RECEPTACLES SYMBOLS
SINGLE RECEPTACLE OUTLET, 18" TO CENTER OF BOX A.F.F., UNO.
DUPLEX RECEPTACLE OUTLET, 18" TO CENTER OF BOX A.F.F., UNO.
QUADRUPLEX RECEPTACLE OUTLET, 18" TO CENTER OF BOX A.F.F., UNO.
DUPLEX RECEPTACLE OUTLET, GROUND-FAULT CIRCUIT INTERRUPTER (GFCI).
SPECIAL PURPOSE OUTLET, ELECTRICAL CHARACTERISTICS AS SPECIFIED ON PLANS.
FLOOR SINGLE RECEPTACLE OUTLET
FLOOR DUPLEX RECEPTACLE OUTLET
FLOOR QUADRUPLEX RECEPTACLE OUTLET
FLOOR SPECIAL PURPOSE OUTLET, ELECTRICAL CHARACTERISTICS AS SPECIFIED ON PLANS.
ABBREVIATIONS
CONDUIT RACEWAY & WIRING SYMBOLS
CONDUIT
CONDUIT TURNING UP.
CONDUIT TURNING DOWN
CONDUIT CHANGE IN ELEVATION
CONDUIT IN SLAB OR UNDERGROUND
BRANCH CIRCUIT CONSISTING OF 2#12, 1#12 GND, IN 3/4" MINIMUM TRADE SIZE CONDUIT
BRANCH CIRCUIT, SLASHES DENOTE NUMBER OF CONDUCTORS
HOT WIRE OR SWITCH LEG
NEUTRAL WIRE
ISOLATED GROUND
GROUND WIRE
HOME RUN TO PANELBOARD OR DEVICE, NO MORE THAN THREE CIRCUITS PER HOME RUN
TEXT DENOTE SPLIT CIRCUIT
SC
POWER AND CONTROL PLAN SYMBOLS
ABBREVIATION DESCRIPTION
A AMPERE
ACB AIR CIRCUIT BREAKER
AF AMPERE FRAME
AFC AVAILABLE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPERES INTERRUPTING CAPACITY
AT AMPERE TRIP
A.T.S. AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
B BELL
BKR BREAKER
C CONDUIT
CAB CABINET
CB CIRCUIT BREAKER
CCT CIRCUIT
CNTL CONTROL
COL COLUMN
COMM COMMUNICATIONS
CONT'D CONTINUED
COR CONTRACTING OFFICER'S REPRESENTATIVE
CP CONTROL PANEL
CR CONTROL RELAY
CFL COMPACT FLUORESCE LAMP
CT CURRENT TRANSFORMER\ CERAMIC TILE\ COOLING TOWER
CU COPPER
D DIMMER\ DEEP\ DEPTH
DIST DISTRIBUTION
DS DISCONNECT SWITCH\ DOWN SPOUT
DWG DRAWING
ELEC ELECTRIC, ELECTRICAL
EMER EMERGENCY
EMT ELECTRICAL METALLIC TUBING
EO ELECTRICALLY OPERATED
EPO EMERGENCY POWER OFF
FA FIRE ALARM
FU FUSE
FS FLOW SWITCH
GBT GENERATOR BUS-TIE
GEN GENERATOR\ GENERAL
GF GROUND FAULT
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
HID HIGH INTENSITY DISCHARGE
H-O-A HAND-OFF-AUTOMATIC SWITCH
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INST INSTANTANEOUS
JB JUNCTION BOX\ JOIST BEARING
KA KILOAMPERE
KCMIL THOUSAND CIRCULAR MILLS
KS KEY SWITCH
kV KILOVOLT kVA KILOVOLT-AMPERE kW KILOWATT
LA LIGHTNING ARRESTER
LED LIGHT-EMITTING DIODE
LTG LIGHTING
M METER
MAINT MAINTENANCE
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCP MOTOR CIRCUIT PROTECTOR
MH MANHOLE, METAL HALIDE
MLO MAIN LUGS ONLY
MIN MINIMUM
MOCPD MAXIMUM OVERCURRENT PROTECTIVE DEVICE
MMS MANUAL MOTOR STARTER
MTD MOUNTED
MTR MOTOR
MTS MANUAL TRANSFER SWITCH
NF NON-FUSED, NON-FUSABLE
NC NORMALLY CLOSED
NO NORMALLY OPEN
NEU NEUTRAL
OC OVERCURRENT
OH OVERHEAD\ OPPOSITE HAND
OPER OPERATOR
P POLE
PB PUSHBUTTON\ PULL BOX
PC PHOTOELECTRIC CELL
PF POWER FACTOR\ PROFILE
PNL PANEL
PT POTENTIAL TRANSFORMER
PNLBRD PANELBOARD
PVC POLYVINYL CHLORIDE
REF REFER TO/ REFERENCE/ REFRIGERATOR
PWR POWER
REM REMOTE
RGS/RMC RIGID GALVANIZED STEEL CONDUIT
RM ROOM
SA SURGE ARRESTER
SC SPLIT CIRCUIT
SHLD SHIELDED
SW SWITCH
SPD SURGE PROTECTION DEVICE
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TB TERMINAL BOARD
TC TERMINAL CABINET/ TIME CLOCK/ TRIP COIL
TD TIME DELAY
TGB TELECOMMUNICATIONS GROUND BUSBAR
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
UNSHLD UNSHIELDED
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLT
VCB VACUUM CIRCUIT BREAKER
VFD VARIABLE FREQUENCY DRIVE
W WIRE/ WATT/ WIDTH/ WEST
W/ WITH
WLD WELDING
WP WEATHERPROOF/ WORKING POINT
XFMR TRANSFORMER
XP EXPLOSION PROOF
CEILING SINGLE RECEPTACLE OUTLET
CEILING DUPLEX RECEPTACLE OUTLET
CEILING QUADRUPLEX RECEPTACLE OUTLET
CEILING SPECIAL PURPOSE OUTLET, ELECTRICAL CHARACTERISTICS AS SPECIFIED ON PLANS.
SURFACE MOUNTED PANELBOARD, MOUNT SUCH THAT TOP CIRCUIT BREAKER IS NO MORE
THAN 72" A.F.F.
FLUSH MOUNTED PANELBOARD, MOUNT SUCH THAT TOP CIRCUIT BREAKER IS NO MORE THAN
72" A.F.F.
CONTROL CABINET
DISCONNECT SWITCH NF = NON FUSED
DENOTES SWITCH RATING
DENOTES FUSE RATING
MOTOR CONTROLLER
COMBINATION MOTOR CONTROLLER
MANUAL MOTOR STARTER, 60" A.F.F.M
MANUAL MOTOR STARTER WITH PILOT LIGHT, 60" A.F.F.MP
MAGNETIC CONTACTOR
DRY TYPE TRANSFORMER
NOTES: SUBSCRIPTS SHALL BE ADDED TO SYMBOL WHERE APPLICABLE.
"X" SUBSCRIPT AS INDICATED IN SCHEDULES.
CR SECURITY DEVICE - CARD READER - SEE DETAIL 1/E-401 AND 4/E-401
D SECURITY DEVICE - WALL MOUNTED DURESS BUTTON - SEE DETAIL 4/E-401
ES SECURITY DEVICE - ELECTRIC DOOR STRIKE - SEE DETAIL 1/E-401 AND 4/E-401
WD WIRELESS ACCESS POINT (GOVERNMENT PROVIDED)
SECURITY/TELECOMMUNICATIONS SYMBOLS
NOTES: SUBSCRIPTS SHALL BE ADDED TO SYMBOL WHERE APPLICABLE. "X" SUBSCRIPT
AS INDICATED IN SCHEDULES.
SUBSCRIPTX
SYSTEM SYMBOLS
CABINET OR PANEL SYMBOL
SUBSCRIPTXXX
NOTES: SUBSCRIPTS SHALL BE ADDED TO SYMBOL WHERE APPLICABLE.
"X" SUBSCRIPT AS INDICATED IN SCHEDULES.
