This addendum modifies an invitation for bids for construction services to build an aircraft maintenance unit facility. Key changes include replacing the vapor barrier system below slabs with an integrally bonded underslab vapor protection membrane and sheet waterproofing; adding bid options for alternate foundation designs including drilled piers; revising site civil, structural, and architectural drawings; and modifying specifications for doors, security systems, and earthwork. The single award firm fixed price contract valued over $10 million is set aside 100% for small businesses and has a performance period of 450 calendar days.
View the file
Other files for this federal contract opportunity
Show all 28
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Date: 25 May 2023
To: CMSgt. William Hall
Subject: ADDENDUM NO. 2
Project: AIRCRAFT MAINTENANCE UNIT FACILITY
Job #: ANG# FAKZ169003 / SSL# 18153
From: David Donovan
The plans and Specifications for the Aircraft Maintenance Unit Facility, dated 01 August 2021 are amended as follows. (Where there are conflicts between the plans and specifications and the addendum, this addendum shall govern).
Item No. 1: Delete drawings sheets VI1.1, VI1.2, VI2.1, VI2.2, VI2.3, VI3.1 and
VI32. The under slab vapor barrier and vent system depicted on these drawings sheets is not required by either the base bid or bid options.
Item No. 2: Add the attached specification sections 07 2650 “Integrally Bonded
Underslab Vapor Protection” and 07 1300 “Sheet Waterproofing”
Item No. 3: Add the attached drawings sheet A5.10 – Vapor Protection Details – Base
Bid with a revised date of 19 May 2023.
Item No.4: Delete drawing sheet A6.4 “Enlarged Elevator Plans, Sections, &
Elevations” and replace it with the attached drawing sheet A6.4 with a revised date of 19 May 2023.
Clarification Regarding Items 1-4:
As part of the base bid:
- The Contractor shall install an integrally bonded vapor protection system including sheet membrane waterproofing as indicated in the attached drawing sheet A5.10 – Vapor Protection Details – Base Bid and in accordance with specification section 07 2650 and section 07 1300.
- The vapor mitigation system indicated on the VI drawing sheet is not required and should not be included within the Contractor’s bid.
- The Contractor shall disregard the extent of vapor barrier indicated on A5.2, A5.3, and A5.4. Install integrally bonded vapor protection as indicated on the new drawing sheet A5.10 – Vapor Protection Details.
- The Contractor shall install vapor protection systems including sheet membrane waterproofing at elevator pit as indicated on the revised drawing sheet A6.4.
AIRCRAFT MAINTENANCE UNIT FACILITY FAKZ169003
ADDENDUM NO. 2 Page 2 of 7 Seay Seay & Litchfield, P.C. 25 May 2023
Item No. 5: Refer to drawings. Add the following attached drawing sheets with a revised date of 19 May 2023:
1. C6.1A – Site Details
2. A5.10A – Vapor Protection Details – Bid Option No. 6
3. A5.11A – Vapor Protection Details – Bid Option No. 6
4. S1.1A – First Floor and Foundation Plan - Alternate
5. S1.2A – Drilled Pier & Grade Beam Layout Plan - Alternate
6. S2.7A – Sections and Details - Alternate
7. S2.8A – Sections and Details - Alternate
Item No. 6: Refer to specifications. Delete specification section 01 2300 “Bid
Options” and replace it with the attached specification section 01 2300 with a revised date of 19 May 2023.
Item No. 7: Delete specification section 31 2210 “Earthwork” and replace it with the attached specification section 31 2210 with a revised date of 19 May 2023.
Additions to the specification are noted in bold/italicized text and deletions are noted with strikethrough text. Revisions included, but are not limited to, the following:
- Add references to #57 and #67 stone for backfill for below building slabs and foundations as a part of Bid Option No. 6.
- Omit requirements to proofroll subgrade conditions under building slabs if Bid Option No. 6 for drilled pier foundation system is awarded.
- Omit requirements to scarify and recompact subgrade conditions under building slabs if Bid Option No. 6 for drilled pier foundation system is awarded.
- Omit requirements for compaction of drainage materials if Bid Option No. 6 for drilled pier foundation system is awarded.
- Modify subgrade preparation and select fill placement requirements for base bid “engineered fill” pad foundation systems.
- Add Contractor’s option for ALDOT Section 230 Improved Roadbed or ALDOT Section 825 crushed aggregate for pavement subgrade.
- Add the attached addendum to the geotechnical recommendations dated 12 December 2022 which provides recommendations for drilled piers and structural floor slabs as a second attachment to this specification section.
Item No. 8: Refer to drawing sheet P2.1. Add the following general note to this sheet:
Note: If Bid Option No. 6 is awarded, under-slab, gravity draining sanitary sewer systems shall be installed within the porous backfill layer, above the subgrade elevations indicated on C6.1A, and shall be below structural grade beams so as not to penetrate structural grade beams. Contractor shall coordinate depths and routing of underslab sanitary sewer piping
ADDENDUM NO. 2 Page 3 of 7 Seay Seay & Litchfield, P.C. 25 May 2023 with all affected trades. It is anticipated that the high point of the underground sanitary sewer system will be located at fixture P-9 in room 107 with an approximate invert elevation of 199.99. With the required slope across the system, a discharge elevation of approximately 198.53 is expected where the below grade sanitary sewer system exits the facility footprint in room 102.
Clarification Regarding Items 5-8:
This addendum adds Bid Option No. 6: Alternate Foundation Design. The intent of this addendum is for the Contractor to price, as part of the base bid, ground supported floor slabs over integrally bonded vapor barrier (see items 1-4 of this addendum) bearing on an engineered filled pad as indicated on the original project drawings and the original project geotechnical recommendations from Carmichael Engineering dated 31 March 2021. Bid Option No. 6 should be the additional cost (cost premium after deducting the cost of the base bid engineered filled pad and ground supported floor slab assembly) for the following:
- Installation of structural floor slab systems spanning between, and supported upon, grade beams bearing on a grid of drilled piers as indicated in the revised structural sheets added by item #5 of this addendum and as described in the 12 December 2022 letter from Carmichael Engineering referenced in Item No. 7 of this addendum.
- Revised extent and depths of building undercut and foundation drainage systems indicated on C6.1A.
- Revised extent and installation details associated with integrally bonded vapor protection systems as indicated on A5.10A and A5.11A.
Item No. 9: Delete drawing sheet C1.1 “Site Demolition Plan” and replace it with the attached drawing sheet C1.1 with a revised date of 19 May 2023.
Revisions to the drawing are clouded in the revised drawing and include, but are not limited to, the following:
- Remove demolition of existing water and sanitary sewer utilities along the East side of the facility. The demolition of these utilities has been moved to a different project which is expected to start in the near future. The exact timeline for demolition of these utilities is not known at the time of this addendum. The Contractor will be required to coordinate with Government and Contractor of the adjacent project to coordinate demolition of these items in the sequence that allows both projects to progress simultaneously.
- Add note regarding the presence of copper and steel electrodes abandoned in place on the project site and Contractor’s responsibility regarding demolition of the abandoned electrodes.
- Add note regarding the presence of gravel backfill on the site and the Contractor’s responsibility regarding removal/relocation of the gravel.
ADDENDUM NO. 2 Page 4 of 7 Seay Seay & Litchfield, P.C. 25 May 2023
Item No. 10: Delete drawing sheet C2.1 “Site Layout Plan” and replace it with the attached drawing sheet C2.1 with a revised date of 19 May 2023.
Revisions to the drawing are clouded in the revised drawing and include, but are not limited to, the following:
- Revised extents of concrete paving required to connect the new AMU facility to the adjacent Building 1301. Some of the paving originally indicated within this project has been shifted to a different project.
- Revised configuration of concrete and concrete paver pedestrian walkways to coordinate with the proposed renovation/addition to the adjacent Building 1301.
- Addition of a handicap access island, handicap parking, and associated signage at the AMU facility entrance.
Item No. 11: Delete drawing sheet C3.1 “Site Grading and Drainage” and replace it with the attached drawing sheet C3.1 with a revised date of 19 May 2023.
Revisions to the drawing are clouded in the revised drawing and include, but are not limited to, the following:
- Removal of grate inlets G-20 and G-21 from the project scope. The installation of these structures has been moved to a different project which is expected to start in the near future. The exact timeline for installation of these structures is not known at the time of this addendum. The Contractor will be required to coordinate with Government and Contractor of the adjacent project to coordinate installation of these structures in the sequence that allows both projects to progress simultaneously.
