About this file

This solicitation is for construction services at the Marion VA Medical Center in Marion, Illinois. The scope of work includes infrastructure upgrades to buildings 8, 13, 14, 15, 16, 37, 38, 42, 43, 81, and 82. Specific projects involve renovating and upgrading computer rooms, telecom closets, electrical closets, and other interior spaces. The solicitation seeks fixed-price bids for trade packages including demolition, carpentry, doors/frames/hardware, drywall, flooring, painting, and mechanical/electrical/plumbing work. Bids are due by July 20, 2023. The period of performance is 270 calendar days from NTP. The place of performance is the Marion VAMC. The total estimated value is $6.5 million.

View the file

Other files

File Type Posted
Wage Determination - Williamson County - 9.8.23.pdf PDF
36C77623B0047 0009.docx DOCX document
36C77623B0047 Amendment 0008.docx DOCX document
ae601 door schedule and partition types.pdf PDF
3837_001.pdf PDF
M-105 REFERENCE PLANS - BUILDINGS 81 and 82.pdf PDF
04 20 00 UnitMasonry.pdf PDF
657a5-21-700 ehrm marion il addendum-03.pdf PDF
03 30 00 Cast-in-Place Concrete.pdf PDF
36C77623B0047 Amendment 0007.docx DOCX document
ae408 enlarged plans - bldg 42 43 81.pdf PDF
1 Technical Questions Tracking Spreadsheet - Marion Infra Constr - 8-24-23 Final.pdf PDF
Wage rates - Williamson - 8.14.23.pdf PDF
B 38 Drawing Package_Part5.pdf PDF
Building 14 Boiler Plant Geotechnical Report.pdf PDF
B 38 Drawing Package_Part4.pdf PDF
2. B 37 Marion VA Field Print Model (2 of 2) (1).pdf PDF
2. B 37 Marion VA Field Print Model (2 of 2) (5).pdf PDF
2. B 37 Marion VA Field Print Model (2 of 2) (3).pdf PDF
2017-0502.10 Building 13 Geotech Report.pdf PDF
2. B 37 Marion VA Field Print Model (2 of 2) (2).pdf PDF
36C77623B0047 Amendment 0006.docx DOCX document
B 38 Drawing Package_Part3.pdf PDF
15225023 VA Project 657A5-21-700 EHRM Marion Geotechnical Report.pdf PDF
B 38 Drawing Package_Part1.pdf PDF
B 38 Drawing Package_Part6.pdf PDF
2. B 37 Marion VA Field Print Model (2 of 2) (4).pdf PDF
B 38 Drawing Package_Part2.pdf PDF
Wage Determination - Williamson 8.4.pdf PDF
36C77623B0047 0005.pdf PDF
Attachment 1 - Missing Specs.zip ZIP file
36C77623B0047 0004.pdf PDF
36C77623B0047 0003.pdf PDF
Construction Wage Rates - Williamson County - 7-28-23.pdf PDF
Site Visit Sign-In Sheet - Marion Infra 7-31-23.pdf PDF
Attachment 1 - Electrical Plans 657A5-21-700.zip ZIP file
36C77623B0047 Amendment 0002.pdf PDF
Attachment 1 - 36C77623B0047_1.pdf PDF
36C77623B0047 Amendment 0001.docx DOCX document
Limitations on Subcontracting - Construction.docx DOCX document
STRUCTURAL.pdf PDF
Civil Drawings CU301-CIVIL DETAILS.pdf PDF
HAZARDOUS MATERIALS.pdf PDF
Civil Drawings CU211-CU213.pdf PDF
36C77623B0047_1.docx DOCX document
Civil Drawings CU207-CU210.pdf PDF
GENERAL.pdf PDF
Civil Drawings CU217-CU300.pdf PDF
Civil Drawings CU-214-CU216.pdf PDF
Brand Name Justification - Marion EHRM Infra Redacted.pdf PDF
Show 40 more

Latest 50 of 62 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CSELECT.

