This document contains room data sheets for the Coralville Lake Ranger Building and Admin Repairs project. The sheets provide requirements for various room types including open bays, private offices, conference rooms, restrooms, mechanical rooms, and public spaces. Room details cover finishes, fixtures, furniture, HVAC, electrical, data/communications needs, and other specifications. Requirements are specified for items such as flooring, ceilings, lighting controls, receptacles, networks, security, and fire protection. The project involves renovations and repairs to support operations and management of Coralville Lake.
View the file
Other files
Show all 44
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION 01 10 00.00 20
STATEMENT OF WORK – PROJECT SPECIFIC REQUIREMENTS
APPENDIX 6 – ROOM DATA SHEETS
25 October 2023
Room Name: Open Bay - Open Floor Workspace/Equipment Bays Area (Net): 6,000 Sq. Ft. Min.
Room Number: T.B.D.
Capacity / Personnel: -
Floors: Sealed Concrete Ceiling: Exposed - Painted (Dryfall) Walls: Heavy Duty, High Impact Resistive, Water Resistant Material eg
CMU block or concrete Doors: HM Doors w/ HM Frames Millwork/Casework: - Notes/Special Requirements: -
FF&E (Furniture, Fixtures, and Equipment) -
Notes/Special Requirements: -
Heating Required: Y Heating Temperature: 68° F Occupied/ 55° F Setback Air Conditioning Required: N Cooling Temperature: - Ventilation: Per ASHRAE 62.1 Notes/Special Requirements: Hydronic in-floor heating should be provided. Where in-floor heating cannot provide sufficient heat or rebound, utilize overhead infrared radiant heating or temporarily adjust delivery temperature of make-up air unit. In-floor heating should be coordinated with concrete slab on grade.
Fixtures: Emergency Eyewash and Shower Notes/Special Requirements: OSHA requires an emergency eyewash and showers where an employee's eyes or body could be exposed to injurious corrosive materials. Ready access to an emergency eyewash and shower shall be evaluated with respect to building design.
120VAC Duplex Receptacles QTY: 20 minimum -- Provide GFCI duplex receptacles every 10 Feet along walls; provide 3 ceiling-mounted, 120VAC, 20 Amp 100 Ft. retractible cord reels. Provide GFCI receptacle adjacent to each panelboard and loadcenter grouping. Provide dedicated duplex for a drinking fountain in location by designer.
120VAC Quadplex Receptacles QTY: 4 minimum -- Provide one additional quadplex at workbench.
Also see dedicated electrical equipment.
208VAC Special Receptacles Lighting Control Manual On/ Off, CCTV Monitors Wall 120V Receptacles N/A Video Monitor Wall 120V Receptacles N/A Duress System Monitor & Control N/A
Telephone: N/A Ceiling Mounted Speaker Connections QTY: 3 CCTV Monitors Circuit Outlet N/A HDMI Connector N/A
LAN: QTY: 1 - TYPE: RJ45
CATV/TV: N/A
Networks: NIPR, Commercial Notes/Special Requirements:
Equipment: - Notes/Special Requirements: -
Perimeter STC: 45 Space NC: 30-35 Notes/Special Requirements: -
Equipment (GFGI): - Equipment (CFCI): - Notes/Special Requirements: -
Card Access: N/A Intrusion Detection: Y Notes/Special Requirements: -
Fire Suppression: Y Fire Alarm: Y Hazard Classification: LH Notes/Special Requirements: -
FIRE PROTECTION
OTHER COMMENTS
3 automatic insulated garage doors that 10' H x 10'W, 2 automatic insulated garages doors 14'H x 10'W , 1 automatic insulated garage door that 10' H x 10' W for EV
PLUMBING
AUDIO/VISUAL
ACOUSTICAL
EQUIPMENT
SECURITY
ELECTRICAL
COMMUNICATIONS/NETWORK
HVAC
ROOM DATA SHEET
BUILDING: Coralville - Ranger Garage / Storage Building
ARCHITECTURAL
Finishes:
INTERIORS
Room Name: Open Bay - Wash Bay Area (Net): 1,200 Sq. Ft.
Room Number: T.B.D.
Capacity / Personnel: -
Floors: Sealed Concrete Ceiling: Exposed - Painted (Dryfall) Walls: Heavy Duty, High Impact Resistive, Water Resistant Material
Doors: HM Doors w/ HM Frames Millwork/Casework: - Notes/Special Requirements: -
FF&E (Furniture, Fixtures, and Equipment) -
Notes/Special Requirements: -
Heating Required: Y Heating Temperature: 68° F Occupied/ 55° F Setback Air Conditioning Required: N Cooling Temperature: - Ventilation: Per ASHRAE 62.1 Notes/Special Requirements: Hydronic in-floor heating should be provided. Where in-floor heating cannot provide sufficient heat or rebound, utilize overhead infrared radiant heating or temporarily adjust delivery temperature of make-up air unit. In-floor heating should be coordinated with concrete slab on grade.
Fixtures: Floor drains w/ Sand Traps and oil water separator.
Notes/Special Requirements: Sand traps and oil water separator to be accessible for routine cleaning.
120VAC Duplex Receptacles QTY: 2 -- Coordinate locations 120VAC Quadplex Receptacles N/A 208VAC Special Receptacles QTY: 2 -- Provide one 50A, 208VAC on each garage door wall of wash bay. Coordinate loads and locations of each.
Lighting Control Manual On/Vacancy Off, Dimmable.
CCTV Monitors Wall 120V Receptacles N/A Video Monitor Wall 120V Receptacles N/A Duress System Monitor & Control N/A
Telephone: N/A Ceiling Mounted Speaker Connections N/A CCTV Monitors Circuit Outlet N/A HDMI Connector N/A
LAN: N/A
CATV/TV: N/A
Networks: N/A Notes/Special Requirements: N/A
Equipment: - Notes/Special Requirements: -
Perimeter STC: 45 Space NC: 30-35 Notes/Special Requirements: -
Equipment (GFGI): - Equipment (CFCI): - Notes/Special Requirements: -
Card Access: N/A Intrusion Detection: Y Notes/Special Requirements: -
Fire Suppression: Y Fire Alarm: Y Hazard Classification: LH Notes/Special Requirements: -
HVAC
ROOM DATA SHEET
BUILDING: Coralville Lake - Storage Building
ARCHITECTURAL
Finishes:
INTERIORS
FIRE PROTECTION
OTHER COMMENTS
Provide room for a minimum dimension of 50'L x 24'W of parking space and have the ability to be isolated from the rest of the Open Bay Area with insulated automatic overhead door with a minimum dimension of 12'W x 14'H.
Locate along exterior wall.
PLUMBING
AUDIO/VISUAL
ACOUSTICAL
EQUIPMENT
SECURITY
ELECTRICAL
COMMUNICATIONS/NETWORK
Room Name: Operations Project Manager (Private Office) Area (Net): 140 Sq. Ft. Min.
Room Number: T.B.D.
