This is a solicitation for construction services to build an 18,000 square foot Aircraft Maintenance Unit facility at Dannelly Field Air National Guard Base in Montgomery, Alabama. The scope of work includes site work, excavation, foundations, structural work, architectural, plumbing, mechanical, electrical and utility relocation. The contract duration is 450 calendar days from notice to proceed. The solicitation will be issued on SAM.gov as a 100% small business set-aside, with a NAICS code of 236210 and size standard of $45 million. The magnitude is over $10 million. The solicitation will include five sole source items for compatibility with existing systems.
View the file
Other files for this federal contract opportunity
Show all 28
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Date: 20 June 2023
To: CMSgt. William Hall
Subject: ADDENDUM NO. 3
Project: AIRCRAFT MAINTENANCE UNIT FACILITY
Job #: ANG# FAKZ169003 / SSL# 18153
From: David Donovan
The plans and Specifications for the Aircraft Maintenance Unit Facility, dated 01 August 2021 are amended as follows. (Where there are conflicts between the plans and specifications and the addendum, this addendum shall govern).
Item No. 1: Refer to drawings. Add the attached drawing sheet A0.1 with a revised date of 20 June 2023.
Item No. 2: Refer to drawings. Delete drawing sheet A2.1 “First Floor Plan” and replace it with the attached drawing sheet with a revised date of 20 June 2023.
Changes include, but are not limited to, the following:
- Addition of countertop detail section in Room 103, Maintenance Debrief.
- Change countertop from “GFCI” to “CFCI”
Item No. 3: Refer to drawings. Delete drawing sheet A2.2 “Second Floor Plan” and replace it with the attached drawing sheet with a revised date of 20 June 2023.
- Revised mullion spacing at opening type 2B.
- Add chase wall for wall mounted toilet fixture hangars in rooms
204 & 205.
AIRCRAFT MAINTENANCE UNIT FACILITY FAKZ169003
ADDENDUM NO. 3 Page 2 of 4 Seay Seay & Litchfield, P.C. 20 June 2023
Item No. 4: Refer to drawings. Delete drawing sheet A2.3 “Wall Type / Dimension
Floor Plan” and replace it with the attached drawing sheet with a revised date of 20 June 2023.
- Add chase wall for wall mounted toilet fixture hangars in rooms 204 & 205.
Item No. 5: Refer to drawings. Delete drawing sheet A3.5 “Glazed Opening
Schedule” and replace it with the attached drawing sheet with a revised date of 20 June 2023.
- Revised glazing types within opening 1F.
- Revised mullion spacing at opening type 2B.
- Add mullion detail to opening type 2B.
Item No. 6: Refer to drawings. Delete drawing sheet A6.1B “Enlarged Restroom
Plans & Elevations” and replace it with the attached drawing sheet with a revised date of 20 June 2023. Drawing has been updated to indicate a chase wall in second floor restrooms.
Item No. 7: Refer to specifications. Delete specification 00 0102 “Project Information
& Summary,” and replace it with the attached specification with a revised date of 20 June 2023. Specification has been updated to add Contractor’s Qualified Fire Protection Engineer Requirements and description of recent soil remediation project and resulting elevated temperature of in-situ soil.
Item No. 8: Refer to specifications. Delete specification 07 4113 “Metal Roof
Panels,” and replace it with the attached specification with a revised date of 20 June 2023. Specification has been updated to reflect that the Roofing Consultant Services will be furnished by the Government.
Item No. 9: Refer to specifications. Delete specification 07 4213 “Ribbed Metal Wall
Metal Wall Panels,” and replace it with the attached specification with a revised date of 20 June 2023. Specification has been updated to reflect that the Roofing Consultant Services will be furnished by the Government.
Item No. 10: Refer to specifications. Delete specification 07 4293 “Metal Soffit
Panels,” and replace it with the attached specification with a revised date of 20 June 2023. Specification has been updated to reflect that the Roofing Consultant Services will be furnished by the Government.
ADDENDUM NO. 3 Page 3 of 4 Seay Seay & Litchfield, P.C. 20 June 2023
Item No. 11: Refer to specifications. Delete specification 07 5400 “Thermoplastic
Membrane Roofing,” and replace it with the attached specification with a
Item No. 12: Refer to specifications. Delete specification 07 6200 “Sheet Metal
Flashing and Trim,” and replace it with the attached specification with a
Item No. 13: Refer to specifications. Delete specification 10 2800 “Toilet, Bath, and
Laundry Accessories,” and replace it with the attached specification with a revised date of 20 June 2023. Specifications have been updated to include revised trash / paper towel receptacles, soap dispenser, and toilet tissue dispensers.
Item No. 14: Refer to drawings. Delete drawing sheet FP0.1 “Fire Protection General
Notes, Legend, and Abbreviations” and replace it with the attached drawing sheet with a revised date of 20 June 2023.
- Add QFPE Requirements
Item No. 15: Refer to drawings. Delete drawing sheet E4.1 “First Floor Plan -
Auxiliary” and replace it with the attached drawing sheet with a revised date of 13 June 2023.
- Relocate CCTV camera positions.
- Clarify type (fix versus PTZ) of each CCTV camera.
Item No. 16: Refer to drawings. Delete drawing sheet E4.2 “Second Floor Plan -
Auxiliary” and replace it with the attached drawing sheet with a revised date of 13 June 2023.
- Delete NVR in room 215.
- As referenced in RFI responses, the facility CCTV cameras are intended to report to Base Defense Operations Control (BDOC) in Building 1502 where they will be monitored. Local monitoring of CCTV cameras in the AMU facility is not required. Coordinate camera system with existing head end equipment in the BDOC.
Ensure system is configured for recording and storage of a minimum of 30 days of video footage from the AMU facility.
ADDENDUM NO. 3 Page 4 of 4 Seay Seay & Litchfield, P.C. 20 June 2023
Item No. 17: Refer to drawings. Delete drawing sheet E4.5 “Communication Details” and replace it with the attached drawing sheet with a revised date of 13 June 2023.
- Add fiber optic cabling between the AMU and Squadron Operations Facility Server Room for ALIS connectivity.
Item No. 18: Refer to drawings. Delete drawing sheet E4.6 “Partial Floor Plans –
Comm Room Layouts” and replace it with the attached drawing sheet with a revised date of 13 June 2023.
- Add fiber optic cabling between the AMU and Squadron Operations Facility Server Room for ALIS connectivity.
Item No. 19: Refer to drawings. Delete drawing sheet E6.1 “Fire Alarm Riser and
Notes” and replace it with the attached drawing sheet with a revised date of 20 June 2023.
- Add QFPE Requirements
End of Addendum #3
CREPE M
YRTLE
CREPE M
YRTLE
x
FLIGHT LINE
APPROXIMATE LIMITS OF SQUAD
OPS FACILTY CONSTRUCTION SITE
APPROXIMATE
LIMITS OF AMU
FACILITY
CONSTRUCTION
SITE
CRUSHED AGGREGATE WALKWAY INSTALLED WITHIN THE SQUAD
OPS PROJECT. COORDINATE FENCING WITH ADJACENT SQUAD
OPS CONSTRUCTION EFFORTS.
AMU FACILITY CONSTRUCTION IS LIKELY TO BE ONGOING
DURING THE COURSE OF CONSTRUCTION OF THIS
PROJECT. CONTRACTOR TO COORDINATE THE WORK WITH
THE AWARDED CONTRACTOR FOR THE SQUAD OPS
PROJECT. PARKING AND STORAGE AREA ALONG THE
NORTH SIDE OF THE SQUAD OPS SITE WILL BE SHARED
BETWEEN THE AWARDED CONTRACTORS.
AREA RESERVED FOR GOVERNMENT
PARKING ONLY - CONSTRUCTION PARKING
NOT PERMITTED
CONTRACTOR PARKING AND
STORAGE AREA FOR FAKZ
189102
ACCESS TO CONSTRUCTION
PARKING AND STORAGE AREA
ANTICIPATED EXTENTS OF CONTRACTOR'S
SITE SECURITY FENCING. CONTRACTOR TO
PROVIDE FENCING AS REQUIRED AT SITE
BOUNDARY AND PARKING/STORAGE AREA
BOUNDARY AS REQUIRED TO PROTECT
CONTRACTOR MATERIAL/EQUIPMENT FROM
DAMAGE/THEFT AS WELL AS TO PREVENT
UNAUTHORIZED ACCESS TO
CONSTRUCTION AREAS AND PROTECT
SAFETY OF GENERAL PUBLIC WHO WILL
CONTINUE TO OCCUPY THE GENERAL AREA
DURING CONSTRUCTION ACTIVITIES.