- Revised spot elevations/grading associated with the reconfiguration of concrete and concrete paver pedestrian walkways to coordinate with the proposed renovation/addition to the adjacent Building 1301 and addition of the handicap parking island.
- Modify undercut extents to include mechanical screen wall.
Item No. 12: Delete drawing sheet C4.1 “Site Utility Plan” and replace it with the attached drawing sheet C4.1 with a revised date of 19 May 2023.
Revisions to the drawing are clouded in the revised drawing and include, but are not limited to, the following:
- Modification to site water, sewer, and storm drainage utilities to coordinate with work that was moved to a different construction project. The installation of these structures has been moved to a different project which is expected to start in the near future. Exact timeline for installation of these structures is not known at the time of this addendum; however, the utility work is indicated as existing conditions within the addendum drawings since the work is not required to be performed under this contract. The Contractor will be required to coordinate with Government and Contractor of the
ADDENDUM NO. 2 Page 5 of 7 Seay Seay & Litchfield, P.C. 25 May 2023 adjacent project to coordinate installation of these items in the sequence that allows both projects to progress simultaneously.
- Modify undercut and foundation drain extents to include mechanical screen wall.
Item No. 13: Delete drawing sheet C6.1 “Site Details” and replace it with the attached drawing sheet C6.1 with a revised date of 19 May 2023. Revisions to the drawing are clouded in the revised drawing and include, but are not limited to, the following:
- Modify extents of undercut to incorporate mechanical screen wall.
- Revised invert elevations of foundation drainage system.
Item No. 14: Delete drawing sheet C7.1 “Site Details” and replace it with the attached drawing sheet C7.1 with a revised date of 19 May 2023. Revisions to the drawing are clouded in the revised drawing and include, but are not limited to, the following:
- Add the option for use of ALDOT Section 825 crushed aggregate base in addition to ALDOT Section 230 Improved roadbed for pavement base.
- Increased concrete thickness below paver systems.
- Change paver base from improved roadbed to ALDOT Section 825 crushed aggregate.
- Delete reference to lime stabilization of paving subgrades.
Item No. 15: Delete drawing sheet C8.1 “Site Details” and replace it with the attached drawing sheet C8.1 with a revised date of 19 May 2023. Revisions to the drawing are clouded in the revised drawing and include, but are not limited to, the following:
- Add details for handicap parking island and handicap parking signage.
- Modify storm drainage structure schedule to reflect inlets G20 and
G21 being installed under a separate contract/project.
Item No. 16: Delete drawing sheet C9.1 “Site Details” and replace it with the attached drawing sheet C9.1 with a revised date of 19 May 2023. Revisions to the drawing are clouded in the revised drawing and include, but are not limited to, the following:
- Modify trench bedding material requirements.
ADDENDUM NO. 2 Page 6 of 7 Seay Seay & Litchfield, P.C. 25 May 2023
Item No. 17: Delete drawing sheet C10.1 “Site Details” and replace it with the attached drawing sheet C10.1 with a revised date of 19 May 2023. Revisions to the drawing are clouded in the revised drawing and include, but are not limited to, the following:
- Remove sanitary sewer piping profile as the pipe indicated in this profile section was removed from the project scope and will be installed by a separate project.
Item No. 18: Delete drawing sheet A2.1 “First Floor Plan” and replace it with the attached drawing sheet A2.1 with a revised date of 19 May 2023.
Revisions to the drawing are clouded in the revised drawing and include, but are not limited to, the following:
- Change door 103 to a cased opening.
- Add cased opening 103B
Item No. 19: Delete drawing sheet A2.3 “Wall Type / Dimension Floor Plan” and replace it with the attached drawing sheet A2.3 with a revised date of 19 May 2023. Revisions to the drawing are clouded in the revised drawing and include, but are not limited to, the following:
- Add requirement for STC50 sound rating at walls enclosing room
110.
- Correct drawing to accurately depict location of full height walls in rooms 109D and 109E.
Item No. 20: Delete drawing sheet A3.2 “Door Schedule” and replace it with the attached drawing sheet A3.2 with a revised date of 19 May 2023.
Revisions to the drawing are clouded in the revised drawing and include, but are not limited to, the following:
- Change door 103 to a cased opening.
- Add cased opening 103A
- Change door 110 to STC 50 rating.
Item No. 21: Add the attached drawing sheet A3.8 “STC50 Door Requirements” with a revised date of 19 May 2023.
Item No. 22: Add the attached specification section 08 3481 “Security Rated and Sound
Control Door Assemblies.”
ADDENDUM NO. 2 Page 7 of 7 Seay Seay & Litchfield, P.C. 25 May 2023
Item No. 23: Refer to specification section 08 7100. Delete hardware set 20.0 and replace it with the below revised hardware set.
Set 20.0 Doors: 110 Description: Secure Storage, STC Rated
1 set Cam Lift Hinges By STC Door Manufacturer 1 Mortise Lock (Classroom) JNR 8808FL A620 626 YA 1 Security Combo Lock LKM7000 / X10 w/ key override 1 Cylinder SFIC as required 626 BE 1 Kickplate K1050 10” x 2” LDW 4BE CSK US32D RO 1 Threshold 271A PE 1 STC Gasketing By STC Door Manufacturer 1 Door Stop 409/446 US32D RO 1 Balanced Magnetic Switch By Security Contractor
Item No. 24: Delete specification section 28 0850 and replace it with the attached specification section 28 0850 with a revised date of 19 May 2023.
Revisions to the specification include, but are not limited to, the following:
- Revise engineer qualification requirements.
- Clarify battery sizing requirements.
Item No. 25: Delete specification section 00 0102 “Project Information and Summary” and replace it with the attached specification section 00 0102 with a revised date of 19 May 2023. Additions to the specification are noted in bold/italicized text and deletions are noted with strikethrough text.
Revisions included, but are not limited to, the following:
- Revision to contract duration language.
End of Addendum #2
AIRCRAFT MAINTENANCE FACILITY 18153/FAKZ169003 AUG 01, 2021
DANNELLY FIELD, MONTGOMERY, AL TYPE B-3(100%)
Revised 19 May 2023
INTEGRALLY BONDED UNDERSLAB VAPOR
PROTECTION
072650 - 1
SECTION 072650 - INTEGRALLY BONDED UNDERSLAB VAPOR PROTECTION
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Integrally bonded underslab vapor protection for installation on grade and below grade applications.
B. Contractor to schedule and conduct a Pre-Waterproofing Conference that addresses all concerns of waterproofing, including but not limited to: Location, application, inspections, protection of installed materials, eliminating the trapping of construction moisture, special Government needs, etc. Attendees to be Contracting Officer's Representative, Architect, Contracting Officer, Contractor, Manufacturer's representative, any other trades as applicable, etc.
1.02 RELATED SECTIONS
A. Section 07 1300 - Sheetwaterproofing
1.03 SUMMARY
A. The Work of this Section includes, but is not limited to, underslab vapor retarder/barrier membrane that forms an integral bond to poured concrete for use below slabs on grade and below grade. Shown on architectural drawings as vapor barrier.
B. Related sections include, but are not limited to, the following:
1. Section 03 3000 – Cast-In-Place Concrete
1.04 SUBMITTALS
A. Submit manufacturer's product data, installation instructions and membrane samples for approval.
1.05 REFERENCE STANDARDS
A. The following standards and publications are applicable to the extent referenced in the text.
B. American Society for Testing and Materials (ASTM):
1. D 412 – Standard Test Methods for Rubber Properties in Tension
2. D 903 - Standard Test Method for Peel or Stripping Strength of Adhesive Bonds
3. D 3767 – Standard Practice for Rubber – Measurements of Divisions
Revised 19 May 2023
INTEGRALLY BONDED UNDERSLAB VAPOR
PROTECTION
072650 - 2
4. E 96 - Standard Test Methods for Water Vapor Transmission of Materials
5. E 154 - Standard Test Methods for Water Vapor Retarders Used in Contact with Earth Under Concrete Slabs, on Walls, or as Ground Cover
6. E 1643 – Standard Practice for Installation of Water Vapor Retarders Used in Contact with Earth or Granular Fill Under Concrete Slabs
C. American Concrete Institute (ACI):
1. ACO 302.1R-96 Addendum Vapor Retarder Location: For slabs locate retarder in direct contact with the slab (not beneath a layer of granular fill).
1.06 QUALITY ASSURANCE
A. Materials: For each type of material required for the work of this section, provide primary materials which are the products of one manufacturer.
B. Schedule Coordination: Schedule work such that members will not be left exposed to weather for longer than that recommended by the manufacturer.
