Amendment 4_USDA Personal Service Report_20220211.pdf
PDF 629 KB Posted
- Solicitation number
- 12505B23Q0009
About this file
This combined synopsis and solicitation requests proposals for boiler and chiller chemical water treatment services at the National Animal Disease Center in Ames, Iowa. The contractor shall provide bulk chemicals, equipment, labor, and comprehensive water treatment programs for steam boilers, chillers, cooling towers, and associated piping systems. The base year of performance is one year with four optional one-year extensions. Proposals are due by December 8, 2022 and the award will be a fixed-price small business set-aside contract. The contractor must have a minimum of two years' experience in water treatment and boiler programs. Evaluation will be based on technical acceptability and price, with the lowest priced technically acceptable offer receiving the award.
The contractor will provide all items FOB destination at the government site. Services will be inspected by the contracting officer's representative and accepted at destination. This is a 100% total small business set-aside with a NAICS code of 325998 and size standard of 500 employees.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Company Attention Date : 11-Feb-2022
USDA Troy Dailey, Don Brown, Kevin Lykins
Location Nalco copy to
AMES, IA John Ensign Jr, Daniel Smith
Address
2300 DAYTON AVE
AMES, IA 50010
Summary & Recommendations
ACTION ITEMS:
Determine why check valves and strainers on main condensate tank pumps are corroding shut every 5-6 month's.
Determine location for additional conductivity probes to measure steam quality and condensate quality going into main condensate tank.
Softeners:
West Softeners #1 and 2 were online at time of testing. #1 tested hard and #2 tested soft. Discussed with Troy the effects of channeling during low flow scenarios.
We review conductivity probe readings and noted several instances over the last 30 days of high conductivity leaking from softeners into boiler feedwater.
Feedwater:
The boiler feedwater tested low hardness at 0.2 ppm which is allowable.
The boiler Trasar controller chemical feed is calibrated and working properly. Trasar in the feedwater was in range at 10.8 ppm.
The Trasar ORP probe is calibrated and working properly as residual sulfite was in range for all boilers.
The Trasar pH is calibtrated and working properly with pH in the feedwater at 9.36 which is right in range.
The boiler feedwater Trasar conductivity controller is calibrated and working properly. The feedwater conductivity is higher than we like to see at 225 umhos indicating about a 52% condensate return rate at time of testing. We have seen boiler feedwater conductivity below 100 umhos with a condensate return rate above 75% so we do see big fluctuations from time to time. We did review a graph depicting daily operator testing results for boiler feedwater conductivity beginning September 1, 2021 thru current that showed high feedwater conductivity on average as high as 400 -500 umhos with one excursion as high as 800 indicating boiler carryover. These trends are important in our effort to determine why we are seeing such high corrosion rates in the condensate tank pump check valves and strainers. As such, when these high conductivity results occur we need to determine the source of conductivity like a softener leaking high conductivity (salt) into feedwater, or high conductivity getting into the condensate which can come from the softener, boiler carryover or leaks from heat exchangers on campus.
Condensate
The condensate showed showed higher than normal iron today at 0.54 ppm. Will monitor for trend.
The condensate showed zero hardness.
Condensate pH was in range at 9.2 but at the high end. Please ensure it doesn't go any higher and monitor for cause and trend if it does. Try and correlate conductivity as a source of high pH.
The amine was ing range at 11.85 ppm.
The conductivity tested at 74 micromhos which isn't bad but we expect conductivity to be below 50. We did review a graph showing operator test data for coductivity between September 1, 2021 and present that showed conductivity to be well above 100 umhos on average with some results above 300 umhos. These high excursions are significant as a cause to the type of corrosion we are seeing in the check valves and strainers. When conductivity goes above 100 we need to try and establish the source so we can mitigate and prevent.
As we discussed, the type of corrosion we are seeing is caused by oxygen and accelerated by conductivity (salt). The high conductivity we have seen in the condensate could be coming from the softeners, boiler carryover or contamination in the condensate from campus. We did walk down the softener lines with Troy and located two possible sources coming from the softenrs but valves showed to be closed. We did look at the conductivity probe readings on the softener and showed multiple readings around 1000 indicating the softeners are leaking salt into feedwater. This would certainly contribute to carryover in the boiler/s. We discussed putting in additional conductivity probes on the steam header and incoming condensate to help determine sources of contamination.
