10 L 2 SOW 2023 10 11.pdf
PDF 633 KB Posted
- Attached to
- National Elevator Modernization & Construction IDIQ for Task Orders over $1 Million Federal contract opportunity
- Solicitation number
- 47PM1124R0011
About this file
This document is a presolicitation notice and draft request for proposal for an indefinite delivery/indefinite quantity contract for elevator construction and modernization task orders valued over $1 million. The General Services Administration intends to award the IDIQ contract for a base year and four option periods with a maximum value of $650 million. Small businesses are eligible under NAICS code 238290 with a size standard of $22 million. GSA aims to award up to six contracts. The notice includes draft RFP documents and attachments for two initial task orders. GSA requests that vendors review the materials and provide any questions, comments or recommendations by April 11, 2024 regarding the draft RFP and attachments. Vendors should address all responses to the listed contracting staff and identify the solicitation section being referenced.
View the file
Other files for this federal contract opportunity
Show all 50
National Elevator Modernization & Construction IDIQ for Task Orders over $1 Million has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Title: Elevator Modernization (Passenger 1-12, Freight 13 & 14) Building: The Lafayette Building Building ID #: DC0026ZZ Building Location: 811 Vermont Ave, NWWashington, DC 20571
Project Control Number: VDC00234 GSA Work Items: #1275
RWA #: N/A
Kahua Number: #18995 SOW Authors: John Czarapata
1. GENERAL:
1.1 This section of the specification includes the furnishing of all material and performance of all work required for the removal of existing elevator equipment and installation of new equipment to provide 12 passenger elevators and 2 freight elevators (See Fig 1).
In general, this project requires the full modernization of the elevators in accordance with the Lafayette Federal Building Elevator Study, prepared by DLR Group, Lerch Bates, and Forella Group, dated February 16, 2018, also known as the “Study”, and any additional modernization requirements listed elsewhere in this document, to meet current code, and sound engineering practices.
To be considered successful, the project must achieve the following objectives:
● Complete project on-time
● Complete the project with no security violations or safety incidence
● Complete project within the overall project budget
● Complete the project with no safety incidents
● Complete the project with no security violations or infractions
● Comply with all tenant requirements for executing the project
● Establish and maintain positive relations with the tenant(s)
● Manage the completion of the project with the spirit of partnering
● Provide timely reports and communications
● Follow all security requirements in the delivery of this project
● Ensure elevator control system and other elevator components are of the
NON-Proprietary type as to NOT being maintained and supported by one specific vendor / elevator contractor.
● Paint existing to remain freight elevators #13 & #14 doorframes on all floor levels.
● Replace freight elevators #13 & #14 cabs, platforms and car frames, inner cab doors, and outer doors at each floor level.
Fig 1 - Plan of the Lafayette Building Elevators
1.2 No more than three (3) elevators shall be taken out of service during the normal working hours of the building to perform this work. Any noisy or disruptive work shall be performed after the normal working hours of the facility. Include all after hours work within the proposal.
1.3 Equipment to be reused or replaced: See Study. All other components of the elevator system shall be installed new, whether specifically mentioned in the specifications, to provide 12 passenger and 2 freight complete elevator units.
1.4 All parts of the elevator equipment shall be of such design, size, and material as to satisfactorily function under all conditions of loading and operation with specified rated load and rated speed range. All parts shall be built to standard dimensions, tolerances, and clearances so that similar parts of similar machines and devices are completely interchangeable. The mechanical fastenings used throughout the equipment on parts subject to wear and requiring replacement shall be key and seat, nut, screw, or other removable and replaceable type not requiring physical deformation or field positioning. The use of rivets or similar devices shall not be accepted as mechanical fastenings for such parts.
1.5 The major elevator components shall be the products of one manufacturer of established reputation, except they may be the products, either wholly or in part, of another manufacturer of established reputation provided such items are engineered and produced under coordinated specifications. Also, the major components to be furnished shall be of a make or makes that have performed satisfactorily together under conditions of normal use in not less than two other elevator installations of equal or greater capacity and speed for a period of at least one year. Prior to award, the names and addresses of the buildings and the names of the owners or managers thereof, in which the proposed combination of major components has so performed, shall be furnished.
A. The term "major elevator components" as mentioned above shall mean such items as an elevator hoisting machine, motor drive, controller, selector, and group supervisory control equipment.
1.6 Equipment in the elevator machine room shall be so arranged that such items as rotating elements and sheaves can be removed for repairs or replacement, either by trolley hoist and dolly, or other conventional means, without dismantling or removing other equipment components in the machine room.
1.7 Adequate workspace for maintenance and repair operations shall be provided around the elevator equipment in the machine room with clear passage to any access or trap doors.
1.8 Where practical, elevator controllers shall be located near, and in the same positions relative to the driving machines they control. The driving machine shall be visible from its controller.
