This solicitation requests proposals for construction services to alter and add to an F-35 Squadron Operations facility at Truax Field in Madison, Wisconsin. Work includes reconfiguring existing space for F-35 Autonomic Logistics Information System functions and Optimization of the Human Weapon System, upgrading existing vault wall types to meet ICD 705 standards for multiple classification levels, and constructing additional Sensitive Compartmented Information Facility and Pilot Extraction Simulator Training areas. The project magnitude is between $1-5 million. The solicitation closes on January 20, 2021. The evaluation will consider technical, past performance, and price factors. The intent is to award without discussions. Interested parties must register in SAM and check the beta.SAM.GOV website for amendments and documents. Questions should be directed to the specified email.
View the file
Other files for this federal contract opportunity
Show all 45
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TRUAX FIELD ANGB - F-35: ADAL BLDG 404 ADDENDUM 2
XGFG182010 26 JAN 2021
SECTION 08 11 13
STEEL DOORS AND FRAMES
02/10
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN WELDING SOCIETY (AWS)
AWS D1.1/D1.1M (2015; Errata 1 2015; Errata 2 2016) Structural Welding Code - Steel
ASTM INTERNATIONAL (ASTM)
ASTM C578 (2018) Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation
ASTM E1300 (2016) Standard Practice for Determining Load Resistance of Glass in Buildings
ASTM F2248 (2012) Standard Practice for Specifying an Equivalent 3-Second Duration Design Loading for Blast Resistant Glazing Fabricated with Laminated Glass
BUILDERS HARDWARE MANUFACTURERS ASSOCIATION (BHMA)
ANSI/BHMA A156.115 (2016) Hardware Preparation in Steel Doors and Steel Frames
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 80 (2016; TIA 16-1) Standard for Fire Doors and Other Opening Protectives
NFPA 252 (2017) Standard Methods of Fire Tests of Door Assemblies
STEEL DOOR INSTITUTE (SDI/DOOR)
SDI/DOOR 111 (2009) Recommended Selection and Usage Guide for Standard Steel Doors, Frames and Accessories
SDI/DOOR 113 (2001; R2006) Standard Practice for Determining the Steady State Thermal Transmittance of Steel Door and Frame Assemblies
SDI/DOOR A250.4 (2011) Test Procedure and Acceptance Criteria for Physical Endurance for Steel Doors and Hardware Reinforcing
SECTION 08 11 13 Page 1
SDI/DOOR A250.6 (2003; R2009) Recommended Practice for Hardware Reinforcing on Standard Steel Doors and Frames
SDI/DOOR A250.8 (2003; R2008) Recommended Specifications for Standard Steel Doors and Frames
SDI/DOOR A250.11 (2001) Recommended Erection Instructions for Steel Frames
UNDERWRITERS LABORATORIES (UL)
UL 10C (2016) UL Standard for Safety Positive Pressure Fire Tests of Door Assemblies
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00
SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Doors; G
Recycled Content for Steel Door Product; S
Frames; G
Recycled Content for Steel Frame Product; S
Accessories
Show elevations, construction details, metal gages, hardware provisions, method of glazing, and installation details.
Schedule of Doors; G
Schedule of Frames; G
Submit door and frame locations.
SD-03 Product Data
Doors; G
Frames; G
Submit manufacturer's descriptive literature for doors, frames, and accessories. Include data and details on door construction, panel (internal) reinforcement, insulation, and door edge construction. When "custom hollow metal doors" are provided in lieu of "standard steel doors," provide additional details and data sufficient for comparison to SDI/DOOR A250.8 requirements.
Sound Rated Steel Door And Frame Assemblies
SECTION 08 11 13 Page 2
SD-07 Certificates
ICD-705 Certification For Rated Steel Door And Frame Assemblies
SD-11 Closeout Submittals
2-Year Full Component Warranty
1.3 DELIVERY, STORAGE, AND HANDLING
Deliver doors, frames, and accessories undamaged and with protective wrappings or packaging. Provide temporary steel spreaders securely fastened to the bottom of each welded frame. Store doors and frames on platforms under cover in clean, dry, ventilated, and accessible locations, with 1/4 inch airspace between doors. Remove damp or wet packaging immediately and wipe affected surfaces dry. Replace damaged materials with new.
PART 2 PRODUCTS
2.1 STANDARD STEEL DOORS
SDI/DOOR A250.8, except as specified otherwise. Prepare doors to receive door hardware as specified in Section 08 71 00. Undercut where indicated.
Provide exterior doors with top edge closed flush and sealed to prevent water intrusion. Provide doors at 1-3/4 inch thick, unless otherwise indicated. Provide door material that uses a minimum of 25 percent recycled content. Provide data indicating percentage of recycled content for steel door product. Provide exterior glazing in accordance with ASTM F2248 and ASTM E1300.
2.1.1 Classification - Level, Performance, Model
2.1.1.1 Extra Heavy Duty Doors
SDI/DOOR A250.8, Level 3, physical performance Level A, Model 2 with core construction as required by the manufacturer for interior doors, of size(s) and design(s) indicated.
