This synopsis and draft solicitation are for an indefinite delivery/indefinite quantity contract to establish multiple award task order contracts for elevator modernization projects valued over $1 million within the General Services Administration. The IDIQ contracts will have a base year and four option years not to exceed $650 million total. Two initial modernization task orders are planned for Lafayette Building and an unspecified location. Questions on the draft solicitation are due by April 11, 2024 with responses and any amendments issued prior to the final solicitation planned for release on or around April 19, 2024. Awards will target up to six small businesses as defined by NAICS code 238290 with a size standard of $22 million.
View the file
Other files
Show 40 more
Latest 50 of 52 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2023 OPERATIONS AND MAINTENANCE
INSPECTION REPORT
ROBERT C. WEAVER FEDERAL BUILDING
(DC0092ZZ)
451 7th Street, SW Washington, D.C. 20410
Prepared for
GENERAL SERVICES ADMINISTRATION
Safety, Environment, and Fire Protection Branch
National Capital Region 1800 F Street, NW., Room 4324
Washington, D.C., 20006
Submitted by
Rambin Global JV 6401 Golden Triangle Drive, Suite 304
Greenbelt, MD 20770
September 25, 2023
Contract No. 47PM0618D0014 PDN No. EP-47PM0923F0044 Order No. 47PM0923F0044
Reviewed by:
Judi Todd Darnell Dr. Channa Bambaradeniya, CIH Director of Operations Certified Industrial Hygienist
General Services Administration 2023 O&M Inspection Report Robert C. Weaver Building (DC0092ZZ) Rambin Global JV Project # GSA-2023-01 i
Executive Summary Rambin Global Joint Venture (RGJV) conducted a reinspection at the Robert C. Weaver Federal Building located at 451 7th Street, SW, Washington, D.C., 20410, between the dates of September 5 and 6, 2023. This reinspection was conducted as per the General Services Administration’s (GSA’s) scope of work and in accordance with Asbestos Hazard Emergency Response Act (AHERA) Protocols.
The survey was based on previous reinspection reports submitted to RGJV by GSA.
The following six (6) materials are confirmed as asbestos-containing materials (ACMs):
12”x12” Floor Tile (Grey with Light Grey Streaks) and Black Mastic 12”x12” Floor Tile (Black with Grey Flecks) and Black Mastic Gray Floor Tile and Black Mastic Tank Insulation, Tank T-1-10 Tank Insulation, Tank T-1-7 Underlying Floor Tile (Under HSA#2) *
*Note: HSA=Homogeneous Sampling Area
The following twenty-one (21) materials are presumed asbestos-containing materials (PACM):
12”x12” Floor Tile (Dark Grey with Light Grey Flecks) and Black Mastic 12”x12” Floor Tile (Blue with Light and Dark Blue Flecks) and Black Mastic 12”x12” Floor Tile (Tan with Beige Flecks) and Yellow/Tan Adhesives 12”x12” Floor Tile (Cream with Brown Flecks) and Black Mastic 12”x12” Floor Tile (Grey with Light & Dark Grey Flecks) and Yellow/Brown Adhesive Residual Black Mastic under Carpeting 1’x2’ Tan-Brown Stone Floor Tile 4” Brown Cove Base with Yellow-Tan Adhesive 4” Black Cove Base with Yellow-Tan Adhesive 4” Grey Cove Base with Dark Brown Mastic Drywall Panel Office Wall – Metal Frame Wall Systems Ceiling Plaster (White) in Metal Panel Frames Beige Seam Sealants on Fiberglass HVAC Duct Insulation 2”-4” OD Mudded Fittings on Fiberglass Pipe Insulation 4”-6” OD Mudded Fittings on Fiberglass Pipe Insulation 6”-8” OD Mudded Fittings on Fiberglass Pipe Insulation 8”-10” OD Mudded Fittings on Fiberglass Pipe Insulation 10”-12” OD Mudded Fittings on Fiberglass Insulation Water Supply Pipe Lines 10”-12” OD Mudded Fittings on Fiberglass Insulation Storm-Water Pipe Lines Fire Doors
Sixteen (16) materials are non-ACM per PLM Analysis. A summary of those materials is provided in the Findings section of this report.
ii
All accessible areas were surveyed to identify and assess the condition of ACBMs as part of this reinspection.
The survey information and updates, along with any other observations, are provided in the Findings and Recommendations of this report. To assist GSA with budgeting, approximate abatement costs are provided.
iii
Table of Contents
EXECUTIVE SUMMARY I
TABLE OF CONTENTS III
1.0 INTRODUCTION 1
2.0 METHODOLOGY 2
3.0 FINDINGS 4
4.0 RECOMMENDATIONS 6
APPENDIX A - ASBESTOS-CONTAINING MATERIAL INVENTORY
APPENDIX B – PRESUMED ASBESTOS-CONTAINING MATERIAL INVENTORY
APPENDIX C - NON-ASBESTOS-CONTAINING MATERIAL INVENTORY
APPENDIX D – LABORATORY ANALYTICAL RESULTS
APPENDIX E – GSA ASBESTOS ASSESSMENT FORMS
APPENDIX F – INSPECTOR(S) ACCREDITATION
APPENDIX G – 2023 INVENTORY OF ACM AND PACM, MATERIAL ASSESSMENT, AND APPROXIMATE
ABATEMENT COSTS
1.0 Introduction
In accordance with our Industrial Hygiene Services contract with the General Services Administration (GSA), Rambin Global JV (RGJV) completed the 2023 Asbestos Hazard Emergency Response Act (AHERA) Operations and Maintenance (O&M) survey of the Robert C. Weaver Building (DC0092ZZ) on September 5 and 6, 2023. The Weaver Building is located at 451 7th Street, SW, in Washington, D.C. The purpose of the survey was to assess previously identified asbestos-containing materials (ACMs), to sample and confirm the asbestos content of presumed asbestos-containing materials, and to identify and sample any additional suspect ACMs not previously identified. Sampling within the Weaver Building was limited to 30 samples per the contract’s scope of work. GSA provided RGJV with the 2016 TTL-Arc Environmental JV Reinspection Report. A list of previous abatement activities was not available.
Mr. John Fuentes (#230003039), Mr. Sameera Meegoda (#230002759), and Mr. Daniel Wooddell (#220001918), all EPA and Maryland-accredited AHERA Inspectors, with reciprocity in Washington, D.C., conducted the reinspection. The Inspectors’ certifications are provided in Appendix F.
Survey and reinspection protocols were based on those adopted by the U.S. Environmental Protection Agency (EPA) as detailed in the Asbestos Hazard Emergency Response Act (AHERA; 40 CFR 763, Subpart E), and guidelines detailed by GSA.
2.0 Methodology
RGJV conducted the asbestos survey under protocols established by USEPA 40 Code of Federal Regulations (CFR) 763 Asbestos Hazard Emergency Response Act (AHERA) and 40 CFR 61 Subpart M, National Emission Standards for Hazardous Air Pollutants (NESHAP). GSA-established protocols for asbestos bulk sampling were followed during the survey.
When possible, suspect materials, according to AHERA, that were homogeneous in nature (i.e., uniform in color and texture, installation date) were identified, touched to determine friability, and sampled by removing a small piece. Extreme care was taken to avoid potential fiber release during the inspection/sampling process. Before sample collection, a fine mist of water was typically applied to the sample site. Samples were collected using sharpened core samplers and/or razor knives, where necessary, and immediately placed in labeled containers and sealed. Any dust generated was wet-wiped to minimize the potential for fiber release. Samples were not collected from occupied rooms. The location (selected at random), condition, and quantity of each homogeneous material were recorded in the inspector’s log.
