OUST-IN RANGE PROJECTS
SECTION 26 28 01.00 10
COORDINATED POWER SYSTEM PROTECTION
10/07
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM D 2472 (2000; R 2006) Standard Specification for Sulphur Hexafluoride
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE C2 (2007; Errata 2006 & 2007; INT 44-56 2007;
INT 47, 49, 50, 52-56 2008; INT 57, 58,
51, 48, 59 2009) National Electrical Safety Code
IEEE C37.04 (1999; Amendment A 2003; R 2006; amendment B 2008) Rating Structure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis
IEEE C37.06 (2000) AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis - Preferred Ratings and Related Required Capabilities
IEEE C37.13 (2008; INT 2009) Standard for Low-Voltage AC Power Circuit Breakers Used in Enclosures
IEEE C37.16 (2009) Recommendations for Low-Voltage Power Circuit Breakers and AC Power Circuit Protectors, - Preferred Ratings, Related Requirements, and Application
IEEE C37.2 (2008) Electrical Power System Device Function Numbers and Contact Designations
IEEE C37.20.1 (2002; Addenda A 2005; Addenda B 2006; R 2007) Standard for Metal-Enclosed Low-Voltage Power Circuit-Breaker Switchgear
IEEE C37.46 (2000) For High Voltage Expulsion and Current-Limiting Type Power Class Fuses and Fuse Disconnecting Switches
IEEE C37.90 (2005) Standard for Relays and Relay Systems Associated With Electric Power Apparatus
IEEE C57.13 (2008) Standard Requirements for Instrument Transformers
IEEE Std 242 (2001; Errata 2003) Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems - Buff Book
IEEE Std 399 (1997) Recommended Practice for Power Systems Analysis - Brown Book
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA AB 1 (2002) Molded-Case Circuit Breakers, Molded Case Switches, and Circuit-Breaker Enclosures
NEMA C12.11 (2007) Instrument Transformers for Revenue Metering, 10 kV BIL through 350 kV BIL (0.6 kV NSV through 69 kV NSV)
NEMA C37.50 (1989; R 2000) Low-Voltage AC Power Circuit Breakers Used in Enclosures - Test Procedures
NEMA FU 1 (2002; R 2007) Low Voltage Cartridge Fuses
NEMA ICS 1 (2000; R 2005; R 2008) Standard for Industrial Control and Systems General Requirements
NEMA ICS 2 (2000; R 2005; Errata 2008) Standard for Industrial Control and Systems:
Controllers, Contactors, and Overload Relays Rated Not More than 2000 Volts AC or 750 Volts DC: Part 8 - Disconnect Devices for Use in Industrial Control Equipment
NEMA ICS 3 (2005) Standard for Industrial Control and Systems: Medium Voltage Controllers Rated 2001 to 7200 Volts AC
NEMA ICS 6 (1993; R 2006) Standard for Industrial Controls and Systems Enclosures
NEMA SG 4 (2009) Alternating-Current High-Voltage Circuit Breaker
NEMA SG 6 (2000) Standard for Power Switching Equipment
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2008; AMD 1 2008) National Electrical Code - 2008 Edition
U.S. DEPARTMENT OF DEFENSE (DOD)
UFC 3-310-04 (2007) Seismic Design for Buildings
UNDERWRITERS LABORATORIES (UL)
UL 198M (2003; Rev thru Oct 2007) Mine-Duty Fuses
UL 486E (2009) Equipment Wiring Terminals for Use with Aluminum and/or Copper Conductors
UL 489 (2009) Standard for Molded-Case Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosures
UL 508 (1999; Rev thru Sep 2008) Standard for Industrial Control Equipment
UL 845 (2005; Rev thru Aug 2006) Standard for Motor Control Centers
UL 877 (1993; Rev thru Dec 2009) Circuit Breakers and Circuit-Breaker Enclosures for Use in Hazardous (Classified) Locations
1.2 SYSTEM DESCRIPTION
The power system covered by this specification consists of: Interior electrical distribution.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-03 Product Data
Fault Current Analysis Protective Device Coordination Study
The study along with protective device equipment submittals. No time extensions or similar contact modifications will be granted for work arising out of the requirements for this study. Approval of protective devices proposed will be based on recommendations of this study. The Government shall not be held responsible for any changes to equipment, device ratings, settings, or additional labor for installation of equipment or devices ordered and/or procured prior to approval of the study.