2.1.1.2 Maximum Duty Doors
SDI/DOOR A250.8, Level 4, physical performance Level A, Model 2 with core construction as required by the manufacturer for exterior doors, of size(s) and design(s) indicated.
2.2 INSULATED STEEL DOOR SYSTEMS
Provide insulated steel doors with a core of polyurethane foam; face sheets, edges, and frames of galvanized steel not lighter than 16 gage respectively; magnetic weatherstripping; nonremovable-pin hinges;
thermal-break aluminum threshold; and vinyl door bottom. Provide to doors and frames a phosphate treatment, rust-inhibitive primer, and baked acrylic enamel finish. Test doors in accordance with SDI/DOOR A250.4 and meet the requirements for Level C. Prepare doors to receive specified hardware.
Provide doors 1-3/4 inch thick.
SECTION 08 11 13 Page 3
2.3 SOUND RATED STEEL DOOR AND FRAME ASSEMBLIES
2.3.1 Sound Rated Steel Door and Frame Assembly General
a. Door, frame, and hardwares shall be provided by a singular manufacturer/ supplier and come as a complete assembly system.
b. Assembly shall provide ICD-705 certification for secure area rated steel door and frame assemblies.
c. Assembly shall be installed by a manufacturer certified installer.
d. Assembly must be compatible with ADVANTOR Systems for monitoring and control.
e. Provide manufacturer and installer 2-year full component warranty.
2.3.2 Sound Rated Door
Provide 1-3/4" thick sound rated door with a Sound Transmission Class (STC) of 50, designed for Secure Area Sound Requirements. Doors shall be constructed 16 gauge cold rolled steel skins and acoustical core. Provide wood veneer, select white birch, face to match wood doors and finish in the facility. Door shall have a permanent STC rating label affixed to the face of the door.
2.3.3 Sound Rated Frame
Provide sound rated frame with a Sound Transmission Class (STC) of 50, designed for Secure Area Sound Requirements. Frames shall be constructed 14 gauge prime painted cold rolled steel skins and acoustical core. Provide 8
lb. density Thermafiber sound insulation at perimeter of door installation. Provide adjustable, magnetic perimeter acoustic seals.
Frames shall be compatible with wall construction type noted on drawings.
2.3.4 Hardware
Hardware to be prepped and provided by Sound Rated Steel Door and Frame Assembly manufacturer. See hardware schedule in specification 087110 for requirements.
2.4 ACCESSORIES
2.4.1 Astragals
For pairs of exterior steel doors which will not have aluminum astragals or removable mullions, as specified in Section 08 71 00 DOOR HARDWARE provide overlapping steel astragals with the doors. For interior pairs of fire rated doors, provide stainless steel astragals complying with NFPA 80 for fire rated assemblies.
2.4.2 Moldings
Provide moldings around glass of interior and exterior doors and louvers of interior doors. Provide nonremovable moldings on outside of exterior doors and on corridor side of interior doors. Other moldings may be stationary or removable. Secure inside moldings to stationary moldings, or provide snap-on moldings. Provide muntins that interlock at intersections and are fitted plus welded to stationary moldings.
SECTION 08 11 13 Page 4
2.5 INSULATION CORES
Provide insulating cores of the type specified, and provide an apparent U-factor of .48 in accordance with SDI/DOOR 113 and conforming to:
a. Rigid Polystyrene Foam Board: ASTM C578, Type I or II; or
2.6 STANDARD STEEL FRAMES
SDI/DOOR A250.8, Level 4, except as otherwise specified. Form frames to sizes and shapes indicated, with welded corners. Provide steel frames for doors, transoms, sidelights, and mullions unless otherwise indicated.
Provide frame product that uses a minimum of 25 percent recycled content.
Provide data indicating percentage of recycled content for steel frame product.
2.6.1 Welded Frames
Continuously weld frame faces at corner joints. Mechanically interlock or continuously weld stops and rabbets. Grind welds smooth.
Weld frames in accordance with the recommended practice of the Structural Welding Code Sections 1 through 6, AWS D1.1/D1.1M and in accordance with the practice specified by the producer of the metal being welded.
2.6.2 Mullions and Transom Bars
Provide mullions and transom bars of closed or tubular construction with heads and jambs butt-welded together. Bottom of door mullions must have adjustable floor anchors and spreader connections.
2.6.3 Stops and Beads
Form stops and beads from 20 gage steel. Provide for glazed and other openings in standard steel frames. Secure beads to frames with oval-head, countersunk Phillips self-tapping sheet metal screws or concealed clips and fasteners. Space fasteners approximately 12 to 16 inch on center. Miter molded shapes at corners. Butt or miter square or rectangular beads at corners.
2.6.4 Anchors
Provide anchors to secure the frame to adjoining construction. Provide steel anchors, zinc-coated or painted with rust-inhibitive paint, not lighter than 18 gage.
2.6.4.1 Wall Anchors
Provide at least three anchors for each jamb. For frames which are more than 7.5 feet in height, provide one additional anchor for each jamb for each additional 2.5 feet or fraction thereof.
a. Masonry: Provide anchors of corrugated or perforated steel straps or 3/16 inch diameter steel wire, adjustable or T-shaped;
b. Stud partitions: Weld or otherwise securely fasten anchors to backs of frames. Design anchors to be fastened to closed steel studs with sheet metal screws, and to open steel studs by wiring
SECTION 08 11 13 Page 5 or welding;
c. Completed openings: Secure frames to previously placed concrete or masonry with expansion bolts in accordance with SDI/DOOR 111;
and
d. Solid plaster partitions: Secure anchors solidly to back of frames and tie into the lath. Provide adjustable top strut anchors on each side of frame for fastening to structural members or ceiling construction above. Provide size and type of strut anchors as recommended by the frame manufacturer.
2.6.4.2 Floor Anchors
Provide floor anchors drilled for 3/8 inch anchor bolts at bottom of each jamb member. Where floor fill occurs, terminate bottom of frames at the indicated finished floor levels and support by adjustable extension clips resting on and anchored to the structural slabs.
2.7 FIRE DOORS AND FRAMES
NFPA 80 and this specification. The requirements of NFPA 80 takes precedence over details indicated or specified.
2.7.1 Labels
Provide fire doors and frames bearing the label of Underwriters Laboratories (UL), Factory Mutual Engineering and Research (FM), or Warnock Hersey International (WHI) attesting to the rating required. Testing must be in accordance with NFPA 252 or UL 10C. Provide labels that are metal with raised letters, bearing the name or file number of the door and frame manufacturer. Labels must be permanently affixed at the factory to frames and to the hinge edge of the door. Do not paint door and labels.
2.7.2 Astragal on Fire Doors
On pairs of labeled fire doors, conform to NFPA 80 and UL requirements.
2.8 WEATHERSTRIPPING
As specified in Section 08 71 00 DOOR HARDWARE.
2.9 HARDWARE PREPARATION
Provide minimum hardware reinforcing gages as specified in SDI/DOOR A250.6.
Drill and tap doors and frames to receive finish hardware. Prepare doors and frames for hardware in accordance with the applicable requirements of SDI/DOOR A250.8 and SDI/DOOR A250.6. For additional requirements refer to ANSI/BHMA A156.115. Drill and tap for surface-applied hardware at the project site. Build additional reinforcing for surface-applied hardware into the door at the factory. Locate hardware in accordance with the requirements of SDI/DOOR A250.8, as applicable. Set lock strikes out to provide clearance for silencers.
2.9.1 Hardware for Secure Doors
Secure rated doors must have all hardware prepared and installed on the door at the factory, and shipped to the site as part of the door assembly.
SECTION 08 11 13 Page 6
2.10 FINISHES
2.10.1 Factory-Primed Finish
Thoroughly clean all surfaces of doors and frames then chemically treat and factory prime with a rust inhibiting coating as specified in SDI/DOOR A250.8.
, or paintable A25 galvannealed steel without primer. Where coating is removed by welding, apply touchup of factory primer.
2.11 FABRICATION AND WORKMANSHIP
Provide finished doors and frames that are strong and rigid, neat in appearance, and free from defects, waves, scratches, cuts, dents, ridges, holes, warp, and buckle. Provide molded members that are clean cut, straight, and true, with joints coped or mitered, well formed, and in true alignment. Dress exposed welded and soldered joints smooth. Design door frame sections for use with the wall construction indicated. Corner joints must be well formed and in true alignment. Conceal fastenings where practicable. Design frames in exposed masonry walls or partitions to allow sufficient space between the inside back of trim and masonry to receive caulking compound.
2.11.1 Grouted Frames
For frames to be installed in exterior walls and to be filled with mortar or grout, fill the stops with strips of rigid insulation to keep the grout out of the stops and to facilitate installation of stop-applied head and jamb seals.
2.12 PROVISIONS FOR GLAZING
Materials are specified in Section 08 81 00, GLAZING.
PART 3 EXECUTION
3.1 INSPECTION
Doors and door assemblies may be subject to inspection at the project site prior to acceptance of the door or assembly.
3.2 INSTALLATION
3.2.1 Frames
Set frames in accordance with SDI/DOOR A250.11. Plumb, align, and brace securely until permanent anchors are set. Anchor bottoms of frames with expansion bolts or powder-actuated fasteners. Build in or secure wall anchors to adjoining construction. At sound rated steel door and frame assemblies, backfill frames with mortar, or as recommended by manufacturers.
3.2.2 Doors
Hang doors in accordance with clearances specified in SDI/DOOR A250.8.
After erection and glazing, clean and adjust hardware.
3.2.3 Fire Doors and Frames
Install fire doors and frames, including hardware, in accordance with
NFPA 80.
SECTION 08 11 13 Page 7
3.3 PROTECTION
Protect doors and frames from damage. Repair damaged doors and frames prior to completion and acceptance of the project or replace with new, as directed. Wire brush rusted frames until rust is removed. Clean thoroughly. Apply an all-over coat of rust-inhibitive paint of the same type used for shop coat.
3.4 CLEANING
Upon completion, clean exposed surfaces of doors and frames thoroughly.
Remove mastic smears and other unsightly marks.
-- End of Section --