During the survey, RGJV collected a total of twenty-nine (29) bulk samples of ten (10) suspect materials. The bulk samples were submitted, along with the corresponding chain-of-custody documentation, to AmeriSci Group of Midlothian, VA, a National Voluntary Laboratory Accreditation Program (NVLAP) accredited-laboratory, to determine the presence of asbestos in the sampled materials. Quantification of asbestos content in bulk samples was performed via EPA 600/R-93/116 Method using Polarized Light Microscopy (PLM). The EPA, the Occupational Health and Safety Administration (OSHA), and the District’s Department of Energy and Environment (DOEE) define an ACM as any material containing greater than 1% asbestos.
Assessment of friable ACBM was performed in accordance with Section 763.88 of 40 CFR, Part 763, Subpart E (AHERA). Numerous factors were considered for each homogeneous ACBM in each inspected functional space so as to group each ACBM into one of the seven AHERA assessment categories. Specific factors considered in assessing ACBM conditions included:
Friability Proximity to air plenum/stream Physical condition and extent of damage: Accessibility to building occupants
- Water damage Potential for damage
- Contact damage
- Deterioration
Inaccessible areas could be addressed only through extrapolation of conditions in accessible building space and review of building plans, specifications, or other building documents provided to RGJV. Such inaccessible areas might include but are not limited to:
Within walls Within fire doors Enclosed pipe/duct chases Inside mechanical equipment/ductwork Above plaster ceilings Behind doors that cannot be opened High areas beyond reach of 12-foot ladders
Limited access areas such as those beneath fixed or wall-to-wall carpeting, or above fixed ceilings with small access hatches, etc. were investigated as feasible. Conclusions regarding the presence or absence of asbestos in these areas might be of limited accuracy.
Suspect ACBMs were classified as per § 763.88 of the AHERA Rule, into one of the following seven-hazard assessment categories:
1. Damaged or significantly damaged TSI ACBM
2. Damaged friable surfacing ACBM
3. Significantly damaged friable surfacing ACBM
4. Damaged or significantly damaged friable miscellaneous ACBM
5. ACBM with potential for damage
6. ACBM with potential for significant damage
7. Any remaining friable ACBM or friable suspected ACBM
3.0 Findings
Based on the laboratory analytical results, three (3) of the materials sampled during 2023 survey were confirmed to be asbestos-containing by PLM analysis. The following lists include all materials noted and/or assessed by RGJV’s Inspector.
Details of confirmed asbestos-containing materials, including photos, are provided in Appendix A. Details for presumed ACM is summarized in Appendix B. Details for non-asbestos-containing materials is summarized in Appendix C. Current and previous (when feasible) analytical results may be found in Appendix D. GSA’s Asbestos Assessment Data Forms are provided as Appendix E.
Confirmed ACM
12”x12” Floor Tile (Grey with Light Grey Streaks) and Black Mastic 12”x12” Floor Tile (Black with Grey Flecks) and Black Mastic Gray Floor Tile and Black Mastic Tank Insulation, Tank T-1-10 Tank Insulation, Tank T-1-7 Underlying Floor Tile (Under HSA#2)
PACM
12”x12” Floor Tile (Dark Grey with Light Grey Flecks) and Black Mastic 12”x12” Floor Tile (Blue with Light and Dark Blue Flecks) and Black Mastic 12”x12” Floor Tile (Tan with Beige Flecks) and Yellow/Tan Adhesives 12”x12” Floor Tile (Cream with Brown Flecks) and Black Mastic 12”x12” Floor Tile (Grey with Light & Dark Grey Flecks) and Yellow/Brown Adhesive Residual Black Mastic under Carpeting 1’x2’ Tan-Brown Stone Floor Tile 4” Brown Cove Base with Yellow-Tan Adhesive 4” Black Cove Base with Yellow-Tan Adhesive 4” Grey Cove Base with Dark Brown Mastic Drywall Panel Office Wall – Metal Frame Wall Systems Ceiling Plaster (White) in Metal Panel Frames Beige Seam Sealants on Fiberglass HVAC Duct Insulation 2”-4” OD Mudded Fittings on Fiberglass Pipe Insulation 4”-6” OD Mudded Fittings on Fiberglass Pipe Insulation 6”-8” OD Mudded Fittings on Fiberglass Pipe Insulation 8”-10” OD Mudded Fittings on Fiberglass Pipe Insulation 10”-12” OD Mudded Fittings on Fiberglass Insulation Water Supply Pipe Lines 10”-12” OD Mudded Fittings on Fiberglass Insulation Storm-Water Pipe Lines Fire Doors
Confirmed Non-ACM
4” Black Cove Base with Brown Mastic 6” Gray Cove Base with Brown Mastic Wall Plaster with Skim Coat (Inner Corridor Walls on Pyrobar Block) Wall Plaster with Skim Coat (Outer Office Walls on Wire Mesh) Ceiling Plaster on Drywall 2’x4’ Drop Ceiling Panel (Track and Pinhole Pattern) 2’x4’ Rigid Drop Ceiling Panel Off-White Seam Sealant on Fiberglass HVAC Duct Insulation Off-White Seam Sealant on 2”-4” O.D. Fiberglass Pipe Insulation 9”x9” Floor Tile (Gray with Cream Flecks) Black Mastic Associated with 9”x9” Floor Tile (Gray with Cream Flecks) Tank Insulation (Gray Mud Over Fiberglass) (Tank T-1-11) Tank Insulation (Gray Mud Over Fiberglass) (Tank T-1-28) Underlying Floor Tile (3rd Floor Café) Mastic Associated with Underlying Floor Tile (3rd Floor Café) Mastic Associated with Underlying Floor Tile (Room SB-11) *
* Mastic is associated with Asbestos-Containing Underlying Floor Tile (GSA-HUD-38)
4.0 Recommendations
Any planned renovations or maintenance activities that will disturb known and suspect ACBM (and potentially render them friable) will require the proper response action of abatement, encapsulation, enclosure, and/or repair by AHERA and DOEE-accredited and trained personnel. All ACBM and PACM must be maintained in place, unless removed, in accordance with the O&M plan. All assumed ACBM(s) must be sampled prior to any disturbance to verify the presence of asbestos by an AHERA and DOEE-accredited Inspector and analyzed by a NIST/NVLAP accredited laboratory.
Specific material condition and response actions are provided in the table presented in Appendix G.