Capacity / Personnel: 1
Floors: Modular Carpet Ceiling: Acoustical Ceiling Tile and Grid Walls: Gypsum Board - Painted Doors: Wood w/ Hollow Metal Frame Millwork/Casework: - Notes/Special Requirements: Manually Operated Roller Shade - Light Filtering
FF&E (Furniture, Fixtures, and Equipment) 72"W Powered Stand-Up Desk with 5 drawers, Executive Desk, Executive Desk Chair, 48"W x 72"T Bookshelf, Meeting Table w/ Chairs (4-6 visitors), 2 Drawer 32"W x 71"T Armoire w/ Filing Cabinets, 18" x 72" Credenza, Chair Mat, Standing Mat
Notes/Special Requirements: -
Heating Required: Y Heating Temperature: 68° F Occupied/ 55° F Setback Air Conditioning Required: Y Cooling Temperature: 78° F/ 50% RH Occupied/ Ambient Setback Ventilation: Per ASHRAE 62.1 Notes/Special Requirements: -
Fixtures: N/A Notes/Special Requirements: -
120VAC Duplex Receptacles QTY: 5 120VAC Quadplex Receptacles QTY: 2 208VAC Special Receptacles N/A Lighting Control Manual On/Vacancy Off, Dimmable CCTV Monitors Wall 120V Receptacles QTY: 1 Video Monitor Wall 120V Receptacles QTY: 1 Duress System Control/Monitor N/A
Telephone: N/A Ceiling Mounted Speaker Connections QTY: 1 CCTV Monitors Circuit Outlet QTY: 1 HDMI Connector QTY: 2
LAN: QTY: 3 - TYPE: RJ45
CATV/TV: QTY: 1
Networks: NIPR, Commercial Notes/Special Requirements: Place LAN connections per furniture layout
Equipment: Wall Mounted CCTV Monitor, Wall Mounted Conference Monitor with HDMI Connection
Notes/Special Requirements: Provide HDMI connection for Conference Monitor from occupant computer at desk. Provide Monitor mounting brackets and power in wall behind screens.
Perimeter STC: 45 Space NC: 30-35 Notes/Special Requirements: -
Equipment (GFGI): Wall Mounted Monitors Equipment (CFCI): - Notes/Special Requirements: Provide blocking as required for Wall Mounted TV
Card Access: N/A Intrusion Detection: Y Notes/Special Requirements: -
Fire Suppression: Y Fire Alarm: Y Hazard Classification: LH Notes/Special Requirements: -
FIRE PROTECTION
OTHER COMMENTS
Locate in general vicinity of Lake Manager, Program Analyst, Administrative Officer, and Facility Services Assistant offices. Locate away from Lobby/Reception Area.
PLUMBING
AUDIO/VISUAL
ACOUSTICAL
EQUIPMENT
SECURITY
ELECTRICAL
COMMUNICATIONS/NETWORK
HVAC
ROOM DATA SHEET
BUILDING: Coralville - Administration Building / Visitor Center
ARCHITECTURAL
Room Name: Lake Manager (Private Office) Area (Net): 140 Sq. Ft. Min.
Room Number: T.B.D.
Capacity / Personnel: 1
Floors: Modular Carpet Ceiling: Acoustical Ceiling Tile and Grid Walls: Gypsum Board - Painted Doors: Wood w/ Hollow Metal Frame Millwork/Casework: - Notes/Special Requirements: Manually Operated Roller Shade - Light Filtering
FF&E (Furniture, Fixtures, and Equipment) 72"W Powered Stand-Up Desk with 5 drawers, Executive Desk, Executive Desk Chair, 48"W x 72"T Bookshelf, Meeting Table w/ Chairs (4-6 visitors), 2 Drawer 32"W x 71"T Armoire w/ Filing Cabinets, 18" x 72" Credenza, Chair Mat, Standing Mat
Notes/Special Requirements: -
Heating Required: Y Heating Temperature: 68° F Occupied/ 55° F Setback Air Conditioning Required: Y Cooling Temperature: 78° F/ 50% RH Occupied/ Ambient Setback Ventilation: Per ASHRAE 62.1 Notes/Special Requirements: -
Fixtures: N/A Notes/Special Requirements: -
120VAC Duplex Receptacles QTY: 5 120VAC Quadplex Receptacles QTY: 2 208VAC Special Receptacles N/A Lighting Control Manual On/Vacancy Off, Dimmable CCTV Monitors Wall 120V Receptacles QTY: 1 Video Monitor Wall 120V Receptacles QTY: 1 Duress System Control/Monitor N/A
Telephone: N/A Ceiling Mounted Speaker Connections QTY: 1 CCTV Monitors Circuit Outlet QTY: 1 HDMI Connector QTY: 2
LAN: QTY: 3 - TYPE: RJ45
CATV/TV: QTY: 1
Networks: NIPR, Commercial Notes/Special Requirements: Place LAN connections per furniture layout
Equipment: Provide connection for govt owned Wall Mounted CCTV Monitor, Wall Mounted Conference Monitor with HDMI Connection
Notes/Special Requirements: Provide HDMI connection for Conference Monitor from occupant computer at desk. Provide Monitor mounting brackets and power in wall behind screens.
Perimeter STC: 45 Space NC: 30-35 Notes/Special Requirements: -
Equipment (GFGI): Wall Mounted Monitors Equipment (CFCI): - Notes/Special Requirements: Provide blocking as required for Wall Mounted TV
Card Access: N/A Intrusion Detection: Y Notes/Special Requirements: -
Fire Suppression: Y Fire Alarm: Y Hazard Classification: LH Notes/Special Requirements: -
SECURITY
FIRE PROTECTION
OTHER COMMENTS
Locate in general vicinity of Lake Manager, Program Analyst, Administrative Officer, and Facility Services Assistant offices. Locate away from Lobby/Reception Area.
PLUMBING
ELECTRICAL
COMMUNICATIONS/NETWORK
AUDIO/VISUAL
ACOUSTICAL
EQUIPMENT
HVAC
ROOM DATA SHEET
BUILDING: Coralville - Administration Building / Visitor Center
ARCHITECTURAL
Room Name: Supervisory Natural Resource Specialist (Private Office) Area (Net): 120 Sq. Ft. Min.
Room Number: T.B.D.
Capacity / Personnel: 1
Floors: Modular Carpet Ceiling: Acoustical Ceiling Tile and Grid Walls: Gypsum Board - Painted Doors: Wood w/ Hollow Metal Frame Millwork/Casework: - Notes/Special Requirements: Manually Operated Roller Shade - Light Filtering
FF&E (Furniture, Fixtures, and Equipment) 72"W Powered Stand-Up Desk with 5 drawers, Executive Desk, Executive Desk Chair, Workstation for Computer, 48"W x 72"T Bookshelf, Meeting Table w/ Chairs (2 visitors), 2 Drawer 32"W x 71"T Armoire w/ Filing Cabinets, 18" x 72" Credenza, Chair Mat, Standing Mat
Notes/Special Requirements: -
Heating Required: Y Heating Temperature: 68° F Occupied/ 55° F Setback Air Conditioning Required: Y Cooling Temperature: 78° F/ 50% RH Occupied/ Ambient Setback Ventilation: Per ASHRAE 62.1 Notes/Special Requirements: -
Fixtures: N/A Notes/Special Requirements: -
120VAC Duplex Receptacles QTY: 5 120VAC Quadplex Receptacles QTY: 2 208VAC Special Receptacles N/A Lighting Control Manual On/Vacancy Off, Dimmable CCTV Monitors Wall 120V Receptacles QTY: 1 Video Monitor Wall 120V Receptacles QTY: 1 Duress System Monitor & Control QTY: 1
Telephone: N/A Ceiling Mounted Speaker Connections QTY: 1 CCTV Monitors Circuit Outlet QTY: 1 HDMI Connector QTY: 2
LAN: QTY: 3 - TYPE: RJ45
CATV/TV: QTY: 1
Networks: NIPR, Commercial Notes/Special Requirements: Place LAN connections per furniture layout
Equipment: Provide connection for government owned wall Mounted CCTV Monitor, Wall Mounted Conference Monitor with HDMI Connection
Notes/Special Requirements: Provide HDMI connection for Conference Monitor from occupant computer at desk. Provide Monitor mounting brackets and power in wall behind screens.
