Operation and Maintenance Contract National Center of Agricultural Utilization Research (NCAUR) USDA-ARS, Peoria, IL
July 8, 2021
Operation & Maintenance Contract USDA-ARS-NCAUR, Peoria, IL Solicitation 12505B21R003
Listing of Fire Alarm System Devices
Attached is the annual fire alarm report performed on the fire alarm system at the USDA- NCAUR facility. This report was received in March of 2021.
The Government is furnishing the annual fire alarm report to provide prospective offerors with supplement information on the type and quantity of fire alarm devices in the fire alarm system at the NCAUR facility. Please see attached.
Fire Alarm and Life Safety System Inspection Certificate
For
Alutiiq 1815 N. University Peoria, Illinois 61604
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Annual Inspection Inspection Date Feb 24, 2021
Building: Alutiiq Company: Thompson Electronics Company Contact: Kirk Defrates Contact: Brett Coons
Title: Management Title: Technician
Thompson Electronics Company 1 Download Date: 03/17/2021
Executive Summary Generated by: BuildingReports.com
Building Information Building: Alutiiq Contact: Kirk Defrates
Address: 1815 N. University Phone: 309-681-6502
Address: Fax:
City/State/Zip: Peoria, Illinois 61604 Mobile:
Country: United States of America Email: kirk.defrates@usda.gov
Inspection Performed By Company: Thompson Electronics Company Inspector: Brett Coons
Address: 905 South Bosch Road Phone: 309-265-6055
Address: Fax:
City/State/Zip: Peoria, Illinois 61607 Mobile:
Country: United States of America Email: bmc@thompsonet.com
System Control Unit Manufacturer: SimplexGrinnell Inspection Date: 02/04/2021 IDC Style:
Model Number: 4120 Install Date: 03/06/2017 SLC Style:
Software Version: Version Date: 03/06/2017 NAC Style:
Location: 1st Admin Wing Room 1014A Current Protection: Breaker
Monitoring Company: Phone: Account #:
Central Station Signal Verification Type: Mfg: Model #:
Test Time/Date: Restore Time
Thompson Electronics Company 2 Download Date: 03/17/2021
Inspection Summary
Category Total Items Serviced Passed Failed/Other Qty % Qty % Qty % Qty %
Control 61 5.15% 61 100.00% 61 100.00% 0 0% Auxiliary 1 0.08% 1 100.00% 1 100.00% 0 0% Initiating 1122 94.68% 1121 99.91% 1121 100.00% 0 0% Indicating 1 0.08% 1 100.00% 1 100.00% 0 0%
Totals 1185 100% 1184 99.92% 1184 100.00% 0 0%
Certification Company: Thompson Electronics Company Building: Alutiiq
Inspector: Brett Coons Contact: Kirk Defrates
Signed: Feb 3, 2021 6:31:31 PM Signed:
Thompson Electronics Company 3 Download Date: 03/17/2021
Notes & Recommendations
Building: Alutiiq
Control Panel: 1 - SimplexGrinnell
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
ScanID Note Device Type Location Comment
Initiating 44980814 1 Heat Detector Basement South Admin Elevator Equip Room Passed
Does not shunt elevator power. (2/4/2021) 44980746 2 Smoke Detector North Admin 3rd Behind Room 3016 inaccessible 44981425 3 Heat Detector North Wing Basement Room 0200 Passed
Should be labeled "0201". (2/4/2021)
Thompson Electronics Company 4 Download Date: 03/17/2021
Control Panel: 5 - SimplexGrinnell
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
ScanID Note Device Type Location Comment
Initiating 44981354 4 Heat Detector Attic North Wing Passenger Elev Equip Rm Passed
Did not shunt elevator power. (2/4/2021) 44981239 5 Heat Detector North Wing Basement Room 0226 (Actually
0229) Passed
Should be labeled "0229". (2/4/2021)
Thompson Electronics Company 5 Download Date: 03/17/2021
Control Panel: 9 - SimplexGrinnell 4100U
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
ScanID Note Device Type Location Comment
Initiating 44981496 6 Duct Detector Basement Center Wing W. Mech Rm AHU R.
Passed
Did not shut down AHU. (2/3/21) 44981494 7 Duct Detector Basement Center Wing W. Mech Rm AHU S.
Passed
Did not shut down AHU. (2/3/21) 44981442 8 Heat Detector Basement Center Wing West Stairs Elevator
Mech
Did not shunt elevator power. (2/4/2021)
Thompson Electronics Company 6 Download Date: 03/17/2021
Inspection & Testing
Control Panel: 1 - SimplexGrinnell
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
Auxiliary
Releasing Device Entire Facility Tested 7:58:03 PM 02/04/2021
Control Control Panel 1st Admin Wing Room 1014A Tested 7:28:34 PM 02/04/2021
Indicating Speaker/Strobe Entire Facility Tested 7:57:58 PM 02/04/2021
Initiating Duct Detector Basement NMR Suite 0019C Mech Rm AHU Tested 9:16:02 PM 02/03/2021 Duct Detector Basement North Admin Fan Rm 0010 ASU-A7
Retu Tested 2:23:56 AM 02/03/2021
Duct Detector Basement North Admin Fan Rm 0017 ASU-A6 Ret.
Tested 2:22:59 AM 02/03/2021
Duct Detector Basement North Admin Fan Rm 0017 ASU-A6 Supp
Tested 2:22:52 AM 02/03/2021
Duct Detector Basement North Admin Hall by 0010 ASU-A7 Sup
Tested 2:23:06 AM 02/03/2021
Duct Detector Basement North Admin Room 0026 ASU-A5 Return
Tested 2:18:36 AM 02/03/2021
Duct Detector Basement North Admin Room 0026 ASU-A5 Supply
Tested 2:18:27 AM 02/03/2021
Duct Detector Basement South Admin Room 0056 Tested 12:52:15 AM 02/03/2021 Duct Detector Basement South Admin Room 0038 ASU4 Retn Tested 12:53:43 AM 02/03/2021 Duct Detector Basement South Admin Room 0038 ASU4 Sup1 Tested 12:53:40 AM 02/03/2021 Duct Detector Basement South Admin Room 0038 ASU4 Sup2 Tested 1:32:10 AM 02/03/2021 Duct Detector Basement South Admin Room 0038 ASU4 Sup3 Tested 12:53:39 AM 02/03/2021 Duct Detector Basement South Admin Room 0038 ASU4 Sup4 Tested 12:53:37 AM 02/03/2021 Duct Detector Basement South Admin Room 0043 ASU3 Det2 Tested 12:53:14 AM 02/03/2021 Duct Detector Basement South Admin Room 0047 ASU2 Det1 Tested 12:52:54 AM 02/03/2021 Duct Detector Basement South Admin Room 0047 ASU2 Det2 Tested 12:52:46 AM 02/03/2021 Duct Detector Basement South Admin Room 0047 ASU2 Det3 Tested 12:52:40 AM 02/03/2021 Duct Detector North Admin Basement Rm 0006 ASU-A7
Supply Tested 9:13:35 PM 02/03/2021
