAB FOR SLAB SUPPORT
CONCRETE WALL
WALL VERTICAL
REINFORCING
WALL HORIZONTAL
REINFORCING
WALL / CONTINUOUS
PILE CAP CENTERLINE
NOTES:
REFER TO A1/SB401A
FOR NOTES NOT SHOWN.
R E
FE
R
T O
P
LA
N
T O
P O
F P
IL
E
C A
P
1/2" JOINT FILLER AND
SEALANT BETWEEN
SLAB EDGES AND WALLS
CONTINUOUS
PILE CAP BEYOND
1' - 0"
6" 6"
CONCRETE
WALL BEYOND
CONTINUOUS
PILE CAP BEYOND
SITE GRADE
PERIMETER INSULATION
GROUTED CAVITY
BELOW GRADE
CONCRETE COVER
AT INTERIOR FACE
OF WALLS AT
UTILITY SPACES
1 1/2"
1 1/2"
8" 8"8"
4" 4" 4"
D
GRID LINE /
INTERIOR FACE OF
CONCRETE WALL
INTERIOR FACE OF
CONCRETE WALL
1' - 0"
CONTINUOUS
PILE CAP
COMPACTED
SUBGRADE
PILES BEYOND
WIDEN WALL BELOW
SLAB FOR SLAB SUPPORT
CONCRETE
WALL BEYOND
1/2"
DOOR
NOTES:
REFER TO A1/SB401A
FOR NOTES NOT SHOWN.
WIDEN WALL
BELOW SLAB FOR
SLAB SUPPORT
GROUND
FLOOR SLAB
PREFORMED GAP FOR
JOINT SEALANT - GAP
DEPTH AS REQUIRED
FOR SEALANT
APPLY CURING
COMPOUND TO FACE
OF PREVIOUS POUR TO
PREVENT BONDING
WALL BEYOND
1' - 0"8" 8"
CONTINUE VAPOR
BARRIER ACROSS
TOP OF WALL
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/7
/2
:3
:4
A M
C U s e rs
\d a v id
.s a m m o n s
\D o c u m e n ts \R e v it L o c a l F ile s \P
-1
-S
-R
-S
E G d a v id
.s a m m o n s
.r v t
SB401A
S E
C T
IO
N
S
F O
U N
D A
T
IO
N A
N D
F L O
O R
S L A
B
WCT
12942048
DMS DMS
03/26/2026
S E
G R
E G
A T
IO
N
F A
C
IL
IT
IE
S
MME/WJW
1737010
Y O
R K
T O
W N
V
IR
G
IN
IA
N A
V A
L W
E A
P O
N S
S T
A T
IO
N
JWJ
CGM
HPN
M
ID
L A
N T
D C
C O
R E
S B
A
P W
E A
P O
N M
A G
A Z
IN
E
S
Approved by LCDR VINCE DEL GRECO, ROICC with PWD
YORKTOWN, via Email.
SCALE: 1" = 1'-0"
A1
SECTION
SCALE: 1" = 1'-0"
C1
SECTION
1" = 1' - 0" 0 6" 1' 3'2'
GRAPHIC SCALE
SCALE: 1" = 1'-0"
C4
SECTION
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
D
F
GROUND
FLOOR SLAB
GRID LINE / INTERIOR
FACE OF CONCRETE
WALL BEYOND
WALL FINISH
EXTERIOR FACE
OF WALL BEYOND GRID LINE / INTERIOR
FACE OF CONCRETE
WALL BEYOND
MASONRY
VENEER BEYOND
CONTINUOUS
PILE CAP
PILES BEYOND
CONTINUOUS
PILE CAP
VAPOR BARRIER
POROUS FILL
WIDEN WALL BELOW
SLAB FOR SLAB SUPPORT
CONTINUE VAPOR
BARRIER ACROSS
TOP OF WALL COMPACTED
SUBGRADE
PILES- BEYOND
WIDEN WALL BELOW
SLAB FOR SLAB SUPPORT
WIDEN WALL BELOW
SLAB FOR SLAB SUPPORT
R E
FE
R
T O
P
LA
N
T O
P O
F P
IL
E
C A
P
PREFORMED GAP FOR
SEMI-RIGID EPOXY
JOINT FILLER - GAP
DEPTH AS REQUIRED
FOR FILLER
WALL BEYOND
1' - 0"
CONTINUOUS
PILE CAP BEYOND
3/8"
CONCRETE
WALL BEYOND
CONCRETE
WALL BEYOND
EDGE OF SLAB RECESS
SITE PAVEMENT
SLOPE
CONTINUOUS GALVANIZED
L2X2X1/4 WITH 1/2"Ø HEADED
STUDS AT 1'-0" ON CENTER
1" 1/ 2"
S
TE
P
SLAB RECESS
1' - 4 3/4"
ADDED BAR LENGTH
6' - 0"
ADD #5 WITH STANDARD
180-DEGREE HOOK AT
EACH TOP BAR AT SLAB
EDGE STEP/SLOPE
APPLY CURING
COMPOUND TO FACE
OF PREVIOUS POUR TO
PREVENT BONDING
SLAB EDGE
OVERHEAD DOOR
CONTINUOUS
PILE CAP BEYOND
NOTES:
1. REFER TO SB501A FOR PILE
CAP, CONTINUOUS PILE CAP
AND FLOOR SLAB DETAILS.
