7 8 9 10
A
B
C
E
F
EXISTING 8" CHILLED WATER RETURN
EXISTING 8" CHILLED WATER SUPPLY
NEW 8" CHILLED WATER RETURN
NEW 8" CHILLED WATER SUPPLY
M-116
M-116
M-116
M-116
8"øCWR
8"øCWS
2"øHWS
6"øSTM
4"øSTC 4"øCA
2"øHWR
4" ø C W S
4" ø C W R
4" ø C W R
4" ø C W S
1 1/2"øHWR
1 1/2"øHWR
1 1/2"øHWS
1 1/2"øHWR
1 1/2"øHWS
1 1/2"øHWR 1 1/2"øHWS
1"øHWS
1"øHWR
1"øHWS 1"øHWR
1"øHWS
1"øHWR
1"øCA 1"øCA1"øCA
1" ø C A
6"øSTM
4"øSTC
4"øCA
8"øCWR
8"øCWS
D
M-407
M-407
AHU- 14.5 AHU- 14.6
2"øSTC 3"øSTM
(100# TO BLDG 26)
(BELOW CWS)
1 1/2"øHWS
VAVS- 1050
VAVS- 1049
VAVS- 1061
VAVS- 1055
VAVS- 1047
VAVS- 1048
VAVS- 1048B
VAVS- 1053
1"øCA
VAVS- 1057
VAVS- 1065
VAVS- 1066
VAVS- 1067
VAVS- 1062
VAVS- 1060
VAVS- 1063
VAVS- 1090
VAVS- 1112
VAVS- 1051
VAVS- 1052
VAVS- 1054
VAVS- 1058
VAVS- 1059
VAVS- 1068
VAVS- 1120
STCP-1
DASHED PIPING TO BE
DEMOLISHED, TYPICAL.
3/4" HWS/HWR TAP WITH BALL
VALVES. CAP AFTER 8".
3/4" HWS/HWR TAP WITH BALL
VALVES. CAP AFTER 8".
3/4" HWS/HWR TAP WITH BALL
VALVES. CAP AFTER 8".
3/4" HWS/HWR TAP
WITH BALL VALVES.
CAP AFTER 8".
2" CWS/CWR TAP
WITH BALL VALVES.
CAP AFTER 1'.
2" CWS/CWR TAP
WITH BALL VALVES.
CAP AFTER 1'.
DASHED PIPING TO BE
DEMOLISHED, TYPICAL.
CROMWELL
ARCHITECTS/
ENGINEERS
#5A
R
KANSAS -ENG
IN
EE
R
C E R T
IF
IC
AT
EOF
AUTHORIZ
A T
IO
N PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 12957
S T A T E O F
M A
X W
E L L A . G O
O D
15-JUL-2015
SHEETDRAWING NOSUBMITTED
SCALE DATE DRAWN CHECK
REVISIONS
NO. DATE DESCRIPTION BY CHECK
JEFFERSON,ARKANSAS 72079
NATIONAL CENTER FOR TOXICOLOGICAL RESEARCH
N C T R
BUILDING 14 RENOVATION
MECHANICAL PLATFORM PIPING PLAN PHASE TWO
M-11507/15/2015
1/8" = 1'-0"
1 MECHANICAL PLATFORM PIPING PLAN PHASE 2
KEYED NOTES:
1. CONNECT TOTHE EXISTING BELOW GRADE 8" CHILLED WATER SUPPLY AND CHILLED
WATER RETURN IN THIS VICINITY. FIELD VERIFY THE EXACT POINT OF CONNECTION AND
INVERT.
2. BREAK THE EXISTING BELOW GRADE 8" CHILLED WATER SUPPLY AND RETURN FEEDS TO
THE BUILDING IN THIS VICINITY AND DEMOLISH ALL EXISTING CHILLED WATER SUPPLY
AND CHILLED WATER RETURN LOCATED INSIDE THE BUILDING.
3. VALVE AND CAP 3" HWS AND HWR BRANCH LINES FOR FUTURE.
4. REGION INDICATES LOCATION OF THERMAL EXPANSION LOOPS. PROVIDE EXPANSION
LOOPS IN THIS LOCATION IN THE ALL STEAM, STEAM CONDENSATE, AND HEATING WATER
PIPING. EXPANSION LOOPS SHALL BE EQUAL TO METRAFLEX METRALOOP, LINE SIZED,
DESIGNED FOR 4" EXPANSION. PROVIDE NESTED INSTALLATION. SUBMIT
MANUFACTURER'S SHOP DRAWINGS FOR THE NESTED DESIGN FOR APPROVAL.
5. APPROXIMATE HIGH POINT OF STEAM/STEAM CONDENSATE PITCH.
6. END OF PHASE 2 WETTED PIPING. TRAP THE STEAM PIPING UPSTREAM OF THE
ISOLATION VALVE. THE PIPING SHOWN DOWNSTREAM OF THIS LOCATION SHALL BE
INSTALLED, BUT SHALL REMAIN DRY.
7. 8" CHILLED WATER SUPPLY AND RETURN STUB-OUTS VALVED AND CAPPED FOR FUTURE.
8. STEAM DUPLEX CONDENSATE PUMP/RECEIVER SHALL BE EQUAL TO A SPIRAX-SARCO
#VAS-803, 208/3/60, 5 HP PUMPS, 30 PSIG DISCHARGE PRESSURE, AND 110 GALLON
RECEIVER. VENT TO THE NEAREST EXTERIOR WALL IN STRICT ACCORDACEN WITH THE
MANUFACTURER'S INSTRUCTIONS. VENT SHALL NOT PENETRATE THE ROOF.
NORTH
SCALE : 1/8" = 1'-0"
0 4 8 16
IDENTIFICATION:
PIPING SHALL BE IDENTIFIED BY SYSTEM AND DIRECTION OF FLOW AS STATED BELOW:
1. PIPING MAINS SHALL BE IDENTIFIED EVERY TWENTY FEET.
2. BRANCHES FROM MAIN SHALL BE IDENTIFIED AT TAKE OFF FROM MAIN, AT THE END OF EACH
BRANCH AND EVERY TWENTY FEET.
IDENTIFICATION SHALL BE ABLE TO BE READ FROM PERSONNEL WHILE AT FLOOR LEVEL. FINAL
SYSTEM ABBREVIATIONS AND NOMENCLATURE BY CONTRACTING OFFICER.
GENERAL NOTES:
1. REFER TO SHEET M-001 FOR ALL ABBREVIATIONS,
LEGENDS AND GENERAL NOTES.
2. CONTRACTOR SHALL FURNISH AND INSTALL
VALVING AT EACH BRANCH FROM MAIN PIPING AND
AT ALL ENDS OF MAINS (WHETHER SHOWN OR
NOT). VALID FOR ALL SYSTEMS AND ALL PHASES.
3. ALL HWS AND HWR LINES SERVING VAV TERMINAL
SHALL BE 3/4" UNLESS SPECIFICALLY STATED
OTHERWISE. CONTRACTOR SHALL FURNISH AND
INSTALL ISOLATION VALES AT MAIN PIPING AS WELL
AS THOSE SHOWN IN DETAIL.
4. ALL PIPING TAKE OFFS SHALL TAKEN OFF OF TOP
OF MAIN PIPING.
5. CONTRACTOR SHALL INSTALL ALL VALVES SO THAT
THE VALVE OPERATOR IS AT TOP OF PIPE AND THE
VALVE OPERATOR IS NOT BE IMPEDED
THROUGHOUT ITS ENTIRE RANGE.
E
8"øCWR
8"øCWS
6"øSTM
4"øSTC
4"øCA
3/4"øHWR 3/4"øHWS
3/4"øHWS 3/4"øHWR
1/ 2" ø H W S
1/ 2" ø H W R
VAVS- 1048B
VAVS- 1057
3/4"øHWR
3/4"øHWS
1" ø H W S
1" ø H W R
VAVS- 1048
2"øHWR
D m-fp02
11' - 2"
F
EXISTING LINE LEVEL
16' - 2"
4"øSTC 4"øCA
6"øSTM
STCP-1
END OF PHASE 2 WETTED PIPING - VALVE AND KEEP ALL PIPING
DOWNSTREAM OF THESE VALVES DRY UNTIL THEY ARE
EXTENDED TO BACKFFED BUILDING 26 IN A FUTURE PHASE -
TRAP THE STEAM PIPING
m-fp02
11' - 2"
2"øHWR
2"øHWS
6"øSTM
4"øSTC
4"øCA
D m-fp01
0" m-fp02
11' - 2"
4"øCA
6"øSTM
END OF PHASE 2 PIPING - CAP
AND VALVE FOR FUTURE
EXTENSION TO BUILDING 26
PROVIDE 24" BY 24" HINGED
ACCESS PANEL SO THAT
MAINTENANCE PERSONNEL
MAY ACCESS VALVES.
CROMWELL
ARCHITECTS/
ENGINEERS
#5A
R
KANSAS -ENG
IN
EE
R
C E R T
IF
IC
AT
EOF
AUTHORIZ
A T
IO
N PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 12957
S T A T E O F
M A
X W E L L A . G
O
O D
15-JUL-2015
SHEETDRAWING NOSUBMITTED
SCALE DATE DRAWN CHECK
REVISIONS
NO. DATE DESCRIPTION BY CHECK
JEFFERSON,ARKANSAS 72079
NATIONAL CENTER FOR TOXICOLOGICAL RESEARCH
N C T R
BUILDING 14 RENOVATION
MECHANICAL PLATFORM PIPING SECTIONS AND
ENLARGED PLANS PHASE TWO
M-11607/15/2015
1/4" = 1'-0"
1 ENLARGED MECHANICAL PLATFORM PIPING PLAN PHASE 2
1/4" = 1'-0"
3 MECHANICAL PIPING SECTION CANOPY ONE
1/4" = 1'-0"
2 MECHANICAL PIPING SECTION PHASE TWO
1/4" = 1'-0"
4 MECHANICAL PIPING SECTION CANOPY TWO
SCALE : 1/4" = 1'-0"
0 2 4 8
SCALE : 1/4" = 1'-0"
0 2 4 8
SCALE : 1/4" = 1'-0"
0 2 4 8
SCALE : 1/4" = 1'-0"
0 2 4 8
5 7 8 9 10
B
C
E
F
VAVS- 1050
VAVS- 1049
AHU- 14.5
AHU- 14.6
VAVS- 1054
VAVS- 1052
VAVS- 1051
VAVS- 1059
VAVS- 1068
VAVS- 1067
VAVS- 1066
VAVS- 1058
VAVS- 1055
VAVS- 1047
VAVS- 1048
12"ø
VAVS- 1057
VAVS- 1048B
VAVS- 1053
14"x14" 8"ø
10"ø 14"x14"
20"x14"
12"ø
10"ø
4" x2 0"
4" x1 4"
2" x3 0"
16"x14"
LI-5
LI-6
LE-6
LE-5LE-4
6" x2 4"
6" x2 4"
VAVS- 1061
6" x3 4"
6" x3 4"
6" x3 4"
6" x3 4"
14"x14"
20"x14" 1
0" ø
2" ø
12"ø
20"x14"
20"x14"
VAVS- 1060
VAVS- 1062
VAVS- 1063
VAVS- 1065
VAVS- 111220"x14"
20"x14"
4" x1 4"
14"x14"
14"x14"
44"x36" 44"x36"
VAVS- 1120
6"ø
0" x1 0"
12"ø
4" x2 0"
8"ø
8"ø
14"x14"
14"x14"
4" x1 4"
VAVS- 1090
0" x1 0"
2" ø
0" ø
"ø
"ø1 2" ø
10"x10"
AHU- UTE
CU- UTE
14"x14"
10"ø
14"x14"
CUVRV- 2N
CUVRV- 2S
20"x20"
14"x14"
14"x14"
8"ø
8"ø
16"x14"
14"x14"
CONNECT AHU-4 TO SUPPLY PLENUM
54"x26"
CONNECT AHU-4 TO NEW
OUTSIDE AIR SYSTEM
EF- MASS SPEC 3
EF- MASS SPEC 4
12"ø 20"x14"
20"x14"
14"x14"
8"ø
8"ø
8"ø
54"x26"
54"x26"
THIS AREA SHALL
REMAIN
UNOBSTRUCTED
FOR REQUIRED UNIT
CLEARANCE
PIPING
CONNECTIONS,
COIL PULL, FILTER
AND ALL MAIN
MAINTENANCE
ACCESS THIS SIDE
OF UNIT.
