SECTION 28 16 01 Page 1
SECTION 28 16 01.00 10
SMALL INTRUSION DETECTION SYSTEM
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI INCITS 154 (1988; R 2004) Office Machines and Supplies -
Alphanumeric Machines-Keyboard Arrangement
ANSI INCITS 92 (1980; R 2003) Data Encryption Algorithm
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE C2 (2007; Errata 2007; INT 2008) National Electrical
Safety Code
IEEE C62.41.1 (2002) IEEE Guide on the Surges Environment in Low-
Voltage (1000 V and Less) AC Power Circuits
IEEE C62.41.2 (2002) IEEE Recommended Practice on Characterization of Surges in Low-Voltage (1000 V and Less) AC Power Circuits
IEEE Std 142 (2007) Recommended Practice for Grounding of
Industrial and Commercial Power Systems - IEEE Green Book (Color Book Series)
INTERNATIONAL TELECOMMUNICATION UNION (ITU)
ITU V.34 (1998) Data Communication Over the Telephone Network:
A Modem Operating at Data Signaling Rates of up to 33,600 bits for use on the General Switched Telephone Network and on Leased Point-to-Point Two-Wire Telephone Type Circuits
ITU V.42 (2002; CORR 1 2003) Data Communications Over the
Telephone Network: Error-Correcting Procedures for DCEs Using Asynchronous-to-Synchronous Conversion
ITU V.42 bis (1990) Data Communication over the Telephone Network:
Data Compression Procedures for Data Circuit Terminating Equipment (DCE) Using Error Correction Procedures
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA 250 (2003) Enclosures for Electrical Equipment (1000
Volts Maximum)
SECTION 28 16 01 Page 2
NEMA ICS 1 (2000; R 2005; R 2008) Standard for Industrial Control and Systems General Requirements
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2007; AMD 1 2008) National Electrical Code - 2008
Edition
TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)
TIA-232-F (1997; R 2002) Interface Between Data Terminal Equipment and Data Circuit-Terminating Equipment Employing Serial Binary Data Interchange
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
47 CFR 15 Radio Frequency Devices
47 CFR 68 Connection of Terminal Equipment to the Telephone
Network
UNDERWRITERS LABORATORIES (UL)
UL 1037 (1999; Rev thru Nov 2004) Standard for Safety Antitheft Alarms and Devices
UL 1076 (1995; Rev thru Mar 2005) Standard for Safety
Proprietary Burglar Alarm Units and Systems
UL 294 (1999; Rev thru Aug 2005) Access Control System Units
UL 639 (2007) Intrusion Detection Units
UL 681 (1999; Rev thru Jan 2001) Installation and
Classification of Burglar and Holdup Alarm Systems
UL 796 (2006; Rev thru Feb 2008) Printed-Wiring Boards
1.2 DEFINITIONS
1.2.1 Intrusion Alarm
An alarm resulting from the detection of a specified target and which results in an attempt to intrude into the protected area or when entry into an entry controlled area is attempted without successfully using entry control procedures.
1.2.2 Nuisance Alarm
An alarm resulting from the detection of an alarm stimuli, but which does not represent an attempt to intrude into the protected area.
1.2.3 Environmental Alarm
An alarm during environmental conditions which exceed those specified.
SECTION 28 16 01 Page 3
1.2.4 False Alarm
An alarm when there is no alarm stimulus.
1.2.5 Duress Alarm
An alarm condition which results from a set of pre-established conditions such as entering a special code into a keypad or by activating a switch.
This alarm category shall take precedence over other alarm categories.
1.2.6 Standard Intruder
Individual that weighs 100 pounds or less and is 5 feet tall or less, dressed in a long-sleeved shirt, slacks and shoes, unless environmental conditions at the site require protective clothing. Standard intruder movement is defined as any movement such as walking, running, crawling, rolling, or jumping through a protected zone in the most advantageous manner for the intruder.
1.3 SYSTEM DESCRIPTION
1.3.1 General
Configure the Intrusion Detection System (IDS) as described and shown, including Government Furnished Equipment (GFE). Computing devices, as defined in 47 CFR 15, shall be certified to comply with the requirements for Class A computing devices and labeled as set forth in 47 CFR 15.
1.3.2 Overall System Reliability Requirement
The system, including all components and appurtenances, shall be configured and installed to yield a mean time between failures (MTBF) of at least 10,000 hours continuous operation.
1.3.3 Probability of Detection
Each zone shall have a continuous probability of detection greater than 90 percent and shall be demonstrated with a confidence level of 95 percent.
This probability of detecting a standard intruder equates to 49 successful detections out of 50 tests or 98 successful detections out of 100 tests.
1.3.4 Electrical Requirements
Electrically powered IDS equipment shall operate on 120 or 240 volt 60 Hz AC sources as shown. Equipment shall be able to tolerate variations in the voltage source of plus or minus 10 percent, and variations in the line frequency of plus or minus 2 percent with no degradation of performance.
1.3.5 Power Line Surge Protection
Protect equipment connected to alternating current circuits from power line surges. Equipment protection shall withstand surge test waveforms described in IEEE C62.41.1 and IEEE C62.41.2. Fuses shall not be used for surge protection.