2. REFER TO SB502A FOR
BOLLARD DETAILS.
3. REFER TO A1/SB401A FOR
NOTES NOT SHOWN. GROUND
FLOOR SLAB
PREFORMED GAP FOR
SEMI-RIGID EPOXY
JOINT FILLER - GAP
DEPTH AS REQUIRED
FOR JOINT FILLER
APPLY CURING
COMPOUND TO FACE
OF PREVIOUS POUR TO
PREVENT BONDING
1 1/4"Ø X 1'-6" LONG SMOOTH
GREASED STEEL DOWEL AT
12" ON CENTER - LOCATE
CENTERLINE OF FIRST DOWEL
AT 6" FROM END OF JOINT
BOLLARDS BEYOND
1 1/2" COVER
8" 8" 8"
C O
V E
R
1/ 2"
EQ EQ
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
M
ID
-A T
LA
N
T
IC
N A
V A
L S
T A
T
IO
N
N O
R F
O L K
V
A
AS NOTED
/7
/2
:3
:4
A M
C U s e rs
\d a v id
.s a m m o n s
\D o c u m e n ts \R e v it L o c a l F ile s \P
-1
-S
-R
-S
E G d a v id
.s a m m o n s
.r v t
SB402A
S E
C T
IO
N
S
F O
U N
D A
T
IO
N A
N D
F L O
O R
S L A
B
WCT
12942049
DMS DMS
03/26/2026
S E
G R
E G
A T
IO
N
F A
C
IL
IT
IE
S
MME/WJW
1737010
Y O
R K
T O
W N
V
IR
G
IN
IA
N A
V A
L W
E A
P O
N S
S T
A T
IO
N
JWJ
CGM
HPN
M
ID
L A
N T
D C
C O
R E
S B
A
P W
E A
P O
N M
A G
A Z
IN
E
S
Approved by LCDR VINCE DEL GRECO, ROICC with PWD
YORKTOWN, via Email.
SCALE: 1" = 1'-0"
A1
SECTION
1" = 1' - 0" 0 6" 1' 3'2'
GRAPHIC SCALE
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
PILES
PILE CAP
COLUMN DOWELS
WITH STANDARD 90-
DEGREE HOOK
CONCRETE COLUMN
CONCRETE FLOOR SLAB -
REINFORCING, POROUS
FILL AND OTHER DETAILS
NOT SHOWN
COLUMN/PILE CAP
CENTERLINE
1'
2"
P
IL
E C
A P
D E
P
TH
2'
6"
(10) #7 EACH DIRECTION
BOTTOM WITH STANDARD
180-DEGREE HOOK EACH END
2" C
LE
A
R 4"
E M
B E
D
3' - 0" 3' - 0"
SQUARE
6' - 0"
PILE CENTERLINES
NOTE:
EXTEND SLAB VAPOR BARRIER
1'-6" ACROSS TOP OF PILE CAP
1' - 6"3' - 0"1' - 6"
STONE BASE COURSE ON
COMPACTED SUBGRADE
T Y
P
6"
TOP OF PILE CAP -
TURN SLAB DOWN
TO PILE CAP
NOTE:
REFER TO PRECAST/PRESTRESSED
CONCRETE PILE NOTES ON S-001A FOR
PILE BUTT ELEVATION TOLERANCES.
INCREASE PILE CAP DEPTH TO MAINTAIN
4" PILE EMBEDMENT.
GROUND FLOOR TOS
0' - 0"
CONTINUOUS PILE CAP WIDTH
5' - 10" UNO
R E
FE
R
T O
P
LA
N
C O
N
TI
N U
O U
S P
IL
E
C A
P D
E P
TH
2'
4"
4" E
M B
E D
PILES
CONTINUOUS PILE CAP
WALL DOWELS WITH
STANDARD 90-
DEGREE HOOK
CONCRETE WALL
CONCRETE FLOOR SLAB -
REINFORCING, POROUS
FILL AND OTHER DETAILS
NOT SHOWN
WALL/PILE CAP
CENTERLINE
(6) #6 ((4) #6 AT CPC36X28)
CONTINUOUS TOP AND
BOTTOM WITH STANDARD
180-DEGREE HOOKS
EACH END
NOTE:
REFER TO 'ELEVATION AT
CONSTRUCTION JOINT' FOR
CONTINUOUS REINFORCING
SPLICING REQUIREMENTS.
#6 TRANSVERSE TOP
AND BOTTOM AT 1'-0"
ON CENTER WITH
STANDARD 180-DEGREE
HOOK EACH END
NOTES:
1. DETAIL SHOWN AT INTERIOR WALL.
DETAIL IS SIMILAR AT OTHER WALLS.
2. REFER TO PRECAST/PRESTRESSED
CONCRETE PILE NOTES ON S-001A FOR
PILE BUTT ELEVATION TOLERANCES.
INCREASE PILE CAP DEPTH TO
MAINTAIN 4" PILE EMBEDMENT.
PILE CENTERLINES
1' - 9" 2' - 4" 1' - 9"
SECTION ELEVATION AT CONSTRUCTION JOINT
2"
STONE BASE…