CONTRACTOR TO FIELD VERIFY AND
COORDINATE FENCE LOCATIONS WITH
CONTRACTING OFFICER ON SITE.
CONTRACTOR PARKING AND
STORAGE AREA
APPROXIMATE EXTENTS OF EXISTING FLIGHT LINE SECURTY
FENCING. FENCING TO REMAIN. TIE NEW CONSTRUCTION
SECURITY FENCING TO EXISTING FLIGHT LINE SECURITY
FENCING.
ACCESS TO CONSTRUCTION
PARKING AND STORAGE AREA
FOR SQUAD OPS PROJECT
ANTICIPATED EXTENTS OF CONTRACTOR'S
SITE SECURITY FENCING. CONTRACTOR TO
PROVIDE FENCING AS REQUIRED AT SITE
BOUNDARY AND PARKING/STORAGE AREA
BOUNDARY AS REQUIRED TO PROTECT
CONTRACTOR MATERIAL/EQUIPMENT FROM
DAMAGE/THEFT AS WELL AS TO PREVENT
UNAUTHORIZED ACCESS TO
CONSTRUCTION AREAS AND PROTECT
SAFETY OF GENERAL PUBLIC WHO WILL
CONTINUE TO OCCUPY THE GENERAL AREA
DURING CONSTRUCTION ACTIVITIES.
CONTRACTOR TO FIELD VERIFY AND
COORDINATE FENCE LOCATIONS WITH
CONTRACTING OFFICER ON SITE.
Sheet Number
Sheet Title
Project Title
M on tg om er y
D ot ha n
W W
W .S
SL
A
R C
H .C
O M
(M ) 3
. 2
. 5
(D
) 3
. 7
. 5
Job Number
Date
Drawn By
Checked By
A
RC
H
IT
E
CT
U
RE
IN
TE
RI
O R
D E
SI
G
N
A0.1
SITE ACCESS
DIAGRAM
A
IR
CR
A
FT
M
A
IN
TE
N
A N
CE
FA
CI
LI
TY
U
N
IT
D A
N N
E
LL
Y F
IE
LD
M O
N
TG
O M
E
RY
A L
18153
08/01/2021
NJ, SS, LG, JJ
FEL
Rev. Description Date
1 ADD#3 6/20/23
1" = 30'-0"A0.1
1 SITE ACCESS PLAN
1 REFER TO CIVIL DRAWINGS FOR EXTENT OF DEMOLITION OF
EXISTING FENCING. CONTRACTOR TO COORDINATE
SEQUENCE AND SCHEDULE FOR REMOVAL OF TEMPORARY
CONSTRUCTION FENCING AND EXISTING FLIGHT LINE
SECURTY FENCING WITH SECURITY FORCES AND OVERALL
CONSTRUCTION SCHEDULE. FENCING SHALL REMAIN IN
PLACE FOR THE DURATION OF THE PROJECT. TEMPORARY
RELOCATION OF FENCING TO ALLOW PAVING CONNECTION
TO FLIGHT LINE WILL BE ALLOWED AND SHALL BE
COORDINATED IN ADVANCE WITH SECURITY FORCES.
REMOVAL OF FENCING SHALL NOT PROCEED UNTIL
COMPLETION OF LANDSCAPE WALLS TO PERMANENTLY
SECURE FLIGHT LINE AND AUTHORIZATION BY THE
GOVERNMENT.
SPECIFIC NOTES
UP
A4.2
L O
C
KE
R S
110 SF
BATTERY
STORAGE
109D
LINEAR NO-TOUCH
WASH BASIN - SEE
PLUMBING
HAZ AND SAP
PMA RACK PROVIDED BY
GENERAL CONTRACTOR.
EQUAL TO TEKCART
UNIVERSAL SC-DPH-48L-09
A5.1
A4.1
ICE MAKER - SEE SPECS
1221 SF
MENS
434 SF
WOMENS
492 SF
READY ROOM III
1063 SF
READY ROOM II
803 SF
READY ROOM I
314 SF
MAINTENANCE
DEBRIEF
345 SF
PRO SUPER
109 SF
SECURE
STORAGE
79 SF
COMM
93 SF
ELECTRICAL
55 SF
FIRE
345 SF
MECHANICAL
43 SF
BATTERY
CHARGING
109E
470 SF
EQUIPMENT
CHECKOUT
A5.2
A5.2
A5.2
A5.2
2 31 76
G
D
C
B
A
54 SF
JANITOR
J
106 SF
ELEV. MACHINE
ROOM
209 SF
STAIR
101B
144 SF
VESTIBULE
101A
979 SF
CIRCULATION
101C
76 SF
VEST.
101D
A7.11 2
A6.1 2
A6.13
A5.1
A5.1
A7.1
109C
109F
113112
109D
109G
101D
105A106A
105B
107B
101G
101A
109A109B
115 116 117 118
101E
101C
342 SF
TOOL COUNTER
1538 SF
TOOL STORAGE
(WEAPONS)
154 SF
DEPLOYMENT
LOADING
109B
720 SF
TOOL STORAGE
(AMU)
109C
A6.1B
A6.1B
A6.4
A5.3
A5.4
A5.3
A5.3
A5.3
106B
A5.4
A5.3
A5.3
101F
43 SF
VEST.
101E
107D
107E
A7.2 1
149 SF
BATHROOM
VESTIBULE
A6.2
A6.2
A6.3
A2.1
A7.2
A4.2 2 A4.11
E
H
1L
1K
1O
1P
1Q1Q
1R1S
1T
1N
1M
1M
BOLLARDS
1A
1B
1C
1D
1E
1G1H1I1G
1J
1F
A7.1 12
178 SF
TOOL STORAGE
(AVIONICS)
109G
MECHANICAL UNITS - SEE
MECHANICAL
MECHANICAL UNITS -
SEE MECHANICAL
L2.0
L2.0
101B
C.9
C.J.C.J.
SIM
107G
METAL
WALL
PANEL
BRICK
VENEER
ALL EQUIPMENT IN THIS SPACE TO BE
PROVIDED BY THE GOVERNMENT
107H
(3) AUTOMOTIVE SHELF
CABINETS WITH DOOR EQUAL
TO A1-232940FT-S2FHDN BY
BURROUGH BY CONTRACTOR.
PROVIDE TAPERED STAINLESS
STEEL TOP 30" DEEP, LENGTH
AS REQUIRED.
(5) MODULAR DRAWER
CABINETS EQUAL TO
M1-232940FT-MA05AL BY
BURROUGH PROVIDED BY
CONTRACTOR.
ELECTRIC WATER COOLER
WITH BOTTLE FILLER - SEE
PLUMBING
PROVIDE STAINLESS STEEL
COUNTERTOP 30" DEEP,
LENGTH AS REQUIRED.
109E
SIM
K
2.6 2.8 5.2 5.4 5.9 7.1 7.5
F
D.6
7.3
103A C
O U N
TE
R C
FC
I)
A7.4
3 7
D
C
B
A
2936 SF
MECHANICAL
MEZZANINE
A2.4
A2.4
A2.4
A2.6
MECHANICAL UNITS - SEE MECHANICAL
OPEN
TO
BELOW
A2.6
1. REFER TO TITLE SHEETS FOR ADDITIONAL GENERAL NOTES.
2. PROVIDE METAL STUD FURRING/FRAMING AND 5/8" GWB TO CONCEAL ALL STRUCTURAL ELEMENTS FROM FLOOR TO 6" FINISHED CEILING, UNLESS NOTED OTHERWISE.
3. GWB ON INTERIOR SIDE OF EXTERIOR WALLS TO EXTEND TO UNDERSIDE OF ROOF DECK AND/OR FLOOR DECK AS REQUIRED TO CONCEAL WALL
INSULATION.
GENERAL NOTES
LEGEND:
DOOR - SEE DOOR SCHEDULE
101 DOOR TAG - SEE DOOR SCHEDULE
ROOM NAME
101 ROOM TAG
A101
SIM
SECTION TAG
SF1 GLAZED OPENING TAG
RECESSED FIRE EXTINGUISHER CABINET
(CFCI)
(GFGI)
INDICATED ITEMS TO BE FURNISHED AND INSTALLED BY THE
CONTRACTOR
INDICATED ITEMS TO BE FURNISHED AND INSTALLED BY THE
GOVERNMENT.