THIS AREA SHALL
REMAIN
UNOBSTRUCTED
FOR REQUIRED UNIT
CLEARANCE
PIPING
CONNECTIONS,
COIL PULL, FILTER
AND ALL MAIN
MAINTENANCE
ACCESS THIS SIDE
OF UNIT.
THIS AREA SHALL REMAIN
UNOBSTRUCTED FOR
REQUIRED UNIT CLEARANCE
PIPING CONNECTIONS,
COIL PULL, FILTER AND
ALL MAIN MAINTENANCE
ACCESS THIS SIDE OF
UNIT.
D
HS-AHU14.5
HS-AHU14.6
HS-AHU14A2
6 6
M-405
M-406
M-407
M-406
VF- 2.1N VF- 2.2N VF- 2.3N VF- 2.4N
VF- 2.1S VF- 2.2S VF- 2.3S VF- 2.4S
7 7
4"ø 2"ø
4"ø
4"ø
6"ø
3"ø
8 8 8 8
9 9 9 9
CROMWELL
ARCHITECTS/
ENGINEERS
#5A R
K
ANSAS -ENG
IN
EE
R
C E R T
IF
IC
AT
EOF
AUTHORIZ
A T
IO
N
PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 12957
S T A T E O F
M A
X W E L L A . G
O
O D
15-JUL-2015
SHEETDRAWING NOSUBMITTED
SCALE DATE DRAWN CHECK
REVISIONS
NO. DATE DESCRIPTION BY CHECK
JEFFERSON,ARKANSAS 72079
NATIONAL CENTER FOR TOXICOLOGICAL RESEARCH
N C T R
BUILDING 14 RENOVATION
MECHANICAL PLATFORM SUPPLY RENOVATION PHASE
TWO
M-11707/15/2015
1/8" = 1'-0"
1 MECHANICAL PLATFORM RENOVATION SUPPLY PLAN PHASE TWO
SCALE : 1/8" = 1'-0"
0 4 8 16
NORTH
KEYED NOTES:
1. SUPPLY DUCTWORK TO CRITICAL SPACES
BELOW.
2. GENERAL VENTILATION DUCTWORK THROUGH
PLATFORM TO SERVE SPACES BELOW.
3. VENTILATION DUCTWORK FOR OFFICE SPACES
SEE FLOOR PLAN. VAV TERMINAL SERVING
SYSTEM SHALL BE ENABLED AND DISABLED ON
AN ADJUSTABLE SCHEDULE.
4. AIR HANDLING UNIT EXHAUST SHALL BE
CONNECTED TO NEW LOUVER SHOWN.
EXISTING EXHAUST DUCT PENETRATION TO BE
REPAIRED AND SEALED WATER AND AIR TIGHT.
5. CONTRACTOR SHALL FURNISH AND INSTALL NEW
STEAM HUMIDIFIER FOR AIR HANDLING UNIT.
6. EACH AIR HANDLING UNIT SHALL BE FURNISHED
AND INSTALLED WITH DAMPERS ON MAIN
SUPPLY AND RETURN CONNECTIONS. DAMPERS
SHALL CLOSE DURING UNIT ALARM AND FAILURE.
DAMPER STATUS SHALL BE MONITORED BY
BUILDING 54. DAMPER ACTUATORS TO BE
PROVIDED BY THE CONTROLS CONTRACTOR.
7. NEW SUPPLY SIDE DAMPER. DAMPER SHALL BE
INSTALLED DOWNSTREAM OF HUMIDIFIER.
STATIC PRESSURE SHALL BE MEASURED
DOWNSTREAM OF DAMPER. UNIT SHALL
MAINTAIN 1.15 IN W.G. AT PLENUM, ADJ. INTENT
IS THAT PRESSURE IN LOW PRESSURE
DUCTWORK SERVING LABS BE APPROXIMATELY
0.01 IN W.G. DURING NORMAL OPERATION. VAV
TERMINALS SHALL MODULATE HOT WATER
COILS TO MAINTAIN TEMPERATURE. SUPPLY
AIR VOLUME TO INCREASE TO MAINTAIN OFFSET
UPON INCREASE OF EXHAUST, DUE TO LAB
HOOD USE.
8. VENTILATION FAN SERVING MECHANICAL
PLATFORM. THREE TEMPERATURE SENSORS
SHALL BE MOUNTED IN SPACE, NEAR MAIN
AIRHANDLING UNIT CONTROL PANELS.
THERMOSTATS SHALL BE AVERAGED AND UPON
SETPOINT, ADJ BY OWNER, SHALL DETERMINE
OPERATION OF FAN. FAN SHALL BE MONITORED
FOR ALARM FROM BUILDING 54. DIRECTION OF
FLOW SHALL BE INTO SPACE.
9. VENTILATION FAN SERVING MECHANICAL
PLATFORM. THREE TEMPERATURE SENSORS
SHALL BE MOUNTED IN SPACE, NEAR MAIN
AIRHANDLING UNIT CONTROL PANELS.
THERMOSTATS SHALL BE AVERAGED AND UPON
SETPOINT, ADJ BY OWNER, SHALL DETERMINE
OPERATION OF FAN. FAN SHALL BE MONITORED
FOR ALARM FROM BUILDING 54. DIRECTION OF
FLOW SHALL BE OUT OF SPACE.
GENERAL NOTES:
1. ALL CONDENSATE SHALL BE ROUTED TO NEAREST
ROOF DRAIN. CONDENSATE SHALL BE RUN FULL
SIZE. MATERIAL SHALL BE COPPER. FULLY
INSULATE LINE. LINES SHALL BE MOUNTED AND
SUPPORTED BY STRUCTURE OR FROM PLATFORM
THROUGH THE USE OF SYSTEM INTENDED FOR
ROOFTOP SUPPORT, EQUAL TO B-LINE DURA-BLOK
SYSTEM.
2. SUPPLY PLENUM FROM ALL AIRHANDLING UNITS
SHALL BE SUPPORTED FROM PLATFORM THROUGH
THE USE OF SYSTEM INTENDED FOR ROOFTOP
SUPPORT, EQUAL TO B-LINE DURA-BLOK SYSTEM.
3. DEDICATED EXHAUST SYSTEM SHALL BE PVC
PIPING, DOWNSTREAM ON FAN. UPSTREAM OF FAN
DUCT SHALL BE STANDARD GALVANIZED. FULLY
INSULATE EXHAUST SYSTEM IN EQUIPMENT AREA.
ALL FEEDS FROM SYSTEM SHALL BE PROVIDED
WITH MEANS TO BALANCE AND ADJUST FLOW.
4. SYSTEMS TO BE INSTALLED IN PHASE ONE AND
PHASE TWO ARE SIMILAR. CONSTRUCTION
DOCUMENTS PERTAINING TO SYSTEMS FOUND ON
SHEETS NOTED FOR PHASE ONE SHALL BE VALID
FOR PHASE TWO, AND VISE VERSA. IN THE EVENT
OF A CONTRADICTION, THE MORE STRINGENT
REQUIREMENT SHALL DICTATE WORK.
B
C
E
F
CU- UTE
AHU- UTE
VAVGE- 1056
8"x8"
"ø
26"x20"
6" x2 0"
14"x14"
14"x14" 14"x14"
16"x14"
2" ø
"ø
VAVGE- 1047
VAVHE- 1047SW
6" x3 4"
6" x3 4"
6" x3 4"
VAVHE- 1047SE
8"ø
VAVHE- 1055S
8"ø
"ø 1 2" ø
VAVHE- 1055N
VAVGE- 1055
VAVGE- 1062
VAVHE- 1062S
2" ø
"ø
20"x18"
"ø
"ø
VAVHE- 1063S
VAVHE- 1062N
0" x2 4"
32"x28"
8" x2 0"
46"x30"46"x30"
6" x3 4"
6" x3 4"
AHU- 14.6
AHU- 14.5
M-118
2 2
CUVRV- 2S
1 2
3 3
VAVGE- 1063
VAVGE- 1065
VAVHE- 1063N
12"ø
12"ø
8"ø
VAVGE- 1066
VAVHE- 1066S
8"ø
8"ø
12"ø
VAVHE- 1067N
VAVHE- 1068S
VAVGE- 1067
VAVGE- 1068
VAVHE- 1059S
VAVGE- 1059
VAVGE- 1058
VAVHE- 1058N
VAVGE- 1054
14"x14"
10"ø
8"ø
8"ø
12"ø
10"ø
12"ø
10"ø
8"ø
8"ø
VF- 2.1N VF- 2.2N VF- 2.3N VF- 2.4N
CUVRV- 2N
VF- 2.1S VF- 2.2S VF- 2.3S VF- 2.4S
LE-5 LE-6
LI-5 LI-6
LI-UTE
2" x2 8"
2" x2 6"
VAVGE- 1057
D
C
8" x2 0"
8"ø
12"ø
VAVGE- 1048
VAVHE- 1049S
4" x2 0"
VAVGE- 1049
VAVHE- 1048N
VAVHE- 1048B
VAVGE- 1048
8"ø
8"ø
8"ø
14"x14" 8"ø
12"ø
8"ø
"ø
6" x3 4"
8"ø
8"ø
8"ø
8"ø
1 2
D
VAVGE- 1051
VAVHE- 1051S
8"ø
10"ø
8"ø
22"x14"
VAVHE- 1057W
CROMWELL
ARCHITECTS/
ENGINEERS
#5A R
K
ANSAS -ENG
IN
EE
R
C E R T
IF
IC
AT
EOF
AUTHORIZ
A T
IO
N
PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 12957
S T A T E O F
M A
X W
E L L A . G O
O D
15-JUL-2015
SHEETDRAWING NOSUBMITTED
SCALE DATE DRAWN CHECK
REVISIONS
NO. DATE DESCRIPTION BY CHECK
JEFFERSON,ARKANSAS 72079
NATIONAL CENTER FOR TOXICOLOGICAL RESEARCH
N C T R
BUILDING 14 RENOVATION
MECHANICAL PLATFORM RETURN RENOVATION PLAN
PHASE TWO
M-11807/15/2015
1/8" = 1'-0"
1 MECHANICAL PLATFORM RENOVATION RETURN PLAN PHASE TWO
SCALE : 1/8" = 1'-0"
0 4 8 16
NORTH
1/4" = 1'-0"
2 PHASE TWO RETURN ENLARGED PLAN
NORTH
SCALE : 1/4" = 1'-0"
0 2 4 8
KEYED NOTES:
1. EXHAUST TERMINAL SERVING GENERAL EXHAUST.
2. EXHAUST TERMINAL SERVING HOOD. IN THE EVENT HOOD DOES NOT REQUIRE
EXHAUST OR PARTIAL EXHAUST SCHEDULED, TERMINAL SHALL BE INSTALLED
AS SHOWN AND AIRFLOW SHALL BE BALANCED TO THAT REQUIRED. IF NONE
REQUIRED, EXTEND DUCT ONE FOOT INTO ROOM AND CAP.
3. RETURN DUCTWORK SERVING ULTRA COOL ROOM.
4. DUCTWORK BELOW DECK.
B
C
E
F
PCR LAB
ACBPCR LAB
HIGH CONCENTRATION
PREP LAB
1059 PROTEOMICS MASS SPEC
LAB
LOW CONCENTRATION
PREP LAB
SAMPLE PREP
MASS SPEC LAB
CELL CULTURE LAB
PENCE MASS SPEC LAB
HUMAN SAMPLE PREP
CHEMISTRY LAB
RAPID B-FLOW
CYTOMETRY
GENERAL STORAGE
ULTRA COOL
MOLECULAR LAB 1
OMIPRINT MS LAB
AMES LAB
CELL LAB
1048B
TC LAB
TC LAB
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
ENTRY
VENDING
1090 OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
1098 OFFICE
OFFICE
LOBBY S.E.