1.3.6 Sensor Wiring and Communication Circuit Surge Protection
SECTION 28 16 01 Page 4
Protect inputs against surges induced on sensor wiring. Outputs shall be protected against surges induced on control and sensor wiring installed outdoors and as shown. All communications equipment shall be protected against surges induced on any communications circuit. All cables and conductors, except fiber optics, which serve as communications circuits from the console to field equipment, and between field equipment, shall have surge protection circuits installed at each end. Protection shall be furnished at equipment, and additional triple electrode gas surge protectors rated for the application on each wireline circuit shall be installed within 3 feet of the building cable entrance. Fuses shall not be used for surge protection. The inputs and outputs shall be tested in both normal mode and common mode using the following two waveforms:
a. A 10 microsecond rise time by 1000 microsecond pulse width waveform with a peak voltage of 1500 volts and a peak current of 60 amperes.
b. An 8 microsecond rise time by 20 microsecond pulse width waveform with a peak voltage of 1000 volts and a peak current of 500 amperes.
1.3.7 System Reaction
All alarms shall be annunciated on the displays within 1 second of their occurring at a local processor.
1.3.8 System Capacity
The system shall monitor and control the number of inputs and outputs shown and shall include an expansion capability of a minimum of 25 percent.
1.4 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-03 Product Data
Intrusion Detection System; G
a. System block diagram.
b. Console installation, block diagrams, and wiring diagrams.
c. Processor installation, typical block, and wiring diagrams.
d. Details of connections to power sources, including power supplies and grounding.
e. Details of surge protection device installation.
f. Sensor detection patterns.
g. The qualifications of the Manufacturer, Contractor, and Installer to perform the work specified herein.
Key Control Plan; G
Key control plan including the following:
a. Procedures that will be used to log and positively control all keys during installation.
SECTION 28 16 01 Page 5
b. A listing of all keys and where they are used.
c. A listing of all persons allowed entry to the keys.
Spare Parts
Data lists of spare parts, tools, and test equipment for each different item of material and equipment specified.
Manufacturer's Instructions; G
Printed copies of manufacturer's recommendations for installation of materials prior to installation. Where installation procedures, or any part thereof, are required to be in accordance with manufacturer's recommendations, installation of the item will not be allowed to proceed until the recommendations are received and approved.
Testing; G
Test plan defining all tests required to ensure that the system meets technical, operational and performance specifications, 60 days prior to proposed test date. The test plan must be approved before the start of any testing. The test plan shall identify the capabilities and functions to be tested, and include detailed instructions for the setup and execution of each test and procedures for evaluation and documentation of the results.
Experience
Written proof of specified experience requirements.
SD-06 Test Reports
Performance Verification Test
Test reports, in booklet form with witness signatures verifying execution of tests. Reports shall show the field tests to verify compliance with the specified performance criteria. Test reports shall include records of the physical parameters verified during testing. Test reports shall be submitted within 14 days after completion of testing.
SD-07 Certificates
Materials and Equipment
Where materials or equipment are specified to conform, be constructed or tested to meet specific requirements, certification that the items provided conform to such requirements. Certification by a nationally recognized testing laboratory that a representative sample has been tested to meet the requirements, or a published catalog specification statement to the effect that the item meets the referenced standard, will be acceptable as evidence that the item conforms. Compliance with these requirements does not relieve the contractor from compliance with other requirements of the specifications.
SECTION 28 16 01 Page 6
1.5 QUALITY ASSURANCE
Submit written proof that the following experience requirements are being met.
1.5.1 Hardware Manufacturer
All system components shall be produced by manufacturers who have been regularly engaged in the production of intrusion detection system components of the types to be installed for at least 3 years.
1.5.2 Software Manufacturer
All system and application software shall be produced by manufacturers who have been regularly engaged in the production of intrusion detection system and application software of similar type and complexity as the specified system for at least 2 years.
1.5.3 System Installer
The system shall be installed by a contractor who has been regularly engaged in the installation of intrusion detection systems of similar type and complexity as the specified system for at least 2 years.
1.5.4 Line Supervision
1.5.4.1 Signal and Data Transmission System (DTS) Line Supervision
All signal or DTS lines between sensors and the alarm annunciation console shall be supervised by the system. The system shall supervise the signal lines by monitoring changes in the direct current that flows through the signal lines and a terminating resistor. The system shall initiate an alarm in response to a current change of 5 percent or greater. The system shall also initiate an alarm in response to opening, closing, shorting, or grounding of the signal and DTS lines.
1.5.4.2 Data Encryption
(Data encryption is not required unless stated in the Task Order). The intrusion detection system shall incorporate data encryption equipment on data transmission media links as shown. The algorithm used for encryption shall be the Data Encryption Standard (DES) algorithm described in ANSI
INCITS 92.
1.5.5 Data Transmission System (DTS)
If so stated in the Task Order, the contractor shall provide Data Transmission Systems as shown.
1.6 ENVIRONMENTAL REQUIREMENTS
1.6.1 Interior, Controlled Environment
All system components, except the console, installed in interior locations having controlled environments shall be rated for continuous operation under ambient environmental conditions of 36 to 122 degrees F dry bulb and 20 to 90 percent relative humidity, noncondensing.
SECTION 28 16 01 Page 7
1.6.2 Interior, Uncontrolled Environment
All system components installed in interior locations having uncontrolled environments shall be rated for continuous operation under ambient environmental conditions of 0 to 122 degrees F dry bulb and 10 to 95 percent relative humidity, noncondensing.