GYPSUM BOARD METAL STUD VERTICAL EXPANSION JOINT
Sheet Number
Sheet Title
Project Title
M on tg om er y
D ot ha n
W W
W .S
SL
A
R C
H .C
O M
(M ) 3
. 2
. 5
(D
) 3
. 7
. 5
Job Number
Date
Drawn By
Checked By
A
RC
H
IT
E
CT
U
RE
IN
TE
RI
O R
D E
SI
G
N
A2.1
FIRST FLOOR PLAN
A
IR
CR
A
FT
M
A
IN
TE
N
A N
CE
FA
CI
LI
TY
U
N
IT
D A
N N
E
LL
Y F
IE
LD
M O
N
TG
O M
E
RY
A L
18153
08/01/2021
NJ, SS, LG, JJ
FEL
1/8" = 1'-0"A2.1
1 FIRST FLOOR PLAN
1/8" = 1'-0"A2.1
2 MECHANICAL MEZZANINE
SPECIFIC NOTE LEGEND
ACCESS LADDER - COORDINATE LOCATION WITH ALL ARCHITECTURAL, ELECTRICAL, MECHANICAL, FIRE PROTECTION, STRUCTURAL, AND PLUMBING ELEMENTS. REFER TO SECTION 5/A2.4
PROVIDE STEEL PAINTED RAILINGS TO PROTECT INACTIVE LEAVES OF SLIDING DOOR (INTERIOR AND EXTERIOR). LOCATE VERTICAL 1 1/2" POSTS AS REQUIRED. COORDINATE LOCATION WITH DOOR MANUFACTURER. GUARD TO BE 36" TALL, WITH 1-1/2" RAILS AS FOLLOWS:
TOP RAIL@ 36" AFF, INTERMEDIATE RAIL @ 18" AFF, BOTTOM RAIL @ 4" AFF. PAINT.
3 PROVIDE ONE GLASS WRITABLE BOARD IN THIS LOCATION, TO BE 7'-2 3/4" LONG, 3'-0" TALL, BOTTOM EDGE TO BE MOUNTED AT 3'-0" AFF.
4 PROVIDE REMOVABLE GUARDRAIL ACROSS ENTIRE OPEN EDGE OF MEZZANINE. REMOVEABLE SECTIONS SHALL BE NO LONGER THAN 8'-0" - SPACE BETWEEN REMOVABLE SECTIONS SHALL NOT BE GREATER THAN 4". SUBMIT COMPLETE SHOP DRAWINGS FOR WRITTEN APPROVAL.
5 PROVIDE 2,000 LB CAPACITY DAVIT CRATE WITH 87.25 INCH REACH MINIMUM. EQUAL TO VESTIL WTJ-20-4-DC. COORDINATE EXACT
LOCATION WITH GOVERNMENT AND MECHANICAL / ELECTRICAL EQUIPMENT AS REQUIRED.
6 ELECTRICAL OUTLETS ON THIS WALL TO BE MOUNTED ABOVE STORAGE SOLUTIONS - COORDINATE WITH COUNTER HEIGHT. SEE ELCTRICAL.
Rev. Description Date
1 ADD#2 5/19/23
2 ADD#3 6/20/23
UP
A4.2
A5.1
OPEN TO BELOW
151 SF
ST SGT
155 SF
NCOIC
155 SF
NCOIC
155 SF
WEAPONS
SUPER
161 SF
AVIONICS
SUPER
210 161 SF
FLIGHT OFF.
208 SF
FLIGHT OFF.
376 SF
CONFERENCE
ROOM
378 SF
BREAK ROOM
58 SF
UNI RR
63 SF
UNI RR
204 180 SF
ELECTRICAL /
COMM
109 SF
CTK OFFICE
295 SF
FSR ADMIN
A5.2
A5.2
A5.2
A5.2
2 31 76
G
D
C
B
A
J
965 SF
CIRCULATION
201C
674 SF
FLIGHT ADMIN
A5.1
334 SF
CIRCULATION
201B
A5.1
A5.4
128 SF
STAIR
201A
204205
201B
213 212 211214 210 209
201A
A5.3
A5.4
A5.3
A5.3
A5.3
A5.4
A6.2
A6.2
A6.3
A6.1B 2
A7.3
A7.3
A7.6
A7.6 2
A7.63
E
H
2I
2J
2L
2M2M2M2M2M2M
2N
2O
2K
A2.6
2A 1B
1C
1D
2B
2C1F
2D2D2D2D
2E
2E
2F 2F
2G
2G
A7.3
A6.1B
201C
C.9
A2.6
METAL
WALL
PANEL
BRICK
VENEER
A5.2
A5.2
SIM
SIM
K
2.6 2.8 5.2 5.4 5.9 7.1 7.5 7.7
F
D.6
7.3
1. REFER TO TITLE SHEETS FOR ADDITIONAL GENERAL NOTES.
2. PROVIDE METAL STUD FURRING/FRAMING AND 5/8" GWB TO CONCEAL ALL STRUCTURAL ELEMENTS FROM FLOOR TO 6" FINISHED CEILING, UNLESS NOTED OTHERWISE.
3. GWB ON INTERIOR SIDE OF EXTERIOR WALLS TO EXTEND TO UNDERSIDE OF ROOF DECK AND/OR FLOOR DECK AS REQUIRED TO CONCEAL WALL
INSULATION.
GENERAL NOTES
LEGEND:
DOOR - SEE DOOR SCHEDULE
101 DOOR TAG - SEE DOOR SCHEDULE
ROOM NAME
101 ROOM TAG
A101
SIM
SECTION TAG
SF1 GLAZED OPENING TAG
RECESSED FIRE EXTINGUISHER CABINET
(CFCI)
(GFGI)
INDICATED ITEMS TO BE FURNISHED AND INSTALLED BY THE
CONTRACTOR
INDICATED ITEMS TO BE FURNISHED AND INSTALLED BY THE
GOVERNMENT.
GYPSUM BOARD METAL STUD VERTICAL EXPANSION JOINT
Sheet Number
Sheet Title
Project Title
M on tg om er y
D ot ha n
W W
W .S
SL
A
R C
H .C
O M
(M ) 3
. 2
. 5
(D
) 3
. 7
. 5
Job Number
Date
Drawn By
Checked By
A
RC
H
IT
E
CT
U
RE
IN
TE
RI
O R
D E
SI
G
N
A2.2
SECOND FLOOR
PLAN
A
IR
CR
A
FT
M
A
IN
TE
N
A N
CE
FA
CI
LI
TY
U
N
IT
D A
N N
E
LL
Y F
IE
LD
M O
N
TG
O M
E
RY
A L
18153
08/01/2021
NJ, SS, LG, JJ
FEL
1/8" = 1'-0"A2.2
1 SECOND FLOOR PLAN
PROVIDE PARTITION CLOSURE TRIMS IN THIS LOCATION - SEE 9/A2.41
SPECIFIC NOTE LEGEND
PROVIDE FURRING FOR ENCLOSURE OF VAPOR MITIGATION VENT,
SIZE AS REQUIRED TO CONCEAL. COORDINATE WITH ADJACENT
GLAZED OPENING - REFER TO VAPOR MITIGATION DRAWINGS.