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
LOBBY N.E.
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
SPRINKLER
OFFICE
OFFICE
VENDING
ENTRY
28"x14"
C- 1330
2 26"x14"
A- 205
(TYPICAL 6)
C- 1800
C- 1330
26"x14"
A- 270
(TYPICAL 6)
A- 205
(TYPICAL 6)
B- 900 A- 270
(TYPICAL 3)
A- 270
(TYPICAL 3)
C- 1330
B- 900
A- 205
(TYPICAL 6)
2A- 205
(TYPICAL 6)
28"x14"
28"x14"
26"x14"
14"x14"
26"x14"
26"x14" 14"x14"
28"x14"
26"x14"
26"x14"
28"x14"
C- 1430
B- 900
14"x14"
A- 270
26"x14"
28"x14"
C- 1800
2 26"x14"
A- 270
(TYPICAL 6)
D- 75
8"x8"
(TYPICAL 3)
28"x14"
C- 1430
A- 250
(TYPICAL 3) 1B- 900
14"x14"
26"x14"
A- 270
(TYPICAL 6) 2
26"x14"
A- 270
(TYPICAL 6)
26"x14"
A- 205
(TYPICAL 6)
28"x14" C- 1800
VRVSC- 2.1 VRVSC- 2.2 VRVSC- 2.3 VRVSC- 2.4 VRVSC- 2.5 VRVSC- 2.6 VRVSC- 2.7 VRVSC- 2.8 VRVSC- 2.9 VRVSC- 2.10
VRVSC- 2.15
VRVSC- 2.14
VRVSC- 2.13
VRVSC- 2.12
VRVSC- 2.11
VRVNC- 2.1 VRVNC- 2.2 VRVNC- 2.3
VRVNW- 2.1
VRVNC- 2.15
VRVNC- 2.4 VRVNC- 2.5 VRVNC- 2.6 VRVNC- 2.7 VRVNC- 2.8 VRVNC- 2.9
VRVNC- 2.11
VRVNC- 2.12
VRVNC- 2.13
VRVNC- 2.14
VRVNW- 2.2
A- 205
(TYPICAL 6)
VRVSW- 2.2
VRVSW- 2.3
VRVNW- 2.2
M-119
D- 900
"x
24"x10"
(TYPICAL 5)
(TYPICAL 5)
14"x14"
14"x14"
14"x14"
E- 500
(TYPICAL 4)
slope slope sl op e sl op e slope slopeslope
D- 75
F
F
M-401
M-401
M-401
3"ø2"ø
2"ø 3"ø
2"ø
3"ø 4"ø
1" AND 3/4"
DROPS,
TYPICAL
14"x14"
12"x12"
E- 900
E- 200
"x
E- 900
14"x14"
E- 200
E- 900
E- 200
12"x12"
14"x14"
D
T T T T T T T T T T T
10"x8" 8"x8" 4"ø10"x8"8"x8"
4"ø
TYPICAL ALL
4"ø
TYPICAL ALL
8" x8
"x 8"
"x
8"
VENTILATION
DUCTWORK
FROM ABOVE
4" ø
8" x8
10"x8"
4"ø
TYPICAL ALL
VENTILATION
DUCTWORK
FROM ABOVE
10"x10"10"x8"4"ø 8"x8" 10"x8"
VENTILATION DUCTWORK FROM ABOVE 10"x10"
10"x10"
T
T
T
T
T
T
T
T
T
T
T
TTTTTTTTTT
T
VRVSW- 2.1
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
10"x24"
VRVNW- 2.3
VRVSW- 2.4
sl op e2"ø
6 DROPS, REFER TO DETAIL
ONE DEDICATED EXHAUST
SHEET
2 DROPS, REFER TO DETAIL FIVE
DEDICATED EXHAUST SHEET
2"ø
4 DROPS,
REFER TO
DETAIL FIVE
DEDICATED
EXHAUST
SHEET
INDOOR UNITS SHALL BE PROVIDED WITH THERMOSTAT MOUNTED ON
WALL NEAR UNIT, FINAL LOCATION BY CONTRACTING OFFICER.
(TYPICAL ALL SHEETS, ALL PHASES)
FINAL LOCATION SHALL BE
COORDINATED WITH FINISHES. FINAL
LOCATION BY CONTRACTING OFFICER.
T
T
FINAL LOCATION SHALL BE
COORDINATED WITH FINISHES. FINAL
LOCATION BY CONTRACTING OFFICER.
C
AMES LAB
CELL LAB
1048B
MOLECULAR LAB 1
ACBPCR LAB
TC LAB
TC LAB
CORRIDOR
CORRIDOR
8"ø
8" ø
14"x14"8"ø
VAVGE- 1050
8"ø 8"ø
8"ø14"x14"
VAVGE- 1053
VAVHE- 1053W
28"x14"
14"x14"
8"ø
8"ø
14"x14"
8"ø28"x14"
26"x14" 26"x14"
B- 900
C- 1800
26"x14"
A- 400
(TYPICAL 2)
B- 900
A- 400
(TYPICAL 2)
A- 400
(TYPICAL 2)
A- 400
(TYPICAL 2)
B- 900 B- 900
C- 1430
VAVHE- 1050S
D
CROMWELL
ARCHITECTS/
ENGINEERS
#5A
R
KANSAS -ENGIN
EE
R
C E
R T
IF
IC
ATEOFAUTHORIZ
A
T
IO
N PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 12957
S T A T E O F
M A
X W
E L L A . G O
O D
15-JUL-2015
SHEETDRAWING NOSUBMITTED
SCALE DATE DRAWN CHECK
REVISIONS
NO. DATE DESCRIPTION BY CHECK
JEFFERSON,ARKANSAS 72079
NATIONAL CENTER FOR TOXICOLOGICAL RESEARCH
N C T R
BUILDING 14 RENOVATION
MECHANICAL FLOOR PLAN RENOVATION PHASE TWO
M-11907/15/2015
1/8" = 1'-0"
1 MECHANICAL FLOOR PLAN RENOVATION PLAN PHASE TWO
SCALE : 1/8" = 1'-0"
0 4 8 16
NORTH
1/4" = 1'-0"
2 MECHANICAL FLOOR ENLARGED PLAN PHASE TWO
NORTH
SCALE : 1/4" = 1'-0"
0 2 4 8
KEYED NOTES:
1. GENERAL EXHAUST DUCTWORK FROM ABOVE.
2. SUPPLY DUCTWORK FROM ABOVE.
3. FUME HOOD DUCTWORK FROM ABOVE.
4. RETURN SERVING UTLRA COOL ROOM.
5. SUPPLY SERVING UTLRA COOL ROOM.
GENERAL NOTES:
1. SEE DETAIL SHEETS FOR CONSTRUCTION AND INSTALLATION DETAILS FOR FURTHER DETAILING ON
SUPPLY, EQUIPMENT EXHAUST, GENERAL EXHAUST AND FUME HOOD EXHAUST SYSTEMS.
2. ALL OFFICES AND LABS SHALL HAVE INDIVIDUAL THERMOSTATS, WHETHER SHOWN ON PLANS OR
NOT. THERMOSTAT LOCATION SHALL NOT INTERFERE WITH EQUIPMENT OR BE IN DIRECT
SUNLIGHT. FINAL LOCATION BY GOVERNMENT'S REPRESENTATIVE.
3. ALL INDOOR VRF UNITS SHALL HAVE ISOLATION VALVES TO ALLOW FOR REMOVAL OF ANY UNIT
FROM SYSTEM WITHOUT CAUSING A SHUTDOWN. VALVING SHALL BE EASILY ACCESSIBLE FROM
SPACE.
4. CONTRACTOR SHALL PROVIDE SAMPLE THERMOSTAT TO CONTRACTING OFFICER FOR FINAL
APPROVAL. THERMOSTAT SHALL BE NON-READOUT TYPE.
m-fp01
0"
FINISHED FLOOR
0' - 0"
2.5
BALL VALVE
2"ø
1"ø 3/4"ø
1"ø 3/4"ø 1"ø
2"ø
OPEN END. TURN UP
BEFORE PIPE TERMINATION.
3/4"ø
THREADED PIPE PLUG (TYPICAL 6)
FOUR INCH (MIN) NIPPLE (TYPICAL 6)
slope slope m-fp01
0" m-fp02
11' - 2" slope slope
3"ø 3"ø
4"ø
4"ø
2"ø
BALL VALVE
CLEAR TUBING
SUPPORT FROM
UNITSTRUT FRAME.
NOTE:
FINAL LOCATION OF SYSTEM
AND DRAIN SHALL BE
DETERMINED BY OWNER.
D m-fp01
0"
2"ø
BALL VALVE
1"ø
1"ø
1"ø
BALL VALVE BALL VALVE
CLEAR TUBING
SUPPORT FROM
UNITSTRUT FRAME.
NOTE:
FINAL LOCATION OF SYSTEM AND DRAIN
SHALL BE DETERMINED BY OWNER.
m-fp01
0" m-fp02
11' - 2" slope slope
OPEN END. TURN
UP BEFORE PIPE
TERMINATION.
BALL VALVE
BALL VALVE
3"ø
3/4"ø 1"ø 3/4"ø
1"ø
3/4"ø
1"ø
BALL VALVE
CLEAR TUBING
4"ø
BALL VALVE
(TYPICAL)
TAP
(TYPICAL)
CLEAR TUBING
TYPICAL 3/4" DROP
SEE SECTION THIS PAGE TYPICAL 1" DROP
SEE SECTION THIS PAGE
NOTE:
FINAL LOCATION OF SYSTEM
AND DRAIN SHALL BE
DETERMINED BY OWNER. SUPPORT DROP FROM
UNISTRUT, TYPICAL ALL.
m-fp01
0" m-fp02
11' - 2"
C
CLEAR TUBING
BALL VALVE, TYPICAL
1"ø
3/4"ø
3/4"ø
1"ø
THREADED PLUG, TYPICAL
DROP TO BE TAKEN OFF OF TOP OF MAIN
m-fp01
0" m-fp02
11' - 2"
C
DROP TO BE TAKEN OFF OF TOP OF MAIN
CLEAR TUBING THIS SECTION
BALL VALVE, TYPICAL
3/4"ø
THREADED PLUG
3/4"ø
CROMWELL
ARCHITECTS/
ENGINEERS
#5A
R
KANSAS -ENG
IN
EE
R
C E R T
IF
IC
AT
EOF
AUTHORIZ
A T
IO
N PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 12957
S T A T E O F
M A
X W E L L A .
G O
O D
15-JUL-2015
SHEETDRAWING NOSUBMITTED
SCALE DATE DRAWN CHECK
REVISIONS
NO. DATE DESCRIPTION BY CHECK
JEFFERSON,ARKANSAS 72079
NATIONAL CENTER FOR TOXICOLOGICAL RESEARCH
N C T R
BUILDING 14 RENOVATION
MECHANICAL SECTIONS DEDICATED EXHAUST
M-40107/15/2015
1/2" = 1'-0"
1 MASS SPEC SECTION ROOMS 1007, 1008, 1009, 1010, 1047
SCALE : 1/2" = 1'-0"
0 1 2 4
1/2" = 1'-0"
2 MASS SPEC RISE ROOM 1008
SCALE : 1/2" = 1'-0"
0 1 2 4
3 TMP LAB 1012
RELOCATED EQUIPMENT FOR TMP LAB. (TYPICAL 2)
PROVIDE WITH 2" PVC PIPING
MAIN WITH VALVE.
PROVIDE WITH 1" PVC PIPING
BRANCH WITH VALVE. SLOPE
TO EQUIPMENT.