Equipment
Data consisting of manufacturer's time-current characteristic curves for individual protective devices, recommended settings of adjustable protective devices, and recommended ratings of non-adjustable protective devices.
System Coordinator
Verification of experience and license number, of a registered Professional Engineer with at least 3 years of current experience in the design of coordinated power system protection. Experience data shall include at least five references for work of a magnitude comparable to this contract, including points of contact, addresses and telephone numbers. This engineer must perform items required by this section to be performed by a registered Professional Engineer.
Protective Relays
Data including calibration and testing procedures and instructions pertaining to the frequency of calibration, inspection, adjustment, cleaning, and lubrication.
Installation
Procedures including diagrams, instructions, and precautions required to properly install, adjust, calibrate, and test the devices and equipment.
SD-06 Test Reports
Field Testing
The proposed test plan, prior to field tests, consisting of complete field test procedure including tests to be performed, test equipment required, and tolerance limits, including complete testing and verification of the ground fault protection equipment, where used. Performance test reports in booklet form showing all field tests performed to adjust each component and all field tests performed to prove compliance with the specified performance criteria, upon completion and testing of the installed system.
Each test report shall indicate the final position of controls.
SD-07 Certificates
Devices and Equipment
Certificates certifying that all devices or equipment meet the requirements of the contract documents.
1.4 QUALITY ASSURANCE
1.4.1 System Coordinator
System coordination, recommended ratings and settings of protective devices, and design analysis shall be accomplished by a registered professional electrical power engineer with a minimum of 3 years of current experience in the coordination of electrical power systems.
1.4.2 System Installer
Calibration, testing, adjustment, and placing into service of the protective devices shall be accomplished by a manufacturer's product field service engineer or independent testing company with a minimum of two years of current product experience in protective devices.
1.5 DELIVERY, STORAGE, AND HANDLING
Devices and equipment shall be visually inspected when received and prior to acceptance from conveyance. Protect stored items from the environment in accordance with the manufacturer's published instructions. Damaged items shall be replaced.
1.6 PROJECT/SITE CONDITIONS
Devices and equipment furnished under this section shall be suitable for the following site conditions.
a. Altitude: 500 feet
b. Ambient Temperature: -30 to 40 degrees C.
c. Frequency: 60
PART 2 PRODUCTS
2.1 STANDARD PRODUCT
Provide protective devices and equipment which are the standard product of a manufacturer regularly engaged in the manufacture of the product and that essentially duplicate items that have been in satisfactory utility type use for at least two years prior to bid opening.
2.2 NAMEPLATES
Provide nameplates to identify all protective devices and equipment.
Nameplate information shall be in accordance with NEMA AB 1.
2.3 CORROSION PROTECTION
Metallic materials shall be protected against corrosion. Ferrous metal hardware shall be zinc or chrome-plated.
2.8 MOLDED-CASE CIRCUIT BREAKERS
2.8.1 General
Molded-case circuit breakers shall conform to NEMA AB 1 and UL 489.
Circuit breakers may be installed in panelboards, switchboards, enclosures, motor control centers, or combination motor controllers. Circuit breakers and circuit breaker enclosures located in hazardous (classified) areas shall conform to UL 877.
2.8.2 Construction
Molded-case circuit breakers shall be assembled as an integral unit in a supporting and enclosing housing of glass reinforced insulating material providing high dielectric strength. Circuit breakers shall be suitable for mounting and operating in any position. Lugs shall be listed for copper conductors only or copper and aluminum conductors in accordance with UL 486E.
