This document contains a detailed sewer pipe inspection report from Pipe Tec for a project in DEVA-NP (likely Death Valley National Park) on 6/8/2023. The report covers eight separate pipe segment inspections between multiple manholes (MH-008 to MH-005), utilizing different pipe materials including Vitrified Clay Pipe (VCP), Polyvinyl Chloride (PVC), and Cast Iron. The total length surveyed was 511 linear feet across various pipe segments, with pipe sizes ranging from 6 to 8 inches.

Key findings from the inspections reveal significant issues in multiple pipe segments, including severe debris obstructions, joint offsets and separations, line misalignments, and corrosion. Several inspections were abandoned due to severe debris and poor pipe conditions. The survey was conducted by R. Vargas under dry weather conditions, with no pre-cleaning performed. The purpose of the investigation was a pre-rehabilitation survey for sanitary sewage pipes, suggesting potential upcoming maintenance or replacement work may be necessary given the extensive pipe degradation observed.

View the file

Other files

File Type Posted
B09_Amd11_-_B08_Attach3_-_WD_CA20260020_Mod2_0011.pdf PDF
Sol_140P2025R0082_Amd_0011.pdf PDF
B09_Amd10_-_QR55_Attach_Drawing_01-C4_42_Jan2026_0010.pdf PDF
B09_Amd10_-_QR55_Attach_Drawing_01-C4_38_Jan2026_0010.pdf PDF
B09_Amd10_-_QR55_Attach_Drawing_01-C4_40_Jan2026_0010.pdf PDF
B09_Amd10_QR_Tracker_-_DEVA_318717_Final_0010.xlsx XLSX spreadsheet
B09_Amd10_-_QR55_Attach_Drawing_01-C4_39_Jan2026_0010.pdf PDF
B09_Amd10_-_QR55_Attach_Drawing_00-C8_27_Jan2026_0010.pdf PDF
B09_Amd10_-_QR86_Attach_Drawing_C1_40_0010.pdf PDF
B09_Amd10_-_Drawing_G1_22_0010.pdf PDF
B09_Amd10_-_QR86_Attach_Drawing_C1_40B_0010.pdf PDF
Sol_140P2025R0082_Amd_0010.pdf PDF
B09_Amd10_-_B08_Attach4_-_DetailedContractPriceSchedule_0010.xlsx XLSX spreadsheet
B09_Amd10_-_Drawing_G1_2_0010.pdf PDF
B09_Amd10_-_Drawing_Coversheet_00_DEVA_318717_Jan2026x_0010.pdf PDF
B09_Amd10_-_Drawing_G1_21_0010.pdf PDF
Sol_140P2025R0082_Amd_0009.pdf PDF
B09_Amd8_-_Drawing_02-C5_29_Jan2026_0008.pdf PDF
B09_Amd8_-_Spec_33_14_19_-_VALVES___HYDRANTS_FOR_WATER_UTILITY_SERVICE_0008.pdf PDF
B09_Amd8_-_Drawing_02-G1_16_Dec2025_0008.pdf PDF
B09_Amd8_-_Spec_08_33_22_-_ALUMINUM_ROLLING_OVERHEAD_DOORS_0008.pdf PDF
B09_Amd8_-_Drawing_01-C1_29_Jan2026_0008.pdf PDF
B09_Amd8_-_QR22_Attach_Drawing_00-C7_1_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_02-C5_25_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_00-C8_30_Dec2025_0008.pdf PDF
B09_Amd8_-_Drawing_01-C4_42_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_01-C3_1_Dec2025_0008.pdf PDF
B09_Amd8_-_Drawing_00-C3_20_Dec2025_0008.pdf PDF
B09_Amd8_-_Spec_33_32_00_-_WASTEWATER_PUMPING_STATIONS_0008.pdf PDF
B09_Amd8_-_Spec_33_31_11_-_GRAVITY_SEWER_PIPELINE___MANHOLE_INSTALLATION_0008.pdf PDF
B09_Amd8_QR_Tracker_-_DEVA_318717_0008.xlsx XLSX spreadsheet
B09_Amd8_-_Drawing_Coversheet_00_DEVA_318717_Jan2026_0008.pdf PDF
Sol_140P2025R0082_Amd_0008.pdf PDF
B09_Amd8_-_Drawing_01-C1_31_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_02-C6_7_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_00-C3_15_Dec2025_0008.pdf PDF
B09_Amd8_-_Drawing_00-G1_2_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_02-C7_5_Dec2025_0008.pdf PDF
B09_Amd8_-_Spec_33_11_13_-_POTABLE_WATER_SUPPLY_WELLS_0008.pdf PDF
B09_Amd8_-_Drawing_00-C3_18_Dec2025_0008.pdf PDF
B09_Amd8_-_Drawing_02-C5_33_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_01-C1_42_Jan2026_0008.pdf PDF
B09_Amd8_-_QR56_Attach_Drawing_02-C2_20_Dec2025_0008.pdf PDF
B09_Amd8_-_Spec_33_31_05_-_MANHOLE_LINING___REHABILITATION_0008.pdf PDF
B09_Amd8_-_Drawing_01-G1_15_Jan2026_0008.pdf PDF
B09_Amd8_-_QR56_Attach_Drawing_02-C2_18_Dec2025_0008.pdf PDF
B09_Amd8_-_Drawing_01-C1_67_Jan2026_0008.pdf PDF
B09_Amd8_-_Spec_46_33_11_-_CHEMICAL_FEED_-_LIQUID_SYSTEMS_0008.pdf PDF
B09_Amd8_-_Drawing_02-C2_22_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_02-X1_2_Jan2026_0008.pdf PDF
Show 40 more