NOTES: PROVIDE #10 AWG NEUTRALS IN MULTI-WIRE CIRCUITS
V-TEL DEVICE - VIDEO TELECONFERENCE - REFER TO DETAIL 3/E-402
D
DATA DEVICE - DURESS SYSTEM. REFER TO DETAIL 1/E-402
INFORMATION OUTLET - (#) DENOTES CABLE QUANTITY. REFER TO DETAIL 1/E-402
N NURSE CALL DEVICE - TOILET STATION
N NURSE CALL DEVICE - DOME LIGHT
SB A/V DEVICE - SMARTBOARD - REFER TO DETAIL 7/E-402
AV A/V DEVICE - A/V BOX FOR OVERHEAD PROJECTOR - REFER TO DETAIL 7/E-402
VT
ND
NM
NC NURSE CALL DEVICE - CODE STATION
NURSE CALL DEVICE - MASTER STATION
NURSE CALL DEVICE - DUTY STATION
TV TV DEVICE - J-BOX FOR CCTV - REFER TO DETAIL 3/E-402 AND
D SECURITY DEVICE - DESK MOUNTED DURESS BUTTON - SEE DETAIL 3/E-401
NOTES:
A. VERIFY EXACT MOUNTING
HEIGHTS WITH PROJECT
REQUIREMENTS. DEVICES MAY
OR MAY NOT APPLY TO THIS
PROJECT. REFER TO PLANS.
B. ALL NEW DEVICES SHALL BE
INSTALLED ACCORDING TO THE
MOUNTING HEIGHTS INDICATED
U.N.O.
FINISHED FLOOR
RECEPTACLE
COMM DATA
TELEPHONE
COUNTER HT.
RECEPTACLE
DATA
LIGHT
SWITCH
LIGHTING FIXTURE SYMBOLS
CEILING MOUNTED SURFACE OR
RECESSED LIGHTING FIXTURE.
LIGHTING FIXTURE, WITH INTEGRAL
EMERGENCY BATTERY PACK.
LIGHTING FIXTURE.
LIGHTING FIXTURE, WITH INTEGRAL
EMERGENCY BATTERY PACK.
EXIT LIGHTING, DARKENED SECTION(S) DENOTE FACE(S).
USE DIRECTIONAL ARROWS WHERE INDICATED.
EMERGENCY LIGHTING FIXTURE
A
A A
NOTES: UPPER CASE LETTER DENOTES FIXTURE TYPE. REFER TO LIGHTING FIXTURE SCHEDULE.
LOWERCASE LETTERS DENOTED LIGHTING ZONE.
CEILING WALL
LIGHTING FIXTURE
a
PANEL - CIRCUIT
LOWERCASE LETTERS DENOTED LIGHTING ZONE CONTROLS FOR ROOMS
UPPER CASE LETTER DENOTES FIXTURE TYPE
PANEL & CIRCUIT DESIGNATION
LIGHTING CONTROL PLAN SYMBOLS
NOTES: SUBSCRIPTS SHALL BE ADDED TO SYMBOL WHERE
APPLICABLE. "X" SUBSCRIPT AS INDICATED IN SCHEDULES.
XX
X
WALL MOUNTED ELECTRICAL SWITCH SYMBOL
WALL MOUNTED ELECTRICAL SWITCH SYMBOL (EMERGENCY)
CEILING MOUNTED ELECTRICAL SWITCH SYMBOL
CEILING MOUNTED ELECTRICAL SWITCH SYMBOL (EMERGENCY)
WALL MOUNTED ELECTRICAL LIGHT SWITCH SYMBOL
LIGHTING CONTROLS SYMBOL
SUBSCRIPTXXX
D WALL MOUNTED DIMMER SWITCH SYMBOL - SEE DETAIL 5/E-401 AND 6/E-401
WALL MOUNTED ELECTRICAL LIGHT SWITCH (3-WAY) SYMBOL
WALL MOUNTED ELECTRICAL LIGHT SWITCH (4-WAY) SYMBOL
30 x 42
G E
N
R
L
O
T
S
618-16-111
Project Title
V.A. MEDICAL CENTER
ONE VETERANS DRIVE
MINNEAPOLIS, MN 55417
REGISTRATION NUMBER:
Office of Facilities
Management Drawing Scale
Plot Scale
Drawing Title
Approved: Division Chief
Approved: Service Director
Building Number
Checked Drawn
Location
Date
Project No.
DRAWING NO.
o n e -e ig h th i n c f t
-q u rt r in re s
-h lf i n d n
TRUE NORTH
PLAN NORTH
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENING SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
I HEREBY CERTIFY THAT THIS PLAN,
SPECIFICATION OR REPORT WAS
PREPARED BY ME OR UNDER MY DIRECT
SUPERVISION AND THAT I AM A DULY
LICENSED PROFESSIONAL ENGINEER UNDER
THE LAWS OF THE STATE OF MINNESOTA
C U rs
\w ik w \D m ts
\3
B
F
.r v
/4
/2
:0
:4
P
M
As indicated
1322- E-001
BRC SPM
EXPAND OUTPATIENT MENTAL HEALTH
ELECTRICAL LEGEND AND ABBREVIATIONS
ELECTRICAL
05/05/2017 DWG. 78 OF 94
GENERAL NOTES
NOT TO SCLAEE-001
1 MOUNTING HEIGHT DETAIL
A. NOT ALL THE SYMBOLS USED IN THIS LEGEND ARE USED IN THIS SET
OF DRAWINGS.
B. REFER TO GROUNDING AND LIGHTNING PROTECTION PLANS FOR
ADDITIONAL SYMBOLS AND INFORMATION.
C. ADDITIONAL LEGENDS INCLUDE SYMBOLS AND INFORMATION
PROVIDED ON OTHER SHEETS THROUGHOUT THIS SET OF
DRAWINGS.
D. REFER TO EQUIPMENT PLANS FOR POWER TO HVAC, ELEVATORS,
PUMPS, FIRE ALRAM, AND OTHER DISCIPLINE COORDINATION.
E. ALL ELECTRICAL WORK TO BE PER NEC AND ALL LOCAL APPLICABLE
CODES AND ORDINANCES.
F. ALL CIRCUITS SHALL HAVE NEUTRAL (EXCEPT 3W, 3PH.), AND
GROUND CONDUCTORS AND THESE SHALL NOT BE SHARED BY
OTHER CIRCUITS. ALL SINGLE PHASE BRANCH CIRCUITS SHALL HAVE
A SEPARATE NEUTRAL. NEUTRALS SHALL NOT BE SHARED AS IN
MULTI-WIRE CIRCUITS. ALL GROUND CIRCUITS SHALL BE INSULATED
AND COLOR CODED GREEN. DOES NOT APPLY TO MODULAR
FURNITURE.
G. ALL MULTI-WIRE BRANCH CIRCUIT CONDUCTORS SHALL ORIGINATE
FROM THE SAME PANELBOARD, THE GROUNDED AND UNGROUNDED
CONDUCTORS SHALL BE GROUPED WITHIN THE PANELBOARD AND
THEY SHALL BE PROVIDED WITH A MEANS THAT WILL
SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED CONDUCTORS.
H. OPENINGS AROUND ELECTRICAL PENETRATIONS THROUGH FIRE
RESISTANT RATED WALLS, PARTITIONS, FLOOR OR CEILING SHALL
BE FIRE STOPPED TO MAINTAIN THE FIRE RESISTANCE RATING.
DESCRIPTION DATE
43914
05-05-17Brian R Crisp
XYZAABBCCDDEEFFGGHH
CL1J1-1 -1
NH1J1-1 -3
NH1J1-1 -7
NH1J1-1 -11
NH1J1-1 -17
NH1J1-1 -10
NH1J1-1 -13
NH1J1-1 -5
NH1J1/9
NH1J1-1 -4
NH1J1/15
NH1J1-1 -8
-<unnamed>
XR2
XR2 XR2 XR2
XR2 XR2
XR3
XR3 XR3
n i n n
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENING SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
PREPARED BY ME OR UNDER MY DIRECT
SUPERVISION AND THAT I AM A DULY
1/8" = 1'-0"
1322- ED110
LIGHTING DEMOLITION PLAN - LEVEL 1 AREA K
05/05/2017 DWG. 79 OF 94
1 LIGHTING DEMOLITION PLAN - LEVEL 1 AREA K
A. DRAWINGS INDICATE EXISTING CONDITIONS AS THEY WERE
INDICATED ON OWNER PROVIDED AS BUILT DRAWINGS AND SITE
VERIFICATION. ACTUAL CONDITIONS MAY VARY FROM THE
CONDITIONS INDICATED. THE CONTRACTOR IS RESPONSIBLE TO
FIELD VERIFY EXACT CONDITIONS PRIOR TO BID.
B. ITEMS SHOWN AS DASHED SHALL BE DEMOLISHED UNLESS
INDICATED OTHERWISE.
C. EXISTING CONDUIT PENETRATIONS AND ASSOCIATED BOXES INTO
INTERSTITIAL SPACE SHALL REMAIN IN PLACE FOR REUSE UNLESS
D. ALL EXISTING LIGHT FIXTURES SCHEDULED FOR REMOVAL SHALL
BE OFFERED TO OWNER FOR ATTIC STOCK. ANY FIXTURES
OWNER REFUSES SHALL BE DISPOSED OF BY CONTRACTOR.
E. SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR
DEMOLITION AND CONSTRUCTION. COORDINATE ALL DEMOLITION
WITH GENERAL CONTRACTOR.
F. DISCONNECT AND REMOVE ALL ELECTRICAL DEVICES AND LIGHT
FIXTURES IN AREAS SCHEDULED FOR DEMOLITION EXCEPT WHERE
NOTED OTHERWISE.
G. DISCONNECT AND REMOVE ALL ELECTRICAL DEVICES IN WALLS
SCHEDULED FOR DEMOLITION. WALL TO BE DEMOLISHED ARE
SHOWN DASHED ON DEMOLITION PLANS. DISCONNECT AND
REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST
REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS
NECESSARY FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING
DEVICES TO REMAIN. COORDINATE AND VERIFY REQUIREMENTS
WITH NEW WORK.
H. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY FOR
CONTINUITY OF ANY FEEDERS OR BRANCH CIRCUITS ORIGINATING
OUTSIDE THE DEMOLITION AREA THAT SERVES ANY ELECTRICAL
EQUIPMENT OR DEVICES TO REMAIN AFTER DEMOLITION. MODIFY
OR REPLACE AS REQUIRED.
I. DISCONNECT AND REMOVE ANY EXISTING ELECTRICAL DEVICES
AND BACKBOXES AS NECESSARY WHERE NEW WALL
CONSTRUCTION WILL INTERSECT AN EXISTING WALL. FURNISH AND
INSTALL CONDUIT AND WIRE AS REQUIRED FOR CONTINUITY OF
CIRCUIT.
J. PROPERLY DISPOSE OF HAZERDOUS WASTE, INCLUDING BUT NOT
LIMITED TO:
FLUORESCENT LAMPS
BALLASTS
RADIOACTIVE SELF LUMINOUS EXIT SIGNAGE
RADIOACTIVE IONIZATION TYPE SMOKE DETECTORS
REFER TO SPEC. SECTIONS 017419, 024100 AND 260500
K. REMOVE ALL EXPOSED ABANDON CONDUIT, INCLUDING CONDUIT
ABOVE ACCESSIBLE CEILINGS. CUT OFF CONDUIT FLUSH WITH
WALLS AND FLOORS. PATCH SURFACES.
L. EXISTING UNUSED OPEN BOXES SHALL BE FILLED, PATCHED AND
RECEIVE NEW FINISHES. COORDINATE WITH OTHER TRADES.
BID ALTERNATE
1. ALL EXISTING 2'X4' LIGHT FIXTURES IN CEILINGS THAT ARE NOT
SCHEDULED TO BE REMOVED SHALL BE DISCONNECTED AND
REPLACED WITH NEW TYPE "A" LED FIXTURES. EXISTING
SWITCHING SERVING THESE FIXTURES SHALL BE DISCONNECTED
AND REPLACED WITH NEW DIMMER SWITCH. IN ROOMS WHERE (2)
SWITCHES ARE REMOVED, PROVIDE SINGLE GANG MUD RING FOR
DIMMER SWITCH. PROVIDE NEW FACEPLATES AS REQUIRED.
KEYNOTES
1. DISCONNECT ELECTRICAL CONNECTION TO POLE MOUNTED LIGHT
FIXTURES FED FROM FLOOR. REMOVE ALL CONDUIT/WIRE BACK
TO SOURCE.
2. SALVAGE EXISTING CIRCUITING TO REFEED NEW CORRIDOR
LIGHTING.
W
NL1J1-1B -14,16,18
NL1J1-1B -8,10,12
NL1J1-1B -2,4,6
NL1J1-1A -2,4,6
NL1J1-2 -2,4,6
2 2
4 4
6 6
NL1J1-1B -20,22,24
10 10
8 10
NL1J1-1A -8,10,12
12 7
244141
NL1J1-1A -14,16,18
CL1J1-1 -20
CL1J1-1 -8,10
NL1J1-2 -8,10,12
23 8
CL1J1-1 -7
CL1J1-1 -2,4
CL1J1-1 -5
CL1J1-1 -15
CL1J1-1 -13
21 21
NL1J1-1B -19,21,23
CL1J1-6
CL1J1-9
NL1J1-2/15,17
NL1J1-2/11,13
NL1J1-2 -19
NL1J1-2 -24
26 26
26 35
NL1J1-1A -5
25 25 25
25 27
17 17
19 21
NL1J1-1B -3,5
NL1J1-1A -32
NL1J1-1A - 13
NL1J1-1A - 15,17
NL1J1-1A - 19,21,23
31NL1J1-1A - 37
36 28
28 30
42 42
NL1J1-1B -42
22 22
20 20
26 30
NL1J1-1A - 25,27,29
NL1J1-1A -37,39,41
NL1J1-1A -20,22,24
9 22
NL1J1-2 - 7,9
NL1J1-1A -31,33,35
NL1J1-1A -26,28,30
NL1J1-1B -13,15,17
NL1J1-1B -26,28,30
26 30
30 30
NL1J1-1B -25,27,29
NL1J1-1B -7,9,11
NL1J1-2 -14,16,18
NL1J1-2 -20,22
n i n n
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENING SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
PREPARED BY ME OR UNDER MY DIRECT
SUPERVISION AND THAT I AM A DULY
1322- ED210
POWER DEMOLITION PLAN - LEVEL 1 AREA K
05/05/2017 DWG. 80 OF 94
1 POWER DEMOLITION PLAN - LEVEL 1 AREA K
KEYED NOTES
1. DISCONNECT AND REMOVE DOOR OPENER, HARDWARE AND ALL
ASSOCIATED CONDUIT AND WIRE BACK TO SOURCE.
VERIFICATION. ACTUAL CONDITIONS MAY VARY FROM THE
B. ITEMS SHOWN AS DASHED SHALL BE DEMOLISHED UNLESS
C. EXISTING CONDUIT PENETRATIONS AND ASSOCIATED BOXES INTO
INTERSTITIAL SPACE SHALL REMAIN IN PLACE FOR REUSE UNLESS
D. ALL EXISTING LIGHT FIXTURES SCHEDULED FOR REMOVAL SHALL
BE OFFERED TO OWNER FOR ATTIC STOCK. ANY FIXTURES OWNER
REFUSES SHALL BE DISPOSED OF BY CONTRACTOR.
E. SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR
DEMOLITION AND CONSTRUCTION. COORDINATE ALL DEMOLITION
WITH GENERAL CONTRACTOR.
F. DISCONNECT AND REMOVE ALL ELECTRICAL DEVICES AND LIGHT
FIXTURES IN AREAS SCHEDULED FOR DEMOLITION EXCEPT WHERE
NOTED OTHERWISE.
G. DISCONNECT AND REMOVE ALL ELECTRICAL DEVICES IN WALLS
SCHEDULED FOR DEMOLITION. WALL TO BE DEMOLISHED ARE
SHOWN DASHED ON DEMOLITION PLANS. DISCONNECT AND
REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO LAST
REMAINING DEVICE. FURNISH AND INSTALL CONDUIT AND WIRE AS
NECESSARY FOR CONTINUITY OF CIRCUIT(S) TO ANY EXISTING
DEVICES TO REMAIN. COORDINATE AND VERIFY REQUIREMENTS
WITH NEW WORK.
H. FURNISH AND INSTALL CONDUIT AND WIRE AS NECESSARY FOR
CONTINUITY OF ANY FEEDERS OR BRANCH CIRCUITS ORIGINATING
OUTSIDE THE DEMOLITION AREA THAT SERVES ANY ELECTRICAL
EQUIPMENT OR DEVICES TO REMAIN AFTER DEMOLITION. MODIFY
OR REPLACE AS REQUIRED.
I. DISCONNECT AND REMOVE ANY EXISTING ELECTRICAL DEVICES
CONSTRUCTION WILL INTERSECT AN EXISTING WALL. FURNISH AND
INSTALL CONDUIT AND WIRE AS REQUIRED FOR CONTINUITY OF
CIRCUIT.
J. PROPERLY DISPOSE OF HAZERDOUS WASTE, INCLUDING BUT NOT
LIMITED TO:
FLUORESCENT LAMPS
BALLASTS
RADIOACTIVE SELF LUMINOUS EXIT SIGNAGE
RADIOACTIVE IONIZATION TYPE SMOKE DETECTORS
REFER TO SPEC. SECTIONS 017419, 024100 AND 260500
K. REMOVE ALL EXPOSED ABANDON CONDUIT, INCLUDING CONDUIT
L. EXISTING UNUSED OPEN BOXES SHALL BE FILLED, PATCHED AND
RECEIVE NEW FINISHES. COORDINATE WITH OTHER TRADES.