1.9 Trolley beams shall not be utilized as the normal support of elevator equipment such as sheaves for selector cable.
1.10 Elevator data requirements listed below shall be obtained from either the project drawings or within this specification:
A. Elevator Data:
1. Elevator rated load lifting capacity in pounds.
2. Elevator car rated speed in feet per minute.
3. Car travel in feet.
4. Number of landings.
5. Number of openings.
6. Platform size.
7. Class of service, i.e., passenger or freight.
8. Type of machine, i.e., geared or gearless.
9. Type of control, i.e., rheostatic, generator field, or static (3vf Drive).
10. Type of operation, i.e., two stop single car selective collective, two car selective collective or group automatic.
11. Type of design of passenger car.
12. Type of hoistway doors.
13. Type of hoistway door operation.
14. Type of car door or gate.
15. Type of car door or gate operation.
16. Type of signal system.
17. Characteristics of power supply.
18. Finishes.
1.11 The elevator system shall consist of:
A. Twelve (12) gearless traction electric passenger elevators (cars #1-#12) operating in two banks of six elevators and two (2) simplex gearless traction service elevators (cars #13 & #14).
B. Elevator Machine Room: There is one (1) elevator machine room (EMR) in the building serving all 14 elevators. The EMR is accessible by entering Stairwell #1 to the 13th floor, then through corridor 1307, then up a single story Stairwell #6 to the EMR.
There are three (3) split-system, direct expansion air conditioning units located in the EMR for temperature control. All A/C units and associated ductwork, controls, fire alarm interconnect in the EMR shall be replaced under this contract since they have reached their useful life span of 20 years. This requirement supersedes the “Study” recommendation to keep the A/C units.
C. Add Option #1: Provide twelve (12) card readers in the passenger elevators cars 1 through 12, so that floors 7 through 12 call buttons are activated/light-up upon an approved HSPD-12 badge being read. The EXIM tenant on floors 7 through 12 have requested this upgrade. Contractor shall submit a separate line item with their bid to include Option #1 – Card Readers in Cars 1-12. Selecting of an FIPS 201 approved access control reader compatible with our existing access control system and suitable for elevator environments. The card reader shall be located inside the elevator cabin that's easily accessible to users yet doesn't interfere with the elevator's normal operation. Once the location is determined, mount the reader securely to the elevator panel or integrated into the elevator panel, ensuring all cables are safely routed to prevent any tripping hazards or interference with moving parts. Depending on the elevator's design, you may need to collaborate with an access control system integrator to ensure safe installation and integration with the elevator's control system. Proper signage and instructions should also be provided for users to understand and utilize the system effectively.
2. RELATEDWORK:
2.1 The following related work is included in this section and other sections of the specification and shall be the responsibility of the Elevator Contractor:
A. Elevator hoistways and their enclosures and venting, pit spaces, enclosed machine rooms, trolley beams.
B. Temporary guards at all hoistway openings as required under "Accident Prevention" clause of the General Conditions.
C. Bevel all ledges and platforms between the hoistways at each landing to not less than 75 degrees.
D. Provide Elevator machine room energy efficient lighting and 110 GFCI outlets, energy efficient pit lighting and 110 GFCI outlets, and energy efficient hoistway lighting circuits. Pit lighting switch shall be accessible from access door.
E. Provide pans under roof drains. (as needed)
F Remove sprinklers and heat detectors from the hoistways and machine rooms.
Remove all sprinkler piping from the machine room.
G. Provide all car top guardrails as required.
H. Provide HVAC for machine rooms as needed.
I. Open hoistway vent exhaust openings to maximum size. (if needed)
J. Provide fire rated, self closing and self locking machine room, secondary and pit doors. (If needed)
K. Seal openings in machine room floor, walls hoistways, etc. to maintain fire ratings.
3. STANDARD REFERENCES:
3.1 Unless as modified herein or otherwise distinctly specified, all elevator material, design, clearances, definitions, construction, workmanship and tests shall conform to the requirements of the American National Standard Safety Code for Elevators, and, Escalators, (ANSI A17.1-2022) or latest edition, including errata, interpretations and revisions and hereinafter referred to as the A17.1 Code.
3.2 Wherever Federal Specifications, Codes, Standard Details and other standards are referenced, latest editions and amendments shall apply in accordance with the clause entitled "Standard References: in the General Conditions.
3.3 References to the NEC are to the 2020 National Electrical Code (ANSI C1) or latest edition. All electrical work specified in the A17.1 Code shall be done in accordance with the 2020 NEC.
3.4 References to UL standards are to standards of Underwriters Laboratories, Inc.
3.5 References to NEMA are to Standards of the National Electrical Manufacturers Association.
3.6 Referring to the requirements of clause entitled "Building Codes, Fees and Charges" in the General Conditions the work shall also comply with the applicable State and local Code requirements or regulations except the requirements of the A17.1 Code shall govern in the event of a conflict.
3.7 References to Handicap Provisions are to "Uniform Federal Accessibility Standard" (UFAS) and the "Americans with Disabilities Act Accessibility Guidelines" (ADAAG). In case of conflicts in the requirements, the most stringent requirements shall be required.
4. QUALIFICATIONS:
4.1 The prime contractor must perform a minimum of 80% of the total elevator work. Subcontractors may include fire alarm, electrical, etc.
4.2 The names, addresses, experience, and a statement of the work to be performed by each subcontractor to be used for performance of minor portions of the installation of elevators, shall also be submitted promptly upon request by the Government.
4.3 The bid may be rejected if the bidder has established on former jobs, either Government, municipal, or commercial, a record for unsatisfactory elevator installations, has repeatedly failed to complete contracts awarded to him within the contact time, or otherwise fails to meet the experience requirements of this clause.