1.07 DELIVERY, STORAGE AND HANDLING
A. Deliver materials in labeled packages. Store and handle in strict compliance with manufacturer's instructions. Protect from damage from weather, excessive temperature and construction operations. Remove and dispose of damaged material in accordance with applicable regulations.
PART 2 PRODUCTS
2.01 MATERIALS
A. Underslab on grade Integrally Bonded Vapor Protection: 0.5mm (0.021 in) nominal thickness composite sheet membrane comprising 0.4mm (0.016 in) of high density polyethylene film, and layers of specially formulated synthetic adhesive layers. The membrane shall form an integral and permanent bond to poured concrete to prevent vapor migration at the interface of the membrane and structural concrete. Provide membrane with the following physical properties:
Property Typical Value Test Method Test Method 0.5mm (0.021 in) 0.5mm (0.021 in) Water Vapor Permeance 0.03 perms ASTM E96 Method B Tensile Strength 38 lb/in ASTM E154 Elongation 300% ASTM D412 Puncture Resistance 41 lb ASTM D4833
Revised 19 May 2023
INTEGRALLY BONDED UNDERSLAB VAPOR
PROTECTION
072650 - 3
Peel Adhesion to Concrete >4 lb/in ASTM D903
B. Underslab Below Grade - Intergrally bonded vapor protection: Sheets comprising of a HDPE film and weather resistant protective coating with the following physical properties:
Property Typical Value Test Method Test Method 1.2 mm (0.046 in) ASTM D 3767 Water Vapor Permeance <0.01 perms ASTM E96 Method B Tensile Strength 4,000 psi ASTM D412 Elongation 400% ASTM D412 Puncture Resistance 200 lb ASTM E154 Peel Adhesion to Concrete
5 lb/in ASTM D903
Later Water Migration Resistance
Pass at 231ft of hydrostatic head
ASTM D5385
Low Temperature Flexibility
Unaffected at -20 degress F
ASTM D1970
Resistance to Hydrostatic Head
231 ft (71m) ASTM D5385
Crack Cycling at -9.4 degress F, 100 Cycles
Unaffected, Pass ASTM C836
Lap Peel Adhesion 8 lbs/in ASTM D1876
VOC Permeance Not Detectable Membrane, Seam
ASTM F739
Methan Permeance <40ml/day.m2.atm ASTM D1434 Radon Diffusion Coefficient, m2/s
3.7 x 10-12 Membrane, Seam
Method C of
ISO/TS11665-1
C. Accessories
1. Provide all accessories required by manufacturer for complete installation and warranties.
PART 3 EXECUTION
3.01 EXECUTION
A. The installer shall examine conditions of substrates and other conditions under which this work is to be performed and notify the Contractor, in writing, of circumstances detrimental to the proper completion of the work. Do not proceed with work until unsatisfactory conditions are corrected.
B. Comply with all manufactures instructions for specific products.
Revised 19 May 2023
INTEGRALLY BONDED UNDERSLAB VAPOR
PROTECTION
072650 - 4
3.02 INSTALLATION
A. Earth and stone substrates shall be well compacted to produce an even, solid substrate.
Remove loose aggregate or sharp protrusions. Concrete substrates shall be smooth or broom finished and monolithic. Remove standing water prior to membrane applications.
B. Installation shall be in accordance with manufacturer's instructions and ASTM E1643-98, including but not limited to, the following:
1. Apply membrane with the HDPE film facing the prepared substrate. Remove the release liner during application.
2. Apply succeeding sheets by overlapping the previous sheet 50 mm (2 in) along the marked lap line. End Laps should be staggered to avoid a buildup of layers.
3. Taped Lap Method – Provide manufacturer's seam tape to secure and seal the overlaps. Overband the lap with the 100mm (4 in) wide seam tape using the lap line for alignment. Remove Plastic release liner to ensure bond to concrete.
4. Mix and apply manufacturer's liquid detailing compound to seal around penetrations such as drainage pipes, etc.
3.03 CONCRETE PLACEMENT
A. Place concrete within 30 days. Inspect membrane and repair any damage as recommended by the manufacturer. Ensure all liner is removed from membrane and tape before concrete placement.
3.04 WARRANTY
A. A. The Waterproofing Contractor and General Contractor shall provide a five (5) year, non-prorated, no dollar limit warranty subject to the terms and conditions as rendered in the Project Waterproofing Warranty included at the end of this section.
Revised 19 May 2023
INTEGRALLY BONDED UNDERSLAB VAPOR
PROTECTION
072650 - 5
PROJECT WATERPROOFING WARRANTY
NAME OF PROJECT: ______________________________________________
LOCATION: ______________________________________________
OWNER: ______________________________________________
WATERPROOFING
CONTRACTOR: ______________________________________________
ADDRESS: ______________________________________________
DATE OF ACCEPTANCE:
DATE OF EXPIRATION:
B. The Waterproofing Contractor and General Contractor do hereby certify that the underground waterproofing work included in this contract was installed in strict accordance with all requirements of the plans and specifications and in accordance with approved waterproofing manufacturer's recommendations.
C. The Waterproofing Contractor and General Contractor do hereby guarantee the waterproofing and associated work including but not limited to all underground vertical and horizontal waterproofing to be water tight and free from all leaks, due to faulty or defective materials and workmanship for a period of five (5) years, starting on the date of Beneficial Occupancy of the project.
D. Subject to the terms and conditions listed below, the Waterproofing Contractor and General Contractor also guarantee that during the Guarantee Period he will, at his own cost and expense, make or cause to be made such repairs to, or replacements of said work, in accordance with the waterproofing manufacturers recommendations as are necessary to correct faulty and defective work and/or materials which may develop in the work including. Anticipated life of the waterproofing systems and the best standards applicable to the particular waterproofing type in value and in accordance with construction documents as are necessary to maintain said work in watertight conditions, and further, to respond on or within seven (7) calendar days upon proper notification of leaks or defects by the Government.
1. During the Guarantee Period, if the Government allows alteration of the work by anyone other the Waterproofing Contractor or General Contractor, including cutting, patching and maintenance in connection with penetrations, and positioning of anything effecting the below grade waterproofing, this Guarantee shall become
Revised 19 May 2023
INTEGRALLY BONDED UNDERSLAB VAPOR
PROTECTION
072650 - 6 null and void upon the date of said alterations
2. Future building additions will not void this Guarantee, except for that portion of the future addition that might affect the work under this contract at the point of connection of the waterproofed areas, and any damage caused by such addition.
3. The Government shall promptly notify the Waterproofing Contractor or General Contractor of observed, known or suspected leaks, defects or deterioration, and shall afford reasonable opportunity for the Waterproofing Contractor or General Contractor to inspect the work, and to examine the evidence of such leaks, defects or deterioration.
IN WITNESS THEREOF, this instrument has been duly executed
Waterproofing Contractor's Authorized Signature
General Contractor's Authorized Signature
Typed Name and Title Typed Name and Title
Notary Public
END OF SECTION
Revised 19 May 2023
SHEET WATERPROOFING 071300 - 1
SECTION 071300 - SHEET WATERPROOFING
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Sheet membrane waterproofing system
B. Below-grade waterproofing accessories.
1.02 RELATED REQUIREMENTS
A. Section 03 3000 - Cast-in-Place Concrete : Concrete substrate.
B. Section 01 3325 - Project Sustainability Summary.
C. Section 01 3329 - Sustainable Design Reporting
D. Section 01 6116 - Volatile Organic Compound (VOC) Content
E. Section 04 2000: Masonry joints prepared to receive flashings.
F. Section 07 6500 Wall Flashings
G. Section 221006 - Plumbing Piping Specialties: Roof drain and plumbing vent flashing flanges.
1.03 REFERENCE STANDARDS
1.04 SUBMITTALS
A. See Section 01 3001 - Submittals for submittal procedures.
B. Product Data: Provide data for membrane.
C. Certificate: Certify that products meet or exceed specified requirements.
D. Manufacturer's Installation Instructions: Indicate special procedures.
E. Warranty: Submit manufacturer warranty and ensure forms have been completed in the Owner's name and registered with manufacturer.
1.05 QUALITY ASSURANCE
A. Membrane Manufacturer Qualifications: Company specializing in manufacturing products specified in this section, with not less than three years of documented experience.
Revised 19 May 2023
SHEET WATERPROOFING 071300 - 2
B. Installer Qualifications: Company specializing in performing work of the type specified and with at least three years of documented experience.
C. Commencing of work shall indicate acceptance of substrate by the installer.
1.06 MOCK-UP
A. Construct mock-up consisting of 100 sq ft (10 sq m) of horizontal waterproofed panel;
to represent finished work including internal and external corners.