Rev. Description Date
1 ADD#3 6/20/23
G C J
G C J
G C J
G C J G C J
GCJ GCJ
GCJ
2 31 7
G
D
C
B
A
J
N8N8N8N8
N8 N8N8
N8
N8
N8
N8 N8
N8
N4
N4
N8
N8
N8 N8
N8 N8
N8
N8 N8
N8
N8
N4
N8
N8
N4
N4
N4
N8N8
N8
N8
N8
N8 N8
N8 N8
N8 N8
N8
N8N8
N8N8
N8
N8 N8
N8N8
N8
N4
N4
N4
N4
N4
N4 N4
N4
N8
N8
N8
N8 N8
N8 N8
N8
N8 N8
N8 N8
N8
C6 C6
C3
C3
C3
C3
C3
C3
C3
C8
C3
C8
C3
C3
C3
C6
C3C3
C3
C3
C3A1
A3
C3
N8
N8
N8
N8
A1
A1
E
H
A3
C6
A1
A1
A1A1
A0A1
11' - 6 7/8" 12' - 8 3/4" 4' - 10"
3' - 3 5/16" 3' - 4"
5' - 4"
2' - 4 11/16"
4' - 10" 11' - 6"
2' - 7 7/16" 4' - 9 7/8" 0' - 7 13/16"
10' - 4 3/8" 13' - 2 1/16"
/1
/1
/1
/3
/4
40' - 8 3/4" 5' - 10 1/2" 8' - 5 7/16" 9' - 10 5/16"
10' - 6 5/16" 13' - 7 15/16" 1' - 4 7/16"
/1
/1
/8
/1
/1
/4
9' - 11 1/4"
8' - 0 1/4"
6' - 0 3/4" 6' - 7 7/8" 7' - 9" 7' - 7 1/8" 14' - 1 1/2"
/4
/8
1' - 11 13/16" 2' - 3 5/8"
8' - 1 1/2"
/8
24' - 1 11/16" 31' - 6"
3' - 3 5/8" 3' - 3 5/8"
4' - 8 1/4"
/1
/4
/1
5' - 6" 7' - 6"
5' - 2 9/16"
/4
13' - 3 1/16"
/1
/8
2' - 4" 3' - 1 7/8"
2' - 4 3/8"
10' - 6 1/4"
13' - 1 1/8"
/1
/8
5' - 2 5/8" 13' - 0"
6' - 9 1/8"
3' - 8 5/8" 10' - 6 1/2"
1' - 5 3/8"
10' - 0 7/8"
/1
2' - 1 23/32" 2' - 0" 2' - 0" 2' - 0" 6' - 0 15/32" 0' - 11 1/4"
/4
9' - 4 5/8"
3' - 10 7/16"
/3
/1
C3
C3C3
C.9
THESE WALLS
TO EXTEND TO
10'-0" AFF
K
2.6 2.8 5.2 5.4 5.9 7.1 7.5
F
2 31 76
G
D
C
B
A
J
N8
C6A1
A1
N8 N8
N8
N8
C6C6
C6
C6
A3C6
A3 C6
C6
C3
C3C3C3 C3
C3
C3
C3
C3
C6
C3
C3
C6
E E
H
13' - 6 3/8" 8' - 11 15/16"
1' - 0 1/16"
12' - 0 1/8" 11' - 11 7/8" 12' - 0"
11' - 1 1/4" 10' - 7 1/8" 10' - 7 3/8"
2' - 1 1/4"3' - 0"2' - 11 7/8"3' - 0 1/8"2' - 7 7/8"
1' - 0 9/16"
2' - 9 3/8" 19' - 10 1/2"
/8
/3
/8
/3
/4
/4
/2
8' - 1 7/8"
8' - 9 5/8"
5' - 8 3/8"
4' - 9 7/8" 15' - 10 7/16" 9' - 2 7/16"
/1
/1
/1
/1
11' - 6 7/8" 12' - 8 3/4" 4' - 10"
3' - 3 5/16"
3' - 4"
5' - 4"
2' - 4 11/16" 4' - 10"
11' - 6"
2' - 7 7/16" 4' - 9 7/8" 0' - 7 13/16"
5' - 8"
4' - 8 3/8"
3' - 8" 9' - 6 1/16"
2' - 1 13/32" 2' - 0" 2' - 0" 2' - 0"
/4
2' - 3 1/8"
2' - 3 1/8"
4' - 2 1/4"
1' - 0 1/4"
/2
2' - 9 3/4" 1' - 0"
/3
0' - 6 5/8"9' - 0 23/32"3' - 1 7/16"
12' - 0 11/16"
/8
/4
/2
0' - 10 1/8"
A0 C3
A0
C.9
K
2.6 2.8 5.2 5.4 5.9 7.1 7.5 7.7
F
D.6
7.3
22222
222222
A3 2
1 2*
1. THE FIRST CHARACTER IN THE TAG REFERENCES THE PARTITION TYPE
2. THE SECOND CHARACTER IN THE TAG REFERENCES THE THICKNESS
OF THE STRUCTURE (CMU, METAL STUD, WOOD, ETC.)
REFER TO INTERIOR ELEVATIONS AND ASSOCIATED WALL SECTIONS
AND DETAILS FOR ADDITIONAL FURRING REQUIREMENTS AND
FINISHES NOT SHOWN ON WALL TYPE PLAN SCHEDULE.
**NOTE - REFER TO LIFE SAFETY PLAN FOR PARTITION RATINGS**
PARTITION TAG LEGEND
1. REFER TO FLOOR PLANS FOR ADDITIONAL FURRING REQUIREMENTS THAT MAY NOT BE
SHOWN ON THIS DRAWING.
2. REFER TO EXTERIOR WALL SECTIONS FOR EXTERIOR WALL ASSEMBLIES. THIS PLAN MAY
REQUIRE ADDITION FUR-OUT NOT SHOWN ON THIS DRAWING.
3. UNLESS SPECIFICALLY NOTED OTHERWISE, ALL WALLS ( INCLUDING STRUCTURE, FINISH,
AND INSULATION) SHALL EXTEND TO UNDERSIDE OF ROOF DECK ABOVE.
4. ALL WALLS TO RUN FULL HEIGHT TO STRUCTURE ABOVE. COORDINATE OPENINGS TO
ACCOMODATE MECHANICAL. SEAL ALL PLUMBING, MECHANICAL, ELECTRICAL, AND FIRE
PROTECTION PENETRATIONS.
5. FOR EXTERIOR WALL EXPANSION JOINTS SEE EXTERIOR ELEVATIONS.
6. REFER TO A2.7 AND SPECIFICATION SECTION 01 2300 FOR LOCATIONS DEMOUNTABLE
PARTITIONS TO BE PROVIDED BY BID OPTION.
DIMENSION NOTES: ALL DIMENSIONS ARE MEASURED AS FOLLOWS:
- INTERIOR STUD WALLS ARE DIMENSIONED TO THE CENTER LINE OF THE WALL
- EXTERIOR WALLS ARE DIMENSIONED TO THE OUTSIDE FACE OF THE STUDS OR CMU.
WALL TYPE PLAN LEGEND
EXTEND PARTITION WALLS TO UNDERSIDE OF ROOF
DECK OR FLOOR. SEE A2.6 FOR PARTITION HEAD
DETAILS. PROVIDE CODE COMPLIANT SEAL
WALL TAG
# SPECIFIC NOTE TAG
GYPSUM CONTROL JOINT - REFER TO DETAIL 6/A2.4
WALL TYPE PLAN GENERAL NOTES
WALL TYPE PLAN SPECIFIC NOTES
WALLS IN THESE AREAS TO RECEIVE ADDITIONAL FINISHES.
WALL TAGS ARE INTENDED TO IDENTIFY GENERAL WALL
ASSEMBLY REQUIREMENTS. REFER TO INTERIOR
ELEVATIONS. SUBSTITUTION OF CEMENTITIOUS BOARD FOR
GYPSUM WALL BOARD IS REQUIRED WHERE WALL IS
SCHEDULED TO RECIEVE TILE.
AS AN ALTERNATE CONSTRUCTION METHOD, THIS WALL IS
TO BE A DEMOUNTABLE PARTION PROVIDED BY BID OPTION.
REFER TO A2.7 AND SPECIFICATION SECTION 01 2300 FOR
ADDITIONAL INFORMATION.
DENOTES REQUIRED STC50 RATED ASSEMBLY. GROUT
FILL ALL CELLS. GROUT TOP OF WALL TIGHT TO
UNDERSIDE OF FLOOR ABOVE.