M. RECEPTACLES SCHEDULED FOR REMOVAL THAT ARE LOCATED IN
WALLS NOT SCHEDULED FOR DEMOLITION SHALL BE
DISCONNECTED AND REMOVED. EXISTING JUNCTION BOX AND
CONDUIT TO ABOVE CEILING SHALL REMAIN IN PLACE FOR REUSE.
REFER TO POWER PLAN E-210 FOR NEW CIRCUITING LAYOUT.
W
PA PA
PA
S SS
AV
V
WD WD
WD
N N
DB
DB DB DB
DB DB
DB DBDB
DB DB
DBDB DB
DB DBDBDB
DB DB DB DB DB DB DB DB DB
DB DB DB DB DB
DB DB DB DB
DBDB
n i n n
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENING SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
PREPARED BY ME OR UNDER MY DIRECT
SUPERVISION AND THAT I AM A DULY
:5
1322- ED310
TELECOMMUNICATIONS DEMOLITION PLAN - LEVEL 1
AREA K
05/05/2017 DWG. 81 OF 94
1 TELECOMMUNICATIONS DEMOLITION PLAN - LEVEL 1 AREA K
VERIFICATION. ACTUAL CONDITIONS MAY VARY FROM THE
B. EXISTING CONDUIT PENETRATIONS AND ASSOCIATED BOXES INTO
INTERSTITIAL SPACE SHALL REMAIN IN PLACE FOR REUSE.
C. ALL EXISTING VOICE, DATA AND DURESS CABLING SHALL BE
REMOVED BACK TO SOURCE. CONTRACTOR SHALL PROVIDE
BLANK FACEPLATE AT BACKBOXES LEFT ABANDONED ON WALLS
SCHEDULED TO REMAIN. CONTRACTOR MAY REUSE EXISTING
BOXES FOR NEW DEVICES. SEE E-310 FOR NEW WORK.
D. DISCONNECT AND REMOVE ANY EXISTING ELECTRICAL DEVICES
CONSTRUCTION WILL INTERSECT AN EXISTING WALL. FURNISH
AND INSTALL CONDUIT AND WIRE AS REQUIRED FOR CONTINUITY
OF CIRCUIT.
E. REMOVE ALL EXPOSED ABANDON CONDUIT, INCLUDING CONDUIT
F. ALL EXISTING REMOTE DURESS BUTTONS SHALL BE
DISCONNECTED AND SALVAGED FOR REINSTALLATION AT NEW
WORKSTATIONS. REMOVE ALL EXISTING DURESS SYSTEM
CABLING BACK TO SOURCE IN ROOM 1J-121B.
1. DISCONNECT AND SALVAGE EXISTING PA SPEAKER.
2. SECURE WIRELESS ACCESS POINT TO DECK AND PROTECT FROM
DAMAGE DURING CONSTRUCTION. REINSTALL IN CEILING AFTER
CONSTRUCTION IS COMPLETE.
NH1J1-1 -17
NH1J1-1 -10
NH1J1-1 -4
DDDDDDDDDD
D D D D D D D
D D D
DDD
DD
A-NL
XE
XE
C1
B B
B-NL
BB
B-NLB
B-NL B B
AA
C1 C1
A A A A
A A A A
XR2 XR2
XR2 XR2 XR2
A-NL A
NH1J1-1 -5
A A A
AAA
A A A
NH1J1-1 -12
NH1J1-1 -9
NH1J1-1 -15
1 1 1 z z z zz zz y y w w w w w w w w
LH1B2-1 / 5
A-NLAAA-NLAA
y
NL
NL NL
C2
C2D
1P-360
1P-309
1P-307
1P-305 1P-303
1P-219 1P-217
1P-215
1P-214
C1P-99
C1P-98
1P-212
1P-210
C1P-97
C1P-86
1P-361
1P-362
1P-312
1P-310
1P-314
C1P-92
1P-363
1P-364
1P-365
1P-366
1P-333 1P-326
1P-320
C1P-95
C1P-96
1P-208
1P-321
1P-328
1P-330
1P-334
1P-335
1P-367
1P-368
1P-369
1P-370
1P-336
C1P-90
1P-332
1P-324
1P-322
1P-323
C1P-93
C1P-94
1P-343
1P-342 1P-341
C1P-88
1P-345
1P-346
1P-347 1P-348
1P-344
1P-355
1P-353
1P-3511P-349
1P-373
1P-372
1P-371
C1P-91
C1P-102
1P-99
C1P-86A
1P-96
1P-375 S-10
1P-313 1P-300
1P-308
1P-311
1P-220 1P-218 1P-216
1P-2211P-2231P-225
1P-325
1P-327
1P-329
1P-331
1P-340
1P-254
1P-251 1P-250
1P-253 1P-252 1P-245
1P-2471P-249
1P-248
1P-246 1P-241
1P-243
1P-2631P-2651P-2671P-2691P-2711P-2731P-275
1P-276 1P-274 1P-272 1P-270 1P-268 1P-266 1P-264 1P-262 1P-260
1P-111
1P-261
1P-244
1P-242
1P-240
1P-213
1P-211
1P-209 1P-200
1P-202
1P-204
1P-203
1P-201
1P-103
1P-102
1P-104
1P-105 1P-106
1P-1081P-107
1P-1101P-109
1P-112
1P-205
1P-207
1P-101
1P-206 1P-100a
1P-100
C1P-104
C1P-100
C1P-105
C1P-104A
C1P-103A
C1P-103
C1P-98A
C1P-101
C1P-106
C1P-107
1P-374
1P-376
1P-242a
NH1J1-1 -19
G1
NH1J1-1 -1
NH1J1-1-6
NH1J1-1 -13
NH1B2-1 / 5
H
TYP
C2
NH1J1-1 -16
J1
J1J1
J1J1
K
J2
CL1J1-1 -26
n i n n
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENING SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
PREPARED BY ME OR UNDER MY DIRECT
SUPERVISION AND THAT I AM A DULY
1322- E-110
LIGHTING PLAN - LEVEL 1 AREA K
05/05/2017 DWG. 82 OF 94
1 LIGHTING PLAN - LEVEL 1 AREA K
A. EXISTING CONDUIT PENETRATIONS AND ASSOCIATED BOXES INTO
B. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING
ALL ELECTRICAL ITEMS SHOWN ON THE DRAWINGS.
C. ALL RECESSED LIGHT FIXTURES IN LAY-IN CEILINGS SHALL BE
INSTALLED WITH 6'-0" LONG FLEXIBLE METAL CONDUIT.
D. ALL MOUNTING HEIGHTS FOR LIGHT FIXTURES ARE TO THE BOTTOM
OF THE FIXTURE UNLESS INDICATED OTHERWISE.
E. SEE ARCHITECTURAL INTERIOR ELEVATIONS FOR MOUNING
HEIGHTS OF WALL MOUNTED INTERIOR LIGHT FIXTURES.
F. CIRCUIT NUMBERS AT DEVICES CORRESPOND TO PANELBOARD
BREAKERS (SEE PANELBOARD SCHEDULS). BRANCH CIRCUITS
SHALL BE SIZED ACCORDING TO THE CIRCUIT BREAKER RATING,
UNLESS INDICATED OTHERWISE ON THE ELECTRICAL EQUIPMENT
SCHEDULE.
G. USE #10 AWG CONDUCTORS FOR 20 AMPRE, 277 VOLT BRANCH
CIRCUITS LONGER THAN 175 FEET, UNLESS SPECIFICALLY
INDICATED OTHERWISE. THIS SHALL BE REQUIRED FOR THE
ENTIRE LENGTH OF THE CIRCUIT
BID ALTERNATE
1. ALL EXISTING 2'X4' LIGHT FIXTURES IN CEILINGS THAT ARE NOT
SCHEDULED TO BE REMOVED SHALL BE DISCONNECTED AND
REPLACED WITH NEW TYPE "A" LED FIXTURES. EXISTING
SWITCHING SERVING THESE FIXTURES SHALL BE DISCONNECTED
AND REPLACED WITH NEW DIMMER SWITCH. IN ROOMS WHERE
(2) SWITCHES ARE REMOVED, PROVIDE SINGLE GANG MUD RING
FOR DIMMER SWITCH. PROVIDE NEW FACEPLATES AS REQUIRED.
1. INSTALL SALVAGED 2-LAMP LIGHT FIXTURE AND CONNECT
TO EXISTING CORRIDOR CIRCUIT/SWITCHING OR NIGHT
LIGHT CIRCUIT AS INDICATED.