Latest 50 of 109 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PIPE TEC

5103 ELTON ST, BALDWIN PARK

Tel. (213)761-0031 tomv@pipetec-inc.com

Page P-1

Section Profile

No. PSR Upstream MH Downstream MH Date Material Total Length Length Surveyed

1 6/8/2023 6:32:24 AM MH-008 MH-007 6/8/2023 VCP 60.20 60.20

2 6/8/2023 6:33:47 AM MH-007 MH-006 6/8/2023 VCP 57.80 57.80

4 6/8/2023 8:12:47 AM MH-025 MH-005 6/8/2023 PVC 220.80 220.80

5 6/8/2023 8:22:51 AM MH-026 MH-025 6/8/2023 PVC 49.50 49.50

6 6/8/2023 8:28:15 AM MH-027 MH-026 6/8/2023 PVC 62.70 62.70

7 6/8/2023 8:39:49 AM HQ BLDG MH-026 6/8/2023 CAS 2.00 2.00

6 Circular = 453.00 Total Length (6 Inspections, 453.00 Length Surveyed)

No. PSR Upstream MH Downstream MH Date Material Total Length Length Surveyed

3 6/8/2023 7:08:37 AM MH-006 MH-005 6/8/2023 VCP 56.00 56.00

8 6/8/2023 8:49:13 AM MH-006 MH-005. 6/8/2023 PVC 2.00 2.00

8 Circular = 58.00 Total Length (2 Inspections, 58.00 Length Surveyed)

511.00 Total Length (8 Inspections, 511.00 Length Surveyed)

Project

06_08_2023_DEVA-NP

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_08_2023_DEVA-NP // Page: 1

City: DEVA-NP Drainage Area: Upstream MH: MH-008

Street: FURNACE CREEK Media Label: Up Rim to Invert:

Location Code: Easement/Right of way Flow Control: Downstream MH: MH-007

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 6 " Sewer Category: SEC Joints passed: 0

Pipe material: Vitrified Clay Pipe Purpose: Pre-Rehabilitation Survey Joints failed: 0

Lining Method: Owner:

Additional Info:

1:455 Distance Code Observation Grade

0.0 AMH Manhole / MH-007

0.0 MWL Water Level, 5% of the vertical dimension

0.0 MGO Miscellaneous General Observation / REVERSE

SET UP

3.5 TB Tap Break-in/Hammer at 2 o'clock, dia/height:

4inch

3.5 S01 OBZ Obstruction Other, 20% of cross sectional area

from 4 o'clock to 8 o'clock, Start / DEBRIS

60.2 F01 OBZ Obstruction Other, 20% of cross sectional area

from 4 o'clock to 8 o'clock, Finish / DEBRIS

M3

60.2 OBZ Obstruction Other, 30% of cross sectional area

from 4 o'clock to 8 o'clock / SEVERE DEBRIS

M4

60.2 MSA Miscellaneous Survey Abandoned / SEVERE

DEBRIS UNABLE TO CONTINUE

6/8/2023 Dry R.VARGAS U-209-211 6/8/2023 6:32:24 AM

No Pre-Cleaning Upstream 60.2 ' 60.2 '

QSR QMR SPR MPR OPR SPRI MPRI OPRI

0000 413A 0.0 37.0 0.0 3.1 3.137.0

QOR

413A

MH-007

TB - 3.50

OBZ - 3.50

OBZ - 60.20

OBZ - 60.20

MSA - 60.20

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_08_2023_DEVA-NP // Page: 2

City: DEVA-NP Drainage Area: Upstream MH: MH-007

Street: FURNACE CREEK Media Label: Up Rim to Invert:

Location Code: Easement/Right of way Flow Control: Downstream MH: MH-006

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 6 " Sewer Category: SEC Joints passed: 0

Pipe material: Vitrified Clay Pipe Purpose: Pre-Rehabilitation Survey Joints failed: 0

Lining Method: Owner:

Additional Info:

1:437 Distance Code Observation Grade

0.0 AMH Manhole / MH-007

0.0 MWL Water Level, 5% of the vertical dimension

0.0 MGO Miscellaneous General Observation / REVERSE

SET UP

57.8 OBZ Obstruction Other, 60% of cross sectional area

from 3 o'clock to 9 o'clock / SEVERE DEBRIS

M5

57.8 MSA Miscellaneous Survey Abandoned / SEVERE

DEBRIS UNABLE TO CONTINUE

6/8/2023 Dry R.VARGAS U-209-211 6/8/2023 6:33:47 AM

No Pre-Cleaning Downstream 57.8 ' 57.8 '

QSR QMR SPR MPR OPR SPRI MPRI OPRI

0000 5100 0.0 5.0 0.0 5.0 5.05.0

QOR

MH-007

OBZ - 57.80

MSA - 57.80

MSA - 57.80

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_08_2023_DEVA-NP // Page: 3

City: DEVA-NP Drainage Area: Upstream MH: MH-006

Street: FURNACE CREEK Media Label: Up Rim to Invert:

Location Code: Easement/Right of way Flow Control: Downstream MH: MH-005

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 8 " Sewer Category: SEC Joints passed: 0

Pipe material: Vitrified Clay Pipe Purpose: Pre-Rehabilitation Survey Joints failed: 0

Lining Method: Owner:

Additional Info:

1:423 Distance Code Observation Grade

0.0 AMH Manhole / MH-006

0.0 MWL Water Level, 5% of the vertical dimension

2.0 S01 OBZ Obstruction Other, 10% of cross sectional area

from 4 o'clock to 8 o'clock, Start / DEBRIS

33.4 MMC Miscellaneous Material Change, Cast iron / CIP

56.0 F01 OBZ Obstruction Other, 10% of cross sectional area

from 4 o'clock to 8 o'clock, Finish / DEBRIS

M2

56.0 OBZ Obstruction Other, 40% of cross sectional area

from 3 o'clock to 9 o'clock / SEVERE DEBRIS

M5

56.0 MSA Miscellaneous Survey Abandoned / SEVERE

DEBRIS

6/8/2023 Dry R.VARGAS U-209-211 6/8/2023 7:08:37 AM

No Pre-Cleaning Downstream 56.0 ' 56.0 '

QSR QMR SPR MPR OPR SPRI MPRI OPRI

0000 512A 0.0 27.0 0.0 2.3 2.327.0

QOR

512A

MH-006

MMC - 33.40

OBZ - 56.00

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_08_2023_DEVA-NP // Page: 4

City: DEVA-NP Drainage Area: Upstream MH: MH-025

Street: FURNACE CREEK Media Label: Up Rim to Invert:

Location Code: Easement/Right of way Flow Control: Downstream MH: MH-005

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 6 " Sewer Category: SEC Joints passed: 0

Pipe material: Polyvinyl Chloride Purpose: Pre-Rehabilitation Survey Joints failed: 0

Lining Method: Owner:

Additional Info:

1:1667 Distance Code Observation Grade

0.0 AMH Manhole / MH-005

0.0 MWL Water Level, 30% of the vertical dimension

220.8 AMH Manhole / MH-025

6/8/2023 Dry R.VARGAS U-209-211 6/8/2023 8:12:47 AM

No Pre-Cleaning Upstream 220.8 ' 220.8 '

QSR QMR SPR MPR OPR SPRI MPRI OPRI

0000 0000 0.0 0.0 0.0 0.0 0.00.0

QOR

MH-005

MH-025

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_08_2023_DEVA-NP // Page: 5

City: DEVA-NP Drainage Area: Upstream MH: MH-026

Street: FURNACE CREEK Media Label: Up Rim to Invert:

Location Code: Easement/Right of way Flow Control: Downstream MH: MH-025

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 6 " Sewer Category: SEC Joints passed: 0

Pipe material: Polyvinyl Chloride Purpose: Pre-Rehabilitation Survey Joints failed: 0

Lining Method: Owner:

Additional Info:

1:374 Distance Code Observation Grade

0.0 AMH Manhole / MH-025

0.0 MWL Water Level, 5% of the vertical dimension

20.8 TF Tap Factory Made at 12 o'clock, dia/height: 6inch

39.5 JOM Joint Offset Medium S3

39.5 JSM Joint Separated Medium S3

49.5 AMH Manhole / MH-026

6/8/2023 Dry R.VARGAS U-209-211 6/8/2023 8:22:51 AM

No Pre-Cleaning Upstream 49.5 ' 49.5 '

QSR QMR SPR MPR OPR SPRI MPRI OPRI

3200 0000 6.0 0.0 3.0 0.0 3.06.0

QOR

MH-025

MH-026

TF - 20.80

JOM - 39.50

JSM - 39.50

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_08_2023_DEVA-NP // Page: 6

City: DEVA-NP Drainage Area: Upstream MH: MH-027

Street: FURNACE CREEK Media Label: Up Rim to Invert:

Location Code: Easement/Right of way Flow Control: Downstream MH: MH-026

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 6 " Sewer Category: SEC Joints passed: 0

Pipe material: Polyvinyl Chloride Purpose: Pre-Rehabilitation Survey Joints failed: 0

Lining Method: Owner:

Additional Info:

1:474 Distance Code Observation Grade

0.0 AMH Manhole / MH-026

0.0 MWL Water Level, 5% of the vertical dimension

62.7 AMH Manhole / MH-027

6/8/2023 Dry R.VARGAS U-209-211 6/8/2023 8:28:15 AM

No Pre-Cleaning Upstream 62.7 ' 62.7 '

QSR QMR SPR MPR OPR SPRI MPRI OPRI

0000 0000 0.0 0.0 0.0 0.0 0.00.0

QOR

MH-026

MH-027

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_08_2023_DEVA-NP // Page: 7

City: DEVA-NP Drainage Area: Upstream MH: HQ BLDG

Street: FURNACE CREEK Media Label: Up Rim to Invert:

Location Code: Easement/Right of way Flow Control: Downstream MH: MH-026

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 6 " Sewer Category: SEC Joints passed: 0

Pipe material: Cast Iron Purpose: Pre-Rehabilitation Survey Joints failed: 0

Lining Method: Owner:

Additional Info:

1:50 Distance Code Observation Grade

0.0 MWL Water Level, 0% of the vertical dimension

0.0 AMH Manhole / MH-026

2.0 MGO Miscellaneous General Observation /

CORROSSION IN PIPELINE SEVERE

2.0 OBZ Obstruction Other, 50% of cross sectional area

from 3 o'clock to 9 o'clock / DEBRIS

M5

2.0 MSA Miscellaneous Survey Abandoned / SEVERE

DEBRIS

6/8/2023 Dry R.VARGAS U-209-211 6/8/2023 8:39:49 AM

No Pre-Cleaning Upstream 2.0 ' 2.0 '

QSR QMR SPR MPR OPR SPRI MPRI OPRI

0000 5100 0.0 5.0 0.0 5.0 5.05.0

QOR

MH-026

MGO - 2.00

OBZ - 2.00

MSA - 2.00

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_08_2023_DEVA-NP // Page: 8

City: DEVA-NP Drainage Area: Upstream MH: MH-006

Street: FURNACE CREEK Media Label: Up Rim to Invert:

Location Code: Easement/Right of way Flow Control: Downstream MH: MH-005.

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 8 " Sewer Category: SEC Joints passed: 0

Pipe material: Polyvinyl Chloride Purpose: Pre-Rehabilitation Survey Joints failed: 0

Lining Method: Owner:

Additional Info:

1:50 Distance Code Observation Grade

0.0 AMH Manhole / MH-005

0.0 MWL Water Level, 100% of the vertical dimension

2.0 LR Line Right, 45% M4

2.0 MSA Miscellaneous Survey Abandoned / ALIGNMENT

RIGHT SEVERE

6/8/2023 Dry R.VARGAS U-209-211 6/8/2023 8:49:13 AM

No Pre-Cleaning Upstream 2.0 ' 2.0 '

QSR QMR SPR MPR OPR SPRI MPRI OPRI

0000 4100 0.0 4.0 0.0 4.0 4.04.0

QOR

MH-005.

LR - 2.00

LR - 2.00

6 Circular = 453.00 Total Length (6 Inspections, 453.00 Length Surveyed)
8 Circular = 58.00 Total Length (2 Inspections, 58.00 Length Surveyed)
511.00 Total Length (8 Inspections, 511.00 Length Surveyed)