TYPICAL DETAILS
GENERAL NOTES FOR DIRECT BURIED CABLE DETAILS:
OFFICER IF ACTUAL CONSTRUCTION ISSUES MAY CAUSE RUNS TO EXCEED 90 METERS.
7. COPPER CAT 5e CABLE RUNS SHALL BE NO LONGER THAN 90 METERS. CONTACT THE CONTRACTING
6. AFTER INSTALLATION REPAIR ALL SURFACES TO MATCH EXISITING.
CODE.
5. INSTALLATION SHALL BE IN ACCORDANCE WITH NFPA 70 AND THE NATIONAL ELECTRICAL SAFETY
BURIED CABLING.
SEPARATION DISTANCE, DESCRIBED IN NOTE 3 SHALL APPLY BETWEEN CONDUITS AND DIRECT
4. WHERE DIRECT BURIAL CABLE(S) ARE PLACED IN SAME TRENCH WITH CONDUIT DUCT BANKS, (HORIZONTAL) IS AT LEAST 4" BETWEEN CABLES. TRENCH WIDTH WILL VARY.
ONLY) CAN BE INSTALLED AT THE SAME ELEVATION AS LONG AS MINIMUM SEPARATION DISTANCE
3. ALL DETAILS ARE SHOWN WITH ONE(1) CABLE PER SECTION. MULTIPLE CABLES (OF SAME TYPE
ON SHEETS ES-509 THROUGH ES-512 FOR EXACT QUANTITY OF CABLES.
SHEETS ES-601 THROUGH ES-603 AND PANEL SCHEDULES AND POWER AND DATA DIAGRAMS
2. THESE ARE TYPICAL LAYOUT DETAILS. REFER TO POWER AND DATA ONE-LINE DIAGRAMS ON
1. TRENCHES SHALL BE EXCAVATED. PLOWING IN OF CABLES IS NOT ACCEPTABLE.
EXCAVATED MATERIAL
BACKFILL USING
WARNING TAPE
PLASTIC UG RIBBON
SAND OR SCREENED FILL
LOW VOLTAGE POWER CABLES
12"
42"
6"
4"
EXCAVATED MATERIAL
BACKFILL USING
WARNING TAPE
PLASTIC UG RIBBON
SAND OR SCREENED FILL
FIBER OPTIC DATA CABLES
12"
42"
6"
4"
WARNING TAPE
PLASTIC UG RIBBON
6" LAYERS
COMPACT SOIL IN
DUCT (TYP)
4"SCHEDULE 80 PVC
SAND ENCASEMENT
ON EACH SIDE OF STREAM)
STREAM AND TO A POINT 10 FEET
SPECIFICATIONS (USE STONE BELOW
MATERIAL IN ACCORDANCE WITH
BACKFILL USING SATISFACTORY
MATCH EXISTING SURFACE.
AND OTHERWISE REPAIRED TO
SURFACE MUST BE CUT, PATCHED
12"
3"
7 1/2"
3"
7 1/2"
3"3"
SURFACE
REPAIRED TO MATCH EXISTING
PATCHED AND OTHERWISE
SURFACE MUST BE CUT,
IN 6" LAYERS
COMPACT SOIL
WITH SPECIFICATIONS
MATERIAL IN ACCORDANCE
BACKFILL USING SATISFACTORY
SIZE.
FOR CONDUIT AND WIRE
REFER TO SHEET ES-602
SCHEDULE 80 PVC DUCT.
SAND
WARNING TAPE
PLASTIC UG RIBBON
"12"
3"
3"
3"3"
EXCAVATED MATERIAL
BACKFILL USING
WARNING TAPE
PLASTIC UG RIBBON
SAND OR SCREENED FILL
CABLES
FIBER OPTIC DATA
LOW VOLTAGE POWER CABLES
(US/USL/UF)(USL/UF)
DIRECT BURIED DATA CABLES IN THE SAME TRENCH (US/UF)
LOW VOLTAGE DIRECT BURIED POWER CABLES AND FIBER OPTIC
12"
42"
6"
4"
4"
CABLES.
DETAIL FOR TYPE AND NUMBER OF
REFER TO SPECIFIED DUCT BANK
4500 PSI CONCRETE
WARNING TAPE
PLASTIC UG RIBBON
EXCAVATED MATERIAL
BACKFILL USING
12"
45"
3"
4"
4"
SURFACE
REPAIRED TO MATCH EXISTING
PATCHED AND OTHERWISE
SURFACE MUST BE CUT,
WARNING TAPE
PLASTIC UG RIBBON
IN 6" LAYERS
COMPACT SOIL
WITH SPECIFICATIONS
MATERIAL IN ACCORDANCE
BACKFILL USING SATISFACTORY
#4 REINFORCING RODS
4500 PSI CONCRETE
NUMBER OF DUCTS OR CABLES.
BANK DETAIL FOR TYPE AND
REFER TO SPECIFIED DUCT
3" 3"
3"
3"
"12"
OF 11,000 PSI.
MINIMUM COMPRESSIVE STRENGTH
WITH HEAVY-WEAVE FIBERGLASS.
POLYMER CONCRETE REINFORCED COEFICIENT OF FRICTION.
LOAD. 0.5 MINIMUM
21600 POUND PER SQUARE FOOT
HEAVY DUTY COVER RATED FOR
STEEL BOLTS
3/8 " STAINLESS
TYPE X Y Z
242412HH
NOMINAL DIMENSIONS (INCHES)
Z
X
Y
NO SCALE
DIRECT BURIED DETAIL 5
NO SCALE
DUCT BANK DETAIL -4 NO SCALEDUCT BANK DETAIL
NO SCALE
NO SCALE
CONCRETE ENCASED DUCT 8 NO SCALEHANDHOLE DETAIL
NO SCALE
FIBER OPTIC DIRECT BURIED 2 NO SCALELOW VOLTAGE DIRECT BURIED
E14
E14 E14
E14
E14 E14
E14
E14
44026-E14
E14
REFERENCE ONLY
D A
T E
S Y
M B
O L
R E
V
IS
IO
N S
B Y
DRAWN BY
APPROVED
DRAWING NUMBER SCALE
DATE
L&E NO:
NOTED
D. SAYLOR
K. CHAN
DIRECTORATEDIRECTORATE
OF PUBLIC WORKS
FORT BENNING, GEORGIA
CONCRETE ENCASED DIRECT
BURIED CABLES BANK / CABLE
DIRECTIONAL BORE
(US/USL)
POWER CABLES (US) (USL)DATA CABLES (UF)
BID DOCUMENTS
35% DESIGN
TYPICAL HANDHOLE & DIRECT BURIED DETAILS
FORT BENNING, GEORGIA
PISTOL QUALIFICATION COURSE RANGE
CONVERT OSCAR 5 RANGE TO COMBAT
15 FEB 2019