Perimeter STC: 45 Space NC: 30-35 Notes/Special Requirements: -
Equipment (GFGI): Wall Mounted Monitors Equipment (CFCI): - Notes/Special Requirements: Provide blocking as required for Wall Mounted TV
Card Access: N/A Intrusion Detection: Y Notes/Special Requirements: -
Fire Suppression: Y Fire Alarm: Y Hazard Classification: LH Notes/Special Requirements: -
FIRE PROTECTION
OTHER COMMENTS
Locate in general vicinity of Operations Project Manager, Administrative Officer, Facility Services Assistant and Program Analyst Offices. Located away from Lobby/Reception Area.
PLUMBING
AUDIO/VISUAL
ACOUSTICAL
EQUIPMENT
SECURITY
ELECTRICAL
COMMUNICATIONS/NETWORK
HVAC
ROOM DATA SHEET
BUILDING: Coralville - Administration Building / Visitor Center
ARCHITECTURAL
Room Name: Prog. Analyst (Private Office) Area (Net): 120 Sq. Ft. Min.
Room Number: T.B.D.
Capacity / Personnel: 1
Floors: Modular Carpet Ceiling: Acoustical Ceiling Tile and Grid Walls: Gypsum Board - Painted Doors: Wood w/ Hollow Metal Frame Millwork/Casework: - Notes/Special Requirements: Manually Operated Roller Shade - Light Filtering
FF&E (Furniture, Fixtures, and Equipment) 72"W Powered Stand-Up Desk with 5 drawers Desk Chair, Workstation for Computer, 48"W x 72"T Bookshelf, Meeting Table w/ Chairs (2 visitors), 2 Drawer 32"W x 71"T Armoire w/ Filing Cabinets, 18" x 72" Credenza, Chair Mat, Standing Mat
Notes/Special Requirements: -
Heating Required: Y Heating Temperature: 68° F Occupied/ 55° F Setback Air Conditioning Required: Y Cooling Temperature: 78° F/ 50% RH Occupied/ Ambient Setback Ventilation: Per ASHRAE 62.1 Notes/Special Requirements: -
Fixtures: N/A Notes/Special Requirements: -
120VAC Duplex Receptacles QTY: 5 120VAC Quadplex Receptacles QTY: 2 208VAC Special Receptacles N/A Lighting Control Manual On/Vacancy Off, Dimmable CCTV Monitors Wall 120V Receptacles QTY: 1 Video Monitor Wall 120V Receptacles QTY: 1 Duress System Monitor & Control QTY: 1
Telephone: N/A Ceiling Mounted Speaker Connections QTY: 1 CCTV Monitors Circuit Outlet QTY: 1 HDMI Connector QTY: 2
LAN: QTY: 3 - TYPE: RJ45
CATV/TV: QTY: 1
Networks: NIPR, Commercial Notes/Special Requirements: Place LAN connections per furniture layout
Equipment:
Notes/Special Requirements: Provide HDMI connection for Conference Monitor from occupant computer at desk. Provide Monitor mounting brackets and power in wall behind screens.
Perimeter STC: 45 Space NC: 30-35 Notes/Special Requirements: -
Equipment (GFGI): Wall Mounted Monitors Equipment (CFCI): - Notes/Special Requirements: Provide blocking as required for Wall Mounted TV
Card Access: N/A Intrusion Detection: Y Notes/Special Requirements: -
Fire Suppression: Y Fire Alarm: Y Hazard Classification: LH Notes/Special Requirements: -
SECURITY
FIRE PROTECTION
OTHER COMMENTS
Locate in general vicinity of Operations Project Manager, Administrative Officer, Facility Services Assistant and Program Analyst Offices. Locate away from Lobby/Reception Area.
PLUMBING
ELECTRICAL
COMMUNICATIONS/NETWORK
AUDIO/VISUAL
ACOUSTICAL
EQUIPMENT
HVAC
ROOM DATA SHEET
BUILDING: Coralville - Administration Building / Visitor Center
ARCHITECTURAL
Room Name: Administrative Officer (Private Office) Area (Net SF): 120 Sq. Ft. Min.
Room Number: T.B.D.
Capacity / Personnel: 1
Floors: Modular Carpet Ceiling: Acoustical Ceiling Tile and Grid Walls: Gypsum Board - Painted Doors: Wood w/ Hollow Metal Frame Millwork/Casework: - Notes/Special Requirements: Manually Operated Roller Shade - Light Filtering
FF&E (Furniture, Fixtures, and Equipment) Semi- Enclosed Work Station (Desk with 5 Drawers), Desk Chair, overhead storage, 2 Drawer 32"W x 71"T Armoire w/ Filing Cabinets, Chair Mat, Standing Mat
Notes/Special Requirements: -
Heating Required: Y Heating Temperature: 68° F Occupied/ 55° F Setback Air Conditioning Required: Y Cooling Temperature: 78° F/ 50% RH Occupied/ Ambient Setback Ventilation: Per ASHRAE 62.1 Notes/Special Requirements: -
Fixtures: N/A Notes/Special Requirements: -
120VAC Duplex Receptacles QTY: 4 120VAC Quadplex Receptacles QTY: 2 208VAC Special Receptacles N/A Lighting Control Manual On/Vacancy Off, Dimmable CCTV Monitors Wall 120V Receptacles QTY: 1 Video Monitor Wall 120V Receptacles QTY: 1 Duress System Monitor & Control QTY: 1
Telephone: N/A Ceiling Mounted Speaker Connections QTY: 1 CCTV Monitors Circuit Outlet QTY: 1 HDMI Connector N/A
LAN: QTY: 2 - TYPE: RJ45
CATV/TV: QTY: 1
Networks: NIPR, Commercial Notes/Special Requirements: Place LAN connections per furniture layout
Equipment: Wall Mounted CCTV Monitor, Wall Mounted Conference Monitor with HDMI Connection
Notes/Special Requirements: Provide HDMI connection for Conference Monitor from occupant computer at desk. Provide Monitor mounting brackets and power in wall behind screens.
Perimeter STC: 45 Space NC: 30-35 Notes/Special Requirements: -
Equipment (GFGI): - Equipment (CFCI): - Notes/Special Requirements: -
Card Access: N/A Intrusion Detection: Y Notes/Special Requirements: -
Fire Suppression: Y Fire Alarm: Y Hazard Classification: LH Notes/Special Requirements: -
FIRE PROTECTION
OTHER COMMENTS
Locate in general vicinity of Operations Project Manager, Lake Manager, Program Analyst, and Facility Services Assistant offices. Locate near manager and away from lobby/reception area.