H

SS

FEC

DN

DN

DN

AE402

AE402

1 2 3

A

B

OFFICE

BREAK

CONFERENCE

STOR

OFFICE

OFFICE

OFFICE

OFFICE

RR

OFFICE

RR

OFFICE

OFFICE

ELEC

105A

MECH

101C

HAC

PLAN RM

WORKSTATIONS

121A OFFICE

TR

101D

AE402

AE402

PHARMACY

OFFICE

SUPPLIES

105D

ENGINEERING

105EFREEZER

110A

REFRIGERATOR

110 LOADING

DOCK

OXYGEN

OFFICE

SPACE

105A

MAILROOM

OFFICE

BREAK

ROOM

WAREHOUSE

STORAGE

1 2 3 4 5 6 7 8 9

A

B

C

TR

105D

TELEPHONE

CLOSET

105C

1 2 3 4 5 6 7 8 9

A

B

C

AE403

AE403

AE403

AE403

IRM

STORAGE

TELEPHONE

BIOMED

106A

STOR.

105A

OFFICE

GYM

118B

OFFICE

OFFICE

OFFICE

IRM

123A

IRM OFFICE

OFFICE

VAV

BIOMED

BIOMED OFF

BIOMED OFF

MENS

WOMENS

BEHAVIOR

MEDICINE

BEHAVIOR

MEDICINE

BEHAVIOR

MEDICINE

BEHAVIOR

MEDICINE

COMPUTER

124IRM TECH

STAFF

T/C ELEC

BIOMED OFF

HAC

BEHAVIOR

MEDICING

AMER.

LEGION

VFW

TR

'-7

/2

SITE INVESTIGATION

AE401

AE401

TR

MUSEUM

OFFICE

OFFICE

OFFICE

OFFICE

BREAK

RR

RR

OFFICE

JANITOR

STAIR

A B C D

D

E

E

F

F

G

GA B C

D E F G

AE401

AE401

UNEXC.

CS-2

UNEXC.

CS-1

STORAGE

STORAGE

STORAGE

STORAGE

TR

4A

STORAGE

STOR.

AE401

AE401

EQUIP.

MAINT.

104STORAGE

OFFICE

103B

RR

103A

EMERG.

GEN.

BAY

1 2 3 4 5 6

A

B

C

D

E

F

4.93.92.91.81.7

1. ALL DOOR FRAMES TO BE LOCATED 4" FROM OUTSIDE OF FRAME TO FINISH FACE OF

ADJACENT WALL UNLESS NOTED OTHERWISE.

2. ALL WALL IN-FILL TO MATCH EXSITING OR ADJACENT WALL TYPE CONSTRUCTION. REFER TO

PARTITION TYPES (ON SHEET AE601) FOR WALL TYPES.

3. REFER TO DOOR SCHEDULE & DETAILS SHEET (AE601) FOR DOOR INFORMATION.

4. ALL WALLS ARE DIMENSIONED TO CENTERLINE OF METAL STUD, UNLESS NOTED OTHERWISE.

5. BLOCK OUT SLAB FOR PENETRATIONS SHALL BE 2" LARGER THAN DUCT SIZE TO ALLOW

TOLERANCE FOR DUCT PASSAGE AND FIRE SAFING. COORDINATE WITH MEP FOR DUCT SIZES.

6. FURR AROUND ALL COLUMN PROTRUSIONS AS NEEDED UNLESS NOTED OTHERWISE.

7. REFER TO SHEET AF711 FOR FINISH MATERIAL INFORMATION.

GENERAL PLAN NOTES

N

MOD-4

MOD-3

MOD-1

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024

JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023

CIVIL/ STRUCTURAL ENGINEER

OATES ASSOCIATES

100 LANTER COURT, SUITE 1

COLLINSVILLE, IL 62234

(618) 345-2200

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

2519 MADISON AVE. STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

DATA/COMM CONSULTANT

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

EHRM INFRASTRUCTURE

UPGRADESCOMMISSIONING AGENT

ES2

13401 N. SANTA FE AVE.

OKLAHOMA, OK 73114

(405) 528-4500

/1

/2

:4 :2

A

M

REFERENCE PLANS - BLDG 8, 13, 14, 15,

16, 37

NR 076 205NR

FINAL BID DOCUMENTS

4/20/2023

657A5-21-700

MARION VA MEDICAL CENTER

2401 WEST MAIN ST. | MARION, IL

62959

AE101

SPUR #: 2114

N

1/16" = 1'-0"

REFERENCE PLAN - BLDG 15 LEVEL G4

N

1/16" = 1'-0"

REFERENCE PLAN - BLDG 16 LEVEL G5

N

1/16" = 1'-0"

REFERENCE PLAN - BLDG 37 LEVEL 16

N

1/16" = 1'-0"

REFERENCE PLAN - BLDG 8 LEVEL 11

N

1/16" = 1'-0"

