B09_Amd8_-_Spec_22_11_23_-_PLUMBING_PUMPS_0008.pdf

PDF 83 KB Posted

Attached to
DEVA 318717 - Rehab Furnace & Cow Creeks WTP/WWTP
Solicitation number
140P2025R0082
Issued by

About this file

This is a technical specification document (Section 22 11 23) for Plumbing Pumps that establishes requirements for packaged domestic water booster pump systems in a federal construction project (DEVA 318717, effective January 17, 2025).

The specification requires furnishing complete, packaged domestic water booster pump systems with all necessary components for proper operation. Base manufacturers are limited to Towle Whitney and Amtrol, with optional alternatives including Tigerflow, Xylem/Bell and Gossett, and Federal, subject to approval. All wetted surfaces must be lead-free (<0.25% Pb) and NSF 61 rated per federal law. Each pump must include a separate and independent variable frequency drive (VFD) with pressure transducer, pressure gauge, and relief valve, isolation valves on suction and discharge piping, and a separate disconnect box. Centrifugal pumps must feature stainless steel 304 casings with 304 stainless steel impellers, 316 stainless steel shaft sleeves, and totally enclosed fan cooled (TEFC) motors compliant with CE, RoHS, and CSA standards, capable of operating at ambient temperatures up to 125 degrees Fahrenheit. The VFD must include hands-off automatic capability, 98% or better efficiency, UL approval, NEMA 1 rated enclosure, pump protection against motor overload and hydraulic damage, automatic restart capability, operator control panel, parameter upload/download capability, proportional-integral-derivative control logic, and specific display functions. The hydropneumatic tank must be rated for potable water at maximum 125 PSI operating pressure and pre-charged to 10 PSI below system operating pressure. Component materials include lead-free brass for relief valves, pressure gauges, and ball valves; stainless steel for transducers and check valves; and Type L copper tube for manifold piping. The specification includes additional components such as HOA switches, elapsed time meters, and pump cycle meters. Warranty coverage extends 36 months from shipment. Submittals must include shop drawings, electrical wiring diagrams, pump curves with operation point indicated, and cyber security-related documentation per Section 01 81 33. Installation must follow manufacturer's instructions, and closeout activities must comply with cyber security requirements.

