TARGET POWER RECEPTACLE (TPR) AUXILIARY POWER RECEPTACLE (APR)
W
G G
X
W
Y
ENCLOSURE
INSIDE
ENCLOSURE
OUTSIDE
NOTE BELOW
BUSHING, SEE
NEOPHRENE
NUT
PACKING
CABLE
LOCKNUT
GASKET
SEALING
BODY
SEAL-FITTING
CONDUIT
SPRING DOOR (TYPICAL)
SELF CLOSING
PANELBOARD
RIGID CONDUIT TO
GASKET (TYPICAL)
ONE PIECE EPDM
RECEPTACLE
NEMA L5-20R
120/240V
BOXES WITH WEATHERPROOF WHILE IN USE COVERS.
PROVIDE OUTLETS IN WEATHERPROOF RIGID METALLIC
NOTE:
BOXES WITH WEATHERPROOF WHILE IN USE COVERS.
PROVIDE OUTLETS IN WEATHERPROOF RIGID METALLIC
NOTE:
SPRING DOOR (TYPICAL)
SELF CLOSING
PANELBOARD
RIGID CONDUIT TO
GASKET (TYPICAL)
ONE PIECE EPDM
RECEPTACLE
NEMA L14-20R
120/240V
CENTER HOLE
CONCRETE COVER WITH
CRUSHED STONE
GROUND CONNECTOR
(TYPICAL)
#1/0 AWG BARE COPPER
GROUND ROD
CONNECT TO NEXT
GROUND ROD 3/4" x 10’
COPPER CLAD STEEL
GROUND ROD
CONNECT TO NEXT
OF STATIC GROUND WIRE
CLEAR FOR CONNECTION
LEAVE THE TOP 2" OF ROD
TO PANEL
CONDUCTORS
CIRCUIT
OUTLET
TO NEXT TARGET
EXTEND CIRCUIT
BOX
OUTLET
TARGET
GND
SYS
GND
EQ
TPR APR
10" MIN
A
N
B
G
PIPE
CONCRETE
PRECAST
W
G
W
X
G
Y
TPR APR
REMOVAL OF THE RECEPTACLE WOULD INTERRUPT THE CONTINUITY.
GROUNDING CONDUCTORS SHALL NOT DEPEND ON THE RECEPTACLE CONNECTION, WHERE
THROUGH THE OTHER RECEPTACLE. THE CONTINUITY OF THE NEUTRAL AND EQUIPMENT
EACH RECEPTACLE SHALL BE TAPPED FROM THE CIRCUIT CONDUCTORS AND NOT CONNECTED
SECTION-CABLE SEAL-FITTING5
NO SCALE
NO SCALE
TYPICAL DETAIL SYMBOL1
NO SCALE
TYPICAL DETAIL SYMBOL
NO SCALE
GROUND ROD WELL DETAIL 4
NO SCALE
TARGET OUTLET WIRING DIAGRAM
TYPICAL DETAILS
44026-E11
E11 E11 E11
E11E11
REFERENCE ONLY
E11
D A
T E
S Y
M B
O L
R E
V
IS
IO
N S
B Y
DRAWN BY
APPROVED
DRAWING NUMBER SCALE
DATE
L&E NO:
NOTED
D. SAYLOR
K. CHAN
DIRECTORATEDIRECTORATE
OF PUBLIC WORKS
FORT BENNING, GEORGIA
BID DOCUMENTS
35% DESIGN
TYPICAL RECEPTACLE AND WIRING DETAILS
FORT BENNING, GEORGIA
PISTOL QUALIFICATION COURSE RANGE
CONVERT OSCAR 5 RANGE TO COMBAT