This document contains a comprehensive sewer pipe inspection report from Pipe Tec, detailing CCTV camera surveys of multiple manhole segments in the DEVA-NP area on June 5, 2023. The inspection covered approximately 1,228.90 linear feet across 18 different pipe segments, primarily using 6-inch diameter pipes made of Vitrified Clay Pipe (VCP), Polyvinyl Chloride (PVC), and other materials. The survey was conducted by R. Vargas under certificate number U-209-211, with no pre-cleaning performed before the inspection.

The inspection reports reveal multiple significant findings across the surveyed segments, including severe debris obstructions, liner damages, joint separations, and offset joints. Common issues included obstruction of 20-70% of cross-sectional areas, liner damage from 7 o'clock to 5 o'clock positions, joint separations of medium and large scales, and joint offsets ranging from medium (3 feet) to large (30-45 inches). The pipes were part of a sanitary sewage system in local rural streets, with locations including Skyline Drive, Coyote Loop, and Old Ghost Road. The inspection methodology involved downstream and upstream camera traversals, documenting water levels, tap connections, and various pipe condition anomalies.

View the file

Other files

File Type Posted
B09_Amd11_-_B08_Attach3_-_WD_CA20260020_Mod2_0011.pdf PDF
Sol_140P2025R0082_Amd_0011.pdf PDF
B09_Amd10_-_QR55_Attach_Drawing_01-C4_42_Jan2026_0010.pdf PDF
B09_Amd10_-_QR55_Attach_Drawing_01-C4_38_Jan2026_0010.pdf PDF
B09_Amd10_-_QR55_Attach_Drawing_01-C4_40_Jan2026_0010.pdf PDF
B09_Amd10_QR_Tracker_-_DEVA_318717_Final_0010.xlsx XLSX spreadsheet
B09_Amd10_-_QR55_Attach_Drawing_01-C4_39_Jan2026_0010.pdf PDF
B09_Amd10_-_QR55_Attach_Drawing_00-C8_27_Jan2026_0010.pdf PDF
B09_Amd10_-_QR86_Attach_Drawing_C1_40_0010.pdf PDF
B09_Amd10_-_Drawing_G1_22_0010.pdf PDF
B09_Amd10_-_QR86_Attach_Drawing_C1_40B_0010.pdf PDF
Sol_140P2025R0082_Amd_0010.pdf PDF
B09_Amd10_-_B08_Attach4_-_DetailedContractPriceSchedule_0010.xlsx XLSX spreadsheet
B09_Amd10_-_Drawing_G1_2_0010.pdf PDF
B09_Amd10_-_Drawing_Coversheet_00_DEVA_318717_Jan2026x_0010.pdf PDF
B09_Amd10_-_Drawing_G1_21_0010.pdf PDF
Sol_140P2025R0082_Amd_0009.pdf PDF
B09_Amd8_-_Drawing_02-C5_29_Jan2026_0008.pdf PDF
B09_Amd8_-_Spec_33_14_19_-_VALVES___HYDRANTS_FOR_WATER_UTILITY_SERVICE_0008.pdf PDF
B09_Amd8_-_Drawing_02-G1_16_Dec2025_0008.pdf PDF
B09_Amd8_-_Spec_08_33_22_-_ALUMINUM_ROLLING_OVERHEAD_DOORS_0008.pdf PDF
B09_Amd8_-_Drawing_01-C1_29_Jan2026_0008.pdf PDF
B09_Amd8_-_QR22_Attach_Drawing_00-C7_1_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_02-C5_25_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_00-C8_30_Dec2025_0008.pdf PDF
B09_Amd8_-_Drawing_01-C4_42_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_01-C3_1_Dec2025_0008.pdf PDF
B09_Amd8_-_Drawing_00-C3_20_Dec2025_0008.pdf PDF
B09_Amd8_-_Spec_33_32_00_-_WASTEWATER_PUMPING_STATIONS_0008.pdf PDF
B09_Amd8_-_Spec_33_31_11_-_GRAVITY_SEWER_PIPELINE___MANHOLE_INSTALLATION_0008.pdf PDF
B09_Amd8_QR_Tracker_-_DEVA_318717_0008.xlsx XLSX spreadsheet
B09_Amd8_-_Drawing_Coversheet_00_DEVA_318717_Jan2026_0008.pdf PDF
Sol_140P2025R0082_Amd_0008.pdf PDF
B09_Amd8_-_Drawing_01-C1_31_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_02-C6_7_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_00-C3_15_Dec2025_0008.pdf PDF
B09_Amd8_-_Drawing_00-G1_2_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_02-C7_5_Dec2025_0008.pdf PDF
B09_Amd8_-_Spec_33_11_13_-_POTABLE_WATER_SUPPLY_WELLS_0008.pdf PDF
B09_Amd8_-_Drawing_00-C3_18_Dec2025_0008.pdf PDF
B09_Amd8_-_Drawing_02-C5_33_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_01-C1_42_Jan2026_0008.pdf PDF
B09_Amd8_-_QR56_Attach_Drawing_02-C2_20_Dec2025_0008.pdf PDF
B09_Amd8_-_Spec_33_31_05_-_MANHOLE_LINING___REHABILITATION_0008.pdf PDF
B09_Amd8_-_Drawing_01-G1_15_Jan2026_0008.pdf PDF
B09_Amd8_-_QR56_Attach_Drawing_02-C2_18_Dec2025_0008.pdf PDF
B09_Amd8_-_Drawing_01-C1_67_Jan2026_0008.pdf PDF
B09_Amd8_-_Spec_46_33_11_-_CHEMICAL_FEED_-_LIQUID_SYSTEMS_0008.pdf PDF
B09_Amd8_-_Drawing_02-C2_22_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_02-X1_2_Jan2026_0008.pdf PDF
Show 40 more