Duct Detector North Admin Basement Room 0030 Unit G Tested 2:24:19 AM 02/03/2021 Duct Detector South Admin Basement Room 0038 ASU4 Sup5 Tested 12:53:33 AM 02/03/2021 Heat Detector Basement North Admin Elec Vault #1 0024 Tested 2:19:39 AM 02/03/2021 Heat Detector Basement North Admin Exercise Room 0022 Tested 9:25:22 PM 02/03/2021 Heat Detector Basement North Admin High Volt Vault Behind Tested 2:20:13 AM 02/03/2021
Thompson Electronics Company 7 Download Date: 03/17/2021
Heat Detector Basement North Admin Jan Closet Behind Elev Tested 9:33:06 PM 02/03/2021 Heat Detector Basement North Admin Laundry Rm South 0019 Tested 2:19:44 AM 02/03/2021 Heat Detector Basement North Admin Room 0010 Tested 2:23:19 AM 02/03/2021 Heat Detector Basement North Admin Room 0014 Tested 9:33:15 PM 02/03/2021 Heat Detector Basement North Admin Room 0016 Tested 2:19:51 AM 02/03/2021 Heat Detector Basement North Admin Room 0026 Tested 2:19:08 AM 02/03/2021 Heat Detector Basement South Admin Cooler Area Tested 12:55:54 AM 02/03/2021 Heat Detector Basement South Admin Elevator Equip Room Tested 8:17:54 PM 02/04/2021 Heat Detector Basement South Admin Room 0038 Tested 12:53:48 AM 02/03/2021 Heat Detector Basement South Admin Room 0042 Tested 12:53:22 AM 02/03/2021 Heat Detector Basement South Admin Room 0043 Tested 12:53:16 AM 02/03/2021 Heat Detector Basement South Admin Room 0046 Tested 12:53:04 AM 02/03/2021 Heat Detector Basement South Admin Room 0047 Tested 9:16:58 PM 02/03/2021 Heat Detector Basement South Admin Room 0050 Tested 9:17:07 PM 02/03/2021 Heat Detector Basement South Admin Room 0056 Tested 12:52:10 AM 02/03/2021 Heat Detector Basement South Admin Room 0058 Tested 12:52:06 AM 02/03/2021 Heat Detector Basement South Admin Storage by 0057 Tested 12:51:55 AM 02/03/2021 Heat Detector 1st North Admin Closet by Women's Room Tested 10:21:18 PM 02/02/2021 Heat Detector 1st North Admin Phone Room Tested 10:20:48 PM 02/02/2021 Heat Detector 2nd North Admin Closet by 2001 Tested 10:19:26 PM 02/02/2021 Heat Detector 3rd North Admin Closet by 3001 Tested 3:09:29 AM 02/03/2021 Heat Detector 3rd North Admin Janitor's Closet by 3037 Tested 7:55:08 PM 02/03/2021 Heat Detector 3rd North Admin Odor Room Tested 7:54:49 PM 02/03/2021 Heat Detector 3rd North Admin Room 3013 Tested 7:54:35 PM 02/03/2021 Heat Detector 3rd North Admin Room 3017 Tested 7:53:50 PM 02/03/2021 Heat Detector 3rd North Admin Room 3032 Tested 7:48:55 PM 02/04/2021 Heat Detector Attic North Admin Bay 4002 Tested 8:44:48 PM 02/02/2021 Heat Detector Attic North Admin Bay 4006 Tested 8:44:52 PM 02/02/2021 Heat Detector Attic North Admin Bay 4010 Tested 8:45:01 PM 02/02/2021 Heat Detector Attic North Admin Bay 4017 Tested 8:45:08 PM 02/02/2021 Heat Detector Attic North Admin Bay 4021 Tested 12:19:13 AM 02/04/2021 Heat Detector Attic North Admin Bay 4024 Tested 8:45:13 PM 02/02/2021 Heat Detector Attic North Admin by South Stairs Tested 8:45:18 PM 02/02/2021 Heat Detector Attic North Admin Corridor by 4002 Tested 8:45:31 PM 02/02/2021 Heat Detector Attic North Admin Corridor by 4007 Tested 8:45:34 PM 02/02/2021 Heat Detector Attic North Admin East of AHU-41 Tested 8:45:44 PM 02/02/2021 Heat Detector Attic North Admin Outside Record Storage Tested 8:45:58 PM 02/02/2021 Heat Detector Attic North Admin Record Storage Tested 12:19:21 AM 02/04/2021 Heat Detector Attic North Admin Room 4001 Tested 12:19:31 AM 02/04/2021 Heat Detector Attic North Admin Room 4007 Tested 8:46:05 PM 02/02/2021 Heat Detector Attic North Admin Room 4009 Tested 8:46:09 PM 02/02/2021 Heat Detector Attic North Admin South of AHU 41 Tested 1:15:05 AM 02/04/2021 Heat Detector Attic North Admin South of Penthouse Tested 8:46:18 PM 02/02/2021 Heat Detector Attic South Admin Mechanical by Stairs Tested 10:19:57 AM 02/24/2021 Heat Detector North Admin 1st Closet by 1037 Tested 12:57:32 AM 02/03/2021 Heat Detector North Admin 2nd Closet by 2037 Tested 1:06:42 AM 02/02/2021 Heat Detector North Admin 2nd Room 2009 Tested 10:18:38 PM 02/02/2021 Heat Detector North Admin Basement Fan Room 0017 Tested 2:22:45 AM 02/03/2021 Heat Detector North Admin Basement Laundry Rm North 0019 Tested 12:13:33 AM 02/05/2021
Thompson Electronics Company 8 Download Date: 03/17/2021
Heat Detector North Admin Basement Room 0000 Welding
Shop Tested 9:13:42 PM 02/03/2021
Heat Detector North Admin Basement Room 0006 North Tested 9:13:45 PM 02/03/2021 Heat Detector North Admin Basement Room 0006 South Tested 9:13:47 PM 02/03/2021 Heat Detector North Admin Basement Room 0009 Tested 2:18:15 AM 02/03/2021 Heat Detector North Admin Basement Room 0015 Elec. Shop Tested 2:20:29 AM 02/03/2021 Heat Detector North Admin Basement Room 0030 North Tested 1:28:11 AM 02/03/2021 Heat Detector North Admin Basement Room 0030 West Tested 1:28:18 AM 02/03/2021 Heat Detector North Wing Basement Room 0200 Tested 11:49:46 PM 02/04/2021 Heat Detector South Admin Basement Janitor Closet (Storage
Room by Elev Equip Rm.)
Tested 12:53:58 AM 02/03/2021
Heat Detector South Admin Basement Room 0041 Tested 1:32:32 AM 02/03/2021 Pull Station Basement NMR Suite 0019C Mechanical Room Tested 2:21:56 AM 02/03/2021 Pull Station Basement NMR Suite 0019F Magnet Room Tested 2:22:01 AM 02/03/2021 Pull Station Basement NMR Suite 0019G Vestibule Tested 2:21:47 AM 02/03/2021 Pull Station Basement North Admin by 0026 Tested 2:18:50 AM 02/03/2021 Pull Station Basement North Admin by North Stairs Tested 2:20:55 AM 02/03/2021 Pull Station Basement North Admin East Exit Tested 2:20:04 AM 02/03/2021 Pull Station Basement South Admin Hall by 0058 Tested 12:55:14 AM 02/03/2021 Pull Station Basement South Admin Hall by East Exit Tested 12:55:08 AM 02/03/2021 Pull Station Basement South Admin Hall by North Exit Tested 12:54:40 AM 02/03/2021 Pull Station 1st North Admin by North Stairs Tested 10:21:29 PM 02/02/2021 Pull Station 1st North Admin Hall by 1000 Tested 10:21:03 PM 02/02/2021 Pull Station 1st North Admin Hall by Elevators Tested 11:12:09 PM 02/02/2021 Pull Station 1st North Admin Main Lobby Tested 11:25:15 PM 02/01/2021 Pull Station 2nd North Admin Hall by 2000 Tested 10:19:24 PM 02/02/2021 Pull Station 2nd North Admin Hall by Elevator Tested 1:29:47 AM 02/03/2021 Pull Station 2nd North Admin Hall by North