View the file

Other files

File Type Posted
B09_Amd11_-_B08_Attach3_-_WD_CA20260020_Mod2_0011.pdf PDF
Sol_140P2025R0082_Amd_0011.pdf PDF
B09_Amd10_-_QR55_Attach_Drawing_01-C4_42_Jan2026_0010.pdf PDF
B09_Amd10_-_QR55_Attach_Drawing_01-C4_38_Jan2026_0010.pdf PDF
B09_Amd10_-_QR55_Attach_Drawing_01-C4_40_Jan2026_0010.pdf PDF
B09_Amd10_QR_Tracker_-_DEVA_318717_Final_0010.xlsx XLSX spreadsheet
B09_Amd10_-_QR55_Attach_Drawing_01-C4_39_Jan2026_0010.pdf PDF
B09_Amd10_-_QR55_Attach_Drawing_00-C8_27_Jan2026_0010.pdf PDF
B09_Amd10_-_QR86_Attach_Drawing_C1_40_0010.pdf PDF
B09_Amd10_-_Drawing_G1_22_0010.pdf PDF
B09_Amd10_-_QR86_Attach_Drawing_C1_40B_0010.pdf PDF
Sol_140P2025R0082_Amd_0010.pdf PDF
B09_Amd10_-_B08_Attach4_-_DetailedContractPriceSchedule_0010.xlsx XLSX spreadsheet
B09_Amd10_-_Drawing_G1_2_0010.pdf PDF
B09_Amd10_-_Drawing_Coversheet_00_DEVA_318717_Jan2026x_0010.pdf PDF
B09_Amd10_-_Drawing_G1_21_0010.pdf PDF
Sol_140P2025R0082_Amd_0009.pdf PDF
B09_Amd8_-_Drawing_02-C5_29_Jan2026_0008.pdf PDF
B09_Amd8_-_Spec_33_14_19_-_VALVES___HYDRANTS_FOR_WATER_UTILITY_SERVICE_0008.pdf PDF
B09_Amd8_-_Drawing_02-G1_16_Dec2025_0008.pdf PDF
B09_Amd8_-_Spec_08_33_22_-_ALUMINUM_ROLLING_OVERHEAD_DOORS_0008.pdf PDF
B09_Amd8_-_Drawing_01-C1_29_Jan2026_0008.pdf PDF
B09_Amd8_-_QR22_Attach_Drawing_00-C7_1_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_02-C5_25_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_00-C8_30_Dec2025_0008.pdf PDF
B09_Amd8_-_Drawing_01-C4_42_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_01-C3_1_Dec2025_0008.pdf PDF
B09_Amd8_-_Drawing_00-C3_20_Dec2025_0008.pdf PDF
B09_Amd8_-_Spec_33_32_00_-_WASTEWATER_PUMPING_STATIONS_0008.pdf PDF
B09_Amd8_-_Spec_33_31_11_-_GRAVITY_SEWER_PIPELINE___MANHOLE_INSTALLATION_0008.pdf PDF
B09_Amd8_QR_Tracker_-_DEVA_318717_0008.xlsx XLSX spreadsheet
B09_Amd8_-_Drawing_Coversheet_00_DEVA_318717_Jan2026_0008.pdf PDF
Sol_140P2025R0082_Amd_0008.pdf PDF
B09_Amd8_-_Drawing_01-C1_31_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_02-C6_7_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_00-C3_15_Dec2025_0008.pdf PDF
B09_Amd8_-_Drawing_00-G1_2_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_02-C7_5_Dec2025_0008.pdf PDF
B09_Amd8_-_Spec_33_11_13_-_POTABLE_WATER_SUPPLY_WELLS_0008.pdf PDF
B09_Amd8_-_Drawing_00-C3_18_Dec2025_0008.pdf PDF
B09_Amd8_-_Drawing_02-C5_33_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_01-C1_42_Jan2026_0008.pdf PDF
B09_Amd8_-_QR56_Attach_Drawing_02-C2_20_Dec2025_0008.pdf PDF
B09_Amd8_-_Spec_33_31_05_-_MANHOLE_LINING___REHABILITATION_0008.pdf PDF
B09_Amd8_-_Drawing_01-G1_15_Jan2026_0008.pdf PDF
B09_Amd8_-_QR56_Attach_Drawing_02-C2_18_Dec2025_0008.pdf PDF
B09_Amd8_-_Drawing_01-C1_67_Jan2026_0008.pdf PDF
B09_Amd8_-_Spec_46_33_11_-_CHEMICAL_FEED_-_LIQUID_SYSTEMS_0008.pdf PDF
B09_Amd8_-_Drawing_02-C2_22_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_02-X1_2_Jan2026_0008.pdf PDF
Show 40 more

Latest 50 of 109 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DEVA 318717 22 11 23 - 1

January 17, 2025 PLUMBING PUMPS

SECTION 22 11 23 - PLUMBING PUMPS

PART 1 - GENERAL

1.1 SUMMARY

A. Furnish labor, materials, tools, equipment, and services for Plumbing Pumps, as indicated, in accordance with provisions of Contract Documents.

B. Systems Included:

1. Packaged domestic water booster pumps.

C. Completely coordinate with work of other trades.

1.2 SUBMITTALS

A. Product Data:

1. Packaged domestic water booster pumps

a. Shop drawings.

b. Electrical wiring diagrams.

c. Include pump curves with point of operation indicated.

A. Refer to Section 01 81 33 - Cyber Security Requirements for required cyber security related submittals.

B. Contract Closeout Information:

1. Operation and Maintenance Data.

2. Owner instruction reports.

1.3 QUALITY ASSURANCE

A. Pipe and fittings standards: See Section 22 05 03.

B. Manual-valve and check-valve standards: See Section 23 05 23.

C. Standards:

1. UL 778: Motor Operated Water Pumps.

1.4 WARRANTY

A. Thirty-six (36) months from shipment.

DEVA 318717 22 11 23 - 2

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Packaged Domestic Water Pumping System:

1. Base:

a. Towle Whitney.

b. Amtrol.

2. Optional:

a. Tigerflow.

b. Xylem/Bell and Gossett.

c. Federal.

B. Other manufacturers desiring approval comply with Section 01 61 00.

2.2 MATERIALS

A. Pumps - General:

1. Motors: Section 23 05 00.

2. Motor data: As scheduled.

3. Pump capacities: As scheduled.

4. Provide disconnects.

2.3 PACKAGED DOMESTIC WATER BOOSTER PUMP SYSTEMS

A. Provide complete, packaged domestic water booster pump system including all components required to ensure proper operation.

B. Flow rate and total developed head: As Scheduled.

C. Number of pumps: As Scheduled.

D. Assembled Units:

1. All “wetted surfaces” shall be lead free (<.25% Pb) in conformance with the 1/4/14 federal law and shall be NSF 61 rated

2. Shall include a separate and independent variable frequency drive (VFD) for each pump with a pressure transducer, pressure gauge, and relief valve. Piping and frame shall not interfere with access to the controls

3. Each pump shall include isolation valves on both the suction and discharge piping

4. Each pump shall have a separate and independent disconnect box

5. Shall be mounted on a frame for ease of transport and installation.

E. Centrifugal pump:

DEVA 318717 22 11 23 - 3

1. Shall have a stainless steel casing with 304 stainless steel impellers.

2. Shall have a 316 stainless steel shaft sleeve. Mechanical seal shall be rated to withstand pressure of up to 142 PSI

3. Motor shall be to totally enclosed fan cooled (TEFC). And manufactured in compliance with CE, RoHS and CSA

4. Must be able to withstand and operate with ambient operating temperatures up to 125 degrees F.

F. Variable Frequency Drive (where required)

1. Will alternate the lead pump every 24 hours (field adjustable) of run time. The lag pump shall be in standby

2. Shall have hands-off automatic (HOA) capability

3. Rated to operate using specified power requirement. The drive efficiency shall be 98% or better

4. Have UL approval with all factory installed options and preset values and/or last saved data values will remain available to the operator after power outage.

5. Shall have at least NEMA 1 rated conduit enclosure

6. The program will protect the pumps against damaging hydraulic conditions such as:

a. Motor overload, Pump overflow surges, Loss of prime due to incoming water supply interruption, Hunting

b. Protection from overload through frequency/current optimization

c. Protection from hydraulic damage by restricting the pumps to operate beyond their published end of curve

7. Shall have the ability to automatically restart after an over-current, over-voltage, under-voltage or loss of input signal

8. Shall have an operator control panel for customization of parameters

9. Shall include a feature to upload/download parameters into an external device to be used with another drive or the same drive

10. Shall have a removable non-volatile memory device

11. Shall be capable of accepting individual analog inputs from transducer. All transducer inputs must be wired to the variable

12. frequency drive for continuous scan and comparison function

13. Ladder logic program shall utilize a proportional - integral - derivative control function

14. Shall display the following values:

a. Pump running/standby, Pump speed in Hz, User adjustable parameters such as

PID set points, Motor frequency, Motor current, Threshold set points for PID error, Min operating frequency, Troubleshooting and diagnostics of faults.

G. Transducer:

1. The transducer shall be rated for required system pressure and shall be 4-20 mA analog

2. Separate transducers shall be supplied for each variable frequency drive to ensure.

redundancy.

H. Hydropneumatic Tank:

DEVA 318717 22 11 23 - 4

1. Pneumatic expansion tank shall be rated for use with potable water with an operating pressure of a maximum 125 PSI.

2. Pre-charged to a pressure of 10 PSI below system operating pressure for system to run properly.

I. Component Materials:

1. Relief valves: lead free brass

2. Pressure gauges: lead free brass

3. Transducers: stainless steel

4. Check valves: stainless steel

5. Ball valves: lead free brass

6. Manifold piping: Type L copper tube

7. Fittings: Lead free brass for stainless steel

J. Additional Components

1. HOA switch.

2. Elapsed time meter.

3. Pump cycle meter.

4. Additional components may be provided with the packaged booster pump system or provided and installed separately.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Install as indicated and in accordance with manufacturer's instructions and recommendations.

B. Furnish piping, isolation valves, check valves, and fittings per manufacturer recommendation.

3.2 CLOSEOUT ACTIVITIES

A. Refer to Section 01 81 33 - Cyber-Security Requirements for cyber security related closeout requirements.

END OF SECTION 22 11 23