5. SHOP DRAWINGS:
5.1 Shop drawings shall be submitted in accordance with the "General Conditions" and "Special Conditions" sections.
5.2 Shop drawings shall include the following details as applicable to the systems specified:
A. Full dimension layout in plan and elevation showing the arrangement of equipment and all pertinent details of each elevator unit specified including:
1. Driving machine, controller, selector, motor generator, static motor drive unit, governor and other components located in the machine room.
2. Car, counterweight, sheaves, supporting beams, guide rails, buffers, car and counterweight guide shoes, and other components located in the hoistway.
3. Rail bracket spacing and maximum vertical forces on guide rails in accordance with the A17.1 Code.
4. Reactions at points of support.
5. Weights of principal parts.
6. Top and bottom clearance and over travel of car and counterweight.
7. Location of circuit breaker, switchboard panel or disconnect switch, light switch and feeder termination at controller.
8. Location of outlets for connection of traveling cables for car light and telephone.
9. Location of hoistway access switches.
B. Hoistway entrances and doors showing their method of operation, details of construction; and method of fastening to the structural members of the building.
C. Car designs specified, showing details of construction, fastenings to platform, car lighting, ventilation, location of all car equipment, handrails, and emergency exits including electric contacts and method of hinging and locking.
D. Details of all signal and operating fixtures including hoistway access switches.
E. Details of sound and vibration isolation units for generator sets, if used.
F. Details of roller guide assemblies.
G. Details of sill sections and supports.
H. Details of selection, recall, and emergency operation switches including wiring diagrams.
I. Other drawings required or hereinafter specified.
5.3 The name of manufacturer, type or style designation, and the additional information called for below shall be listed on the shop drawings for each of the following:
A. Driving machine.
B. Driving machine motor including hp and rpm.
C. Elevator controller.
D. Group supervisory system controller.
E. Indicator panel.
F. Car safety including maximum rated load and speed.
G. Governor.
H. Power door operator.
I. Door interlocks and electrical contacts.
J. Buffers including stroke, certified maximum and minimum loads and maximum striking speed.
K. Car ventilation blower including c.f.m. and hp ratings.
L. Car emergency lighting.
M. Static motor drive unit.
6. SAMPLES:
6.1 Referring to the "Sample" requirements of the General Conditions, submit for approval, four samples of all finishes, car floor materials, operating and signal system fixtures, hoistway entrance and door materials, sills, protection pads, and light fixture lenses.
7. MANUALS:
7.1 Three (3) sets of operating and maintenance manuals shall be furnished in bound form. Manuals shall include:
A. Description of the elevator system's method of operation and control including the functions of signals, door devices and other specified features.
B. Written instructions for the adjustment and care of the equipment.
C. Replacement parts list with part numbers.
D. Type of lubricant required for each lubricated part.
E. Complete set of as-built wiring diagrams.
7.2 The identification label for each manual shall include the subject, building name and location, government contract number and the specific elevator numbers to which the manual applies.
7.3 One set of manuals shall be provided in the tool cabinet in the elevator machine room unless otherwise directed. The two additional sets shall be delivered to the Contracting Officer's Representative.
8. WARRANTY AND GUARANTEE:
8.1 All work under this section shall be subject to the terms specified under "Guarantees" in the General Conditions and the guarantee period for an elevator unit shall be one year after the date the final elevator is placed in normal use by the Government.
9. MAINTENANCE:
9.1 Furnish full maintenance for the elevators starting on the day the actual work begins at the site during the installation period, and for 12 months after final acceptance by the Government of the last elevator in the entire project. The maintenance service shall consist of regular weekly examinations of the installation and shall include the necessary adjustments, repairs, cleaning, lubrication, and supply and replacement of all parts to keep the equipment in proper operating condition.
9.2 All routine adjustments and service shall be performed by trained employees of the elevator contractor and may be made during the regular working hours of the trade.
All services required to ensure safe and reliable performance of the elevators shall be provided by regularly assigned maintenance personnel of the elevator contractor.
9.3 Weekly preventive maintenance programs shall be scheduled for each elevator.
The date and hours of work shall be scheduled and submitted for approval and acceptance by the Building Manager. All personnel shall register with the proper Government authority upon entering and leaving the building.
9.4 Provide 24-hour emergency call-back service for the maintenance period, by promptly responding to requests from the Building Manager or his authorized representative by telephone or otherwise, to restore elevator services where a shutdown or trouble should develop. These emergency call-back services shall be limited to minor adjustments required to protect the immediate safety of the equipment and persons in and about the elevator. Contractor shall respond to emergency call backs in one hour or less.
A. The Contractor shall provide and keep current a suitable check chart for each elevator. The charts shall be posted in the machine rooms on which entries shall be made to indicate the status of scheduled items of maintenance work performed, and the time in man-hours. The Contractor must properly initial the chart to indicate that the work has been accomplished.
B. The Contractor shall immediately notify the Contracting Officer (in writing) of the existence or the development of any defects in, or repairs required to the elevators which the Contractor considers he is not responsible for under the terms of the contract, and shall furnish him a written estimate of the cost to make necessary repairs. The Contracting Officer reserves the right to make final determination as to responsibility.