REFERENCE PLAN - BLDG 13 LEVEL G2

N

1/16" = 1'-0"

REFERENCE PLAN - BLDG 14 - LEVEL 23

1" = 400'-0"

KEY PLAN

8, 13, 14, 15, 16, 37

No. REVISION DESCRIPTION DATE

AE404

AE404

A B

AE201

W.I.F. KITCHEN

VENDING

LINEN

6A

STOR

5B

ELEC

MECHANICAL

TRANSFORMER

TRANSFORMER

2A

CLEAN

STORAGE

RETAIL

SHOP

MORGE

33A

SEISMIC

TOWER

MECHANICAL

OFFICE

OFFICE

28A

OFFICE

SEISMIC

TOWER

SHOP

TRANSFORMER

STAIR 1

C

D

IT

AE404

AE404

EXAM

EXAM

EXAM

EXAM

EXAM

A B

AE201

CHAPEL

OFFICE

LAB

STOR

ORAL

SURGERY

OFFICE

HYGENE

DENTAL

DENTAL

DENTAL

DENTAL

X-RAY

DENTAL

104B

HYGENE

104A

BREAK

STOR

HAC

122RR

RR

LOCKER

OFF

120A

OFF

119C

OFF

199E

OFF

119D OFFICE

ELEC

WAITING

103A

EXAM

EXAM

EXAM

102D

OFFICE

102C

CLERKS

OCT

CAMERA

WAIT

111A

HEALTHINFECTION

CONTROL

102A

OCC HEALTH

WAITING

INFECTION

CONTROL

CAMERA

107A

STAIRLOCKER

121A

LOCKER

121B

HAC

STOR

OFFICE

119A

WAIT

RECPT.

119C

LOBBY

OFFICE

LOUNGE

STAIR 2STAIR 1

SEISMIC

TOWER

EXAM

EXAM

TR

123C

EXIST.

DATA

123B

TEAM

OFFICE

#1

C

D

AE405

AE405

A B

LOCKER

SERILE AND

NONSTERILE

STOR.

INVENTORY

MANAGEMENT

DECONTAMINATION

INVENTORY

CONTROL

HAC

SPD MGR

RECEIVING

VISISTOR

LOUNGE

MULTI

PURPOSE

OFFICE

STORAGE

OFFICE

SEISMIC

TOWER

STAIR 1

PHAR

LOGISTICS

NOURISH

RR

330A

ELEC

ETO

WASH

TR

312B

C

D

AE405

AE405

A B

AE201

ANESTHESIA

EQUIP

OR

OR

ELEC

HAC

STRESS LAB

EXAM

EXAM

NURSE

LOUNGE

LOCKER

LOCKER

OR

SOILED

PRE/POST

PRE/POST

CONSULT

RECPT.

WAITING

OFFICE

OFFICE

RR

RR

LOGISTICS

TR

237A

RR

RR

RR

STOR

SEISMIC

TOWER

PATIENT

ROOM

COMFORT

OFFICE

231A

EXAM

OFFICE

OFFICE

229 OFFICE

STAIR 1

STOR

C

D

AE406

AE406

A B

AE201

ROOFMECHANICALROOF

CLEAN

UTILITY

STOR

417A

STAIR 1

ELEC

STOR

RECOVERY

DICTIATION

413B

SEISMIC

TOWER

C

D

TR

418B

OR #2

1. ALL DOOR FRAMES TO BE LOCATED 4" FROM OUTSIDE OF FRAME TO FINISH FACE OF

ADJACENT WALL UNLESS NOTED OTHERWISE.

2. ALL WALL IN-FILL TO MATCH EXSITING OR ADJACENT WALL TYPE CONSTRUCTION. REFER TO

PARTITION TYPES (ON SHEET AE601) FOR WALL TYPES.

3. REFER TO DOOR SCHEDULE & DETAILS SHEET (AE601) FOR DOOR INFORMATION.

4. ALL WALLS ARE DIMENSIONED TO CENTERLINE OF METAL STUD, UNLESS NOTED OTHERWISE.

5. BLOCK OUT SLAB FOR PENETRATIONS SHALL BE 2" LARGER THAN DUCT SIZE TO ALLOW

TOLERANCE FOR DUCT PASSAGE AND FIRE SAFING. COORDINATE WITH MEP FOR DUCT SIZES.

