This combined synopsis and solicitation requests proposals for boiler and chiller chemical water treatment services at the National Centers for Animal Health in Ames, Iowa. The contract will have a one-year base period and four one-year options. Services include providing bulk chemicals and implementing a comprehensive water treatment program for chillers, cooling towers, steam boilers, and associated systems. The NAICS code is 325998 and it is set aside for small businesses with less than 500 employees. Proposals are due by December 8, 2022 and must include technical and price sections. Award will be made to the lowest priced technically acceptable offeror considering past performance. The contractor must have at least two years of water treatment and boiler/chiller program implementation experience, and one designated representative must be a chemical engineer.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Company Attention Date : 19-Aug-2022
USDA Troy Dailey, Donal Brown, Kevin Lykins, Ben Rasmussen
Location Nalco copy to
AMES, IA John Ensign Jr, Ethan King
Address
2300 DAYTON AVE
AMES, IA 50010
Summary & Recommendations
ACTION ITEMS:
Install New Gateway Modems. They have been ordered.
Rush chemical 3DT230 shipment.
Clean and calibrate boiler TRASAR unit – Done.
Softeners:
Softeners tested soft
Feedwater:
The boiler feedwater tested zero hardness.
The boiler Trasar controller chemical feed flow cell was cleaned and calibrated. The cell fouling alarm should now subside. Trasar in the feedwater was in range at 9.30 ppm and the controller read 8.52 ppm.
The Trasar ORP probe is calibrated and working properly. ORP was -193 which is in range.
The Trasar pH was calibrated and working properly with feed water pH at 9.45 The boiler feedwater Trasar conductivity probe was pulled, and a 2-point calibration performed. This will bring the controller reading and actual sample result closer together. This probe is for monitoring purposes only but should be accurate.
Condensate
The condensate conductivity was 11.09 umhos which is great.
The condensate showed zero hardness The iron level was 0.17 ppm which is much better since DA was offline.
Condensate pH is low at 7.23. The amine concentration was low also at 3.95. Please monitor for trend and adjust accordingly.
Boilers: B2, and B3 were online at time of testing.
Boiler 2:
The boiler conductivity was at 4524 umhos. The blowdown probe was calibrated and working properly.
The boiler Trasar inhibitor dosage was at 248 ppm and correlated with boiler cycles.
The boiler sulfite concentration was low at 30 ppm All other boiler chemistry is as expected.
Boiler 3:
The boiler conductivity was low at 1938 umhos. The probe calibration was checked and working properly.
The boiler Trasar inhibitor dosage was at 91 ppm and correlated with boiler cycles.
The boiler sulfite concentration was 15 ppm but correlated with boiler cycels
Cooling Towers:
The TRASAR chemical reader is calibrated and working properly. The TRASAR dose is low but to be expected as inventory is low.
The TRASAR conductivity probe and pH probe are calibrated and working properly.
ST70 injector was plugged. Ben unplugged and cleaned the injector and it was working properly.
All other chemistry is as expected.
Chilled Loop:
The TRASAR level was in range at 2560ppm which is in range.
The iron level was high at 0.68 ppm compared which is much improved since adding the bleach last month.
All other chemistry is as expected.
Personal Service Report National Animal Disease Center
Please do not hesitate to call with any questions.
Thank you!
BOILER SYSTEM TEST DATA AND TRASAR GRAPHS
Boiler System Testing Results 8/19/2022 12:00:00 PM
Sample Point
Hardness
(ppm as
CaCO₃ )
M Alkalinity @
STP (ppm as
CaCO₃ )
Conductivity @
STP (µS/cm) pH @ STP
22310
(ppm)
Total Iron
(ppm)
Total
Amine
(ppm as NH₃ )
O
Alkalinity
(ppm as
CaCO₃ )
Sulfite
(ppm)
Cycles based on Cond
(calculated)
Boiler Feedwater 0.00
0.5 Max
32.00
161.00 50 - 400
9.89
8.5 - 9.5
9.30 0.01
Combined
Condensate
0.00 1 Max
12.00 11.00 50 Max
7.23
8.2 - 9.2
0.17
0.3 Max
3.95 20 Max
Boiler 2 400.00 700 Max
4524.00 4000 - 5000
11.65 11 Min
248.00 312.00 50 Min
30.00 30 Min
28.10
Boiler 3 188.00 700 Max
1938.00 4000 - 5000
11.65 11 Min
91.00 160.00 50 Min
15.00 30 Min
12.04
Boiler FW ORP and Temperature Graph - Last 30 Days Boiler Feedwater Trasar Dosage Last 30 Days
Boiler FW Conductivity Graph - Last 30 Days Boiler Feedwater pH Graph Last 30 Days
Boilers 1 Conductivity Graph - Last 30 Days
Boiler 2 Conductivity Graph Last 30 Days
Boiler 3 Conductivity Graph Last 30 Days
Boiler 4 Conductivity Graph Last 30 Days
Boiler 5 Conductivity Graph Last 30 Days
COOLING WATER SYSTEMS TEST DATA AND TRASAR GRAPHS
Cooling Systems and City Water Test Results 8/19/2022 12:00:00 PM
Sample Point Conductivity @
STP (µS/cm) pH @ STP
3DT - Inert
(ppm)
Free
Chlorine
(ppm as
Cl₂ )
M Alkalinity
@ STP
(ppm as
CaCO₃ )
Hardness (ppm as CaCO₃ )
Calcium
(ppm as
CaCO₃ )
Magnesium
Hardness
(calculated)
(ppm as CaCO₃ )
Total Iron
(ppm)
City Water 425.00 8.75 0.80 44.00 120.00
Cooling Tower 1827.00
1700 - 2000 8.90
76.00 95 - 105
0.00
0.5 - 1.3
200.00 480.00 400.00 80.00 0.17
Chilled Loop 900.00 9.95 8 Min
2560.00 1800 - 2200
0.68
John Ensign | District Representative | 641-260-1819 | john.ensign@ecolab.com Nalco Water, An Ecolab Company | 1601 West Diehl Road | Naperville, IL 60563