PLUMBING
AUDIO/VISUAL
ACOUSTICAL
EQUIPMENT
SECURITY
ELECTRICAL
COMMUNICATIONS/NETWORK
HVAC
ROOM DATA SHEET
BUILDING: Coralville - Administration Building / Visitor Center
ARCHITECTURAL
Room Name: Natural Resource Specialist (Private Office) Area (Net): (8) @ 110 Sq. Ft. = 880 Sq. Ft. Min.
Room Number: T.B.D.
Capacity / Personnel: 1
Floors: Modular Carpet Ceiling: Acoustical Ceiling Tile and Grid Walls: Gypsum Board - Painted Doors: Wood w/ Hollow Metal Frame Millwork/Casework: - Notes/Special Requirements: Manually Operated Roller Shade - Light Filtering
FF&E (Furniture, Fixtures, and Equipment) "L" Shaped Powered Stand-Up Desk, Desk Chair, 72" Credenza w/ Hutch, 48"W x 72"T Bookshelf, Meeting Table w/ Chairs (2 Visitors), Chair Mat, Standing Mat
Notes/Special Requirements: -
Heating Required: Y Heating Temperature: 68° F Occupied/ 55° F Setback Air Conditioning Required: Y Cooling Temperature: 78° F/ 50% RH Occupied/ Ambient Setback Ventilation: Per ASHRAE 62.1 Notes/Special Requirements: -
Fixtures: N/A Notes/Special Requirements: -
120VAC Duplex Receptacles QTY: 5 120VAC Quadplex Receptacles QTY: 2 208VAC Special Receptacles N/A Lighting Control Manual On/Vacancy Off, Dimmable CCTV Monitors Wall 120V Receptacles QTY: 1 Video Monitor Wall 120V Receptacles QTY: 1 Duress System Control/Monitor N/A
Telephone: N/A Ceiling Mounted Speaker Connections QTY: 1 CCTV Monitors Circuit Outlet QTY: 1 HDMI Connector QTY: 2
LAN: QTY: 3 - TYPE: RJ45
CATV/TV: QTY: 1
Networks: NIPR, Commercial Notes/Special Requirements: Place LAN connections per furniture layout
Equipment: - Notes/Special Requirements: -
Perimeter STC: 45 Space NC: 30-35 Notes/Special Requirements: -
Equipment (GFGI): - Equipment (CFCI): - Notes/Special Requirements: -
Card Access: N/A Intrusion Detection: Y Notes/Special Requirements: -
Fire Suppression: Y Fire Alarm: Y Hazard Classification: LH Notes/Special Requirements: -
FIRE PROTECTION
OTHER COMMENTS
Locate centrally to Management and Administration and Natural Resource Specialists
PLUMBING
AUDIO/VISUAL
ACOUSTICAL
EQUIPMENT
SECURITY
ELECTRICAL
COMMUNICATIONS/NETWORK
HVAC
ROOM DATA SHEET
BUILDING: Coralville - Administration Building / Visitor Center
ARCHITECTURAL
Room Name: Seasonal Park Rangers Open Offices Area (Net): (4) Workstations @ 70 Sq. Ft. per person Room Number: T.B.D.
Capacity / Personnel: 4
Floors: Polished/Sealed Concrete Ceiling: Acoustical Ceiling Tile and Grid Walls: Gypsum Board - Painted Doors: Wood w/ Hollow Metal Frame Millwork/Casework: - Notes/Special Requirements: Manually Operated Roller Shade - Light Filtering
FF&E (Furniture, Fixtures, and Equipment) (1) Per Workstation = (4) Total each of the following: Cubicle Systems (7' x 10') w/ power/file cabinets/stand up desk/overhead storage w/lighting (66" High); Desk Chairs; Chair Mats; Standing Mats.
Notes/Special Requirements: -
Heating Required: Y Heating Temperature: 68° F Occupied/ 55° F Setback Air Conditioning Required: Y Cooling Temperature: 78° F/ 50% RH Occupied/ Ambient Setback Ventilation: Per ASHRAE 62.1 Notes/Special Requirements: -
Fixtures: N/A Notes/Special Requirements: -
120VAC Duplex Receptacles QTY: 8 (Multiple Circuits) - Additionally, provide duplex receptacles every 12 Feet along room perimeter walls. Also, in addition to office funriture receptacles, provide one additional receptacle per occupant, dedicated to task lighting for modular funiture feeds.
120VAC Quadplex Receptacles QTY: 8 (Multiple Circuits) - Includes providing Quadplex or equivalent furniture feeders for modular furniture.
208VAC Special Receptacles N/A Lighting Control Manual On/Vacancy Off, Dimmable CCTV Monitors Wall 120V Receptacles N/A Video Monitor Wall 120V Receptacles N/A Duress System Monitor & Control N/A
Telephone: N/A Ceiling Mounted Speaker Connections QTY: 1 CCTV Monitors Circuit Outlet N/A HDMI Connector N/A LAN: QTY: 8 - TYPE: RJ45 (two per office furniture cubicle)
CATV/TV: N/A
Networks: NIPR, Commercial Notes/Special Requirements: Place LAN connections per furniture layout
Equipment: - Notes/Special Requirements: -
Perimeter STC: 45 Space NC: 30-35 Notes/Special Requirements: -
Equipment (GFGI): - Equipment (CFCI): - Notes/Special Requirements: -
Card Access: N/A Intrusion Detection: Y Notes/Special Requirements: -
Fire Suppression: Y Fire Alarm: Y Hazard Classification: LH Notes/Special Requirements: -
FIRE PROTECTION
OTHER COMMENTS
Locate workstations adjacent to Natural Resource Specialist Offices and in general vicinity of one another
PLUMBING
AUDIO/VISUAL
ACOUSTICAL
EQUIPMENT
SECURITY
ELECTRICAL
COMMUNICATIONS/NETWORK
HVAC
ROOM DATA SHEET
BUILDING: Coralville - Administration Building / Visitor Center
ARCHITECTURAL
Room Name: Visitor Center Area (Net): 1,015 Sq. Ft. Min.
Room Number: T.B.D.
Capacity / Personnel: 50-60
Floors: Porcelain Tile Ceiling: Gypsum Board - Painted & Acoustical Ceiling Tile Walls: Wood Paneling - Stained & Gypsum Board - Painted Doors: Wood w/ Hollow Metal Frame Millwork/Casework: Natural History Exhibits/Cultural History Exhibits Notes/Special Requirements: Motor Operated Roller Shades (Light darkening); Aquarium w/ maintenance access and water source; Visitor Center Displays
FF&E (Furniture, Fixtures, and Equipment) Discovery Box
Notes/Special Requirements: -
Heating Required: Y Heating Temperature: 68° F Occupied/ 55° F Setback Air Conditioning Required: Y Cooling Temperature: 78° F/ 50% RH Occupied/ Ambient Setback Ventilation: Per ASHRAE 62.1 Notes/Special Requirements: -
Fixtures: Water Fountain / Filtered Bottle Filling Station
Notes/Special Requirements: -
120VAC Duplex Receptacles QTY: Coordinate and provide one (1) duplex receptacle in center of narrow walls (full width per NFPA along wall less than 12 Feet) and partial walls (not full hieght) as applicable. Do not install more than 8 duplex receptacles on a circuit.