B. Locate where directed.
C. Mock-up may remain as part of this Work.
1.07 FIELD CONDITIONS
A. Maintain ambient temperatures above 40 degrees F (5 degrees C) for 24 hours before and during application and until liquid or mastic accessories have cured.
1.08 WARRANTY
A. Provide five year manufacturer warranty for waterproofing failing to resist penetration of water , except where such failures are the result of structural failures of building.
Hairline cracking of concrete due to temperature change or shrinkage is not considered a structural failure .
PART 2 PRODUCTS
2.01 MATERIALS
A. Sheet Membrane Waterproofing System: a self-adhesive, cold-applied composite sheet consisting of a thickness of 1.4 mm (0.056 in.) of rubberized asphalt and 0.1 mm (0.004 in.) of cross-laminated, high density polyethylene film. Provide rubberized asphalt membrane covered with a release sheet which is removed during installation. No special adhesive or heat shall be required to form laps.
2.02 PHYSICAL PROPERTIES:
Property Test Method Typical Value Color Dark gray-black Thickness ASTM D 3767 Method A 1.5 mm (0.060 in.)
nominal Flexibility, 180, Bend over 25 mm (1 in.), mandrel at -43 C(-45 F)
ASTM D 1970 Unaffected
Tensile Strength, ASTM D 412 2240 kN/m2 (325 lb/in.2)
Revised 19 May 2023
SHEET WATERPROOFING 071300 - 3
Membrane Die C Modified minimum
Tensile Strength, Film ASTM D 882 34 500 kN/m2 (5 000 lb/in.2) minimum
Elongation, Ultimate Failure of Rubberized Asphalt
ASTM D 412 300% minimum
Crack Cycling -32?C (-25?F), 100 Cycles
ASTM C 836 Unaffected
Lap Adhesion at Minimum Application Temperature
ASTM D 1876 700 N/m (4 lb/in.) - Bituthene 3000 880 N/m (5 lb/in.) - Low Temp
Peel Strength ASTM D 903 1576 N/m (9 lb/in.)
Puncture Resistance, Membrane
ASTM E 154 222 N (50 lb) minimum
Resistance to Hydrostatic Head
ASTM D 5385 60 m (200 ft) of water
Exposure to Fungi in Soil, 16 weeks
GSA-PBS 07115 Unaffected
Permeance ASTM E 96 Method B 2.9 ng/m2sPa (0.05 perms) maximum
Water Absorption ASTM D 570 0.1% maximum
2.03 ACCESSORIES
A. Provide all products to include but limited to (primers,tape, liquid membranes as required for a complete systems for manufacturers 5 year warranty.
B. Prefabricated Drainage Composite: Drainage Composite shall be designed to promote positive drainage while serving as a protection course
1. For Vertical Wall Application:
a. Drainage Core Properties:
1) High impact polystyrene type
2) 0.44 inch (11 mm) nominal thickness in accordance with ASTM C366 Method B
3) 15,000 lbs/ft2 (718 kPa) compressive strength in accordance with ASTM D1621 (modified)
Revised 19 May 2023
SHEET WATERPROOFING 071300 - 4
4) 17 gal/min./ft (211 L/min./m) in accordancew with ASTM D4716
b. Geotextile Properties:
1) Nonwoven Type, Polypropylene
2) 4.0 oz/yd2 (136 g/m2) weight in accordance with ASTM D3776
3) 100 lbs (445 N) tensile strength in accordance with ASTM D4632
4) 10 U.S. sieve (0.21 mm) apparent opening size in accordance with ASTM D4751
5) 165 gal/min./ft2 (6724 L/min./m2) flow rate in accordance with ASTM D4491
6) 275 lbs (1.22 kN) CBR puncture in accordance with ASTM D6241.
2. For Horizontal Applications:
a. Drainage Core Properties:
1) High impact polystyrene type
2) 0.44 inch (11 mm) nominal thickness in accordance with ASTM C366 Method B
3) 18,000 lbs/ft2 (862 kPa) compressive strength in accordance with ASTM D1621
4) 17 gal/min./ft (211 L/min./m) in accordancew with ASTM D4716
b. Geotextile Properties:
1) Nonwoven Type, Polypropylene
2) 8.0 oz/yd2 (136 g/m2) weight in accordance with ASTM D3776
3) 205 lbs (912 N) tensile strength in accordance with ASTM D4632
4) 80 U.S. sieve (0.177 mm) apparent opening size in accordance with
ASTM D4751
5) 90 gal/min./ft2 (3668 L/min./m2) flow rate in accordance with ASTM D4491
6) 600 lbs (2.66 kN) CBR puncture in accordance with ASTM D6241.
Revised 19 May 2023
SHEET WATERPROOFING 071300 - 5
PART 3 EXECUTION
3.01 EXAMINATION
A. Verify existing conditions are acceptable prior to starting this work.
B. Verify items that penetrate surfaces to receive waterproofing are securely installed.
3.02 PREPARATION
A. Protect adjacent surfaces from damage not designated to receive waterproofing.
B. Clean and prepare surfaces to receive waterproofing in accordance with manufacturer's instructions; vacuum substrate clean.
C. Do not apply waterproofing to surfaces unacceptable to membrane manufacturer.
D. Seal cracks and joints with sealant using depth to width ratio as recommended by sealant manufacturer .
E. Surfaces for Adhesive Bonding: Apply surface conditioner at a rate recommended by manufacturer, and protect conditioner from rain or frost until dry.
3.03 INSTALLATION - MEMBRANE
A. Install membrane waterproofing in strict accordance with manufacturer's instructions and warranty requirements.
B. Roll out membrane, and minimize wrinkles and bubbles.
C. Self-Adhering Membrane: Remove release paper layer, and roll out onto substrate with a mechanical roller to provide full contact bond.
D. Overlap edges and ends, minimum 3 inches (76 mm), seal permanently waterproof by method recommended by manufacturer, and apply uniform bead of sealant to joint edge.
E. Reinforce membrane with multiple thickness of membrane material over joints, whether joints are static or dynamic.
F. Weather lap joints on sloped substrate in direction of drainage, and seal joints and seams.
G. Flexible Flashings: Seal items watertight that penetrate through waterproofing membrane with flexible flashings.
Revised 19 May 2023
SHEET WATERPROOFING 071300 - 6
H. Seal membrane and flashings to adjoining surfaces. Install counterflashing over all exposed edges.
3.04 INSTALLATION - DRAINAGE PANEL
A. Install drainage panels and protection boards in strict accordance with the manufacturers standards and in conjunction with the manufactures system and warranty requirements.
3.05 FIELD QUALITY CONTROL
A. Upon completion of horizontal membrane installation, dam installation area in preparation for flood testing.
B. Flood to minimum depth of 1 inch (25 mm) with clean water, and after 48 hours inspect for leaks.
C. If leaking is found, remove water, repair leaking areas with new waterproofing materials as directed by the Architect ; repeat flood test, and repair damage to building.
D. When area is proven watertight, drain water and remove dam.
3.06 PROTECTION
A. Per Manufacturers recommendations
B. Do not permit traffic over unprotected or uncovered membrane.
INTEGRALLY BONDED UNDERSLAB VAPOR BARRIER
CONCRETE FLOOR SLAB
POROUS FILL
SHEET MEMBRANE WATERPROOFING
INTEGRALLY BONDED UNDERSLAB VAPOR BARRIER
CONCRETE FLOOR SLAB
POROUS FILL
SHEET MEMBRANE WATERPROOFING
SEALANT
FOOTING - SEE STRUCTURAL
PIER - SEE STRUCTURAL
POROUS FILL
STEEL COLUMN - SEE STRUCTURAL
CONCRETE FLOOR SLAB
INTEGRALLY BONDED UNDERSLAB VAPOR BARRIER
ANCHOR BOLTS
FOOTING - SEE STRUCTURAL
CMU WALL
SHEET MEMBRANE WATERPROOFING
POROUS FILL
CONCRETE FLOOR SLAB
INTEGRALLY BONDED UNDERSLAB VAPOR BARRIER
SEALANT
Sheet Number
Sheet Title
Project Title
M on tg om er y
D ot ha n
W W
W .S
SL
A
R C
H .C
O M
(M ) 3
. 2
. 5
(D
) 3
. 7
. 5
Job Number
Date
Drawn By
Checked By
A
RC
H
IT
E
CT
U
RE
IN
TE
RI
O R
D E
SI
G
N
A5.10
VAPOR
PROTECTION
DETAILS - BASE
BID
A
IR
CR
A
FT
M
A
IN
TE
N
A N
CE
FA
CI
LI
TY
U
N
IT
D A
N N
E
LL
Y F
IE
LD
M O
N
TG
O M
E
RY
A L
18153
08/01/2021
NJ, SS, LG, JJ
FEL
Rev. Description Date
1 ADD#2 5/19/23
1" = 1'-0"A5.10
1 EXTERIOR WALL VAPOR BARRIER DETAIL - METAL STUDS
1" = 1'-0"A5.10
2 EXTERIOR WALL VAPOR BARRIER DETAIL - LOAD BEARING CMU
1" = 1'-0"A5.10
3 INTERIOR COLUMN VAPOR BARRIER DETAIL
1" = 1'-0"A5.10
4 INTERIOR CMU WALL VAPOR BARRIER DETAIL
HOIST BEAM AS REQUIRED
SEE PLAN
SUMP PIT - LOCATE AND SIZE PER
ELEVATOR MANUFACTURER AND
PLUMBING. INSTALL VAPOR
BARRIER ON ALL SIDES.
