This document provides technical drawings and details for infrastructure upgrades at the Marion VA Medical Center in Marion, Illinois. The upgrades include installation of new cable tray systems, grounding and bonding infrastructure, optical fiber cabling, Category 6A unshielded twisted pair cabling to new telecommunications outlets, server cabinets, fiber distribution enclosures, and other technology components. Key aspects of the work involve deployment of new cable tray, optical fiber and copper cabling throughout the facility including in telecommunications rooms, work areas, and equipment spaces. The project also specifies grounding and bonding requirements to ensure all new equipment and infrastructure is properly grounded and bonded according to applicable standards.
View the file
Other files
Show 40 more
Latest 50 of 62 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
J-HOOK CAPACITY FOR CAT6A CABLE
J-HOOK SIZE
1" 1-5/16"
2" 3" 4"
CAPACITY
BASED ON 70% FILL
TYPICAL J-HOOK, CABLE LOOP IN
CEILING ABOVE STATION JACK. J-HOOK, SIZES AS
NEEDED
1/4" OR 3/8" THREADED ROD OR #12 TO #8
HANGER WIRE ATTACHED TO STRUCTURE
ABOVE. (DO NOT USE EXISTING CEILING
HANGER WIRES. MUST HAVE ITS OWN
HANGER WIRE.)
PARALLEL MOUNTING PERPENDICULAR MOUNTING
MOUNTING PLATE FOR CABLE TRAY TO EQUIPMENT
RACKS. KIT INCLUDES ALL MOUNTING HARDWARE.
CHATSWORTH PRODUCTS, INC.: PN 10595-712 (12")
CHATSWORTH PRODUCTS, INC.: PN 10595-718 (18")
CHATSWORTH PRODUCTS, INC.: PN 11312-712
CHATSWORTH PRODUCTS, INC. PN 11421-712
WALL ANGLE BRACKET FOR 12" CABLE TRAY WITH
J-BOLT KIT INCLUDES HEX NUTS AND LOCK WASHERS.
SUPPORT ATTACHES TO PLYWOOD BACKBOARD AS
SPECIFIED.
TRIANGULAR SUPPORT BRACKET FOR CABLE TRAY
TO RACK ATTACHMENT.
RADIUS DROP
RADIUS DROP ATTACHES TO THE TOP OF THE CABINET AND
PROVIDES
A SMOOTH CURVED SUPPORT WHERE CABLES EXIT OR ENTER THE
CABLE MANAGEMENT SPACE ALONG THE SIDES OF THE CABINET.
· ATTACHES TO THE TOP OF THE CABINET TO SUPPORT CABLES
AS THEY EXIT/ENTER THE CABINET
· RADIUS DROP IS 11"L (279 MM) WITH A 1.3" (33MM) DIAMETER
RADIUS
· INCLUDES: RADIUS DROP, INSTALLATION HARDWARE
· MATERIAL: ALUMINUM; SELECT PART NUMBER TO MATCH THE
COLOR OF THE CABINET
A1-A035WRAPAROUND CABLE
LABEL WITHIN 6" OF EACH
END OF THE CABLE
ALL LABELING SHALL BE ANSI/TIA/EIA/606C COMPLIANT. BLACK LETTERING
ON WHITE FIELD. MACHINE PRINTED. FURTHER GUIDANCE ON
ADMINISTRATION MAY BE SPECIFIED IN OTHER SECTIONS OF THIS DESIGN
PACKAGE.
.90
.65 eXtreme 10G QuickPort Connector, Channel-Rated, 8-Conductor
6110G-RX6
LEVITON
TYPICAL FACEPLATE WILL BE INSTALLED WITH TWO RJ45s. HIGH DENSITY FACEPLATES WILL BE ISNTALLED WITH FOUR RJ45s.
TYPICAL WORK AREA OUTLET FACEPLATE WILL BE INSTALLED WITH CATEGORY
6A COMPONENT-COMPLIANT 8P8C MEDIA INTERFACE CONNECTORS (RJ45).
EACH CONNECTOR WILL BE TERMINATED TO HIGH QUALITY CATEGORY 6A
HORIZONTAL CABLING WHICH WILL TERMINATE IN THE TELECOMMUNICATIONS
ROOM AS SPECIFIED ELSEWHERE IN THIS DESIGN PACKAGE. ALL HORIZONTAL
UTP SHALL BE CATEGORY 6A AND TERMINATED TO T568B.