10. INSTRUCTIONS:
10.1 The instruction period for Government employees shall be not less than one (1) eight (8) hour day for the work under this section. Manual and wiring diagram instructions given in the elevator machine room shall be considered the equivalent to classroom instructions.
10.2 Submit outline of instructions to be given, one (1) month prior to the Instruction Period, for approval.
10.3 Instructions shall be completed before the warranty and maintenance period expires.
A. If the instructions have not been completed prior to the termination of the maintenance period, that period shall be extended as a part of the contractual requirements until the instruction requirements have been satisfied.
10.4 Provide, without additional expense to the Government, competent instructors to train employees of the Government, in the care, adjustment and operation and sequence functioning of the operation and the control system. Instruction shall be given during regular working hours and take place at the job site. The instruction shall be by qualified, factory trained engineering representatives possessing complete knowledge of the care, adjustment and operation of the elevator system.
A. Approximately half of the time shall be used for classroom instructions. All other time shall be used for instruction at the equipment. Where significant changes or modifications in equipment are made under the terms of the guarantee, additional instruction shall be provided as may be necessary to acquaint the operating personnel of the changes or modifications.
B. Three copies of an operating and maintenance manual, prepared by the contractor, shall be utilized by the contractor for instruction purposes. After completion of all instructions, the three copies of the manual shall be turned over to the Building Manager.
C. Three sets of as-built wiring diagrams with a complete description of operating sequences shall be furnished and delivered to the Construction Engineer fifteen (15) days prior to the start of the instructions, for use by the instructors.
D. The time and place of the instructions shall be coordinated with the Building Manager.
11. POWER SUPPLY:
11.1 The power available is [See Study and/or verify during pre bid site visit(s).]
11.2 Before any electrical equipment is manufactured or purchased, the characteristics available for elevator power and lighting shall be verified. Where characteristics are different from those specified above, the equipment shall be furnished for the power as verified by the contractor.
11.3 Failure to verify the power supply shall not relieve responsibility for the satisfactory operation of the equipment.
11.4 Controls shall have provisions for sequential return of all elevators and operation elevators on Emergency Power.
12. CAPACITY, SPEED, TRAVEL, PLATFORM SIZE:
12.1 The elevators shall have a capacity to lift the rated load at the rated speed in feet per minute, specified in the following schedule. The rated load shall be exclusive of the weight of the complete car and cables. The travel, terminal floors, number of stops and openings and the overall car platform size given in the schedule shall be verified with requirements indicated on the drawings.
ELEVATOR SCHEDULE
Elevator Number Type Rated Load (Lbs)
Target Speed
(FPM)
Floors Served
# of Stops Platform
1, 2, 3, 4, 5, 6, 7, 8, 9, & 10
Gearless Passenger
3500 600 1-12 12 Refurbish Existing Platform & Cab
11 & 12 Gearless Passenger
3500 600 B, 1, & 7-12
8 Refurbish Existing Platform & Cab
13 Gearless Freight
3000 500 SB, B,
1-12
14 Provide New Platform & Cab
14 Gearless Freight
3000 400 SB, B,
1-12
14 Provide New Platform & Cab
13. ELECTRIC FEEDERS ANDWIRING :
13.1 Provide new electric disconnect switches in both machine rooms for elevator power supply for all elevators rated for the new VVVF-AC drive system and new controls.
13.2 Provide new disconnects for the existing 110 Volt A.C. power supply for car light circuits for all elevators. New disconnects shall be labeled, located in the machine room, and lockable in the off position
13.3 Provide new LED light fixtures with guards in the elevator machine rooms. Provide all hoistways with LED fixtures with a labeled, lockable disconnect in the machine room. LEDs in the hoistway shall be located at each landing.
Conduits and fittings shall be in accordance with the following Federal Specifications:
A. Threaded steel conduit WW-C-581E
B. Electrical metallic tubing (EMT) WW-C-563A
C. Flexible metal conduit WW-C-566C
D. Fittings for cable and flexible conduit W-F-406B
E. Fittings for conduit W-F-408C
13.4 Couplings and connectors for EMT shall be steel or malleable iron, shall be "Liquidtight" or "Raintight", and shall be of either the gland and ring compression type or the stainless steel multiple point locking type. All connectors shall have insulated throats. Fittings using set screws or indentations as a means of attachment shall not be used.
A. Traveling cables shall include six (6) spare shielded pairs, and at least one coaxial cable for addition of video camera. Provide a spare cable for the future addition of EXIM card reader in the COP.
B. Traveling cable shall have adequate wiring to support an digital screen capable of live television installed in the elevators COP. This screen must also be capable of working with MAD VMS system for emergency communications. See section 40
C. Traveling cable shall have adequate wiring to support a camera located in the COP to comply with 2022 ASME 17.1 code for emergency communication requirements.
13.5 All conduit connecting the various items of elevator equipment in the elevator machine room shall be run concealed where practicable. Metal wireways and auxiliary gutters shall be run exposed in readily accessible locations. All raceways embedded in concrete shall be rigid or intermediate steel conduit. At all other locations any of the other types of raceways specified may be used subject to conditions specified. Raceway fittings shall provide conductor passageways free from burrs, shoulders or other projections which will reduce internal passage area or cause abrasion of conductors being pulled through.