Latest 50 of 109 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PIPE TEC

5103 ELTON ST, BALDWIN PARK

Tel. (213)761-0031 tomv@pipetec-inc.com

Page P-1

Section Profile

No. PSR Upstream MH Downstream MH Date Material Total Length Length Surveyed

1 6/5/2023 12:04:03 PM MH-CC154 MH-CC153 6/5/2023 VCP 1.00 1.00

2 6/5/2023 12:22:10 PM MH-CC154 MH-CC153. 6/5/2023 VCP 2.00 2.00

3 6/5/2023 12:30:59 PM MH-CC153 MH-CC152 6/5/2023 VCP 2.00 2.00

4 6/5/2023 12:34:12 PM MH-CC153 MH-CC152. 6/5/2023 VCP 2.00 2.00

5 6/5/2023 12:56:46 PM MH-CC151 MH-CC150 6/5/2023 VCP 2.00 2.00

6 6/5/2023 1:08:13 PM MH-CC151 MH-CC150. 6/5/2023 VCP 2.00 2.00

8 6/5/2023 1:09:24 PM MH-CC150 MH-CC149 6/5/2023 VCP 2.00 2.00

9 6/5/2023 1:23:35 PM MH-CC150 MH-CC149. 6/5/2023 VCP 2.00 2.00

10 6/5/2023 1:33:06 PM MH-CC149 MH-CC148 6/5/2023 VCP 2.00 2.00

11 6/5/2023 2:08:03 PM MH-CC149 MH-CC148. 6/5/2023 VCP 2.00 2.00

13 6/5/2023 2:17:44 PM MH-CC168 MH-CC167 6/5/2023 PVC 149.40 149.40

15 6/5/2023 2:46:23 PM MH-CC169 MH-CC168 6/5/2023 PVC 120.20 120.20

16 6/5/2023 3:02:37 PM MH-CC167 COYOTE LOOP

LIFT STA.