Stairs Tested 1:29:18 AM 02/03/2021 Pull Station 3rd North Admin by Auditorium 3046 Tested 7:55:19 PM 02/03/2021 Pull Station 3rd North Admin by North Stairs Tested 1:30:11 AM 02/03/2021 Pull Station 3rd North Admin by Room 3000 Tested 3:09:28 AM 02/03/2021 Pull Station 3rd North Admin Elevator Lobby Tested 10:48:51 PM 02/04/2021 Pull Station Attic North Admin North Stairs Exit Tested 8:45:50 PM 02/02/2021 Pull Station Attic North Admin South Stairs Exit Tested 8:46:26 PM 02/02/2021 Pull Station Attic South Admin Bay 4313 Tested 1:15:59 AM 02/04/2021 Pull Station Attic South Admin by East Doors Tested 8:53:27 PM 02/02/2021 Pull Station Attic South Admin by North Doors Tested 8:51:57 PM 02/02/2021 Pull Station Attic South Admin by Stairs Tested 8:52:03 PM 02/02/2021 Pull Station Attic South Admin by West Stairs Tested 8:53:42 PM 02/02/2021 Pull Station South Admin Basement Hall by Stairs Tested 12:54:09 AM 02/03/2021 Smoke Detector Basement North Admin Corr by Utilities Office Tested 1:36:03 AM 02/03/2021 Smoke Detector Basement North Admin Corridor by 0009 Tested 10:50:00 PM 02/04/2021 Smoke Detector Basement North Admin Corridor by 0015 Tested 1:33:19 AM 02/03/2021 Smoke Detector Basement North Admin Corridor by 0030 Tested 1:27:46 AM 02/03/2021 Smoke Detector Basement North Admin Corridor by Men's Rm Tested 1:27:52 AM 02/03/2021 Smoke Detector Basement North Admin Corridor by Room 0019 Tested 10:49:37 PM 02/04/2021 Smoke Detector Basement North Admin Elevator Lobby Tested 7:51:32 PM 02/04/2021 Smoke Detector Basement North Admin Hallway by 0000 Tested 7:55:35 PM 02/03/2021 Smoke Detector Basement North Admin North Stairwell Tested 2:18:03 AM 02/03/2021 Smoke Detector Basement North Admin South Stairwell Tested 2:19:01 AM 02/03/2021
Thompson Electronics Company 9 Download Date: 03/17/2021
Smoke Detector Basement South Admin Elevator Lobby Tested 8:01:58 PM 02/04/2021 Smoke Detector Basement South Admin Hall by 0041 Tested 9:16:16 PM 02/03/2021 Smoke Detector Basement South Admin Hall by 0042 Tested 12:55:39 AM 02/03/2021 Smoke Detector Basement South Admin Hall by 0046 Tested 12:55:27 AM 02/03/2021 Smoke Detector Basement South Admin Hall by 0047 Tested 9:16:22 PM 02/03/2021 Smoke Detector Basement South Admin Hall by 0050 Tested 9:16:28 PM 02/03/2021 Smoke Detector Basement South Admin Hall by 0054 Tested 9:16:34 PM 02/03/2021 Smoke Detector Basement South Admin Hall by 0057 Tested 9:16:43 PM 02/03/2021 Smoke Detector Basement South Admin Hall by East Exit Tested 12:54:54 AM 02/03/2021 Smoke Detector Basement South Admin Hall by South Exit Tested 12:54:22 AM 02/03/2021 Smoke Detector Basement South Admin Hall by Stairs Tested 12:54:16 AM 02/03/2021 Smoke Detector Basement South Admin Room 0054 North Tested 12:52:21 AM 02/03/2021 Smoke Detector Basement South Admin Room 0054 South Tested 12:52:18 AM 02/03/2021 Smoke Detector Basement South Admin Stairwell Tested 9:17:15 PM 02/03/2021 Smoke Detector 1st North Admin Center Display Area Tested 12:57:39 AM 02/03/2021 Smoke Detector 1st North Admin Hall behind 1006 Tested 10:21:14 PM 02/02/2021 Smoke Detector 1st North Admin Hall by 1002 Tested 7:46:11 PM 02/04/2021 Smoke Detector 1st North Admin Hall by 1009 Tested 10:20:56 PM 02/02/2021 Smoke Detector 1st North Admin Hall by 1013 Tested 10:20:50 PM 02/02/2021 Smoke Detector 1st North Admin Hall by 1023 Tested 12:57:25 AM 02/03/2021 Smoke Detector 1st North Admin Hall by 1025 Tested 12:57:21 AM 02/03/2021 Smoke Detector 1st North Admin Hall by 1032 Tested 12:57:15 AM 02/03/2021 Smoke Detector 1st North Admin Hall by 1037 Tested 12:57:12 AM 02/03/2021 Smoke Detector 1st North Admin Hall by North Display Area Tested 12:57:06 AM 02/03/2021 Smoke Detector 1st North Admin Hall by South Display Area Tested 12:57:04 AM 02/03/2021 Smoke Detector 1st North Admin Hall by South Fire Doors Tested 12:56:58 AM 02/03/2021 Smoke Detector 1st North Admin Lobby Waiting Area Tested 11:25:30 PM 02/01/2021 Smoke Detector 1st North Admin Main Entrance Tested 11:25:27 PM 02/01/2021 Smoke Detector 1st North Admin Main Lobby Tested 11:25:23 PM 02/01/2021 Smoke Detector 1st North Admin North Display Area Tested 12:56:49 AM 02/03/2021 Smoke Detector 1st North Admin North Stairs Tested 10:20:11 PM 02/02/2021 Smoke Detector 1st North Admin Room 1009 Tested 10:20:36 PM 02/02/2021 Smoke Detector 1st North Admin Room 1010 Tested 10:20:19 PM 02/02/2021 Smoke Detector 1st North Admin Room 1013 Tested 10:20:18 PM 02/02/2021 Smoke Detector 1st North Admin Security Office Tested 11:07:49 PM 02/02/2021 Smoke Detector 1st North Admin South Display Area Tested 12:56:47 AM 02/03/2021 Smoke Detector 1st North Admin South Stairs Tested 12:56:44 AM 02/03/2021 Smoke Detector 2nd North Admin Hall by 2000 Tested 10:19:23 PM 02/02/2021 Smoke Detector 2nd North Admin Hall by 2006 Tested 10:19:19 PM 02/02/2021 Smoke Detector 2nd North Admin Hall by 2017 Tested 1:29:27 AM 02/03/2021 Smoke Detector 2nd North Admin Hall by 2021 Tested 1:29:34 AM 02/03/2021 Smoke Detector 2nd North Admin Hall by 2032 Tested 1:06:50 AM 02/02/2021 Smoke Detector 2nd North Admin Hall by 2036 Tested 1:06:49 AM 02/02/2021 Smoke Detector 2nd North Admin Hall by 2037 Tested 1:06:35 AM 02/02/2021 Smoke Detector 2nd North Admin Hall by N. Stairs Tested 1:29:54 AM 02/03/2021 Smoke Detector 2nd North Admin Hall by Stairs Tested 1:30:00 AM 02/03/2021 Smoke Detector 2nd North Admin North Stairs Tested 1:28:59 AM 02/03/2021 Smoke Detector 2nd North Admin Room 2036 Tested 1:06:46 AM 02/02/2021 Smoke Detector 2nd North Admin South Stairs Tested 1:07:25 AM 02/02/2021 Smoke Detector 3rd North Admin Elevator Lobby Tested 7:58:21 PM 02/04/2021
Thompson Electronics Company 10 Download Date: 03/17/2021