6. FURR AROUND ALL COLUMN PROTRUSIONS AS NEEDED UNLESS NOTED OTHERWISE.

7. REFER TO SHEET AF711 FOR FINISH MATERIAL INFORMATION.

GENERAL PLAN NOTES

MOD-1

MOD-4

MOD-3

N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024

JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023

CIVIL/ STRUCTURAL ENGINEER

OATES ASSOCIATES

100 LANTER COURT, SUITE 1

COLLINSVILLE, IL 62234

(618) 345-2200

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

2519 MADISON AVE. STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

DATA/COMM CONSULTANT

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

EHRM INFRASTRUCTURE

UPGRADESCOMMISSIONING AGENT

ES2

13401 N. SANTA FE AVE.

OKLAHOMA, OK 73114

(405) 528-4500

/1

/2

:5 :5

A

M

REFERENCE PLANS - BLDG 38

NR 077 205NR

FINAL BID DOCUMENTS

4/20/2023

657A5-21-700

MARION VA MEDICAL CENTER

2401 WEST MAIN ST. | MARION, IL

62959

AE102

SPUR #: 2114

N

1/16" = 1'-0"

REFERENCE PLAN - LEVEL G1

N

1/16" = 1'-0"

REFERENCE PLAN - LEVEL 12

N

1/16" = 1'-0"

REFERENCE PLAN - LEVEL 34

N

1/16" = 1'-0"

REFERENCE PLAN - LEVEL 23

N

1/16" = 1'-0"

REFERENCE PLAN - LEVEL 45

1" = 400'-0"

KEY PLAN

RR

RR

UP

UP

AE407

AE407

AE407

AE408

AE407

AE407

AE407

AE408

AE407

AE407

MECH

BC115 CT CONTROL

BC139

CT SCAN

BC138

NUC MED

CONTROL

BC109

OFFICE

BC110

EXAM

BC111

ELEC

BC116

HAC

BC113

CLEAN

BC114

OFFICE

BC112

XRAY STOR

BC118

EXAM

BC120

PROC

BC121

COMPUTER

BC122

PROC

BC123

EXAM

BC131

EXAM

BC133

RR

131A

RR

133A

READING

BC130

TECH

BC132

BONE

BC132A

RR

BC136

STOR

BC134 STOR

CB43A

STOR

CB43C CLERK

CB42

STATIONARY

BC105

WAITING

CB40

HAC

BC135

IMAGING

BC106

CONF

BC108

BREAK

BC107

RR

105A

RR

106A

INJECT

BC104

THYROID

BC102

RADIOPHARMACY

BC103

STOR

BC101

STERIL

BC100A

BIOASSAY

BC100

WAITING

CB34A

HIST FROZ

GR SECT

BB144

DRAW

BB127

RECS

144A

SPEC

127A

CORE

FUNCT.