1.6.3 Exterior Environment
System components that are installed in locations exposed to weather shall be rated for continuous operation under ambient environmental conditions of minus 30 to 122 degrees F dry bulb and 10 to 95 percent relative humidity, condensing. In addition, the system components shall be rated for continuous operation when exposed to performance conditions as specified in UL 294 and UL 639 for outdoor use equipment. In addition, components shall be rated for continuous operation when exposed to rain as specified in NEMA 250, winds up to 85 mph and snow cover up to 2 feet thick, measured vertically.
1.6.4 Hazardous Environment
System components located in areas where fire or explosion hazards may exist because of flammable gases or vapors, flammable liquids, combustible dust, or ignitable fibers or flyings, shall be rated and installed according to Chapter 5 of NFPA 70 and as shown.
1.6.5 Central Station
All central station equipment shall, unless designated otherwise, be rated for continuous operation under ambient environmental conditions of 60 to 85 degrees F and a relative humidity of 20 to 80 percent.
1.7 EXTRA MATERIALS
Submit spare parts data for each different item of equipment and material specified, after approval of detail drawings and not later than 2 months prior to the date of beneficial occupancy. The data shall include a complete list of parts and supplies, with current unit prices and source of supply, and a list of the parts recommended for stocking
PART 2 PRODUCTS
2.1 MATERIALS AND EQUIPMENT
2.1.1 General
Units of the same type of equipment shall be products of a single manufacturer. All material and equipment shall be new and currently in production. Each major component of equipment shall have the manufacturer's model and serial number in a conspicuous place. Provide laminated plastic nameplates for local processors. Each nameplate shall identify the local processor and its location within the system. Laminated plastic shall be 1/8 inch thick, white with black center core. Nameplates shall be a minimum of 1 by 3 inches, with minimum 1/4 inch high engraved block lettering.
Attach nameplates to the inside of the enclosure housing the local processor. Other major components of the system shall have the
SECTION 28 16 01 Page 8 manufacturer's name, address, type or style, model or serial number, and catalog number on a corrosion resistant plate secured to the item of equipment. Nameplates will not be required for devices smaller than 1 by 3 inches.
2.1.2 Enclosures
System enclosures shall be as shown.
2.1.2.1 Interior Sensor
Sensors to be used in an interior environment shall be housed in an enclosure that provides protection against dust, falling dirt, and dripping noncorrosive liquids.
2.1.2.2 Interior Electronics
System electronics to be used in an interior environment shall be housed in enclosures which meet the requirements of NEMA 250 Type 12.
2.1.2.3 Exterior Electronics
System electronics to be used in an exterior environment shall be housed in enclosures which meet the requirements of NEMA 250 Type 4X.
2.1.2.4 Corrosion Resistant
System electronics to be used in a corrosive environment as defined in NEMA 250 shall be housed in an enclosure which meet the requirements of NEMA 250 Type 4X.
2.1.2.5 Hazardous Environment Equipment
System electronics to be used in a hazardous environment shall be housed in an enclosure which meets the requirements of paragraph Hazardous Environment.
2.1.3 Fungus Treatment
System components located in fungus growth inductive environments shall be completely treated for fungus resistance. Treating materials containing a mercury bearing fungicide shall not be used. Treating materials shall not increase the flammability of the material or surface being treated.
Treating materials shall cause no skin irritation or other injury to personnel handling it during fabrication, transportation, operation, or maintenance of the equipment, or during use of the finished items when used for the purpose intended.
2.1.4 Tamper Provisions
2.1.4.1 Tamper Switches
Enclosures, cabinets, housings, boxes, and fittings of every description having hinged doors or removable covers and which contain circuits or connections of the intrusion detection system and its power supplies, shall be provided with cover operated, corrosion-resistant tamper switches, arranged to initiate an alarm signal when the door or cover is moved. The
SECTION 28 16 01 Page 9 enclosure and the tamper switch shall function together in such a manner as to not allow direct line of sight to any internal components before the switch activates. Make tamper switches inaccessible until the switch is activated; have mounting hardware so concealed that the location of the switch cannot be observed from the exterior of the enclosure; be connected to circuits which are under electrical supervision at all times, irrespective of the protection mode in which the circuit is operating; shall be spring-loaded and held in the closed position by the door or cover; and shall be wired so that they break the circuit when the door or cover is disturbed.
a. Nonsensor Enclosures: Tamper switches on nonsensor enclosures, which must be opened to make routine maintenance adjustments to the system and to service the power supplies, shall be push/pull-set, automatic reset type.
b. Sensor Enclosures: Tamper switches on sensor enclosures, which must be opened to make routine maintenance adjustments to the sensor, shall be single pole single throw type.
2.1.4.2 Enclosure Covers
Covers of pull and junction boxes provided to facilitate initial installation of the system need not be provided with tamper switches if they contain no splices or connections, but shall be protected by tack welding or brazing the covers in place or by tamper resistant security fasteners.
Labels shall be affixed to such boxes indicating they contain no connections.