APPENDIX A – ASBESTOS-CONTAINING MATERIAL INVENTORY
Asbestos-Containing Materials Inventory – Robert C. Weaver Building
HSA
Material
Description Location
Estimated Quantity
Sample Number
Results Photograph
GSA-
HUD-01
12”x12” Floor Tile (Gray with Light Gray Streaks) and
Black Mastic
Throughout Building in Main Corridors, Under
Carpeting
610,830 SF
HUD-01A,
01B, 01C
Floor Tile: 2% Chrysotile Mastic: 5% Chrysotile
GSA-
HUD-02
12”x12” Floor Tile (Black with Gray Flecks) and Black
Mastic
Freight Elevator Lobbies, Suite
1100, Layer 2 in 3rd Floor Café, Basement Custodial Break
Room
5,515 SF
HUD-02A,
02B, 02C
Mastic: 5%
HUD-02.1
Gray Floor Tile with Black Mastic
Second Layer of tile in Suite 1100
1,200 SF
HUD-02C-C,
02C-D
Floor Tile: 2% Chrysotile Mastic: 5%
Not Available
Asbestos-Containing Materials Inventory – Robert C. Weaver Building
Material
Description Location
Estimated Quantity
Sample Number
Results Photograph
GSA-
HUD-33
Tank Insulation (Gray Mud over
Fiberglass)
Room B-248, Tank T-1-10
230 SF
GSA-HUD-
33A, 33B, 33C 2% Chrysotile
HUD-35
Tank Insulation (Gray Mud over
Fiberglass)
Room B-248, Tank T-1-7
370 SF
GSA-HUD-
35A, 35B, 35C
HUD-38
Underlying Floor Tile (Under
HSA#2)
Room SB-11 520 SF
GSA-HUD-
38A, 38B, 38C
Key: HSA= Homogeneous Sampling Area
APPENDIX B – PRESUMED ASBESTOS-CONTAINING MATERIAL
INVENTORY
Presumed Asbestos-Containing Materials Inventory – Robert C. Weaver Building
Material
Description Location Quantity Photograph
GSA-
HUD- 13
12”x12” Floor Tile (Dark Grey with Light Grey
Flecks) and Black Mastic
Replacement flooring throughout Main
Corridors of building and in Basement 200
Corridor
2,300 SF
HUD- 14
12”x12” Floor Tile (Blue with Light and Dark
Blue Flecks) and Black Mastic
Room 5133 (Copy Room)
600 SF
HUD- 15
12”x12” Floor Tile (Tan with Beige Flecks) and Yellow/Tan Adhesives
3rd Floor Café with Dining and Restaurant
Areas
1,375 SF
HUD- 16
12”x12” Floor Tile (Cream with Brown Flecks) and Black Mastic
Room B-155 (Vending/Snack
Room)
288 SF
Material
Description Location Quantity Photograph
GSA-
HUD- 17
12”x12” Floor Tile (Grey with Light & Dark
Grey Flecks) and Yellow/Brown
Adhesive
Conference Room 10239 rear AV Room
185 SF
HUD- 18
Residual Black Mastic under
Carpeting
Basement Room B-
600 SF
HUD- 19
1’x2’ Tan-Brown Stone Floor Tile
1st Floor Main Lobby and Corridors, Main 1st Floor Cafeteria central walkway
5,415 SF No Photo Available
GSA-
HUD- 20
4” Brown Cove Base w/Yellow- Tan Adhesive
Throughout Building – Occupied Office Areas
5,200 LF No Photo Available
GSA-
HUD- 21
4” Black Cove Base w/Yellow- Tan Adhesive
Throughout Building – Occupied Office Areas
12,885 LF
HUD- 22
4” Grey Cove Base w/Dark Brown Mastic
Freight Elevator Lobbies, occupied offices, and inner hallways
3,800 LF No Photo Available
GSA-
HUD- 23
Drywall Panel Office Wall – Metal Frame Wall Systems
Throughout Building – Occupied Office Areas
81,525 SF No Photo Available
GSA-
HUD- 24
Ceiling Plaster (White) in Metal
Panel Frames
Stairwell Ceilings:
NW Stairwell 3 Exit on 1st Floor at Security Desk and SE
Stairwell 1 Exit at Security Desk
480 SF
Material
Description Location Quantity Photograph
GSA-
HUD- 25
Beige Seam Sealants on
Fiberglass HVAC Duct Insulation
Penthouse AHU MEC Room ducts and fan units, Sub- Basement Level fan units and associated ductwork
6,800 LF
HUD- 26
2”-4” OD
Mudded Fittings on Fiberglass Pipe Insulation
10th Floor (above ceilings on HVAC wall unit piping);
Stairwells, Penthouse MEC Rooms, Basement & Sub- Basement MEC
Rooms, Restroom piping chases
503 EA
HUD- 27
4”-6” OD
Mudded Fittings on Fiberglass Pipe Insulation
Overhead pipe runs in Penthouse MEC and Sub-Basement MEC Rooms and piping chases to upper floors
72 EA
HUD- 28
6”-8” OD
Mudded Fittings on Fiberglass Pipe Insulation
Overhead pipe runs in Penthouse MEC and Sub-Basement MEC Rooms and piping chases to upper floors
65 EA
Material
Description Location Quantity Photograph
GSA-
HUD- 29
8”-10” OD
Mudded Fittings on Fiberglass Pipe Insulation
25 Fittings in Penthouse Chiller
Plant 18 Fittings in Sub- Basement overhead pipe runs for HVAC and Water Supply
43 EA
HUD- 30
10”-12” OD
Mudded Fittings on Fiberglass Insulation Water
Supply Pipe Lines
Water Supply Line TSI – overhead piping in Basement and Sub-
Basement
12 EA
HUD- 31
10”-12” OD
Mudded Fittings on Fiberglass Insulation Storm- Water Pipe Lines
Storm-Water Drainage
– Vertical Runs in
Stairwells 5/6/7/8 and above ceilings in
22 EA
HUD- 32
Fire Doors
Throughout Building – At Stairwell Exits, Service Exits and Mechanical and
Electrical Room Areas
169 EA
Key: HSA = Homogeneous Sampling Area
APPENDIX C – NON- ASBESTOS-CONTAINING MATERIAL INVENTORY
Non-Asbestos-Containing Materials Inventory – Robert C. Weaver Building HSA Material Description Location Sample Number Results Photograph
GSA-HUD-03
4” Black Cove Base w/Brown Mastic
Freight Elevator Lobbies, Occupied
Office Areas
HUD-03A, 03B,
03C
No Asbestos Detected
No Photo Available
GSA-HUD-04
6” Gray Cove Base w/Brown Mastic Main Corridors throughout building
HUD-04A, 04B,
04C No Asbestos
Detected No Photo Available
GSA-HUD-05
Wall Plaster w/ Skim Coat
(Inner Corridor Walls on Pyrobar Block)
Main Corridors throughout building
HUD-05A, 05B,
05C
No Asbestos Detected
No Photo Available
GSA-HUD-06
Wall Plaster w/ Skim Coat
(Outer Office Walls on Wire Mesh)
Throughout Building – Office Areas
HUD-06A, 06B,
06C
No Asbestos Detected
No Photo Available
GSA-HUD-07
Ceiling Plaster on
Drywall
Main Elevator Lobby Areas
2nd to 10th Floors
HUD-07A, 07B,
07C
No Asbestos Detected
No Photo Available
GSA-HUD-08
2’x4’ Drop Ceiling
Panel (Track w/Pinhole)
Main Corridors throughout building and basement areas
HUD-08A, 08B,
08C, 08D, 08E
No Asbestos Detected
No Photo Available
GSA-HUD-09
2’x4’ Rigid Drop
Ceiling Panel Throughout Building –
Office Areas
HUD-09A, 09B,
09C No Asbestos
Detected No Photo Available
GSA-HUD-10
Off-White Seam Sealant on Fiberglass
HVAC Duct Insulation
Throughout Building - Above ceilings and HVAC mechanical equipment
HUD-10A, 10B,
10C
No Asbestos Detected
No Photo Available
GSA-HUD-11
Off-White Seam Sealant on 2”-4”
O.D.