Smoke Detector 3rd North Admin Hall by 3000 Tested 1:30:23 AM 02/03/2021 Smoke Detector 3rd North Admin Hall by 3004 Tested 1:30:28 AM 02/03/2021 Smoke Detector 3rd North Admin Hall by 3012 Tested 1:30:34 AM 02/03/2021 Smoke Detector 3rd North Admin Hall by 3021 Tested 1:30:52 AM 02/03/2021 Smoke Detector 3rd North Admin Hall by 3032 Tested 7:55:17 PM 02/03/2021 Smoke Detector 3rd North Admin Hall by 3034 Tested 7:55:14 PM 02/03/2021 Smoke Detector 3rd North Admin Hall by 3037 Tested 7:55:12 PM 02/03/2021 Smoke Detector 3rd North Admin Hall by Auditorium 3046 Tested 7:55:22 PM 02/03/2021 Smoke Detector 3rd North Admin Hall by Room 3025 Tested 7:45:44 PM 02/04/2021 Smoke Detector 3rd North Admin Hall by Room 3017 Tested 1:30:45 AM 02/03/2021 Smoke Detector 3rd North Admin Room 3013 Tested 1:30:57 AM 02/03/2021 Smoke Detector 3rd North Admin Room 3015 South Tested 7:53:53 PM 02/03/2021 Smoke Detector 3rd North Admin Room 3017 Tested 7:53:44 PM 02/03/2021 Smoke Detector 3rd North Admin Room 3019 Tested 7:53:41 PM 02/03/2021 Smoke Detector 3rd North Admin Room 3034 Tested 7:53:33 PM 02/03/2021 Smoke Detector 3rd North Admin South Stairs Tested 8:44:33 PM 02/02/2021 Smoke Detector Attic North Admin Elevator Penthouse Tested 10:29:36 AM 02/24/2021 Smoke Detector Attic North Admin North Stairs Tested 1:15:22 AM 02/04/2021 Smoke Detector Attic North Admin South Stairs Landing Tested 1:15:13 AM 02/04/2021 Smoke Detector Attic South Admin Bay 4042 Tested 8:51:39 PM 02/02/2021 Smoke Detector Attic South Admin Bay 4044 Tested 12:19:00 AM 02/04/2021 Smoke Detector Attic South Admin Bay 4048 Tested 8:51:44 PM 02/02/2021 Smoke Detector Attic South Admin Bay 4050 Tested 8:51:46 PM 02/02/2021 Smoke Detector Attic South Admin Bay 4052 Tested 8:51:48 PM 02/02/2021 Smoke Detector Attic South Admin Bay 4301 Tested 8:53:29 PM 02/02/2021 Smoke Detector Attic South Admin Bay 4303 Tested 8:52:22 PM 02/02/2021 Smoke Detector Attic South Admin Bay 4305 Tested 8:52:24 PM 02/02/2021 Smoke Detector Attic South Admin Bay 4307 Tested 8:52:27 PM 02/02/2021 Smoke Detector Attic South Admin Bay 4309 Tested 8:52:29 PM 02/02/2021 Smoke Detector Attic South Admin Bay 4311 Tested 8:52:30 PM 02/02/2021 Smoke Detector Attic South Admin Bay 4313 Tested 8:52:35 PM 02/02/2021 Smoke Detector Attic South Admin Bay 4315 Tested 8:52:40 PM 02/02/2021 Smoke Detector Attic South Admin Bay 4317 Tested 1:15:49 AM 02/04/2021 Smoke Detector Attic South Admin Bay 4319 Tested 8:52:44 PM 02/02/2021 Smoke Detector Attic South Admin Bay 4321 Tested 1:15:53 AM 02/04/2021 Smoke Detector Attic South Admin Bay 4323 Tested 8:53:12 PM 02/02/2021 Smoke Detector Attic South Admin Bay 4325 Tested 8:53:09 PM 02/02/2021 Smoke Detector Attic South Admin Bay 4327 Tested 8:53:05 PM 02/02/2021 Smoke Detector Attic South Admin by Fire Doors Tested 8:51:53 PM 02/02/2021 Smoke Detector Attic South Admin Elevator Lobby Tested 8:10:47 PM 02/04/2021 Smoke Detector Attic South Admin Elevator Shaft Tested 10:20:51 AM 02/24/2021 Smoke Detector Attic South Admin Stairwell Tested 8:52:06 PM 02/02/2021 Smoke Detector Attic South Admin West Stairs Tested 1:15:56 AM 02/04/2021 Smoke Detector North Admin 1st Hall by Elevators Tested 7:55:00 PM 02/04/2021 Smoke Detector North Admin 1st Room 1022 Tested 12:56:32 AM 02/03/2021 Smoke Detector North Admin 2nd Hall by Elevator Tested 7:56:41 PM 02/04/2021 Smoke Detector North Admin 3rd North Stairs Tested 1:29:07 AM 02/03/2021 Smoke Detector North Admin 3rd Room 3015 North Tested 7:53:56 PM 02/03/2021 Smoke Detector North Admin 3rd Room 3022/3020 Tested 7:53:38 PM 02/03/2021 Smoke Detector North Admin 3rd Room 3025 Tested 7:45:52 PM 02/04/2021
Thompson Electronics Company 11 Download Date: 03/17/2021
Smoke Detector North Admin Basement Corridor by 0024 Tested 2:19:28 AM 02/03/2021 Smoke Detector North Admin Basement Corridor by South Stairs Tested 2:19:17 AM 02/03/2021 Smoke Detector North Admin Basement Elect. Storage 0015 Tested 2:20:44 AM 02/03/2021 Smoke Detector North Admin Basement Room 0030 North Tested 1:28:03 AM 02/03/2021 Smoke Detector North Admin Basement Room 0030 West Tested 1:28:13 AM 02/03/2021 Smoke Detector South Admin Attic Bay 4046 Tested 8:51:42 PM 02/02/2021 Smoke Detector South Admin Attic Storage 4041 Tested 8:52:12 PM 02/02/2021 Smoke Detector South Admin Basement Room 0041 Tested 12:21:45 AM 02/05/2021
Untested Initiating
Smoke Detector North Admin 3rd Behind Room 3016
Thompson Electronics Company 12 Download Date: 03/17/2021
Control Panel: 2 - SimplexGrinnell
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which
Control
Annunciator Center Wing Basement Room 0201A Tested 12:34:36 AM 02/02/2021 Battery Basement Center Wing Room 0108 FACP Tested 12:35:08 AM 02/02/2021 Battery Basement Center Wing Room 0108 FACP Tested 12:35:33 AM 02/02/2021 Battery Center Wing 1st Room 1121 Janitor BPS Tested 12:17:18 AM 02/02/2021 Battery Center Wing 1st Room 1121 Janitor BPS Tested 12:17:42 AM 02/02/2021 Battery Center Wing 2nd Room 2121 Janitor BPS Tested 11:23:23 PM 02/03/2021 Battery Center Wing 2nd Room 2121 Janitor BPS Tested 11:23:24 PM 02/03/2021 Battery Center Wing 3rd Room 3121 Janitor BPS Tested 11:51:41 PM 02/01/2021 Battery Center Wing 3rd Room 3121 Janitor BPS Tested 11:52:15 PM 02/01/2021 Control Panel Basement Center Wing Room 0108 Tested 12:34:27 AM 02/02/2021 Power Supply Center Wing 1st Room 1121 Janitor Tested 12:16:11 AM 02/02/2021 Power Supply Center Wing 2nd Room 2121 Janitor Tested 11:22:37 PM 02/03/2021 Power Supply Center Wing 3rd Room 3121 Janitor Tested 11:50:18 PM 02/01/2021
Initiating Heat Detector Garage North Tested 7:15:11 PM 02/04/2021 Heat Detector Garage South Tested 7:15:10 PM 02/04/2021 Heat Detector Center Wing Basement Room 0037 Tested 1:27:19 AM 02/03/2021 Pull Station Garage North Tested 10:48:27 PM 02/04/2021 Pull Station Garage South Tested 7:15:12 PM 02/04/2021 Pull Station Garage West Tested 7:15:10 PM 02/04/2021 Smoke Detector Center Wing Basement Room 0037 Tested 1:27:11 AM 02/03/2021
Thompson Electronics Company 13 Download Date: 03/17/2021
Control Panel: 3 - SimplexGrinnell TruSite Workstatio
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which
Control
Control Panel 1st Admin Security Office Tested 7:59:45 PM 02/03/2021
Thompson Electronics Company 14 Download Date: 03/17/2021
Control Panel: 4 - SimplexGrinnel by o 4020
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which
Control