SUPPORT FROM WALL AS REQUIRED
NOTE:
EXHAUST PIPING SERVING EQUIPMENT
SHALL BE CONNECTED TO MAIN HOOD
EXHAUST IN ROOM AND PERFORM IN
SIMILAR MANNER AS IT CURRENTLY DOES.
PIPING SHALL NOT BE RUN IN "L"
CONFIGURATION.
1/2" = 1'-0"
4 MASS SPEC ROOM 1013
SCALE : 1/2" = 1'-0"
0 1 2 4
1/2" = 1'-0"
5 TYPICAL PHASE TWO MASS SPEC EXHAUST SYSTEM
SCALE : 1/2" = 1'-0"
0 1 2 4
1/2" = 1'-0"
6 TYPICAL 1" DROP
1/2" = 1'-0"
7 TYPICAL 3/4" DROP
SCALE : 1/2" = 1'-0"
0 1 2 4
SCALE : 1/2" = 1'-0"
0 1 2 4 m-fp02
11' - 2" m-fp03
30' - 4"
A B C
AHU- UTW
DUCTWORK TO LOUVER. FURNISH AND
INSTALL MOTORIZED DAMPER IN
DUCTWORK. DAMPER SHALL OPEN
DURING ECONOMIZER MODE.
PROVIDE DAMPER IN DUCTWORK
DOWNSTREAM OF ECONOMIZER DUCTWORK.
DAMPER SHALL BE NORMALLY OPEN AND
CLOSE DURING ECONOMIZER MODE.
RETURN DUCT
SUPPLY DUCT
DUCTWORK DROPS SHALL NOT
INTERFERE WITH UNIT CLEARANCES.
"x
"x
20"x20" 20"x36"
"x
"x
"x "18"x18"
SUPPLY AIR TO
BE DIRECTED
BETWEEN
AISLES
RETURN AIR TO
BE TAKEN FROM
ABOVE ULTRA
COOL UNITS
NOTES:
1. IN THE EVENT OF A SUBSTITUTION, IT IS THE FULL
RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE
A FULLY FUNCTIONAL SYSTEM. CONTRACTOR SHALL
PROVIDE NEW DESIGN INCLUDING STRUCTURE,
DUCTWORK LAYOUT, ELECTRICAL SYSTEM AND ALL
SUPPORTING DETAILING SEALED BY ENGINEER
LICENSED IN THE STATE.
2. CONDENSATE TO BE ROUTED FULL SIZE TO ROOF
DRAIN. PIPING SHALL BE SUPPORTED FROM DECK.
m-fp02
11' - 2"
A
1' - 0"
TYPICAL INTAKE AND
EXHAUST LOUVER.
INSECT SCREEN.
MINIMUM 1' FULL SIZE PLENUM.
PLENUM SHALL SLOPE
GRADUALLY BACK TO LOUVER.
MAIN DUCTWORK
CONNECTION TO MAIN DUCTWORK SHALL BE
MADE WITH TRANSITION SIMILAR TO THAT
SHOWN. TRANSITION SHALL SLOPE TO LOUVER.
COORDINATE NECESSARY
FRAMING OF LOUVER WITH
EXISTING STRUCTURE.
NOTE:
1. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE THE AVAILABLE
SPACE WITH THE SIZE OF ALL LOUVERS AND FRAMING SYSTEM FOR ALL LOUVERS.
2. IF ABSOLUTELY NECESSARY, THE LOUVER DIMENSION MAY BE ALTERED TO BE
MOUNTED IN AVAILABLE SPACE, PROVIDED THE FREE AREA OF THE ORIGINAL DESIGN
IS MAINTAINED.
3. ADDITIONAL COST INCURRED BY SUBSTITUTION IS THE RESPONSIBILITY OF THE
CONTRACTOR.
m-fp02
11' - 2" m-fp03
30' - 4"
A B C E FD
AHU- 14.1
LI-1
24"x66"
VAVS- 1006 10"ø
20"x14"
26"x14"
SUPPLY DUCTWORK SERVING
ULTRA COOL ROOM 1002.
SUPPLY DUCTWORK SERVING
ULTRA COOL ROOM 1002.
VAVGE- 1007
RETURN PLENUM, MATCH
UNIT OPENING DIMENSION.
DEDICATED MASS
SPEC EXHAUST.
NEW POLYPROPYLENE EXHAUST
DUCT SERVING TMP LAB.
"x
SUPPLY PLENUM, MATCH
UNIT OPENING DIMENSION.
FIRST ELBOW OF EACH EXHAUST FAN
SHALL BE PROVIDED WITH FLANGED,
REMOVABLE, CONNECTIONS.
OUTSIDE AIR DUCTWORK
EXHAUST DUCTWORK
STEAM
HUMIDIFIER IN
DUCTWORK
AIR HANDLING UNIT SUPPLY
DUCTWORK TO BE ROUTED
FULL SIZE TO PLENUM.
SUPPLY PLENUM ON RACK.
INTENT OF RACK SYSTEM IS TO PROVIDE ACCESS ALONG
BUILDING. DUCTWORK AND OTHER ACCESSORIES RUN
UNDERNEATH WILL ONLY BE ACCEPTED AS ABSOLUTELY
NECESSARY TO SERVE SPACES BELOW.
TERMINAL BOXES SHALL BE AT
ELEVATION WHICH FACILITATES EASE
OF MAINTENANCE.
TERMINAL BOXES SHALL BE AT
ELEVATION WHICH FACILITATES EASE
OF MAINTENANCE.
24"x66"
VAVGE- 1005
VAVGE- 1010
3' 3/ 6"
VAVS- 1005
5'
VAVGE- 1009
VAVGE- 1003
VAVS- 1004
12"ø
18"x18"12"ø
PIPING TO DROP TO LOWER
LEVEL OF RACK SYSTEM.
LE-1
CROMWELL
ARCHITECTS/
ENGINEERS
#5A
R
KANSAS -ENG
IN
EE
R
C E R T
IF
IC
AT
EOF
AUTHORIZ
A T
IO
N PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 12957
S T A T E O F
M A
X W E L L A .
G O
O D
15-JUL-2015
SHEETDRAWING NOSUBMITTED
SCALE DATE DRAWN CHECK
REVISIONS
NO. DATE DESCRIPTION BY CHECK
JEFFERSON,ARKANSAS 72079
NATIONAL CENTER FOR TOXICOLOGICAL RESEARCH
N C T R
BUILDING 14 RENOVATION
MECHANICAL SECTIONS
M-40207/15/2015
1/4" = 1'-0"
1 SECTION AIR HANDLING UNIT ULTRA COOL WEST
SCALE : 1/4" = 1'-0"
0 2 4 8
1/4" = 1'-0"
2 TYPICAL LOUVER DETAIL
SCALE : 1/4" = 1'-0"
0 2 4 8
SCALE : 1/4" = 1'-0"
0 2 4 8
1/4" = 1'-0"
3 AHU-14.1 UNIT SECTION
m-fp02
11' - 2" m-fp03
30' - 4"
A B C E FD
VF- 1.2N
DIRECTION OF AIRFLOW DIRECTION OF AIRFLOW
VF- 1.2S
24"x40"
48"x24"
VAVS- 1007
"ø
16"x16"
VALVES SHALL BE FURNISHED AND INSTALL
WITH CHAIN ASSIST, OPERATIONAL FROM
THE FLOOR. (TYP ALL)
VAVHE- 1009S
VAVHE- 1010N
VAVS- 1009
CHILLED WATER TAPS
VAVHE- 1009N
VAVHE- 1008S
VAVGE- 1008
VAVS- 1000
VAVHE- 1007S
VAVHE- 1006
VAVGE- 1006
VAVHE- 1007N
28"x14"
12"ø
20"x26"
40"x30"
8" ø
8" ø
VAVHE- 1010S
20"x20"
14"x14"
24"x40" 24"x32"
20"x20"
CHILLED WATER
FROM BUILDING 6
FOR PHASE ONE
5' /2
5' /2
4'
3' 3/ 6" 6'
9' /2 m-fp02
11' - 2" m-fp03
30' - 4"
A B C E FD
EXISTING AHU- 14A1
EXHAUST DUCTWORK
AIR HANDLING UNIT SUPPLY
DUCTWORK TO BE ROUTED
FULL SIZE TO PLENUM.
SUPPLY PLENUM
ON RACK.
INTENT OF RACK SYSTEM IS TO PROVIDE ACCESS ALONG
BUILDING. DUCTWORK AND OTHER ACCESSORIES RUN
UNDERNEATH WILL ONLY BE ACCEPTED AS ABSOLUTELY
NECESSARY TO SERVE SPACES BELOW.
TERMINAL BOXES SHALL BE AT
ELEVATION WHICH FACILITATES EASE
OF MAINTENANCE.
PIPING BELOW RACK SYSTEM
HOT WATER SUPPLY AND RETURN SHALL
BE CONNECTED TO TOP OF MAIN,
TYPICAL ALL SHEETS AND ALL PHASES.
ALL TAKE OFF SHALL BE FURNISHED AND
INSTALLED WITH ISOLATING BALL VALVE.
VAVS- 1010 20"x14"12"ø
26"x14"
26"x54"
24"x66"
TWO FOOT SECTION OF EACH
EXHAUST FAN EXHAUST DUCT SHALL
BE PROVIDED WITH FLANGED,
REMOVABLE, CONNECTIONS.
2' - 0"
NEW HUMIDIFIER IN
SUPPLY DUCTWORK
LI-2 LE-2
6"øHWR
6"øHWS
VAVS- 1008
"x
DUCTWORK SERVING CORRIDOR
RETURN PLENUM, MATCH
UNIT OPENING DIMENSION.
24"x66"
CROMWELL
ARCHITECTS/
ENGINEERS
#5A
R
KANSAS -ENG
IN
EE
R
C E R T
IF
IC
AT
EOF
AUTHORIZ
A T
IO
N PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 12957
S T A T E O F
M A
X W E L L A . G
O
O D
15-JUL-2015
SHEETDRAWING NOSUBMITTED
SCALE DATE DRAWN CHECK
REVISIONS
NO. DATE DESCRIPTION BY CHECK
JEFFERSON,ARKANSAS 72079
NATIONAL CENTER FOR TOXICOLOGICAL RESEARCH
N C T R
BUILDING 14 RENOVATION
MECHANICAL SECTIONS
M-40307/15/2015
1/4" = 1'-0"
1 DUCTWORK SECTION
1/4" = 1'-0"
2 EXISTING AHU-14A1 SECTION
SCALE : 1/4" = 1'-0"
0 2 4 8 m-fp03
30' - 4"
A B C E FD
VF- 1.3N
DIRECTION OF AIRFLOW
DIRECTION OF AIRFLOW
VF- 1.3S
VAVGE- 1012
CUVRV- 1N
20"x26"48"x24"
CUVRV- 1S
VAVS- 1015
VAVHE- 1015S
VAVS- 1088
2' 3/ 6"
5' "6'
5' /2
14"x14"
26"x14" VAVS- 1013 VAVS- 1019
20"x26" 14"x18"
18"x24"
VAVS- 1011
VAVHE- 1015N
10"ø
VAVGE- 1019
5'
VAVGE- 1013
"ø
8" ø
8" ø
10"x10"
VENTILATION DUCTWORK SERVING
OFFICES. PENETRATION SHALL BE
SEALED WATER AND AIR TIGHT. VALID
FOR ALL SIMILAR VENTILATION DUCT
PENETRATIONS, ALL PHASES.
16"x22"
14"x20"
40"x30"
INTENT OF RACK SYSTEM IS TO PROVIDE
ACCESS ALONG BUILDING. DUCTWORK AND
OTHER ACCESSORIES RUN UNDERNEATH
WILL ONLY BE ACCEPTED AS ABSOLUTELY
NECESSARY TO SERVE SPACES BELOW.