6/5/2023 PVC 65.50 65.50

18 6/5/2023 3:09:38 PM MH-CC158 MH-CC157. 6/5/2023 PVC 260.80 260.80

19 6/5/2023 3:52:32 PM MH-CC157 MH-CC156 6/5/2023 ZZZ 117.40 117.40

20 6/5/2023 4:20:57 PM MH-CC145 MH-CC144 6/5/2023 ZZZ 268.60 268.60

21 6/5/2023 4:38:27 PM MH-CC144 MH-CC143 6/5/2023 PVC 131.10 131.10

22 6/5/2023 4:58:36 PM MH-CC144 .MH-CC143. 6/5/2023 PVC 96.90 96.90

6 Circular = 1228.90 Total Length (18 Inspections, 1228.90 Length Surveyed)

1228.90 Total Length (18 Inspections, 1228.90 Length Surveyed)

Project

06_05_2023_D.E.V.ANP

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_05_2023_D.E.V.ANP // Page: 1

City: DEVA-NP Drainage Area: Upstream MH: MH-CC154

Street: SKYLINE DR Media Label: Up Rim to Invert:

Location Code: Local rural streets with light traffic Flow Control: Downstream MH: MH-CC153

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 6 " Sewer Category: SEC Joints passed: 0

Pipe material: Vitrified Clay Pipe Purpose: Joints failed: 0

Lining Method: Owner:

Additional Info:

1:50 Distance Code Observation Grade

0.0 AMH Manhole / MH-CC153

0.0 MWL Water Level, 5% of the vertical dimension

0.0 OBZ Obstruction Other, 70% of cross sectional area

from 2 o'clock to 10 o'clock / SEVERE DEBRIS

M5

1.0 MSA Miscellaneous Survey Abandoned / END OF

CCTV SEVERE DEBRIS

6/5/2023 Dry R VARGAS U-209-211 6/5/2023 12:04:03 PM

No Pre-Cleaning Downstream 1.0 ' 1.0 '

QSR QMR SPR MPR OPR SPRI MPRI OPRI

0000 5100 0.0 5.0 0.0 5.0 5.05.0

QOR

MH-CC154

OBZ - 0.00

OBZ - 0.00

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_05_2023_D.E.V.ANP // Page: 2

City: DEVA-NP Drainage Area: Upstream MH: MH-CC154

Street: SKYLINE DR Media Label: Up Rim to Invert:

Location Code: Local rural streets with light traffic Flow Control: Downstream MH: MH-CC153.

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 6 " Sewer Category: SEC Joints passed: 0

Pipe material: Vitrified Clay Pipe Purpose: Joints failed: 0

Lining Method: Owner:

Additional Info:

1:50 Distance Code Observation Grade

0.0 AMH Manhole / MH-CC154

0.0 MWL Water Level, 5% of the vertical dimension

2.0 OBZ Obstruction Other, 30% of cross sectional area

from 4 o'clock to 8 o'clock / SEVERE DEBRIS

M4

2.0 MSA Miscellaneous Survey Abandoned / SEVERE

DEBRIS

6/5/2023 Dry R VARGAS U-209-211 6/5/2023 12:22:10 PM

No Pre-Cleaning Upstream 2.0 ' 2.0 '

QSR QMR SPR MPR OPR SPRI MPRI OPRI

0000 4100 0.0 4.0 0.0 4.0 4.04.0

QOR

MH-CC153.

OBZ - 2.00

OBZ - 2.00

MSA - 2.00

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_05_2023_D.E.V.ANP // Page: 3

City: DEVA-NP Drainage Area: Upstream MH: MH-CC153

Street: SKYLINE DR Media Label: Up Rim to Invert:

Location Code: Local rural streets with light traffic Flow Control: Downstream MH: MH-CC152

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 6 " Sewer Category: SEC Joints passed: 0

Pipe material: Vitrified Clay Pipe Purpose: Joints failed: 0

Lining Method: Owner:

Additional Info:

1:50 Distance Code Observation Grade

0.0 AMH Manhole / MH-CC153

0.0 MWL Water Level, 5% of the vertical dimension

2.0 OBZ Obstruction Other, 50% of cross sectional area

from 3 o'clock to 9 o'clock / SEVERE DEBRIS

M5

6/5/2023 Dry R VARGAS U-209-211 6/5/2023 12:30:59 PM

No Pre-Cleaning Downstream 2.0 ' 2.0 '

QSR QMR SPR MPR OPR SPRI MPRI OPRI

0000 5100 0.0 5.0 0.0 5.0 5.05.0

QOR

MH-CC153

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_05_2023_D.E.V.ANP // Page: 4

City: DEVA-NP Drainage Area: Upstream MH: MH-CC153

Street: SKYLINE DR Media Label: Up Rim to Invert:

Location Code: Local rural streets with light traffic Flow Control: Downstream MH: MH-CC152.