Fiberglass Pipe
Insulation
Throughout Building - Above ceilings in overhead piping
HUD-11A, 11B,
11C
No Asbestos
GSA-HUD-12
9”x9” Floor Tile (Gray w/ Cream
Flecks) Room B-182
GSA-HUD-12A-
FT, 12B-FT,
12C-FT
No Asbestos
Black Mastic Associated with
HSA#12
Room B-182
GSA-HUD-12A-
M, 12B-M, 12C-
M
No Asbestos Detected
GSA-HUD-34
Tank Insulation (Gray Mud Over Fiberglass)
Room B-248, Tank T-1-11
GSA-HUD-34A,
34B, 34C
GSA-HUD-36
Tank Insulation (Gray Mud Over Fiberglass)
North Penthouse Mechanical Room, Tank
T-1-28
GSA-HUD-36A,
36B
GSA-HUD-37
Underlying Floor Tile (Under HSA#15)
3rd Floor Café
GSA-HUD-37A-
FT, 37B-FT,
37C-FT
Mastic Associated with Underlying Floor Tile
(Under HSA#15) 3rd Floor Café
GSA-HUD-37A-
M, 37B-M, 37C-
M
No Asbestos Detected
GSA-HUD-38
*Mastic Associated with Underlying Floor Tile (Under HSA#2)
Room SB-11
GSA-HUD-38A-
M, 38B-M, 38C-
M
No Asbestos
HSA: Homogeneous Sampling Area
*Mastic is associated with Asbestos-Containing Underlying Floor Tile (GSA-HUD-38)
APPENDIX D – LABORATORY ANALYTICAL RESULTS
September 18, 2023
Dear Judi Darnell:
Global Consulting, Inc.
Attn: Judi Darnell 6401 Golden Triangle Drive, #304 Greenbelt, MD 20770
RE: Global Consulting, Inc.
Job Number 123091258
P.O. #GSA-2023-01
GSA-2023-01; GSA Weaver Bldg 2023; 451 7th St SW; Washington DC
AmeriSci Richmond
13635 GENITO ROAD
MIDLOTHIAN, VIRGINIA 23112
TEL: 8047631200 FAX: 8047631800
Enclosed are the results for PLM asbestos analysis of the following Global Consulting, Inc. samples received at AmeriSci on Monday, September 11, 2023, for a 5 day turnaround:
GSA-HUD-12A-FT, GSA-HUD-12B-FT, GSA-HUD-12C-FT, GSA-HUD-12A-M, GSA-HUD-12B-M, GSA-HUD-12C-M, GSA-HUD-33A, GSA-HUD-33B, GSA-HUD-33C, GSA-HUD-34A, GSA-HUD-34B, GSA-HUD-34C, GSA-HUD-35A, GSA-HUD-35B, GSA-HUD-35C, GSA-HUD-36A, GSA-HUD-36B, GSA-HUD-37A-FT, GSA-HUD-37B-FT, GSA-HUD-37C-FT, GSA-HUD-37A-M, GSA-HUD-37B-M, GSA-HUD-37C-M, GSA-HUD-38A-FT, GSA-HUD-38B-FT, GSA-HUD-38C-FT, GSA-HUD-38A-M, GSA-HUD-38B-M, GSA-HUD-38C- M
The 29 samples contained in zip lock bag were shipped to AmeriSci via Fed Ex 8123 4318 3760 B 840. These samples were prepared and analyzed according to EPA PLM Method (EPA 600/R-93/116 Section 2.2). The required analytical information, analysis results, analyst signature and laboratory identification are contained in the PLM Bulk Asbestos Report. If TEM analysis was requested for selected samples the gravimetric reduction data (by Sec 2.3) and TEM Asbestos % (by Sec 2.5) are included in Table 1 along with a summary of Asbestos % by PLM for all samples analyzed.
This report relates ONLY to the sample analysis expressed as % asbestos. AmeriSci assumes no responsibility for customer supplied data such as “sample type”, "location", or “area sampled”. This report must not be used to claim product endorsement by AmeriSci, NVLAP or any agency of the U. S. Government. The National Institute of Standards and Technology accreditation requirements mandate that this report must not be reproduced, except in full, without the written approval of the laboratory.
This report may contain specific data not covered by NVLAP or ELAP accreditations, if so identified in relevant footnotes.
Glenn F. Massey
Sincerely, QA Manager | Authorized Signatory
AmeriSci appreciates this opportunity to serve your organization. Please contact us for any further assistance or with any questions.
Boston - Los Angeles - New York - Richmond
AmeriSci Richmond
13635 GENITO ROAD
MIDLOTHIAN, VIRGINIA 23112
TEL: (804) 763-1200 • FAX: (804) 763-1800
09/11/23 AmeriSci Job # 123091258 09/15/23
1 8 GSA-2023-01; GSA Weaver Bldg 2023; 451 7th St SW;
Washington DC
PLM Bulk Asbestos Report Date Received Date Examined
RE:
ofPage
P.O. # Global Consulting, Inc.
6401 Golden Triangle Drive, #304
Greenbelt, MD 20770
Attn: Judi Darnell
Asbestos Present Total % AsbestosClient No. / HGA Lab No.
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-12A-FT 123091258-01L1 NAD
9"X9" FLOOR TILE (GRAY W/CREAM FLECKS); ROOM B-18212
Green, Heterogeneous, Non-Fibrous, Carpet Mastic
Non-fibrous 100%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-12A-FT 123091258-01L2 NAD
9"X9" FLOOR TILE (GRAY W/CREAM FLECKS); ROOM B-18212
Gray, Heterogeneous, Non-Fibrous, Floor Tile
Non-fibrous 100%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-12B-FT 123091258-02L1 NAD
9"X9" FLOOR TILE (GRAY W/CREAM FLECKS); ROOM B-18212
Green, Heterogeneous, Non-Fibrous, Carpet Mastic
Non-fibrous 100%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-12B-FT 123091258-02L2 NAD
9"X9" FLOOR TILE (GRAY W/CREAM FLECKS); ROOM B-18212
Gray, Heterogeneous, Non-Fibrous, Floor Tile
Non-fibrous 100%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-12C-FT 123091258-03L1 NAD
9"X9" FLOOR TILE (GRAY W/CREAM FLECKS); ROOM B-18212
Green, Heterogeneous, Non-Fibrous, Carpet Mastic
Non-fibrous 100%
(by CVES) by Gordon T. Saleeby on 09/15/23
See Reporting notes on last page
AmeriSci Job #: 123091258 Page 2 of 8
GSA-2023-01; GSA Weaver Bldg 2023; 451 7th St SW;
Washington DC
PLM Bulk Asbestos Report Client Name: Global Consulting, Inc.
Asbestos Present Total % AsbestosClient No. / HGA Lab No.
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-12C-FT 123091258-03L2 NAD
9"X9" FLOOR TILE (GRAY W/CREAM FLECKS); ROOM B-18212
Gray, Heterogeneous, Non-Fibrous, Floor Tile
Non-fibrous 100%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-12A-M 123091258-04 NAD
BLACK MASTIC ASSOCIATED WITH HSA#12; ROOM B-18212
Black, Heterogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-12B-M 123091258-05 NAD
BLACK MASTIC ASSOCIATED WITH HSA#12; ROOM B-18212
Black, Heterogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-12C-M 123091258-06 NAD
BLACK MASTIC ASSOCIATED WITH HSA#12; ROOM B-18212
Black, Heterogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
YesGSA-HUD-33A 123091258-07 2.0%
TANK INSULATION (GRAY MUD OVER FIBERGLASS); ROOM B-248,
TANK T-1-10,END OF TANK
Gray, Heterogeneous, Non-Fibrous, Bulk Material Chrysotile 2.0% Fibrous glass 30%, Non-fibrous 68%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
GSA-HUD-33B 123091258-08 NA/PS
TANK INSULATION (GRAY MUD OVER FIBERGLASS); ROOM B-248,
TANK T-1-10,END OF TANK
Bulk Material
AmeriSci Job #: 123091258 Page 3 of 8
Washington DC
PLM Bulk Asbestos Report Client Name: Global Consulting, Inc.