120VAC Quadplex Receptacles QTY: Provide one(1) quadplex every 12 Feet along walls with no more than 4 quadplex receptacles on one circuit.
208VAC Special Receptacles QTY: Coordinate and provide either specialy receptacles and hard-wired circuit connections for each display.
Lighting Control Manual On/Vacancy Off, Dimmable. Separate adjustable control and minimum of 8 programmable scenes for walls, displays, and general room lighting zones. Provide track lights to accent special displays and wash walls. Provide track lights adjustable in both the vertical and horizontal axis. Provide a minimum of 8 zones.
Coordinate with customer for special displays and distribution of lighting control zones.
CCTV Monitors Wall 120V Receptacles N/A Video Monitor Wall 120V Receptacles QTY: One (1) each for the Dam Water Pool Elevation Monitor and additional monitor wall 120VAC receptacles as coordinated for and required by all video monitor displays included in the design.
Duress System Monitor & Control N/A
Telephone: N/A Ceiling Mounted Speaker Connections QTY: Designed to layout with the new room space for proper audio coverage. Used for general PA announcements.
Dam Pool Elevation Monitors Circuit Outlet QTY: 1
CCTV Monitors Circuit Outlet N/A HDMI Connector N/A LAN: Qty: Per Exhibit Design Requirements
CATV/TV: QTY: 1
Networks: N/A Notes/Special Requirements: N/A
Equipment: Hydropower Website Monitor Notes/Special Requirements: Interactive Exhibits/Displays (with headsets used to listen), Motion activated audio exhibits/displays. Provide monitor wall mount, power and data connections.
Perimeter STC: 45 Space NC: 30-35 Notes/Special Requirements: -
Equipment (GFGI): Hydropower Website Monitor Equipment (CFCI): - Notes/Special Requirements: -
Card Access: Y Intrusion Detection: Y Notes/Special Requirements: -
Fire Suppression: Y Fire Alarm: Y Hazard Classification: LH Notes/Special Requirements: -
FIRE PROTECTION
OTHER COMMENTS
PLUMBING
AUDIO/VISUAL
ACOUSTICAL
EQUIPMENT
SECURITY
ELECTRICAL
COMMUNICATIONS/NETWORK
HVAC
ROOM DATA SHEET
BUILDING: Coralville - Administration Building / Visitor Center
ARCHITECTURAL
Room Name: Main Conference Room / Theatre / Classroom Area (Net): 634 sq. ft. Min.
Room Number: T.B.D.
Capacity / Personnel: 50
Floors: Modular Carpet Ceiling: Acoustical Ceiling Tile and Grid Walls: Gypsum Board - Painted Doors: Wood w/ Hollow Metal Frame Millwork/Casework:
Notes/Special Requirements:
FF&E (Furniture, Fixtures, and Equipment) Space Maximizing Conference Tables w/ Chairs, Lectern. That can easily be removed and stored out of the way.
Notes/Special Requirements: This room will have multiple uses. Public meetings/open houses for 50 to 100 walking around, conferences so tables need to be able to be configured in several ways, or a classroom. A smart screen, and multiple TVs, and/or projector, AV system capable of showing movies, DVDs, blue ray, etc. These need to be easily viewed from every seat. This will likely be most often be used as a classroom.
Heating Required: Y Heating Temperature: 68° F Occupied/ 55° F Setback Air Conditioning Required: Y Cooling Temperature: 78° F/ 50% RH Occupied/ Ambient Setback Ventilation: Per ASHRAE 62.1 Notes/Special Requirements: -
Fixtures:
Notes/Special Requirements: -
120VAC Duplex Receptacles QTY: 30 minimum - (Multiple Circuits) Provide duplex in front center for motorized projector screen and duplex in ceiling for projector.
Provide duplex dedicated to planned conference table seating area and floor outlets based on the planned table and NFPA 70 requirements. Additionally, provide a duplex every 12 Feet around the perimeter of the room.
120VAC Quadplex Receptacles QTY: 8 - (Multiple Circuits) Provide one of the quadplexes to left of the main center screen location for a future portable lectern. Provide quadplex behind not less than three flat screen monitor locations.
Provide quadplex in front center for audiovisual cabinet front center below the motorized screen.
208VAC Special Receptacles N/A Lighting Control Manual On/Vacancy Off, Dimmable. Separate adjustable control and minimum choice of 6 programmable scenes for front stage/lectern area, aisles, house lighting, and conference room table areas.
CCTV Monitors Wall 120V Receptacles N/A Video Monitor Wall 120V Receptacles QTY: 5 Motorized Projector Screen 120VAC Rec. QTY: 1 Projector Ceiling Receptacle QTY: 1 Duress System Monitor & Control N/A
Telephone: QTY: 1 Sound and Microphone Amplification System QTY: 1
Ceiling Projector System Connections QTY: 1 Ceiling Mounted Speaker Connections QTY: 6 minimum CCTV Monitors Circuit Outlet N/A HDMI Connector QTY: 4 LAN: QTY: 65 - TYPE: RJ45 (Provide 1 RJ45 for each seat. Provide 2 for lectern; 2 for audiovisual credenza; 2 at each monitor; 1 wall-mounted for wall-mounted VOIP; 1 to the conference room table.
Provide floor mounted data in/out in lieu of wall-mounted where table space exceeds 12 Feet from wall. In addition to network connections noted, provide additional cabling and jacks for audio/visual (A/V) connections and control of AV equipment required by the designer (e.g. monitors, designated laptop connections, touchscreen displays, cameras, microphones) to provide a complete and working system.
CATV/TV: QTY: 1
Networks: NIPR, Commercial Notes/Special Requirements: Place LAN connections per furniture and equipment layout requirements.
Equipment: Refer to Conference Room Audiovisual Systems Requirements
Notes/Special Requirements: Refer to Conference Room Audiovisual Systems Requirements
Perimeter STC: 50 Space NC: 30-35 Notes/Special Requirements: -
Equipment (GFGI): - Equipment (CFCI): Y Notes/Special Requirements: Provide Audiovisual Equipment
Card Access: N/A Intrusion Detection: Y Notes/Special Requirements: -
Fire Suppression: Y Fire Alarm: Y Hazard Classification: LH Notes/Special Requirements: -
FIRE PROTECTION
OTHER COMMENTS
Locate adjacent to Lobby/Reception Area and to include space for AV presentations, interpretive exhibits and displays. To be located near the main entrance of the building adjacent to the Lobby/Reception Area. Visitor Center Interior displays to retain from old facility include: A stand alone display that is programmable with maps, history of Corps, etc. We also have a sand table, a drowning machine, Dunkleoteous skull, fossils, several taxidermy mounted
PLUMBING
AUDIO/VISUAL
ACOUSTICAL
EQUIPMENT
SECURITY
ELECTRICAL
COMMUNICATIONS/NETWORK
HVAC
ROOM DATA SHEET
BUILDING: Coralville - Administration Building / Visitor Center
ARCHITECTURAL
Room Name: Kitchenette Area (Net): 330 sq. ft. Min.
Room Number: T.B.D.