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 6 " Sewer Category: SEC Joints passed: 0

Pipe material: Vitrified Clay Pipe Purpose: Joints failed: 0

Lining Method: Owner:

Additional Info:

1:50 Distance Code Observation Grade

0.0 AMH Manhole / MH-CC153

0.0 MWL Water Level, 5% of the vertical dimension

2.0 OBZ Obstruction Other, 45% of cross sectional area

from 4 o'clock to 8 o'clock / SEVERE DEBRIS

M5

2.0 LR Line Right, 45% M4

DEBRIS AND ALIGNMENT RIGHT SEVERE

6/5/2023 Dry R VARGAS U-209-211 6/5/2023 12:34:12 PM

Light Cleaning Upstream 2.0 ' 2.0 '

QSR QMR SPR MPR OPR SPRI MPRI OPRI

0000 5141 0.0 9.0 0.0 4.5 4.59.0

QOR

MH-CC152.

OBZ - 2.00

LR - 2.00

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_05_2023_D.E.V.ANP // Page: 5

City: DEVA-NP Drainage Area: Upstream MH: MH-CC151

Street: SKYLINE DR Media Label: Up Rim to Invert:

Location Code: Local rural streets with light traffic Flow Control: Downstream MH: MH-CC150

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 6 " Sewer Category: SEC Joints passed: 0

Pipe material: Vitrified Clay Pipe Purpose: Joints failed: 0

Lining Method: Owner:

Additional Info:

1:50 Distance Code Observation Grade

0.0 AMH Manhole / MH-CC150

0.0 MWL Water Level, 5% of the vertical dimension

2.0 OBZ Obstruction Other, 30% of cross sectional area

from 4 o'clock to 8 o'clock / SEVERE DEBRIS

M4

6/5/2023 Dry R VARGAS U-209-211 6/5/2023 12:56:46 PM

QSR QMR SPR MPR OPR SPRI MPRI OPRI

0000 4100 0.0 4.0 0.0 4.0 4.04.0

QOR

MH-CC151

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_05_2023_D.E.V.ANP // Page: 6

City: DEVA-NP Drainage Area: Upstream MH: MH-CC151

Street: SKYLINE DR Media Label: Up Rim to Invert:

Location Code: Local rural streets with light traffic Flow Control: Downstream MH: MH-CC150.

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 6 " Sewer Category: SEC Joints passed: 0

Pipe material: Vitrified Clay Pipe Purpose: Joints failed: 0

Lining Method: Owner:

Additional Info:

1:50 Distance Code Observation Grade

0.0 AMH Manhole / MH-CC150

0.0 MWL Water Level, 5% of the vertical dimension

2.0 OBZ Obstruction Other, 45% of cross sectional area

from 3 o'clock to 9 o'clock / SEVERE DEBRI

M5

6/5/2023 Dry R VARGAS U-209-211 6/5/2023 1:08:13 PM

QSR QMR SPR MPR OPR SPRI MPRI OPRI

0000 5100 0.0 5.0 0.0 5.0 5.05.0

QOR

MH-CC150.

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_05_2023_D.E.V.ANP // Page: 7

City: DEVA-NP Drainage Area: Upstream MH: MH-CC150

Street: SKYLINE DR Media Label: Up Rim to Invert:

Location Code: Local rural streets with light traffic Flow Control: Downstream MH: MH-CC149

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 6 " Sewer Category: SEC Joints passed: 0

Pipe material: Vitrified Clay Pipe Purpose: Joints failed: 0

Lining Method: Owner:

Additional Info:

1:50 Distance Code Observation Grade

0.0 AMH Manhole / MH-CC150

0.0 MWL Water Level, 10% of the vertical dimension

2.0 OBZ Obstruction Other, 45% of cross sectional area

from 3 o'clock to 9 o'clock / SEVERE DEBRIS

M5

6/5/2023 Dry R VARGAS U-209-211 6/5/2023 1:09:24 PM

QSR QMR SPR MPR OPR SPRI MPRI OPRI

0000 5100 0.0 5.0 0.0 5.0 5.05.0

QOR

MH-CC150

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_05_2023_D.E.V.ANP // Page: 8

City: DEVA-NP Drainage Area: Upstream MH: MH-CC150

Street: SKYLINE DR Media Label: Up Rim to Invert:

Location Code: Local rural streets with light traffic Flow Control: Downstream MH: MH-CC149.