2. CONNECT NEW FIXTURES TO EXISTING CORRIDOR
LIGHTING CIRCUIT.
3. CONNECT NEW EXIT LIGHTS AND NL FIXTURES TO EXISTING
EXITLIGHT/ NIGHT LIGHT CIRCUIT(S).
4. PROVIDE NEW PENETRATION INTO INTERSTITIAL SPACE.
REFERENCE DETAIL 11/E-500.
5. PROVIDE LUTRON 0-10V DIMMING SWITCH FOR LED ARRAY.
REFER TO DETAIL 8/E-402 AND 9/E-402 AND ARCHITECTURAL
SHEETS FOR MORE INFORMATION.
F F-NL F
FF F
F-NL
F F
F F-NL
FF
F-NL
NH1J1-1 -2
LH1B2-1 / 20,22
*20 (EXIT LIGHTS)
*22 (NL)
2 2 2 n i n n
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENING SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
PREPARED BY ME OR UNDER MY DIRECT
SUPERVISION AND THAT I AM A DULY
1322- E-115
LIGHTING PLAN - LEVEL 1 INTERSTITIAL AREA K
05/05/2017 DWG. 83 OF 94
1 LIGHTING PLAN - LEVEL 1 INTERSTITIAL AREA K
C. ALL RECESSED LIGHT FIXTURES IN LAY-IN CEILINGS SHALL BE
INSTALLED WITH 6'-0" LONG FLEXIBLE METAL CONDUIT.
D. ALL MOUNTING HEIGHTS FOR LIGHT FIXTURES ARE TO THE BOTTOM
OF THE FIXTURE UNLESS INDICATED OTHERWISE.
E. SEE ARCHITECTURAL INTERIOR ELEVATIONS FOR MOUNING
HEIGHTS OF WALL MOUNTED INTERIOR LIGHT FIXTURES.
SHALL BE SIZED ACCORDING TO THE CIRCUIT BREAKER RATING,
G. USE #10 AWG CONDUCTORS FOR 20 AMPRE, 277 VOLT BRANCH
INDICATED OTHERWISE. THIS SHALL BE REQUIRED FOR THE
ENTIRE LENGTH OF THE CIRCUIT
1. CONNECT FIXTURE TO EXISTING CIRCUITING/SWITCHING.
2. PROVIDE NEW 4-WAY SWITCH AT EXISTING DOOR. PROVIDE ALL
CONDUIT AND WIRING REQUIRED TO OPERATE WITH EXISTING 3-
WAY SWITCH LOCATIONS.
BRISCH-CRAMER
WAHMANHOLM
PERRY
MONTALO
LESKELA
POWERS
HERMANSEN
HESS
HURWITZ
YUE
MHI
ANM
TRUMBULL
SMITH
ROBINSON-
ANDREW
MOSHER
SERPOSS
SCHMITT
SPRING
VARICAT
FRANSEN
ERICKSON-
PRADO
RODMAN
ROBERTS
HEGEMAN
DAHL
TEAM A
FELLOW
ATKINSON
BERNT
ACKERMAN
TESTING
VINE
MHI MD
24x48
24x60
BBFFF
COMBO
t A dj
24x72
36 36
BBF
BC
36/4
Ht Adj x7 x6
BBF FF
60 TB24 TB
36 TB
36 TB36 TB
48 TB24 TB
48 TB
48 TB 24 TB
36 TB 36 TB
x4
48 B
24 TB
48B
FF BBF
FFBBF
slide door closer to corner
VF
30/4
NIENOW
CBSST
x
NIC
WAGNER
MEYERS
McCarthy
ALLEN
GALLARDO
LICHTSINN
REDDING
STINSON
CURRYC
VOLLER
McCallum
PISCHKE
CHUICK
KOFFEL
MUELLER
COLUMN?
KALER
NIC
24x36 24x36 24x36 24x36 24x36
Stg Cab
36 TB 36 TB 36 TB 36 TB 36 TB
NEMSCHOFF
2750-10
-1
0 N
0N
24x36
Students
Office
Office lockers 24x72 bi hu b biz hub
24x42
15x42
24x4824x42 x9
Judy
60 TB
4'-6"
7'-9"
4' 3"
X
TA
LE
x
SCALE
4'-6" x x x x
24x60 24x60
24x6024x60 x x x biz hub
24x60 24x48
24x7824x78
COAT RACK
A T
R A x x x x x x x seated/ADA standing height
10 Lockers mailboxes mobile ob ile mobile obile
DROGEMULLER
Furniture in Alcoves - CODE:
- furn cannot create less than 6' clear in main corridor
- furn must be bolted down
J
NL1J1-1B -14,16,18
NL1J1-1B -20,22,24
NL1J1-1A -8,10,12
CL1J1-1 -20
CL1J1-1 -8,10
CL1J1-1 -7
CL1J1-1 -2,4
CL1J1-1 -5
CL1J1-1 -15
CL1J1-1 -13
21 21
NL1J1-2 -19
NL1J1-2 -24
E-400
NL1J1-1B -42
1P-360
1P-309 1P-307 1P-305
1P-303 1P-219
1P-217
1P-362
1P-312
1P-333 1P-326
1P-332 1P-324
1P-342
1P-341
1P-347
1P-348
1P-3531P-3511P-349
1P-220 1P-218
1P-216
1P-221
1P-223
1P-225
1P-253
1P-252 1P-245
1P-247 1P-249
1P-2631P-2651P-2671P-2691P-2711P-273 1P-275
1P-276 1P-274 1P-272 1P-270 1P-268 1P-266 1P-264 1P-262 1P-260
1P-111
1P-209 1P-200
1P-205 1P-207
1P-206 1P-100a
NL1J1-1A -13,15,17
NL1J1-1A -7,9,11
NL1J1-1A -25,27,29
NL1J1-1A -19,21,23
31 31
33 33 33
35 35 35
28 28
NL1J1-1B - 19,21,23
7 7
25 25 25
23 23
NL1J1-2 -21,23
NL1J1-2 -7,9,11
CL1J1-1 -25
NL1J1-3 - 1,3,5 NL1J1-3 - 2,4,6 NL1J1-3 - 7,9,11
NL1J1-3 - 8,10,12
3 3 3
3 3
NL1J1-3 - 13,15,17
NL1J1-3 - 14,16,18
NL1J1-3 - 19,21,23
NL1J1-3 - 20,22,24
NL1J1-3 - 25,27,29
7 7
1 1
1 1
11 10
13 13
C1P-108
NL1J1-3 - 26,28,30
2828262828
30 30 30
CL1J1-1-22,24
CL1J1-1 -6
n i n n
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENING SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
PREPARED BY ME OR UNDER MY DIRECT
SUPERVISION AND THAT I AM A DULY
1322- E-210
POWER PLAN - LEVEL 1 AREA K
05/05/2017 DWG. 84 OF 94
1 POWER PLAN - LEVEL 1 AREA K
C. WHERE CONNECTED TO 20A BRANCH CIRCUIT SUPPLYING AN
INDIVIDUAL RECEPTACLE, THE RECEPTACLE SHALL BE RATED AT
20A.
D. COORDINATE LOCATIONS OF DEVICES WITH ARCHITECTURAL
PLANS, ELEVATIONS AND DETAILS. ARCHITECTURAL PLANS,
ELEVATIONS AND DETAILS TAKE PRECEDENCE OVER LOCATIONS
SHOWN ON ELECTRICAL DRAWINGS. SEE ARCHITECTURAL
ELEVATIONS FOR LOCATIONS OF ELECTRICAL DEVICES.
E. VERIFY LOCATIONS AND ROUGH-IN REQUIREMENTS OF ALL OWNER
FURNISHED EQUIPMENT PRIOR TO ROUGH-IN.
SHALL BE SIZED ACCORDING TO THE CIRCUIT BREAKER RATING,
G. USE #10 AWG CONDUCTORS FOR 20 AMPRE, 120 VOLT BRANCH
INDICATED OTHERWISE. THIS SHALL BE REQUIRED FOR THE ENTIRE
LENGTH OF THE CIRCUIT
1. PROVIDE POWER TO POWERED DOOR ACTUATOR. CONTRACTOR
SHALL PROVIDE ALL REQUIRED CONDUIT AND CABLING BETWEEN
DOOR ACTUATOR AND ASSOCAITED BUTTON(S). COORDINATE
INSTALLATION WITH DOOR HARDWARE PROVIDER.
2. ABANDON EXISTING PENESTRATION INTO INTERSTITAL SPACE.
CAP AS REQUIRED PER SPECIFICATIONS.