13.6 All conductors to the car shall consist of flexible traveling elevator cables, conforming with the requirements of the NEC. Cables shall be run from the car junction box to a machine room junction box and from these boxes, conductors shall be run to various required locations. Each traveling cable conductor shall have a distinctive color code for identification of the individual conductors. Each traveling cable shall have at least 20 percent spare conductors. Junction boxes shall contain approved terminal blocks for connection of conductors. Terminal blocks shall have indelible identification numbers for each terminal connection. All connections to terminal blocks shall be made with pressure wire connectors.
A. Traveling cables shall be so suspended, anchored and run that the strain on individual cable conductors shall be reduced to a minimum and connections to terminal blocks shall be free from all strain. The outer cable covering must remain intact between junction boxes and abrupt bending of cable producing distortion of cable shall not be permitted. If, due to sway or change in relative position of traveling cables, complete freedom from contact with the hoistway construction cannot be avoided, suitable shields or pads shall be provided wherever necessary to prevent chafing or damage to the cables.
13.7 Furnish and install all wires and cables necessary for the proper connection and operation of all equipment installed under the elevator contract. All conductors shall be in accordance with NEC requirements. The conductor size shall be such that the maximum current carried shall not exceed limits prescribed by the NEC.
A. Unless otherwise specified, conductors exclusive of traveling cables, shall be annealed copper with 60o Centigrade or better insulation and shall be in accordance with Federal Specification J-C-30A. Single and multiple conductor cables shall have color coding or other suitable identification for each conductor. Unless otherwise specified, no joints or splices shall be permitted in wiring except at outlets. Tap connectors may be used in wireways provided they meet all NEC requirements. Installation of conductors in raceways shall conform to the NEC.
13.8 All conductors used for external wiring between the various items of elevator equipment shall be connected to terminal blocks which meet UL Standard 1059 (1975). Crimp-type connectors shall be applied with an appropriate setting tool to ends of all size No. 10 or smaller external wires.
14. ACCESSORIES:
14.1 Three sets each of complete, legible field wiring diagrams, including single line diagrams showing all electrical circuits shall be furnished. All symbols shall be listed corresponding to the identity or markings on all of the elevator machine room and hoistway apparatus of the systems specified. One set of diagrams shall be coated with laminated plastic, or other approved covering, suitably bound and placed in the machine room where directed. Each of the two remaining sets shall be neatly bound and delivered to the Contracting Officer's Representative. The diagrams shall be revised to include all field modifications.
14.2 A complete set of tools necessary for making all system adjustments shall be furnished for each elevator machine room and delivered to the GSA Project Manager and/or CM Firm. (A metal tool cabinet having two shelves and a hinged door shall be provided in each elevator machine room. Cabinet size shall be not less than 48 inches high, 18 inches wide and 14 inches deep.)
14.3 Include an adjuster's level service tool or terminal with complete written installation manuals, service manuals, adjustment information and instructions for performing systems adjustments, special and emergency functions, diagnostic trouble shooting, and systems testing as required by ANSI A17.1 code. The service tool shall become the property of GSA, and if the device requires reprogramming it shall be performed at no additional cost to the government for the life of the equipment.
---AND ---
Provide a monitoring laptop capable of monitoring all elevator activities and trouble alarms. Device shall be delivered to the Construction Engineer. Device at a minimum shall come equipped with 16GB of ram upgradable to 32GB. The processor must provide a minimum of 3.5 GHz of speed. The screen must be a touch screen. Included with complete written installation manuals, service manuals, adjustment information and instructions for performing systems adjustments, special and emergency functions, diagnostic trouble shooting, and systems testing as required by ANSI A17.1 elevator code. The service tool shall become the property of GSA, and if the device requires reprogramming it shall be performed at no additional cost to the government for the life of the equipment.
14.4 Cylinder locks shall have a bronze cylinder with not less than five pin tumblers or shall have not less than a five-disc combination provided wafer keyways, tumblers, and springs are of stainless steel. Provide three nickel silver keys for each lock and deliver the same to the Construction Engineer. Provide an identification tag on each key with stamped legend "PROPERTY OF U.S. GOVERNMENT" on the reverse side. Tags shall conform to Federal Specification FF-T-77B, Type A, Class 1, engraved. Locks shall be independently keyed unless otherwise specified. Key operated switches shall be of the cylinder lock key operated type.
14.5 A hoistway access switch shall be provided at the top and bottom terminal landings for all elevators. Hoistway access switches shall be of the key operated type meeting all requirements of the A17.1 Code. The movement of a car by means of the hoistway access switch at the top terminal landing shall be limited to approximately 12 feet down travel and a return to the top landing. Access switches shall be mounted flush and inconspicuously in the door jamb.
A. Faceplates, if furnished, shall be of metal of the same composition and finish as the faceplates of landing call buttons for the corresponding landing. The exposed portion of each access switch or its faceplate shall have indelible legends to indicate its "Identity" and the "Up," "Down" or "Off" positions.
14.6 All elevators shall be provided with an operating device mounted on the car crosshead which will permit slow speed operation of the car. Separate additional means for operation of power door operators and automatic car leveling devices are not required. The operating device shall be mounted in a metal box and shall be rigidly secured in a position conveniently accessible on top of the car. Operating devices shall be shrouded or otherwise protected in an approved manner to prevent accidental movement. Provide indication of Fire Service Operation within or adjacent to the car top operating device.