BB129

CLINICAL

MICRO

BB131

STERILE

PREP

BB133

STOR

141A

COOLER

141B

WORK

141C

CLINICAL

PATH

BB143

BLOOD

BANK

HEMATOLOGY

BB142

ELECTRICAL

BB139A

BULK

PROCESS

BB141

MECHANICAL

BB139

OFFICE

BB135

LOCKER

BB134

OFFICE

BB132

OFFICE

BB130

BLOOD

DRAW

BB128

HAC

RR

ULTRASOUND

BC119

RR

119A

UTLRASOUND

BC125

BREAK

BC124

RR

124A

AAI

BC126

OFFICE

BC127

OFFICE

BC128

OFFICE

BC129

STOR

CT SCAN

CONTROL

MRI

EQUIP

CHANGE

PREP

PREP

RR

ELEC

NURSE

D125

EXAM

D126

EXAM

D127

EXAM

D128

EXAM

D129

EXAM

D130

WAITING

D116

RECPT

D117

EXAM

D119

EXAM

D120

EXAM

D121

EXAM

D122

NURSE

D123 STOR

D124

OFFICE

D118OFFICE

BD108E

PHARMACY

BD109

LOUNGE

BD107

RR

107A

RR

107B

OFFICE

BB103

CLERK

CB20B

CLINIC

BB116

CLINIC

BB118

CLINIC

BB117

EXAM

BB102

EXAM

BB101

EXAM

BB100

OFFICE

BB104

EXAM

BA121

OFFICE

BA122

CLERK

CB19B

CLINIC

BB105

CLINIC

BB115

PROC

BB106

CLINIC

BB114

RR

BB107

OFFICE

107A

OFF

113A

BREAK

BA142

SOILED

BA141

LOG

BA140

MED

BA139

EXAM

BA137

EXAM

BA136

OFFICE

BB109

OFFICE

BB110

OFFICE

BB111

CLINIC

BB112

LINEN

RR

STOR

BB119

CLINIC

BB121

NURSE

EXAM

BB124

OFFICE

BB123

EXAM

BB125

RR

BA135 SAFE

BA134

EXAM

BA132

SAFE

BA133

LIFE

SUPPORT

BA131

OFFICE

BA126

RR

106A

NOUR

BA138

LIFE

SUPPORT

BA129

EXAM

BA128

EXAM

BA130

EXAM

BA126

RR

RR

126B

DECON

BA119

NURSE

CB11

NAME

EXAM

BA113

EXAM

BA112

EXAM

BA108

MOD

BA144

BEREAV

BA107

EXAM

BA106

COMMAND

CENTER

BA143

EXAM

BA146RR

CLEAN

BA110

RR

MSA

CB6B

WAITING

CB6

SEC

CB6A

OFFICE

BA106

OFFICE

BA107

CASHIER

BA104

OFFICE

BA103

EXAM

BA103A

EXAM

BA103B

CLERK

CB3A

OFFICE

BA101

POLICE

BA102

WORK

BA102A

WAITING

CB49

CONFERENCE

ROOM

BD100 STOR

100A

OFFICE

BA100A

CLERK

BA100

OFFICE

BA125

ARMORY

BA102C

LOCKER

CB18A

ELEC

BA124

RR

BD106

RR

BD105

HAC

BD103

PHARM

BD102

COUNSEL

BD101

STOR

BD113

MIX

113A

PREP

113B

RR

111A

HAC

MECH

BD115

CONT.

SUBST

BD110

VAULT

BD110A

SPECIMAN

E018

COOLER

E018A

BLOOD

BANK

E021

ACID

E023A

MICRO

E019A

HIST

E023

IT

E025

MAIN LAB

E019

SHARED

OFFICE

E016

OPEN

OFFICE

E010

OFFICE

E012

PSA

E014

STOR

E008

OFFICE

E017

SHARED

OFFICE

E015

OFFICE

E013

STA

E009

STA

E011

STA

E003

STA

E005

PHLEBO

E002

RR

E004

RR

E006

STA

E007

WAITING

E001

CONF

E026

BREAK

E024

HAC

E024A

RR

E022

RR

E020

BUF

108B

STOR

108D

BUF

108A

ANTE

BD108

BUF

108C

VENDING

CB52

TR

CB52A

ELECTRICAL

CB13B-42

COMMUNICATIONS

CLOSET

CB13A-42

1. ALL DOOR FRAMES TO BE LOCATED 4" FROM OUTSIDE OF FRAME TO FINISH FACE OF

ADJACENT WALL UNLESS NOTED OTHERWISE.

2. ALL WALL IN-FILL TO MATCH EXSITING OR ADJACENT WALL TYPE CONSTRUCTION. REFER TO

PARTITION TYPES (ON SHEET AE601) FOR WALL TYPES.

3. REFER TO DOOR SCHEDULE & DETAILS SHEET (AE601) FOR DOOR INFORMATION.

4. ALL WALLS ARE DIMENSIONED TO CENTERLINE OF METAL STUD, UNLESS NOTED OTHERWISE.

5. BLOCK OUT SLAB FOR PENETRATIONS SHALL BE 2" LARGER THAN DUCT SIZE TO ALLOW

TOLERANCE FOR DUCT PASSAGE AND FIRE SAFING. COORDINATE WITH MEP FOR DUCT SIZES.

6. FURR AROUND ALL COLUMN PROTRUSIONS AS NEEDED UNLESS NOTED OTHERWISE.

7. REFER TO SHEET AF711 FOR FINISH MATERIAL INFORMATION.

GENERAL PLAN NOTES

MOD-4

MOD-3

MOD-1

N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024

JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023

CIVIL/ STRUCTURAL ENGINEER

OATES ASSOCIATES

100 LANTER COURT, SUITE 1

COLLINSVILLE, IL 62234

(618) 345-2200

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

2519 MADISON AVE. STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

DATA/COMM CONSULTANT

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

EHRM INFRASTRUCTURE

UPGRADESCOMMISSIONING AGENT

ES2

13401 N. SANTA FE AVE.

OKLAHOMA, OK 73114

(405) 528-4500

/1

/2

:4 :3

A

M

REFERENCE PLANS - BLDG 42

NR 078 205NR

FINAL BID DOCUMENTS

4/20/2023

657A5-21-700

MARION VA MEDICAL CENTER

2401 WEST MAIN ST. | MARION, IL

62959

AE103

SPUR #: 2114

N

1/16" = 1'-0"

REFERENCE PLAN - BLDG 42 LEVEL G1

1" = 400'-0"

KEY PLAN

DN

EX

DN

EX

DN

EX

DN

EX

1. ALL DOOR FRAMES TO BE LOCATED 4" FROM OUTSIDE OF FRAME TO FINISH FACE OF

ADJACENT WALL UNLESS NOTED OTHERWISE.