3. PROVIDE NEW PENETRATION INTO INTERSTITIAL SPACE.
REFERENCE DETAIL 11/E-500.
4. PROVIDE FLEXIBLE WHIP CONNECTION TO SYSTEMS FURNITURE.
COORDNATE WIRING REQUIREMENTS WITH FURNITURE SUPPLIER.
5. SEE ARCHITECTURAL ELEVATION FOR RECEPTACLE HEIGHTS
ASSOCIATED WITH MICROWAVES, REFRIGERATORS AND
COUNTER RECEPTACLE.
6. PROVIDE ELECTRICAL CONNECTION TO DRIVERS FOR LED ARRAY.
REFER TO DETAIL 8/E-402 AND 9/E-402 FOR WIRING INFORMATION.
7. FINAL LOCATION OF CRASH CART RECEPTACLE DETERMINED IN
FIELD BY OWNER.
8. PROVIDE J-BOX, 120VAC CIRCUIT, AND 24VDC POWER SUPPLY
FOR MAGNETIC DOOR HOLD-OPEN. REF. SPECIFICATION 087100.
COORDINATE WITH GENERAL CONTRACTOR. MAKE FINAL
CONNECTIONS.
9. PROVIDE NEW CONDUCTORS FROM PANEL CL1J1-1 FOR DOOR
HOLD-OPENS. SEE SHEE E-215.
E-500
NL1J1-1B -14,16,18 NL1B1-1B -20,22,24
NL1J1-1A - 8,10,12
CL1J1-1 -2,4,6
NL1J1-1B - 19,21,23
NL1J1-1A -25,27,29
NL1J1-1A -37
NL1J1-1A -13
NL1J1-1A -15,17
NL1J1-1A -19,21,23
CL1J1-1 -3
NH1J1-1 -5NH1J1-1 -19
NH1J1-1 -12
NH1J1-1 -10 NH1J1-1 -13
NH1J1-1 -15
NH1J1-1 -9
NH1J1-1 -16
NH1J1-1 -1
NL1J1-3 - 1,3,5 NL1J1-3 - 2,4,6 NL1J1-3 - 7,9,11 NL1J1-3 - 8,10,12 NL1J1-3 - 13,15,17
NL1J1-3 - 14,16,18
NL1J1-3 - 19,21,23
NL1J1-3 - 25,27,29
CL1J1-1 -25
NH1J1-1-6
NL1J1-3 - 20,22,24
NL1J1-3 - 26,28,30
NL1J1-1A -13,15,17
NL1J1-1A-7,9,11
NL1J1-2 -7,9,11
NL1J1-2 -21,23
CL1J1-1-22,24
CL1J1-1-26
n i n n
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENING SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
PREPARED BY ME OR UNDER MY DIRECT
SUPERVISION AND THAT I AM A DULY
:2
1322- E-215
POWER PLAN - LEVEL 1 INTERSTITIAL AREA K
05/05/2017 DWG. 85 OF 94
1 POWER PLAN - LEVEL 1 INTERSTITIAL - AREA K
C. WHERE CONNECTED TO 20A BRANCH CIRCUIT SUPPLYING AN
INDIVIDUAL RECEPTACLE, THE RECEPTACLE SHALL BE RATED AT
20A.
D. COORDINATE LOCATIONS OF DEVICES WITH ARCHITECTURAL
PLANS, ELEVATIONS AND DETAILS. ARCHITECTURAL PLANS,
ELEVATIONS AND DETAILS TAKE PRECEDENCE OVER LOCATIONS
SHOWN ON ELECTRICAL DRAWINGS. SEE ARCHITECTURAL
ELEVATIONS FOR LOCATIONS OF ELECTRICAL DEVICES.
E. VERIFY LOCATIONS AND ROUGH-IN REQUIREMENTS OF ALL OWNER
FURNISHED EQUIPMENT PRIOR TO ROUGH-IN.
SHALL BE SIZED ACCORDING TO THE CIRCUIT BREAKER RATING,
G. USE #10 AWG CONDUCTORS FOR 20 AMPRE, 120 VOLT BRANCH
INDICATED OTHERWISE. THIS SHALL BE REQUIRED FOR THE ENTIRE
LENGTH OF THE CIRCUIT
1. EXTEND EXISTING 4" X 4" WIREWAY "NH1J1-1" FROM THIS
LOCATION. REFER TO ELEVATION DETAILS ON E-500 FOR MORE
INFORMATION.
2. EXTEND EXISTING 4" X 4" WIREWAY "SIGNAL" FROM THIS
LOCATION. REFER TO ELEVATION DETAILS ON E-500 FOR MORE
3. PROVIDE NEW 4" X 4" WIREWAY "NL1J1-3". ROUTE FROM PANEL
"NL1J1-3" FOUND IN ROOM 1P-96 INTO INTERSTITIAL SPACE.
REFER TO ELEVATION DETAILS ON E-500 FOR MORE
4. PROVIDE NEW CIRCUIT CONDUCTORS (CIRCUIT #6) FOR DOOR
HOLD-OPENS. SEE SHEET E-210.
ES
D D
D D D D D D D D
DDDD
D DD
D DD DD
DDD D
D D DD
WD WD
CR
DN
ND
NC
SB
2 2 2 2
D 2
2 D
2 D
2 2 22
2 2 2
2 2 3 2 2 2
2D
2 6
2 22
5 6
TYP.
1P-360 1P-309 1P-307
1P-305 1P-303 1P-219
1P-217
1P-362 1P-312
1P-333 1P-326
1P-332 1P-324
1P-342
1P-341
1P-347 1P-348
1P-3531P-3511P-349
1P-220 1P-218 1P-216
1P-2211P-2231P-225
1P-253 1P-252 1P-245
1P-2471P-249
1P-2631P-2651P-2671P-269 1P-2711P-2731P-275
1P-276 1P-274 1P-272 1P-270 1P-268 1P-266 1P-264 1P-262 1P-260 1P-111
1P-209
1P-200
1P-205 1P-207
1P-206
1P-100a
11 11
C1P-109
C1P-108
3 13 n i n n
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENING SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
PREPARED BY ME OR UNDER MY DIRECT
SUPERVISION AND THAT I AM A DULY
:1
1322- E-310
TELECOMMUNICATIONS PLAN - LEVEL 1 AREA K
05/05/2017 DWG. 86 OF 94
1 TELECOMMUNICATIONS PLAN - LEVEL 1 AREA K
B. LECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING
C. MAXIMUM NUMBER OF OF 4 INFORMATION OUTLET LOCATIONS PER
CONDUIT HOMERUN TO MDF OR IDF ID PERMITTED. CONDUIT
SHALL BE SIZED AS FOLLOWS:
1 INFORMATION OUTLET LOCATIONS: 1"
2 INFORMATION OUTLET LOCATIONS: 1"
3 INFORMATION OUTLET LOCATIONS: 1-1/4"
4 INFORMATION OUTLET LOCATIONS: 1-1/2"
D. INSTALL CONDUIT WITH NO MORE THAN (2) 90 DEGREE BENDS
BETWEEN PULLBOXES AND NO MORE THAN 100'-0" BETWEEN
PULLBOXES. PULLBOXES SHALL BE INSTALLED FOR STRAIGHT
THROUGH PULLS ONLY.
E. INSTALL ALL WIRING AND CABLES IN CONDUIT AND WIREWAYS IN
INTERSTITIAL SPACE ABOVE. REFER TO INTERSTITIAL SPACE
ELECTRICAL PLAN FOR WIREWAY LOCATIONS.
F. OBTAIN SALVAGED PRIVATE WIRELESS ACCESS POINT DEVICES
FROM DVA. INSTALL IN LOCATIONS WITHIN 2'-0" OF DVA MARKINGS
INDICATED PRIOR TO REMOVAL.
G. REINSTALL SPEAKERS SALVAGED FROM DEMOLITION AND
RECONNECT TO EXISTING PUBLIC ADDRESS ZONES.
1. INSTALL SALVAGED PA SPEAKER. (TYPICAL OF 4). RECONNEC TO
EXISTING PA SPEAKER ZONE.
2. REINSTALL SALVAGED WIRELESS ACCESS POINT IN CEILING.
3. PROVIDE NEW PA SPEAKER TO MATCH EXISTING. CONNECT TO
EXISTING PA SPEAKER ZONE SERVING AREA K.
4. PROVIDE NEW NURSE CALL TOILET STATION WHERE ORIGNAL WAS
REMOVED.
5. PROVIDE NEW NURSE CALL DOME LIGHT WHERE ORIGNAL WAS
REMOVED.