Asbestos Present Total % AsbestosClient No. / HGA Lab No.
Location:
Analyst Description:
Asbestos Types:
Other Material:
GSA-HUD-33C 123091258-09 NA/PS
TANK INSULATION (GRAY MUD OVER FIBERGLASS); ROOM B-248,TANK
T-1-10, MIDDLE OF TANK
Bulk Material
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-34A 123091258-10L1 NAD
TANK INSULATION (GRAY MUD OVER FIBERGLASS); ROOM B-248,TANK
T-1-11,END OF TANK
Orange, Heterogeneous, Non-Fibrous, Wrap
Cellulose 65%, Non-fibrous 35%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-34A 123091258-10L2 NAD
TANK INSULATION (GRAY MUD OVER FIBERGLASS); ROOM B-248,TANK
T-1-11,END OF TANK
Gray, Heterogeneous, Non-Fibrous, Mud
Fibrous glass 30%, Non-fibrous 70%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-34B 123091258-11L1 NAD
TANK INSULATION (GRAY MUD OVER FIBERGLASS); ROOM B-248,
TANK T-1-11,MIDDLE OF TANK
Orange, Heterogeneous, Non-Fibrous, Wrap
Cellulose 65%, Non-fibrous 35%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-34B 123091258-11L2 NAD
TANK INSULATION (GRAY MUD OVER FIBERGLASS); ROOM B-248,
TANK T-1-11,MIDDLE OF TANK
Gray, Heterogeneous, Non-Fibrous, Mud
Fibrous glass 30%, Non-fibrous 70%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-34C 123091258-12L1 NAD
TANK INSULATION (GRAY MUD OVER FIBERGLASS); ROOM B-248,
TANK T-1-11,END OF TANK
Orange, Heterogeneous, Non-Fibrous, Wrap
Cellulose 65%, Fibrous glass 35%
(by CVES) by Gordon T. Saleeby
AmeriSci Job #: 123091258 Page 4 of 8
Washington DC
PLM Bulk Asbestos Report Client Name: Global Consulting, Inc.
Asbestos Present Total % AsbestosClient No. / HGA Lab No.
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-34C 123091258-12L2 NAD
TANK INSULATION (GRAY MUD OVER FIBERGLASS); ROOM B-248,
TANK T-1-11,END OF TANK
Gray, Heterogeneous, Non-Fibrous, Mud
Fibrous glass 30%, Non-fibrous 70%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-35A 123091258-13L1 NAD
TANK INSULATION (GRAY MUD OVER FIBERGLASS); ROOM B-248,
TANK T- 1-7, END OF TANK
Blue, Homogeneous, Fibrous, Wrap
Cellulose 65%, Non-fibrous 35%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
YesGSA-HUD-35A 123091258-13L2 2.0%
TANK INSULATION (GRAY MUD OVER FIBERGLASS); ROOM B-248,
TANK T- 1-7, END OF TANK
Gray, Heterogeneous, Non-Fibrous, Mud Chrysotile 2.0% Fibrous glass 30%, Non-fibrous 68%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-35B 123091258-14L1 NAD
TANK INSULATION (GRAY MUD OVER FIBERGLASS); ROOM B-248,
TANK T-1-7, END OF TANK
Blue, Heterogeneous, Non-Fibrous, Wrap
Cellulose 65%, Non-fibrous 35%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
GSA-HUD-35B 123091258-14L2 NA/PS
TANK INSULATION (GRAY MUD OVER FIBERGLASS); ROOM B-248,
TANK T-1-7, END OF TANK
Mud
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-35C 123091258-15L1 NAD
TANK INSULATION (GRAY MUD OVER FIBERGLASS); ROOM B-248,
TANK T-1-7, MIDDLE OF TANK
Blue, Heterogeneous, Non-Fibrous, Wrap
Cellulose 65%, Non-fibrous 35%
(by CVES) by Gordon T. Saleeby
AmeriSci Job #: 123091258 Page 5 of 8
Washington DC
PLM Bulk Asbestos Report Client Name: Global Consulting, Inc.
Asbestos Present Total % AsbestosClient No. / HGA Lab No.
Location:
Analyst Description:
Asbestos Types:
Other Material:
GSA-HUD-35C 123091258-15L2 NA/PS
TANK INSULATION (GRAY MUD OVER FIBERGLASS); ROOM B-248,
TANK T-1-7, MIDDLE OF TANK
Mud
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-36A 123091258-16L1 NAD
TANK INSULATION (GRAY MUD OVER FIBERGLASS); NORTH
PENTHOUSE MECHANICAL ROOM, TANK T-1-28, END OF TANK
Orange, Heterogeneous, Non-Fibrous, Wrap
Cellulose 65%, Non-fibrous 35%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-36A 123091258-16L2 NAD
TANK INSULATION (GRAY MUD OVER FIBERGLASS); NORTH
PENTHOUSE MECHANICAL ROOM, TANK T-1-28, END OF TANK
Gray, Homogeneous, Fibrous, Mud
Fibrous glass 30%, Non-fibrous 70%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-36B 123091258-17L1 NAD
TANK INSULATION (GRAY MUD OVER FIBERGLASS); NORTH
PENTHOUSE MECHANICAL ROOM, TANK T-1-28, END OF TANK
Blue, Heterogeneous, Non-Fibrous, Wrap
Cellulose 65%, Non-fibrous 35%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-36B 123091258-17L2 NAD
TANK INSULATION (GRAY MUD OVER FIBERGLASS); NORTH
PENTHOUSE MECHANICAL ROOM, TANK T-1-28, END OF TANK
Gray, Heterogeneous, Non-Fibrous, Mud
Fibrous glass 30%, Non-fibrous 70%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-37A-FT 123091258-18 NAD
UNDERLYING FLOOR TILE (UNDER HSA#15); 3RD FLOOR CAFE37
Black, Heterogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100%
(by CVES) by Gordon T. Saleeby
AmeriSci Job #: 123091258 Page 6 of 8
Washington DC
PLM Bulk Asbestos Report Client Name: Global Consulting, Inc.
Asbestos Present Total % AsbestosClient No. / HGA Lab No.
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-37B-FT 123091258-19 NAD
UNDERLYING FLOOR TILE (UNDER HSA#15); 3RD FLOOR CAFE37
Black, Heterogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-37C-FT 123091258-20 NAD
UNDERLYING FLOOR TILE (UNDER HSA#15); 3RD FLOOR CAFE37
Black, Heterogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-37A-M 123091258-21 NAD
MASTIC ASSOCIATED WITH UNDERLYING FLOOR TILE (UNDER
HSA#15); 3RD FLOOR CAFE
Clear, Heterogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-37B-M 123091258-22 NAD
MASTIC ASSOCIATED WITH UNDERLYING FLOOR TILE (UNDER
HSA#15); 3RD FLOOR CAFE
Dark, Heterogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-37C-M 123091258-23 NAD
MASTIC ASSOCIATED WITH UNDERLYING FLOOR TILE (UNDER
HSA#15); 3RD FLOOR CAFE
Clear, Heterogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
YesGSA-HUD-38A-FT 123091258-24 2.0%
UNDERLYING FLOOR TILE (UNDER HSA#2); ROOM SB-1138
Drk. Gray, Heterogeneous, Non-Fibrous, Bulk Material Chrysotile 2.0% Non-fibrous 98%
(by CVES) by Gordon T. Saleeby
AmeriSci Job #: 123091258 Page 7 of 8
Washington DC
PLM Bulk Asbestos Report Client Name: Global Consulting, Inc.
