Appendix M

View the file

Other files for this federal contract opportunity

Other files attached to Thule Consolidation 1 (Base Shops & Base Supply Facility), newest first.
File Type Posted
Bid_Abstract_-_W912DS-16-B-0002.pdf PDF
C-106.pdf PDF
C-103.pdf PDF
W912DS-16-B-0002_-_Amendment_0005.pdf PDF
Greenland_-_DBA_Waiver_-_Greenland.pdf PDF
C-107.pdf PDF
C-303.pdf PDF
Thule_Consol_1_CE_shop_-_100__ELECT_SPEC_27_10_00_(Rev_1)_25_April_2016.pdf PDF
Thule_Consol_1_CE_shop_-_100__ELECT_SPEC_(REGISTER)_27_10_00_(Rev_1)_25_April_2016.pdf PDF
C-104.pdf PDF
C-105.pdf PDF
C-304.pdf PDF
W912DS-16-B-0002_Amendment_0004.pdf PDF
Thule_Consol_1_CE_Shop_-_Updated_100__CID_Package_25_April_2016.pdf PDF
Thule_Consol_1_CE_shop_-_100__ELECT_SPEC_27_10_00_(Rev_1)_25_April_2016.pdf PDF
Thule_Consol_1_CE_shop_-_100__ELECT_SPEC_(REGISTER)_27_10_00_(Rev_1)_25_April_2016.pdf PDF
Consoliation_1_Revised_Drwgs_Amd_0004.pdf PDF
W912DS-16-B-0002_Amendment_0003.pdf PDF
ES-102A_-_NEW_REVISED_SITE_FOR_CE_SHOP(4-25-2016).pdf PDF
ES-601_-_SITE_ELEC_REVISED_(25_APR_2016).pdf PDF
ES-601A_-_FEEDER_SCHEDULE(4-25-2016).pdf PDF
W912DS-16-B-0002_Amendment_0002.pdf PDF
W912DS-16-B-0002_-_Amendment_0001.pdf PDF
Package_2_-_Thule_Consolidation_1_-_Specifications_100.pdf PDF
W912DS-16-B-0002.pdf PDF
Appendix_C_-_Conservation_Mgmt_Plan.pdf PDF
Appendix_A_-_Active_Landfills.pdf PDF
Appendix_K_-_FGS-GL_(Environmental_Protection).pdf PDF
Appendix_L_-_Affirmative_Proc_Plan.pdf PDF
Package_3_-_Thule_Consolidation_1_-_SID_ _CID.pdf PDF
Appendix_R_-_Demo_(Lead_ _Asbestos_Survey _As-Builts).pdf PDF
Appendix_G_-_Solid_Waste_Mgmt_Plan.pdf PDF
Appendix_D_-_HWM_Plan.pdf PDF
Appendix_W_-_Natural_Resources_Management_Plan.pdf PDF
Appendix_B_-_NFS_Material_Borrow_Sites.pdf PDF
Appendix_T_-_Fuel_Pricing_and_DLA_info.pdf PDF
Appendix_N_-_Asbestos_Mgmt_Plan.pdf PDF
Appendix_Q_-_Thule_Site_Topo_Survey.dwg DWG drawing
Appendix_E_-_Spill_Prevention-Response_Plan.pdf PDF
Appendix_O_-_Lead_Paint_Mgmt_Plan.pdf PDF
Appendix_U_-_Shipping_Rates_Gov_Furnished_Transport.pdf PDF
Appendix_P_-_DBA_Waiver.pdf PDF
Appendix_J_-_Installation_HAZMAT_Management_Plan.pdf PDF
Appendix_V_-_Geotechnical_Investigation.pdf PDF
Appendix_S_-_FY14_-_FY17_Sealift_Rates.pdf PDF
Appendix_X_-_Pacer_Goose_Shipping_Instructions.pdf PDF
Appendix_F_-_PPM_Plan.pdf PDF
Appendix_I_-_Slug_Mgmt_Plan.pdf PDF
Package_1_-_Thule_Consolidation_1_-_Plans_100.pdf PDF
Appendix_H_-_Storm_Water_Mgmt_Plan.pdf PDF
Show all 50

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1 January 2010

CDRL CEV-12

Polychlorinated Biphenyl (PCB) Replacement Plan

Thule Air Base, Greenland

FINAL, FY-15

OPR: GREENLAND CONTRACTORS

Chief of Environmental Engineering

DSN 629-2698

Contract No.FA2523-05-C-9001 Supersedes CDRL CEV-12 FY-14 edition

CDRL CEV-12 Polychlorinated Biphenyl (PCB) Replacement Plan

Thule Air Base, Greenland Page 2 of 20 FY-15

INSTALLATION IMPLEMENTING INSTRUCTION

Date: 1 January 2015

Requiring Office: 21 CES/CEIE

OPR: Greenland Contractors, Environmental Engineering

Subject: CDRL CEV-12 Polychlorinated Biphenyl Replacement Plan

Reference(s): Thule BMC Statement of Work (SOW)

Greenland Final Governing Standards for Environmental Protection (FGS)

Purpose: To implement a Polychlorinated Biphenyl Replacement Plan for Thule Air

Base (Thule AB), Greenland. This plan covers identification, inventory and replacement of PCBs.

Discussion: This plan has been prepared in accordance with the above mentioned referenced documents. This plan is a comprehensive document used by all personnel working at Thule AB. It was designed to ensure installation compliance with federal state and host policies, laws and regulation concerning pollution prevention.

Applicability: Relevant Thule AB personnel and organizations will review the plan and ensure full compliance. Through implementation and cooperation this plan will ensure a safe, healthy, and clean environment for current and future generations.

Action: This Polychlorinated Biphenyl (PCB) Replacement Plan is effective after informal coordination with the requiring office (21 CES/CEIE). Draft coordination will be considered acceptable if no requiring office comments are received within 45 days.

Thule Air Base, Greenland Page 3 of 20 FY-15

TABLE OF CONTENTS

1.0 LETTER OF INSTRUCTION

1.1 Security and Administrative Instructions

2.0 INTRODUCTION

2.1 Polychlorinated biphenyls

2.2 Examples - PCB containing products

3.0 PCB IDENTIFICATION, REMOVAL, AND INVENTORY

3.1 PCB on Thule Air Base

3.2 Requirements for PCB-transformers

3.3 Definitions of different PCB items

3.4 Requirements for PCB items

3.5 Procedures for potential PCB contaminated items

3.6 PCB Storage and disposal

3.7 PCB Spills

4.0 ACRONYMS

APPENDIX 1: PCB INVENTORY

APPENDIX 2: Inventory of Transformers

APPENDIX 3: ENVIRONMENTAL REVIEW COMMENTS

APPENDIX 4: Distribution list

Thule Air Base, Greenland Page 4 of 20 FY-15

1.0 LETTER OF INSTRUCTION

1.1 Security and Administrative Instructions

Title: The title of this document is “Polychlorinated Biphenyl Replacement Plan”. The acronym, PCBRP, will be used throughout the document.

Classification: The title and the document are unclassified, and do not fall within the scope of directives governing the protection of information affecting National Security and specified in the United States Air Force (USAF) directives, in the Air Force Instruction (AFI) 31-series.

Responsibilities: Greenland Contractors, Environmental Engineering (GC/EE) is the office of primary responsibility for developing and maintaining the PCBRP. The instruction given in this plan is applicable to all organizations and tenant units at Thule AB. Organizations are authorized to extract and reproduce those sections of the PCBRP that are essential in the accomplishment of necessary planning and in the preparation of supporting document and reports.

Reviews/Changes:

The PCBRP will be reviewed and updated annually. Furthermore, the plan is subject to change if any of the applicable laws, regulations, or requirements are altered.

Thule Air Base, Greenland Page 5 of 20 FY-15

2.0 INTRODUCTION

2.1 Polychlorinated biphenyls.

PCBs are a subset of the synthetic organic chemicals known as chlorinated hydrocarbons.

Polychlorinated biphenyls or PCB are a group of industrial chemicals developed in the 1920s and and they have been widely used in the electronic industry. PCBs consist of two aromatic rings which can have 1-10 chlorine atoms attached – the more chlorine atoms the higher toxicity.

The group of PCBs are mixtures of synthetic organic chemicals with the same basic chemical structure and similar physical properties ranging from oily liquids to waxy solids. Due to their non-flammability, chemical stability, high boiling point and electrical insulating properties, PCBs were used in a wide variety of industrial and commercial applications including electrical heat transfer and hydraulic equipment; as plasticizers in paints, plastics, and rubber products; in pigments, dyes, and carbonless copy paper and many other applications.

PCB is an environmental poison and it has several damaging effects on living organisms. One of the reasons that PCBs are so damaging is that it can be transported unaffected through water and air. It is first when it comes into contact with a living organism that its nature is disclosed.

PCB is fat soluble which means that it can be accumulated in fat tissue hence PCBs can give cause to brain damage. As PCB is found in fat tissue, the concentration of PCB will be higher in the living organism than in the organism’s surroundings (bioaccumulation). Going up the food chain, the concentration of PCB is magnified as the predator is accumulating higher and higher concentrations (biomagnifying) – this means that the polar bear holds more PCBs than the seal it prays on, and that the seal holds more PCBs than the fish it prays on etc. Looking at humans, the source of PCB contamination in the body happens through animal fat / by eating. But just by touching a PCB containing item the living animal/human can accumulate PCB – even by breathing (vapors from PCB containing items). PCB is much resistant to chemical or biological decomposition - when first released into nature, PCB is difficult to decompose.

The concern about the toxicity and persistence in the environment of PCBs led the United States’ Congress in 1976 to enact §6(e) of the Toxic Substances Control Act (TSCA) that included, among other things, prohibitions on the manufacture, processing, and distribution in commerce of PCBs. Thus, TSCA legislated true "cradle to grave" (i.e. from manufacture to disposal) management of PCBs in the United States.

Even though focus has been on replacing and eliminating the use of PCB containing products some of these products have been collected to refuse disposal plants, which has the proper knowhow to destroy the chemical in a proper way. But a large part of the produced PCB still http://da.wikipedia.org/wiki/Fil:Polychlorinated_biphenyl_structure.svg�

Thule Air Base, Greenland Page 6 of 20 FY-15 surrounds us. The remaining PCB can be found in old electronically products, buildings or in deposit sites resulting in continuously exposure of animals and humans through generations.

2.2 Examples - PCB containing products.

More than 1.5 billion pounds of PCBs were manufactured in the United States prior to cessation of production in 1977. Between 1926 and 1977, PCB-containing products were manufactured for applications demanding stable, fire-resistant, heat-transfer properties.

The most extensive use of PCBs occurred in dielectric fluids. Such fluids typically have the following characteristics: heavy oil appearance, high boiling point, high chemical stability, high flash point, low electrical conductivity, and low water solubility. PCBs were also used as plasticizers and additives in lubricating and cutting fluids. PCBs are clear to yellow colored oily liquids or solids. Overheated PCB material from a ruptured capacitor may be black in color.

Applications include electrical transformers, large high- and low-voltage capacitors and fluorescent lamp fixture ballasts.

PCBs are found in electrical equipment manufactured between 1932 and 1977. These include transformers, capacitors, switches, and other items. PCBs can also be found in fluorescent light ballasts, air conditioning units, and sometimes refrigerators.

Light ballasts are the electrical components at the end of fluorescent light fixtures under a metal cover plate. Prior to 1977, ballasts were commonly manufactured with PCBs in the capacitor oil and in a tar-like substance that surrounds ballast components called "potting compound."

Ballasts made after 1977 are usually marked "Non-PCB." Ballasts manufactured after 1977 may contain a PCB replacement called DEHP, a probable human carcinogen.

Originally the capacitors used were hermetically sealed devices that isolated the PCBs from human contact. The typical high power fluorescent ballast contained about 0.02 kilograms (0.05 pounds) of 100% PCB liquid. That amount represented 0.59 deciliters (1-2 fluid ounces). The weight of PCBs used in relationship to the total capacitor weight was approximately 15%. In relationship to the total ballast weight, it varied from 0.6% (slim line ballasts) to 1.5% (2 lamp 40 watt ballasts). The degree of chlorination was 42%.

For the originally high intensity discharge ballasts, the capacitors were larger; it may have been as much as 1.77 deciliters (5-6 ounces) of liquid. In all cases, the amount of liquid that could leak if the can ruptured was less because most of it was by the blotter-like dielectric material.

The EPA has recognized the existence of PCBs in ballasts, has evaluated the situation, and has concluded that continued use in existing lighting installations is acceptable.

PCB transformers may range in size from old, pole mount units, kettle-type pots to very large 5000 KVA units that contain over 1100 gallons of dielectric fluid. Most transformers can be found in basement equipment rooms or electrical vaults and tunnels. Historically two management strategies have been employed for large transformers. The first is replacement. Typically, during electrical upgrade projects older PCB transformers are removed and replaced with the dry, pad mount variety. The second strategy is called retro filling. The PCB containing fluid is replaced a number of times with a non-PCB fluid. In theory, over a period of time measured in years, transformers will no longer contain PCBs. After a given number of retro-fill cycles, the transformer was filled with a non-PCB replacement dielectric fluid. This method had very mixed results.

Transformers with PCB content less than 50 ppm are considered to be "Non-PCB."

Thule Air Base, Greenland Page 7 of 20 FY-15

3.0 PCB IDENTIFICATION, REMOVAL, AND INVENTORY

The use of PCBs and PCB items shall be minimized at Thule Air Base without degrading mission performance.

Therefore, no PCBs or PCB items shall be purchased or otherwise taken under control for use at TAB. All procurement of transformers or any other equipment containing dielectric or hydraulic fluid shall be accompanied by a manufacturer’s certification that the equipment contains no detectable PCB and the items shall have permanent labels affixed stating that they are PCB-free. Only those PCB –items in need of replacement shall be replaced.

Thule AB is required to maintain a written inventory of PCB items, including all marked PCB items in use and PCB items placed into storage for disposal or disposed of for that year (appendix 1).

Inventory records should be maintained for a period of time at least 3 years after the last item on the list is disposed of. Furthermore, a transformer inventory by facility for the installation is maintained (appendix 2). The transformer inventory can be used to indicate if the PCB status of if a specific transformer has been determined.

Discarded dielectric oil containing less than 50 ppm PCB is not considered PCB waste. However, oil containing PCBs in any amount cannot be incinerated on-base and shall be disposed via DLA- DS It must be shipped either as unregulated waste or hazardous waste (if the oil has one or more characteristics of hazardous waste IAW CDRL15-B.

3.1 PCB on Thule Air Base

In the late 80’s and early 90’s a number of transformers, some filters, and capacitors were demolished and shipped out. After the port season 1994, TAB was considered free from major PCB containing or contaminated transformers and filters. However, articles continue to be found that either contain or could contain PCB. It is therefore a requirement to survey buildings for PCBs before demolition. For transformers, the following definitions from the FGS apply:

• A non-PCB Transformer is a transformer that contains less than 50 ppm PCB.

• A PCB transformer is any transformer that contains 500 ppm or greater amount of PCB.

• All transformers will be considered and treated as PCB transformers unless information to the contrary exists

3.2 Requirements for PCB-transformers

PCB transformers that are in use or in storage (at a GC/Supply controlled area) will not be used in any application that poses a risk of contamination to food or feed.

PCB transformers removed from function will not be reused unless there is no practical alternative and such alternative use will not exceed one year. PCB–transformers taken out of service are disposed of through GC/Supply, the on-base DLA-DS function. If the transformers classified as PCB contaminated are in need of service they will only be serviced with dielectric fluid containing less than 500 ppm PCB. Service requiring removal of the transformer coil is prohibited and the transformer is to be replaced by a non-PCB transformer. Repair or replacement of a leaking PCB transformer is to be done within 48 hours or as soon as possible, and the transformer will be inspected daily and leaking PCB collected until proper repair. PCBs removed during servicing will be captured and either reused as dielectric fluid or disposed of through the DLA-DS function.

Thule Air Base, Greenland Page 8 of 20 FY-15

All PCB transformers in use or in or near commercial buildings or located in sidewalks vaults are by this inventory registered by the servicing fire department.

Appropriate measures to control water runoff will be taken if any PCB transformer is involved in a fire and/or PCBs are leaking from it. Runoff water will be tested and managed if required.

There are currently no in-service PCB transformers at Thule AB.

3.3 Definitions of different PCB items

• A PCB item is any PCB article, container, equipment (ex.: electronically equipment as ex.: capacitors, circuit breaks, cables, and florescent light ballasts and fixtures) etc.

that deliberately or unintentionally contains or has as a part of it any PCB or PCBs at a concentration of 50 ppm or greater.

• PCB article: Any manufactured article, other than a PCB container (can, bottle, drum tank etc.), that contains PCBs and whose surface has been in direct contact with PCB

– this includes capacitors, transformers, electrical motors, pumps, and pipes.

3.4 Requirements for PCB items

PCB items other than transformers (see above) will be serviced as follows:

• Only with dielectric fluid containing less than 500 ppm PCB. Larger concentrations are prohibited to use at TAB.

• PCBs removed during servicing will be captured and either reused as dielectric fluid or disposed of through the DLA-DS function on TAB.

• Any PCB item removed from service will be marked with the date on which it is being removed from service. This is done by the DLA-DS function when the item is turned in to storage or disposal.

• If an item is turned in which the DLA-DS function suspect to be contaminated by PCBs will be subject to sampling and analysis for further clarifications. Until the item is recognized as a PCB item or not it will be treated as a PCB item.

• All PCB items with PCB concentrations 50 ppm or greater, as well as any containers, vaults, and storage areas containing used to store the preceding items, must be prominently marked in English and the host nation languages (both Danish and Greenlandic). The marking must identify the item as containing PCBs, warn against improper disposal and handling, and provide a phone number in case of spills or if questions arise about disposal.

• In addition, the following PCB items must be marked at the time of items’ removal from use if not already marked: PCB large low voltage capacitors and equipment containing a PCB Transformer or PCB large high voltage capacitor.

• Use and storage for reuse of capacitors which exposes risk to food or feed is prohibited.

• Use and storage for reuse of capacitors is prohibited unless the capacitor are used within special restricted areas without public access and with the possibility to contain any releases of PCBs.

Thule Air Base, Greenland Page 9 of 20 FY-15

3.5 Procedures for potential PCB contaminated items

At Thule AB it is typically the maintenance function (GC/UFM) that encounters potential PCB items. Suspected PCB items must be turned in to GC/Supply immediately. Contracts to renovate or demolish a facility must include requirements to survey for potential PCB containing items. Contractors shall contact Environmental Engineering for guidelines in case any potential PCB items are located during contracted work.

GC/EE is responsible for determining sampling requirements. The DLA-DS are responsible for storage of the item until it can be shipped out of Thule Air Base during the summer months.

Types of PCB contaminated items which have been considered:

• Transformers

• Ballast in Fluorescent light fixtures

• RF-filters

• Different containers with dielectric fluid

• Capacitors

• Circuit breaks

• Different items as microwave ovens, small transformers for laptops, mobile phones etc.

Provided an item contains less than 50 ppm PCB or is the private property owned by installation personnel, it shall not to be inventoried.

Transformers

If a transformer is found at TAB and it is suspected that it could be a PCB transformer (i.e. not included in the inventory in appendix 2), Environmental Engineering will contacted.

Environmental Engineering will coordinate storage, sampling and shipping with GC Operations, the Fire Department and the DLA-DS office.

• If the transformer does not contain PCB, it will be drained and disposed of at the sanitary landfill.

• If there is any doubt about the transformer containing PCB, it will be sampled and analyzed by a certified laboratory for PCB (Arochlors). Until analytical results to the contrary are received, such items will be treated as PCB transformers.

The analysis will be paid for by funds managed by GC/EE.

Storage of confirmed and suspected PCB items will occur under GC/Supply control in a secured area.

Ballasts

Fluorescent light fixtures manufactured before 1974 are likely to have ballasts containing PCB, and light fixtures of this type are still in use at various locations at Thule Air Base. The ballasts are not considered to pose any danger as long as they are not leaking. The amount of this type of ballast being found at Thule Airbase is rapidly declining, as the projects to replace the ballasts are completed.

Thule Air Base, Greenland Page 10 of 20 FY-15

When the ballasts are replaced during normal maintenance or light fixture replacement projects the PCB containing or suspected to contain PCB, ballasts shall be turned in at an approved accumulation point IAW Hazardous Waste Management Plan CDRL CEV-15B.

RF-filters

Filtron PCB containing filters in Bldg. 4002 have been disconnected and removed. Work was completed October 1996. Filters were disposed of through DLA-DS summer 1997.

RF-filters are no longer in use in Bldg. 4012. The filters were disposed of through DLA-DS in 2004.

Any other suspect electronic filter will be analyzed for PCB content prior to its disposal by GC/Supply through the DLA-DS function.

Cables

Cables at Thule AB have been suspected of containing PCB. However, even after comprehensive sampling efforts, no cables sample has ever been analyzed for PCB above trace levels. This sampling is well documented in files maintained by GC/EE; for example in the Final report:

Disposal of PCB Containing Cables, Pilot Study, Greenland Contractors, 26th September 2005 (Project: WWCX 71-3591).

3.6 PCB Storage and disposal

No PCBs will be disposed of in Greenland and all disposals will be conducted through the DLA- DS function. PCB items will be stored IAW the FGS.

When first found, the PCB items such as ballasts are stored at HWAPs even though PCBs are not technically hazardous waste. The HWAP is inspected weekly by the GC/Supply and if PCB items are found at the HWAP they will be transferred to the GC/Supply controlled DLA-DS main building.

For larger items which cannot be stored at a HWAP, such as transformers, the GC/Supply function will be contacted in order to coordinate the proper actions to take for correct storage of the item. Bldg 937 is designated for PCB transformer storage.

To meet requirements for shipping PCB waste to the United States, prior to any shipment of PCB containing items to the US a letter signed by 821 SPTS/CE will provided by the air force stating ownership and that the items contains PCBs and have not been tampered with (except for sampling purpose of for instance transformers and the analytical result will follow the item).

Environmental Engineering together with GC/Supply will prepare a draft letter for 821st SPTS/CE to sign.

PCB items that are not currently owned and has not previously been owned by the Air Forces shall be the responsibility of the current owner.

Thule Air Base, Greenland Page 11 of 20 FY-15

3.7 PCB Spills

If any storage PCB items leaks or causes a spill the response to this will follow the guidance provided in FGS chapter 14. Spills will be handled as hazardous waste spill. Absorbent materials used in the cleanup process will be disposed of through the DLA-DS function. Funding requirements for managing PCB contaminated soil will be coordinated with 21 CES/CEIE

A leaking PCB item shall be either drained sufficiently or an appropriate containment shall be provided IAW FGS chapter 14.

Thule Air Base, Greenland Page 12 of 20 FY-15

4.0 ACRONYMS

AB Air Base

AFI Air Force Instruction

CES Civil Engineering Squadron (Peterson AFB)

CEIE Environmental Office (Peterson AFB)

DLA-DS Defense Logistics Agency – Disposition Services

EPA U.S. Environmental Protection Agency

FGS Final Governing Standards

GC Greenland Contractors

GC/EE Greenland Contractors/Environmental Engineering

Lb Pound(s)

OPR Office of primary responsibility

PCB Polychlorinated Biphenyl

PPB

PPM

Parts per billion

Parts per million

TAB Thule Air Base

TSCA Toxic Substances Control Act

UFM

USAF

Utilities Facilities Maintenance

United States Air Force

Thule Air Base, Greenland Page 13 of 20 FY-15

APPENDIX 1: PCB INVENTORY

Item

Location Notes

Unlabeled Transformer #1

(Black, Picture below)

In storage in #937, Awaiting transport off-base.

100% PCB

Property of Telepost (non-US origin)

Unlabelled Transformer #2

(Gray)

In storage in #937, Awaiting transport off-base

684 µg/kg PCB (non PCB)

Property of Telepost (non-US origin)

Ballasts with dielectric fluid, unknown production years.

50 gal drum of discarded ballasts stored in bldg 935 (app. 50% full 1 Jan 2015).

In use basewide in old facilities with unmodified lighting systems

Unlabelled transformer #1

Thule Air Base, Greenland Page 14 of 20 FY-15

APPENDIX 2: Inventory of Transformers

Transformers – Airfield

Facility

Transformer Information

PCB

Test/ Qty

Info from Remarks Manufacturer Model/Serial No. kVA Type

01102 N/A N/A N/A N/A N/A TP No Transformer

01103 General Electric 9T25Y4282/JC 30 Dry N/A SV In Operation General Electric 9T21B9120/GT 25 Dry N/A SV In Operation

01104 OLSUN Electrics corporation 32040-A-112468 37,5 Dry N/A SV In Operation

01105

ESCO transformer Magnatrans 12233989 300 Dry N/A SV In Operation ESCO transformer Magnatrans 1118/2329/AFT 150 Dry N/A SV In Operation Crouse-Hinds Airport Lighting product 32960-D-20-9-20-05-0780 20 Dry N/A SV In Operation Crouse-Hinds Airport Lighting product 82960-D-15-9-20-05-0780 20 Dry N/A SV In Operation Crouse-Hinds Airport Lighting product 82960-D-20-9-20-05-0783 20 Dry N/A SV In Operation Crouse-Hinds Airport Lighting product 82960-D-30-9-20-05-0784 20 Dry N/A SV In Operation Crouse-Hinds Airport Lighting product 82960-D-20+9-20-05-0781 20 Dry N/A SV In Operation Crouse-Hinds Airport Lighting product 82960-D-20-9-20-05-0782 20 Dry N/A SV In Operation Crouse-Hinds Airport Lighting product 82960-D-20-9-20-05-0509 20 Dry N/A SV In Operation Crouse-Hinds Airport Lighting product 82960-D-20-9-20-05-0770 20 Dry N/A SV In Operation Crouse-Hinds Airport Lighting product 82960-D-20-9-20-05-0772 20 Dry N/A SV In Operation Crouse-Hinds Airport Lighting product 82960-D-07-1-66-01/0181 6,6 Dry N/A SV In Operation Crouse-Hinds Airport Lighting product 82960-D-07-1-66-01/0180 6,6 Dry N/A SV In Operation Crouse-Hinds Airport Lighting product 82960-D-07-1-66-01/0179 6,6 Dry N/A SV In Operation Crouse-Hinds Airport Lighting product 82960-D-07-1-66-01/0182 6,6 Dry N/A SV In Operation

01117 N/A N/A N/A N/A N/A TP No Transformer 01118 N/A N/A N/A N/A N/A TP No Transformer 01126 N/A N/A N/A N/A N/A TP No Transformer 01128 Westinghouse N/A N/A Dry N/A SV In Operation Hammond Power Solutions MF025LE / - 25 Dry N/A SV In Operation General Electric 9T21B9120 / LS 25 Dry N/A SV In Operation

Transformers - DET-1

Facility

Transformer Information

PCB

Test/ Qty

Info from Remarks Manufacturer Model/Serial No. kVA Type

Virginia Transformer Corp 321000H511-4552A 1000 DRY N/A SV In Operation Virginia Transformer Corp 321000H511-4552B 1000 DRY N/A SV In Operation ITE Power Transformer 3F3Y225-C9676-587 225 DRY N/A SV In Operation Square D company 24158684-002-041 750 DRY N/A SV In Operation Square D company 24158684-005-01 750 DRY N/A SV In Operation Square D company 36349-17112-004 500 DRY N/A SV In Operation

Jefferson Electric 323-3194 30 DRY N/A SV In Operation General Electric 9T23B3872/ 475A541XAC001-R0 30 DRY N/A SV In Operation ITE Power Transformer 3F5Y075-ES / DO462-687 75 DRY N/A SV In Operation ITE Power Transformer 3F5Y075-ES / DO483-687 75 DRY N/A SV In Operation

Siemens 3F3Y030-OL 30 DRY N/A SV In Operation

ITE Power Transformer

3F3Y030-ES /

29-C9617-487 30 DRY N/A SV In Operation

ITE Power Transformer

3F3Y030-ES /

29-C7566-1286 30 DRY N/A SV In Operation

Thule Air Base, Greenland Page 15 of 20 FY-15

Transformers – 12 SWS

Transformer Information

PCB

Test/Qty Info from Remarks Manufacturer Model/Serial No. kVA Type

Siemens 3F3Y045/J89B0774 45 Dry N/A SV In Operation Siemens 3F3Y045/J89B0769 45 Dry N/A SV In Operation ITE-Power-Transformer 3F3Y075/475A645CA001 75 Dry N/A SV In Operation Square D Company 75T3H/34349-17212-064 75 Dry N/A SV In Operation Cutler-Hammer V48M28T75J/J98K2732 75 Dry N/A SV In Operation Square D Company 45T3H/33749-17212-082 45 Dry N/A SV In Operation Westinghouse electric corporation 88601-232-A-034 A N/A Dry N/A SV In Operation Westinghouse electric corporation 88601-232-A-034 B N/A Dry N/A SV In Operation Square D Company 920694-A1/ 480Y/277 1000 OIL < 1ppm SV In Operation Square D Company 920694-A1/ 480Y/277 1000 OIL < 1ppm SV In Operation Square D Company 920694-A1/ 480Y/277 1000 OIL < 1ppm SV In Operation Square D Company 920694-A1/ 480Y/277 1000 OIL < 1ppm SV In Operation Square D Company 920694-A1/ 208Y/120 750 OIL < 1ppm SV In Operation Square D Company 920694-A1/ 208Y/120 750 OIL < 1ppm SV In Operation Square D Company 920694-A1/ 208Y/120 500 OIL < 1ppm SV In Operation Square D Company 920694-A1/ 208Y/120 500 OIL < 1ppm SV In Operation Westinghouse electric corporation 482645B-670122 N/A Dry N/A SV In Operation

RTE Small Power 74CA14D231/886003882 1752 OIL < 1ppm SV In Operation

RTE Small Power 74CA14D231/886003882 1752 OIL < 1ppm SV In Operation

BBC- Brown Boveri 37-55667-B/ 24-30461 1500 Dry N/A SV In Operation BBC- Brown Boveri 37-55667-A/34-3046 1500 Dry N/A SV In Operation

RTE Small Power 74GA14D24L/886003883 1725 OIL < 1ppm SV In Operation

Square D Company 920694-H1/208Y1120 750 OIL < 1ppm SV In Operation Square D Company 920694-E1/ 208Y/120 500 OIL < 1ppm SV In Operation Square D Company 920694-G1/ 480Y/277 1000 OIL < 1ppm SV In Operation Square D Company 920694-A2/ 480Y/277 1000 OIL < 1ppm SV In Operation Square D Company 920694-G2/ 480Y/277 1000 OIL < 1ppm SV In Operation Square D Company 34349-17222-045 75 Dry N/A SV In Operation Square D Company 34759-17212-107/23261580-001 75 Dry N/A SV In Operation ITE Electrical products/ Siemens 3F3Y030/475A644XAG001RO 30 Dry N/A SV In Operation Federal Pacific 50340-M/ 1/84 15 Dry N/A SV In Operation

Square D Company 34759-17212-107/ 23261580-001 75 Dry N/A SV In Operation

ITE Electrical products /Siemens 3F3Y030/475A644XAG001RO 30 Dry N/A SV In Operation

Federal Pacific 50340-M/ 1/84 15 Dry N/A SV In Operation

Square D Company 30T3HF/33749-17212-082 30 Dry N/A SV In Operation Square D Company 35149-17212-059 112,5 Dry N/A SV In Operation Square D Company 30T3HF/33749-17212-082 30 Dry N/A SV In Operation

Square D Company 34759-17212-107/ 23261580-002 75 Dry N/A SV In Operation

Transformers – Vortac

Transformer Information

PCB

Test/Qty Info from Remarks Manufacturer Model/ Serial No. kVA Type

05001 N/A N/A N/A Dry N/A TP In Operation

05003 N/A N/A N/A N/A N/A TP No Transformer

Transformers – Cabins etc. off base

Transformer Information

PCB

Test/Qty

Info from Remarks Manufacturer Model/ Serial No. kVA Type

02300 N/A N/A N/A N/A N/A TP No Transformer 02301 N/A N/A N/A N/A N/A TP No Transformer 02302 N/A N/A N/A N/A N/A TP No Transformer 02303 N/A N/A N/A N/A N/A TP No Transformer 02304 N/A N/A N/A N/A N/A TP No Transformer 02305 N/A N/A N/A N/A N/A TP No Transformer

Thule Air Base, Greenland Page 16 of 20 FY-15

Transformers - Storm shelters

Transformer Information

PCB

Test/Qty

Info from Remarks Manufacturer Model/ Serial No. kVA Type

02201 N/A N/A N/A N/A N/A SV No Transformer 02202 N/A N/A N/A N/A N/A SV No Transformer 02203 N/A N/A N/A N/A N/A SV No Transformer 02204 N/A N/A N/A N/A N/A SV No Transformer 02205 N/A N/A N/A N/A N/A SV No Transformer 02206 N/A N/A N/A N/A N/A SV No Transformer 02207 N/A N/A N/A N/A N/A SV No Transformer 02208 N/A N/A N/A N/A N/A SV No Transformer 02209 N/A N/A N/A N/A N/A SV No Transformer 02210 N/A N/A N/A N/A N/A SV No Transformer 02211 N/A N/A N/A N/A N/A SV No Transformer 02212 N/A N/A N/A N/A N/A SV No Transformer 02224 N/A N/A N/A N/A N/A SV No Transformer 02225 N/A N/A N/A N/A N/A SV No Transformer

Transformers - North Mtn. + Lake Crescent

Transformer Information

PCB

Test/Qty

Info from Remarks Manufacturer Model/ Serial No. kVA Type

01620 N/A N/A N/A N/A N/A TP No Transformer 01695 N/A N/A N/A N/A N/A TP No Transformer 01696 N/A N/A N/A N/A N/A TP No Transformer 01701 N/A N/A N/A N/A N/A TP No Transformer 62004 N/A N/A N/A N/A N/A TP No Transformer 65027 N/A N/A N/A N/A N/A TP No Transformer

Transformers - South Mtn. + D-launch + Landfill

Transformer Information

PCB

Test/Qty

Info from Remarks

Manufacturer Model/Serial No. kVA Type

01949 N/A N/A N/A N/A N/A TP No Transformer 01950 N/A N/A N/A N/A N/A TP No Transformer 01955 N/A N/A N/A N/A N/A TP No Transformer 01957 N/A N/A N/A N/A N/A TP No Transformer 01958 N/A N/A N/A N/A N/A TP No Transformer 01960 N/A N/A N/A N/A N/A TP No Transformer 01961 N/A N/A N/A N/A N/A TP No Transformer 01969 N/A N/A N/A N/A N/A TP No Transformer 01970 N/A N/A N/A N/A N/A TP No Transformer 01971 N/A N/A N/A N/A N/A TP No Transformer 01973 N/A N/A N/A N/A N/A TP No Transformer 01974 N/A N/A N/A N/A N/A TP No Transformer 01975 N/A N/A N/A N/A N/A TP No Transformer 01991 N/A N/A N/A N/A N/A TP No Transformer 02000 N/A N/A N/A N/A N/A TP No Transformer 02044 N/A N/A N/A N/A N/A TP No Transformer 02045 N/A N/A N/A N/A N/A TP No Transformer 02046 N/A N/A N/A N/A N/A TP No Transformer 02050 N/A N/A N/A N/A N/A TP No Transformer 02060 N/A N/A N/A N/A N/A TP No Transformer 02070 N/A N/A N/A N/A N/A TP No Transformer 50020 N/A N/A N/A N/A N/A TP No Transformer 60100 N/A N/A N/A N/A N/A TP No Transformer 65032 N/A N/A N/A N/A N/A TP No Transformer 65085 N/A N/A N/A N/A N/A TP No Transformer

Thule Air Base, Greenland Page 17 of 20 FY-15

Transformers – Electrical substations on Main Base

Transformer Information PCB

Test/Qty Info from Remarks Manufacturer Model/Serial No. kVA Type

1203 / by pavillion Square D Company HVMH 3055025 N/A Dry N/A SV In Operation 1307 N/A N/A N/A N/A N/A SV No Transformer 1391 / M-plant Cutle-Hammer J03E05976 225 Dry N/A SV In Operation

1391 / M-plant FPT Federal pacific trans company 53934 30 Dry N/A SV In Operation

1391 / M-plant Westinghouse DCV 3684-0102 1000 Dry N/A SV In Operation 1391 / M-plant Westinghouse DCV 3684-0101 1000 Dry N/A SV In Operation 1391 / M-plant ABB small power 1LUS/HL14350-001 10.000 Dry N/A SV In Operation 1391 / M-plant ABB small power 1LUS/HL14349-001 10.000 Dry N/A SV In Operation

1391 / M-plant 3 reactors connected to the above transformer?

067/45482+067/4548 3+067/45484 1400 OIL < 1ppm SV In Operation

1401/ K-Plant General Electric B3-30202 150 Dry N/A SV In Operation 1401/ K-Plant SAB NIFE INC 846650 150 Dry N/A SV In Operation 7001 N/A N/A N/A N/A N/A SV No Transformer 7002 Square D Company 1332R 240 Dry N/A SV In Operation 7004 General Electric 151638 120 Dry N/A SV In Operation 7005 N/A N/A N/A N/A N/A SV No Transformer 7006 N/A N/A N/A N/A N/A SV No Transformer 7008 N/A N/A N/A N/A N/A SV No Transformer 7009 N/A N/A N/A N/A N/A SV No Transformer 7010 N/A N/A N/A N/A N/A SV No Transformer 7012 N/A N/A N/A N/A N/A SV No Transformer 7014 Square D Company HTC-7014-54 240 Dry N/A SV In Operation 7016 Powerstat 1749 240 Dry N/A SV In Operation 7017 N/A N/A N/A N/A N/A SV No Transformer 7023 General Electric 912181005 G2 7,5 Dry N/A SV In Operation

7026 Westinghouse 90B0248 7,5 Dry N/A SV None In Operation

7027 N/A N/A N/A N/A N/A SV No Transformer 7029 Westinghouse 88A244040 75 Oil N/A SV Not in Operation

Electric power Equipment company 86-906-300 / 8731607 300 Dry N/A SV In Operation

7038 N/A N/A N/A N/A N/A TP No transformer

Electric power Equipment company 86-906-300 / 8615011 300 Dry N/A SV Not In Operation

7041 N/A N/A N/A N/A N/A SV No Transformer 7079 Square D Company 192730-9 300 Dry N/A SV In Operation 7097 Square D Company 192730-9 300 Dry N/A SV In Operation 7098 Square D Company 192730-9 300 Dry N/A SV In Operation 7101 Square D Company 192730-0 300 Dry N/A SV In Operation 7103 Square D Company 192730-7 300 Dry N/A SV In Operation 7107 TRANSFORMERS PRESENT N/A N/A N/A N/A SV In Operation 7113 Square D Company 192730-1 300 Dry N/A SV In Operation 7116 TRANSFORMERS PRESENT N/A N/A N/A N/A SV In Operation 7118 Square D Company 034091-A1 300 Dry N/A SV In Operation 7118 Square D Company 034091-B1 300 Dry N/A SV In Operation 7124 Square D Company N/A N/A Dry N/A SV In Operation 7133 Square D Company 35176-1722-013 150 Dry N/A SV In Operation 7143 Square D Company ? / 192730-6 300 Dry N/A SV In Operation

Electric power Equipment company 86-906-150 / 8615003 150 Dry N/A SV In Operation

7206 Westinghouse N/A N/A Dry N/A SV In Operation 7236 / TOW Westinghouse N/A N/A Dry N/A SV In Operation 7244 Westinghouse N/A N/A Dry N/A SV In Operation 7272 N/A N/A N/A N/A N/A SV No Transformer 7287 N/A N/A N/A N/A N/A SV No Transformer 7324 Westinghouse N/A N/A Dry N/A SV In Operation 7341 Square D Company 014079-A1 12,5 Dry N/A SV In Operation 7363 N/A N/A N/A N/A N/A SV No Transformer 7364 N/A N/A N/A N/A N/A SV No Transformer 7421 N/A N/A N/A N/A N/A TP No Transformer 7443 N/A N/A N/A N/A N/A SV No Transformer 7454 N/A N/A N/A N/A N/A SV No Transformer 7461 N/A N/A N/A N/A N/A SV No Transformer 7517 N/A N/A N/A N/A N/A SV No Transformer

Thule Air Base, Greenland Page 18 of 20 FY-15

Transformers – Electrical substations on Main Base

Transformer Information PCB

Test/Qty Info from Remarks Manufacturer Model/Serial No. kVA Type

7553 N/A N/A N/A N/A N/A SV No Transformer 7557 N/A N/A N/A N/A N/A TP No Transformer 7561 Cutle-Hammer T-3991-1 150 Dry N/A SV In Operation 7562 N/A N/A N/A N/A N/A TP No Transformer 7571 N/A N/A N/A N/A N/A SV No Transformer

Electric power Equipment company 86-906-300 / 8615012 300 Dry N/A SV In Operation

7580 N/A N/A N/A N/A N/A SV No Transformer 7593 N/A N/A N/A N/A N/A SV No Transformer 7605 Square D Company 35176-17112-013 150 Dry N/A SV In Operation 7608 / fitness Square D company 192730-1 300 Dry N/A SV In Operation 7617 Square D company N/A N/A Dry N/A SV In Operation

Electric power Equipment company N/A N/A Dry N/A SV In Operation

7628 N/A N/A N/A N/A N/A TP No Transformer 7705 N/A N/A N/A N/A N/A SV No Transformer 7708 N/A N/A N/A N/A N/A SV No Transformer 7750 N/A N/A N/A N/A N/A SV No Transformer 7836 Power former 227-295-010 225 Dry N/A SV In Operation 7933 N/A N/A N/A N/A N/A TP No Transformer 7976 General Electric 9T25Y4282 30 Dry N/A SV In Operation 7990 New Transformer installed N/A N/A Dry N/A SV In Operation

Transformers – Various Locations (not substations)

Transformer Information

PCB

Test/Qty

Info from Remarks Manufacturer

Model/ Serial No. kVA Type

# 200 Westinghouse unmarked N/A Dry N/A SV In Operation # 241 N/A N/A N/A Dry N/A TP In Operation # 615 N/A N/A N/A Dry N/A TP In Operation # 616 N/A N/A N/A Dry N/A TP In Operation # 617 N/A N/A N/A Dry N/A TP No Transformer # 629 / HG # 9 N/A N/A N/A N/A N/A TP No Transformer # 630 / HG # 10 N/A N/A N/A N/A N/A TP No Transformer

# 933 Federal pacific transformer company 54043 300 Dry N/A TP In Operation

# 937 N/A N/A N/A OIL 1 ppm FVC Not in Operation # 937 N/A N/A N/A OIL 100% PCB FVC Not in Operation # 972 (Non AF) N/A N/A N/A N/A N/A TP No Transformer # 974 N/A N/A N/A Dry N/A TP In Operation # 976 N/A N/A N/A N/A N/A TP No Transformer # 1408 N/A N/A N/A Dry N/A TP In Operation # 1411 Allis Chalmers 3200253 150 Dry N/A TP In Operation # 4003 ABB (from 1997) 069WO400AQ 69 N/A N/A SV To be removed

Thule Air Base, Greenland Page 19 of 20 FY-15

APPENDIX 3: ENVIRONMENTAL REVIEW COMMENTS

GC Reply

Comment no. 1: DRMO has been changed to DLA-DS when appropriate. DRMO was also used to refer to the BMC on base Disposition Services. The on base services is GC/Supply.

Thule Air Base, Greenland Page 20 of 20 FY-15

APPENDIX 4: Distribution list (Distributed in PDF format)

Requiring Office 21 CES/CEIE donald.chase@us.af.mil

Program Office 21 SW/PMD 21sw.pmd.thule@us.af.mil

Copies 821 ABG/CC 821SPTS.cc.wf@us.af.mil

821 SPTS/CE 821SPTSCEDISTRO@US.AF.MIL

Greenland Contractors, Thule Air Base Distributed on GC LAN mailto:donald.chase@us.af.mil� mailto:21sw.pmd.thule@peterson.af.mil�

1.0 LETTER OF INSTRUCTION
1.1 Security and Administrative Instructions
2.0 INTRODUCTION
2.1 Polychlorinated biphenyls.
2.2 Examples - PCB containing products.
3.0 PCB IDENTIFICATION, REMOVAL, AND INVENTORY
3.1 PCB on Thule Air Base
3.2 Requirements for PCB-transformers
3.3 Definitions of different PCB items
3.4 Requirements for PCB items
3.5 Procedures for potential PCB contaminated items
3.6 PCB Storage and disposal
3.7 PCB Spills
4.0 ACRONYMS
APPENDIX 1: PCB INVENTORY
APPENDIX 2: Inventory of Transformers
APPENDIX 3: ENVIRONMENTAL REVIEW COMMENTS
APPENDIX 4: Distribution list