Single-pole circuit breakers shall be full module size with not more than one pole per module. Multi-pole circuit breakers shall be of the common-trip type having a single operating handle such that an overload or short circuit on any one pole will result in all poles opening simultaneously. Sizes of 100 amperes or less may consist of single-pole breakers permanently factory assembled into a multi-pole unit having an internal, mechanical, nontamperable common-trip mechanism and external handle ties. All circuit breakers shall have a quick-make, quick-break overcenter toggle-type mechanism, and the handle mechanism shall be trip-free to prevent holding the contacts closed against a short-circuit or sustained overload. All circuit breaker handles shall assume a position between "ON" and "OFF" when tripped automatically. All ratings shall be clearly visible.
2.8.3 Ratings
Voltage ratings shall be not less than the applicable circuit voltage. The interrupting rating of the circuit breakers shall be at least equal to the available short-circuit current at the line terminals of the circuit breaker and correspond to the UL listed integrated short-circuit current rating specified for the panelboards and switchboards. Molded-case circuit breakers shall have nominal voltage ratings, maximum continuous-current ratings, and maximum short-circuit interrupting ratings in accordance with NEMA AB 1. Ratings shall be coordinated with system X/R ratio.
2.8.4 Cascade System Ratings
Circuit breakers used in series combinations shall be in accordance with UL 489. Equipment, such as switchboards and panelboards, which house series-connected circuit breakers shall be clearly marked accordingly.
Series combinations shall be listed in the UL Recognized Component Directory under "Circuit Breakers-Series Connected."
2.8.5 Thermal-Magnetic Trip Elements
Thermal magnetic circuit breakers shall be provided as shown. Automatic operation shall be obtained by means of thermal-magnetic tripping devices located in each pole providing inverse time delay and instantaneous circuit protection. The instantaneous magnetic trip shall be adjustable and accessible from the front of all circuit breakers on frame sizes above 150 amperes.
2.8.6 Solid-State Trip Elements
Solid-state circuit breakers shall be provided as shown. All electronics shall be self-contained and require no external relaying, power supply, or accessories. Printed circuit cards shall be treated to resist moisture absorption, fungus growth, and signal leakage. All electronics shall be housed in an enclosure which provides protection against arcs, magnetic interference, dust, and other contaminants. Solid-state sensing shall measure true RMS current with error less than one percent on systems with distortions through the 13th harmonic. Peak or average actuating devices are not acceptable. Current sensors shall be toroidal construction, encased in a plastic housing filled with epoxy to protect against damage and moisture and shall be integrally mounted on the breaker. Where indicated on the drawings, circuit breaker frames shall be rated for 100 percent continuous duty. Circuit breakers shall have tripping features as shown on the drawings and as described below:
a. Long-time current pick-up, adjustable from 50 percent to 100 percent of continuous current rating.
b. Adjustable long-time delay.
c. Short-time current pick-up, adjustable from 1.5 to 9 times long-time current setting.
d. Adjustable short-time delay.
e. Short-time I square times t switch.
f. Instantaneous current pick-up, adjustable from 1.5 to 9 times long-time current setting.
g. Ground-fault pick-up, adjustable from 20 percent to 60 percent of sensor rating, but in no case greater than 1200 amperes. Sensing of ground-fault current at the main bonding jumper or ground strap shall not be permitted.
h. Adjustable ground-fault delay.
i. Ground-fault I square times t switch.
j. Overload and Short-circuit and Ground-fault trip indicators shall be provided.
2.14 COORDINATED POWER SYSTEM PROTECTION
Analyses shall be prepared to demonstrate that the equipment selected and system constructed meet the contract requirements for ratings, coordination, and protection. They shall include a load flow analysis, a fault current analysis, and a protective device coordination study. The studies shall be performed by a registered professional engineer with demonstrated experience in power system coordination in the last 3 years.