Sheet Number
Sheet Title
Project Title
M on tg om er y
D ot ha n
W W
W .S
SL
A
R C
H .C
O M
(M ) 3
. 2
. 5
(D
) 3
. 7
. 5
Job Number
Date
Drawn By
Checked By
A
RC
H
IT
E
CT
U
RE
IN
TE
RI
O R
D E
SI
G
N
A2.3
WALL TYPE /
DIMENSION
FLOOR PLAN
A
IR
CR
A
FT
M
A
IN
TE
N
A N
CE
FA
CI
LI
TY
U
N
IT
D A
N N
E
LL
Y F
IE
LD
M O
N
TG
O M
E
RY
A L
18153
08/01/2021
NJ, SS, LG, JJ
FEL
1/8" = 1'-0"A2.3
1 1ST FLOOR - WALL TYPE / DIM PLAN
1/8" = 1'-0"A2.3
2 2ND FLOOR - WALL TYPE / DIM PLAN
Rev. Description Date
1 ADD#2 5/19/23
2 ADD#3 6/20/23
(Aluminum Curtain Wall System)
1A
Opening Type 1A
IG-1 IG-1
SEE DOOR
SCHEDULE
AS SCHEDULED
DOOR WIDTH
D O
O R
H
EI
G H T
A S S
C H
ED
U
LE
D
EQ EQ
A5.5
A5.8
A5.8
SIM
(Aluminum Window System)
1B
Opening Type 1B
IG-2
IG-1
IG-1
IG-1
IG-1
IG-1IG-1
IG-1IG-1
EQ EQ
6' - 2 3/4"
/2
/2
/4
/4
/4
/4
A5.6
A5.7
A5.5
A5.8
A5.8
A5.8
A5.8
IG-2
IG-1
IG-1
(Aluminum Window System)
1C
Opening Type 1C
IG-1 IG-1 IG-1 IG-1
IG-1IG-1IG-1IG-1
IG-1 IG-1 IG-1 IG-1
IG-1IG-1IG-1IG-1
IG-1 IG-1 IG-1 IG-1
IG-1IG-1IG-1IG-1
17' - 6 3/8"
/4
/8
/8
/4
A5.6
A5.5
A5.7
A5.8
A5.8
A5.8
A5.8
SIM
SIM
EQ EQ EQ EQ
(Aluminum Curtain Wall System)
1D
Opening Type 1D
IG-1 IG-1 IG-1
IG-1IG-1IG-1
IG-2 IG-2 IG-2
IG-1IG-1
EQ
AS SCHEDULED
DOOR WIDTH
EQ
D O
O R
H
EI
G H T
A S S
C H
ED
U
LE
D
/4
SEE DOOR SCHEDULE
7' - 9 3/4"
A5.5
A5.8
A5.8
A5.9
(Aluminum Window System)
1E
Opening Type 1E
IG-1 IG-1 IG-1
IG-2IG-2IG-2
EQEQEQ
A5.5
A5.8
A5.8
A5.5
12' - 7 3/4"
(Aluminum Curtain Wall System)
1G
Opening Type 1G
IG-1 IG-1 IG-1
IG-2IG-2IG-2
3' - 3 3/4" 3' - 4 1/2" 3' - 3 3/4"
10' - 0"
A5.9
A5.9
A5.9
A5.9
(Aluminum Curtain Wall System)
1H
Opening Type 1H
IG-2 IG-2 IG-2
IG-1IG-1
SEE DOOR
SCHEDULE
3' - 4" 3' - 4 1/4"
AS SCHEDULED
DOOR WIDTH
10' - 0"
SEE NOTE 6
D O
O R
H
EI
G H T
A S S
C H
ED
U
LE
D
A5.9
A5.9
A5.9
A5.9
(Aluminum Curtain Wall System)
1I
Opening Type 1I
IG-2 IG-2 IG-2
IG-1IG-1
SEE DOOR
SCHEDULE
10' - 0"AS SCHEDULED
DOOR WIDTH
3' - 4 3/8" 3' - 3 7/8"
D O
O R
H
EI
G H T
A S S
C H
ED
U
LE
D
A5.9
A5.9
SEE NOTE 6
A5.9
A5.9
(Aluminum Curtain Wall System)
1F
Opening Type 1F
IG-2 IG-2
IG-1IG-1
IG-1 IG-1
IG-2IG-2
IG-2 IG-2
IG-1IG-1 SEE DOOR
SCHEDULE
EQ EQ
/4
/2
/2
D O
O R
H
EI
G H T
A S S
C H
ED
U
LE
D
/2
5' - 0 7/8"
A5.5
A5.9 ___________3
A5.9
A5.8
(Aluminum Window System)
1J
Opening Type 1J
IG-1IG-1IG-1
4' - 0" 4' - 0" 4' - 0"
12' - 0"
A5.7
A5.9
A5.9
A5.7
(Aluminum Window System)
2A
Opening Type 2A
IG-1 IG-1 IG-1
IG-1IG-1IG-1
IG-1 IG-1 IG-1
/2
/2
/4
/4
3' - 3 1/2" 3' - 3 1/2" 3' - 3 1/2"
A5.7
A5.8
A5.6
A5.8
(Aluminum Window System)
2B
Opening Type 2B
IG-1IG-1IG-1IG-1
IG-1 IG-1 IG-1 IG-1
/2
/2
21' - 4"
A5.5
A5.6
A5.6
A5.6
SIM
5' - 4" 5' - 4" 5' - 4" 5' - 4"
A2.4
(Aluminum Window System)
2D
Opening Type 2D
IG-1IG-1IG-1
IG-1 IG-1 IG-11
/2
/2
EQ EQ EQ
10' - 0"
A5.7
A5.5
A5.8
A5.8
(Aluminum Window System)
2E
Opening Type 2E
IG-1 IG-1
4' - 0" 4' - 0"
8' - 0"
A5.7
A5.8
A5.8
A5.6
(Aluminum Window System)
2F
Opening Type 2F
IG-1 IG-1 IG-1 IG-1 IG-1 IG-1 IG-1
35' - 10 1/8"
A5.6
A5.8
A5.8
A5.6
IG-1
A5.7
8' - 4 3/4"0' - 10 1/8"26' - 7 1/4"
4' - 8 3/4" 3' - 8"3' - 8 1/8" 4' - 7" 4' - 7" 4' - 7" 4' - 7" 4' - 7"
A5.6
A5.6
(Aluminum Window System)
2C
Opening Type 2C
IG-1
IG-1
A5.5
A5.8 ___________9
A5.8
A5.7
8' - 6 1/2"
8' - 6 1/2"
IG-1
IG-1
Sheet Number
Sheet Title
Project Title
M on tg om er y
D ot ha n
W W
W .S
SL
A
R C
H .C
O M
(M ) 3
. 2
. 5
(D
) 3
. 7
. 5
Job Number
Date
Drawn By
Checked By
A
RC
H
IT
E
CT
U
RE
IN
TE
RI
O R
D E
SI
G
N
A3.5
GLAZED OPENING
SCHEDULE
A
IR
CR
A
FT
M
A
IN
TE
N
A N
CE
FA
CI
LI
TY
U
N
IT
D A
N N
E
LL
Y F
IE
LD
M O
N
TG
O M
E
RY
A L
18153
08/01/2021
NJ, SS, LG, JJ
FEL
GENERAL CURTAIN WALL AND STOREFRONT NOTES:
1. BLAST MITIGATION
A. ALL EXTERIOR GLAZED CURTAIN WALL AND STOREFRONT FRAMED ENTRANCE ASSEMBLIES. INCLUDING, BUT NOT LIMITED TO, GLAZING, FRAMING, CONNECTIONS, AND SUPPORTING STRUCTURAL ELEMENTS MUST MEET OR EXCEED DESIGN AND TEST REQUIREMENTS OF UFC 4.10.01 DOD MINIMUM ANTI-TERRORISM
STANDARD FOR BUILDINGS (LATEST EDITION).
2. FIRE-RESISTANCE RATING
A. ALL INTERIOR AND EXTERIOR CURTAIN WALL, STOREFRONT AND STOREFRONT FRAMED ENRANCE SHALL BE
PROVIDED TO MEET THE FIRE-RESISTANCE RATINGS AT LOCATIONS INDICATED ON SCHEDULES AND
DRAWINGS. SEE LIFE SAFETY PLAN FOR REQUIRED ASSEMBLY RATINGS.
3. CURTAIN WALL AND STOREFRONT MANUFACTURER/ FABRICATOR/ INSTALLER SHALL PROVIDE, INSTALL AND/OR ANCHOR ANY ADDITIONAL STEEL/REINFORCEMENT NOT OTHERWISE SHOWN ON DRAWINGS AND PROVIDE ALL ANCHORAGES NECESSARY TO MEET ANTI-TERRORISM STANDARDS AND INTERNATIONAL BUILDING CODE
WINDLOADING REQUIREMENTS.
4. VERIFY ALL DIMENSIONS PRIOR TO FABRICATION AND INSTALLATION FOR CURTAIN WALL AND STOREFRONT.
IMMEDIATELY NOTIFY ARCHITECT OF ANY DISCREPENCIES.
5. INSTALL CURTAIN WALL AND STOREFRONT ASSEMBLIES AND IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS.
6. COORDINATE CLEAR OPENING (WIDTH AND HEIGHT) OF CURTAIN WALL TO ACCOMODATE ALUMINUM SUBFRAME
WITH OPENING SIZES SPECIFIED.