Asbestos Present Total % AsbestosClient No. / HGA Lab No.
Location:
Analyst Description:
Asbestos Types:
Other Material:
GSA-HUD-38B-FT 123091258-25 NA/PS
UNDERLYING FLOOR TILE (UNDER HSA#2); ROOM SB-1138
Bulk Material
Location:
Analyst Description:
Asbestos Types:
Other Material:
GSA-HUD-38C-FT 123091258-26 NA/PS
UNDERLYING FLOOR TILE (UNDER HSA#2); ROOM SB-1138
Bulk Material
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-38A-M 123091258-27 NAD
MASTIC ASSOCIATED WITH UNDERLYING FLOOR TILE (UNDER HSA#2);
ROOM SB-11
Black, Heterogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-38B-M 123091258-28 NAD
MASTIC ASSOCIATED WITH UNDERLYING FLOOR TILE (UNDER HSA#2);
ROOM SB-11
Black, Heterogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100%
(by CVES) by Gordon T. Saleeby on 09/15/23
Location:
Analyst Description:
Asbestos Types:
Other Material:
NoGSA-HUD-38C-M 123091258-29 NAD
MASTIC ASSOCIATED WITH UNDERLYING FLOOR TILE (UNDER HSA#2);
ROOM SB-11
Black, Heterogeneous, Non-Fibrous, Bulk Material
Non-fibrous 100%
(by CVES) by Gordon T. Saleeby
AmeriSci Job #: 123091258 Page 8 of 8
Washington DC
PLM Bulk Asbestos Report Client Name: Global Consulting, Inc.
Reporting Notes:
*NAD = no asbestos detected, Detection Limit <1%, Reporting Limits: CVES = 1%, 400 Pt Ct = 0.25%, 1000 Pt Ct = 0.1%; "Present" or NVA = "No Visible Asbestos" are observations made during a qualitative analysis; NA = not analyzed; NA/PS = not analyzed / positive stop; PLM Bulk Asbestos Analysis using Olympus, Model BH-2 microscope, Serial #237649, by EPA 600/R-93/116 per 40 CFR 763 (NVLAP Lab Code 101904-0) and ELAP PLM Analysis Protocol 198.1 for New York friable samples which includes quantitation of any vermiculite observed (198.6 for NOB samples) or EPA 400 pt ct by EPA 600/M4-82-020 (NYSDOH ELAP Lab # 10984); CA ELAP Lab # 2508; Note: PLM is not consistently reliable in detecting asbestos in floor coverings and similar NOB materials. NAD or Trace results by PLM are inconclusive, TEM is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos-containing in New York State (also see EPA Advisory for floor tile, FR 59, 146, 38970, 8/1/94). NIST Accreditation requirements mandate that this report must not be reproduced except in full without the approval of the laboratory. This PLM report relates ONLY to the items tested.
Analyzed by: Gordon T. Saleeby Date: 9/15/2023
Reviewed by: Gordon T. Saleeby
LAB #173190
Lab Sample ID Lab Notes mastic 11612552PLM_1 tile1612552PLM_36 mastic 21612552PLM_37 mastic 11612552PLM_2 tile1612552PLM_38 mastic 21612552PLM_39
1612552PLM_3
tile1612552PLM_41 mastic 21612552PLM_42 tile1612552PLM_4 mastic1612552PLM_43 tile1612552PLM_5 mastic1612552PLM_44 tile 11612552PLM_6 mastic 11612552PLM_45 tile 21612552PLM_46 mastic 21612552PLM_47 cove base1612552PLM_7 mastic1612552PLM_48 cove base1612552PLM_8 mastic 11612552PLM_49 mastic 21612552PLM_50 cove base1612552PLM_9 mastic 11612552PLM_51 mastic 21612552PLM_52 cove base1612552PLM_10 mastic1612552PLM_53 cove base1612552PLM_11 mastic 11612552PLM_54 mastic 21612552PLM_55 cove base1612552PLM_12 mastic 11612552PLM_56 mastic 21612552PLM_57 skim1612552PLM_13 plaster1612552PLM_58 skim1612552PLM_14 plaster1612552PLM_59 skim1612552PLM_15 plaster1612552PLM_60 skim1612552PLM_16 plaster1612552PLM_61 skim1612552PLM_17 plaster1612552PLM_62 skim1612552PLM_18 plaster1612552PLM_63 drywall1612552PLM_19 skim1612552PLM_64 drywall1612552PLM_20 skim1612552PLM_65 drywall1612552PLM_21 skim1612552PLM_66
1612552PLM_22
1612552PLM_23
1612552PLM_24
1612552PLM_25
1612552PLM_26
1612552PLM_27
1612552PLM_28
1612552PLM_29
1612552PLM_30
1612552PLM_31
1612552PLM_32
1612552PLM_33
1612552PLM_34
1612552PLM_35
APPENDIX E – GSA ASBESTOS ASSESSMENT FORMS
Asbestos Assessment Data Form
Bldg. Name: Robert C. Weaver Building Assessment Date:
9/6/2023
Address: 451 7th St. SW, Washington, DC
GSA Bldg. No: DC0092ZZ Amounts
(SF/LF/CF):
610,830 SF
Asbestos Inspector: John Fuentes, Sameera Meegoda, Daniel Wooddell
Homogeneous Sampling Area #: GSA-HUD- 01
(Assign HSA Number)
HSA Description: 12”x12” Floor Tile (Gray with Light Gray Streaks) and Black Mastic
Location(s) of HSA in Bldg.: Throughout building in Main Corridors and under carpeting in Occupied Office Areas
(Include Functional Space)
HSA Category Damage Accessibility
Surfacing Material Significant High
Thermal Systems Insulation Minor Medium
X Miscellaneous Material X None X Low
Air Plenum: Yes X No
Friability Traffic Vibration Potential for Air Erosion
Yes High High High
X No Medium Medium Medium
X Low X Low X Low
Comments: ACM identified on prior survey. Floor Tile 2% Chrysotile, Mastic 5% Chrysotile
AHERA
Classification:
5 1. Damaged or significantly damaged TSI ACBM
2. Damaged friable surfacing ACBM
3. Significantly damaged friable surfacing ACBM
4. Damaged and significantly damaged friable miscellaneous ACBM
5. ACBM with potential for damage
Sample Number Sample Location Result
HUD-01A Room 10250 Floor Tile: 2% Chrysotile
Mastic: 5% Chrysotile HUD-01B Room 10258 Floor Tile: 2% Chrysotile
Mastic: 5% Chrysotile HUD-01C Room 9154 Floor Tile: 2% Chrysotile
Mastic: 5% Chrysotile
(Include percent and type of asbestos in result, e.g. 50% Chrysotile)
NOTE: Use one form per homogeneous sampling area. Consult 40 CFR Part 763 for sampling and analytical protocols and definitions.
Date:
9/6/2023
Address: 451 7th St. SW, Washington, DC
GSA Bldg. No: DC0092ZZ Amounts
(SF/LF/CF):
5,515 SF
Homogeneous Sampling Area #: GSA-HUD- 02
HSA Description: 12”x12” Floor Tile (Black with Gray Flecks) and Black Mastic
Location(s) of HSA in Bldg.: Freight Elevator Lobbies, Suite 1100, Layer 2 in 3rd Floor Café, Basement Level Custodial Break Room
Thermal Systems Insulation X Minor Medium
X Miscellaneous Material None X Low
Comments: ACM identified on prior survey. Floor Tile 2% Chrysotile, Mastic 5% Chrysotile.