INTEGRALLY BONDED UNDERSLAB
VAPOR BARRIER
CONTINUOUS WATER STOP
DRAIN - SEE CIVIL
AGGREGATE FILL MATERIAL
FILTER FABRIC
PREFAB. DRAINAGE
COMPOSITE
SHEET MEMBRANE
WATERPROOFING MEMBRANE ALL
SIDES OF PIT
GRANULAR FILL
POROUS FILL
INTEGRALLY BONDED UNDERSLAB
VAPOR BARRIER
CONCRETE SLAB ON GRADE
CONTINUOUS WATER STOP
ELEVATOR DOOR - REFER TO SPECIFICATIONS
ELEVATOR DOOR - REFER TO SPECIFICATIONS
BOND BEAM - SEE STRUCTURAL
BOND BEAM - SEE STRUCTURAL
ELEVATOR MACHINERY AS
REQUIRED - COORDINATE WITH
ELEVATOR MANUFACTURER
RAIL BRACKETS AS REQUIRED
First Floor 0'-0"
Second Floor 15'-0"
Mech. Mezz.
11'-9 1/2"
Level 5 15' - 0"
Level 6 11' - 9 1/2"
A5.8
SUSPENDED CEILING
WITH LED LIGHTING -
SEE SPECS
V
ER
IF
Y
W
IT
H E
LE
V A
TO
R M
A N U
FA
C
TU
R
ER
PLASTIC LAMINATE
STAINLESS STEEL
HANDRAILS
PLASTIC LAMINATE
STAINLESS STEEL
HANDRAILS
V
ER
IF
Y
W
IT
H E
LE
V A
TO
R M
A N U
FA
C
TU
R
ER
ELEVATOR DOOR
V
ER
IF
Y
W
IT
H E
LE
V A
TO
R M
AN
U
FA
C
TU
R
ER
A6.4
106 SF
ELEV. MACHINE
ROOM
V
ER
IF
Y
W
IT
H E
LE
V A
TO
R M
AN
U
FA
C
TU
R
ER
" C
LE
A R
H O
IS
T-
W A Y
A N D
P
IT
VERIFY WITH ELEVATOR MANUFACTURER
5' - 9" CLEAR HOIST-WAY AND PIT
ELEVATOR MACHINERY AS
REQUIRED - COORDINATE
WITH ELEVATOR
MANUFACTURER
HOISTWAY LADDER AS REQUIRED - TO BE PROVIDED AND INSTALLED BY CONTRACTOR
A6.4 3
A5.8
Sheet Number
Sheet Title
Project Title
M on tg om er y
D ot ha n
W W
W .S
SL
A
R C
H .C
O M
(M ) 3
. 2
. 5
(D
) 3
. 7
. 5
Job Number
Date
Drawn By
Checked By
A
RC
H
IT
E
CT
U
RE
IN
TE
RI
O R
D E
SI
G
N
A6.4
ENLARGED
ELEVATOR PLANS,
SECTIONS, &
ELEVATIONS
A
IR
CR
A
FT
M
A
IN
TE
N
A N
CE
FA
CI
LI
TY
U
N
IT
D A
N N
E
LL
Y F
IE
LD
M O
N
TG
O M
E
RY
A L
18153
08/01/2021
NJ, SS, LG, JJ
FEL
1/2" = 1'-0"A6.4
6 ELEVATOR SECTION
1/2" = 1'-0"A6.4
2 ELEVATOR CEILING
1/2" = 1'-0"A6.4
3 ELEVATOR ELEVATION 1 1/2" = 1'-0"A6.4
4 ELEVATOR ELEVATION 2
1/2" = 1'-0"A6.4
5 ELEVATOR ELEVATION 3
1/2" = 1'-0"A6.4
1 ELEVATOR ENLARGED FLOOR PLAN
PROVIDE LVT FLOORING SEE
SPEC 09 6519 AND SHEET A3.0
Rev. Description Date
1 ADD#2 5/19/23
INTEGRALLY BONDED UNDERSLAB VAPOR BARRIER
CONCRETE FLOOR SLAB
GRAVEL FILL - SEE CIVIL
DRILLED PIER - SEE STRUCTURAL
GRAVEL FILL - SEE CIVIL
SUBGRADE - SEE CIVIL
GRADE BEAM - SEE STRUCTURAL
VOID FORM
VOID FORM
SLOPE (0.5%)
FOUNDATION DRAIN - SEE CIVIL
PIER - SEE STRUCTURAL
GRADE BEAM - SEE STRUCTURAL
STEEL COLUMN - SEE STRUCTURAL
CONCRETE FLOOR SLAB
INTEGRALLY BONDED UNDERSLAB VAPOR BARRIER
GRAVEL FILL - SEE STRUCTURAL
GRAVEL FILL - SEE STRUCTURAL
INTEGRALLY BONDED UNDERSLAB VAPOR BARRIER
VOID FORM
VOID FORM
SUBGRADE - SEE CIVIL
SLOPE
ANCHOR BOLTS
INTEGRALLY BONDED UNDERSLAB VAPOR BARRIER
CONCRETE FLOOR SLAB
GRAVEL FILL - SEE CIVIL
DRILLED PIER - SEE STRUCTURAL
GRAVEL FILL - SEE CIVIL
SUBGRADE - SEE CIVIL
GRADE BEAM - SEE STRUCTURAL
VOID FORM
VOID FORM
SLOPE (0.5%)
FOUNDATION DRAIN - SEE CIVIL
PIER - SEE STRUCTURAL
INTEGRALLY BONDED UNDERSLAB VAPOR BARRIER
GRAVEL FILL - SEE CIVIL
CMU WALL
CONCRETE FLOOR SLAB
INTEGRALLY BONDED UNDERSLAB VAPOR BARRIER
BOND BREAKER
GRAVEL FILL - SEE CIVIL
SUBGRADE - SEE CIVIL
VOID FORM
VOID FORM
SLOPE
Sheet Number
Sheet Title
Project Title
M on tg om er y
D ot ha n
W W
W .S
SL
A
R C
H .C
O M
(M ) 3
. 2
. 5
(D
) 3
. 7
. 5
Job Number
Date
Drawn By
Checked By
A
RC
H
IT
E
CT
U
RE
IN
TE
RI
O R
D E
SI
G
N
A5.10A
VAPOR
PROTECTION
DETAILS - BID
OPTION #6
A
IR
CR
A
FT
M
A
IN
TE
N
A N
CE
FA
CI
LI
TY
U
N
IT
D A
N N
E
LL
Y F
IE
LD
M O
N
TG
O M
E
RY
A L
18153
08/01/2021
NJ, SS, LG, JJ
FEL
1" = 1'-0"A5.10A
1 EXTERIOR WALL VAPOR BARRIER DETAIL - METAL STUDS (BID OPTION)
1" = 1'-0"A5.10A
2 INTERIOR COLUMN VAPOR BARRIER DETAIL (BID OPTION)
1" = 1'-0"A5.10A
3 EXTERIOR WALL VAPOR BARRIER DETAIL - LOAD BEARING CMU (BID OPTION)
1" = 1'-0"A5.10A
4 INTERIOR CMU WALL VAPOR BARRIER DETAIL (BID OPTION)
1 ADD#2 5/19/23
SUBGRADE ELEVATION - SEE CIVIL
FOUNDATION DRAIN - SEE CIVIL
FILTER FABRIC
GRAVEL FILL
SHEET MEMBRANE
WATERPROOFING - ALL SIDES OF PIT
VOID FORM
VOID FORM
CONTINUOUS WATER STOP
CONTINUOUS WATER STOP
CONCRETE FLOOR SLAB - SEE
STRUCTURAL
INTEGRALLY BONDED UNDERSLAB
VAPOR BARRIER
SUMP PIT - LOCATE AND SIZE PER ELEVATOR
MANUFACTURER AND PLUMBING. INSTALL
VAPOR BARRIER ON ALL SIDES.