SUPPLY DUCTWORK
RETURN
DUCTWORK
RETURN DUCTWORK
OFFSETS OVER RACK
RETURN DUCTWORK
ALL SUPPLY TERMINALS SHALL BE
FURNISHED AND INSTALLED WITH ISOLATION
VALVES AT LEVEL OF TERMINAL, IN
ACCESSIBLE LOCATION. VALID ALL PHASES.
m-fp02
11' - 2" m-fp03
30' - 4"
A B C E F
VRV CASSETTE, TYPICAL.
EACH CASSETTE SHALL BE FURNISHED
AND INSTALLED WITH ROOM SENSOR.
SENSOR SHALL BE MOUNTED IN
NORMALLY OCCUPIED ZONE OF ROOM,
OUT OF DIRECT SUNLIGHT.
CASSETTES SHALL BE PROVIDED WITH
SELF CLEANING FILTERS.
VENTILATION DUCTWORK, 4", TYPICAL ALL
OFFICE CASSETTES. VENTILATION
DUCTWORK SHALL BE PROVIDED WITH
MANUAL BALANCING DAMPER ASSESSABLE
THROUGH CEILING TILE IN SPACE.
4"ø
NOTES:
1. ALL VRV SYSTEMS SHALL BE PROVIDED WITH MEANS TO
DISCHARGE CONDENSATE TO APPROPRIATE RECEPTACLE.
OFFICE UNITS SHALL BE PROVIDED WITH PUMP AND
CONDENSATE HEADER, DISCHARGING INTO HUB DRAIN.
APPLICABLE FOR ALL SHEETS AND PHASES.
VENTILATION DUCTWORK PENETRATION SHALL
BE SEALED WATER AND AIR TIGHT, TYPICAL ALL.
RETURN PLENUM
INDIVIDUAL AIR HANDLING UNIT
RETURN DUCTWORK TO BE ROUTED
FULL SIZE TO PLENUM.
OUTSIDE AIR DUCTWORK
TERMINAL BOX PROVIDING
VENTILATION TO OFFICE SPACES.
TERMINAL BOX TO BE OPERATE ON
ADJUSTABLE SCHEDULE.
EXHAUST DUCTWORK
VAVS- 1032
4' /2
VAVGE- 1016
4'
STEAM
HUMIDIFIER IN
DUCTWORK
AIR HANDLING UNIT SUPPLY
DUCTWORK TO BE ROUTED
FULL SIZE TO PLENUM.
SUPPLY PLENUM ON RACK.
INTENT OF RACK SYSTEM IS TO PROVIDE ACCESS ALONG
BUILDING. DUCTWORK AND OTHER ACCESSORIES RUN
UNDERNEATH WILL ONLY BE ACCEPTED AS ABSOLUTELY
NECESSARY TO SERVE SPACES BELOW.
VENTILATION DUCTWORK IN
CORRIDOR SPACE.
TERMINAL BOXES SHALL BE AT
ELEVATION WHICH FACILITATES EASE
OF MAINTENANCE.
TERMINAL BOXES SHALL BE AT
ELEVATION WHICH FACILITATES EASE
OF MAINTENANCE.
EXHAUST LOUVER
OUTSIDE INTAKE LOUVER
D
FIRST ELBOW OF EACH EXHAUST FAN
SHALL BE PROVIDED WITH FLANGED,
REMOVABLE, CONNECTIONS.
AHU- 14.3
VAVGE- 1015
VAVGE- 1032
VAVHE- 1032S
4' /2
DUCTWORK SERVING CORRIDOR
VAVGE- 1040
10"x10" VAVS- 1127
"x
14"x14" 12"x12"
CROMWELL
ARCHITECTS/
ENGINEERS
#5A
R
KANSAS -ENG
IN
EE
R
C E R T
IF
IC
AT
EOF
AUTHORIZ
A T
IO
N PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 12957
S T A T E O F
M A
X W
E L L A . G O
O D
15-JUL-2015
SHEETDRAWING NOSUBMITTED
SCALE DATE DRAWN CHECK
REVISIONS
NO. DATE DESCRIPTION BY CHECK
JEFFERSON,ARKANSAS 72079
NATIONAL CENTER FOR TOXICOLOGICAL RESEARCH
N C T R
BUILDING 14 RENOVATION
MECHANICAL SECTIONS
M-40407/15/2015
1/4" = 1'-0"
1 DUCTWORK SECTION TWO
1/4" = 1'-0"
2 AHU-14.3 UNIT SECTION
SCALE : 1/4" = 1'-0"
0 2 4 8 m-fp03
30' - 4"
A B C E FD
LI-3
24"x66"
EXISTING RETURN
SERVING AHU-14A2
EXISTING AHU- 14A2
EXISTING EXHAUST
DUCTWORK THROUGH ROOF
EXISTING SUPPLY
EXISTING SUPPLY PLENUM. SUPPLY
PLENUM TO BE REPLACED DURING
SECOND PHASE AND DECK
UNDERNEATH TO BE REPAIRED.
MAIN SUPPLY DUCT
EXHAUST DUCTWORK
SERVING RESTROOMS
"x
VAVGE- 1025
EXHAUST DUCTWORK
SHALL BE ROUTED IN A
MANNER AS TO NOT
INTERFERE WITH THE
STRUCTURE FOR THE
AIR COMPRESSORS.
VAVGE- 1024
"ø
14"x14"
HOT WATER SUPPLY AND RETURN SHALL BE
ROUTED OFF OF THE TOP OF MAIN PIPING AND
BE INSTALLED WITH A ISOLATION VALVE.
NEW RETURN MAIN
EXISTING EXHAUST
DUCTWORK THROUGH ROOF
SHALL BE REMOVED AND ROOF
REPAIRED IN PHASE TWO.
m-fp02
11' - 2" m-fp03
30' - 4"
A B C E FD
CU- UTE
VAVS- 1061 14"x14"
"x
10"ø
10"ø
LE-5LI-5
RETURN MAIN
34"x66"
AHU- 14.5
34"x66"
26"x54"
INDIVIDUAL AIR HANDLING UNIT
RETURN DUCTWORK TO BE ROUTED
FULL SIZE TO PLENUM.
STEAM HUMIDIFIER
IN DUCTWORK
AIR HANDLING UNIT SUPPLY
DUCTWORK TO BE ROUTED
FULL SIZE TO PLENUM.
INTENT OF RACK SYSTEM IS TO PROVIDE ACCESS ALONG
BUILDING. DUCTWORK AND OTHER ACCESSORIES RUN
UNDERNEATH WILL ONLY BE ACCEPTED AS ABSOLUTELY
NECESSARY TO SERVE SPACES BELOW.
FIRST ELBOW OF EACH EXHAUST FAN
SHALL BE PROVIDED WITH FLANGED,
REMOVABLE, CONNECTIONS.
SUPPLY PLENUM. PLENUM
TO BE FULL SIZE OF UNIT
OUTLET CONNECITON.
PIPING SHAL BE VALVED IN PHASE ONE.
PIPING SHALL BE EXTENDED TO EAST SIDE
OF BUILDING IN PHASE TWO. (TYPICAL ALL)
SUPPLY MAIN
6'
TERMINAL BOXES SHALL BE AT
ELEVATION WHICH FACILITATES EASE
OF MAINTENANCE.
EXHAUST DUCT SHALL BE FULL SIZE
OF EXHAUST OUTLET, TYPICAL ALL.
CROMWELL
ARCHITECTS/
ENGINEERS
#5A
R
KANSAS -ENG
IN
EE
R
C E R T
IF
IC
AT
EOF
AUTHORIZ
A T
IO
N PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 12957
S T A T E O F
M A
X W E L L A .
G O
O D
15-JUL-2015
SHEETDRAWING NOSUBMITTED
SCALE DATE DRAWN CHECK
REVISIONS
NO. DATE DESCRIPTION BY CHECK
JEFFERSON,ARKANSAS 72079
NATIONAL CENTER FOR TOXICOLOGICAL RESEARCH
N C T R
BUILDING 14 RENOVATION
MECHANICAL SECTIONS
M-40507/15/2015
1/4" = 1'-0"
1 EXISTING AHU-14A2 PHASE ONE SECTION
1/4" = 1'-0"
2 AHU-14.5 SECTION
m-fp03
30' - 4"
A B C E FD
M-407
INDIVIDUAL AIR HANDLING UNIT
RETURN DUCTWORK TO BE ROUTED
FULL SIZE TO PLENUM.
STEAM HUMIDIFIER
IN DUCTWORK
AIR HANDLING UNIT SUPPLY
DUCTWORK TO BE ROUTED
FULL SIZE TO PLENUM.
INTENT OF RACK SYSTEM IS TO PROVIDE ACCESS ALONG
BUILDING. DUCTWORK AND OTHER ACCESSORIES RUN
UNDERNEATH WILL ONLY BE ACCEPTED AS ABSOLUTELY
NECESSARY TO SERVE SPACES BELOW.
FIRST ELBOW OF EACH EXHAUST FAN
SHALL BE PROVIDED WITH FLANGED,
REMOVABLE, CONNECTIONS.
SUPPLY PLENUM. PLENUM
TO BE FULL SIZE OF UNIT
OUTLET CONNECITON.
TERMINAL BOXES SHALL BE AT
ELEVATION WHICH FACILITATES EASE
OF MAINTENANCE.
EXHAUST DUCT SHALL BE FULL SIZE
OF EXHAUST OUTLET, TYPICAL ALL.
AHU- 14.6
LI-6 LE-6
VAVGE- 1047 VAVHE- 1047SW
2' /2
AHU- UTE
34"x66"
SUPPLY PLENUM34"x66" m-fp02
11' - 2"
A B C E FD
DIRECTION OF AIRFLOW
VF- 2.1N
DIRECTION OF AIRFLOW VALID
FOR ALL VENTILATION FANS ON
THE NORTH SIDE, ALL PHASES.
DIRECTION OF AIRFLOW
DIRECTION OF AIRFLOW VALID
FOR ALL VENTILATION FANS ON
THE SOUTH SIDE, ALL PHASES.
VF- 2.1S
INDIVIDUAL AIR HANDLING UNIT
RETURN DUCTWORK TO BE ROUTED
FULL SIZE TO PLENUM.
INTENT OF RACK SYSTEM IS TO PROVIDE ACCESS ALONG
BUILDING. DUCTWORK AND OTHER ACCESSORIES RUN
UNDERNEATH WILL ONLY BE ACCEPTED AS ABSOLUTELY
NECESSARY TO SERVE SPACES BELOW.
TERMINAL BOXES SHALL BE AT
ELEVATION WHICH FACILITATES EASE
OF MAINTENANCE.
SUPPLY DUCT
VAVS- 1047
VAVHE- 1055S
8"ø
VAVS- 1048
VAVHE- 1055N
VAVGE- 1056
VAVGE- 1055
VAVHE- 1059S
VAVHE- 1058N
VAVS- 1051VAVS- 1052
VAVGE- 1057
VAVHE- 1057WVAVS- 1058
"x
8" ø
RETURN DUCT
CROMWELL
ARCHITECTS/
ENGINEERS
#5A
R
KANSAS -ENG
IN
EE
R
C E R T
IF
IC
AT
EOF
AUTHORIZ
A T
IO
N PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 12957
S T A T E O F
M A
X W E L L A . G
O
O D
15-JUL-2015
SHEETDRAWING NOSUBMITTED
SCALE DATE DRAWN CHECK
REVISIONS
NO. DATE DESCRIPTION BY CHECK
JEFFERSON,ARKANSAS 72079
NATIONAL CENTER FOR TOXICOLOGICAL RESEARCH
N C T R
BUILDING 14 RENOVATION
MECHANICAL SECTIONS
M-40607/15/2015
1/4" = 1'-0"
1 AHU-14.6 SECTION
1/4" = 1'-0"
2 DUCTWORK SECTION THREE
SCALE : 1/4" = 1'-0"
0 2 4 8 m-fp02
11' - 2"
C
EXISTING LINE LEVEL
16' - 2"
M-401
D m-fp01
0" m-fp02
11' - 2"
EXISTING LINE LEVEL
16' - 2" m-fp02
11' - 2" m-fp03
30' - 4"
VAVS- 1061
CU- UTE
AHU- UTE
20"x26"
20"x20"
FULL SIZE OF UNIT CONNECTION.
