Tech Drawings T600-T603.pdf

PDF 3 MB Posted

Attached to
36C77623B0047 - Y1DA--657A5-21-700 EHRM Infrastructure Upgrades Construction Marion, IL VAMC
Solicitation number
36C77623B0047_1
Issued by

About this file

This document provides technical drawings and details for infrastructure upgrades at the Marion VA Medical Center in Marion, Illinois. The upgrades include installation of new cable tray systems, grounding and bonding infrastructure, optical fiber cabling, Category 6A unshielded twisted pair cabling to new telecommunications outlets, server cabinets, fiber distribution enclosures, and other technology components. Key aspects of the work involve deployment of new cable tray, optical fiber and copper cabling throughout the facility including in telecommunications rooms, work areas, and equipment spaces. The project also specifies grounding and bonding requirements to ensure all new equipment and infrastructure is properly grounded and bonded according to applicable standards.

View the file

Other files

File Type Posted
Wage Determination - Williamson County - 9.8.23.pdf PDF
36C77623B0047 0009.docx DOCX document
36C77623B0047 Amendment 0008.docx DOCX document
ae601 door schedule and partition types.pdf PDF
3837_001.pdf PDF
M-105 REFERENCE PLANS - BUILDINGS 81 and 82.pdf PDF
04 20 00 UnitMasonry.pdf PDF
657a5-21-700 ehrm marion il addendum-03.pdf PDF
03 30 00 Cast-in-Place Concrete.pdf PDF
36C77623B0047 Amendment 0007.docx DOCX document
ae408 enlarged plans - bldg 42 43 81.pdf PDF
1 Technical Questions Tracking Spreadsheet - Marion Infra Constr - 8-24-23 Final.pdf PDF
Wage rates - Williamson - 8.14.23.pdf PDF
B 38 Drawing Package_Part5.pdf PDF
Building 14 Boiler Plant Geotechnical Report.pdf PDF
B 38 Drawing Package_Part4.pdf PDF
2. B 37 Marion VA Field Print Model (2 of 2) (1).pdf PDF
2. B 37 Marion VA Field Print Model (2 of 2) (5).pdf PDF
2. B 37 Marion VA Field Print Model (2 of 2) (3).pdf PDF
2017-0502.10 Building 13 Geotech Report.pdf PDF
2. B 37 Marion VA Field Print Model (2 of 2) (2).pdf PDF
36C77623B0047 Amendment 0006.docx DOCX document
B 38 Drawing Package_Part3.pdf PDF
15225023 VA Project 657A5-21-700 EHRM Marion Geotechnical Report.pdf PDF
B 38 Drawing Package_Part1.pdf PDF
B 38 Drawing Package_Part6.pdf PDF
2. B 37 Marion VA Field Print Model (2 of 2) (4).pdf PDF
B 38 Drawing Package_Part2.pdf PDF
Wage Determination - Williamson 8.4.pdf PDF
36C77623B0047 0005.pdf PDF
Attachment 1 - Missing Specs.zip ZIP file
36C77623B0047 0004.pdf PDF
36C77623B0047 0003.pdf PDF
Construction Wage Rates - Williamson County - 7-28-23.pdf PDF
Site Visit Sign-In Sheet - Marion Infra 7-31-23.pdf PDF
Attachment 1 - Electrical Plans 657A5-21-700.zip ZIP file
36C77623B0047 Amendment 0002.pdf PDF
Attachment 1 - 36C77623B0047_1.pdf PDF
36C77623B0047 Amendment 0001.docx DOCX document
ARCHITECTURAL.pdf PDF
Limitations on Subcontracting - Construction.docx DOCX document
STRUCTURAL.pdf PDF
Civil Drawings CU301-CIVIL DETAILS.pdf PDF
HAZARDOUS MATERIALS.pdf PDF
Civil Drawings CU211-CU213.pdf PDF
36C77623B0047_1.docx DOCX document
Civil Drawings CU207-CU210.pdf PDF
GENERAL.pdf PDF
Civil Drawings CU217-CU300.pdf PDF
Civil Drawings CU-214-CU216.pdf PDF
Show 40 more

Latest 50 of 62 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

J-HOOK CAPACITY FOR CAT6A CABLE

J-HOOK SIZE

1" 1-5/16"

2" 3" 4"

CAPACITY

BASED ON 70% FILL

TYPICAL J-HOOK, CABLE LOOP IN

CEILING ABOVE STATION JACK. J-HOOK, SIZES AS

NEEDED

1/4" OR 3/8" THREADED ROD OR #12 TO #8

HANGER WIRE ATTACHED TO STRUCTURE

ABOVE. (DO NOT USE EXISTING CEILING

HANGER WIRES. MUST HAVE ITS OWN

HANGER WIRE.)

PARALLEL MOUNTING PERPENDICULAR MOUNTING

MOUNTING PLATE FOR CABLE TRAY TO EQUIPMENT

RACKS. KIT INCLUDES ALL MOUNTING HARDWARE.

CHATSWORTH PRODUCTS, INC.: PN 10595-712 (12")

CHATSWORTH PRODUCTS, INC.: PN 10595-718 (18")

CHATSWORTH PRODUCTS, INC.: PN 11312-712

CHATSWORTH PRODUCTS, INC. PN 11421-712

WALL ANGLE BRACKET FOR 12" CABLE TRAY WITH

J-BOLT KIT INCLUDES HEX NUTS AND LOCK WASHERS.

SUPPORT ATTACHES TO PLYWOOD BACKBOARD AS

SPECIFIED.

TRIANGULAR SUPPORT BRACKET FOR CABLE TRAY

TO RACK ATTACHMENT.

RADIUS DROP

RADIUS DROP ATTACHES TO THE TOP OF THE CABINET AND

PROVIDES

A SMOOTH CURVED SUPPORT WHERE CABLES EXIT OR ENTER THE

CABLE MANAGEMENT SPACE ALONG THE SIDES OF THE CABINET.

· ATTACHES TO THE TOP OF THE CABINET TO SUPPORT CABLES

AS THEY EXIT/ENTER THE CABINET

· RADIUS DROP IS 11"L (279 MM) WITH A 1.3" (33MM) DIAMETER

RADIUS

· INCLUDES: RADIUS DROP, INSTALLATION HARDWARE

· MATERIAL: ALUMINUM; SELECT PART NUMBER TO MATCH THE

COLOR OF THE CABINET

A1-A035WRAPAROUND CABLE

LABEL WITHIN 6" OF EACH

END OF THE CABLE

ALL LABELING SHALL BE ANSI/TIA/EIA/606C COMPLIANT. BLACK LETTERING

ON WHITE FIELD. MACHINE PRINTED. FURTHER GUIDANCE ON

ADMINISTRATION MAY BE SPECIFIED IN OTHER SECTIONS OF THIS DESIGN

PACKAGE.

.90

.65 eXtreme 10G QuickPort Connector, Channel-Rated, 8-Conductor

6110G-RX6

LEVITON

TYPICAL FACEPLATE WILL BE INSTALLED WITH TWO RJ45s. HIGH DENSITY FACEPLATES WILL BE ISNTALLED WITH FOUR RJ45s.

TYPICAL WORK AREA OUTLET FACEPLATE WILL BE INSTALLED WITH CATEGORY

6A COMPONENT-COMPLIANT 8P8C MEDIA INTERFACE CONNECTORS (RJ45).

EACH CONNECTOR WILL BE TERMINATED TO HIGH QUALITY CATEGORY 6A

HORIZONTAL CABLING WHICH WILL TERMINATE IN THE TELECOMMUNICATIONS

ROOM AS SPECIFIED ELSEWHERE IN THIS DESIGN PACKAGE. ALL HORIZONTAL

UTP SHALL BE CATEGORY 6A AND TERMINATED TO T568B.

RECOMMENDED UTP PATCH PANEL:

LEVITON e2XHD-BLK HIGH-DENSITY ANGLED

48 POSITION

ONE (1) RACK UNIT PER PANEL

TYPICAL WALL-MOUNT (VOIP) OUTLET TYPICAL FLOOR -MOUNT OUTLET

TYPICAL HIGH DENSITY WALL MOUNTED WORK AREA STANDARD DENSITY WALL MOUNTED WORK AREA

OUTLET CONFIGURATION OUTLET CONFIGURATION

FOUR POSITION FACEPLATE

MOUNTED ON SINGLE GANG

WORKBOX. FACEPLATE COLOR

SPECIFIED BY OTHERS.

TWO CATEGORY 6A

8P8C OUTLETS ACTIVE

FOR TELEPHONY/DATA

FOUR POSITION FACEPLATE

MOUNTED ON SINGLE GANG

WORKBOX. FACEPLATE COLOR

SPECIFIED BY OTHERS.

FOUR CATEGORY 6A 8P8C

OUTLETS ACTIVE FOR

TELEPHONY/DATA

SINGLE GANG WORKBOX

WITH TWO CONNECTOR

CHASSIS.

SINGLE GANG

WORKBOX WITH ONE

CONNECTOR

CHASSIS.

MINIMUM OF FOUR

CATEGORY 6A 8P8C

OUTLETS FOR DATA OR

TELEPHONY

ONE CATEGORY 6A

8P8C OUTLET

ACTIVE FOR

TELEPHONY

3/4" FIRE-RETARDANT TREATED PLYWOOD

SPANNING AT LEAST TWO BUILDING

STUDS, OR IF THAT IS NOT POSSIBLE,

ANCHORED INTO AT LEAST ONE STUD

AND TOGGLED INTO THE DRYWALL WITH

5/16" OR LARGER TOGGLE BOLT WITH

FENDER WASHERS.

NUT, 5/16-18 HEX,

STEEL 2 PLACES

WASHER, SLIT LOCK, FOR

5/16, SCR STEEL, 2 PLACES

Ø5/16" LAG BOLTS, FOR PLYWOOD

BACKER BOARDS OR Ø5/16" HEX

CAPBOLTS AND APPROPRIATE WALL

ANCHORS FOR CONCRETE WALLS

FLAT WASHER,

FOR 5/16" BOLTS

J-BOLT, 5/16-18 THD'D

X 2.25" LONG, 2 PLACES

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

EHRM INFRASTRUCTURE

UPGRADES

No. REVISION DESCRIPTION DATE

CIVIL/ STRUCTURAL ENGINEER

OATES ASSOCIATES

100 LANTER COURT, SUITE 1

COLLINSVILLE, IL 62234

(618) 345-2200

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

2519 MADISON AVE. STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

DATA/COMM CONSULTANT

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

COMMISSIONING AGENT

ES2

13401 N. SANTA FE AVE.

OKLAHOMA, OK 73114

(405) 528-4500

SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024

JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023

6/

/2

2:

:4

PM

TECHNOLOGY DETAILS

NR 202 205SR04/20/2023

657A5-21-700

MARION VA MEDICAL CENTER

2401 WEST MAIN ST.

MARION, IL 62959 T-600

N/A

SPUR #: 2114

CABLE SUPPORTS (J-HOOK) DETAIL1

CABLE TRAY TO RACK SUPPORT DETAIL2

CABLE TRAY WALL SUPPORT DETAIL 13

CABLE TRAY WALL SUPPORT DETAIL 24TYPICAL RADIUS DROP DETAIL5

CABLE LABELING DETAIL6

CATEGORY 6A UTP JACK (RJ-45 TYPE) DETAIL7UNSHIELDED TWISTED PAIR (UTP) PATCH PANEL DETAIL8

TELECOMMUNICATIONS OUTLET DETAIL9

FINAL BID DOCUMENTS

204201

RECOMMENDED CASSETTE: LEVITON HDX ENTERPRISE MTP

FIBER TYPE: OM4/OS1

FIBER COUNT: 12-FIBER

CONNECTOR (FRONT): LC CONNECTOR

(REAR): MPO POLARITY: TYPE A

RECOMMENDED FIBER DISTRIBUTION CABINET:

LEVITON ANGLED OPT-X UHDX

144 FIBER

ONE (1) RACK UNIT

UNIVERSAL EARTHQUAKE BRACING KIT

RACK TO WALL

TO WALL

FRAMING TO CEILING

TO CEILING

RACK TO FRAMING

TO PBB/SBB

IRREVERSIBLE CRIMP CONNECTOR

EXAMPLE “A” EXAMPLE “B”

UNIT BONDING CONDUCTOR (6AWG)

TOP-MOUNTED RBB RACK BONDING CONDUCTOR (6AWG)

TO PBB/SBB

TELECOMMUNICATIONS

EQUIPMENT BONDING

CONDUCTOR (TEBC) – 6AWG IRREVERSIBLE

CRIMP CONNECTOR

CABLE TRAY BONDING

CONDUCTOR. TYPICAL AT EACH

SECTION CONNECTION POINT

RACK

ISOLATION

PADS (IF

APPLICABLE)

RACK BONDING CONDUCTOR

EXTENDED TO BOTTOM OF RACK

TO ACCOMMODATE FUTURE

GROWTH

INDIVIDUAL EQUIPMENT BONDING

CONDUCTORS FROM EACH PIECE

OF EQUIPMENT AND RACK TO THE

RACK BONDING CONDUCTOR

RACK BONDING

CONDUCTORS – ALL

CONDUCTORS

ROUTED TO PBB/ SBB

TWO-HOLE COMPRESSION

LUGS (RACKS SHALL NOT BE

MODIFIED IF ONLY ONE-HOLE IS

PROVIDED; USE ONE-HOLE

COMPRESSION LUGS IN THIS

CASE)

RACK BONDING

CONDUCTOR (6AWG)

TEBC

(TELECOMMUNICATIONS

EQUIPMENT BONDING

CONDUCTOR – 6AWG)

IRREVERSIBLE

COMPRESSION

CONNECTION

CHATSWORTH PRODUCTS, INC.: PN 10622-020

WALL MOUNTED BUS BAR KIT INCLUDES 4"W x 12"L x 1/4"T

COPPER GROUND BAR, INSULATORS, AND STAND-OFF

BRACKETS. MOUNTING HEIGHT @ 18" AFF. UON

12"

4"

ALL EQUIPMENT SHALL BE GROUNDED PER MANUFACTURER’S INSTRUCTIONS.

ANSI/EIA/TIA COMPLIANT BUSBAR

CHATSWORTH P/N: 40158-012

ALL GROUNDING SHALL BE DONE IN ACCORDANCE WITH J-STD-607 “COMMERCIAL BUILDING GROUNDING (EARTHING) AND BONDING REQUIREMENTS FOR TELECOMMUNICATIONS”, NFPA 70, AND IN COMPLIANCE

WITH LOCAL CODES.

OPTICAL FIBER CABLE

RADIUS ELBOW

3 PROVIDE GROUNDING JUMPER BETWEEN EACH SECTION OF TRAY (MOUNTED ON

OVER CABLE TRAY FROM ANY OBSTRUCTION

MECHANICAL DUCT SYSTEMS STRIVE TO MAINTAIN MINIMUM 12" OF CLEARANCE

PER ANSI/TIA/EIA STANDARDS CABLE TRAY SHALL NOT IMPEDE ANY

INSTALLATION GUIDE AS WELL AS THE MINIMUM CABLE BEND RADIUS ALLOWED

CUTTING AND BENDING RECOMMENDATIONS FROM THE MANUFACTURER'S

THAT INTERFERE WITH THE DECLARED PATH CONTRACTOR SHALL FOLLOW

2 CABLE TRAY SHALL BE ROUTED AROUND, OVER OR UNDER ANY OBSTACLES

APPROVED MANUFACTURER HAS TO OFFER

1 CABLE TRAY MAY BE SUPPORTED WITH OTHER SUPPORT MECHANISMS THAT THE

GENERAL NOTES:

SIDE) AND FROM TRAY TO EACH HORIZONTAL DISTRIBUTION CONDUIT

COMPLETE WORKING INSTALLATION INCLUDING MISCELLANEOUS APPURTENANCES

4 NOT ALL PARTS ARE SHOWN THE CONTRACTOR IS RESPONSIBLE FOR A

NOTE:

SIDE VIEW

EZ-PATH FIRESTOP DEVICE

EZ-PATH FIRESTOP DEVICE

FRONT VIEW

CABLE LADDER RETAINING POST

RUNWAY DROPS

WASHER

CLAMP

LOCKING NUT

WASHER

NOTE:

FROM TYPICAL LOCATION

#6 AWG

SUPPORT RUNWAY AT 1 8 METER

INTERVALS CABLE LADDER FOR

USE IN COMMUNICATIONS ROOMS

ONLY

AFFIX CABLE TRAY TO

WALL THAT SHALL BE

NO MORE THAN 2" FROM

BOTTOM OF SLEEVE

STEEL WALL PLATE

AND GASKET (TYPICAL)

STI NO: EZDP33FW F

RATINGS-1 AND 2 HOUR T

RATINGS-3/4 AND 1 HOUR

GYPSUM BOARD OPENING SHALL

BE 3-1/4"Wx3-1/4"H MAXIMUM

GYPSUM BOARD OPENING SHALL

BE 3-1/4"Wx3-1/4"H MAXIMUM

TELECOMMUNICATIONS

COPPER AND OPTICAL

FIBER CABLES

TELECOMMUNICATIONS

COPPER AND OPTICAL

FIBER CABLES

STEEL WALL PLATE

AND GASKET

INTUMESCENT

MATERIAL

150mm - 300mm WIDE

HOT DIPPED

GALVANIZED STEEL

CABLE RUNWAY

WITH 225mm RUNG

SPACING

GALVANIZED

THREADED ROD

WITH PVC SLEEVES

PROVIDE RETAINING POST

EVERY 150mm ON BOTH

SIDES OF THE CABLE LADDER

LADDER TYPE CABLE TRAY

TEE INTERSECTION

LADDER TYPE CABLE TRAY

90° RETURN

UNIVERSAL SUPPORT BRACKET SUPPORT

TRAY AT 5 FOOT INTERVALS, STARTING

AT 1 FOOT OFF THE FIRST AND LAST

SEGMENTS OF CABLE TRAY

CLAMP CORNERS WIIH

SPLICE WASHER ASSEMBLY

12" CABLE TRAY, SEE

PLANS FOR LOCATION

PROVIDE WATERFALLS AT

CABLE EXIT LOCATIONS

TELECOMMUNICATIONS ROOM

CABLE TRAY SYSTEM

TRAPEZE HANGING CLIPS WITH THREADED ROD AT 5

FOOT INTERVALS, STARTING AT 1 FOOT OFF THE

FIRST AND LAST SEGMENTS OF CABLE TRAY

TYPICAL RADIUS CORNER INTERIOR

RADIUS SHALL BE 5" MINIMUM, OUTSIDE

SIZE WILL VARY WITH TRAY WIDTH

MAINTAIN 12" MIN CLEARANCE ABOVE

TRAY TO OBSTRUCTIONS OR CEILING

PROVIDE TWO UL LISTED FAST

SPLICE FOR CABLE TRAY COUPLING

OR BOND SECTIONS TOGETHER

GROUND BUSHING WITH

#6 AWG TO CABLE TRAY

PROPOSED CABLE TRAY:

CABLOFIL CF150/300

6" DEEP X 12" WIDE MINIMUM (4"X16" OR 4"X18" ACCEPTABLE)

WHITE POWERCOAT

TRAY INSERT

MAX. CAPACITY:

MAXIMUM PLANNED UTP CABLE FILL:

288 CABLES AT .35 OD CMP

MAXIMUM LOAD:

15.68 LBS PER FOOT

MAXIMUM ANTICIPATED LOAD:

~13.41 LBS PER FOOT

LOAD IN LBS FT PER SPAN:

5: 175.9 6: 155* 7: 113.9 8: 98.3

* RECOMMENDED MAX UNSUPPORTED SPAN

357 CATEGORY 6A UTP (0.35 OD)

486 CATEGORY 6A UTP (0.30 OD)

SCREWS (M4)

NETWORK EQUIPMENT MUST BE GROUNDED. NEVER DEFEAT THE GROUND CONDUCTOR

OR OPERATE THE EQUIPMENT IN THE ABSENCE OF A SUITABLY INSTALLED GROUND

CONDUCTOR. THESE DEVICES WILL BE BONDED TO THE RBB IN THE SAME RACK. EACH

DEVICE WILL HAVE A DEDICATED UNIT BONDING CONDUCTOR (UBC). THE UBC WILL NOT

BE SHARED.

DIRECTLY BONDED TO

RBB

TWO-HOLE

COMPRESSION LUG

SYSTEM GROUND

LOCATION

GROUNDING PAD

UBC

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

EHRM INFRASTRUCTURE

UPGRADES

No. REVISION DESCRIPTION DATE

CIVIL/ STRUCTURAL ENGINEER

OATES ASSOCIATES

100 LANTER COURT, SUITE 1

COLLINSVILLE, IL 62234

(618) 345-2200

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

2519 MADISON AVE. STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

DATA/COMM CONSULTANT

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

COMMISSIONING AGENT

ES2

13401 N. SANTA FE AVE.

OKLAHOMA, OK 73114

(405) 528-4500

SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024

JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023

6/

/2

2:

:4

PM

TECHNOLOGY DETAILS

NR 203 205SR04/20/2023

657A5-21-700

MARION VA MEDICAL CENTER

2401 WEST MAIN ST.

MARION, IL 62959 T-601

N/A

SPUR #: 2114

FIBER CASSETTE DETAIL1FIBER DISTROBUTION ENCLOSURE DETAIL2

UNIVERSAL SEISMIC BRACING DETAIL3

PATHWAY- RACK- BONDING CONDUCTOR CONNECTION REQUIREMENTS4

TELECOMMUNICATIONS PRIMARY BONDING BUSBAR (PBB)5TELECOMMUNICATIONS SECONDARY BONDING BUSBAR (SBB) DETAIL6

BASKET TRAY 1 DETAIL7

BASKET TRAY 2 DETAIL8

EARTHING EXAMPLE (CISCO 6509) Ref. CISCO PRODUCT INSTALLATION GUIDE9

FINAL BID DOCUMENTS

204202

F-Series TeraFrame Gen 3 Cabinet System with accessories installed Configuration includes the following components:

Item Number Description (Qty) FF1N-111C-E52-B F-Series TeraFrame Gen 3 Cabinet System, 45 RMU, 84.6 in. (2149mm) H x 23.6" (600mm) W x 43.30" (1100mm), D Square-Punched Rails, 2-Pair, Single, Perforated Metal Front Door, Two Point, Keyed Swing Handle Lock, Single Solid Metal Rear Door, Two Point, Keyed Swing Handle Latch, Vertical Exhaust Duct System 14-20" (356-508mm), 2 Solid Side Panel, Glacier White, 6-Slide Frame (1) 024-739003-E63 Frame, 6 Slide, 23.6'' (600 mm) W x 43.3'' (1100 mm) D x 45 RMU, Glacier

White (1)

024-739060-E03 Door, TeraFrame, Front, Assembly, 23.6'' (600 mm) W x 45 RMU, Glacier White (1)

024-739064-703 Lock Kit, 2-Point, Keyed, Front Door, 45 RMU (1)

024-739070-E03 Door, Solid, Rear, Assembly, 23.6'' (600 mm) W x 45 RMU, Glacier White (1)

024-739074-703 Lock Kit, 2-Point, Keyed, Solid Door, 45 RMU (1)

024-739191-E12 Vertical Exhaust Duct Kit, 20”H-34"H (508 mm-863 mm), TeraFrame, Cable Port, 23.6'' (600 mm) W x 43.3'' (1100 mm) Glacier White (1)

024-739046-E63 Side Panel, 6 SLIDE, 43.3'' (1100 mm) D x 45 RMU, Glacier White (2)

024-739200-002 Kit, Common Parts Parts, Teraframe, UL, White (1)

024-739110-701 PDU Bracket, Assembly, Standard, 0.7'' (17 mm) W x 3.9'' (100 mm) D x 2.4" (60 mm), Black (1)

39110-C01 PDU Bracket, Assembly, Standard, 0.7'' (17 mm) W x 3.9'' (100 mm) D x 2.4" (60 mm), Black (1)

024-739107-E00 Air Director, Glacier White (1)

024-739240-003 Kit, Packaging, 600 W x 1075-1200D x 42U - 48U (1)

024-739029-001 Caster Kit, Two Swivel, Two Fixed, 1.6'' (41 mm) W x 2'' (51 mm) D x 2" (41

mm) H

024-735077-002 F-Series TeraFrame Cabinet with Caster Packaging, 600-700mm X 1025- 1200mm D X 36-45U H (1)

39085-E03

39137-703

39132-E00

31920-E03

Air Dam, 6 SLIDE, 23.6'' (600 mm) W x 45 RMU, Glacier White (1)

Baying Seal Kit, 45U (2)

Bottom Panel with Brushes (1)

Finger Cable Manager no Cover (2)

UL2416 This Cabinet and any included accessories are UL Listed under the NWIN category per the UL2416 Standard. UL file number E227626. Note, the UL Listing only applies to cabinets manufactured in the United States.

(VENDOR TO PROVIDE 45 RU OF PLENAFILL BLANKING PANEL PER ENCLOSURE)

NOTE: SERVER CABINETS MAY ONLY HOUSE SERVER AND

STORAGE EQUIPMENT AND SUPPORTING PATCH

PANELS. SERVER CABINETS MAY NOT HOUSE

TELECOMMUNICATIONS (NETWORK) EQUIPMENT

84.6"

23.6" (599 mm)

(2148 mm)

43.3" (1100 mm)

RECOMMENDED UTP MEDIA: ATLAS-X1 COPPER TRUNKS

CAT 6A UTP CMP CABLE ASSEMBLY

BUNDLE OF 6 BLUE CABLES

BERK-TEK - LANMARK-10G2 (UTP) BRANDED CABLE

TIA/EIA WIRING T568B

TESTED TO TIA 568-C.2

TERMINATION: ATLAS-X1 E2XHD CONNECTION

RECOMMENDED A-SIDE JACK

COLOR: BLUE

RECOMMENDED B-SIDE JACK

COLOR: YELLOW

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

EHRM INFRASTRUCTURE

UPGRADES

No. REVISION DESCRIPTION DATE

CIVIL/ STRUCTURAL ENGINEER

OATES ASSOCIATES

100 LANTER COURT, SUITE 1

COLLINSVILLE, IL 62234

(618) 345-2200

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

2519 MADISON AVE. STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

DATA/COMM CONSULTANT

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

COMMISSIONING AGENT

ES2

13401 N. SANTA FE AVE.

OKLAHOMA, OK 73114

(405) 528-4500

SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024

JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023

6/

/2

2:

:4

PM

TECHNOLOGY DETAILS

NR 204 205SR04/20/2023

657A5-21-700

MARION VA MEDICAL CENTER

2401 WEST MAIN ST.

MARION, IL 62959 T-602

N/A

SPUR #: 2114

MDA TYPICAL RACK ELEVATION1

MCR STRUCTURED CABLING DETAIL2

SERVER CABINET DETAIL3

SERVER CABINET DETAIL4

FINAL BID DOCUMENTS

DIVERSE ROUTING HORIZONTAL DISTRIBUTION AREA TO MAIN DISTRIBUTION AREA5

DIVERSE ROUTING CABINETS (EQUIPMENT DISTRIBUTOR) TO HORIZONTAL DISTRIBUTION AREA (STANDARD DENSITY)6

HDA TYPICAL RACK ELEVATION7

204203 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

EHRM INFRASTRUCTURE

UPGRADES

No. REVISION DESCRIPTION DATE

CIVIL/ STRUCTURAL ENGINEER

OATES ASSOCIATES

100 LANTER COURT, SUITE 1

COLLINSVILLE, IL 62234

(618) 345-2200

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

2519 MADISON AVE. STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

DATA/COMM CONSULTANT

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

COMMISSIONING AGENT

ES2

13401 N. SANTA FE AVE.

OKLAHOMA, OK 73114

(405) 528-4500

SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024

JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023

6/

/2

2:

:4

PM

TECHNOLOGY DETAILS

NR 205 205SR04/20/2023

657A5-21-700

MARION VA MEDICAL CENTER

2401 WEST MAIN ST.

MARION, IL 62959 T-603

N/A

SPUR #: 2114

TYPICAL TE INSTALLATION1 TR TYPICAL RACK ELEVATION EQUIPMENT PLACEMENT2 NETWORK CHANNEL RACK3 VERTICAL WIREMANAGER4

FINAL BID DOCUMENTS

TYPICAL TE GROUNDING/BONDING5

NETWORK RACK & SERVER CABINET VERTICAL BONDING BUSBAR6

204204

201_T-600 - TECHNOLOGY DETAILS
202_T-601 - TECHNOLOGY DETAILS
203_T-602 - TECHNOLOGY DETAILS
204_T-603 - TECHNOLOGY DETAILS