*GENERAL NOTE: VERIFY ALL DIMENSIONS WITH JOB CONDITIONS PRIOR TO FABRICATION
Rev. Description Date
1 ADD#3 6/20/23
E
F
BD
G
PNT 5
A
RB1
D
B
PNT 5
K
G
E
C
F
CL
RB1
IK C
PNT 5
RB 1
SS2
1' - 9"
CHECK ELECTRICAL
RB 1
MM
N N
M
N
HT-1
PNT-1
RB 1
P
N N M M
HT-1
HT-1
RB 1
O
E N
P
N
MM
HT-1
E
CONCRETE MASONRY UNIT
WATERPROOOF MEMBRANE
THIN SET HARD TILE WITH EPOXY GROUT
SEALANT & BACKER ROD
WATERPROOFING
HARD TILE - SEE FINISH SCHEDULE
AND FLOOR PATTERN PLAN
SETTING BED
ADA COMPLIANT SLOPE
RECESSED SLAB - SEE
STRUCTURAL
ADA COMPLIANT SLOPENO SLOPE
A6.1B 2
A6.1B 4
SIM
F
G
B
D
F
G
D
B
KK
CC
E E
58 SF
UNI RR
63 SF
UNI RR
I I
A A
1' - 8" 1' - 8"
/8
/8
204205
JJ
/2 " M
IN
/2 " M
IN
A6.1 ___________4
A6.1
FIRE EXTINGUISHER - SEE LIFE SAFETY PLAN
Sheet Number
Sheet Title
Project Title
M on tg om er y
D ot ha n
W W
W .S
SL
A
R C
H .C
O M
(M ) 3
. 2
. 5
(D
) 3
. 7
. 5
Job Number
Date
Drawn By
Checked By
A
RC
H
IT
E
CT
U
RE
IN
TE
RI
O R
D E
SI
G
N
A6.1B
ENLARGED
RESTROOM PLANS
& ELEVATIONS
A
IR
CR
A
FT
M
A
IN
TE
N
A N
CE
FA
CI
LI
TY
U
N
IT
D A
N N
E
LL
Y F
IE
LD
M O
N
TG
O M
E
RY
A L
18153
08/01/2021
NJ, SS, LG, JJ
FEL
1/2" = 1'-0"A6.1B
2 SECOND FLOOR RESTROOM ELEVATION A
1/2" = 1'-0"A6.1B
3 SECOND FLOOR RESTROOM ELEVATION B
1/2" = 1'-0"A6.1B
4 SECOND FLOOR RESTROOM ELEVATION C
1/2" = 1'-0"A6.1B
5 MEN'S SHOWER NORTH ELEVATION
1/2" = 1'-0"A6.1B
6 MEN'S SHOWER SOUTH ELEVATION
1/2" = 1'-0"A6.1B
7 WOMEN'S SHOWER ELEVATION
GENERAL NOTES:
1. REFER TO SPEC SECTION 10 2800 - TOILET, BATH, AND LAUNDRY ACCESSORIES
FOR TOILET AND BATH ACCESSORIES SCHEDULE.
2. PROVIDE AND INSTALL CONCEALED WOOD BLOCKING IN STUD FRAMING WALLS
FOR SECURING TOILET ACCESSORIES AND TOILET PARTITIONS PER
MANUFACTURERS RECOMMENDATION PRIOR TO INSTALLING SUBSTRATES AND
FINISH WALL MATERIALS.
3. LOCATE AND INSTALL TOILET ACCESSORIES AT HEIGHTS AND DISTANCES
COMPLYING WITH ICC A117.1 (LATEST EDITION), ADA (LATEST EDITION), AND
MANUFACTURERS INSTALLATION RECOMMENDATIONS FOR COMPLYING WITH
ADA.
4. REFER TO PLUMBING FOR ADDITIONAL REQUIREMENTS.
5. PROVIDE 3/4" THICK QUARTZ SS2 AS SHOWN BEHIND ELECTRIC HAND-DRYER AS
SHOWN IN ROOMS 205 AND 205. QUARTZ TO PROJECT OUT FROM GYPSUM
WALL BOARD 3/4". THE RUBBER BASE SHALL TERMINATE IN THE 1/4" QUARTZ
PROJECTION.
3" = 1'-0"A6.1B
8 SHOWER FLOOR DETAIL, TYPICAL
3/4" = 1'-0"A6.1B
1 SECOND FLOOR UNISEX RESTROOM PLANS
Rev. Description Date
1 ADD#3 6/20/23
AIRCRAFT MAINTENANCE FACILITY 18153/FAKZ169003 AUG 01, 2021
DANNELLY FIELD, MONTGOMERY, AL TYPE B-3(100%)
Revised 20 June 2023
PROJECT INFORMATION AND SUMMARY 000102 - 1
SECTION 000102 - PROJECT INFORMATION AND SUMMARY
PART 1 GENERAL
1.01 PROJECT IDENTIFICATION
A. Project Name: Aircraft Maintenance Unit Facility, located at 187th Fighter Wing, Air National Guard (ANG) Base at Dannelly Field, Montgomery, AL.
B. Government Project Number: FAKZ169003
C. Architect's Project Number: 18153.
D. The Owner, hereinafter referred to as the Government: Alabama Air National Guard.
E. Owner's Representatives:
1. Contracting Officer: Mr. Craig Kast
2. Contracting Specialist: Mr. Stephen Shanks
3. Contracting Officer Representative: Major Adam Sanders, Base Civil Engineer
4. Alternate Contracting Officer Representative: Major Nathan Brock, Deputy Base Civil Engineer
1.02 CONTRACT DURATION
A. 450 calendar days from notice to proceed to Beneficial Occupancy, this is in addition to 30 days for the punch list to be completely accomplished. The Government intends to occupy the building upon Beneficial Occupancy. The Contractor will be responsible for coordinating punch list activities around the Government's activities if both are occurring at the same time. (Deleted by Addenum No. 2)
B. 450 calendar days from notice to proceed to Beneficial Occupancy. The listed duration shall include completion of all punch list activities identified at the project final inspection. The Government intends to occupy the building upon Beneficial Occupancy. (Added by Addendum No. 2)
1.03 PROJECT DESCRIPTION
A. Project scope includes sitework, subgrade excavation, building foundations, structural, architectural, plumbing, mechanical, electrical and relocation of existing utilities for a new two story facility with mechanical platform and associated sitework per the contract documents. The proposed project includes the following:
Revised 20 June 2023
PROJECT INFORMATION AND SUMMARY 000102 - 2
1. Vertical construction will consist of work on one facility. The Aircraft Maintenance Facility will be an approximate 18,000 square foot building housing the Base's Aircraft Maintenance Unit (AMU). Within the new Aircraft Maintenance facility, special facilities include non-secure office space, tool storage space, secure storage room, conference and ready rooms, locker rooms, and a break room.
2. Special attention will need to be paid to layout, erosion control, and laydown operations due to the limitations of the site and existing utilities on site. Scope of work will include the rerouting of underground utilities.
3. The new building’s structural system includes slab on grade with engineered fill soil stabilization, structural steel framing as well as load bearing masonry, composite floor slab, open web joists, and accoustical roof decking. The roof will have both low slope components with tapered insulation and thermoplastic roofing, sloped standing seam roofing. The exterior walls include veneer brick, cast stone, aluminm curtainwall, and metal wall panels.
4. Major building systems include a 4 pipe chilled and hot water system with associated boiler, chillers, and pumps.
5. Specialty equipment included in the project includes metal lockers and tool storage solutions.
6. Underground utility work will include all building necessary power, sanitary, storm, gas, water, and telecommunications infrastructure. Coordination will be required with existing utilities to maintain operation through and around the site and will include power, sanitary, storm, gas, water, and data.
7. Site work will comprise of on-site parking, pedestrian paving, landscape and retaining walls, sodding, and landscape planting
B. Antiterrorism and Building Standoff Requirements:
1. The project site and building structural, architectural, electrical and mechanical systems have been designed to meet the prescribed levels of protection against terrorist attacks in accordance with the Department of Defense (DoD) Unified Facilities Criteria (UFC) 4-010-01 DoD Minimum Antiterrorism Standards for Buildings.
C. Special Access Program Facilities (SAPF)
1. The project contains SAPF areas. These facilities are designed and shall be constructed in accordance with ICD 705-1 and IC Tech Spec for ICD/ICS 705 Technical Specifications for Construction and Management of Sensitive
Revised 20 June 2023
PROJECT INFORMATION AND SUMMARY 000102 - 3
Compartmented Information Facilities. These manuals establish physical and automated security design and construction standards for governing the construction, protection, and security of SAPF and SAPCA. Refer to the drawings and specifications for related scope of work including, but not limited to, physical construction of perimeter walls, floors, and ceilings ; Intrusion Detection System (IDS) and Closed Circuit Television (CCTV) System. The Contractor shall fully familiarize himself with relevant requirements and provide the necessary information and instruction to all subcontractors, installers, and suppliers.
D. Intrusion Detection System (IDS) and CCTV:
1. The Secure Storage room is designed to be equipped with an ICD 705 compliant Instruction Detection System and CCTV.
2. The IDS system must be fully compatible with the existing USAF approved Advantor IDS Annunciator located in the 187th SFS BDOC.
3. As part of the base bid, the contractor is responsible for engaging Advantor Systems Cooperation (which is a sole source security system) for the procurement (purchase) and installation of the IDS and CCTV systems. Refer to limited source justification included in the solicitation documents furnished by the Government.