6. PROVIDE NEW DURESS BUTTON. SEE DETAIL 2/E-401.
7. INSTALL SALVAGED DESK-MOUNTED DURESS BUTTON. PROVIDE
NEW BUTTON AS NECESSARY. REFER TO DETAIL 3/E-401.
8. PROVIDE NEW CARD READER/KEYPAD. SEE DETAIL 4/E-401 FOR
BOX/CONDUIT/CABLING REQUIREMENTS.
9. PROVIDE 2-GANG J-BOX WITH 1" CONDUIT STUBED TO ABOVE
CEILING. SEE DETAIL 8/E-401 FOR WIRING DIAGRAM.
10. PROVIDE CEILING MOUNTED SPEAKER FOR RECEPTION AREA
MUSIC SYSTEM. MANUFACTURER/MODEL: YAMAHA # VXC4W OR
APPROVED EQUAL. SPEAKERS SHALL BE WIRED BACK TO J-BOX
REFERENCED BY KEYNOTE #9. SEE DETAIL 8/E-401 FOR WIRING
DIAGRAM.
11. PROVIDE NEW PENETRATION INTO INTERSTITIAL FOR ROUTING OF
NEW CAT 6A CABLING. REFER TO DETAIL 7/E-401 FOR CONDUIT
REQUIREMENTS. ALL CABLING ROUTED THROUGH PENETRATION
MUST TERMINATE AT A DEVICE WITHIN A 25'-0" (MAXIMUM) RADIUS
OF PENETRATION AND BE RUN IN A PLAN N/S/E/W CONFIGURATION
ABOVE CEILING TO EACH DEVICE. NO ANGLES WILL BE
PERMITTED. CONDUIT PENETRATIONS ARE SHOWN FOR
REFERENCE ONLY. PROVIDE SIZES AND QUANITITIES AS
REQUIRED FOR INSTALLATION. COORDINATE FINAL LOCATIONS IN
THE FIELD WITH OTHER TRADES.
12. SMARTBOARD (PROVIDED BY OTHERS). E.C. TO PROVIDE ROUGH-
IN BOXES AND CONDUIT FOR A/V CABLING. REFER TO DETAIL 7/E-
402 ROUGH-IN REQUIREMENTS.
13. PROVIDE 2-GANG J-BOX AT 66" A.F.F WITH (2) 1" CONDUITS TO
INTERSTITIAL SPACE CABLE TRAY. TV, MOUNT AND CABLING
SHALL BE PROVIDED BY OWNER.
6 7 n i n n
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENING SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
PREPARED BY ME OR UNDER MY DIRECT
SUPERVISION AND THAT I AM A DULY
:1
1322- E-315
TELECOMMUNICATIONS PLAN - LEVEL 1 INTERSTITIAL
AREA K
05/05/2017 DWG. 87 OF 94
1 TELECOMMUNICATIONS PLAN - LEVEL 1 INTERSTITIAL - AREA K
1. PROVIDE NEW 24" WIDE X 6" TALL BASKET TRAY.
2. PROVIDE TRANSITION TO 18" WIDE X 4" TALL BASKET TRAY.
3. PROVIDE 18" WIDE X 4" TALL BASKET TRAY.
4. PROVIDE TRANSITION TO 12" WIDE X 4" TALL BASKET TRAY.
5. PROVIDE 12" WIDE X 4" TALL BASKET TRAY.
6. PROVIDE TRANSITION TO 8" WIDE X 4" TALL BASKET TRAY.
7. PROVIDE 8" WIDE X 4" TALL BASKET TRAY.
8. PROVIDE WATERFALL BASKET TRAY TRANSITION INTO IT
CLOSET 1J-110. UTILIZE EXISTING 8"X8" SLEEVE THROUGH
INTERSTITIAL FLOOR TO ROUTE NEW CABLING INTO IT CLOSET.
C. MAXIMUM NUMBER OF 4 INFORMATION OUTLET LOCATIONS PER
CONDUIT HOMERUN TO MDF OR IDF ID PERMITTED. CONDUIT
SHALL BE SIZED AS FOLLOWS:
1 INFORMATION OUTLET LOCATIONS: 1"
2 INFORMATION OUTLET LOCATIONS: 1"
3 INFORMATION OUTLET LOCATIONS: 1-1/4"
4 INFORMATION OUTLET LOCATIONS: 1-1/2"
D. INSTALL CONDUIT WITH NO MORE THAN (2) 90 DEGREE BENDS
BETWEEN PULLBOXES AND NO MORE THAN 100'-0" BETWEEN
PULLBOXES. PULLBOXES SHALL BE INSTALLED FOR STRAIGHT
THROUGH PULLS ONLY.
E. INSTALL ALL WIRING AND CABLES IN CONDUIT AND WIREWAYS IN
INTERSTITIAL SPACE ABOVE. REFER TO INTERSTITIAL SPACE
ELECTRICAL PLAN FOR WIREWAY LOCATIONS.
F. OBTAIN SALVAGED PRIVATE WIRELESS ACCESS POINT DEVICES
FROM DVA. INSTALL IN LOCATIONS WITHIN 2'-0" OF DVA MARKINGS
INDICATED PRIOR TO REMOVAL.
G. REINSTALL SPEAKERS SALVAGED FROM DEMOLITION AND
RECONNECT TO EXISTING PUBLIC ADDRESS ZONES.
H. REFER TO DETAIL 7/E-401 FOR INSTALLATION OF BASKET TRAY.
VFD
VFD VFD VFD VFD
HH
NH1J1-1
NT1J1-1
NL1J1-1B
NL1J1-1A
NL1J1-2
CL1J1-1 NL1J1-3
NT1J1-3
LL1J1-1
NT1J1-2
1 2
NEW COMMUNICATION DEVICES IN
THIS AREA SHALL BE ROUTED TO
DATA CLOSET 1P-375
NEW COMMUNICATION DEVICES IN
THIS AREA SHALL BE ROUTED TO
DATA CLOSET 1P-376
HH
7 6
EEFFGGHH
EXISTING
SUBSTATION #6
PP1J2-1 -37,39,41
PP1J2-1 -2,4,6
PP1J2-1 -38,40,42
PP1J2-1 -31,33,35 PP1J2-1 -32,34,36
EE
SECURITY
PANEL
PP1J2-1
SEC. 1 SEC. 2 SEC. 3
ROOM 1P-96
EXISTING SUBSTATION #6
#2 CU
GND
ROOM 1J121C
TRANSFORMER
NT1J1-3
75KVA
480V~208Y/120
NL1J1-3
208V/120
CL1J1-1
208V/120
100A DISC. SWITCH IN
NEMA 1 ENCLOSURE
1-1/4" CONDUIT W/ (3) #1 & (1) #8 GND.
1-1/4" CONDUIT W/ (3) #1 & (1) #8 GND.
2-1/2" CONDUIT W/ (4) #4/0 & (1) #2 GND.
EXISTING FEEDER TO REMAIN
PROVIDE
EXOTHERMIC
WELD TO NEAREST
BUILDING STEEL
PER NEC
SEE KEYNOTE #1
ROOM 1J-121 ROOM 1J-121B
480V
20HP
1" EMT C.
W/ (3) #8 &
(1) #10 GND.
PP1J2-1
1" EMT C.
W/ (3) #8 &
(1) #10 GND.
10HP
10HP
3/4" EMT C. W/ (3) #12 & (1) #12 GND.
70-RF-8 70-SF-15(1) 70-SF-15(2) 70-SF-15(3) 70-SF-15(4)
n i n n
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENING SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
PREPARED BY ME OR UNDER MY DIRECT
SUPERVISION AND THAT I AM A DULY
:2
As indicated
1322- E-400
ENLARGED PLANS AND DETAILS
05/05/2017 DWG. 88 OF 94
1/4" = 1'-0"
3 ENLARGED ELECTRICAL PLAN - 1P-96
1" = 20'-0"
1 OVERALL ELECTRICAL PLAN - AREA K/AREA J
4 ENLARGED ELECTRICAL PLAN - 1P-375/1P-376
2 ENLARGED ELECTRICAL PLAN - 1J-121/1J-121C
5 ENLARGED ELECTRICAL PLAN - 1J-121A/1J-121B
1. REPLACE EXISTING 24 POLE ELECTRICAL PANEL "CL1J1-1" WITH
NEW 42 POLE ELECTRCIAL PANEL. ALL LOADS SHALL BE
DISCONNECTED FROM EXISTING PANEL AND REFED TO NEW PANEL.
REFER TO ONE-LINE DIAGRAM, PANEL SCHEDULE AND
SPECIFICATIONS FOR NEW PANEL REQUIREMENTS.
2. PROVIDE NEW ELECTRICAL PANEL NL1J1-3. REFER TO ONE-LINE
DIAGRAM 7/E-400, PANEL SCHEDULE AND SPECIFICATIONS FOR
ELECTRICAL PANEL REQUIREMENTS.
3. PROVIDE NEW 4" X 4" WIREWAY FROM TOP OF NEW ELECTRICAL
PANEL NL1J1-3, UP THROUGH CEILING, INTO THE INTERSTITIAL
SPACE. REFER TO SHEET E-215 FOR CONTINUATION OF WIREWAY
ROUTING.
4. PROVIDE NEW 75KVA TRANSFORMER NT1J1-3. REFER TO ONE-LINE
DIAGRAM 7/E-400 FOR TRANSFORMER REQUIREMENTS.
5. PROVIDE NEW 100A DISCONNECT SWITCH. REFER TO ONE-LINE
DIAGRAM 7/E-400 AND SPECIFICATIONS FOR DISCONNECT
REQUIREMENTS.
6. EXISTING COMMUNICATIONS RACK IN CLOSET 1P-376. REFER TO
DETAIL 1/E-400 FOR COMMUNICATIONS CABLING ROUTED TO THIS
CLOSET.
7. EXISTING COMMUNICATIONS RACK IN CLOSET 1P-375. REFER TO
DETAIL 1/E-400 FOR COMMUNICATIONS CABLING ROUTED TO THIS
CLOSET.
8. EXISTING NURSE CALL EQUIPMENT PANEL IS LOCATED IN THIS
ROOM. ALL NEW NURSE CALL CABLING SHALL BE ROUTED TO THIS
ROOM.
9. EXISTING SECURITY/DURESS SYSTEM EQUIPMENT PANEL IS
LOCATED IN THIS ROOM. ALL NEW SECUIRTY/DURESS CABLING
SHALL BE ROUTED TO THIS ROOM.
10. CONNECT NEW FEEDER TO SPARE 100A CIRCUIT BREAKER IN
SUBSTATION #6. PROVIDE NEW LABEL FOR CIRCUIT BREAKER PER
SPECIFICATIONS.
11. PROVIDE NEW FEEDER FROM SUBSTATION #6 TO FEED NEW
TRANSFORMER NT1J1-3. REFERENCE ELECTRICAL ONE-LINE
DIAGRAM 7/E-400.
12. DISCONNECT EXISTING ELECTRICAL CONNECTION TO
VFD/DISCONNECT SWITCH FOR SUPPLY FAN "70-SF-15". EXISTING
VFD/DISCONNECT SWITCH SHALL BE TURNED OVER TO OWNER.
13. PROVIDE VFD CONTROLLER FOR EACH SUPPLY FAN MOTOR. SEE
DETAIL 6/E-400 FOR WIRING REQUIREMENTS.
14. DISCONNECT EXISTING ELECTRICAL CONNECTION TO
VFD/DISCONNECT SWITCH FOR RETURN FAN "70-RF-8". REMOVE
WIRING BACK TO SOURCE. EXISTING CONDUIT SHALL BE REUSED.
EXISTING VFD/DISCONNECT SWITCH SHALL BE TURNED OVER TO
OWNER.
15. PROVIDE VFD CONTROLLER FOR NEW RETURN FAN MOTOR "70-RF-
8". SEE DETAIL 6/E-400 FOR WIRING REQUIREMENTS.
12" = 1'-0"
7 ELECTRICAL ONE-LINE DIAGRAM
12" = 1'-0"
6 ONE-LINE DIAGRAM - SUPPLY FAN ARRAY
A .F .F
1" CONDUIT WITH PULLSTRING
TO SECURITY PANEL. ROUTE
SECURITY CABLING FROM
KEYPAD/PROX CARD READER.
6" x 6" x 4" JUNCTION BOX WITH
BLANK COVER. SURFACE
MOUNT ABOVE CEILING ON
SECURE SIDE OF WALL.
3/4" CONDUIT WITH PULLSTRING
FOR POWER TRANSFER DEVICE
IF USED. COORDINATE WITH
DOOR HARDWARE PROVIDER.
ELECTRIC STRIKE.
COORDINATE WITH DOOR
HARDWARE PROVIDER. WIRE
KEYPAD/PROX CARD READER
TO ELECTRIC STRIKE.
SECURE
SIDE
FINISH FLOOR
CEILING
3/4" CONDUIT WITH PULLSTRING
4 11/16" x 4 11/16" x 2 1/8" Dp.
JUNCTION BOX WITH SINGLE GANG
MUD RING. MOUNT RECESSED IN
WALL ON NON-SECURE SIDE OF
WALL FOR INSTALLATION OF
KEYPAD/PROXIMITY CARD READER.
1" CONDUIT WITH PULLSTRING. ALL
CONDUITS CONCEALED IN WALL
WHEN BELOW CEILING, LOCATED
ON SECURE SIDE OF WALL (TYP).
CEILING
2" x 4" x 2 1/8" DEEP JUNCTION BOX
FLUSH MOUNTED ON SECURE SIDE
OF WALL FOR REQUEST-TO-EXIT
SENSOR. LAY BOX ON IT'S SIDE.
NON-SECURE
SIDE
J-BOX
3/4" CONDUIT TO
SECURITY SECURITY
DEVICE IT CLOSET
CEILING AS
SCHEDULED
CONDUIT LOCATED
IN WALL
DURESS
BUTTON
2X4 FLUSH MOUNTED J-BOX
WITH FACEPLATE
J-BOX
3/4" CONDUIT TO
SECURITY DEVICE IT
CLOSET
CEILING AS
SCHEDULED
CONDUIT LOCATED
IN WALL
DURESS
BUTTON
2X4 FLUSH MOUNTED J-BOX
WITH RJ-45 AND FACEPLATE
NOTE:
LOCATION TO BE COORDINATED WITH FURNITURE
LOCATION AND/OR WORKSTATION CONFIGURATION.
PROVIDE ACCESS CONTROL CABLE FROM SECURITY DEVICES TO PACS
LENEL 1300 CONTROL BOARDS LOCATED IN SECURITY IT CLOSET (1J-121B).
REFER TO SPECIFICATIONS FOR CABLE REQUIREMENTS.
TO MAGNETIC LOCK (GRAY JACKET) 4 CONDUCTOR 18 AWG.
TO CARD READER (ORANGE JACKET) 3 PAIR 22 AWG.
TO DOOR CONTACTS (WHITE JACKET) 2 CONDUCTOR, 22 AWG.
TO REQUEST TO EXIT (BLUE JACKET) 4 CONDUCTOR 22 AWG.
NOTES:
ALL NEW CARD READER/KEY PADS AND REQUEST-TO-EXIT DEVICE BACK
BOXES SHALL BE MOUNTED NO MORE THAN 5'-0" FROM DOOR FRAME, NO
LESS THAN 8" UNLESS MOUNTED TO THE DOOR MULLION OR FRAME.
DOOR SWITCH (BALANCED MAGNETIC TYPE)
MAG LOCK
REQUEST-TO-EXIT PUSH BUTTON
DOOR STOP
REQUEST-TO-EXIT MOTION SENSOR
NON-SECURE SIDE
SECURE SIDE
CARD READER
DOOR STOP
MAG LOCK
DOOR SWITCH (BALANCED
MAGNETIC TYPE)
RED
RED/WHITE
GROUND
DIMMER SWITCH
0-10V
120-277 V~ 50/60 Hz
BLACKLINE/HOT
NEUTRAL
VIOLET (+)
GRAY (-)
0-10V DRIVER
SWITCHED
HOT
3-WAY SWITCH
RED
RED/WHITE
DIMMER SWITCH
0-10V
120-277 V~ 50/60 Hz
BLACKLINE/HOT
THREADED ROD
BASKET TYPE CABLE TRAY
TRAPEZE SUPPORT
FOR CABLE TRAY
PROVIDE MINIMUM
OF 4" CLEARANCE
ABOVE CABLE TRAY
BASKET TYPE CABLE TRAY
TRAPEZE SUPPORT
FOR CABLE TRAY
THREADED ROD
1. CABLE TRAY SHALL BE BONDED TO GROUND.
2. PLACE AND SECURE COMMUNICATIONS CABLE TO MAINTAIN 4" MINIMUM CLEARANCE BETWEEN
LOW VOLTAGE CABLING AND POWER CONDUIT AND BOXES.
CEILING MOUNTED
TRAPEZE STYLE SUPPORT
WIRE BASKET CABLE TRAY
4'
EMT CONDUIT TO CABLE TRAY FROM…