PREFAB. DRAINAGE COMPOSITE
RAIL BRACKETS AS REQUIRED
CONTINUOUS WATER STOP
VOID FORM
Sheet Number
Sheet Title
Project Title
M on tg om er y
D ot ha n
W W
W .S
SL
A
R C
H .C
O M
(M ) 3
. 2
. 5
(D
) 3
. 7
. 5
Job Number
Date
Drawn By
Checked By
A
RC
H
IT
E
CT
U
RE
IN
TE
RI
O R
D E
SI
G
N
A5.11A
Vapor Protection Details – Bid Option No. 6
A
IR
CR
A
FT
M
A
IN
TE
N
A N
CE
FA
CI
LI
TY
U
N
IT
D A
N N
E
LL
Y F
IE
LD
M O
N
TG
O M
E
RY
A L
18153
08/01/2021
NJ, SS, LG, JJ
FEL
Rev. Description Date
1" = 1'-0"A5.11A
1 ELEVATOR PIT DETAIL - BID OPTION NO. 6
K
1 2 4 6
7 9
8 11
J
A
B
C
DD
EE
3 5
H
GF
2.6 2.8 5.2 5.4 5.9 7.1 7.5
C.9
W8X24
W8X24
W8X48
W8X48
W8X24
W8X48
W8X24
W8X58
W8X58
W8X31W8X40W8X48W8X48
W8X31
W8X67
W8X58 W8X58
W8X58
W8X58 W8X58
W8X48 W8X48
S2.7A
S2.7A
S2.7A
S2.7A
31' - 9 1/16" 50' - 10 3/16" 30' - 10 5/8"
20' - 6 15/16" 11' - 2 1/8" 11 1/4"
21' - 1 7/16" 11' - 6 7/8" 20' - 10 1/16" 3' - 4" 5' - 4" 21' - 4 1/8" 4' - 9 7/8" 24' - 2 1/4" 11 1/4"
/4
/4
/1
/1
72' - 8 3/16" 11' - 7 1/2" 9' - 8 1/4" 11' - 2 1/8" 9' - 2 11/16"
/8
/1
/1
/1
/4
/1
/1
/1
/1
/4
/4
/4
11 1/4"
6 1/2" 6"
20' - 9"
8"
10' - 4"
40' - 11"
8"
16' - 1"
8"
24' - 9"
8"
29' - 8"
11"
11 1/4" 11 1/4"
W8X58
HSS6x6x3/8 GIRT
HSS6x6x3/8 GIRT
HSS6x6x3/8 GIRT
HSS6x6x3/8 GIRT
HSS6x6x1/4 STUB COL.
HSS6X6X1/4
HSS6X6X1/4
HSS6X6X1/4
HSS6X6X1/4
HSS6X6X1/4
5' - 5 11/16" 10' - 4 3/8" 13' - 2 1/16"12' - 8 3/4" 4' - 10" 6' - 7 5/16" 7' - 8 11/16" 4' - 10" 11' - 6"
1' - 8 3/16"
HSS8x6x1/4
(LDV) GIRT
10' - 1"
8"
5' - 9" 8"
/4 " 9 3/16"1' - 6 1/4"
47' - 7 7/8" 1' - 2 1/4"
' - 2
/ 4
88°
1' - 6 1/4"
8" 23' - 6"
8"
17' - 0"
/4
/4
1' - 6 1/4"
CENTERLINE OF ROOF
BEAM BEARING ABOVE.
AREAS SHOWN THUS ARE 2-
FILLED CELLS (16") FULL HT. &
REINF. W/ REBAR SAME SIZE
AS WALL REINF. IN EA. CELL.
LANDSCAPE WALL.
SEE SHEET L1.0
LANDSCAPE WALL.
SEE SHEET L1.0
DEPRESS SLAB AS REQ'D.
@ SHOWERS. SEE ARCH.
DWGS. FOR LOCATIONS.
DEPRESS SLAB
AS REQ'D. FOR
WALK OFF MAT
DEPRESS SLAB
AS REQ'D. FOR
WALK OFF MAT
DEPRESS SLAB
AS REQ'D. FOR
WALK OFF MAT
DEPRESS SLAB
AS REQ'D. FOR
WALK OFF MAT
2' - 5" 17' - 4"
/4
HSS12X8X3/8
HSS12X8X3/8
TOP OF PIER
EL.= -5'-0"
PROVIDE 2-FILLED CELLS & REINF.
W/ #5 EA. CELL FULL HT. BELOW
BEARING OF FLOOR BEAMS ABOVE.
PROVIDE 2-FILLED CELLS & REINF.
W/ #5 EA. CELL FULL HT. BELOW
BEARING OF FLOOR BEAMS ABOVE.
FLOOR CONSTRUCTION
8" THICK CONCRETE SLAB OVER VAPOR
BARRIER, OVER VOID FORM, OVER POROUS
FILL. SEE SECTIONS FOR REINFORCING.
FINISH FLOOR EL.+0'-0" (+0'-0")
NOTE:
UNLESS NOTED OTHERWISE, TOP
OF DRILLED PIER EL. = (-2'-8")
S2.7A
S2.7A
S2.7A
S2.7A
S2.7A
S2.7A
S2.7A
S2.7A
S2.7A
S2.7A
S2.7A
S2.7A
S2.7A
S2.8A
S2.7A
S2.7A
S2.7A
S2.8A
S2.8A
A
S2.8A
B
S2.8A
B
S2.8A
S2.8A
C
S2.8A
SIM TO
S2.8A
S2.8A
13' - 6"
GENERAL NOTES FOR ALTERNATE FOUNDATION
FOUNDATION:
1. DRILLED CAISSONS WERE DESIGNED BASED ON THE ALLOWABLE
SHAFT CAPACITIES OUTLINED IN THE GEOTECHNICAL REPORT.
2. ELEVATIONS SHOWN ON PLAN ARE TOP OF FOOTINGS AND ARE MINIMUM
DEPTH. DIFFERENT OR UNUSUAL CONDITIONS SHALL BE REPORTED TO
THE ARCHITECT AND/OR ENGINEER. DRILLED CAISSON TOP ELEVATION
AND MINIMUM DEPTH OF EMBEDMENT ARE INDICATED ON PLANS.
ALONG WITH THEIR BID, CONTRACTOR SHALL SUBMIT UNIT PRICES
PER LINEAR FOOT TO ADD OR DEDUCT LENGTH OF
CAISSON DUE TO VARIATION.
3. ALL DRILLED PIERS AND GRADE BEAMS SHALL HAVE F'c=5000 SPI.
CONCRETE:
1. ALL CONCRETE SHALL HAVE A COMPRESSIVE STRENGTH AT 28 DAYS OF
F'c = 5000 PSI AND A MAXIMUM WATER-CEMENT RATIO OF 0.43.
ALL CONCRETE FOR EXTERIOR APPLICATIONS SHALL CONTAIN
ENTRAINED AIR. SEE SPECS FOR ADDITIONAL INFORMATION.
2. REINFORCING STEEL SHALL CONFORM TO ASTM A615 GRADE 60.
3. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185 OR ASTM A1064.
4. UNLESS NOTED OTHERWISE PROTECTIVE COVERING OF REINFORCEMENT
SHALL BE AS FOLLOWS ( SEE DETAILS ) : FOOTINGS AND GRADE BEAMS
3" CLEAR BOTTOM AND SIDES, 2" CLEAR TOP. CONCRETE SLABS
1 1/2" CLEAR. WALLS 1 1/2" CLEAR SIDES. BEAMS 1 1/2" CLEAR TO
STIRRUPS. FORMED CONCRETE COLUMNS 1 1/2" CLEAR TO TIES.
5. LAP ALL CONCRETE WALL VERTICAL REINFORCING AND CONCRETE BEAM
HORIZONTAL REINFORCING WITH CLASS B LAP SPLICES. LAP ALL OTHER
CONTINUOUS BARS WITH CLASS A SPLICES UNLESS NOTED OTHERWISE.
6. PLACING PLANS AND DETAILS SHALL BE IN ACCORDANCE WITH THE
LATEST "A.C.I. DETAILING MANUAL".
7. STEEL FABRICATOR SHALL SUBMIT SHOP DRAWINGS FOR THE ARCHITECT
AND/OR ENGINEER'S REVIEW.
8. DO NOT RUN CONDUITS, RACEWAYS, OR PIPES IN CONCRETE SLABS, BEAMS,
OR COLUMNS WITHOUT SPECIFIC APPROVAL FROM BLACKBURN DANIELS O'BARR.
NOTE:
PROVIDE REBAR 3" CLEAR
BOTTOM & SIDES & 2" CLEAR
TOP FOR ALL GRADE BEAMS
RUNNING NOTH & SOUTH.
FOR GRADE BEAMS RUNNING
EAST & WEST, PLACE ALL
STEEL INSIDE OF NORTH -
SOUTH BEAMS. TERMINATE
ALL TOP BARS W/ A
STANDARD HOOK. EXTEND
BOTTOM BARS A MINIMUM OF
8" INTO SUPPORT BEAM.
Sheet Number
Sheet Title
Project Title
Job Number
Date
Drawn By
Checked By
S o u th C o u rt S tr ee t
M o n tg o m er y, A L
T el
W W W .S S L A R C H .C O M
A R
C H
IT
E
C T
U R
E
I N
T E
R
IO
R D
E S
IG
N
05-19-23
S1.1A
First Floor and Foundation Plan - Alternate
A
IR
C R
A F
T M
A
IN
T E
N A
N C
E F
A C
IL
IT
Y U
N
IT
D A
N N
E L
L Y
F
IE
L D
M O
N T
G O
M E
R Y
A
L
18153
05/19/2023
1/8" = 1'-0"
First Floor and Foundation Plan - ALTERNATE
K
1 2 4 6
7 9
8 11
J
A
B
C
DD
EE
3 5
H
GF
2.6 2.8 5.2 5.4 5.9 7.1 7.5
C.9
31' - 9 1/16" 50' - 10 3/16" 30' - 10 5/8"
20' - 6 15/16" 11' - 2 1/8" 11 1/4"
21' - 1 7/16" 11' - 6 7/8" 20' - 10 1/16" 3' - 4" 5' - 4" 21' - 4 1/8" 4' - 9 7/8" 24' - 2 1/4" 11 1/4"
/4
/4
/1
/1
/1
/8
/1
/4
/8
/1
/1
/1
/4
/1
/8
/4
/1
/1
/2
/1
/1
/4
/4
/4
11 1/4"
11 1/4"
11 1/4"
5' - 5 11/16" 10' - 4 3/8" 13' - 2 1/16"12' - 8 3/4" 4' - 10" 6' - 7 5/16" 7' - 8 11/16" 4' - 10" 11' - 6"
1' - 8 3/16"
88°
/4
1' - 0 1/4"
1' - 4 7/16"
8' - 3 3/4" 9' - 0 1/4"
1' - 4 3/4" 1' - 1 7/8" 9" 1' - 4"
2' - 1 3/8"
10' - 8 1/16" 14' - 6"
72' - 8 3/16" 11' - 7 1/2" 9' - 8 1/4" 11' - 2 1/8" 9' - 2 11/16"
1' - 0 1/4" 7' - 7 3/4" 16' - 4 5/8" 16' - 2 5/8" 8' - 1 9/16" 6' - 2 7/16"
2' - 5 1/16"
11' - 3 11/16" 4' - 4 7/16" 9' - 10 1/16" 9 3/16"
9' - 5 3/4"
11 1/2"
5' - 10 5/16"
3' - 7 9/16"
9' - 2 11/16"
/4
15' - 7 1/16" 15' - 7 1/16" 15' - 7 1/16"
2' - 6"
2' - 6"
5' - 10 1/2" 8' - 5 1/2"
/8
2' - 0"
LANDSCAPE WALL.
SEE SHEET L1.0.
PROVIDE 30"Ø
DRILLED PIERS
SPACED @ 10'-0"
MAX. CENTERED
BELOW WALL.
LANDSCAPE WALL.
SEE SHEET L1.0.
PROVIDE 30"Ø
DRILLED PIERS
SPACED @ 10'-0"
MAX. CENTERED
BELOW WALL.
2' - 0"
8' - 2 15/16"9' - 10"
4' - 4"
CONTINUE THIS
GRADE BEAM TO
NEXT GRADE
BEAM AS SHOWN
Sheet Number
Sheet Title
Project Title
Job Number
Date
Drawn By
Checked By
S o u th C o u rt S tr ee t
M o n tg o m er y, A L
T el
W W W .S S L A R C H .C O M
A R
C H
IT
E
C T
U R
E
I N
T E
R
IO
R D
E S
IG
N
05-19-23
S1.2A
Drilled Pier & Grade Beam Layout Plan - Alternate
A
IR
C R
A F
T M
A
IN
T E
N A
N C
E F
A C
IL
IT
Y U
N
IT
D A
N N
E L
L Y
F
IE
L D
M O
N T
G O
M E
R Y
A
L
18153
05/19/2023
1/8" = 1'-0"
Drilled Pier & Grade Beam Layout Plan - ALTERNATE
#3 TIES @ 12"O.C.
SIZE TIES FOR 14"x14"
PIER, 1 1/2" CLEAR.
#4 TIES @
18"O.C., VERT.
(4)#8 VERT.
30"Ø
30"Ø DRILLED
PIER
(14)#9 VERT.
STANDARD 90°
HOOK, TYP.
BEARING STRATA
SHALL BE APPROVED
BY TESTING LAB.
VOID FORM
GRADE BEAM &
STRUCTURAL SLAB.
SEE SECTIONS
TYPICAL DRILLED PIER DETAIL
VIEW A-A
30"Ø
(14)#9 VERT.
#4 TIES @
18"O.C., VERT.
#3 TIES @ 12"O.C.
SIZE TIES FOR 14"x14"
PIER, 1 1/2" CLEAR.
(6)#7 VERT.
NOTE:
TEMPORARILY CASE
DRILLED PIER TO ALLOW
FOR MANUAL CLEANING
& INSPECTION.
TIP EL.= -35'-0" FROM
GROUND SURFACE
(EL. 165'-0")
NOTE:
PROVIDE VOID FORM
UNDER ALL GRADE
BEAMS BETWEEN
DRILLED PIER, TYPICAL.
12" C.M.U. W/ #5 @ EA. JAMB
& @ 24"O.C., CENTERED. FILL
CELLS SOLID W/ CONC. FULL
HT. OF WALL ONLY @ #5.
30"Ø DRILLED PIER
BEYOND. SEE SHT.
2.7A FOR TYPICAL
DRILLED PIER DETAIL.
VOID FORM
6 5/8"
CONT. HORIZ. MAS-
ONRY JOINT REINF.
@ 16"O.C., VERT.
FIN. GRADE. SEE
CIVIL DWGS.
PROVIDE 3/8" PEJ. W/
SEALANT WHERE
CONC. ABUTS WALL
CAST STONE. SEE
ARCH. DWGS.
FILL CAVITY W/ CONC.
BELOW FIN. GRADE
(4)#8 CONT. TOP &
BOT. W/ #4 @ 8"O.C.
SIZE STIRRUPS FOR
1'-6" x 2'-0" DEEP
GRADE BEAM.
1' - 9 5/8"
FIN. FLOOR
+0'-0"
#6 @ 8"O.C. 1" CL.
TOP & 1 1/2" CL. BOT.
S P
L
IC
E
D
IA
#5 @ 12"O.C.
FIN. GRADE. SEE
CIVIL DWGS.
PROVIDE 3/8" PEJ. W/
SEALANT WHERE
CONC. ABUTS WALL
6"x1 5/8"x16GA. 'C' STUDS @
16"O.C. W/ CONT. TRACK TOP
& BOT. PROVIDE CONT.
BRIDGING @ 48"O.C., VERT.
MASONRY TIES @
16"O.C., EA. WAY
SHEATHING. SEE
ARCH. DWGS.
CAST STONE. SEE
ARCH. DWGS.
T.O.S.
(+3'-3 1/2")
HSS6x6x1/4 GIRT WHERE
STOREFRONT OCCURS
STOREFRONT.
SEE ARCH. DWGS.
7 1/4"
30"Ø DRILLED PIER
BEYOND. SEE SHT.
2.7A FOR TYPICAL
DRILLED PIER DETAIL.
VOID FORM
FILL CAVITY W/ CONC.
BELOW FIN. GRADE
(4)#8 CONT. TOP &
BOT. W/ #4 @ 8"O.C.
1' - 6"
FIN. FLOOR
+0'-0"
#6 @ 8"O.C. 1" CL.
TOP & 1 1/2" CL. BOT.