Capacity / Personnel: 20 max
Floors: Vinyl Tile Ceiling: Acoustical Ceiling Tile and Grid Walls: Gypsum Board - Painted Doors: Wood w/ Hollow Metal Frame Millwork/Casework: Base Cabinets w/ Countertop, Wall Cabinets Notes/Special Requirements: Provide small kitchenette w/ sink, coffee maker, and microwave.
FF&E (Furniture, Fixtures, and Equipment)
Notes/Special Requirements: -
Heating Required: Y Heating Temperature: 68° F Occupied/ 55° F Setback Air Conditioning Required: Y Cooling Temperature: 78° F/ 50% RH Occupied/ Ambient Setback Ventilation: Per ASHRAE 62.1 Notes/Special Requirements: -
Fixtures: Sink (Kitchenette) Notes/Special Requirements: -
120VAC Duplex Receptacles 120VAC Quadplex Receptacles 208VAC Special Receptacles N/A Lighting Control Manual On/Vacancy Off, Dimmable CCTV Monitors Wall 120V Receptacles N/A Video Monitor Wall 120V Receptacles N/A Motorized Projector Screen 120VAC Rec. N/A Projector Ceiling Receptacle N/A Duress System Monitor & Control N/A
Telephone: N/A Sound and Microphone Amplification System QTY: 1
Ceiling Projector System Connections QTY: 1 Ceiling Mounted Speaker Connections CCTV Monitors Circuit Outlet N/A HDMI Connector QTY: 4
LAN:
CATV/TV: QTY: 1
Networks:
Notes/Special Requirements:
Equipment:
Notes/Special Requirements:
Perimeter STC: 50 Space NC: 30-35 Notes/Special Requirements: -
Equipment (GFGI): - Equipment (CFCI): Y Notes/Special Requirements:
Card Access: N/A Intrusion Detection: Y Notes/Special Requirements: -
Fire Suppression: Y Fire Alarm: Y Hazard Classification: LH Notes/Special Requirements: -
SECURITY
FIRE PROTECTION
OTHER COMMENTS
Locate away from office area.
PLUMBING
ELECTRICAL
COMMUNICATIONS/NETWORK
AUDIO/VISUAL
ACOUSTICAL
EQUIPMENT
HVAC
ROOM DATA SHEET
BUILDING: Coralville - Administration Building / Visitor Center
ARCHITECTURAL
Finishes:
INTERIORS
b5ecdf9a Text Box include fridge, stove b5ecdf9a Text Box update # of occ.
Room Name: Storage Area (Net): Various Areas Totalling 500 Sq. Ft. Min.
Room Number: T.B.D.
Capacity / Personnel: -
Floors: Polished/Sealed Concrete Ceiling: Exposed - Painted (Dryfall) Walls: Gypsum Board - Painted Doors: Wood w/ Hollow Metal Frame Millwork/Casework: - Notes/Special Requirements: -
FF&E (Furniture, Fixtures, and Equipment) -
Notes/Special Requirements: -
Heating Required: Y Heating Temperature: 68° F Occupied/ 55° F Setback Air Conditioning Required: Y Cooling Temperature: Based on stored material requirements Ventilation: Per ASHRAE 62.1 Notes/Special Requirements: Cooling provided thru economizer only.
Fixtures: N/A Notes/Special Requirements: -
120VAC Duplex Receptacles QTY: Provide GFCI convenience receptacles only accessible from aisles. Provide one minimum GFCI housekeeping receptacle.
120VAC Quadplex Receptacles N/A 208VAC Special Receptacles N/A Lighting Control Occupancy On/Vacancy Off CCTV Monitors Wall 120V Receptacles N/A Video Monitor Wall 120V Receptacles N/A Duress System Monitor & Control N/A
Telephone: N/A Ceiling Mounted Speaker Connections QTY: 1 CCTV Monitors Circuit Outlet N/A HDMI Connector N/A
LAN: N/A
CATV/TV: N/A
Networks: N/A Notes/Special Requirements: N/A
Equipment: - Notes/Special Requirements: -
Perimeter STC: 45 Space NC: 30-35 Notes/Special Requirements: -
Equipment (GFGI): - Equipment (CFCI): - Notes/Special Requirements: -
Card Access: N/A Intrusion Detection: N/A Notes/Special Requirements: -
Fire Suppression: Y Fire Alarm: Y Hazard Classification: LH Notes/Special Requirements: -
HVAC
ROOM DATA SHEET
BUILDING: Coralville Lake - Administration Building / Visitor Center
ARCHITECTURAL
Finishes:
INTERIORS
FIRE PROTECTION
OTHER COMMENTS
Multiple secure areas for storage of files, supplies and equipment. Exterior storage for outdoor landscaping.
PLUMBING
AUDIO/VISUAL
ACOUSTICAL
EQUIPMENT
SECURITY
Room Name: Employee Restrooms Area (Net): (2) @ 184 Sq. Ft. Min.
Room Number: T.B.D.
Capacity / Personnel: -
Floors: Resinous Flooring w/ Integral Base Ceiling: Gypsum Board - Painted Walls: Gypsum Board - Painted, Porcelain Tile Doors: Wood w/ Hollow Metal Frame Millwork/Casework: (1) Lavatory each = (2) Total Notes/Special Requirements: -
FF&E (Furniture, Fixtures, and Equipment) Toilet Partitions, Automatic Toilet Tissue Dispenser, Sanitary Napkin Disposal, Soap Dispenser and Paper Towel Dispenser, Toilet Seat Dispensers, Waste Receptacles, Mirrors, Grab Bars
Notes/Special Requirements: -
Heating Required: Y Heating Temperature: 68° F DB Air Conditioning Required: N Cooling Temperature: Passive thru transfer air only.
Ventilation: Per ASHRAE 62.1 Notes/Special Requirements: Use largest: 2 CFM/SF, 10 air changes per hour, ASHRAE 62.1.
Maintain negative pressure to adjacent rooms.
Fixtures: Lavatories, Water Closets, Urinal Notes/Special Requirements: Mens - (1) Lavatory, (1) Water Closet, (1) Urinal; Womens - (1)
Lavatory, (2) Water Closets
120VAC Duplex Receptacles QTY: Provide GFCI receptacle at countertops and sinks every 3 Feet. Provide 1 GFCI receptacle for housekeeping.
120VAC Quadplex Receptacles N/A 208VAC Special Receptacles N/A Lighting Control Occupancy On/Vacancy Off CCTV Monitors Wall 120V Receptacles N/A Video Monitor Wall 120V Receptacles N/A Duress System Monitor & Control N/A
Telephone: N/A Ceiling Mounted Speaker Connections QTY: 1 CCTV Monitors Circuit Outlet N/A HDMI Connector N/A
LAN: N/A
CATV/TV: N/A
Networks: N/A Notes/Special Requirements: N/A
Equipment: - Notes/Special Requirements: -
Perimeter STC: 45 Space NC: 30-35 Notes/Special Requirements: -
Equipment (GFGI): - Equipment (CFCI): - Notes/Special Requirements: -
Card Access: N/A Intrusion Detection: N/A Notes/Special Requirements: -
Fire Suppression: Y Fire Alarm: Y Hazard Classification: LH Notes/Special Requirements: -
HVAC
ROOM DATA SHEET
BUILDING: Coralville Lake - Administration Building / Visitor Center
ARCHITECTURAL
Finishes:
INTERIORS
FIRE PROTECTION
OTHER COMMENTS
Locate centrally to all offices.
PLUMBING
AUDIO/VISUAL
ACOUSTICAL
EQUIPMENT
SECURITY
Room Name: ADA Public Restrooms Area (Net): (2) @ 175 Sq. Ft. = 350 Sq. Ft. Min.
Room Number: T.B.D.
Capacity / Personnel: -
Floors: Resinous Flooring w/ Integral Base Ceiling: Gypsum Board - Painted Walls: Gypsum Board - Painted, Porcelain Tile Doors: Wood w/ Hollow Metal Frame Millwork/Casework: (3) Lavatories each = (6) Total Notes/Special Requirements: -
FF&E (Furniture, Fixtures, and Equipment) Toilet Partitions, Automatic Toilet, Tissue Dispenser, Sanitary Napkin Disposal, Automatic/touchless Soap Dispenser and Automatic/touchless Paper Towel Dispenser, Toilet Seat Dispensers, Waste Receptacles, Mirrors, Grab Bars
Notes/Special Requirements: -
Heating Required: Y Heating Temperature: 68° F DB Air Conditioning Required: N Cooling Temperature: Passive thru transfer air only.
Ventilation: Per ASHRAE 62.1 Notes/Special Requirements: Use largest: 2 CFM/SF, 10 air changes per hour, ASHRAE 62.1.
Maintain negative pressure to adjacent rooms.
Fixtures: Lavatories, Water Closets, Urinals Notes/Special Requirements: Mens - (3) Lavatory, (2) Water Closet, (2) Urinal; Womens - (3)
Lavatory, (4) Water Closets
120VAC Duplex Receptacles QTY: Provide 1 GFCI receptacle for housekeeping.
120VAC Quadplex Receptacles N/A 208VAC Special Receptacles N/A Lighting Control Occupancy On/Vacancy Off CCTV Monitors Wall 120V Receptacles N/A Video Monitor Wall 120V Receptacles N/A Duress System Monitor & Control N/A
Telephone: N/A Ceiling Mounted Speaker Connections QTY: 1 CCTV Monitors Circuit Outlet N/A HDMI Connector N/A
LAN: N/A
CATV/TV: N/A
Networks: N/A Notes/Special Requirements: N/A
Equipment: - Notes/Special Requirements: -
Perimeter STC: 45 Space NC: 30-35 Notes/Special Requirements: -
Equipment (GFGI): - Equipment (CFCI): - Notes/Special Requirements: -
Card Access: N/A Intrusion Detection: Y Notes/Special Requirements: -
Fire Suppression: Y Fire Alarm: Y Hazard Classification: LH Notes/Special Requirements: -
HVAC
ROOM DATA SHEET
BUILDING: Coralville Lake - Administration Building / Visitor Center
ARCHITECTURAL
Finishes:
INTERIORS
FIRE PROTECTION
OTHER COMMENTS
Locate adjacent to Lobby/Entrance and Visitor Center
PLUMBING
AUDIO/VISUAL
ACOUSTICAL
EQUIPMENT
SECURITY
Room Name: Janitor Closets Area (Net): 48 Sq. Ft. Min.
Room Number: T.B.D.
Capacity / Personnel: -
Floors: Sealed Concrete Ceiling: Exposed - Painted (Dryfall) Walls: Gypsum Board - Painted Doors: Wood w/ Hollow Metal Frame Millwork/Casework: - Notes/Special Requirements: FRP at Service Sink Walls
FF&E (Furniture, Fixtures, and Equipment) Janitorial Supply Storage Shelving, Mop/Broom Holder
Notes/Special Requirements: -
Heating Required: N Heating Temperature: Passive thru Transfer Air Air Conditioning Required: N Cooling Temperature: Passive thru Transfer Air Ventilation: Per ASHRAE 62.1 Notes/Special Requirements: Minimum 10 air changes per hour. Maintain negative pressure to adjacent rooms.
Fixtures: Service Sink Notes/Special Requirements: -
120VAC Duplex Receptacles QTY: Provide 1 GFCI receptacle minimum accessible at door 120VAC Quadplex Receptacles N/A 208VAC Special Receptacles N/A Lighting Control Occupancy On/Vacancy Off CCTV Monitors Wall 120V Receptacles N/A Video Monitor Wall 120V Receptacles N/A Duress System Monitor & Control N/A
Telephone: N/A Ceiling Mounted Speaker Connections N/A CCTV Monitors Circuit Outlet N/A HDMI Connector N/A
LAN: N/A
CATV/TV: N/A
Networks: N/A Notes/Special Requirements: N/A
Equipment: - Notes/Special Requirements: -
Perimeter STC: 45 Space NC: 30-35 Notes/Special Requirements: -
Equipment (GFGI): - Equipment (CFCI): - Notes/Special Requirements: -
Card Access: N/A Intrusion Detection: N/A Notes/Special Requirements: -
Fire Suppression: Y Fire Alarm: Y Hazard Classification: LH Notes/Special Requirements: -
HVAC
ROOM DATA SHEET
BUILDING: Coralville Lake - Administration Building / Visitor Center
ARCHITECTURAL
Finishes:
INTERIORS
FIRE PROTECTION
OTHER COMMENTS
Locate adjacent to Public Restrooms and Employee Shower Rooms
PLUMBING
AUDIO/VISUAL
ACOUSTICAL
EQUIPMENT
SECURITY
Room Name: Open Lobby/Reception Area Area (Net): 420 Sq. Ft. Min.
Room Number: T.B.D.
Capacity / Personnel: 2
Floors: Porcelain Tile Ceiling: Gypsum Board - Painted & Acoustical Ceiling Tile Walls: Wood Paneling - Stained & Gypsum Board - Painted Doors: Thermally Broken Storefront Millwork/Casework: Built-in Reception Counter/Desk Notes/Special Requirements: Reception/Tourism/Chamber of Commerce Desk, Viewing
Windows, Lockable Sales Area
FF&E (Furniture, Fixtures, and Equipment) (1) Per Workstation = (2) Total each of the following: Cubicle Systems (7' x 10') w/ power/file cabinets/stand up desk/overhead storage w/lighting (66" High); Desk Chairs; Chair Mats; Standing Mats.
Notes/Special Requirements: Namesake Interpretation, Donor Wall, Brochure Distribution
Heating Required: Y Heating Temperature: 68° F Occupied/ 55° F Setback Air Conditioning Required: Y Cooling Temperature: 78° F/ 50% RH Occupied/ Ambient Setback Ventilation: Per ASHRAE 62.1 Notes/Special Requirements: -
Fixtures: N/A Notes/Special Requirements: -
120VAC Duplex Receptacles QTY: 14 (Multiple Circuits) - Additionally, provide duplex receptacles every 12 Feet along room perimeter walls.
120VAC Quadplex Receptacles QTY: 6 (Multiple Circuits) - Includes providing Quadplex or equivalent furniture feeders for furniture.