4. The base bid shall include all plant, labor, and materials to provide all collateral support as required by Advantor (in addition to collateral support indicated in the contract documents) for installation of a fully operational IDS and CCTV systems as defined by Advantor System Corporation.
5. The required scope of work is as outlined in the drawings. Advantor systems assisted in the design of the security systems and have furnished a "quote" as part of the design process. The "quote" is included in the project specifications for reference and identification of the required devices/materials. The Contractor shall contact ADVANTOR and receive an updated "quote" as part of the bid process.
All costs to install a complete and operation IDS and CCTV systems shall be included in the Contractor's bid.
E. Sustainability Design and Energy Conservation:
1. The project design incorporates Sustainability Concepts to achieve optimum resource efficiency, constructibility, sustainability, and energy conservation.
2. This project hass been registered with the USGBCI for guiding principals assesment recognition process.
3. The Contractor is responsible for ensuring all specified sustainable and energy conservation goals are achieved and fully implemented. Refer to section 01 3329
Revised 20 June 2023
PROJECT INFORMATION AND SUMMARY 000102 - 4
for sustainability reporting requirements. Refer to technical specifications for specific product requirements.
F. Building Systems Commissioning:
1. Refer to specification section 01 9113 - General Commissioning Requirements, and other individual specifications sections for Contractor's responsibilities related to Building Systems Commissioning.
G. Government Furnished Furniture, furnishings and Equipment (FF&E):
1. Contractor's base bid shall include rough-ins for plumbing, mechanical, and electrical; including installation and final connection of all items indicated on the drawings as Government Furnished Contractor Installed (GFCI). (Deleted by Addendum No. 1)
H. Contractor's Qualified Fire Protection Engineers (QFPE) Services: (ADDED BY
ADDENDUM NO. 3)
1. The Contractor shall employ a Qualified Fire Protection Engineer (QFPE) meeting the requirements of UFC 3-600-01.
2. The QFPE shall review, sign, and certify all fire protection and life safety systems including; but, not limited to fire alarm, mass notification, and sprinkler systems included within the proposed project.
3. All shop drawing / calculations / material submittals for applicable life safety systems must be reviewed and stamped by the Contractor’ QFPE in accordance with section 9-6.3 of UFC 3-600-01.
4. Waterflow testing shall be performed under the direction of the Contractor’s QFPE in accordance with section 9-6.4 of UFC 3-600-01. Waterflow testing shall be performed by the Contractor in order to develop required hydraulic calculations. Use of waterflow testing performed by the Architect during design cannot be utilized by the Contractor for preparation of project submittals.
5. During Construction the Contractor’s QFPE must visit the site in intervals/quantities required to certify that the system has been installed in accordance with the project requirements. At a minimum, the QFPE shall attend/witness the above ceiling inspection and attend/witness final acceptance testing for all fire protection and life safety systems. Additional site inspections are at the discretion of the Contractor’s QFPE. The Contractor’s QFPE shall certify, in writing, that the system has been installed in accordance with project requirements. The Contractor’s QFPE certification shall be in writing, on company letterhead, and include the QFPE’s registration stamp.
Revised 20 June 2023
PROJECT INFORMATION AND SUMMARY 000102 - 5
1.04 SOIL AND GROUND WATER CONTAMINATION: (ADDED BY ADDENDUM NO. 3)
A. A soil remediation project has been recently completed to remediate contaminated soil and ground water containing high concentrations of TCE. The project is complete and recent soil and ground water test results indicate that all known contaminants have been removed to below regulated levels.
B. The remediation process utlized electric resistance heating to heat the in-situ soil in order to volatilize and extract the contaminates. Refer to sheet C1.1, as modified by Addendum No. 2, for description and quanity of electrodes present on site and the Contractor's responsbility for removal of electrodes as required to complete the work of this project. The amended drawing sheet C1.1 also indicates a layer of gravel that is present on the site and not depicted on the original site demolition plan. The Contractor will be responsible for relocating the existing gravel as noted on the amended drawing sheet C1.1.
C. The remediation process heated the in-situ soils to approximately 100 degrees, Celsius. At the time of the bid the soil temperature are estimated to be approximately 90 degrees, Celsius. The soil temperature is expected to continue to decrease between bid, award, and commencement of construction; however, the temperature of the soil at the time construction commences is not known. The soil temperature is likely to remain elevated during the course of the project. The Contractor shall include in their bid all cost that may be required to properly protect both personnel and equipment required to complete the earthwork activities outlined within the project scope.
1.05 PERMITS, FEES AND NOTICES
A. Unless otherwise provided in the Contract Documents, the Contractor shall secure and pay for the building permit and other permits and governmental fees, licenses, and inspections necessary for proper execution and completion of the Work which are customarily secured after award of the Construction Contract and which are in effect on the date of receipt of bids.
1. City of Montgomery Building Permit will not be required.
B. The Contractor shall comply with and give notices required by all laws, ordinances, rules, regulations, and lawful orders of public authorities applicable to performance of the Work.
1.06 USE OF SITE AND MISC. REQUIREMENTS
A. The space available to the contractor for the performance of the work, either exclusively or in conjunction with others performing other construction as part of the
Revised 20 June 2023
PROJECT INFORMATION AND SUMMARY 000102 - 6
project, is as per the Government's approval.
1. Other areas are off limits to all construction personnel.
B. Access to site will be limited; obtain Government's approval of proposed routes of access.
C. Keep existing sidewalks, roads, parking lots and drives on site clear and available at all times. Promptly remove mud, dirt, debris, etc. from sidewalks, streets, and public right-of-way during construction as it occurs.
D. Storage areas on site are very minimal and will be limited to materials that are to be immediately used in the progress of the work. If additional storage is required, then Contractor shall secure and be responsible to pay for such off site storage in a fully bonded and insured facility acceptable to the Government, with all items clearly identified as being assigned to this project.
1. Contractor will be limited to the areas included within the project limits shown on the civil drawings.
E. Provide secure temporary barricades, fencing, etc. as required to separate the public from construction operations. Compliant safety and/or warning signage is to be provided as well in conjunction with fencing and barricades.
1. Site safety and security is the General Contractor's responsibility. Fencing shall be provided as deemed necessary to protect the site from theft and damage and to prevent access to the site by the public. A fence along the project limits is anticipated at a minimum. However, exact location/extents of fencing is at the discretion of the Contractor. Removal of project boundary fencing along the Northern boundary of the project limits and connection of project fencing with fencing of the adjacent base supply project would be acceptable if agreed upon by both Contractors.
F. Construction operations are not to affect any of the ongoing operations throughout the site and/or adjacent sites. Construction equipment is not to be attached to, or swing over existing buildings to remain, public areas, occupied buildings or parking lots, right-of-ways, etc.
G. Comply with the Government's security requirements - refer to specification section 01 3553.
H. The contractor shall provide all testing, inspections, and similar services; these services also include those specified to be performed by an independent agency.
Revised 20 June 2023
PROJECT INFORMATION AND SUMMARY 000102 - 7
1. Where indicated on the drawings work outside of the site extents may be required to connect to existing/new utilities.
1.07 UTILITY OUTAGES AND SHUTDOWN
A. All electrical and communication shut downs shall be performed on a non-working day for the Government(Saturday, Sunday, Monday, or Holidays) unless specifically approved by the base Contracting Officer Representative.
B. Limit shutdown of utility services to 8 hours at a time, arranged at least 72 hours in advance with the Government.
C. Prevent accidental disruption of utility services to other facilities.
1.08 PHASING OF WORK
A. The work of this project shall be completed in one phase. However, the Contractor shall coordinate the work as required to ensure all existing roadways and facilities adjacent to the project site remain open and accessible for use by the Government.
1.09 WORK SEQUENCE
A. Coordinate construction schedule and operations with Contracting Officer Representative.
B. Rerouting of existing utilities shown on the drawings must be properly sequenced with work associated with undercutting of the building pad so that shutdown of utility services is limited. Rerouting of existing utilities shall take place prior to the undercutting of the building pad. Rerouting of waterlines shall take place prior to the rerouting of the sanitary sewer. Storm water may be partially rerouted prior to starting the work associated with undercutting the building pad and commence again after undercutting is complete. Order and schedule of sequencing of this work shall be determined by the Contractor and coordinated with the Government.
1. Do not remove from service existing utilities serving adjacent facilities until new service can be established. Provide temporary service if necessary to allow construction to proceed prior to establishing new permanent service(s).
C. The contractor shall be responsible for all means, methods, sequencing of work, demolition, and reparations to the property and facilities as required to accomplish the work. This shall include but is not imited to the installation of all equiment furnishings, and materials.