5 1. Damaged or significantly damaged TSI ACBM
2. Damaged friable surfacing ACBM
3. Significantly damaged friable surfacing ACBM
4. Damaged and significantly damaged friable miscellaneous ACBM
5. ACBM with potential for damage
HUD-02A 10th Floor North Freight Elevator Lobby Mastic: 5% Chrysotile HUD-02B Room 9231 / South Freight Elevator Lobby Mastic: 5% Chrysotile HUD-02C Room 1100 Mastic: 5% Chrysotile
NOTE: Use one form per homogeneous sampling area. Consult 40 CFR Part 763 for sampling and analytical protocols and definitions.
Date:
9/6/2023
Address: 451 7th St. SW, Washington, DC
GSA Bldg. No: DC0092ZZ Amounts
(SF/LF/CF):
1,200 SF
Homogeneous Sampling Area #: GSA-HUD- 02.1
HSA Description: Gray Floor Tile and Black Mastic
Location(s) of HSA in Bldg.: Second Layer of tile in Suite 1100
Comments: ACM identified on prior survey. Floor Tile 2% Chrysotile, Mastic 5% Chrysotile
5 1. Damaged or significantly damaged TSI ACBM
2. Damaged friable surfacing ACBM
3. Significantly damaged friable surfacing ACBM
4. Damaged and significantly damaged friable miscellaneous ACBM
5. ACBM with potential for damage
HUD-02C Room 1100 Floor Tile: 2% Chrysotile
Mastic: 5% Chrysotile
NOTE: Use one form per homogeneous sampling area. Consult 40 CFR Part 763 for sampling and analytical protocols and definitions
Date:
9/6/2023
Address: 451 7th St. SW, Washington, DC
GSA Bldg. No: DC0092ZZ Amounts
(SF/LF/CF):
230 SF
Homogeneous Sampling Area #: GSA-HUD- 33
HSA Description: Tank Insulation, Tank T-1-10
Location(s) of HSA in Bldg.: Room B-248
Surfacing Material Significant X High
X Thermal Systems Insulation X Minor Medium
Miscellaneous Material None Low
X Yes High High High
No Medium Medium Medium
Comments:
1 1. Damaged or significantly damaged TSI ACBM
2. Damaged friable surfacing ACBM
3. Significantly damaged friable surfacing ACBM
4. Damaged and significantly damaged friable miscellaneous ACBM
5. ACBM with potential for damage
GSA-HUD-33A Room B-248, Tank T-1-10 2% Chrysotile GSA-HUD-33B Room B-248, Tank T-1-10 Not Analyzed - Positive Stop GSA-HUD-33C Room B-248, Tank T-1-10 Not Analyzed – Positive Stop
NOTE: Use one form per homogeneous sampling area. Consult 40 CFR Part 763 for sampling and analytical protocols and definitions.
Date:
9/6/2023
Address: 451 7th St. SW, Washington, DC
GSA Bldg. No: DC0092ZZ Amounts
(SF/LF/CF):
370 SF
Homogeneous Sampling Area #: GSA-HUD-35
HSA Description: Tank Insulation, Tank T-1-7
Location(s) of HSA in Bldg.: Room B-248
Surfacing Material Significant X High
X Thermal Systems Insulation Minor Medium
Miscellaneous Material X None Low
5 1. Damaged or significantly damaged TSI ACBM
2. Damaged friable surfacing ACBM
3. Significantly damaged friable surfacing ACBM
4. Damaged and significantly damaged friable miscellaneous ACBM
5. ACBM with potential for damage
GSA-HUD-35A Room B-248, Tank T-1-7 2% Chrysotile
GSA-HUD-35B Room B-248, Tank T-1-7 Not Analyzed – Positive Stop
GSA-HUD-35C Room B-248, Tank T-1-7 Not Analyzed – Positive Stop
NOTE: Use one form per homogeneous sampling area. Consult 40 CFR Part 763 for sampling and analytical protocols and definitions.
Date:
9/6/2023
Address: 451 7th St. SW, Washington, DC
GSA Bldg. No: DC0092ZZ Amounts
(SF/LF/CF):
520 SF
Homogeneous Sampling Area #: GSA-HUD-38
HSA Description: Underlying Floor Tile (Under HSA#2)
Location(s) of HSA in Bldg.: Room SB-11
5 1. Damaged or significantly damaged TSI ACBM
2. Damaged friable surfacing ACBM
3. Significantly damaged friable surfacing ACBM
4. Damaged and significantly damaged friable miscellaneous ACBM
5. ACBM with potential for damage
GSA-HUD-38A-FT Room SB-11 2% Chrysotile GSA-HUD-38B-FT Room SB-11 Not Analyzed – Positive Stop GSA-HUD-38C-FT Room SB-11 Not Analyzed – Positive Stop
NOTE: Use one form per homogeneous sampling area. Consult 40 CFR Part 763 for sampling and analytical protocols and definitions.
Date:
9/6/2023
Address: 451 7th St. SW, Washington, DC
GSA Bldg. No: DC0092ZZ Amounts
(SF/LF/CF):
2,300 SF
Homogeneous Sampling Area #: GSA-HUD- 13
HSA Description: 12”x12” Floor Tile (Dark Grey with Light Grey Flecks) and Black Mastic
Location(s) of HSA in Bldg.: Replacement flooring throughout Main Corridors of building and in Basement 200 Corridor
5 1. Damaged or significantly damaged TSI ACBM
2. Damaged friable surfacing ACBM
3. Significantly damaged friable surfacing ACBM
4. Damaged and significantly damaged friable miscellaneous ACBM
5. ACBM with potential for damage
NOTE: Use one form per homogeneous sampling area. Consult 40 CFR Part 763 for sampling and analytical protocols and definitions.
Date:
9/6/2023
Address: 451 7th St. SW, Washington, DC
GSA Bldg. No: DC0092ZZ Amounts
(SF/LF/CF):
600 SF
Homogeneous Sampling Area #: GSA-HUD- 14
HSA Description: 12”x12” Floor Tile (Blue with Light and Dark Blue Flecks) and Black Mastic
Location(s) of HSA in Bldg.: Room 5133 (Copy Room)
Comments: Material is presumed to be asbestos-containing
5 1. Damaged or significantly damaged TSI ACBM
2. Damaged friable surfacing ACBM
3. Significantly damaged friable surfacing ACBM
4. Damaged and significantly damaged friable miscellaneous ACBM
5. ACBM with potential for damage
NOTE: Use one form per homogeneous sampling area. Consult 40 CFR Part 763 for sampling and analytical protocols and definitions.
Date:
9/6/2023
Address: 451 7th St. SW, Washington, DC
GSA Bldg. No: DC0092ZZ Amounts
(SF/LF/CF):
1,375 SF
Homogeneous Sampling Area #: GSA-HUD- 15
HSA Description: 12”x12” Floor Tile (Tan with Beige Flecks) and Yellow/Tan Adhesives
Location(s) of HSA in Bldg.: 3rd Floor Café with Dining and Restaurant Areas
5 1. Damaged or significantly damaged TSI ACBM
2. Damaged friable surfacing ACBM
3. Significantly damaged friable surfacing ACBM
4. Damaged and significantly damaged friable miscellaneous ACBM
5. ACBM with potential for damage
NOTE: Use one form per homogeneous sampling area. Consult 40 CFR Part 763 for sampling and analytical protocols and definitions.