Provide a list of references complete with points of contact, addresses and telephone numbers. The selection of the engineer is subject to the approval of the Contracting Officer.
2.14.1 Scope of Analyses
The fault current analysis, and protective device coordination study shall begin at: the source bus and extend down to system buses where fault availability is 10,000 amperes (symmetrical) for building/facility 600 volt level distribution buses.
2.14.2 Determination of Facts
Assume the primary source is an infinite bus, as fault current availability is unknown.
2.14.3 Single Line Diagram
A single line diagram shall be prepared to show the electrical system buses, devices, transformation points, and all sources of fault current (including motor contributions). A fault-impedance diagram or a computer analysis diagram may be provided. Each bus, device or transformation point shall have a unique identifier. If a fault-impedance diagram is provided, impedance data shall be shown. Location of switches, breakers, and circuit interrupting devices shall be shown on the diagram together with available fault data, and the device interrupting rating.
2.14.4 Fault Current Analysis
2.14.4.1 Method
The fault current analysis shall be performed in accordance with methods described in IEEE Std 242, and IEEE Std 399.
2.14.4.2 Data
Actual data shall be utilized in fault calculations. Bus characteristics and transformer impedance shall be those proposed. Data shall be documented in the report.
2.14.4.3 Fault Current Availability
Balanced three-phase fault, bolted line-to-line fault, and line-to-ground fault current values shall be provided at each voltage transformation point and at each power distribution bus. The maximum and minimum values of fault available at each location shall be shown in tabular form on the diagram or in the report.
2.14.5 Coordination Study
The study shall demonstrate that the maximum possible degree of selectivity has been obtained between devices specified, consistent with protection of equipment and conductors from damage from overloads and fault conditions.
The study shall include a description of the coordination of the protective devices in this project. A written narrative shall be provided describing: which devices may operate in the event of a fault at each bus;
the logic used to arrive at device ratings and settings; situations where system coordination is not achievable due to device limitations (an analysis of any device curves which overlap); coordination between upstream and downstream devices; and relay settings. Recommendations to improve or enhance system reliability, and detail where such changes would involve additions or modifications to the contract and cost damages (addition or reduction) shall be provided. Composite coordination plots shall be provided on log-log graph paper.
2.14.6 Study report
a. The report shall include a narrative describing: the analyses performed; the bases and methods used; and the desired method of coordinated protection of the power system.
b. The study shall include descriptive and technical data for new protective devices proposed. The data shall include manufacturers published data, nameplate data, and definition of the fixed or adjustable features of the existing or new protective devices.
c. The report shall document utility company data including system voltages, fault MVA, and system X/R ratio.
d. The report shall contain fully coordinated composite time-current characteristics curves for each bus in the system, as required to ensure coordinated power system protection between protective devices or equipment. The report shall include recommended ratings and settings of all protective devices in tabulated form.
e. The report shall provide the calculation performed for the analyses, including computer analysis programs utilized. The name of the software package, developer, and version number shall be provided.
PART 3 EXECUTION
3.1 EXAMINATION
After becoming familiar with details of the work, verify dimensions in the field, and advise the Contracting Officer of any discrepancy before performing any work.
3.2 INSTALLATION
Install protective devices in accordance with the manufacturer's published instructions and in accordance with the requirements of NFPA 70 and IEEE C2.
3.3 FIELD TESTING
3.3.2 Safety
Provide and use safety devices such as rubber gloves, protective barriers, and danger signs to protect and warn personnel in the test vicinity.
Replace any devices or equipment which are damaged due to improper test procedures or handling.
3.3.3 Molded-Case Circuit Breakers
Circuit breakers shall be visually inspected, operated manually, and connections checked for tightness. Current ratings shall be verified and adjustable settings incorporated in accordance with the coordination study.
-- End of Section --