RECOMMENDED UTP PATCH PANEL:
LEVITON e2XHD-BLK HIGH-DENSITY ANGLED
48 POSITION
ONE (1) RACK UNIT PER PANEL
TYPICAL WALL-MOUNT (VOIP) OUTLET TYPICAL FLOOR -MOUNT OUTLET
TYPICAL HIGH DENSITY WALL MOUNTED WORK AREA STANDARD DENSITY WALL MOUNTED WORK AREA
OUTLET CONFIGURATION OUTLET CONFIGURATION
FOUR POSITION FACEPLATE
MOUNTED ON SINGLE GANG
WORKBOX. FACEPLATE COLOR
SPECIFIED BY OTHERS.
TWO CATEGORY 6A
8P8C OUTLETS ACTIVE
FOR TELEPHONY/DATA
FOUR POSITION FACEPLATE
MOUNTED ON SINGLE GANG
WORKBOX. FACEPLATE COLOR
SPECIFIED BY OTHERS.
FOUR CATEGORY 6A 8P8C
OUTLETS ACTIVE FOR
TELEPHONY/DATA
SINGLE GANG WORKBOX
WITH TWO CONNECTOR
CHASSIS.
SINGLE GANG
WORKBOX WITH ONE
CONNECTOR
CHASSIS.
MINIMUM OF FOUR
CATEGORY 6A 8P8C
OUTLETS FOR DATA OR
TELEPHONY
ONE CATEGORY 6A
8P8C OUTLET
ACTIVE FOR
TELEPHONY
3/4" FIRE-RETARDANT TREATED PLYWOOD
SPANNING AT LEAST TWO BUILDING
STUDS, OR IF THAT IS NOT POSSIBLE,
ANCHORED INTO AT LEAST ONE STUD
AND TOGGLED INTO THE DRYWALL WITH
5/16" OR LARGER TOGGLE BOLT WITH
FENDER WASHERS.
NUT, 5/16-18 HEX,
STEEL 2 PLACES
WASHER, SLIT LOCK, FOR
5/16, SCR STEEL, 2 PLACES
Ø5/16" LAG BOLTS, FOR PLYWOOD
BACKER BOARDS OR Ø5/16" HEX
CAPBOLTS AND APPROPRIATE WALL
ANCHORS FOR CONCRETE WALLS
FLAT WASHER,
FOR 5/16" BOLTS
J-BOLT, 5/16-18 THD'D
X 2.25" LONG, 2 PLACES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
EHRM INFRASTRUCTURE
UPGRADES
No. REVISION DESCRIPTION DATE
CIVIL/ STRUCTURAL ENGINEER
OATES ASSOCIATES
100 LANTER COURT, SUITE 1
COLLINSVILLE, IL 62234
(618) 345-2200
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
2519 MADISON AVE. STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
DATA/COMM CONSULTANT
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
COMMISSIONING AGENT
ES2
13401 N. SANTA FE AVE.
OKLAHOMA, OK 73114
(405) 528-4500
SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024
JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023
6/
/2
2:
:4
PM
TECHNOLOGY DETAILS
NR 202 205SR04/20/2023
657A5-21-700
MARION VA MEDICAL CENTER
2401 WEST MAIN ST.
MARION, IL 62959 T-600
N/A
SPUR #: 2114
CABLE SUPPORTS (J-HOOK) DETAIL1
CABLE TRAY TO RACK SUPPORT DETAIL2
CABLE TRAY WALL SUPPORT DETAIL 13
CABLE TRAY WALL SUPPORT DETAIL 24TYPICAL RADIUS DROP DETAIL5
CABLE LABELING DETAIL6
CATEGORY 6A UTP JACK (RJ-45 TYPE) DETAIL7UNSHIELDED TWISTED PAIR (UTP) PATCH PANEL DETAIL8
TELECOMMUNICATIONS OUTLET DETAIL9
FINAL BID DOCUMENTS
204201
RECOMMENDED CASSETTE: LEVITON HDX ENTERPRISE MTP
FIBER TYPE: OM4/OS1
FIBER COUNT: 12-FIBER
CONNECTOR (FRONT): LC CONNECTOR
(REAR): MPO POLARITY: TYPE A
RECOMMENDED FIBER DISTRIBUTION CABINET:
LEVITON ANGLED OPT-X UHDX
144 FIBER
ONE (1) RACK UNIT
UNIVERSAL EARTHQUAKE BRACING KIT
RACK TO WALL
TO WALL
FRAMING TO CEILING
TO CEILING
RACK TO FRAMING
TO PBB/SBB
IRREVERSIBLE CRIMP CONNECTOR
EXAMPLE “A” EXAMPLE “B”
UNIT BONDING CONDUCTOR (6AWG)
TOP-MOUNTED RBB RACK BONDING CONDUCTOR (6AWG)
TO PBB/SBB
TELECOMMUNICATIONS
EQUIPMENT BONDING
CONDUCTOR (TEBC) – 6AWG IRREVERSIBLE
CRIMP CONNECTOR
CABLE TRAY BONDING
CONDUCTOR. TYPICAL AT EACH
SECTION CONNECTION POINT
RACK
ISOLATION
PADS (IF
APPLICABLE)
RACK BONDING CONDUCTOR
EXTENDED TO BOTTOM OF RACK
TO ACCOMMODATE FUTURE
GROWTH
INDIVIDUAL EQUIPMENT BONDING
CONDUCTORS FROM EACH PIECE
OF EQUIPMENT AND RACK TO THE
RACK BONDING CONDUCTOR
RACK BONDING
CONDUCTORS – ALL
CONDUCTORS
ROUTED TO PBB/ SBB
TWO-HOLE COMPRESSION
LUGS (RACKS SHALL NOT BE
MODIFIED IF ONLY ONE-HOLE IS
PROVIDED; USE ONE-HOLE
COMPRESSION LUGS IN THIS
CASE)
RACK BONDING
CONDUCTOR (6AWG)
TEBC
(TELECOMMUNICATIONS
EQUIPMENT BONDING
CONDUCTOR – 6AWG)
IRREVERSIBLE
COMPRESSION
CONNECTION
CHATSWORTH PRODUCTS, INC.: PN 10622-020
WALL MOUNTED BUS BAR KIT INCLUDES 4"W x 12"L x 1/4"T
COPPER GROUND BAR, INSULATORS, AND STAND-OFF
BRACKETS. MOUNTING HEIGHT @ 18" AFF. UON
12"
4"
ALL EQUIPMENT SHALL BE GROUNDED PER MANUFACTURER’S INSTRUCTIONS.
ANSI/EIA/TIA COMPLIANT BUSBAR
CHATSWORTH P/N: 40158-012
ALL GROUNDING SHALL BE DONE IN ACCORDANCE WITH J-STD-607 “COMMERCIAL BUILDING GROUNDING (EARTHING) AND BONDING REQUIREMENTS FOR TELECOMMUNICATIONS”, NFPA 70, AND IN COMPLIANCE
WITH LOCAL CODES.
OPTICAL FIBER CABLE
RADIUS ELBOW
3 PROVIDE GROUNDING JUMPER BETWEEN EACH SECTION OF TRAY (MOUNTED ON
OVER CABLE TRAY FROM ANY OBSTRUCTION
MECHANICAL DUCT SYSTEMS STRIVE TO MAINTAIN MINIMUM 12" OF CLEARANCE
PER ANSI/TIA/EIA STANDARDS CABLE TRAY SHALL NOT IMPEDE ANY
INSTALLATION GUIDE AS WELL AS THE MINIMUM CABLE BEND RADIUS ALLOWED
CUTTING AND BENDING RECOMMENDATIONS FROM THE MANUFACTURER'S
THAT INTERFERE WITH THE DECLARED PATH CONTRACTOR SHALL FOLLOW
2 CABLE TRAY SHALL BE ROUTED AROUND, OVER OR UNDER ANY OBSTACLES
APPROVED MANUFACTURER HAS TO OFFER
1 CABLE TRAY MAY BE SUPPORTED WITH OTHER SUPPORT MECHANISMS THAT THE
GENERAL NOTES:
SIDE) AND FROM TRAY TO EACH HORIZONTAL DISTRIBUTION CONDUIT
COMPLETE WORKING INSTALLATION INCLUDING MISCELLANEOUS APPURTENANCES
4 NOT ALL PARTS ARE SHOWN THE CONTRACTOR IS RESPONSIBLE FOR A
NOTE:
SIDE VIEW
EZ-PATH FIRESTOP DEVICE
EZ-PATH FIRESTOP DEVICE
FRONT VIEW
CABLE LADDER RETAINING POST
RUNWAY DROPS
WASHER
CLAMP
LOCKING NUT
WASHER
NOTE:
FROM TYPICAL LOCATION
#6 AWG
SUPPORT RUNWAY AT 1 8 METER
INTERVALS CABLE LADDER FOR
USE IN COMMUNICATIONS ROOMS
ONLY
AFFIX CABLE TRAY TO
WALL THAT SHALL BE
NO MORE THAN 2" FROM
BOTTOM OF SLEEVE
STEEL WALL PLATE
AND GASKET (TYPICAL)
STI NO: EZDP33FW F
RATINGS-1 AND 2 HOUR T
RATINGS-3/4 AND 1 HOUR
GYPSUM BOARD OPENING SHALL
BE 3-1/4"Wx3-1/4"H MAXIMUM
GYPSUM BOARD OPENING SHALL
BE 3-1/4"Wx3-1/4"H MAXIMUM
TELECOMMUNICATIONS
COPPER AND OPTICAL
FIBER CABLES
TELECOMMUNICATIONS
COPPER AND OPTICAL
FIBER CABLES
STEEL WALL PLATE
AND GASKET
INTUMESCENT
MATERIAL
150mm - 300mm WIDE
HOT DIPPED
GALVANIZED STEEL
CABLE RUNWAY
WITH 225mm RUNG
SPACING
GALVANIZED
THREADED ROD
WITH PVC SLEEVES
PROVIDE RETAINING POST
EVERY 150mm ON BOTH
SIDES OF THE CABLE LADDER
LADDER TYPE CABLE TRAY
TEE INTERSECTION
LADDER TYPE CABLE TRAY
90° RETURN
UNIVERSAL SUPPORT BRACKET SUPPORT
TRAY AT 5 FOOT INTERVALS, STARTING
AT 1 FOOT OFF THE FIRST AND LAST
SEGMENTS OF CABLE TRAY
CLAMP CORNERS WIIH
SPLICE WASHER ASSEMBLY
12" CABLE TRAY, SEE
PLANS FOR LOCATION
PROVIDE WATERFALLS AT
CABLE EXIT LOCATIONS
TELECOMMUNICATIONS ROOM
CABLE TRAY SYSTEM
TRAPEZE HANGING CLIPS WITH THREADED ROD AT 5
FOOT INTERVALS, STARTING AT 1 FOOT OFF THE
FIRST AND LAST SEGMENTS OF CABLE TRAY
TYPICAL RADIUS CORNER INTERIOR
RADIUS SHALL BE 5" MINIMUM, OUTSIDE
SIZE WILL VARY WITH TRAY WIDTH
MAINTAIN 12" MIN CLEARANCE ABOVE
TRAY TO OBSTRUCTIONS OR CEILING
PROVIDE TWO UL LISTED FAST
SPLICE FOR CABLE TRAY COUPLING
OR BOND SECTIONS TOGETHER
GROUND BUSHING WITH
#6 AWG TO CABLE TRAY
PROPOSED CABLE TRAY:
CABLOFIL CF150/300
6" DEEP X 12" WIDE MINIMUM (4"X16" OR 4"X18" ACCEPTABLE)
WHITE POWERCOAT
TRAY INSERT
MAX. CAPACITY:
MAXIMUM PLANNED UTP CABLE FILL:
288 CABLES AT .35 OD CMP
MAXIMUM LOAD:
15.68 LBS PER FOOT
MAXIMUM ANTICIPATED LOAD:
~13.41 LBS PER FOOT
LOAD IN LBS FT PER SPAN:
5: 175.9 6: 155* 7: 113.9 8: 98.3
* RECOMMENDED MAX UNSUPPORTED SPAN
357 CATEGORY 6A UTP (0.35 OD)
486 CATEGORY 6A UTP (0.30 OD)
SCREWS (M4)
NETWORK EQUIPMENT MUST BE GROUNDED. NEVER DEFEAT THE GROUND CONDUCTOR
OR OPERATE THE EQUIPMENT IN THE ABSENCE OF A SUITABLY INSTALLED GROUND
CONDUCTOR. THESE DEVICES WILL BE BONDED TO THE RBB IN THE SAME RACK. EACH
DEVICE WILL HAVE A DEDICATED UNIT BONDING CONDUCTOR (UBC). THE UBC WILL NOT
BE SHARED.
DIRECTLY BONDED TO
RBB
TWO-HOLE
COMPRESSION LUG
SYSTEM GROUND
LOCATION
GROUNDING PAD
UBC
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
EHRM INFRASTRUCTURE
UPGRADES
No. REVISION DESCRIPTION DATE
CIVIL/ STRUCTURAL ENGINEER
OATES ASSOCIATES
100 LANTER COURT, SUITE 1
COLLINSVILLE, IL 62234
(618) 345-2200
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
2519 MADISON AVE. STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
DATA/COMM CONSULTANT
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
COMMISSIONING AGENT
ES2
13401 N. SANTA FE AVE.
OKLAHOMA, OK 73114
(405) 528-4500
SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024
JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023
6/
/2
2:
:4
PM
TECHNOLOGY DETAILS
NR 203 205SR04/20/2023
657A5-21-700
MARION VA MEDICAL CENTER
2401 WEST MAIN ST.
MARION, IL 62959 T-601
N/A
SPUR #: 2114
FIBER CASSETTE DETAIL1FIBER DISTROBUTION ENCLOSURE DETAIL2
UNIVERSAL SEISMIC BRACING DETAIL3
PATHWAY- RACK- BONDING CONDUCTOR CONNECTION REQUIREMENTS4
TELECOMMUNICATIONS PRIMARY BONDING BUSBAR (PBB)5TELECOMMUNICATIONS SECONDARY BONDING BUSBAR (SBB) DETAIL6
BASKET TRAY 1 DETAIL7
BASKET TRAY 2 DETAIL8
EARTHING EXAMPLE (CISCO 6509) Ref. CISCO PRODUCT INSTALLATION GUIDE9
FINAL BID DOCUMENTS
204202
F-Series TeraFrame Gen 3 Cabinet System with accessories installed Configuration includes the following components:
Item Number Description (Qty) FF1N-111C-E52-B F-Series TeraFrame Gen 3 Cabinet System, 45 RMU, 84.6 in. (2149mm) H x 23.6" (600mm) W x 43.30" (1100mm), D Square-Punched Rails, 2-Pair, Single, Perforated Metal Front Door, Two Point, Keyed Swing Handle Lock, Single Solid Metal Rear Door, Two Point, Keyed Swing Handle Latch, Vertical Exhaust Duct System 14-20" (356-508mm), 2 Solid Side Panel, Glacier White, 6-Slide Frame (1) 024-739003-E63 Frame, 6 Slide, 23.6'' (600 mm) W x 43.3'' (1100 mm) D x 45 RMU, Glacier
White (1)
024-739060-E03 Door, TeraFrame, Front, Assembly, 23.6'' (600 mm) W x 45 RMU, Glacier White (1)
024-739064-703 Lock Kit, 2-Point, Keyed, Front Door, 45 RMU (1)
024-739070-E03 Door, Solid, Rear, Assembly, 23.6'' (600 mm) W x 45 RMU, Glacier White (1)
024-739074-703 Lock Kit, 2-Point, Keyed, Solid Door, 45 RMU (1)
024-739191-E12 Vertical Exhaust Duct Kit, 20”H-34"H (508 mm-863 mm), TeraFrame, Cable Port, 23.6'' (600 mm) W x 43.3'' (1100 mm) Glacier White (1)
024-739046-E63 Side Panel, 6 SLIDE, 43.3'' (1100 mm) D x 45 RMU, Glacier White (2)
024-739200-002 Kit, Common Parts Parts, Teraframe, UL, White (1)
024-739110-701 PDU Bracket, Assembly, Standard, 0.7'' (17 mm) W x 3.9'' (100 mm) D x 2.4" (60 mm), Black (1)
39110-C01 PDU Bracket, Assembly, Standard, 0.7'' (17 mm) W x 3.9'' (100 mm) D x 2.4" (60 mm), Black (1)
024-739107-E00 Air Director, Glacier White (1)
024-739240-003 Kit, Packaging, 600 W x 1075-1200D x 42U - 48U (1)
024-739029-001 Caster Kit, Two Swivel, Two Fixed, 1.6'' (41 mm) W x 2'' (51 mm) D x 2" (41
mm) H
024-735077-002 F-Series TeraFrame Cabinet with Caster Packaging, 600-700mm X 1025- 1200mm D X 36-45U H (1)
39085-E03
39137-703
39132-E00
31920-E03
Air Dam, 6 SLIDE, 23.6'' (600 mm) W x 45 RMU, Glacier White (1)
Baying Seal Kit, 45U (2)
Bottom Panel with Brushes (1)
Finger Cable Manager no Cover (2)
UL2416 This Cabinet and any included accessories are UL Listed under the NWIN category per the UL2416 Standard. UL file number E227626. Note, the UL Listing only applies to cabinets manufactured in the United States.
(VENDOR TO PROVIDE 45 RU OF PLENAFILL BLANKING PANEL PER ENCLOSURE)
NOTE: SERVER CABINETS MAY ONLY HOUSE SERVER AND
STORAGE EQUIPMENT AND SUPPORTING PATCH
PANELS. SERVER CABINETS MAY NOT HOUSE
TELECOMMUNICATIONS (NETWORK) EQUIPMENT
84.6"
23.6" (599 mm)
(2148 mm)
43.3" (1100 mm)
RECOMMENDED UTP MEDIA: ATLAS-X1 COPPER TRUNKS
CAT 6A UTP CMP CABLE ASSEMBLY
BUNDLE OF 6 BLUE CABLES
BERK-TEK - LANMARK-10G2 (UTP) BRANDED CABLE
TIA/EIA WIRING T568B
TESTED TO TIA 568-C.2
TERMINATION: ATLAS-X1 E2XHD CONNECTION
RECOMMENDED A-SIDE JACK
COLOR: BLUE
RECOMMENDED B-SIDE JACK
COLOR: YELLOW
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
EHRM INFRASTRUCTURE
UPGRADES
No. REVISION DESCRIPTION DATE
CIVIL/ STRUCTURAL ENGINEER
OATES ASSOCIATES
100 LANTER COURT, SUITE 1
COLLINSVILLE, IL 62234
(618) 345-2200
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
2519 MADISON AVE. STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
DATA/COMM CONSULTANT
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
COMMISSIONING AGENT
ES2
13401 N. SANTA FE AVE.
OKLAHOMA, OK 73114
(405) 528-4500
SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024
JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023
6/
/2
2:
:4
PM
TECHNOLOGY DETAILS
NR 204 205SR04/20/2023
657A5-21-700
MARION VA MEDICAL CENTER
2401 WEST MAIN ST.
MARION, IL 62959 T-602
N/A
SPUR #: 2114
MDA TYPICAL RACK ELEVATION1
MCR STRUCTURED CABLING DETAIL2
SERVER CABINET DETAIL3
SERVER CABINET DETAIL4
FINAL BID DOCUMENTS
DIVERSE ROUTING HORIZONTAL DISTRIBUTION AREA TO MAIN DISTRIBUTION AREA5
DIVERSE ROUTING CABINETS (EQUIPMENT DISTRIBUTOR) TO HORIZONTAL DISTRIBUTION AREA (STANDARD DENSITY)6
HDA TYPICAL RACK ELEVATION7
204203 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
EHRM INFRASTRUCTURE
UPGRADES
No. REVISION DESCRIPTION DATE
CIVIL/ STRUCTURAL ENGINEER
OATES ASSOCIATES
100 LANTER COURT, SUITE 1
COLLINSVILLE, IL 62234
(618) 345-2200
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
2519 MADISON AVE. STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
DATA/COMM CONSULTANT
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
COMMISSIONING AGENT
ES2
13401 N. SANTA FE AVE.
OKLAHOMA, OK 73114
(405) 528-4500
SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024
JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023
6/
/2
2:
:4
PM
TECHNOLOGY DETAILS
NR 205 205SR04/20/2023
657A5-21-700
MARION VA MEDICAL CENTER
2401 WEST MAIN ST.
MARION, IL 62959 T-603
N/A
SPUR #: 2114
TYPICAL TE INSTALLATION1 TR TYPICAL RACK ELEVATION EQUIPMENT PLACEMENT2 NETWORK CHANNEL RACK3 VERTICAL WIREMANAGER4
FINAL BID DOCUMENTS
TYPICAL TE GROUNDING/BONDING5
NETWORK RACK & SERVER CABINET VERTICAL BONDING BUSBAR6
204204
| 201_T-600 - TECHNOLOGY DETAILS |
| 202_T-601 - TECHNOLOGY DETAILS |
| 203_T-602 - TECHNOLOGY DETAILS |
| 204_T-603 - TECHNOLOGY DETAILS |