Date:
9/6/2023
Address: 451 7th St. SW, Washington, DC
GSA Bldg. No: DC0092ZZ Amounts
(SF/LF/CF):
288 SF
Homogeneous Sampling Area #: GSA-HUD- 16
HSA Description: 12”x12” Floor Tile (Cream with Brown Flecks) and Black Mastic
Location(s) of HSA in Bldg.: Room B-155 (Vending/Snack Room)
5 1. Damaged or significantly damaged TSI ACBM
2. Damaged friable surfacing ACBM
3. Significantly damaged friable surfacing ACBM
4. Damaged and significantly damaged friable miscellaneous ACBM
5. ACBM with potential for damage
NOTE: Use one form per homogeneous sampling area. Consult 40 CFR Part 763 for sampling and analytical protocols and definitions.
Date:
9/6/2023
Address: 451 7th St. SW, Washington, DC
GSA Bldg. No: DC0092ZZ Amounts
(SF/LF/CF):
185 SF
Homogeneous Sampling Area #: GSA-HUD- 17
HSA Description: 12”x12” Floor Tile (Grey with Light & Dark Grey Flecks) and Yellow/Brown Adhesive
Location(s) of HSA in Bldg.: Conference Room 10239 rear AV Room
5 1. Damaged or significantly damaged TSI ACBM
2. Damaged friable surfacing ACBM
3. Significantly damaged friable surfacing ACBM
4. Damaged and significantly damaged friable miscellaneous ACBM
5. ACBM with potential for damage
NOTE: Use one form per homogeneous sampling area. Consult 40 CFR Part 763 for sampling and analytical protocols and definitions.
Date:
9/6/2023
Address: 451 7th St. SW, Washington, DC
GSA Bldg. No: DC0092ZZ Amounts
(SF/LF/CF):
600 SF
Homogeneous Sampling Area #: GSA-HUD- 18
HSA Description: Residual Black Mastic under Carpeting
Location(s) of HSA in Bldg.: Basement Room B- 160
5 1. Damaged or significantly damaged TSI ACBM
2. Damaged friable surfacing ACBM
3. Significantly damaged friable surfacing ACBM
4. Damaged and significantly damaged friable miscellaneous ACBM
5. ACBM with potential for damage
NOTE: Use one form per homogeneous sampling area. Consult 40 CFR Part 763 for sampling and analytical protocols and definitions.
Date:
9/6/2023
Address: 451 7th St. SW, Washington, DC
GSA Bldg. No: DC0092ZZ Amounts
(SF/LF/CF):
5,415 SF
Homogeneous Sampling Area #: GSA-HUD- 19
HSA Description: 1’x2’ Tan-Brown Stone Floor Tile
Location(s) of HSA in Bldg.: 1st Floor Main Lobby and Corridors, Main 1st Floor Cafeteria central walkway
5 1. Damaged or significantly damaged TSI ACBM
2. Damaged friable surfacing ACBM
3. Significantly damaged friable surfacing ACBM
4. Damaged and significantly damaged friable miscellaneous ACBM
5. ACBM with potential for damage
NOTE: Use one form per homogeneous sampling area. Consult 40 CFR Part 763 for sampling and analytical protocols and definitions.
Date:
9/6/2023
Address: 451 7th St. SW, Washington, DC
GSA Bldg. No: DC0092ZZ Amounts
(SF/LF/CF):
5,200 SF
Homogeneous Sampling Area #: GSA-HUD- 20
HSA Description: 4” Brown Cove Base w/Yellow-Tan Adhesive
Location(s) of HSA in Bldg.: Throughout Building – Occupied Office Areas
5 1. Damaged or significantly damaged TSI ACBM
2. Damaged friable surfacing ACBM
3. Significantly damaged friable surfacing ACBM
4. Damaged and significantly damaged friable miscellaneous ACBM
5. ACBM with potential for damage
NOTE: Use one form per homogeneous sampling area. Consult 40 CFR Part 763 for sampling and analytical protocols and definitions.
Date:
9/6/2023
Address: 451 7th St. SW, Washington, DC
GSA Bldg. No: DC0092ZZ Amounts
(SF/LF/CF):
12,885 LF
Homogeneous Sampling Area #: GSA-HUD-21
HSA Description: 4” Black Cove Base w/Yellow-Tan Adhesive
5 1. Damaged or significantly damaged TSI ACBM
2. Damaged friable surfacing ACBM
3. Significantly damaged friable surfacing ACBM
4. Damaged and significantly damaged friable miscellaneous ACBM
5. ACBM with potential for damage
NOTE: Use one form per homogeneous sampling area. Consult 40 CFR Part 763 for sampling and analytical protocols and definitions.
Date:
9/6/2023
Address: 451 7th St. SW, Washington, DC
GSA Bldg. No: DC0092ZZ Amounts
(SF/LF/CF):
3,800 LF
Homogeneous Sampling Area #: GSA-HUD- 22
HSA Description: 4” Grey Cove Base w/Dark Brown Mastic
Location(s) of HSA in Bldg.: Freight Elevator Lobbies, occupied offices and inner hallways
5 1. Damaged or significantly damaged TSI ACBM
2. Damaged friable surfacing ACBM
3. Significantly damaged friable surfacing ACBM
4. Damaged and significantly damaged friable miscellaneous ACBM
5. ACBM with potential for damage
NOTE: Use one form per homogeneous sampling area. Consult 40 CFR Part 763 for sampling and analytical protocols and definitions.
Date:
9/6/2023
Address: 451 7th St. SW, Washington, DC
GSA Bldg. No: DC0092ZZ Amounts
(SF/LF/CF):
81,525
Homogeneous Sampling Area #: GSA-HUD- 23
HSA Description: Drywall Panel Office Wall – Metal Frame Wall Systems
5 1. Damaged or significantly damaged TSI ACBM
2. Damaged friable surfacing ACBM
3. Significantly damaged friable surfacing ACBM
4. Damaged and significantly damaged friable miscellaneous ACBM
5. ACBM with potential for damage
NOTE: Use one form per homogeneous sampling area. Consult 40 CFR Part 763 for sampling and analytical protocols and definitions.
Date:
9/6/2023
Address: 451 7th St. SW, Washington, DC
GSA Bldg. No: DC0092ZZ Amounts
(SF/LF/CF):
480 SF
Homogeneous Sampling Area #: GSA-HUD- 24
HSA Description: Ceiling Plaster (White) in Metal Panel Frames
Location(s) of HSA in Bldg.: Stairwell Ceilings: NW Stairwell 3 Exit on 1st Floor at Security Desk and SE Stairwell 1 Exit at Security Desk
X Surfacing Material Significant High
Miscellaneous Material X None X Low
5 1. Damaged or significantly damaged TSI ACBM
2. Damaged friable surfacing ACBM
3. Significantly damaged friable surfacing ACBM
4. Damaged and significantly damaged friable miscellaneous ACBM
5. ACBM with potential for damage
NOTE: Use one form per homogeneous sampling area. Consult 40 CFR Part 763 for sampling and analytical protocols and definitions.
Date:
9/6/2023
Address: 451 7th St. SW, Washington, DC
GSA Bldg. No: DC0092ZZ Amounts
(SF/LF/CF):
6,800 LF
Homogeneous Sampling Area #: GSA-HUD- 25
HSA Description: Beige Seam Sealants on Fiberglass HVAC Duct Insulation
Location(s) of HSA in Bldg.: Penthouse AHU MEC Room ducts and fan units, Sub- Basement Level fan units and associated ductwork
5 1. Damaged or significantly damaged TSI ACBM
2. Damaged friable surfacing ACBM
3. Significantly damaged friable surfacing ACBM
4. Damaged and significantly damaged friable miscellaneous ACBM
5. ACBM with potential for damage
NOTE: Use one form…