14.7 Where access to the elevator pit is through the bottom terminal landing, the pit stop switches shall be located 4 feet above pit floor and 18” above bottom landing floor and adjacent to the pit ladder.
14.8 Provide Hoistway Door Unlocking Devices at each entrance for all elevators, conforming to the requirements of the A17.1 Code. New hoistway doors shall include door unlock access.
14.9 Provide a digital display to be installed in the elevator in the car station. System shall have the ability to scroll live television broadcast as well as a self-designed building directory and/or events calendar, system to be owned by GSA and not a subscription service. This display's main function shall be the car interior position indicator and work with the code required video and messaging system.
14.10 Provide as an alternate elevator lobby panel to be located in the Lobby and the fire command center. Panel shall show the location and status of each elevator located in the building at all times. Additionally, the panel shall have two way voice communication between each individual car and the lobby panel via a handset style phone to be incorporated in the fire command center lobby panel.
15. PAINTING AND FINISHING:
15.1 Unless otherwise specified the machine, motor, motor drive, controller, selector, sheaves, car frame, counterweight frame, machine and sheave beams, guide rails and buffers except their machined surfaces, door operator, cams, and other ferrous metal items furnished for each elevator shall be painted with not less than one shop priming coat and one field coat of semi-gloss enamel in the manufacturer's standard color.
A. Holes or other imperfections in the surfaces of a machine, motor, casting, motor generator and the like shall be filled and smoothed off before the factory priming coat is applied.
B. The painting and finishing of governor, car, hoistway entrances and doors shall be as specified under their respective headings.
C. The machine room floor, pit floor and car top shall have all unused holes or defects filled and shall be painted with semi-gloss light colored gray.
D. Hoistway walls shall be cleaned down and painted as needed to provide a consistent finish with what is currently there. In addition, any penetrations in hoistway walls shall be smoothed and filled to provide a 2hr fire rating.
i. If the hoistway is unpainted CMU, no painting is necessary however the contractor is still required to fill any penetrations to result in a 2hr fire rating.
E. Fill and finish all unused holes in the machine room, secondary floors and walls, and hoistway. The result is a 2 hour fire rating.
F. Any exposed ferrous metal used in the project shall be primed and painted prior to acceptance.
G. Paint rails as necessary.
H. Paint all buffers with black or darker gray semi-gloss paint
15.2 Identification Markings:
A. Elevator hoistways shall have floor designations on the walls and/or doors of hoistways in accordance with the A17.1 Code.
B. Floor designations shall be provided at each hoistway entrance on both sides of the jamb visible from within the car and the elevator lobby at a height of 60 inches above the floor. Designations shall be on a contrasting color background, a minimum of 2-1/2 inches high and raised at least 0.030 inch.
Identification markings for machines, motor generators, controllers, etc. shall be provided at locations where directed. The numbers of hoisting machines and motor generators sets shall be 4 inches high and the numbers for controllers, selectors and other auxiliary equipment shall be 2 inches high.
C. The identification numerals or letters for floor landings, machines, etc., shall be either stencil painted or decal type of a color which will contrast with color of the surface to which the marking is applied. Decal type markings shall have a coat of clear varnish or equivalent after application.
16. MACHINE BEAMS AND OTHER SUPPORT STEEL
16.1 All necessary structural steel beams or other steel members required for support of elevator machine, sheaves, rope hitches, governor, buffers, grating, and other elevator equipment, shall be provided. Bearing plates and anchors shall be provided to mount adapter beams and other support steel securely in place.
Existing beams and slabs may be reused provided the calculations reveal they are adequate for the equipment to be used and support the loads in accordance with the A17.1 Code. Otherwise, provide support as required.
16.2 Provide metal sleeves projecting 2 inches above the concrete slab for all hoisting rope and governor rope, selector rope or tape, and other similar openings. Sleeves shall be not less than No. 12 U.S.S. Gage and shall have inside sleeves sloped the same as the ropes and tapes.
16.3 Fill and finish all unused holes in the machine room, secondary floors, and walls, and hoistway.
16.4 All structural and supporting steel in the pit has notable rust. All pit channels, anchors, and other supporting steel in the elevator pit shall be removed and replaced with new steel coated to resist corrosion from future flooding and water intrusion in the building.
16.5 Remove all debris from the cubby located in the pit of elevator 1, Fabricate and install a cage made of security mesh, with sliding or hinged gate for access.
16.6 Fabricate and install a security cage for the first floor window that is blocked off with Drywall to keep intruders from entering the elevator shaft from the first floor.
17. GEARLESS MACHINE:
17.1 Existing machines for all elevators shall be replaced with new AC gearless overhead machines.
A. For all elevators, AC gearless machines shall be provided.
B. GSA requests alternate pricing for vendor non-proprietary belted machines.
17.2 All sheaves shall be replaced new, including but not limited to deflector sheaves, overhead, and cartop sheaves.
17.3 Provide A17.1 required means to prevent ascending car and unintentional movement of car safety devices. No pneumatic devices accepted per the GSA authority having jurisdiction.