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 6 " Sewer Category: SEC Joints passed: 0

Pipe material: Vitrified Clay Pipe Purpose: Joints failed: 0

Lining Method: Owner:

Additional Info:

1:50 Distance Code Observation Grade

0.0 AMH Manhole / MH-CC149

0.0 MWL Water Level, 10% of the vertical dimension

0.0 MGO Miscellaneous General Observation / POSSIBLE

LINER

2.0 OBZ Obstruction Other, 30% of cross sectional area

from 4 o'clock to 8 o'clock / SEVERE DEBRIS

M4

6/5/2023 Dry R VARGAS U-209-211 6/5/2023 1:23:35 PM

QSR QMR SPR MPR OPR SPRI MPRI OPRI

0000 4100 0.0 4.0 0.0 4.0 4.04.0

QOR

MH-CC149.

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_05_2023_D.E.V.ANP // Page: 9

City: DEVA-NP Drainage Area: Upstream MH: MH-CC149

Street: SKYLINE DR Media Label: Up Rim to Invert:

Location Code: Local rural streets with light traffic Flow Control: Downstream MH: MH-CC148

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 6 " Sewer Category: SEC Joints passed: 0

Pipe material: Vitrified Clay Pipe Purpose: Joints failed: 0

Lining Method: Owner:

Additional Info:

1:50 Distance Code Observation Grade

0.0 AMH Manhole / MH-CC149

0.0 MWL Water Level, 10% of the vertical dimension

0.0 MGO Miscellaneous General Observation / POSSIBLE

2.0 OBZ Obstruction Other, 30% of cross sectional area

from 4 o'clock to 8 o'clock / SEVERE DEBRIS

M4

6/5/2023 Dry R VARGAS U-209-211 6/5/2023 1:33:06 PM

QSR QMR SPR MPR OPR SPRI MPRI OPRI

0000 4100 0.0 4.0 0.0 4.0 4.04.0

QOR

MH-CC149

OBZ - 2.00

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_05_2023_D.E.V.ANP // Page: 10

City: DEVA-NP Drainage Area: Upstream MH: MH-CC149

Street: SKYLINE DR Media Label: Up Rim to Invert:

Location Code: Local rural streets with light traffic Flow Control: Downstream MH: MH-CC148.

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 6 " Sewer Category: SEC Joints passed: 0

Pipe material: Vitrified Clay Pipe Purpose: Joints failed: 0

Lining Method: Owner:

Additional Info:

1:50 Distance Code Observation Grade

0.0 AMH Manhole / MH-CC148

0.0 MWL Water Level, 10% of the vertical dimension

2.0 OBZ Obstruction Other, 50% of cross sectional area

from 3 o'clock to 9 o'clock / SEERE DEBRIS

M5

6/5/2023 Dry R VARGAS U-209-211 6/5/2023 2:08:03 PM

QSR QMR SPR MPR OPR SPRI MPRI OPRI

0000 5100 0.0 5.0 0.0 5.0 5.05.0

QOR

MH-CC148.

OBZ - 2.00

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_05_2023_D.E.V.ANP // Page: 11

City: DEVA-NP Drainage Area: Upstream MH: MH-CC168

Street: COYOTE LOOP Media Label: Up Rim to Invert:

Location Code: Local rural streets with light traffic Flow Control: Downstream MH: MH-CC167

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 6 " Sewer Category: SEC Joints passed: 0

Pipe material: Polyvinyl Chloride Purpose: Joints failed: 0

Lining Method: Owner:

Additional Info:

1:1128 Distance Code Observation Grade

0.0 AMH Manhole / MH-CC167

0.0 MWL Water Level, 5% of the vertical dimension

15.8 TF Tap Factory Made at 10 o'clock, dia/height: 4inch

84.3 TF Tap Factory Made at 10 o'clock, dia/height: 4inch

149.4 AMH Manhole / MH-CC167

6/5/2023 Dry R VARGAS U-209-211 6/5/2023 2:17:44 PM

No Pre-Cleaning Downstream 149.4 ' 149.4 '

QSR QMR SPR MPR OPR SPRI MPRI OPRI

0000 0000 0.0 0.0 0.0 0.0 0.00.0

QOR

MH-CC168

MH-CC167

TF - 15.80

TF - 84.30

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_05_2023_D.E.V.ANP // Page: 12

City: DEVA-NP Drainage Area: Upstream MH: MH-CC169

Street: COYOTE LOOP Media Label: Up Rim to Invert:

Location Code: Local rural streets with light traffic Flow Control: Downstream MH: MH-CC168

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 6 " Sewer Category: SEC Joints passed: 0

Pipe material: Polyvinyl Chloride Purpose: Joints failed: 0

Lining Method: Owner:

Additional Info:

1:908 Distance Code Observation Grade

0.0 AMH Manhole / MH-CC168

0.0 MWL Water Level, 5% of the vertical dimension

120.2 AMH Manhole / MH-CC169

6/5/2023 Dry R VARGAS U-209-211 6/5/2023 2:46:23 PM

No Pre-Cleaning Upstream 120.2 ' 120.2 '

QSR QMR SPR MPR OPR SPRI MPRI OPRI

0000 0000 0.0 0.0 0.0 0.0 0.00.0

QOR

MH-CC168

MH-CC169

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_05_2023_D.E.V.ANP // Page: 13

City: DEVA-NP Drainage Area: Upstream MH: MH-CC167

Street: COYOTE LOOP Media Label: Up Rim to Invert:

Location Code: Local rural streets with light traffic Flow Control: Downstream MH: COYOTE LOOP LIFT STA.

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 6 " Sewer Category: SEC Joints passed: 0

Pipe material: Polyvinyl Chloride Purpose: Joints failed: 0

Lining Method: Owner:

Additional Info:

1:495 Distance Code Observation Grade

0.0 AMH Manhole / MH-CC167

0.0 MWL Water Level, 5% of the vertical dimension

65.5 LD Line Down, 45% M4

65.5 MSA Miscellaneous Survey Abandoned / ALIGNMENT

DOWN SEVERE END OF CCTV

6/5/2023 Dry R VARGAS U-209-211 6/5/2023 3:02:37 PM

No Pre-Cleaning Downstream 65.5 ' 65.5 '

QSR QMR SPR MPR OPR SPRI MPRI OPRI

0000 4100 0.0 4.0 0.0 4.0 4.04.0

QOR

MH-CC167

LD - 65.50

MSA - 65.50

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_05_2023_D.E.V.ANP // Page: 14

City: DEVA-NP Drainage Area: Upstream MH: MH-CC158

Street: SKYLINE DR Media Label: Up Rim to Invert:

Location Code: Easement/Right of way Flow Control: Downstream MH: MH-CC157.

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 6 " Sewer Category: SEC Joints passed: 0

Pipe material: Polyvinyl Chloride Purpose: Joints failed: 0

Lining Method: Owner:

Additional Info:

1:1969 Distance Code Observation Grade

0.0 AMH Manhole / MH-CC158

0.0 MWL Water Level, 5% of the vertical dimension

0.2 MGO Miscellaneous General Observation /

CORRECTION LINER

0.2 MMC Miscellaneous Material Change, Not known /

38.7 S01 LFZ Lining Feature Other from 7 o'clock to 5 o'clock, Start / LINER DAMAGE

64.8 F01 LFZ Lining Feature Other from 7 o'clock to 5 o'clock, Finish / LINER DAMAGE

74.6 RFJ Roots Fine Joint from 5 o'clock to 7 o'clock, within 8 inch

M1

78.1 MMC Miscellaneous Material Change / VCP

78.9 OBZ Obstruction Other, 20% of cross sectional area

from 4 o'clock to 8 o'clock / DEBRS

M3

79.4 MMC Miscellaneous Material Change, Not known /

86.0 S02 LFZ Lining Feature Other from 7 o'clock to 5 o'clock, Start / LINER DAMAGE

156.3 F02 LFZ Lining Feature Other from 7 o'clock to 5 o'clock, Finish / LINER DAMAGE

177.6 S03 LFZ Lining Feature Other from 7 o'clock to 5 o'clock, Start / DAMAGE

256.0 F03 LFZ Lining Feature Other from 7 o'clock to 5 o'clock, Finish / DAMAGE

260.8 AMH Manhole / MH-CC157

6/5/2023 Dry R VARGAS U-209-211 6/5/2023 3:09:38 PM

No Pre-Cleaning Downstream 260.8 ' 260.8 '

MH-CC158

MH-CC157.

LFZ - 38.70

RFJ - 74.60

MMC - 78.10

OBZ - 78.90

LFZ - 86.00

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_05_2023_D.E.V.ANP // Page: 15

6/5/2023 Dry R VARGAS U-209-211 6/5/2023 3:09:38 PM

No Pre-Cleaning Downstream 260.8 ' 260.8 '

QSR QMR SPR MPR OPR SPRI MPRI OPRI

0000 3111 0.0 4.0 0.0 2.0 2.04.0

QOR

LFZ - 177.60

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_05_2023_D.E.V.ANP // Page: 16

City: DEVA-NP Drainage Area: Upstream MH: MH-CC157

Street: SKYLINE DR Media Label: Up Rim to Invert:

Location Code: Easement/Right of way Flow Control: Downstream MH: MH-CC156

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 6 " Sewer Category: SEC Joints passed: 0

Pipe material: Other Purpose: Joints failed: 0

Lining Method: Owner:

Additional Info:

1:887 Distance Code Observation Grade

0.0 AMH Manhole / MH-CC157

0.0 MWL Water Level, 5% of the vertical dimension

117.4 AMH Manhole / MH-CC156

6/5/2023 Dry R VARGAS U-209-211 6/5/2023 3:52:32 PM

No Pre-Cleaning Downstream 117.4 ' 117.4 '

QSR QMR SPR MPR OPR SPRI MPRI OPRI

0000 0000 0.0 0.0 0.0 0.0 0.00.0

QOR

MH-CC157

MH-CC156

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_05_2023_D.E.V.ANP // Page: 17

City: DEVA-NP Drainage Area: Upstream MH: MH-CC145

Street: OLD GHOST RD Media Label: Up Rim to Invert:

Location Code: Local rural streets with light traffic Flow Control: Downstream MH: MH-CC144

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 6 " Sewer Category: SEC Joints passed: 0

Pipe material: Other Purpose: Joints failed: 0

Lining Method: Owner:

Additional Info:

1:2028 Distance Code Observation Grade

0.0 AMH Manhole / MH-CC145

0.0 MWL Water Level, 5% of the vertical dimension

0.0 MGO Miscellaneous General Observation / LINER

102.1 TF Tap Factory Made at 2 o'clock, dia/height: 4inch

268.4 MMC Miscellaneous Material Change, Polyvinyl

chloride / PVC

268.6 JOM Joint Offset Medium S3

268.6 AMH Manhole / MH-CC144 OFFSET JOINT 3 FT

AWAY FROM MH

6/5/2023 Dry R VARGAS U-209-211 6/5/2023 4:20:57 PM

No Pre-Cleaning Downstream 268.6 ' 268.6 '

QSR QMR SPR MPR OPR SPRI MPRI OPRI

3100 0000 3.0 0.0 3.0 0.0 3.03.0

QOR

MH-CC145

MH-CC144

TF - 102.10

MMC - 268.40

JOM - 268.60

AMH - 268.60

AMH - 268.60

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_05_2023_D.E.V.ANP // Page: 18

City: DEVA-NP Drainage Area: Upstream MH: MH-CC144

Street: OLD GHOST RD Media Label: Up Rim to Invert:

Location Code: Local rural streets with light traffic Flow Control: Downstream MH: MH-CC143

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 6 " Sewer Category: SEC Joints passed: 0

Pipe material: Polyvinyl Chloride Purpose: Joints failed: 0

Lining Method: Owner:

Additional Info:

1:990 Distance Code Observation Grade

0.0 AMH Manhole / MH-CC144

0.0 MWL Water Level, 5% of the vertical dimension

4.5 JSM Joint Separated Medium S3

17.5 JSL Joint Separated Large S4

18.8 TF Tap Factory Made at 2 o'clock, dia/height: 4inch

19.6 JOM Joint Offset Medium S3

98.3 TF Tap Factory Made at 10 o'clock, dia/height: 6inch

130.7 JOL Joint Offset Large, 30Inch S4

131.1 MSA Miscellaneous Survey Abandoned / OFFSET

JOINT SEVERE

6/5/2023 Dry R VARGAS U-209-211 6/5/2023 4:38:27 PM

No Pre-Cleaning Downstream 131.1 ' 131.1 '

MH-CC144

JSM - 4.50

JSL - 17.50

TF - 18.80

JOM - 19.60

TF - 98.30

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_05_2023_D.E.V.ANP // Page: 19

6/5/2023 Dry R VARGAS U-209-211 6/5/2023 4:38:27 PM

No Pre-Cleaning Downstream 131.1 ' 131.1 '

QSR QMR SPR MPR OPR SPRI MPRI OPRI

4232 0000 14.0 0.0 3.5 0.0 3.514.0

QOR

JOL - 130.70 MSA - 131.10

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_05_2023_D.E.V.ANP // Page: 20

City: DEVA-NP Drainage Area: Upstream MH: MH-CC144

Street: OLD GHOST RD Media Label: Up Rim to Invert:

Location Code: Local rural streets with light traffic Flow Control: Downstream MH: .MH-CC143.

Location Details: Sheet Number: Down Rim to Invert:

Pipe shape: Circular Sewer Use: Sanitary Sewage Pipe Total gallons used: 0.0

Pipe size: 6 " Sewer Category: SEC Joints passed: 0

Pipe material: Polyvinyl Chloride Purpose: Joints failed: 0

Lining Method: Owner:

Additional Info:

1:732 Distance Code Observation Grade

0.0 AMH Manhole / .MH-CC143.

0.0 MWL Water Level, 5% of the vertical dimension

5.5 JOL Joint Offset Large, 45Inch S4

75.6 TF Tap Factory Made at 12 o'clock, dia/height: 6inch

94.1 JOM Joint Offset Medium S3

95.2 TF Tap Factory Made at 9 o'clock, dia/height: 6inch

96.9 JOL Joint Offset Large, 45Inch S4

96.9 MSA Miscellaneous Survey Abandoned / JOINT

OFFSET LARGE OUNABLE TO CONTINUE

6/5/2023 Dry R VARGAS U-209-211 6/5/2023 4:58:36 PM

No Pre-Cleaning Upstream 96.9 ' 96.9 '

.MH-CC143.

JOL - 5.50

TF - 75.60

JOM - 94.10

TF - 95.20

JOL - 96.90

Tel. (213)761-0031 tomv@pipetec-inc.com

Inspection report Date: Work Order: Pipe Segment Ref.:Weather: Surveyed By: Certificate Number:

Year laid: Pre-cleaning: Pipe Joint Length:Direction: Total Length: Length Surveyed:

06_05_2023_D.E.V.ANP // Page: 21

6/5/2023 Dry R VARGAS U-209-211 6/5/2023 4:58:36 PM

No Pre-Cleaning Upstream 96.9 ' 96.9 '

QSR QMR SPR MPR OPR SPRI MPRI OPRI

4231 0000 11.0 0.0 3.7 0.0 3.711.0

QOR

MSA - 96.90

6 Circular = 1228.90 Total Length (18 Inspections, 1228.90 Length Surveyed)
1228.90 Total Length (18 Inspections, 1228.90 Length Surveyed)