#5 @ 12"O.C.
SLOPE
3/8" PEJ. W/ SEALANT
JAMB BEYOND
/8
L2x2x1/4 CONT. W/
3/8"Ø HEADED STUD
ANCHORS @ 24"O.C.
COORDINATE W/
ROLL-UP DOOR MFR.
30"Ø DRILLED PIER
BEYOND. SEE SHT.
2.7A FOR TYPICAL
DRILLED PIER DETAIL.
VOID FORM
(4)#8 CONT. TOP &
BOT. W/ #4 @ 8"O.C.
SIZE STIRRUPS FOR
1'-6" x 2'-0" DEEP
GRADE BEAM.
1' - 9 5/8"
FIN. FLOOR
+0'-0"
#6 @ 8"O.C. 1" CL.
TOP & 1 1/2" CL. BOT.
#5 @ 12"O.C.
SLOPE
3/8" PEJ. W/ SEALANT
30"Ø DRILLED PIER
BEYOND. SEE SHT.
2.7A FOR TYPICAL
DRILLED PIER DETAIL.
VOID FORM
FIN. FLOOR
+0'-0"
#6 @ 8"O.C. 1" CL.
TOP & 1 1/2" CL. BOT.
6 5/8"
(4)#8 CONT. TOP &
BOT. W/ #4 @ 8"O.C.
2' - 0 5/8"
#5 @ 12"O.C.
8" SEE PLAN 8"
#4 @ 8"O.C. EA.
WAY, CENTERED.
(4)SIDES OF PIT
#5 @ 12"O.C., EA. WAY. 2"
CLEAR TOP & 3" CLEAR BOT.
NOTE:
BLOCK OUT AS REQ'D. FOR
CYLINDER & SEE PLUMBING
DWGS. FOR SUMP LOCATION.
SILL SUPPORT ANGLE BY
ELEVATOR MFR. (L4x4x1/4
MIN.) W/ 3/4"Ø ANCHOR
BOLTS EA. END & 16"O.C.
JAMB BEYOND
#4 @ 48"O.C., CENTERED.
FILL CELLS W/ CONC.
FULL HT. ONLY @ #4.
VOID FORM
FIN. FLOOR
+0'-0"
S P
L
IC
E
D
IA
DRILLED PIER
BEYOND
(4)#8 CONT. TOP &
BOT. W/ #4 @ 8"O.C.
1' - 6"
#6 @ 8"O.C. 1" CL.
TOP & 1 1/2" CL. BOT.
#5 @ 12"O.C.
E L
E V
A T
O R
M F
R
V
E R
IF
Y
W
30"Ø DRILLED PIER
BEYOND. SEE SHT.
2.7A FOR TYPICAL
DRILLED PIER DETAIL.
VOID FORM
(4)#8 CONT. TOP &
BOT. W/ #4 @ 8"O.C.
1' - 6"
FIN. FLOOR
+0'-0"
#6 @ 8"O.C. 1" CL.
TOP & 1 1/2" CL. BOT.
S P
L
IC
E
D
IA
#4 @ EA. JAMB & @ 48"O.C.,
CENTERED. FILL CELLS
SOLID W/ CONC. FULL HT.
OF WALL ONLY @ #4.
CONT. HORIZ. MAS-
ONRY JOINT REINF.
@ 16"O.C., VERT.
8"
#5 @ 12"O.C.
6x6-W1.4xW1.4 W.W.F.FIN. GRADE. SEE
CIVIL DWGS.
PROVIDE 3/8"
PEJ. W/ SEALANT
WHERE CONC.
ABUTS WALL
6"x1 5/8"x16GA. 'C'
STUDS @ 16"O.C. W/
CONT. TRACK TOP &
BOT. PROVIDE
CONT. BRIDGING @
48"O.C., VERT.
3/8" PEJ. W/ SEALANT
SEE ARCH. DWGS.
FOR FINISH
8"
#4 @ 12"O.C. EA.
WAY, CENTERED6"Ø MAX. 6"Ø MAX.
6"Ø MAX.
PLACE SLEEVES
BETWEEN REINF.
PLACE SLEEVES
BETWEEN REINF.
TYPICAL PLUMBING SLEEVE IN GRADE BEAM DETAILS
NOTE:
1. ALL SLEEVES PLACED IN GRADE BEAMS SHALL BE MADE W/ SCHEDULE
40 STEEL PIPE. PROVIDE 3"Ø STEEL PIPE SLEEVES FOR 2"Ø PLUMBING
PIPES & 6"Ø SLEEVES @ 4"Ø PLUMBING PIPES.
2. PLACE PLUMBING PIPE OUTSIDE & BELOW GRADE BEAMS WHERE
POSSIBLE. ONLY SLEEVE GRADE BEAM WHEN THIS IN NOT POSSIBLE.
Sheet Number
Sheet Title
Project Title
Job Number
Date
Drawn By
Checked By
S o u th C o u rt S tr ee t
M o n tg o m er y, A L
T el
W W W .S S L A R C H .C O M
A R
C H
IT
E
C T
U R
E
I N
T E
R
IO
R D
E S
IG
N
05-19-23
S2.7A
Sections and Details - Alternate
A
IR
C R
A F
T M
A
IN
T E
N A
N C
E F
A C
IL
IT
Y U
N
IT
D A
N N
E L
L Y
F
IE
L D
M O
N T
G O
M E
R Y
A
L
18153
05/19/2023
3/4" = 1'-0"
SECTION
1 3/4" = 1'-0"
SECTION
2 3/4" = 1'-0"
SECTION
3/4" = 1'-0"
SECTION
3/4" = 1'-0"
SECTION
5 3/4" = 1'-0"
SECTION
3/4" = 1'-0"
SECTION
NOTE:
WHERE GRADE BEAM BAR SPLICES
OCCUR, SPLICE ALL TOP BARS @ BEAM
CENTERLINE & ALL BOTTOM BARS @
CENTERLINE OF DRILLED PIERS.
5' - 6"
2' - 1 7/8" 1' - 2 1/4" 2' - 1 7/8"
SEE PLAN
FOR EL.
FILL ALL CELLS W/ CONC.
BELOW FIN. FLOOR
#5 @ 12"O.C. EA.
WAY, TOP & BOT.
6x6-W1.4xW1.4 W.W.F.
8" C.M.U. W/ #6 @ 8"O.C., CENTERED. FILL ALL
CELLS SOLID W/ CONC.
FULL HT. OF WALL.
CONT. HORIZ. MAS-
ONRY JOINT REINF.
@ 16"O.C., VERT.
FILL CAVITY W/ CONC.
BELOW FIN. GRADE
FIN. GRADE. SEE
CIVIL DWGS.
PROVIDE 3/8" PEJ. W/
SEALANT WHERE
CONC. ABUTS WALL
S P
L
IC
E
D
IA
CAST STONE. SEE
ARCH. DWGS.
VARIES -
14'-0" MAX.
T.O.W.
6 5/8"
CONT. U-BLOCK W/
#5 TOP & BOTTOM
WALL CAP. SEE
ARCH. DWGS.
30"Ø DRILLED PIER
BEYOND. SEE SHT.
2.7A FOR TYPICAL
DRILLED PIER DETAIL.
DOWEL INNER REINF.
INTO FOOTING SIM. TO
TYPICAL DRILLED PIER
DETAIL ON SHT. 2.7A
SLOPE
3/8" PEJ. W/ SEALANT
SEE ARCH. DWGS.
FOR FINISH
#4 @ EA. JAMB & @
48"O.C., CENTERED. FILL
CELLS W/ CONC. FULL HT.
OF WALL ONLY @ #4.
30"Ø DRILLED PIER
BEYOND. SEE SHT.
2.7A FOR TYPICAL
DRILLED PIER DETAIL.
VOID FORM
1' - 6"
FIN. FLOOR
+0'-0"
8"
S P
L
IC
E
D
IA
(4)#8 CONT. TOP &
BOT. W/ #4 @ 8"O.C.
#6 @ 8"O.C. 1" CL.
TOP & 1 1/2" CL. BOT.
#5 @ 12"O.C.
SLOPE
3/8" PEJ. W/ SEALANT
30"Ø DRILLED PIER
BEYOND. SEE SHT.
2.7A FOR TYPICAL
DRILLED PIER DETAIL.
VOID FORM
(4)#8 CONT. TOP &
BOT. W/ #4 @ 8"O.C.
SIZE STIRRUPS FOR
1'-6" x 2'-0" DEEP
GRADE BEAM.
1' - 6"
FIN. FLOOR
+0'-0"
7…