18. GEARLESS MACHINE &MOTOR:
18.1 Provide high efficiency Permanent Magnet AC-motor, brake assembly, support frame, and grooved drive sheave. The motor and brake assembly shall be attached to the support frame and have a common rotating shaft of the gearless design. The motor shall also be suited in all respects to the AC used. The motor shall be ruggedly designed and all parts shall be capable of meeting the severe requirements of elevator service. The motor shall have sufficient capacity to meet the test requirements.
18.2 The speed of the motor when operated with the controller in full speed position shall not vary more than 5 percent of the normal rated speed under all loads within the capacity range.
18.3 The insulation resistance between conductors and frame of motor shall be not less than one megohm. The dielectric shall successfully pass a dielectric test of 60 Hertz alternating current applied for one minute.
18.4 The motor bearings shall be either the ball or roller type arranged for grease lubrication and fitted with grease gun connections and drain plugs. The bearings and lubricant reservoirs shall be dust tight and shall incorporate effective lubricant seals or other means to prevent lubricant leakage. The fittings for lubrication may be omitted where pre-lubricated sealed for life type bearings are used.
19. CONTROLLER
19.1 Furnish and install new non-proprietary controls for all elevators. The elevator controller shall provide operation as specified hereinafter. Controllers shall be of the floor mounted, free-standing type with NEMA 1 enclosures, with locking cabinet doors. Bolt the bottoms of the control panels to the floor.
19.2 The sockets or circuits boards used for the mounting of relays and electrical or electronic components shall be made of an approved moisture resisting dielectric material having dielectric and structural properties suitable for its intended usage.
The material shall conform to requirements of NEMA LI 1-1971 (R 1976) for the type and grade suited for the application. The sockets and circuit boards shall be secured to panel frames with bolts, screws, or other approved demountable means.
A. The controller panel frame shall be of rigid steel construction to provide means for mounting circuit boards or devices. Panel frames supporting controller switching devices which produce a perceptible panel frame vibration, shall be provided with an approved vibration absorbing mounting.
19.3 All wiring on the panels shall be neatly formed and securely fastened in place. All equipment on the panels shall be readily accessible and easily replaceable. All controller relays shall be magnetically operated. Solid state components shall be electrically sized, physically spaced, and ventilated so their heat can be adequately dissipated during operation. All controller components shall be designed and rated to provide at least 20 years of operation as specified, with recommended maintenance, before replacement is required.
A. All mechanical switches and relays shall be opened either compression of leaf type contact springing or gravity when power is interrupted except those switches or relays which are magnetically or mechanically latched closed. All A.C. relay magnets shall be designed so residual magnetism shall not interfere with proper operation. All similar switch and relay units on controllers shall be of the same manufacture.
19.4 Wiring for the various external control and operating circuits shall be brought to a terminal board and then shall continue to the various components on the controller panel. Terminal board may be an integral part of a panel, or a separate panel mounted adjacent to the same panel or terminal blocks mounted on the panel. Each terminal is to have indelible means of identification to facilitate testing of the various controller circuits. All connection of wires to terminal boards from external circuits shall be made with solderless pressure type wire connectors.
When a number of external connections are made to the same terminal, stud washers shall be provided between lugs to ensure uniform seating and contact.
19.5 Each device on the controller panels shall be properly identified by name, letter or standard symbol which shall be neatly stencil painted, (or otherwise marked) in an approved indelible and legible manner, on the device or panel. The identification markings shall be coordinated with identical markings used on the wiring diagrams.
20. SOLID STATE MOTOR DRIVE (3VF DRIVE) :
20.1 Remove existing drives and provide Variable Voltage Variable Frequency AC Regenerative type operation for all elevators.
System shall be adequate size to handle the new hoist machine. Suitable isolation transformer shall be provided. The system shall, during acceleration and deceleration periods, gradually change the voltage and frequency applied to the elevator motor without interruption of power to the motor to provide smooth acceleration, deceleration and running speeds, and accurate floor stops. All safety circuits shall conform to ASME 17.1 Code. Line filters, noise spike or notching suppressors and isolation transformers shall be provided to ensure electrical feedback to power source of power generated by overhauling loads shall not affect other computer operated equipment in the building. Resilient isolators shall be provided to support all drives and transformers. Audible noise shall not exceed 70 decibels under any operating condition.
A. The motor drive shall be equipped with devices which shall limit the current applied to the hoisting motor to that required for actual specified duty, and shall prevent damage to the hoist motor from overload, overvoltage, or excessive current.
B. In case of brake application under normal operation, the hoisting motor shall be slowed down electrically, through a dynamic braking effect, so it will be practically stopped at the instant of brake application.
C. Motor drive components shall be installed in a NEMA 1 enclosure located in the machine room. All components shall be conservatively rated to provide a life of not less than 80,000 hours. All electric connections between the electric feeder, the motor drive, and the elevator hoist motor shall be made with suitable connectors or to suitable terminal blocks.
21. CAR LIGHTING AND FAN CONTROL:
21.1 The control system shall be equipped with an adjustable timing device which when an elevator that has remained idle at its assigned parking floor for a predetermined time after the last registered call has been answered, shall automatically extinguish the regular interior car lighting and stop the car fan or blower, if running, of the corresponding car but the power circuits to convenience lights and receptacles on top and bottom of car shall not be interrupted. Any hall or car call registration shall cause the car lighting and fan to resume their normal functions.