The following questions were discussed for consideration when testing and analyzing to determine the cause/s of high corrosion rates:
1. When condensate repairs are done, how long to they throw away the condensate? Days? Weeks? ….How would throwing away condensate make the condensate tank go up in conductivity?
2. The softened makeup goes directly into the DA. Is there ever an occassion when we would send softened makeup to the condensate tank besides when the DA tank is under repair?
3. Has there been level control issues with the DA or condensate tank?
Personal Service Report National Animal Disease Center
4. Has the condensate tank overflowed in the last 6 mo?
5. Are the softeners able to satisfy the demand from DA level control swings in when someone is throwing away condensate? Is there a chance that somehow adding softened water to the condensate tank helped level out DA level control issues?
6. Are condensate pump seals leaking in air?
As we continue to review test results we will discuss these questions for possible answers
Boilers: B2, B4 and B5 were online at time of testing.
Boiler 2:
The boiler conductivity is in range at 5413. The Trasar conductivity probe was calibrated to maintain conductivity in range.
The boiler Trasar inhibitor dosage was at 182ppm and correlated with boiler cycles.
The boiler sulfite concentration was as expected at 45 ppm.
All other boiler chemistry is as expected.
Boiler 4:
The boiler conductivity is in range at 3949. A one point calibration on the probe was performed and working correctly.
The boiler Trasar inhibitor dosage was at 175ppm and correlated with boiler cycles.
The boiler sulfite concentration was as expected at 30 ppm.
All other boiler chemistry is as expected.
Boiler 3:
The boiler conductivity is in range at 2842. A one point calibration on the probe was performed and working properly.
The boiler Trasar inhibitor dosage was at 106ppm and correlated with boiler cycles.
The boiler sulfite concentration was as expected at 30 ppm.
All other boiler chemistry is as expected.
Boiler 5:
The boiler conductivity is in range at 4260. A one point calibration on the probe was performed and working properly.
The boiler Trasar inhibitor dosage was at 147ppm and correlated with boiler cycles.
The boiler sulfite concentration was as expected at 35 ppm.
All other boiler chemistry is as expected.
Cooling Towers:
Off line for the season.
Chilled Loop:
Off line for the season.
Please don't hesitat to call with any questions.
Thank You.
BOILER SYSTEM TEST DATA AND TRASAR GRAPHS
Boiler System Testing Results 2/11/2022 2:00:00 PM
Sample Point
Hardness
(ppm as
CaCO₃ )
M Alkalinity @
STP (ppm as
CaCO₃ )
Conductivity @
STP (µS/cm) pH @ STP
22310
(ppm)
Total Iron
(ppm)
Total
Amine
(ppm as NH₃ )
O
Alkalinity
(ppm as
CaCO₃ )
Sulfite
(ppm)
Cycles based on Cond
(calculated)
Boiler Feedwater 0.20
0.5 Max
32.00
225.00 50 - 400
9.36
8.5 - 9.5
10.80 0.03
Combined
Condensate
0.00 1 Max
8.00 74.00 50 Max
9.20
8.2 - 9.2
0.54
0.3 Max
11.85 20 Max
Boiler 2 460.00 700 Max
5413.00 4000 - 5000
11.66 11 Min
182.00 280.00 50 Min
45.00 30 Min
24.06
Boiler 4 330.00 700 Max
2842.00 4000 - 5000
11.90 11 Min
107.00 160.00 50 Min
30.00 30 Min
12.63
Boiler 5 450.00 700 Max
4260.00 4000 - 5000
11.70 11 Min
147.00 264.00 50 Min
35.00 30 Min
18.93
Boiler FW ORP and Temperature Graph - Last 30 Days Boiler Feedwater Trasar Dosage Last 30 Days
Boiler FW Conductivity Graph - Last 30 Days Boiler Feedwater pH Graph Last 30 Days
Boilers 1 Conductivity Graph - Last 30 Days
Boiler 2 Conductivity Graph Last 30 Days
Boiler 3 Conductivity Graph Last 30 Days
Boiler 4 Conductivity Graph Last 30 Days
Boiler 5 Conductivity Graph Last 30 Days