Annunciator South Wing Basement West Exit Tested 12:03:37 AM 02/03/2021 Battery Basement South Wing Room 0301 FACP Tested 2:25:53 AM 02/04/2021 Battery Basement South Wing Room 0301 FACP Tested 2:25:55 AM 02/04/2021 Battery Basement South Wing Room 0301 Left BPS Tested 2:26:21 AM 02/04/2021 Battery Basement South Wing Room 0301 Left BPS Tested 2:26:22 AM 02/04/2021 Battery Basement South Wing Room 0301 Right BPS Tested 8:26:25 PM 02/03/2021 Battery Basement South Wing Room 0301 Right BPS Tested 8:26:30 PM 02/03/2021 Battery South Wing Basement Greenhouse BPS Tested 8:31:45 PM 02/03/2021 Battery South Wing Basement Greenhouse BPS Tested 8:31:46 PM 02/03/2021 Control Panel South Wing Basement Room 0301 Tested 2:26:49 AM 02/04/2021 Power Supply South Wing Basement Room 0301 Left Tested 8:24:26 PM 02/03/2021 Power Supply South Wing Basement Room 0301 Right Tested 8:24:38 PM 02/03/2021 Power Supply South Wing Basement Greenhouse Tested 8:30:48 PM 02/03/2021
Initiating Duct Detector Basement South Wing Rm 0316 ASU 8 DET1 Tested 12:42:29 AM 02/03/2021 Duct Detector Basement South Wing Room 0300 East Tested 12:43:37 AM 02/03/2021 Duct Detector Basement South Wing Room 0305 Det1 Tested 12:43:29 AM 02/03/2021 Duct Detector Basement South Wing Room 0313 ASU-10 Tested 12:43:10 AM 02/03/2021 Duct Detector Basement South Wing Room 0313 ASU-7 Det 1 Tested 12:43:08 AM 02/03/2021 Duct Detector Basement South Wing Room 0323 ASU 9 Det 1 Tested 12:40:55 AM 02/03/2021 Duct Detector 2nd South Wing North Unit 2328 Tested 9:55:56 PM 02/01/2021 Duct Detector 2nd South Wing South Unit 2328 Tested 9:55:59 PM 02/01/2021 Heat Detector Basement South Wing Behind Room 0326 Tested 12:50:26 AM 02/03/2021 Heat Detector Basement South Wing Generator Room Tested 11:51:33 PM 02/04/2021 Heat Detector Basement South Wing Hall Behind Cold Rm
Center Tested 12:39:56 AM 02/03/2021
Heat Detector Basement South Wing Hall Behind Cold Rm East Tested 12:39:54 AM 02/03/2021 Heat Detector Basement South Wing Hall Behind Cold Rm West Tested 12:39:49 AM 02/03/2021 Heat Detector Basement South Wing Janitor Closet/0300 Tested 12:43:43 AM 02/03/2021 Heat Detector Basement South Wing Room 0300 Tested 12:43:41 AM 02/03/2021 Heat Detector Basement South Wing Room 0301 East Tested 12:23:08 AM 02/05/2021 Heat Detector Basement South Wing Room 0301 West Tested 11:50:40 PM 02/04/2021 Heat Detector Basement South Wing Room 0305 Tested 12:43:32 AM 02/03/2021 Heat Detector Basement South Wing Room 0311 East Tested 12:43:25 AM 02/03/2021 Heat Detector Basement South Wing Room 0314 Tested 12:42:49 AM 02/03/2021 Heat Detector Basement South Wing Room 0318 Tested 12:41:54 AM 02/03/2021 Heat Detector Basement South Wing Room 0320 Tested 12:41:28 AM 02/03/2021 Heat Detector Basement South Wing Room 0322 Tested 12:41:04 AM 02/03/2021 Heat Detector Basement South Wing Room 0324 Tested 12:40:38 AM 02/03/2021 Heat Detector Basement South Wing Room 0326 Tested 12:40:35 AM 02/03/2021 Heat Detector Basement South Wing Room 0328 Tested 12:40:13 AM 02/03/2021 Heat Detector Basement South Wing Behind West Stairs Tested 11:50:26 PM 02/04/2021
Thompson Electronics Company 15 Download Date: 03/17/2021
Heat Detector Basement South Wing Elect Vault Behind 0327 Tested 12:40:23 AM 02/03/2021 Heat Detector Basement South Wing Room 0313 by ASU 10 Tested 9:19:28 PM 02/03/2021 Heat Detector Basement South Wing Room 0315 Tested 12:42:36 AM 02/03/2021 Heat Detector Basement South Wing Room 0317 Tested 12:42:21 AM 02/03/2021 Heat Detector Basement South Wing Room 0319 Tested 12:41:35 AM 02/03/2021 Heat Detector Basement South Wing Room 0321 Tested 12:41:20 AM 02/03/2021 Heat Detector Basement South Wing Room 0323 Tested 12:40:54 AM 02/03/2021 Heat Detector Basement South Wing Room 0327 Tested 12:43:56 AM 02/03/2021 Heat Detector 1st South Admin Closet 1051 Tested 10:14:16 PM 02/01/2021 Heat Detector 1st South Wing Janitors Closet Tested 11:26:02 PM 02/01/2021 Heat Detector 1st South Wing Micro Rm 1322 Tested 7:47:21 PM 02/04/2021 Heat Detector 1st South Wing Rm 1300 Visually / electrically test
7:42:41 PM 02/01/2021
Heat Detector 1st South Wing Rm 1301 Visually / electrically test
7:40:36 PM 02/01/2021
Heat Detector 1st South Wing Rm 1302 Visually / electrically test
7:43:08 PM 02/01/2021
Heat Detector 1st South Wing Rm 1303 Visually / electrically test
7:41:06 PM 02/01/2021
Heat Detector 1st South Wing Rm 1304 Visually / electrically test
7:48:28 PM 02/01/2021
Heat Detector 1st South Wing Rm 1305 Tested 9:49:22 PM 02/01/2021 Heat Detector 1st South Wing Rm 1306 Tested 10:12:52 PM 02/01/2021 Heat Detector 1st South Wing Rm 1307 Visually / electrically test
9:43:24 PM 02/01/2021
Heat Detector 1st South Wing Rm 1308 Tested 9:49:31 PM 02/01/2021 Heat Detector 1st South Wing Rm 1309 Tested 9:49:48 PM 02/01/2021 Heat Detector 1st South Wing Rm 1310 Tested 9:50:28 PM 02/01/2021 Heat Detector 1st South Wing Rm 1311 Tested 9:50:13 PM 02/01/2021 Heat Detector 1st South Wing Rm 1312 Tested 9:51:14 PM 02/01/2021 Heat Detector 1st South Wing Rm 1313 Tested 9:51:04 PM 02/01/2021 Heat Detector 1st South Wing Rm 1314 Tested 9:51:19 PM 02/01/2021 Heat Detector 1st South Wing Rm 1316 Tested 9:51:38 PM 02/01/2021 Heat Detector 1st South Wing Rm 1317 Tested 9:51:52 PM 02/01/2021 Heat Detector 1st South Wing Rm 1318 Tested 7:46:56 PM 02/04/2021 Heat Detector 1st South Wing Rm 1319 Tested 9:52:18 PM 02/01/2021 Heat Detector 1st South Wing Rm 1321 Tested 9:53:03 PM 02/01/2021 Heat Detector 1st South Wing Rm 1322 Tested 9:53:24 PM 02/01/2021 Heat Detector 1st South Wing Rm 1323 Tested 7:47:29 PM 02/04/2021 Heat Detector 1st South Wing Rm 1324 Tested 9:53:43 PM 02/01/2021 Heat Detector 1st South Wing Rm 1326 East Tested 9:54:08 PM 02/01/2021 Heat Detector 1st South Wing Rm 1326 West Tested 7:47:48 PM 02/04/2021 Heat Detector 1st South Wing Rm 1327 Tested 9:54:00 PM 02/01/2021 Heat Detector 1st South Wing Rm 1328 Tested 9:54:03 PM 02/01/2021 Heat Detector 1st South Wing Room 1315 Tested 9:51:29 PM 02/01/2021 Heat Detector 2nd South Admin Room 2051 Tested 11:06:55 PM 02/04/2021 Heat Detector 2nd South Wing Janitor Closet/2300 Tested 11:07:12 PM 02/04/2021 Heat Detector 2nd South Wing Rm 2300 Tested 10:09:32 PM 02/01/2021 Heat Detector 2nd South Wing Rm 2301 Tested 11:07:49 PM 02/04/2021 Heat Detector 2nd South Wing Rm 2302 Tested 11:08:11 PM 02/04/2021
Thompson Electronics Company 16 Download Date: 03/17/2021
Heat Detector 2nd South Wing Rm 2303 Tested 10:09:19 PM 02/01/2021 Heat Detector 2nd South Wing Rm 2304 Tested 10:09:09 PM 02/01/2021 Heat Detector 2nd South Wing Rm 2305 Tested 10:09:03 PM 02/01/2021 Heat Detector 2nd South Wing Rm 2306 Tested 10:08:50 PM 02/01/2021 Heat Detector 2nd South Wing Rm 2307 Tested 10:08:42 PM 02/01/2021 Heat Detector 2nd South Wing Rm 2308 Tested 10:08:34 PM 02/01/2021 Heat Detector 2nd South Wing Rm 2309 Tested 10:07:49 PM 02/01/2021 Heat Detector 2nd South Wing Rm 2310 Tested 10:06:09 PM 02/01/2021 Heat Detector 2nd South Wing Rm 2311 Tested 10:05:53 PM 02/01/2021 Heat Detector 2nd South Wing Rm 2312 Tested 11:09:07 PM 02/04/2021 Heat Detector 2nd South Wing Rm 2313 Tested 10:05:20 PM 02/01/2021 Heat Detector 2nd South Wing Rm 2314 Tested 10:01:31 PM 02/01/2021 Heat Detector 2nd South Wing Rm 2315 Tested 10:01:19 PM 02/01/2021 Heat Detector 2nd South Wing Rm 2316 Tested 10:01:03 PM 02/01/2021 Heat Detector 2nd South Wing Rm 2317 Tested 10:00:34 PM 02/01/2021 Heat Detector 2nd South Wing Rm 2318 Tested 10:00:21 PM 02/01/2021 Heat Detector 2nd South Wing Rm 2319 Tested 10:00:09 PM 02/01/2021 Heat Detector 2nd South Wing Rm 2320 Tested 11:09:30 PM 02/04/2021 Heat Detector 2nd South Wing Rm 2321 Tested 9:59:44 PM 02/01/2021 Heat Detector 2nd South Wing Rm 2322 Tested 9:58:21 PM 02/01/2021 Heat Detector 2nd South Wing Rm 2323 Tested 9:58:12 PM 02/01/2021 Heat Detector 2nd South Wing Rm 2324 Tested 9:56:26 PM 02/01/2021 Heat Detector 2nd South Wing Rm 2326 East Tested 9:56:02 PM 02/01/2021 Heat Detector 2nd South Wing Rm 2327 Tested 9:55:43 PM 02/01/2021 Heat Detector 2nd South Wing Rm 2328 Tested 9:55:52 PM 02/01/2021 Heat Detector 2nd South Wing Room 2326 West Tested 9:56:12 PM 02/01/2021 Heat Detector 3rd South Admin Safety Closet Tested 11:32:56 PM 02/01/2021 Heat Detector 3rd South Admin Storage Rm by Projection Tested 11:32:35 PM 02/01/2021 Heat Detector 3rd South Wing Rm 3301 Tested 11:32:59 PM 02/01/2021 Heat Detector 3rd South Wing Rm 3303 Tested 11:32:50 PM 02/01/2021 Heat Detector 3rd South Wing Rm 3305 Tested 11:32:39 PM 02/01/2021 Heat Detector 3rd South Wing Rm 3307 Tested 11:32:23 PM 02/01/2021 Heat Detector 3rd South Wing Rm 3309 Tested 11:31:46 PM 02/01/2021 Heat Detector 3rd South Wing Rm 3321 Tested 11:30:15 PM 02/01/2021 Heat Detector 3rd South Wing Rm 3323 Tested 11:29:49 PM 02/01/2021 Heat Detector 3rd South Wing Rm 3327 Tested 11:29:45 PM 02/01/2021 Heat Detector 3rd South Wing Room 3311 Tested 11:31:32 PM 02/01/2021 Heat Detector 3rd South Wing Room 3313 Tested 11:31:20 PM 02/01/2021 Heat Detector 3rd South Wing Room 3314 Tested 11:27:40 PM 02/01/2021 Heat Detector 3rd South Wing Room 3315 Tested 11:30:56 PM 02/01/2021 Heat Detector 3rd South Wing Room 3316 Tested 11:28:04 PM 02/01/2021 Heat Detector 3rd South Wing Room 3317 Tested 11:30:47 PM 02/01/2021 Heat Detector 3rd South Wing Room 3318 Tested 11:28:24 PM 02/01/2021 Heat Detector 3rd South Wing Room 3319 Tested 11:30:28 PM 02/01/2021 Heat Detector 3rd South Wing Room 3320 Tested 11:28:33 PM 02/01/2021 Heat Detector 3rd South Wing Room 3322 Tested 11:28:51 PM 02/01/2021 Heat Detector 3rd South Wing Room 3324 East Tested 11:29:19 PM 02/01/2021 Heat Detector 3rd South Wing Room 3324 West Tested 11:29:27 PM 02/01/2021 Heat Detector 3rd South Wing Room 3326 Tested 11:29:36 PM 02/01/2021 Heat Detector 3rd South Wing Room 3327 Storage Tested 7:48:39 PM 02/04/2021
Thompson Electronics Company 17 Download Date: 03/17/2021
Heat Detector 3rd South Wing Room 3328 Tested 11:29:40 PM 02/01/2021 Heat Detector Commodities Bldg Attic East Tested 10:49:04 AM 02/24/2021 Heat Detector Commodities Building 1st Center Tested 7:17:23 PM 02/04/2021 Heat Detector Commodities Building 1st East Tested 7:17:24 PM 02/04/2021 Heat Detector Commodities Building 1st West Tested 7:17:20 PM 02/04/2021 Heat Detector Commodities Building Attic Center Tested 7:17:27 PM 02/04/2021 Heat Detector Commodities Building Attic West Tested 7:17:31 PM 02/04/2021 Heat Detector Gallery South Wing East Center Tested 12:39:28 AM 02/03/2021 Heat Detector Gallery South Wing West Tested 12:39:12 AM 02/03/2021 Heat Detector Gallery South Wing West Center Tested 12:39:06 AM 02/03/2021 Heat Detector Greenhouse Room North Entrance Tested 9:11:52 PM 02/03/2021 Heat Detector Greenhouse Hall by 103 Tested 9:11:30 PM 02/03/2021 Heat Detector Greenhouse Hall by 106 Tested 9:11:33 PM 02/03/2021 Heat Detector Greenhouse Room 100A Tested 9:35:22 PM 02/03/2021 Heat Detector Greenhouse Room 100B Tested 9:11:36 PM 02/03/2021 Heat Detector Greenhouse Room 102 Tested 9:36:30 PM 02/03/2021 Heat Detector Greenhouse Room 103 Tested 9:11:39 PM 02/03/2021 Heat Detector Greenhouse Room 104 Tested 9:11:41 PM 02/03/2021 Heat Detector Greenhouse Room 105 Tested 10:50:03 PM 02/03/2021 Heat Detector Greenhouse Room 106 Tested 9:37:50 PM 02/03/2021 Heat Detector Greenhouse Room 107 Tested 9:11:46 PM 02/03/2021 Heat Detector South Wing 1st Rm 1320 Tested 9:52:41 PM 02/01/2021 Heat Detector South Wing 3rd Janitor Closet/3300 Tested 11:26:36 PM 02/01/2021 Heat Detector South Wing 3rd Room 3300 Tested 11:26:48 PM 02/01/2021 Heat Detector South Wing 3rd Room 3302 Tested 11:26:51 PM 02/01/2021 Heat Detector South Wing 3rd Room 3304 Tested 11:27:02 PM 02/01/2021 Heat Detector South Wing 3rd Room 3306 Tested 11:27:12 PM 02/01/2021 Heat Detector South Wing 3rd Room 3308 Tested 11:27:20 PM 02/01/2021 Heat Detector South Wing 3rd Room 3310 Tested 7:48:31 PM 02/04/2021 Heat Detector South Wing 3rd Room 3312 Tested 11:27:27 PM 02/01/2021 Heat Detector South Wing Basement Room 0313 by ASU-7 Tested 9:19:31 PM 02/03/2021 Heat Detector South Wing Basement Service Bldg Center Tested 7:18:51 PM 02/04/2021 Heat Detector South Wing Basement Service Bldg East Center Tested 7:18:49 PM 02/04/2021 Heat Detector South Wing Basement Service Bldg North Center Tested 7:18:57 PM 02/04/2021 Heat Detector South Wing Basement Service Bldg North East Tested 7:18:54 PM 02/04/2021 Heat Detector South Wing Basement Service Bldg North West Tested 9:09:44 PM 02/04/2021 Heat Detector South Wing Basement Service Bldg South Center Tested 7:18:47 PM 02/04/2021 Heat Detector South Wing Basement Service Bldg South East Tested 7:19:00 PM 02/04/2021 Heat Detector South Wing Basement Service Bldg West Center Tested 9:09:49 PM 02/04/2021 Heat Detector South Wing Basement Room 0311 West Tested 9:42:32 PM 02/03/2021 Heat Detector South Wing Basement Service Building South
West Tested 9:09:35 PM 02/04/2021
Pull Station Basement South Wing by East Exit Tested 12:50:03 AM 02/03/2021 Pull Station Basement South Wing by 0317 Tested 12:50:14 AM 02/03/2021 Pull Station Basement South Wing by West Stairs Tested 12:49:42 AM 02/03/2021 Pull Station Basement South Wing Hall by NW Exit Tested 12:45:47 AM 02/03/2021 Pull Station Basement South Wing Hall by Service Bldg Tested 12:45:42 AM 02/03/2021 Pull Station 1st South Admin by Stairs Tested 10:14:30 PM 02/01/2021 Pull Station 1st South Admin Hall by 1049 Tested 10:13:29 PM 02/01/2021 Pull Station 1st South Admin Hall by North Door Tested 10:13:12 PM 02/01/2021
Thompson Electronics Company 18 Download Date: 03/17/2021
Pull Station 1st South Admin Library by Office Tested 10:14:01 PM 02/01/2021 Pull Station 1st South Wing by East Doors Tested 11:25:52 PM 02/01/2021 Pull Station 1st South Wing Hall by 1311 Tested 7:46:43 PM 02/04/2021 Pull Station 1st South Wing Hall by West Stairs Tested 9:53:27 PM 02/01/2021 Pull Station 2nd South Admin Hall by North Door Tested 10:12:34 PM 02/01/2021 Pull Station 2nd South Admin Rm by Stairs Tested 10:12:14 PM 02/01/2021 Pull Station 2nd South Wing by West Stairs Tested 9:56:21 PM 02/01/2021 Pull Station 2nd South Wing Hall by 2311 Tested 10:05:45 PM 02/01/2021 Pull Station 2nd South Wing Hall by East Doors Tested 10:11:55 PM 02/01/2021 Pull Station 3rd South Admin Hall by Stairs Tested 11:26:21 PM 02/01/2021 Pull Station 3rd South Admin North End Tested 11:33:18 PM 02/01/2021 Pull Station 3rd South Wing by West Stairs Tested 11:29:07 PM 02/01/2021 Pull Station 3rd South Wing Hall by 3311 Tested 11:27:43 PM 02/01/2021 Pull Station Commodities Building Center Exit Tested 7:17:14 PM 02/04/2021 Pull Station Gallery South Wing East Exit Tested 12:39:21 AM 02/03/2021 Pull Station Gallery South Wing West Exit Tested 12:39:04 AM 02/03/2021 Pull Station Greenhouse by South Exit Tested 9:11:26 PM 02/03/2021 Pull Station Greenhouse Room North Entrance Tested 9:11:50 PM 02/03/2021 Pull Station South Admin 1st Library South Door Tested 10:13:34 PM 02/01/2021 Pull Station South Wing 3rd Hall by 3300 Tested 11:26:31 PM 02/01/2021 Pull Station South Wing Basement Service Bldg East Exit Tested 12:37:31 AM 02/03/2021 Pull Station South Wing Basement Service Bldg West Exit Tested 12:37:26 AM 02/03/2021 Smoke Detector Basement South Wing Behind Room 0326 Tested 12:50:25 AM 02/03/2021 Smoke Detector Basement South Wing Hall by 0300 Tested 9:19:02 PM 02/03/2021 Smoke Detector Basement South Wing Hall by 0301 Tested 12:49:33 AM 02/03/2021 Smoke Detector Basement South Wing Hall by 0302 Tested 12:49:28 AM 02/03/2021 Smoke Detector Basement South Wing Hall by 0305 Tested 12:49:24 AM 02/03/2021 Smoke Detector Basement South Wing Hall by 0308 Tested 12:49:21 AM 02/03/2021 Smoke Detector Basement South Wing Hall by 0310 Tested 12:49:18 AM 02/03/2021 Smoke Detector Basement South Wing Rm 0328 Tested 12:40:11 AM 02/03/2021 Smoke Detector Basement South Wing Room 0311 East Tested 12:43:27 AM 02/03/2021 Smoke Detector Basement South Wing Room 0318 Tested 12:41:44 AM 02/03/2021 Smoke Detector Basement South Wing Room 0320 Tested 9:19:38 PM 02/03/2021 Smoke Detector Basement South Wing Room 0322 Tested 12:41:08 AM 02/03/2021 Smoke Detector Basement South Wing Room 0324 Tested 12:40:39 AM 02/03/2021 Smoke Detector Basement South Wing Room 0326 Tested 12:40:32 AM 02/03/2021 Smoke Detector Basement South Wing Hall by 0312 Tested 12:49:10 AM 02/03/2021 Smoke Detector Basement South Wing Hall by 0315 Tested 12:49:08 AM 02/03/2021 Smoke Detector Basement South Wing Hall by 0318 Tested 12:49:05 AM 02/03/2021 Smoke Detector Basement South Wing Hall by 0321 Tested 12:48:14 AM 02/03/2021 Smoke Detector Basement South Wing Hall by 0322 Tested 12:48:05 AM 02/03/2021 Smoke Detector Basement South Wing Hall by 0325 Tested 12:47:44 AM 02/03/2021 Smoke Detector Basement South Wing Hall by 0326 Tested 9:19:21 PM 02/03/2021 Smoke Detector Basement South Wing Hall by 0329 Tested 12:45:58 AM 02/03/2021 Smoke Detector Basement South Wing Hall by 0328 Tested 12:46:03 AM 02/03/2021 Smoke Detector Basement South Wing Hall by NW Exit Tested 12:45:41 AM 02/03/2021 Smoke Detector Basement South Wing Room 0317 Tested 12:42:22 AM 02/03/2021 Smoke Detector Basement South Wing Room 0319 Tested 12:41:36 AM 02/03/2021 Smoke Detector Basement South Wing Room 0321 Tested 12:41:23 AM 02/03/2021 Smoke Detector Basement South Wing West of Stairs Tested 11:50:19 PM 02/04/2021
Thompson Electronics Company 19 Download Date: 03/17/2021