21.2 The circuits shall be so arranged that power to the car lighting and car fan or blower shall not be interrupted by an overload, blown fuse, disconnect switch, or other abnormal conditions to the elevator controls.
21.3 Car lighting shall be LED 4000K color. Lighting shall be supplied from Man-D-Tec or approved equivalent. LED light fixtures with plastic guards shall be provided on top of the car and also beneath the car platform. Duplex receptacles shall be provided on the top of the car and beneath the car platform to supply 120 V.A.C. outlets shall be 2 pole, 3 wire grounded type rated for 15 amperes at 125 volts conforming to Federal Specification W-C-596/12A.
The interior lighting system shall be dimmable meeting the minimum output for all applicable code at the lowest illumination. Lighting shall be controlled by an on/off switch located in the car station control panel and provided with a dimmer when the car is unoccupied through timeout.
21.4 A ventilation system of exhaust type shall be provided for each elevator arranged to exhaust air through openings around the suspended ceiling.
A. The system shall include a blower driven by a direct connected motor and mounted on top of the car with isolation to effectively prevent transmission of vibration to the car structure. The blower shall have three operating speeds (low, med, high) with a rated free delivery air displacement to meet the size of the elevator to current ASHRAE standards at the respective speeds. The unit design and installation shall be such that the maximum noise level when operating at high speed shall not exceed 55 dba approximately three feet above the car floor. A four-position switch to control the blower unit shall be provided in the car service cabinet. (off, low, med, high)
22. GROUP AUTOMATIC OPERATION
22.1 Passenger elevators Nos. 1 - 6 and 7 - 12 shall have group automatic operation and shall operate as two separate groups.
22.2 The operating devices for group automatic operation shall include dispatch buttons in each car, landing call buttons and a group supervisory control system, all electrically connected to the control equipment governing selection of landing stops be made, direction of travel, starting, acceleration, retardation and stopping of the elevator cars and the systematic dispatching operations of the elevators.
22.3 A new car operating panel(s) shall be provided to all elevators. The panel shall be of the swing return type and contain the following devices:
A. A series of car dispatch buttons having designations corresponding to the landing served and an integral registration light for each button. The actuation of a dispatch button in either panel shall cause the corresponding registration light in both panels to be illuminated until the call is canceled.
B. Key operated emergency stop switch.
C. Emergency signal button connected to a 6-inch diameter bell located on the car top.
D. Door open and close buttons.
E. Key operated emergency service switch, pilot light and all necessary instructions, signage, etc. in the main panel.
F. Key operated independent service switch, on main panel only, exposed flush on faceplate.
G. Provisions for hands-free emergency communication system, i.e. speaker perforation, buttons, operating instructions, signage, etc.
H. Space and wiring for future card reader system. Terminate wiring into a “Security” junction box located on the side of controllers. Provide a smoked plexiglass panel over the card reader space.
22. 4 All exposed car controls shall be at least 3/4-inch in size. All control buttons shall be designated by Braille and raised standard alphabet characters for letters, arabic characters for numerals, and standard symbols as required by the A17.1 Code.
Identification markings for all exposed controls shall be adjacent in a contrasting color background to the left of the controls. Symbols, letters, or numerals shall be a minimum of 1/2 inch high and raised or recessed 0.030 inch. The control button for the main entrance shall be designated by a raised star to the left of the button.
Symbols shall be industry recognized standard types firmly affixed without adhesives.
22. 5 The emergency stop and emergency signal bell devices shall be approximately 35 inches above the car floor. The highest car dispatch button shall be no more than 54 inches above the floor.
22. 6 A metal service cabinet shall be located directly below, or arranged as an integral lower section, of the main car operating panel. The service cabinet shall have a hinged door with independently keyed cylinder lock. Door shall be arranged to swing away from the elevator entrance. The following devices shall be mounted behind the metal door:
A. Car light switch.
B. Car fan or blower switch.
C. Emergency light test button.
D. Keyed inspection switch to permit use of hoistway access switch.
E. 110 V GFCI duplex receptacle complete with wiring and cover installed within the service cabinet of each car.
F. The devices in all car operating panels shall be located in identical relative positions. Readable, indelible markings shall be provided for each device as required to indicate its identity and positions.
22.7 Provide new landing button signal fixtures, with space and wiring for future card reader control for the security system for all elevators containing up and down buttons at each intermediate landing, single button fixtures at each terminal landing, and an integral registration light for each button. The group of elevators shall have landing call buttons, installed at ADA height in the existing locations.
23. MICROPROCESSOR GROUP SUPERVISORY CONTROL :
23.1 Microprocessor Group Automatic Control: The microprocessor dispatching shall be based on an advanced 16 bit microprocessor computer system that continuously scans and analyzes every elevator's changing position, condition and workload. It shall compute the potential arrival of every car in REAL TIME; it shall assign and reassign hall calls to the car that can arrive there the quickest. Supervisory and individual controllers shall be of the floor mounted, free-standing type with NEMA 1 enclosures, with locking cabinet doors.
23.2 REAL TIME Management” REAL TIME management…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .