OUST-AR RANGE PROJECTS FY19
SECTION 32 31 13.53
HIGH-SECURITY CHAIN LINK FENCES AND GATES
04/08
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM A 116 (2005) Standard Specification for Metallic-Coated, Steel Woven Wire Fence Fabric
ASTM A 121 (2007) Standard Specification for Metallic-Coated Carbon Steel Barbed Wire
ASTM A 153/A 153M (2009) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware
ASTM A 176 (1999; R 2009) Standard Specification for Stainless and Heat-Resisting Chromium Steel Plate, Sheet, and Strip
ASTM A 392 (2007) Standard Specification for Zinc-Coated Steel Chain-Link Fence Fabric
ASTM A 478 (1997; R 2008) Standard Specification for Chromium-Nickel Stainless Steel Weaving and Knitting Wire
ASTM A 491 (2007) Standard Specification for Aluminum-Coated Steel Chain-Link Fence Fabric
ASTM A 666 (2003) Standard Specification for Annealed or Cold-Worked Austenitic Stainless Steel Sheet, Strip, Plate and Flat Bar
ASTM A 702 (1989; R 2006) Standard Specification for Steel Fence Posts and Assemblies, Hot Wrought
ASTM A 780/A 780M (2001; R 2006) Standard Practice for Repair of Damaged and Uncoated Areas of Hot-Dip Galvanized Coatings
ASTM A 824 (2001; R 2007) Standard Specification for Metallic-Coated Steel Marcelled Tension Wire for Use With Chain Link Fence
ASTM B 117 (2009) Standing Practice for Operating Salt Spray (Fog) Apparatus
ASTM C 94/C 94M (2009a) Standard Specification for Ready-Mixed Concrete
ASTM F 1043 (2008) Strength and Protective Coatings on Metal Industrial Chain-Link Fence Framework
ASTM F 1083 (2008) Standard Specification for Pipe, Steel, Hot-Dipped Zinc Coated (Galvanized) Welded, for Fence Structures
ASTM F 1184 (2005) Industrial and Commercial Horizontal Slide Gates
ASTM F 567 (2007) Standard Practice for Installation of Chain Link Fence
ASTM F 626 (2008) Standard Specification for Fence Fittings
ASTM F 668 (2007) Poly(Vinyl Chloride) (PVC) and other Organic Polymer-Coated Steel Chain-Link Fence Fabric
ASTM F 883 (2009) Padlocks
ASTM F 900 (2005) Industrial and Commercial Swing Gates
U.S. GENERAL SERVICES ADMINISTRATION (GSA)
FS RR-F-191 (Rev K) Fencing, Wire and Post Metal (and Gates, Chain-Link Fence Fabric, and Accessories)
FS RR-F-191/1 (Rev D) Fencing, Wire and Post, Metal (Chain-Link Fence Fabric)
FS RR-F-191/2 (Rev D) Fencing, Wire and Post, Metal (Chain-Link Fence Gates)
FS RR-F-191/3 (Rev D) Fencing, Wire and Post, Metal (Chain-Link Fence Posts, Top Rails and Braces)
FS RR-F-191/4 (Rev D) Fencing, Wire and Post, Metal (Chain-Link Fence Accessories)
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Fence Installation Installation Drawings Location of gate, corner, end, and pull posts Gate Assembly Turnstiles Gate Hardware and Accessories
Installation drawings in accordance with paragraph titled, "ASSEMBLY AND INSTALLATION DRAWINGS" of this section.
SD-03 Product Data
Fence Installation Gate Assembly Gate Hardware and Accessories
Manufacturer's catalog data.
SD-04 Samples
Fabric Posts Post Caps Braces Line Posts Sleeves Tension Wire Barbed Wire Barbed Wire Supporting Arms Stretcher Bars Gate Posts Gate Hardware and Accessories Turnstiles Padlocks Wire Ties
Samples as described within this section.
SD-06 Test Reports
Weight in ounces for zinc coating
SD-07 Certificates
Chain Link Fence
Submit reports, signed by an official authorized to certify on behalf of the manufacturer, attesting that the chain link fence and component materials meet the specified requirements.
Zinc Coating PVC coating aluminum alloy coating Fabric Barbed Wire Stretcher Bars Gate Hardware and Accessories Concrete
GATE OPERATOR
SD-08 Manufacturer's Instructions
Submit Manufacturer's instructions for the following items:
Fence Installation Gate Assembly Hardware Assembly Accessories
SD-10 Operation and Maintenance Data
Electro-Mechanical Locks Gate Operator
Submit operating and maintenance instructions
1.3 QUALITY ASSURANCE
1.3.1 Required Report Data
Submit reports of chain-link fencing listing and accessories regarding weight in ounces for zinc coating.
1.3.2 Assembly and Installation Drawings
Submit complete Fence Installation Drawings for review and approval by the Contracting Officer prior to shipment. Drawing details shall include, but are not limited to: Fence Installation, Location of gate, corner, end, and pull posts, Gate Assembly, Turnstiles, and Gate Hardware and Accessories.
1.4 DELIVERY, STORAGE, AND HANDLING
Deliver materials to site in an undamaged condition. Store materials off the ground to provide protection against oxidation caused by ground contact.
PART 2 PRODUCTS
2.1 FENCE FABRIC
2.1.1 General
Provide ASTM A 392, Class 1, zinc-coated steel wire with minimum coating weight of 1.2 ounces of zinc per square foot of coated surface. Set fabric height as shown. Fabric shall be twisted and barbed on the top selvage and knuckled on the bottom selvage. Secure fabric to posts using stretcher bars or ties spaced 15 inches on center, or by integrally weaving to integral fastening loops of end, corner, pull, and gate posts for full length of each post. Install fabric on opposite side of posts from area being secured.
2.2 POSTS
2.2.1 Metal Posts for Chain Link Fence
a. Provide posts conforming to ASTM F 1083, zinc-coated. Group IA, with external coating Type A steel pipe. Provide sizes as shown on the drawings. Line posts and terminal (corner, gate, and pull) posts selected shall be of the same designation throughout the fence.
Provide gate post for the gate type specified subject to the limitation specified in ASTM F 900 and/or ASTM F 1184. Post spacing shall conform to the recommended guidelines as set forth in the CLFMI "Wind Load Guide for the Selection of Line Post Spacing and Size" unless specified to exceed those guidelines.
2.2.2 Accessories
a. Provide accessories conforming to ASTM F 626. Ferrous accessories shall be zinc coated.
b. Furnish truss rods for each terminal post. Provide truss rods with turnbuckles or other equivalent provisions for adjustment.
c. Provide Barbed wire supporting arms of the single 45 degree outward angle 3-strand arm type and of the design required for the post furnished. Secure arms by riveting.
d. Furnish post caps in accordance with manufacturer's standard accessories.
e. Provide 9 gauge steel tie wire for attaching fabric to rails, braces, and posts and match the coating of the fence fabric.
Miscellaneous hardware coatings shall conform to ASTM A 153/A 153M unless modified.
2.3 BRACE RAILS
a. ASTM F 1083, zinc-coated, Group IA, steel pipe, size 1.66 inch O.D.
b.
2.4 WIRE
2.4.1 Wire Ties
Provide wire ties constructed of the same material as the fencing fabric.
2.4.2 Barbed Wire
Provide barbed wire conforming to ASTM A 121 zinc-coated, Type Z, Class 3, or aluminum-coated, Type A, with 12.5 gauge wire with 14 gauge, round, 4-point barbs spaced no more than 5 inches apart.
2.4.3 Tension Wire
Provide Type I or Type II tension wire, Class 4 coating, in accordance with ASTM A 824. Provide 7 gauge coil spring wire for top and bottom wire.
2.6 CONCRETE
ASTM C 94/C 94M, using 3/4 inch maximum size aggregate, and having minimum compressive strength of 3000 psi at 28 days. Grout shall consist of one part portland cement to three parts clean, well-graded sand and the minimum amount of water to produce a workable mix.
2.7 GATES
2.7.1 Gate Assembly
Provide gate assembly conforming to ASTM F 900 and/or ASTM F 1184 of the type and swing shown. Provide gate frames conforming to strength and coating requirements of ASTM F 1083 for Group IA, steel pipe, with external coating Type A, nominal pipe size (NPS) 1-1/2. Provide gate frames conforming to strength and coating requirements of ASTM F 1043, for Group IC, steel pipe with external coating Type A. Gate fabric shall be as specified for chain link fabric.
2.7.2 Gate Leaves
For gate leaves, more than 8 feet wide, provide either intermediate members and diagonal truss rods or tubular members as necessary to provide rigid construction, free from sag or twist. Gate leaves less than 8 feet wide shall have truss rods or intermediate braces. Provide intermediate braces on all gate frames with an electro-mechanical lock. Attach fabric to the gate frame by method standard with the manufacturer except that welding will not be permitted.
2.7.3 Gate Hardware and Accessories
Furnish and install latches, hinges, stops, keepers, rollers, and other hardware items as required for the operation of the gate. Arrange latches for padlocking so that the padlock will be accessible from both sides of the gate. Provide stops for holding the gates in the open position. For high security applications, each end member of gate frames shall be extended sufficiently above the top member to carry three strands of barbed wire in horizontal alignment with barbed wire strands on the fence.
2.10 GATE OPERATOR
Provide electric gate operators for sliding gates as follows: Electrical gate operators shall have a right angle gearhead instantly reversing motor with magnetic drum-type brake, friction disc clutch, reversing starter with thermal overload protection, and a chain-driven geared rotary-type automatic limit switch. Gears shall consist of a hardened steel machine cut worm and mating bronze gear. All gears and bearings shall operate in a bath of oil. Gate operators with V-belt pulleys are not allowed. Equip gate operators with an emergency release to allow the gate to be operated manually. The emergency release mechanism shall be capable of being locked in the engaged or disengaged position. Provide positive stops on the gate tracks as a backup to the limit switches.
2.11 ELECTRO-MECHANICAL LOCKS
Electro-mechanical locking devices for sliding gates and personnel gates shall be solenoid actuated such that the deadbolt retracts when the solenoid is energized and remains electrically retracted until the gate is closed. Provide continuous duty type selenoid, rated for 120V ac, 60Hz operation. The locking device shall be unlockable by key and keyed on both sides. Status of the electro-mechanical lock shall be monitored by two limit switches (integral to the locking device) wired in series. One switch shall monitor the deadlock lever and the other monitor the locking tongue.
PART 3 EXECUTION
3.1 FENCE INSTALLATION
Perform complete installation conforming to ASTM F 567.
3.1.1 Line and Grade
Install fence to the lines and grades indicated. Clear the area on either side of the fence line to the extent indicated. Space line posts equidistant at intervals not exceeding 10 feet. Terminal (corner, gate, and pull) posts shall be set at abrupt changes in vertical and horizontal alignment. Provide fabric continuous between terminal posts; however, runs between terminal posts shall not exceed 500 feet. Repair any damage to galvanized surfaces, including welding, with paint containing zinc dust in accordance with ASTM A 780/A 780M.
3.1.2 Excavation
Clear all post holes of loose material. Spread waste material where directed. Eliminate ground surface irregularities along the fence line to the extent necessary to maintain a 2 inch clearance between the bottom of the fabric and finish grade.
3.2 POST INSTALLATION
3.2.1 Earth and Bedrock
a. Set posts plumb and in alignment. Except where solid rock is encountered, set posts in concrete to the depth indicated on the drawings. Where solid rock is encountered with no overburden, set posts to a minimum depth of 18 inches in rock. Where solid rock is covered with an overburden of soil or loose rock, set posts to the minimum depth indicated on the drawing unless a penetration of 18 inches in solid rock is achieved before reaching the indicated depth, in which case terminate depth of penetration. Grout all portions of posts set in rock.
b. Portions of posts not set in rock shall be set in concrete from the rock to ground level. Posts set in concrete shall be set in holes not less than the diameter shown on the drawings. Make diameters of holes in solid rock at least 1 inch greater than the largest cross section of the post. Thoroughly consolidate concrete and grout around each post, free of voids and finished to form a dome. Allow concrete and grout to cure for 72 hours prior to attachment of any item to the posts.
Test fence post rigidity by applying a 50 pound force on the post, perpendicular to the fabric, at 5 feet above ground. Post movement measured at the point where the force is applied shall be less than or equal to 3/4 inch from the relaxed position. Test every tenth post for rigidity. When a post fails this test, make further tests on the next four posts on either side of the failed post. All failed posts shall be removed, replaced, and retested at the Contractor's expense.
3.4 FABRIC INSTALLATION
a. Install chain link fabric on the side of the post indicated.
Attach fabric to terminal posts with stretcher bars and tension bands.
Space bands at approximately 15 inch intervals. Install fabric and pull taut to provide a smooth and uniform appearance free from sag, without permanently distorting the fabric diamond or reducing the fabric height. Fasten fabric to line posts at approximately 15 inch intervals and fastened to all rails and tension wires at approximately 24 inch intervals.
b. Cut fabric by untwisting and removing pickets. Accomplish splicing by weaving a single picket into the ends of the rolls to be joined.
The bottom of the installed fabric shall be 2 plus or minus 1/2 inch above the ground.
c. After the fabric installation is complete, exercise the fabric by applying a 50 pound push-pull force at the center of the fabric between posts; the use of a 30 pound pull at the center of the panel shall cause fabric deflection of not more than 2.5 inches when pulling fabric from the post side of the fence; every second fence panel shall meet this requirement; resecure and retest all failed panels at the Contractor's expense.
3.5 SUPPORTING ARMS
Install barbed wire supporting arms and barbed wire as indicated on the drawings and as recommended by the manufacturer. Anchor supporting arms with 3/8 inch diameter plain pin rivets or, at the Contractor's option, with studs driven by low-velocity explosive-actuated tools for steel, wrought iron, ductile iron, or malleable iron. Studs driven by an explosive-actuated tool shall not be used with gray iron or other material that can be fractured. Use a minimum of two studs per support arm. Pull barbed wire taut and attach to the arms with clips or other means that will prevent easy removal.
3.7 GATE INSTALLATION
a. Install gates at the locations shown. Mount gates to swing as indicated. Install latches, stops, and keepers as required. Install Slide gates as recommended by the manufacturer.
b.Submit Six copies of operating and maintenance instructions, a minimum of 2 weeks prior to field training. Operating instructions shall outline the step-by-step procedures required for system startup, operation, and shutdown. Include the manufacturer's name, model number, service manual, parts list, and brief description of all equipment and their basic operating features. Include in the maintenance instructions routine maintenance procedures, possible breakdowns and repairs, and troubleshooting guide. Also include the general gate layout, equipment layout and simplified wiring and control diagrams of the system as installed.
3.8 GROUNDING
a. Ground fencing as indicated on drawings and specified.
b. Ground fences crossed by overhead powerlines in excess of 600 volts. Electrical equipment attached to the fence shall be grounded.
c. Ground fences on each side of all gates, at each corner, at the closest approach to each building located within 50 feet of the fence, and where the fence alignment changes more than 15 degrees. Grounding locations shall not exceed 650 feet. Bond each gate panel with a flexible bond strap to its gate post. Ground fences crossed by powerlines of 600 volts or more at or near the point of crossing and at distances not exceeding 150 feet on each side of crossing.
d. Provide ground conductor consisting of No. 8 AWG solid copper wire. Grounding electrodes shall be 3/4 inch by 10 foot long copper-clad steel rod. Drive electrodes into the earth so that the top of the electrode is at least 6 inches below the grade. Where driving is impracticable, electrodes shall be buried a minimum of 12 inches deep and radially from the fence. The top of the electrode shall not be less than 2 feet or more than 8 feet from the fence. Clamp ground conductor to the fence and electrodes with bronze grounding clamps to create electrical continuity between fence posts, fence fabric, and ground rods. Total resistance of the fence to ground shall not be greater than 25 ohms.
3.9 SECURITY
Install new security fencing, remove existing security fencing, and perform related work to provide continuous security for facility. Schedule and fully coordinate work with Contracting Officer and cognizant Security Officer.
3.10 CLEANUP
Remove waste fencing materials and other debris from the work site each workday.
-- End of Section --