Smoke Detector Basement South Wing West Stairs Tested 12:40:06 AM 02/03/2021 Smoke Detector 1st South Admin by stairs Tested 10:14:21 PM 02/01/2021 Smoke Detector 1st South Admin Elevator Lobby Tested 8:54:13 PM 02/04/2021 Smoke Detector 1st South Admin Hall by 1046 Tested 10:13:24 PM 02/01/2021 Smoke Detector 1st South Admin Hall by 1046E Tested 10:13:20 PM 02/01/2021 Smoke Detector 1st South Admin Hall by 1049 Tested 10:13:28 PM 02/01/2021 Smoke Detector 1st South Admin Hall by 1050 Tested 10:14:14 PM 02/01/2021 Smoke Detector 1st South Admin Hall by North Door Tested 10:13:08 PM 02/01/2021 Smoke Detector 1st South Admin Library Bio. Abs. Tested 7:42:49 PM 02/03/2021 Smoke Detector 1st South Admin Library by 1046B Tested 10:13:42 PM 02/01/2021 Smoke Detector 1st South Admin Library by 1046E Tested 10:13:38 PM 02/01/2021 Smoke Detector 1st South Admin Library by Office Tested 10:13:57 PM 02/01/2021 Smoke Detector 1st South Admin Library Chem. Abs. Tested 7:42:43 PM 02/03/2021 Smoke Detector 1st South Admin Library Journals Tested 7:42:38 PM 02/03/2021 Smoke Detector 1st South Admin Library Lobby Tested 7:42:32 PM 02/03/2021 Smoke Detector 1st South Admin Library South Tested 10:14:07 PM 02/01/2021 Smoke Detector 1st South Admin Library Southeast Tested 10:13:47 PM 02/01/2021 Smoke Detector 1st South Admin Library Southwest Tested 10:13:51 PM 02/01/2021 Smoke Detector 1st South Admin Room 1057A Tested 10:14:36 PM 02/01/2021 Smoke Detector 1st South Admin Stairwell Tested 10:14:26 PM 02/01/2021 Smoke Detector 1st South Admin 1026 Library Shelves N. Tested 7:43:44 PM 02/03/2021 Smoke Detector 1st South Admin 1030 Library Shelves S. Tested 7:43:28 PM 02/03/2021 Smoke Detector 1st South Wing Hall by 1301 Tested 9:47:27 PM 02/01/2021 Smoke Detector 1st South Wing Hall by 1305 Tested 9:47:36 PM 02/01/2021 Smoke Detector 1st South Wing Hall by 1309 Tested 9:49:59 PM 02/01/2021 Smoke Detector 1st South Wing Hall by 1310 Tested 9:50:22 PM 02/01/2021 Smoke Detector 1st South Wing Hall by 1315 Tested 9:51:11 PM 02/01/2021 Smoke Detector 1st South Wing Hall by 1319 Tested 9:51:59 PM 02/01/2021 Smoke Detector 1st South Wing Hall by 1321 Tested 9:53:09 PM 02/01/2021 Smoke Detector 1st South Wing Hall by 1324 Tested 9:53:30 PM 02/01/2021 Smoke Detector 1st South Wing Hall by 1328 Tested 9:53:52 PM 02/01/2021 Smoke Detector 1st South Wing Hall by East Doors Tested 7:47:56 PM 02/04/2021 Smoke Detector 1st South Wing Rm 1300 Tested 10:14:38 PM 02/01/2021 Smoke Detector 1st South Wing Rm 1301 Tested 9:47:19 PM 02/01/2021 Smoke Detector 1st South Wing Rm 1302 Tested 9:47:24 PM 02/01/2021 Smoke Detector 1st South Wing Rm 1303 Tested 9:47:16 PM 02/01/2021 Smoke Detector 1st South Wing Rm 1304 Tested 9:47:29 PM 02/01/2021 Smoke Detector 1st South Wing Rm 1305 Tested 7:46:29 PM 02/04/2021 Smoke Detector 1st South Wing Rm 1306 Tested 9:48:46 PM 02/01/2021 Smoke Detector 1st South Wing Rm 1307 Tested 9:49:18 PM 02/01/2021 Smoke Detector 1st South Wing Rm 1308 Tested 9:49:28 PM 02/01/2021 Smoke Detector 1st South Wing Rm 1309 Tested 9:49:42 PM 02/01/2021 Smoke Detector 1st South Wing Rm 1311 Tested 9:50:05 PM 02/01/2021 Smoke Detector 1st South Wing Rm 1312 Tested 9:50:53 PM 02/01/2021 Smoke Detector 1st South Wing Rm 1313 Tested 9:51:02 PM 02/01/2021 Smoke Detector 1st South Wing Rm 1314 Tested 11:19:56 PM 02/01/2021 Smoke Detector 1st South Wing Rm 1316 Tested 9:51:35 PM 02/01/2021 Smoke Detector 1st South Wing Rm 1317 Tested 9:51:48 PM 02/01/2021 Smoke Detector 1st South Wing Rm 1318 Tested 7:46:57 PM 02/04/2021 Smoke Detector 1st South Wing Rm 1319 Tested 9:52:05 PM 02/01/2021
Thompson Electronics Company 20 Download Date: 03/17/2021
Smoke Detector 1st South Wing Rm 1320 Tested 9:52:32 PM 02/01/2021 Smoke Detector 1st South Wing Rm 1321 Tested 9:53:00 PM 02/01/2021 Smoke Detector 1st South Wing Rm 1322 Tested 9:53:18 PM 02/01/2021 Smoke Detector 1st South Wing Rm 1323 Tested 7:47:14 PM 02/04/2021 Smoke Detector 1st South Wing Rm 1324 Tested 9:53:34 PM 02/01/2021 Smoke Detector 1st South Wing Rm 1326 East Tested 9:54:06 PM 02/01/2021 Smoke Detector 1st South Wing Rm 1326 West Tested 7:47:42 PM 02/04/2021 Smoke Detector 1st South Wing Rm 1327 Tested 9:53:55 PM 02/01/2021 Smoke Detector 1st South Wing Room 1315 Tested 9:51:26 PM 02/01/2021 Smoke Detector 1st South Wing West Stairs Tested 9:54:11 PM 02/01/2021 Smoke Detector 2nd South Admin Elevator Lobby Tested 8:03:40 PM 02/04/2021 Smoke Detector 2nd South Admin Hall by 2041 Tested 10:12:28 PM 02/01/2021 Smoke Detector 2nd South Admin Hall by 2045 Tested 10:12:25 PM 02/01/2021 Smoke Detector 2nd South Admin Hall by 2049 Tested 10:12:23 PM 02/01/2021 Smoke Detector 2nd South Admin Hall by 2054 Tested 10:12:01 PM 02/01/2021 Smoke Detector 2nd South Admin Room 2057A Tested 10:12:19 PM 02/01/2021 Smoke Detector 2nd South Admin Stairwell Landing Tested 12:12:59 AM 02/05/2021 Smoke Detector 2nd South Wing Hall by 2301 Tested 10:09:24 PM 02/01/2021 Smoke Detector 2nd South Wing Hall by 2305 Tested 10:08:53 PM 02/01/2021 Smoke Detector 2nd South Wing Hall by 2309 Tested 10:07:16 PM 02/01/2021 Smoke Detector 2nd South Wing Hall by 2315 Tested 10:01:43 PM 02/01/2021 Smoke Detector 2nd South Wing Hall by 2319 Tested 10:00:28 PM 02/01/2021 Smoke Detector 2nd South Wing Hall by 2323 Tested 9:58:25 PM 02/01/2021 Smoke Detector 2nd South Wing Hall by 2328 Tested 9:55:49 PM 02/01/2021 Smoke Detector 2nd South Wing Hall by East Doors Tested 10:11:51 PM 02/01/2021 Smoke Detector 2nd South Wing Hall by West Stairs Tested 9:56:17 PM 02/01/2021 Smoke Detector 2nd South Wing Rm 2300 Tested 10:09:28 PM 02/01/2021 Smoke Detector 2nd South Wing Rm 2301 Tested 11:07:59 PM 02/04/2021 Smoke Detector 2nd South Wing Rm 2302 Tested 11:08:55 PM 02/04/2021 Smoke Detector 2nd South Wing Rm 2303 Tested 10:09:16 PM 02/01/2021 Smoke Detector 2nd South Wing Rm 2304 Tested 10:09:07 PM 02/01/2021 Smoke Detector 2nd South Wing Rm 2305 Tested 10:08:59 PM 02/01/2021 Smoke Detector 2nd South Wing Rm 2306 Tested 10:08:47 PM 02/01/2021 Smoke Detector 2nd South Wing Rm 2307 Tested 10:08:39 PM 02/01/2021 Smoke Detector 2nd South Wing Rm 2308 Tested 10:08:03 PM 02/01/2021 Smoke Detector 2nd South Wing Rm 2309 Tested 10:07:20 PM 02/01/2021 Smoke Detector 2nd South Wing Rm 2310 Tested 10:06:04 PM 02/01/2021 Smoke Detector 2nd South Wing Rm 2311 Tested 10:05:58 PM 02/01/2021 Smoke Detector 2nd South Wing Rm 2312 Tested 11:22:02 PM 02/01/2021 Smoke Detector 2nd South Wing Rm 2313 Tested 10:05:06 PM 02/01/2021 Smoke Detector 2nd South Wing Rm 2314 Tested 10:01:25 PM 02/01/2021 Smoke Detector 2nd South Wing Rm 2315 Tested 10:01:14 PM 02/01/2021 Smoke Detector 2nd South Wing Rm 2316 Tested 10:00:52 PM 02/01/2021 Smoke Detector 2nd South Wing Rm 2317 Tested 10:00:39 PM 02/01/2021 Smoke Detector 2nd South Wing Rm 2318 Tested 10:00:17 PM 02/01/2021 Smoke Detector 2nd South Wing Rm 2319 Tested 10:00:01 PM…