2.1.5 Locks and Key-Lock Switches
2.1.5.1 Locks
Install locks on system enclosures for maintenance purposes. Locks shall be UL listed, round-key type, with three dual, one mushroom, and three plain pin tumblers or conventional key type lock having a combination of five cylinder pin and five-point three position side bar. Keys shall be stamped "U.S. GOVT. DO NOT DUP". The locks shall be so arranged that the key can only be withdrawn when in the locked position. All maintenance locks shall be keyed alike and only two keys shall be furnished for all of these locks.
These keys shall be controlled in accordance with the key control plan.
2.1.5.2 Key-Lock-Operated Switches
All key-lock-operated switches required to be installed on system components shall be UL listed, round-key type, with three dual, one mushroom, and three plain pin tumblers or conventional key type lock having a combination of five cylinder pin and five-point three position side bar. Keys shall be stamped "U.S. GOVT. DO NOT DUP". Key-lock-operated switches shall be two position, with the key removable in either position. All key-lock-operated switches shall be keyed differently and only two keys shall be furnished for each key-lock-operated-switch. These keys shall be controlled in accordance with the key control plan.
2.1.5.3 Construction Locks
SECTION 28 16 01 Page 10
If the contractor requires locks during installation and construction, a set of temporary locks shall be used. The final set of locks installed and delivered to the Government shall not include any of the temporary locks.
2.1.6 Application of System Component
System components shall be designed for continuous operation. Electronic components shall be solid state type, mounted on printed circuit boards conforming to UL 796. Printed circuit board connectors shall be plug-in, quick-disconnect type. Power dissipating components shall incorporate safety margins of not less that 25 percent with respect to dissipation ratings, maximum voltages, and current carrying capacity. Light duty relays and similar switching devices shall be solid state type or sealed electro-mechanical.
2.1.6.1 Maintainability
Components shall be designed to be maintained using commercially available tools and equipment. Components shall be arranged and assembled so they are accessible to maintenance personnel. There shall be no degradation in tamper protection, structural integrity, EMI/RFI attenuation, or line supervision after maintenance when it is performed in accordance with manufacturer's instructions. The system shall be configured and installed to yield a mean time to repair (MTTR) of not more than 8 hours. Repair time is the clock time from the time maintenance personnel are given entrance to the system and begin work, until the system is fully functional.
2.1.6.2 Interchangeability
Construct the system with off-the-shelf components which are physically, electrically and functionally interchangeable with equivalent components as complete items. Replacement of equivalent components shall not require modification of either the new component or of other components with which the replacement items are used. Custom designed or one-of-a-kind items shall not be used. Interchangeable components or modules shall not require trial and error matching in order to meet integrated system requirements, system accuracy, or restore complete system functionality.
2.1.6.3 Electromagnetic and Radio Frequency Interference (EMI/RFI)
System components generating EMI/RFI shall be designed and constructed in accordance with 47 CFR 15.
2.1.6.4 Product Safety
System components shall conform to applicable rules and requirements of NFPA
70. System components shall be equipped with instruction plates, including warnings and cautions, describing physical safety, and special or important procedures to be followed in operating and servicing system equipment.
2.1.7 Controls and Designations
Provide controls and designations as specified in NEMA ICS 1.
2.1.8 Special Test Equipment
SECTION 28 16 01 Page 11
Provide all special test equipment, special hardware, software, tools, and programming or initialization equipment needed to start or maintain any part of the system and its components. Special test equipment is defined as any test equipment not normally used in an electronics maintenance facility.
2.1.9 Alarm Output
The alarm output of each sensor shall be a single pole double throw (SPDT) contact rated for a minimum of 0.25 A at 24 volts DC.
2.1.10 Alarm Indicator Lights
Indicator lights used throughout the system shall be light emitting diodes (LED) or long life incandescent lamps. The indicator lights used shall be visible from a distance of 30 feet in an area illuminated to 75 foot candles. The indicator lights shall conform to the following color coding:
a. FLASHING RED to alert an operator that a zone has gone into an unacknowledged alarm or that primary power has failed.
b. RED to alert an operator that a zone is in alarm and that the alarm has been acknowledged.
c. YELLOW to advise an operator that a zone is in access.
d. GREEN to indicate that a zone is secure or that power is on.
2.1.11 Access/Secure Devices
Access/secure devices shall be used to place a protected zone in ACCESS.
The device shall disable all sensor alarm outputs, with the exception of tamper alarm outputs within the protected zone, and sensors in zones above false ceilings or other inaccessible locations as shown.
2.1.11.1 Switches
The switch shall consist of a double pull key-operated switch housed in a NEMA 12 equivalent enclosure.
2.1.11.2 Key Pads
Secure/Access keypads shall use a unique combination of alphanumeric and other symbols as an identifier. Keypads shall contain an integral alphanumeric/special symbols keyboard with symbols arranged in ascending ASCII code ordinal sequence. The keypad shall have a contact output.
2.2 INTERIOR SENSORS
2.2.1 Balanced Magnetic Switch (BMS)
The BMS shall detect 1/4 inch of separating relative movement between the magnet and the switch housing. Upon detecting such movement, it shall transmit an alarm signal to the alarm annunciation system.
2.2.1.1 BMS Subassemblies
SECTION 28 16 01 Page 12
The BMS shall consist of a switch assembly and an actuating magnetic assembly. The switch mechanism shall be of the balanced magnetic type.
Each switch shall be provided with an overcurrent protective device, rated to limit current to 80 percent of the switch capacity. Switches shall be rated for a minimum lifetime of one million operations. The housings of surface mounted switches and magnets shall be made of nonferrous metal and shall be weatherproof. The housings of recess mounted switches and magnets shall be made of nonferrous metal or plastic.
2.2.1.2 Remote Test
Provide a remote test capability. The remote test shall be initiated when commanded by the alarm annunciation system. The remote test shall activate the sensor's switch mechanism causing an alarm signal to be transmitted to the alarm annunciation system. The remote test shall simulate the movement of the actuating magnet relative to the switch subassembly.
2.2.2 Glass Break Sensor, Piezoelectric
The glass break sensor shall detect high frequency vibrations generated by the breaking of glass while ignoring all other mechanical vibrations. An alarm signal shall be transmitted upon detecting such frequencies to the alarm annunciation system.
2.2.2.1 Sensor Element
The sensor element shall consist of piezoelectric crystals. The sensor element housing shall be designed to be mounted directly to the glass surface being protected. Only the adhesive recommended by the manufacturer of the sensor shall be used to mount detectors to glass. The detection pattern of a sensor element shall be circular with at least a 5 foot radius on a continuous pane of glass. A factory installed hookup cable of not less than 6 feet shall be included with each sensor. The sensor element shall not exceed 4 square inches. The sensor element shall be equipped with a light emitting diode (LED) activation indicator. The activation indicator shall light when the sensor responds to the high frequencies associated with breaking glass. The LED shall be held on until it is turned off manually at the sensor signal processor or by command from the alarm annunciation system.
2.2.2.2 Sensor Signal Processor
The sensor signal processor shall process the signals from the sensor elements and provide the alarm signal to the alarm annunciation system. The sensitivity of the sensor shall be adjustable by controls within the sensor signal processor. The controls shall not be accessible when the sensor signal processor housing is in place. The sensor signal processor may be integral with the sensor or may be a separate assembly.
2.2.2.3 Glass Break Simulator
Provide a device that can induce frequencies into the protected pane of glass that will simulate breaking glass to the sensor element without causing damage to the pane of glass.
2.2.3 Glass Break Sensor, Acoustic
SECTION 28 16 01 Page 13
The glass break sensor shall detect high frequency vibrations generated by the breaking of glass while ignoring all other mechanical vibrations. An alarm signal shall be transmitted upon detecting such frequencies to the
2.2.3.1 Acoustic Sensor Element
The sensor element shall be a microprocessor based digital device. The sensor shall detect breakage of plate, laminate, tempered, and wired glass while rejecting common causes of false alarms. The detection pattern of the sensor element shall be a range of 20 feet minimum. The sensor element shall be equipped with a light emitting diode (LED) activation indicator.
The activation indicator shall light when the sensor responds to the high frequencies associated with breaking glass. The LED shall be held on until it is turned off manually at the sensor signal processor or by command from the alarm annunciation system. The sensor signal processor shall process the signals from the sensor element and provide the alarm signal to the
2.2.3.2 Acoustic Sensor Signal Processor
The sensor signal processor shall process the signals from the sensor elements and provide the alarm signal to the alarm annunciation system. The sensitivity of the sensor shall be adjustable by controls within the sensor signal processor. The controls shall not be accessible when the sensor signal processor housing is in place. The sensor signal processor may be integral with the sensor or may be a separate assembly.
2.2.3.3 Acoustic Glass Break Simulator
A device that can induce frequencies which simulate breaking glass to the sensor shall be available for the specific sensor selected. The simulator shall not cause damage to the pane of glass.
2.2.4 Duress Alarm Switches
Duress alarm switches shall provide the means for an individual to covertly notify the alarm annunciation system that a duress situation exists.
2.2.4.1 Footrail
Footrail duress alarms shall be designed to be foot activated and floor mounted. No visible or audible alarm or noise shall emanate from the switch when activated. The switch shall lock in the activated position until manually reset with a key. The switch housing shall shroud the activating lever to prevent accidental activation. Switches shall be rated for a minimum lifetime of 50,000 operations.
2.2.4.2 Pushbutton
Latching pushbutton duress alarms shall be designed to be activated by depressing a pushbutton located on the duress switch housing. No visible or audible alarm or noise shall emanate from the switch. The switch shall lock in the activated position until manually reset with a key. The switch housing shall shroud the activating button to prevent accidental activation.
Switches shall be rated for a minimum lifetime of 50,000 operations.
SECTION 28 16 01 Page 14
2.2.4.3 Wireless
Wireless duress alarms shall consist of portable alarm transmitters and permanently installed receivers. The transmitter shall be activated by depressing a pushbutton located on the housing. An alarm signal shall be transmitted to one or more receivers located within a protected zone. The receivers shall, in-turn, transmit an alarm signal to the alarm annunciation system. No visible or audible alarm or noise shall emanate from the transmitter or receiver when activated. The receiver shall lock in a transmitting mode until manually reset. The transmitter housing shall shroud the activating button to prevent accidental activation. The transmitter shall be designed to be unobtrusive and still be activated in a covert manner. Switches shall be rated for a minimum lifetime of 50,000 operations. The transmitters shall have a range of 100 feet.
2.2.5 Security Screen
Security screens shall detect a standard intruder when the sensor wire is disconnected, cut, or broken. An alarm signal shall be transmitted to the alarm annunciation system. The sensor shall be constructed from 26 gauge insulated hard-drawn copper wire installed in a grid pattern on a wooden frame or as shown. The sensor grid wires connection to the alarm annunciation system shall be housed within a junction box as shown. A tamper switch shall be provided to detect attempts to remove the screen and to detect attempts to tamper with connections and end of line resistor.
2.2.6 Vibration Sensor
The vibration sensor shall detect the high frequency vibrations generated by the use of such tools as oxyacetylene torches; oxygen lances; high speed drills and saws; and explosives, to penetrate a structure while ignoring all other mechanical vibrations. An alarm signal shall be transmitted to the alarm annunciation system. The sensor shall consist of a sensor signal processor and piezoelectric crystal sensor elements that are designed to be rigidly mounted to the structure being protected. The sensor signal processor may be integral with the sensor element or may be a separate assembly. The sensor signal processor shall process the signals from the sensor elements and provide the alarm signal to the alarm annunciation system. The sensitivity of the sensor shall be adjustable by controls within the sensor signal processor. The controls shall not be accessible when the sensor signal processor housing is in place. The detection pattern of a sensor element shall be circular with at least a 6 foot radius on the protected structure.
2.2.7 Microwave Motion Sensor
The transmitted microwave motion sensor shall detect changes in a microwave signal. Upon detecting a specific change, the sensor shall transmit an alarm signal to the alarm annunciation system. The sensor shall detect a standard intruder moving within the sensor's detection pattern at a speed of
0.3 to 7.5 feet per second. The sensor shall comply with 47 CFR 15 Subpart F. The sensor's coverage pattern shall be as shown. The sensitivity of the sensor shall be adjustable by controls within the sensor. The controls shall not be accessible when the sensor housing is in place. The sensor shall be adjustable to obtain the coverage shown.
SECTION 28 16 01 Page 15
2.2.7.1 Test Indicator, Microwave Signal
The microwave motion sensor shall be equipped with an LED walk test indicator. The walk test indicator shall not be visible during normal operations. When visible, the walk test indicator shall light when the sensor detects an intruder. The sensor shall either be equipped with a manual control, located within the sensor's housing, to enable/disable the test indicator or the test indicator shall be located within the sensor such that it can only be seen when the housing is open/removed.
2.2.7.2 Remote Test, Microwave Signal
Provide a remote test capability. The remote test hardware may be integral to the sensor or a separate piece of equipment. The remote test shall be initiated when commanded by the alarm annunciation system. The remote test shall excite the sensing element and associated electronics causing an alarm signal to be transmitted to the alarm annunciation system. The sensor stimulation generated by the remote test hardware shall simulate a standard intruder moving within the sensor's detection pattern.
2.2.8 Passive Infrared Motion Sensor
The passive infrared motion sensor shall detect changes in the ambient level of infrared emissions caused by the movement of a standard intruder within the sensor's field of view. Upon detecting such changes, the sensor shall transmit an alarm signal to the alarm annunciation system. The sensor shall detect a change in temperature of no more than 2 degrees F, and shall detect a standard intruder traveling within the sensor's detection pattern at a speed of 0.3 to 7.5 feet per second across two adjacent segments of the field of view. Emissions monitored by the sensor shall be in the 8 to 14 micron range. The sensor shall be adjustable to obtain the coverage pattern shown. The sensor shall be equipped with a temperature compensation circuit.
2.2.8.1 Test Indicator, Infrared Emissions
The passive infrared motion sensor shall be equipped with an LED walk test indicator. The walk test indicator shall not be visible during normal operations. When visible, the walk test indicator shall light when the sensor detects an intruder. The sensor shall either be equipped with a manual control, located within the sensor's housing, to enable/disable the test indicator or the test indicator shall be located within the sensor such that it can only be seen when the housing is open/removed.
2.2.8.2 Remote Test, Infrared Emissions
to the sensor or a separate piece of equipment. The remote test shall be initiated when commanded by the alarm annunciation system. The remote test shall excite the sensing element and associated electronics causing an alarm signal to be transmitted to the alarm annunciation system. The sensor
2.2.9 Microwave-Passive Infrared Dual Detection Motion Sensor
SECTION 28 16 01 Page 16
The dual detection motion sensor shall be a single unit combining a detector which detects changes in the transmitted microwave signal and a detector which detects changes in the ambient level of infrared emissions caused by the movement of a standard intruder within the detection pattern. The detection pattern shall be capable of covering a 20 by 30 feet room. Upon detection of changes by either detector, a window of more than 3 seconds but less than 8 seconds shall be opened. If the other detector detects a change during this window, the sensor shall transmit an alarm signal to the alarm annunciation system. The passive infrared detector shall detect a change in temperature of no more than 2 degrees F, and shall detect a standard intruder traveling within the detection pattern at a speed of 0.3 to 7.5 feet per second across two adjacent segments of the field of view.
Emissions monitored by the sensor shall be in the range of 8 to 14 microns.
The microwave detector shall detect a standard intruder moving within the detection pattern at a speed of 0.3 to 7.5 feet per second. The microwave detector shall comply with 47 CFR 15 Subpart F. The controls shall not be accessible when the sensor housing is in place. The sensor shall be configured to produce an alarm when both detectors sense a target.
2.2.9.1 Test Indicator
The sensor shall be equipped with an LED walk test indicator for both the passive infrared detector and the microwave detector. The walk test indicator shall not be visible during normal operations. When visible, the walk test indicator shall light when the sensor detects an intruder. The sensor shall either be equipped with a manual control, located within the sensor's housing, to enable/disable the test indicators or the test indicators shall be located within the sensor such that it can only be seen when the housing is open/removed.
2.2.9.2 Remote Test
to the sensor or a separate piece of equipment. The remote test shall be initiated when commanded by the alarm annunciation system. The remote test shall excite each sensing element and associated electronics causing an alarm signal to be transmitted to the alarm annunciation system. The sensor
2.2.10 Photo-Electric Sensor
The photo-electric sensor shall detect an interruption of the light beam that links the transmitter and receiver caused by a standard intruder walking at a speed of less than 7.5 feet per second through the beam. Upon detecting such an interruption, the sensor shall transmit an alarm signal to the alarm annunciation system. The sensor shall use a pulsed infrared light source. Multiple sensors shall be able to operate within the same zone without interfering with each other. The coverage pattern shall be as shown.
2.2.10.1 Test Indicator, Photo-Electric System
The sensor shall be equipped with an LED walk test indicator. The walk test indicator shall not be visible during normal operations. When visible, the walk test indicator shall light when the sensor detects an intruder. The sensor shall either be equipped with a manual control, located within the
SECTION 28 16 01 Page 17 sensor's housing, to enable/disable the test indicator or the test indicator shall be located within the sensor so that it can only be seen when the housing is open/removed.
2.2.10.2 Remote Test, Photo Electric System
to the sensor or a separate piece of equipment. The remote test shall be initiated when commanded by the alarm annunciation system. The remote test shall excite each sensing element and associated electronics causing an alarm signal to be transmitted to the alarm annunciation system. The sensor
2.3 CENTRAL STATION HARDWARE
The central station computer shall be a standard unmodified digital computer of modular design. The CPU word size shall be 64 bits or larger. The operating speed of the processor shall be at least 150 MHZ.
2.3.1 Memory
The computer shall contain at least 40 megabytes of usable installed memory.
2.3.2 Power Supply
The power supply shall have a minimum capacity of 250 Watts.
2.3.3 Serial Port
a. One TIA-232-F serial port shall be provided for general use.
b. Adjustable data transmission rates from 9600 to 57.6 kbps shall be selectable under program control.
2.3.4 Parallel Port
An enhanced parallel port shall be provided.
2.3.5 Color Monitor
The monitor shall be no less than 17 inches, with a minimum resolution of 1280 by 1024 pixels, noninterlaced, and a maximum dot pitch of 0.0112 inches. The video card shall support at least 256 colors at a resolution of 1280 by 1024 pixels at a minimum rate of 70 Hz.
2.3.6 Keyboard
A 101 keyboard having a minimum 64 character standard ASCII character set based on ANSI INCITS 154 shall be furnished.
2.3.7 Enhancement Hardware
Enhancement hardware such as special function keyboards, special function keys, touch screen devices, or mouse shall be provided for frequently used operator commands such as: Help, Alarm Acknowledge, Place Zone In Access, SECTION 28 16 01 Page 18
Place Zone In Secure, System Test, Print Reports, Change Operator, Security Lighting Controls, and Display Graphics.
2.3.8 Disk Storage
A hard disk with controller having a maximum average access time of 10 milliseconds shall be provided. The hard disk shall provided a minimum of
2.0 gigabytes of formatted storage.
2.3.9 Floppy Disk Drive
A minimum of 1 high density floppy disk drive and controller in 3-1/2 inch diameter size shall be provided.
2.3.10 Magnetic Tape System
A 0.16 inch cartridge magnetic tape system shall be provided. The system capacity shall be 0.8 gigabytes minimum per tape. Each tape shall be computer grade, in a rigid cartridge with spring-loaded cover and write-protect capability.
2.3.11 Modem
Modem shall operate at 28.000 bps, full duplex on circuits using asynchronous communications. The modem shall have error detection, auto answer/autodial, and call progress detection. The modem shall meet the requirements of ITU V.34, ITU V.42 for error correction and ITU V.42 bis for data compression standards, and shall be suitable for operating on unconditioned voice grade telephone lines in conformance with 47 CFR 68.
2.3.12 Audible Alarm
The manufacturer's standard audible alarm shall be provided.
2.3.13 CD-ROM Drive
A CD-ROM drive having a nominal storage capacity of 650 megabytes shall be provided. The CD-ROM drive shall have the following minimum characteristics:
a. Data Transfer Rate: 1.2 Mbps.
b. Average Access Time: 150 milliseconds.
c. Cache memory: 256 Kbytes.
d. Data throughput: 1 Mbyte/second, minimum.
2.3.14 Dot Matrix Alarm Printer
A dot matrix alarm printer shall be provided and interconnected to the central station equipment. The dot matrix alarm printers shall have a minimum 96 character standard ASCII character set based on ANSI INCITS 154 and with graphics capability. The printer shall be able to print in both red and black without ribbon change. The printers shall have adjustable sprockets for paper width up to 11 inches, print at least 80 columns per line and have a minimum speed of 200 characters per second. Character spacing shall be selectable at 10, 12, or 17 characters per inch. The printers shall utilize sprocket-fed fan fold paper. The units shall have
SECTION 28 16 01 Page 19 programmable control of top-of-form. The printer shall be provided with 25,000 sheets of printer paper and 12 ribbons.
2.3.15 Report Printer
A report printer shall be provided and interconnected to the central station equipment. The printer shall be a laser printer with printer resolution of a minimum of 600 dots per inch. The printer shall have a minimum of 2 megabytes of RAM. Printing speed shall be a minimum of 8 pages per minute with a 100 sheet paper cassette and with automatic feed. Two thousand sheets of paper and 5 toner cartridges shall be furnished after successful completion of the endurance test.
2.3.16 Uninterruptible Power Supply (UPS)
A self contained UPS, suitable for installation and operation at the central station, shall be provided sized to provide a minimum of 6 hours of operation of the central station equipment. Equipment connected to the UPS shall not be affected in any manner by a power outage of a duration less than the rated capacity of the UPS. UPS shall be complete with all necessary power supplies, transformers, batteries, and accessories and shall include visual indication of normal power operation, UPS operation, abnormal operation and visual and audible indication of low battery power. The UPS shall be as specified.
2.4 SOFTWARE
The software shall support all specified functions. The central station shall be online at all times and shall perform all required functions as specified. Software shall be resident at the central station and/or the local processor as required to perform all specified functions.
2.4.1 System Software
The operating system shall perform the following functions:
a. Support multiuser operator with multiple tasks for each user.
b. Support operation and management of all peripheral devices.
c. Provide file management functions for disk I/O, including creation and deletion of files, copying of files, a directory of all files including size and location of each sequential and random ordered records.
d. Provide printer spooling.
2.4.2 Applications Software
2.4.2.1 Operator Commands
The operator's commands shall provide the means for entry of monitoring and control commands, and for retrieval of system information. Processing of operator commands shall commence within 1 second of entry, with some form of acknowledgment provided at that time. The operator's commands shall perform tasks including:
SECTION 28 16 01 Page 20
a. Request help with the system operation.
b. Acknowledge alarms.
c. Place zone in access.
d. Place zone in secure.
e. Test the system.
f. Change operator.
2.4.2.2 Command Input
Operator's commands shall be full English language words and acronyms selected to allow operators to use the system without extensive training or data processing backgrounds. The system shall prompt the operator in English word, phrase, or acronym. Commands shall be available in an abbreviated mode, in addition to the full English language (words and acronyms) commands, allowing an experienced operator to disregard portions, or all, of the prompt-response requirements.
2.4.2.3 Command Input Errors
The system shall supervise operator inputs to ensure they are correct for proper execution. Operator input assistance shall be provided whenever a command cannot be executed because of operator input errors. The system shall explain to the operator, in English words and phrases, why the command cannot be executed. The error responses requiring an operator to look up a code in a manual or other document are not acceptable. Conditions for which operator error assist messages shall be generated include:
a. The command used is incorrect or incomplete.
b. The operator is restricted from using that command.
c. The command addresses a point which is disabled or out of service.
d. The command addresses a point which does not exist.
e. The command would violate constraints.
2.4.2.4 Enhancements
The system shall implement the following enhancements by use of special function keys, touch screen, or mouse, in addition to all other command inputs specified:
a. Help: Used to produce a display for all commands available to the operator. The help command, followed by a specific command shall produce a short explanation of the purpose, use, and system reaction to that command.
b. Acknowledge Alarms: Used to acknowledge that the alarm message has been observed by the operator.
c. Place Zone in Access: Used to remotely disable all intrusion alarm circuits emanating from a specific zone. The system shall be structured so that tamper circuits cannot be disabled by the console operator.
d. Place Zone in Secure: Used to remotely activate all intrusion alarm circuits emanating from a specific zone.
e. System Test: Allows the operator to initiate a system wide operational test.
SECTION 28 16 01 Page 21
f. Zone Test: Allows the operator to initiate an operational test for a specific zone.
g. Print Reports: Allows the operator to initiate printing of reports.
h. Change Operator: Used for changing operators.
i. Security Lighting Controls: Allows the operator to remotely turn on/off security lights.
j. Display Graphics: Used to display any graphic displays implemented in the system.
2.4.3 Site Specific Database Software
2.4.3.1 Database Definition Process
Software shall be provided to define and modify each point in the database using operator commands. The definition shall include all physical parameters and constraints associated with each sensor, commandable output, zone, etc. Each database item shall be callable for display or printing, including EEPROM, ROM and RAM resident data. Define and enter the database into the central station based upon input from the Government.
2.4.3.2 System Access Control
The system shall provide a means to define system operator capability and functions through multiple, password operated protected operator levels. At least 3 operator levels shall be provided. System operators and managers with appropriate password clearances shall be able to change operator levels for all operators. Three successive attempts by an operator to execute functions beyond their defined level during a 24-hour period shall initiate a software tamper alarm. A minimum of 32 passwords shall be usable with the intrusion detection system software. The system shall display the operator's name or initials in the console's first field. The system shall print the operator's name or initials, action, date, and time on the system printer at log-on and log-off. The password shall not be displayed or printed. Each password shall be definable and assignable for the following:
a. Commands usable.
b.