Amendment 4_USDA Personal Service Report_20220819.pdf

PDF 373 KB Posted

Attached to
Boiler/Chiller Chemical Water Treatment - Ames, IA
Solicitation number
12505B23Q0009
Issued by

About this file

This combined synopsis and solicitation requests proposals for boiler and chiller chemical water treatment services at the National Centers for Animal Health in Ames, Iowa. The contract will have a one-year base period and four one-year options. Services include providing bulk chemicals and implementing a comprehensive water treatment program for chillers, cooling towers, steam boilers, and associated systems. The NAICS code is 325998 and it is set aside for small businesses with less than 500 employees. Proposals are due by December 8, 2022 and must include technical and price sections. Award will be made to the lowest priced technically acceptable offeror considering past performance. The contractor must have at least two years of water treatment and boiler/chiller program implementation experience, and one designated representative must be a chemical engineer.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Company Attention Date : 19-Aug-2022

USDA Troy Dailey, Donal Brown, Kevin Lykins, Ben Rasmussen

Location Nalco copy to

AMES, IA John Ensign Jr, Ethan King

Address

2300 DAYTON AVE

AMES, IA 50010

Summary & Recommendations

ACTION ITEMS:

Install New Gateway Modems. They have been ordered.

Rush chemical 3DT230 shipment.

Clean and calibrate boiler TRASAR unit – Done.

Softeners:

Softeners tested soft

Feedwater:

The boiler feedwater tested zero hardness.

The boiler Trasar controller chemical feed flow cell was cleaned and calibrated. The cell fouling alarm should now subside. Trasar in the feedwater was in range at 9.30 ppm and the controller read 8.52 ppm.

The Trasar ORP probe is calibrated and working properly. ORP was -193 which is in range.

The Trasar pH was calibrated and working properly with feed water pH at 9.45 The boiler feedwater Trasar conductivity probe was pulled, and a 2-point calibration performed. This will bring the controller reading and actual sample result closer together. This probe is for monitoring purposes only but should be accurate.

Condensate

The condensate conductivity was 11.09 umhos which is great.

The condensate showed zero hardness The iron level was 0.17 ppm which is much better since DA was offline.

Condensate pH is low at 7.23. The amine concentration was low also at 3.95. Please monitor for trend and adjust accordingly.

Boilers: B2, and B3 were online at time of testing.

Boiler 2:

The boiler conductivity was at 4524 umhos. The blowdown probe was calibrated and working properly.

The boiler Trasar inhibitor dosage was at 248 ppm and correlated with boiler cycles.

The boiler sulfite concentration was low at 30 ppm All other boiler chemistry is as expected.

Boiler 3:

The boiler conductivity was low at 1938 umhos. The probe calibration was checked and working properly.

The boiler Trasar inhibitor dosage was at 91 ppm and correlated with boiler cycles.

The boiler sulfite concentration was 15 ppm but correlated with boiler cycels

Cooling Towers:

The TRASAR chemical reader is calibrated and working properly. The TRASAR dose is low but to be expected as inventory is low.

The TRASAR conductivity probe and pH probe are calibrated and working properly.

ST70 injector was plugged. Ben unplugged and cleaned the injector and it was working properly.

All other chemistry is as expected.

Chilled Loop:

The TRASAR level was in range at 2560ppm which is in range.

The iron level was high at 0.68 ppm compared which is much improved since adding the bleach last month.

All other chemistry is as expected.

Personal Service Report National Animal Disease Center

Please do not hesitate to call with any questions.

Thank you!

BOILER SYSTEM TEST DATA AND TRASAR GRAPHS

Boiler System Testing Results 8/19/2022 12:00:00 PM

Sample Point

Hardness

(ppm as

CaCO₃ )

M Alkalinity @

STP (ppm as

CaCO₃ )

Conductivity @

STP (µS/cm) pH @ STP

22310

(ppm)

Total Iron

(ppm)

Total

Amine

(ppm as NH₃ )

O

Alkalinity

(ppm as

CaCO₃ )

Sulfite

(ppm)

Cycles based on Cond

(calculated)

Boiler Feedwater 0.00

0.5 Max

32.00

161.00 50 - 400

9.89

8.5 - 9.5

9.30 0.01

Combined

Condensate

0.00 1 Max

12.00 11.00 50 Max

7.23

8.2 - 9.2

0.17

0.3 Max

3.95 20 Max

Boiler 2 400.00 700 Max

4524.00 4000 - 5000

11.65 11 Min

248.00 312.00 50 Min

30.00 30 Min

28.10

Boiler 3 188.00 700 Max

1938.00 4000 - 5000

11.65 11 Min

91.00 160.00 50 Min

15.00 30 Min

12.04

Boiler FW ORP and Temperature Graph - Last 30 Days Boiler Feedwater Trasar Dosage Last 30 Days

Boiler FW Conductivity Graph - Last 30 Days Boiler Feedwater pH Graph Last 30 Days

Boilers 1 Conductivity Graph - Last 30 Days

Boiler 2 Conductivity Graph Last 30 Days

Boiler 3 Conductivity Graph Last 30 Days

Boiler 4 Conductivity Graph Last 30 Days

Boiler 5 Conductivity Graph Last 30 Days

COOLING WATER SYSTEMS TEST DATA AND TRASAR GRAPHS

Cooling Systems and City Water Test Results 8/19/2022 12:00:00 PM

Sample Point Conductivity @

STP (µS/cm) pH @ STP

3DT - Inert

(ppm)

Free

Chlorine

(ppm as

Cl₂ )

M Alkalinity

@ STP

(ppm as

CaCO₃ )

Hardness (ppm as CaCO₃ )

Calcium

(ppm as

CaCO₃ )

Magnesium

Hardness

(calculated)

(ppm as CaCO₃ )

Total Iron

(ppm)

City Water 425.00 8.75 0.80 44.00 120.00

Cooling Tower 1827.00

1700 - 2000 8.90

76.00 95 - 105

0.00

0.5 - 1.3

200.00 480.00 400.00 80.00 0.17

Chilled Loop 900.00 9.95 8 Min

2560.00 1800 - 2200

0.68