1.10 PROJECT CONSULTANTS
A. The Architect, hereinafter referred to as Architect: Seay Seay & Litchfield P.C..
Revised 20 June 2023
PROJECT INFORMATION AND SUMMARY 000102 - 8
1. Address: 1115 South Court Street.
2. City, State, Zip: Montgomery AL 36104.
3. Phone/Fax: 334-263-5162 334-263-5170.
4. Project Manager: Jake Johnson, AIA
5. Prinicipals-in-Charge: Wes R. Osmer, AIA, LEED AP
B. Architect's Consultants:
1. Civil Engineering:
a. Professional Engineering Consultants
b. Address: 822 South McDonough St..
c. City, State, Zip: Montgomery, AL, 36104.
d. Phone/Fax: 334-262-7307 / 334-262-7309.
e. Contact: Steve Green - Pat Moseley
2. Structural Engineering:
a. Blackburn Daniels O'Barr, Inc.
b. Address: 8805 County Rd. 40E
c. City, State, Zip: Lowndesboro, AL, 36752.
d. Phone/Fax: 334-265-0206 / 334-265-0207.
e. Contact: Mark O'Barr
3. Plumbing, Mechanical & Fire Suppression Engineering:
a. HHB Engineers, P.C.
b. Address: 104 Josie Run
c. City, State, Zip: Prattville, AL, 36066
d. Phone: 334-358-2707
e. Contact: Tom Hattemer, P.E.
4. Electrical Engineering:
Revised 20 June 2023
PROJECT INFORMATION AND SUMMARY 000102 - 9
a. Gunn & Associates, P.C.
b. Address: 3102 Hwy 14
c. City, State, Zip: Millbrook, AL 36054
d. Phone: 334-285-1273
e. Contact: Barry Gravlee, P.E.
PART 2 PRODUCTS (NOT USED)
PART 3 EXECUTION (NOT USED)
END OF SECTION
Revised 20 June 2023
METAL ROOF PANELS 074113 - 1
SECTION 074113 - METAL ROOF PANELS
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Mechanically-seamed, standing seam metal roof panels, with related metal trim and accessories.
B. Materials included in this section shall meet the requirements for High Performance Sustainable Buildings for New Construction points for the following Sections:
1. 2-6.1.1 - Recycled Content
2. The contractor is expected to understand the HPSB requirements for these sections and include all applicable overhead in their base bid for the necessary documentation to achieve the above listed credits.
1.02 RELATED REQUIREMENTS
A. Section 01 3325 - Project Sustainability Summary
B. Section 01 3329 - Sustainable Design Reporting
C. Section 01 6000 - Product Requirements
D. D. Section 01 7419 - Construction Waste Management and Disposal
E. Division 05 Section "Structural Steel Framing" for structural steel framing supporting metal panels.
F. Division 05 Section "Steel Decking" for continuous metal decking supporting metal panels.
G. Division 07 Section "Metal Wall Panels" for factory-formed metal wall [and soffit] panels.
H. Division 07 Section "Sheet Metal Flashing and Trim" for formed sheet metal copings, flashings, reglets, and roof drainage items in addition to items specified in this Section.
I. Division 07 Section "Roof Specialties" for manufactured copings, reglets, and roof drainage items in addition to items specified in this Section.
J. Division 07 Section "Joint Sealants" for field-applied Joint Sealants
1.03 REFERENCES
A. American Architectural Manufacturer's Association (AAMA): www.aamanet.org
Revised 20 June 2023
METAL ROOF PANELS 074113 - 2
1. AAMA 621 - Voluntary Specifications for High Performance Organic Coatings on Coil Coated Architectural Hot Dipped Galvanized (HDG) & Zinc-Aluminum Coated Steel Substrates.
2. AAMA 809.2 - Voluntary Specification Non-Drying Sealants.
B. American Society of Civil Engineers (ASCE): www.asce.org/codes-standards
1. ASCE 7 - Minimum Design Loads for Buildings and Other Structures.
C. ASTM International (ASTM): www.astm.org
1. ASTM A 653 - Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc- Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process.
2. ASTM A 755 - Specification for Steel Sheet, Metallic Coated by the Hot-Dip Process and Prepainted by the Coil-Coating Process for Exterior Exposed Building Products.
3. ASTM A 792/A 792M - Standard Specification for Steel Sheet, 55 % Aluminum- Zinc Alloy-Coated by the Hot-Dip Process.
4. ASTM A 980 - Standard Specification for Steel, Sheet, Carbon, Ultra High Strength Cold Rolled.
5. ASTM C 645 - Specification for Nonstructural Steel Framing Members.
6. ASTM D 226 - Standard Specification for Asphalt-Saturated Organic Felt Used in Roofing and Waterproofing.
7. ASTM D 1003 - Standard Test Method for Haze and Luminous Transmittance of Transparent Plastics.
8. ASTM D 2244 - Test Method for Calculation of Color Differences from Instrumentally Measured Color Coordinates.
9. ASTM D 4214 - Test Methods for Evaluating Degree of Chalking of Exterior Paint Films.
10. ASTM E 1592 - Standard Test Method for Structural Performance of Sheet Metal Roof and Siding Systems by Uniform Static Air Pressure Difference.
11. ASTM E 1646 - Standard Test Method for Water Penetration of Exterior Metal Roof Panel Systems by Uniform Static Air Pressure Difference.
12. ASTM E 1680 - Standard Test Method for Rate of Air Leakage Through Exterior Metal Roof Panel Systems.
Revised 20 June 2023
METAL ROOF PANELS 074113 - 3
13. ASTM E 1980 - Practice for Calculating Solar Reflectance Index of Horizontal and Low-Sloped Opaque Surfaces.
D. Cool Roof Rating Council (CRRC): www.coolroofs.org/productratingprogram.html
1. CRRC-1-2008 - CRRC Product Rating Program.
E. International Accreditation Service (IAS):
1. IAS AC 472 - Accreditation Criteria for Inspection Programs for Manufacturers of Metal Building Systems, Part B.
F. Underwriters Laboratories, Inc. (UL): www.ul.com
1. UL 580 - Tests for Uplift Resistance of Roof Assemblies
G. US Environmental Protection Agency: www.energystar.gov/index.cfm
1. Energy Star Reflective Roof Products.
1.04 ADMINISTRATIVE REQUIREMENTS
A. Preinstallation Meeting: Prior to erection of framing, conduct preinstallation meeting at site attended by Contracting Officer, Contracting Officer Representative(s), Architect, manufacturer's technical representative, inspection agency and related trade contractors.
1. Coordinate building framing in relation to metal panel system.
2. Coordinate openings and penetrations of metal panel system.
3. Coordinate work of Division 07 Sections "Roof Specialties" and openings and penetrations and manufacturer's accessories with installation of metal panels.
4. Coordinate roofing slopes as required by manufacturer.
1.05 QUALITY ASSURANCE
A. Manufacturer/Source: Provide metal roof panel assembly and accessories from a single manufacturer providing fixed-base roll forming, and accredited under IAS AC 472 Part B.
B. Manufacturer Qualifications: Approved manufacturer listed in this Section with minimum five years experience in manufacture of similar products in successful use in similar applications.
1. Approval of Comparable Products: Submit the following in accordance with project substitution requirements, within time allowed for substitution review:
Revised 20 June 2023
METAL ROOF PANELS 074113 - 4
a. Product data, including certified independent test data indicating compliance with requirements.
b. Samples of each component and each color
c. Sample submittal from similar project.
d. Project references: Minimum of five installations not less than five years old, with Owner and Architect contact information.
e. Sample warranty.
f. IAS AC 472 certificate.
C. Installer Qualifications: Experienced Installer certified by metal panel manufacturer with minimum of five years experience with successfully completed projects of a similar nature and scope.
1. Installer's Field Supervisor: Experienced mechanic certified by metal panel manufacturer supervising work on site whenever work is underway.
1.06 ACTION SUBMITTALS
A. Product Data: Manufacturer’s data sheets for specified products.
B. Shop Drawings: Show layouts of metal panels. Include details of each condition of installation, panel profiles, and attachment to building. Provide details at a minimum scale 1-1/2-inch per foot of edge conditions, joints, fastener and sealant placement, flashings, openings, penetrations, roof accessories, lightning arresting equipment, and special details. Make distinctions between factory and field assembled work.
1. Indicate points of supporting structure that must coordinate with metal panel system installation.
2. Include data indicating compliance with performance requirements.
3. Include structural data indicating compliance with requirements of authorities having jurisdiction.
C. Samples for Initial Selection: For each exposed product specified including sealants.
Provide representative color charts of manufacturer's full…