UNIT SHALL BE INSTALLED SO THAT
REQUIRED CLEARANCES ARE MAINTAINED
AS PRESCRIBED BY UNIT MANUFACTURER.
RETURN
SUPPLY
CROMWELL
ARCHITECTS/
ENGINEERS
#5A
R
KANSAS -ENGIN
EE
R
C E R T
IF
IC
AT
EOFAUTHORIZ
A T
IO
N PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 12957
S T A T E O F
M A
X W
E L L A . G O
O D
15-JUL-2015
SHEETDRAWING NOSUBMITTED
SCALE DATE DRAWN CHECK
REVISIONS
NO. DATE DESCRIPTION BY CHECK
JEFFERSON,ARKANSAS 72079
NATIONAL CENTER FOR TOXICOLOGICAL RESEARCH
N C T R
BUILDING 14 RENOVATION
MECHANICAL SECTIONS
M-40707/15/2015
1/4" = 1'-0"
1 PHASE TWO CHILLED WATER SECTION
1/4" = 1'-0"
2 PHASE TWO CHILLED WATER SECTION TWO
1/4" = 1'-0"
3 AHU-UTE SECTION
SCALE : 1/4" = 1'-0"
0 2 4 8
SCALE : 1/4" = 1'-0"
0 2 4 8
28' - 0"
4" 4" 4" 4" 4" 1' - 9"
NOTE:
1. IT IS THE INTENT OF DUCTWORK IN LAB AREAS TO BE OF SIMILAR DIMENSION.
FINAL LAYOUT OF THE SPACE AND EQUIPMENT MAY DICTATE A MODIFICATION
TO SHOWN DIMENSIONS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO
FIELD VERIFY AND PROVIDE ALL NECESSARY ACCOMMODATIONS TO INSTALL
FULLY FUNCTIONAL SYSTEM.
26"x14" 26"x14"
SUPPLY DUCTWORK TO
MECHANICAL AREA ABOVE.
A- 270
E
5' - 0"
28"x14"
EXHAUST DUCTWORK TO
MECHANICAL AREA ABOVE.
1' - 9" C- 1800
NOTE:
1. IT IS THE INTENT OF DUCTWORK IN LAB AREAS TO BE OF SIMILAR
DIMENSION. FINAL LAYOUT OF THE SPACE AND EQUIPMENT MAY DICTATE A
MODIFICATION TO SHOWN DIMENSIONS. IT IS THE RESPONSIBILITY OF THE
CONTRACTOR TO FIELD VERIFY AND PROVIDE ALL NECESSARY
ACCOMMODATIONS TO INSTALL FULLY FUNCTIONAL SYSTEM.
5' - 0"
1' - 10"
NOTE:
1. IT IS THE INTENT OF DUCTWORK IN LAB AREAS TO BE OF SIMILAR
DIMENSION. FINAL LAYOUT OF THE SPACE AND EQUIPMENT MAY
DICTATE A MODIFICATION TO SHOWN DIMENSIONS. IT IS THE
RESPONSIBILITY OF THE CONTRACTOR TO FIELD VERIFY AND
PROVIDE ALL NECESSARY ACCOMMODATIONS TO INSTALL FULLY
FUNCTIONAL SYSTEM.
EXHAUST DUCTWORK TO MECHANICAL AREA ABOVE.
B- 750
D
14' - 0"
4" 4" 1' - 0"
NOTE:
1. IT IS THE INTENT OF DUCTWORK IN LAB AREAS TO BE OF
SIMILAR DIMENSION. FINAL LAYOUT OF THE SPACE AND
EQUIPMENT MAY DICTATE A MODIFICATION TO SHOWN
DIMENSIONS. IT IS THE RESPONSIBILITY OF THE
CONTRACTOR TO FIELD VERIFY AND PROVIDE ALL NECESSARY
ACCOMMODATIONS TO INSTALL FULLY FUNCTIONAL SYSTEM.
SUPPLY DUCTWORK TO
MECHANICAL AREA ABOVE.
26"x14"
A- 270
SUPPLY AIR TERMINAL
DUCTWORK SHALL BE DOUBLE WALL
IN SECTIONS INDICATED. INTENT IS TO
PROVIDE DOUBLE WALL AS THE DUCT
TRAVELS THROUGH THE DECK,
INCLUDING THE FIRST ELBOW.
INSULATION SHALL NOT COMMUNICATE
WITH AIRSTREAM.
DUCTWORK IN THIS SECTION SHALL BE
SINGLE WALL, 22 GAUGE. DUCTWORK
SHALL IN SUPPORTED BY 18 GAUGE
INTERNAL ANGLE FRAMES IN BETWEEN
AND AT THE ENDS OF DIFFUSERS.
DUCTWORK SHALL BE PROVIDED WITH 4' TALL PLASTIC SCRIM AS IT
PENETRATES THE DECK (SEE BUILDING 62). THIS WILL BE LABELED WITH
THE NAME OF THE TERMINAL AND THE FULL NAME OF THE ROOM IT
SERVES. VALID FOR EXHAUST AND SUPPLY FOR ALL SPACES, NOT ONLY
LABS.
DUCTWORK SHALL BE INSTALLED AFTER THE CAREFUL COORDINATION
WITH STRUCTURAL, LIGHTING AND ALL OTHER TRADES. CONFLICT WILL
BE BROUGHT TO THE ATTENTION OF THE GOVERNMENT'S
REPRESENTATIVE. ITEMS NEEDING MOVEMENT AND COORDINATION WILL
BE DONE AT NO COST TO THE OWNER.
GENERAL NOTES:
1. DUCTWORK IN SPACE SHALL BE FIELD PAINTED WHITE.
2. DIFFUSER AND ASSEMBLY SHALL BE PROVIDED WITH WHITE FACTORY
FINISH. DIFFUSER AND ASSEMBLY SHALL NOT BE FIELD PAINTED.
DUCTWORK SHALL BE INSTALLED AFTER THE CAREFUL
COORDINATION WITH STRUCTURAL, LIGHTING AND ALL OTHER
TRADES. CONFLICT WILL BE BROUGHT TO THE ATTENTION OF THE
GOVERNMENT'S REPRESENTATIVE. ITEMS NEEDING MOVEMENT
AND COORDINATION WILL BE DONE AT NO COST TO THE OWNER.
DUCTWORK SHALL BE PROVIDED WITH 4' TALL PLASTIC SCRIM AS IT
PENETRATES THE DECK (SEE BUILDING 62). THIS WILL BE LABELED WITH
THE NAME OF THE TERMINAL AND THE FULL NAME OF THE ROOM IT
SERVES. VALID FOR EXHAUST AND SUPPLY FOR ALL SPACES, NOT ONLY
LABS.
DUCTWORK SHALL BE DOUBLE WALL IN
SECTIONS INDICATED. INTENT IS TO
PROVIDE DOUBLE WALL AS THE DUCT
TRAVELS THROUGH THE DECK, INCLUDING
THE FIRST ELBOW. INSULATION SHALL NOT
COMMUNICATE WITH AIRSTREAM.
GENERAL EXHAUST TERMINAL
DUCTWORK IN THIS SECTION SHALL
BE AS PER SMACNA STANDARDS.
HOOD EXHAUST TERMINAL
GENERAL NOTES:
1. DUCTWORK IN SPACE SHALL BE FIELD PAINTED WHITE.
2. DIFFUSER AND ASSEMBLY SHALL BE PROVIDED WITH WHITE
FACTORY FINISH. DIFFUSER AND ASSEMBLY SHALL NOT BE
FIELD PAINTED.
m-fp01
0" m-fp02
11' - 2"
E
GENERAL NOTES:
1. ALL MECHANICAL SYSTEMS SHALL NOT BE ANCHORED TO
OR SUPPORTED FROM DECK.
2. ALL SYSTEMS SHALL BE SUPPORTED FROM STRUCTURE.
ALL DUCT SHALL BE HUNG FROM TOP OF JOIST.
DUCTWORK SHALL NOT BE SUPPORTED BY NEW JOIST
BRIDGING, SEE STRUCTURAL. SUBMIT SHOP DRAWINGS FOR
APPROVAL TO ENGINEER BEFORE FABRICATION AND
INSTALLATION.
KEYED NOTES:
1. SUPPORT FOR DUCTWORK SHALL SPAN AND BE
PERMANENTLY CONNECTED TO STRUCTURE, FROM TOP OF
JOIST. EQUIVALENT TO UNISTRUT.
2. SUPPORT SHALL BE SPACED BASED ON FINAL WEIGHT OF
SYSTEM, SMACNA, MANUFACTURER'S RECOMMENDATIONS
AND BEST INDUSTRY PRACTICE.
3. CONTRACTOR SHALL INSTALL FULLY FUNCTIONAL SUPPORT
SYSTEM. SYSTEM SHALL NOT INTERFERE WITH OTHER
SYSTEMS IN SPACE INCLUDING LIGHTS, PIPING AND OTHER
ANCILLARY EQUIPMENT.
MECHANICAL SYSTEM SUPPORT SYSTEM BETWEEN
TOP OF STRUCTURAL MEMBERS, TYPICAL.
SUPPORT ENVELOPING
DUCTWORK. DUCTWORK TO HANG
FROM SUPPORT ABOVE, TYPICAL.
1 1
3 3
D
CROMWELL
ARCHITECTS/
ENGINEERS
#5A
R
KANSAS -ENG
IN
EE
R
C E R T
IF
IC
AT
EOF
AUTHORIZ
A T
IO
N PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 12957
S T A T E O F
M A
X W E L L A .
G O
O D
15-JUL-2015
SHEETDRAWING NOSUBMITTED
SCALE DATE DRAWN CHECK
REVISIONS
NO. DATE DESCRIPTION BY CHECK
JEFFERSON,ARKANSAS 72079
NATIONAL CENTER FOR TOXICOLOGICAL RESEARCH
N C T R
BUILDING 14 RENOVATION
MECHANICAL ENLARGED PLANS
M-40807/15/2015
1/4" = 1'-0"
1 LAB LARGE SUPPLY DUCTWORK ENLARGED PLAN
1/4" = 1'-0"
2 LAB LARGE RETURN DUCTWORK ENLARGED PLAN
1/4" = 1'-0"
3 LAB SMALL RETURN DUCTWORK ENLARGED PLAN
1/4" = 1'-0"
4 LAB SMALL SUPPLY DUCTWORK ENLARGED PLAN 5 LAB SUPPLY ISOMETRIC
SCALE : 1/4" = 1'-0"
0 2 4 8
SCALE : 1/4" = 1'-0"
0 2 4 8
SCALE : 1/4" = 1'-0"
0 2 4 8
SCALE : 1/4" = 1'-0"
0 2 4 8
6 LAB EXHAUST ISOMETRIC
1/4" = 1'-0"
7 MECHANCIAL SUPPORT IN SPACES
SCALE : 1/4" = 1'-0"
0 2 4 8
NOTE:
1. SYSTEMS SHOWN HAVE BEEN TESTED AROUND BASIS OF DESIGN. SUBSTITUTIONS MAY BE CONSIDERED PROVIDING THAT SIDE BY SIDE COMPARISON PROVES POTENTIALLY SUBSTITUTED PRODUCT PERFORMS EQUALLY LIKE BASIS OF DESIGN. COMPARISON SHALL BE VIDEOED. FOR COMPARISON, SYSTEM FOR BASIS OF DESIGN SHALL BE PROVIDED BY MANUFACTURER OF BASIS OF DESIGN.
SYSTEMS SHALL BE TESTED AT 800 CFM AND 1,600 CFM AT 55, 60 AND 67 DEGREES F.
FLEX SHALL BE RUN AS STRAIGHT AS POSSIBLE
AND CUT TO MINIMUM LENGTH. SWEEPING BENDS
TO ACCOMMODATE EXCESS LENGTH ARE NOT ALLOWED.
INSULATED FLEXIBLE DUCT
(MAXIMUM LENGTH 5'-0")
CONICAL OR 45° TAKE-OFF FITTING
WITH 1" MOUNTING FLANGE AND
ADHESIVE COATED GASKET. ATTACH
WITH SHEET METAL SCREWS.
GRILLE WITH
ROUND NECK.
INSULATE BACK
OF DIFFUSER
RIGID ELBOW
QUADRANT-LOCKING DAMPER
OFF-SET TO ALLOW FOR
INSULATION THICKNESS.
RIGID ROUND DUCT
SIDE OR BOTTOM TAP
(TOP TAP IS NOT ACCEPTABLE)
AIR DEVICE
TRUNK DUCT
CEILING (SEE ARCH. PLANS)
1" SECURING STRAP (TYP.)
INSULATION
INSULATED FLEXIBLE DUCT
(MAXIMUM LENGTH 5'-0")
INSULATE BACK
OF DIFFUSER
RIGID ELBOW
AIR DEVICE CEILING (SEE ARCH. PLANS)
1" SECURING STRAP (TYP.)
INSULATION
4" DEEP SQUARE TO ROUND
ADAPTER EQUAL TO FLEXMASTER
"F4SC". PAINT INSIDE FLAT BLACK
INSULATE BACK
OF DIFFUSER
AIR DEVICE CEILING (SEE ARCH. PLANS)
1" SECURING STRAP (TYP.)
SIDE INLET BOX EQUAL TO
FLEXMASTER "SIDB". PAINT
INSIDE FLAT BLACK 45°
1/4xW
MANUAL DAMPER WITH
QUADRANT INDICATOR
AND STAND-OFF BRACKET
RECTANGULAR TO RECTANGULAR
45°
MANUAL DAMPER WITH
QUADRANT INDICATOR
AND STAND-OFF BRACKET
RECTANGULAR TO ROUND
90°
MANUFACTURED FITTING
SEE SPECIFICATIONS.
1½" POCKET SLIP
DUCT
SHEET METAL AS SPECIFIED
FOR DUCTWORK
1½" MIN. TO 3" MAX. INSTALLED.
6" NOMINAL W/ MATERIAL TAUT.
ALTERNATE POSITION
FOR BOLT
FLANGED CONNECTION
ON FAN SIDE
WASHER
SHEET METAL AS SPECIFIED
FOR DUCTWORK
1" FLANGE & HEM
BOLT ON 4" CENTERS
1"x ⅛" IRON BAND
FLEXIBLE MATERIAL
AS SPECIFIED
1"x ½" DRAWBAND (TYP.)
SHEET METAL SCREWS
ON 12" CENTERS
RIVET ON 4" CENTERS
DUCT
1½" MIN. TO 3" MAX. INSTALLED
6" NOMINAL W/ MATERIAL TAUT
5/16" FLANGE
BOLT ON 4" CENTERS
1" x ½" IRON BAND
WASHER
FLEXIBLE MATERIAL
AS SPECIFIED
FLANGED
CONNECTION
ON FAN SIDE
1½" ½" ½"
TAPE OVER JOINTS IN VAPOR
BARRIER
LAP VAPOR BARRIER AND SEAL
ALL THREAD ROD
MECHANICAL FASTNERS SUPPORTING
INSULATION ON THE UNDERSIDE OF DUCTS
OVER 24" WIDE, SEAL OVER FASTENER
PENTRATIONS WITH TAPE
NOTES:
1. PROVIDE SADDLES AT DUCT SUPPORT POINTS.
2. DO NOT TAKE DUCT SUPPORTS OR STRAPS INTO THE INSULATION.
3. PROVIDE INSULATION INSERT SO THAT INSULATION DOES NOT COMPRESS
FROM WEIGHT OF DUCT.
4. PROVIDE SEMI-RIGID INSULATION ON ALL DUCTWORK IN MECHANICAL
EQUIPMENT ROOMS AND OTHER HIGH ABUSE AREAS AS SPECIFIED.
HEAVY GAUGE SHEET METAL SADDLE
VAPOR BARRIER, TAPE OVER
TEARS AND PENETRATIONS OF
THE VAPOR BARRIER JACKET
PROVIDE RIGID INSERT FOR SUPPORT SO
THAT INSULATION DOES NOT COMPRESS
AT DUCT SUPPORT LOCATIONS
BLANKET INSULATION
RECTANGULAR DUCT
DUCT SUPPORT SEMI-RIGID BOARD INSULATION
ADHESIVE SPACED AS
REQUIRED TO ASSIST IN
INSULATION
MECHANICAL FASTNERS SUPPORTING
INSULATION ON THE UNDERSIDE OF DUCTS
OVER 24" WIDE, SEAL OVER FASTENER
PENTRATIONS WITH TAPE
NOTES:
1. PROVIDE SADDLES AT DUCT SUPPORT POINTS.
2. DO NOT TAKE DUCT SUPPORTS OR STRAPS INTO THE INSULATION.
3. PROVIDE INSULATION INSERT SO THAT INSULATION DOES NOT COMPRESS
FROM WEIGHT OF DUCT.
4. PROVIDE SEMI-RIGID INSULATION ON ALL DUCTWORK IN MECHANICAL
EQUIPMENT ROOMS AND OTHER HIGH ABUSE AREAS AS SPECIFIED.
5. SHAPE INSULATION BY REMOVING MITERED SEGMENTS TO CONFORM TO
ROUND END OR FLAT OVAL DUCTWORK.
HEAVY GAUGE SHEET METAL SADDLE
VAPOR BARRIER, TAPE OVER
TEARS AND PENETRATIONS OF
THE VAPOR BARRIER JACKETRECTANGULAR DUCT
DUCT SUPPORT
ALL THREAD ROD
VAV TERMINAL UNIT
BALL VALVE
REDUCER
3 WAY MODULATING VALVE
BALL VALVE
UNION (TYP.)
T&P PLUG (TYP.)
HR
AIR INLET
SUPPLY AIR
H.W. REHEAT COIL
DRAIN VALVE
WITH HOSE CONN.
AUTOMATIC FLOW
CONTROL VALVE
MANUAL AIR VENT
(TYP.)
(3-WAY VALVE)
HS
NOTE:
1. PROVIDE FLEX. CONNECTION ATDISCHARGE OF TERMINAL UNIT.
2. CONTRACTOR SHALL COMPLETELY INSULATE (AIR TIGHT) HEATING
WATER COIL BOXES, EXTERNAL PIPING (U-TUBES), VALVE BODIES,
CLEANOUTS, STRAINERS OR ANY OTHER COMPONENT THAT COULD
PRODUCE CONDENSATE IN EVENT HOT WATER SYSTEM MALFUNCTIONS
OR IS TURNED OFF - TWO AND THREE WAY WATER COILS.
VAV TERMINAL UNIT
BALL VALVE
REDUCER, TYP.
2 WAY MODULATING VALVE
BALL VALVE
UNION (TYP.)
T&P PLUG (TYP.)
HR
AIR INLET
SUPPLY AIR
H.W. REHEAT COIL
DRAIN VALVE
WITH HOSE CONN.
AUTOMATIC FLOW
CONTROL VALVE
MANUAL AIR VENT
(TYP.)
(2-WAY VALVE)
HS
TRIM AIR HANDLER HOUSING FLUSH
WITH BELLMOUTH FITTING AND SEAL
WITH DUCT SEALER AND SILICONE.
A
IR
F
LO
W
AIR HANDLER
UNIT WALL COVER
FLEXIBLE DUCT
CONNECTION
MOUNT BELLMOUTH ON INSIDE WALL OF AIR
HANDLER AND SEAL WITH DUCT SEALANT.
NOTE:
ALL CONNECTIONS TO AIR SUPPLY
TERMINALS AND GENERAL EXHAUST
TERMINALS SHALL BE BELL MOUTH TYPE.
NOTES:
1. CONSTRUCTION IS ALUMINUM.
2. PLASTER FRAME ADAPTER CONSTRUCTION IS ALUMINUM.
3. STANDARD FINISH IS 44 WHITE FOR ASSEMBLY.
ASSEMBLY PARTS SEE NOTES
SECURITY CLIP
GASKET
FRAME
PERFORATED
PANEL AIR DEVICE
DUCT BY OTHERS
E X P A N S
IO
N T A N K
H W E T -1
AIR SEPARATOR HWAS-1
STEAM-WATER
HX
4"
FEEDWATER
(SEE DETAIL)
COLD WATER
HWS TO BUILDING
5# S T E A M
STEAM CONDENSATE
TO CONDENSATE
RETURN SYSTEM
HWP-1A HWP-1B
HWET-1
JOHN WOOD #JAER-23-609
BLADDER TYPE EXPANSION TANK
120 GALLON TANK
108 GALLON ACCEPTANCE VOLUME
HWAS-1
JOHN WOOD #JASR-19-404
TANGENTIAL AIR SEPARATOR
4"
4"
1-1/2"
3/4"
AUTOMATIC AIR VENT -
PIPE TO DRAIN
HWR FROM COILS
MEZZANINE FINISHED FLOOR
4"
1-1/2"
REFER TO PLANS AND THE
DETAIL ON SHEET M-504
4"
NOTE: ALL VALVES, UNIONS AND OTHER
PIPE APPURTENANCES REQUIRED BY THE
MANUFACTURER'S OF THE HEATING
WATER SYSTEM COMPONENTS IS NOT
SHOWN. ALL COMPONENTS SHALL BE
INSTALLED IN STRICT ACCORDANCE WITH
EACH COMPONENT'S MANUFACTURER'S
REQUIREMENTS
REFER TO THE BASE MOUNTED
PUMP DETAIL ON SHEET M-504
CROMWELL
ARCHITECTS/
ENGINEERS
#5A
R
KANSAS -ENG
IN
EE
R
C E R T
IF
IC
AT
EOF
AUTHORIZ
A T
IO
N PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 12957
S T A T E O F
M A
X W E L L A . G
O
O D
15-JUL-2015
SHEETDRAWING NOSUBMITTED
SCALE DATE DRAWN CHECK
REVISIONS
NO. DATE DESCRIPTION BY CHECK
JEFFERSON,ARKANSAS 72079
NATIONAL CENTER FOR TOXICOLOGICAL RESEARCH
N C T R
BUILDING 14 RENOVATION
HVAC DETAILS
M-50107/15/2015
N.T.S.
1 DUCT CONNECTION DETAIL
N.T.S.
2 DUCT TAKE-OFF (SQUARE & ROUND) DUCT
N.T.S.
3 RECTANGULAR FLEXIBLE CONNECTION
N.T.S.
4 ROUND FLEXIBLE DUCT
N.T.S.
6 DUCT SUPPORT (LESS THAN 36 INCHES)
N.T.S.
7 DUCT SUPPORT (MORE THAN 36 INCHES)
N.T.S.
5 VAV TERMINAL W/ HOT WATER COIL
N.T.S.
8 BELL MOUTH
N.T.S.
9 LOW VELOCITY RADIAL AIR DEVICE DETAIL
N.T.S.
11 MAKE UP WATER DETAIL
N.T.S.
10 HEATING WATER SCHEMATIC
NOTES:
1. INTENT OF DETAIL IS TO SHOW AIR HANDLING UNIT MODULES.
2. MAIN AREAS OF CLEARANCE AND PIPING CONNECTIONS SHOWN ON DRAWINGS.
3. ELECTRICAL AND CONTROL CONNECTIONS SHALL BE MADE NEAR SOUTHERN END OF UNIT
STRUCTURAL FRAME IN ACCESSIBLE AREA, SEE EXISTING UNITS.
4. ANY SUBSTITUTION CHANGING DIMENSION OR WEIGHT MAY ONLY BE CONSIDERED FOR
ACCEPTANCE IF ACCOMPANIED BY DESIGN FOR SUPPORTING UNIT SIGNED AND SEALED BY
STRUCTURAL ENGINEER LICENSED IN THE STATE OF ARKANSAS. ALL COSTS OF SUBSTITUTIONS
ARE THE RESPONSIBILITY OF THE CONTRACTOR.
NOTES:
1. INTENT OF DETAIL IS TO SHOW AIR HANDLING UNIT MODULES.
2. MAIN AREAS OF CLEARANCE AND PIPING CONNECTIONS SHOWN ON DRAWINGS.
3. ELECTRICAL AND CONTROL CONNECTIONS SHALL BE MADE NEAR SOUTHERN END OF UNIT STRUCTURAL
FRAME IN ACCESSIBLE AREA, SEE EXISTING UNITS.
4. ANY SUBSTITUTION CHANGING DIMENSION OR WEIGHT MAY ONLY BE CONSIDERED FOR ACCEPTANCE IF
ACCOMPANIED BY DESIGN FOR SUPPORTING UNIT SIGNED AND SEALED BY STRUCTURAL ENGINEER
LICENSED IN THE STATE OF ARKANSAS. ALL COSTS OF SUBSTITUTIONS ARE THE RESPONSIBILITY OF THE
CONTRACTOR.
CROMWELL
ARCHITECTS/
ENGINEERS
#5A R
K
ANSAS -ENG
IN
EE
R
C E R T
IF
IC
AT
EOF
AUTHORIZ
A T
IO
N
PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 12957
S T A T E O F
M A
X W
E L L A . G O
O D
15-JUL-2015
SHEETDRAWING NOSUBMITTED
SCALE DATE DRAWN CHECK
REVISIONS
NO. DATE DESCRIPTION BY CHECK
JEFFERSON,ARKANSAS 72079
NATIONAL CENTER FOR TOXICOLOGICAL RESEARCH
N C T R
BUILDING 14 RENOVATION
HVAC DETAILS
M-50207/15/2015
N.T.S.
1 PHASE ONE LAB AIR HANDLING UNIT DETAIL
2 PHASE TWO LAB AIR HANDLING UNIT DETAIL
I RA
NOTES:
DRAIN VALVE WITH HOSE
CONNECTION
SUPPLY
RETURNNOTE 4 (TYP.)
UNION (TYP)
CONTROL VALVE (TYP)
MANUAL AIR VENT (TYP)
BALANCING VALVE
CONTROL SYSTEM
TEMPERATURE GAUGE (TYP)
T&P PLUG (TYP)
T & P PLUG
BUTTERFLY SERVICE
VALVE (TYP)
BUTTERFLY SERVICE
VALVE (TYP)
1. SUPPORT RISERS AS SHOWN INDEPENDENT OF COIL.
2. INSTALL PIPING IN A MANNER THAT DOES NOT BLOCK ACCESS DOOR.
3. PROVIDE FLANGED CONNECTIONS FOR PIPING 2½" AND LARGER.
PROVIDE UNIONS FOR PIPING 2" AND SMALLER.
4. PROVIDE BALL VALVE FOR PIPING 2" AND SMALLER. BUTTERFLY
VALVE FOR PIPING 2½" AND LARGER.
5. TYPICAL FOR AHU's, ENERGY RECOVERY UNITS, AND MAKE-UP AIR
UNITS.
I RA
STRAINER
PRESSURE GUAGE (TYP)
BALL VALVE
HOSE-BIBB AT BASE OF RISER
NOTE 3
DRAIN PAN
CONDENSATE TO BE RUN
FULL SIZE TO FLOOR DRAIN
(NOT APPLICABLE TO HOT
WATER COIL)
MANUAL AIR VENTS
DISPERSION TUBES SUPPORTS
STEAM DISCHARGE
PORTS TOWARD
UPSTREAM DIRECTION
DUCT
STEAM SUPPLY
STRAINER (BY MFG.)
TO HUMIDISTAT
HUMIDIFIER
CONTROL
VALVE
SCALE POCKET
TEMPERATURE SWITCH
STEAM
CONDENSATE
RETURN
STEAM TRAP
(BY MFG.)
AIR
316 STAINLESS STEEL DUCT, SLOPE TO
DRAIN. MIN. 1/8" PER FOOT
TO FLOOR
DRAIN
GALVANIZED
DUCT AS
SPECIFIED
ISOLATION
VALVE
DISPERSION
TUBES (TYP)
ABSORPTION DISTANCE
NOTE: TYPICAL FOR ALL LABS
0'-3"
WALL
FLOOR
5' -6
FLUSH MOUNTED MAGNEHELIC GAUGE
FOR DIFFERENTIAL PRESSURE INDICATION.
DWYER OR EQUAL.
NOTE:
DRILL PANEL COVERS FOR
SENSOR PROBE PENETRATIONS AS
REQUIRED. SEAL PENETRATIONS
ON LAB SIDE, AIR AND WATER
TIGHT.
LAB CORRIDOR
FLUSH MOUNTED
HOFFMAN PANEL AIR
AND WATER TIGHT.
NOTE:
FINAL LOCATION TO BE
DETERMINED BY CONTRACTING
OFFICER.
PROBE PENETRATION.
INSTALL AS PER
MANUFACTURER'S
RECOMMENDATION.
SEAL AROUND
PENETRATION AIR TIGHT.
NOTE:
1. CONTROLS CONTRACTOR SHALL FURNISH AND INSTALL MAGNEHELIC GAUGE IN
EACH LAB AND ULTRACOOL ROOM. REFER TO CONTRATING OFFICER FOR FINAL
LOCATION.
2. GAUGE IS NOT INTENDED TO BE USED IN SEQUENCE OF OPERATION, BUT TO
MONITOR.
CROMWELL
ARCHITECTS/
ENGINEERS
#5A
R
KANSAS -ENG
IN
EE
R
C E R T
IF
IC
AT
EOF
AUTHORIZ
A T
IO
N PROFESSIONAL
REGISTERED
ARKANSAS
ENGINEER
No. 12957
S T A T E O F
M A
X W
E L L A . G O
O D
15-JUL-2015
SHEETDRAWING NOSUBMITTED
SCALE DATE DRAWN CHECK
REVISIONS
NO. DATE DESCRIPTION BY CHECK
JEFFERSON,ARKANSAS 72079
NATIONAL CENTER FOR TOXICOLOGICAL RESEARCH
N C T R
BUILDING 14 RENOVATION
HVAC DETAILS
M-50307/15/2015
N.T.S.
2 AHU CHILLED AND HOT WATER COIL
N.T.S.
1 DUCT MOUNTED HUMIDIFIER
N.T.S.
3 DUCT MOUNTED HUMIDIFIER ELEVATION
4 MAGNEHELIC GAUGE
FINISHED FLOOR
SUCTION DIFFUSER
SUCTION DIFFUSER BRACE
SUCTION DIFFUSER DRAIN PLUG
FLEXIBLE PIPE
CONNECTOR, TYPICAL
TYPICAL SHUT-OFF VALVE - FULL-PORT
BALL OR BUTTERFLY TYPE ONLY - GATE
VALVES SHALL NOT BE PERMITTED
MOUNT ON UNIT SUPPORT EQUAL TO MIRO MECHANICAL UNIT
SUPPORT-HD. INSTALL LEVEL. BASE MATERIAL TO
POLYCARBONATE. PLATFORM TO BE SIZED AND INSTALL AS PER
MANUFACTURERS RECOMMENDATION.
TRIPLE DUTY VALVE
CONCENTRIC REDUCER, TYPICAL
PUMP DIFF. PRESS. GAUGE
WITH 1/4" SUCTION AND
DISCHARGE NEEDLE OR
GLOBE VALVES
ANCHOR PUMP TO SUPPORT
NOTE:
ISOLATION VALVING SHALL BE
FURNISHED AND INSTALLED AT PIPING
MAIN.
DETAIL NOTES:
1.
2.
3.
4.
SEE FLOOR PLANS FOR PIPE SIZES.
SEE EQUIPMENT SCHEDULES FOR VALVE DATA AND PIPE SIZES D1 AND D2.
INSTALL VALVES AS RECOMMENDED BY MANUFACTURER.
MAKE BYPASS VALVE DISCHARGE PIPE THE SAME SIZE AS D2 FOR THE
LARGEST PRV.
PROVIDE NECESSARY UNIONS FOR THE REMOVAL OF VALVE WITH SCREWED
CONNECTIONS.
SIPHON (TYP.)
VENT TO ATMOSPHERE
PILOT CONTROL LINE
REDUCER (TYP.)
IF REQUIRED.
NOTE 1
D1
N.C.
D2
D2
NOTE 1
NOTE 3
INVERTER
BUCKET TRAP
ASSEMBLY TYP.
PSV
4 D2 MIN.
20 D2 MIN.10 D1 MIN.
GENERAL NOTES:
A. DESIGNATE LOWER VALVE (A) AND UPPER VALVE (B) (1-PRV1A, 1-PRV1B).
B. USE DUAL VALVE PRESSURE REDUCING STATION WHEN THE MINIMUM LOAD OS
10% OR LESS THAN PEAK LOAD.
C. SAFETY VALVES SHALL BE SIZED SO AS TO RELIEVE AT PRESSURES OF 5-10 PSIG [35-
70kPa] IN EXCESS OF DELIVERED PRESSURES OF PRV'S AND TO HAVE A CAPACITY
EQUAL TO THE MAXIMUM CAPACITY OF PRV IT IS TO RELIEVE. VENT PIPE SHALL BE
NO LESS THAN ONE PIPE SIZE LARGER THAN SAFETY VALVE DISCHARGE AND SHALL
FURTHER BE SIZED SO THAT FRICTIONAL RESISTANCE OR VENT DOES NOT EXCEED
VELOCITY PRESSURE AT SAFETY VALVE OUTLET. VENTS FROM SAFETY VALVES
SHALL RUN THE SHORTEST AND MOST DIRECT ROUTE TO OUTDOOR THRU THE
ROOF. WHERE VENTS RUN IN FINISHED SPACE THEY SHALL BE FURRED IN TO MATCH
ADJACENT BUILDING CONSTRUCTION; IN UNFINISHED SPACE, PIPE TO BE COVERED
ONLY. SAFETY VALVES SHALL BE LOCATED AS SHOWN ON THE FLOOR PLANS.
NOTE:
1.
2.
3.
4.
5.
WHEN COIL IS INCLUDED IN CASING MOUNTED ON VIBRATION ISOLATOR
UNITS, THE RUNOUT PIPING FOR CONNECTIONS TO COIL SHALL BE
INSTALLED WITH SWING JOINTS TO ALLOW FOR THE VIBRATION.
PIPING SHALL BE INSTALLED IN SUCH MANNER THAT IT WILL NOT BLOCK
THE SWING OR USE OF ACCESS DOORS OR PANELS; NEITHER SHALL IT
BLOCK THE SERVICING OF FILTERS, VALVES, OR EQUIPMENT.
TRAP EACH COIL SEPARATELY WHEN INSTALLED IN A BANK OF TWO OR
MORE HIGH. ALSO PROVIDE SEPARATE VACUUM BREAKER FOR EACH
COIL.
TWO TRAP ASSEMBLIES IN PARALLEL ARE SHOWN. TWO TRAPS
REQUIRED WHEN CONDENSATE LOAD IS 5,000 LBS/HR [2400 KG/HR] OR
GREATER.
SUPPLY & RETURN PIPES ARE SHOWN FROM SAME END. REHEAT COIL
MAY HAVE SUPPLY & RETURN PIPES FROM OPPOSITE ENDS.
PIPE HANGER SHALL SUPPORT
PIPING INDEPENDENT OF COIL (TYP.)
PITCH COIL DOWN 1/4" [8mm] PER
FOOT TO CONDENSATE OUTLET
FULL SIZE TAPPING
PRESSURE GAGE
SCALE POCKET
SEE NOTE NO. 4
STEAM CONDENSATE RETURN
1/2" [15mm] CHECK VALVE
VACUUM BREAKER
INCREASER, IF REQUIRED
REDUCER,…