208VAC Special Receptacles N/A Lighting Control Manual On/Vacancy Off, Dimmable CCTV Monitors Wall 120V Receptacles QTY: 1 Video Monitor Wall 120V Receptacles QTY: 2 Duress System Monitor & Control QTY: 1
Telephone: N/A Ceiling Mounted Speaker Connections QTY: 2 CCTV Monitors Circuit Outlet QTY: 1 HDMI Connector QTY: 1 LAN: QTY: 4 - TYPE: RJ45 and as needed for interactive map and monitors designed in this space.
CATV/TV: QTY: 2
Networks: NIPR, Commercial Notes/Special Requirements: Place LAN connections per furniture layout
Equipment: Wall Mounted Monitor Notes/Special Requirements: Interactive Project Map
Perimeter STC: 45 Space NC: 30-35 Notes/Special Requirements: -
Equipment (GFGI): - Equipment (CFCI): Interactive Project Map & Monitor Notes/Special Requirements: -
Card Access: N/A Intrusion Detection: Y Notes/Special Requirements: -
Fire Suppression: Y Fire Alarm: Y Hazard Classification: LH Notes/Special Requirements: -
FIRE PROTECTION
OTHER COMMENTS
Provide secured reception counter for greeting visitors located at the main entrance of the building. Provide seating space for two (2) visitors. Information bulletins, and wall exhibits identifying the Corps of Engineers as the agency responsible for Coralville Lake Visitor Center and the project it represents.
PLUMBING
AUDIO/VISUAL
ACOUSTICAL
EQUIPMENT
SECURITY
ELECTRICAL
COMMUNICATIONS/NETWORK
HVAC
ROOM DATA SHEET
BUILDING: Coralville - Administration Building / Visitor Center
ARCHITECTURAL
Room Name: Mechanical & Electrical Rooms Area (Net): Various Rooms/Areas = 220 sq ft Room Number: T.B.D.
Capacity / Personnel: -
Floors: Sealed Concrete Ceiling: Exposed - Painted (Dryfall) Walls: Gypsum Board - Painted Doors: Wood w/ Hollow Metal Frame Millwork/Casework: - Notes/Special Requirements: -
FF&E (Furniture, Fixtures, and Equipment) -
Notes/Special Requirements: -
Heating Required: Y Heating Temperature: 55° F Air Conditioning Required: Y Cooling Temperature: Determined by equipment requirements.
Ventilation: Per ASHRAE 62.1 Notes/Special Requirements: Ventilation shall be sufficient to satify combusition air and equipment cooling requirements, minimum 1 air change per hour.
Fixtures: Floor drain Notes/Special Requirements: -
120VAC Duplex Receptacles QTY: 4 minimum -- GFCI convenience receptacles for housekeeping and tools. Also, provide dedicated duplex receptacles as needed for mechanical equipment. Provide one (duplex) below or adjacen to each panelboard.
120VAC Quadplex Receptacles N/A 208VAC Special Receptacles N/A Lighting Control Manual On/Manual Off CCTV Monitors Wall 120V Receptacles N/A Video Monitor Wall 120V Receptacles N/A Duress System Monitor & Control N/A
Telephone: N/A Ceiling Mounted Speaker Connections QTY: 2 CCTV Monitors Circuit Outlet N/A HDMI Connector N/A
LAN: QTY: 1 - TYPE: RJ45
CATV/TV: N/A
Networks: NIPR, Commercial Notes/Special Requirements: N/A
Equipment: - Notes/Special Requirements: -
Perimeter STC: 45 Space NC: 30-35 Notes/Special Requirements: -
Equipment (GFGI): - Equipment (CFCI): - Notes/Special Requirements: -
Card Access: N/A Intrusion Detection: Y Notes/Special Requirements: -
Fire Suppression: Y Fire Alarm: Y Hazard Classification: LH Notes/Special Requirements: -
HVAC
ROOM DATA SHEET
BUILDING: Coralville Lake - Administration Building /Visitor Center
ARCHITECTURAL
Finishes:
INTERIORS
FIRE PROTECTION
OTHER COMMENTS
Locate in basement floor of building with exterior access.
PLUMBING
AUDIO/VISUAL
ACOUSTICAL
EQUIPMENT
SECURITY
Room Name: Lift / Fire exit Area (Net): ### Sq. Ft.
Room Number: T.B.D.
Capacity / Personnel: #
Floors: concrete Ceiling: Acoustical Ceiling Tile and Grid Walls: Gypsum Board - Painted Doors: Wood w/ Hollow Metal Frame Millwork/Casework: - Notes/Special Requirements: -
FF&E (Furniture, Fixtures, and Equipment) Emergency Lighting Notes/Special Requirements: -
Heating Required: Y Heating Temperature: 68° F Occupied/ 55° F Setback Air Conditioning Required: Y Cooling Temperature: 78° F/ 50% RH Occupied/ Ambient Setback
Ventilation: Per ASHRAE 62.1 Notes/Special Requirements: -
Fixtures:
Notes/Special Requirements: -
120VAC Duplex Receptacles QTY: 5 120VAC Quadplex Receptacles QTY: 2 208VAC Special Receptacles N/A Lighting Control Manual On/Vacancy Off, Dimmable CCTV Monitors Wall 120V Receptacles QTY: 1 Video Monitor Wall 120V Receptacles QTY:1 Duress System Control/Monitor N/A
Telephone: N/A Ceiling Mounted Speaker Connections QTY: 1 CCTV Monitors Circuit Outlet QTY: 1 HDMI Connector QTY: 2
LAN: QTY: 3 - TYPE: RJ45
CATV/TV: N/A
Networks: NIPR, Commercial Notes/Special Requirements: Place LAN connections per furniture layout
Equipment: - Notes/Special Requirements: -
Perimeter STC: 45 Space NC: 30-35 Notes/Special Requirements: -
HVAC
ROOM DATA SHEET
BUILDING: Coralville - Administration Building / Visitor Center
ARCHITECTURAL
Finishes:
INTERIORS
PLUMBING
ELECTRICAL
COMMUNICATIONS/NETWORK
AUDIO/VISUAL
ACOUSTICAL
Equipment (GFGI): - Equipment (CFCI): - Notes/Special Requirements: -
Card Access: N/A Intrusion Detection: Y Notes/Special Requirements: -
Fire Suppression: Y Fire Alarm: Y Hazard Classification: LH Notes/Special Requirements: -
SECURITY
FIRE PROTECTION
OTHER COMMENTS
With the office being two levels we need a way to get someone physically impaired from one leve to the next, some type of lift system will be necessary. This will also aid in getting equipment, bulky, heavy items from one level to the next safely. The office will need a fire exit from the and bottom floors.
EQUIPMENT
| Appendix 6 - Room Data Sheets Cover Page - 25 Oct. 2023 |
| Appendix 6 - Pt. 1 |
| O.B.-Op. Flr. W.S. |
| Appendix 6 - Pt. 2 |
| Ops. Proj. Mgr. |
| Lake Mgr. |
| Supv. Ranger |
| Prog. Analyst |
| Admin. Ofc. |
| Nat. Res. Spc. |
| Seas. Park. Rngr. |
| Vis. Ctr. |
| Main Conf. |
| Kitchenette |
| Stor. |
| Empl. Restr. |
| Publ. Restr. |
| Jan. Clos. |
| Lob. Rec. |
| Mech. & Elec. |
| Lift & Fire Escape |