2. ALL WALL IN-FILL TO MATCH EXSITING OR ADJACENT WALL TYPE CONSTRUCTION. REFER TO

PARTITION TYPES (ON SHEET AE601) FOR WALL TYPES.

3. REFER TO DOOR SCHEDULE & DETAILS SHEET (AE601) FOR DOOR INFORMATION.

4. ALL WALLS ARE DIMENSIONED TO CENTERLINE OF METAL STUD, UNLESS NOTED OTHERWISE.

5. BLOCK OUT SLAB FOR PENETRATIONS SHALL BE 2" LARGER THAN DUCT SIZE TO ALLOW

TOLERANCE FOR DUCT PASSAGE AND FIRE SAFING. COORDINATE WITH MEP FOR DUCT SIZES.

6. FURR AROUND ALL COLUMN PROTRUSIONS AS NEEDED UNLESS NOTED OTHERWISE.

7. REFER TO SHEET AF711 FOR FINISH MATERIAL INFORMATION.

GENERAL PLAN NOTES

AE408

AE408

EMERG.

GEN.

ELECT.

EQUIP.

SERVING

MECHANICAL

SOILED

LINEN

HKS

PATIO

PHYSICAL

ACTIVITIES

RECREATION

DINING

1 BED

1 BED

1 BED

110 2 BED

2 BED

2 BED

2 BED

2 BED

2 BED

4 BED

2 BED

2 BED

2 BED

PHYSICAL

THERAPY

OFFICE

OFFICE

100A

OFFICE

100B

OFFICE

OFFCE

CLASSROOM

CONFERENCE

LOBBY

VESTIBULE

HR LINK

N.W. ELEC.

HAC

4 BED

CONG BATH

RR

CLEAN

SOILED

MECH

2 BED

2 BED

2 BED

2 BED

2 BED

2 BED

2 BED

2 BED

2 BED

2 BED

2 BED

1 BED

1 BED

1 BED

HOSPICE

STORAGE

TREATMENT

TEL

ELC

HAC

MED

TEAM

NURSE

OFF

OFF

RR

RR

OFF

LOUNGE

OFF

LOCKER

LOCKER

STORAGE

169B

STR.

169A

STR.

RR

170A

AE408

AE408

EDUC

DAY ROOM

DAY ROOM

150 DINING

EXERCISE

CONF

WAITING

OFFICE

OFF

OFF

OFF

OFF

OFF

DINING RM

SUPPLY

HSKP

STOR

KITCHEN

HSKP

SOILED

ELEC

SOILED

STOR

STOR

BED

STOR

BED

BED

LAUNDRY

MECH

BED

BED

BED

BED

BED

BED

OFF

OFF

OFF

BED

BED

SHOWER

GROUP

ROOM

BED

BED

STAFF

BED

COMMUNICATION

CENTER

EXAM

MED

CONSULT

WAITING

101B

BED

RR

104A

RR

OFFICE

TR

AE409

AE409

WAITING

RR

RR

RECPT

OFFICE

OFFICE

OPEN

OFFICE

OFFICE

OFFICE

EXAM

EXAM

EXAM

EXAM

EXAM

EXAM

EXAM

EXAM

EXAM

STOR

PRO OFF

PT WS

PRO DS

152 OPEN GYM

RR

RR

HAC

OFFICE

EXAM

EXAM

EXAM

SHARED OFF

EXAM

EXAM

RR

RR

LG GROUP

EXAM

EXAM

EXAM

EXAM

PROSTHESIS

SUPPLY

THERAPY

BATH

EQUIP

DRESS

130A

STOR

SUPPLY

MECH

BREAK

LOCKER

LOCKER

TR

OFFICE

MOD-4

MOD-3

MOD-1

N

N

1/16" = 1'-0"

REFERENCE PLAN - BLDG 43 LEVEL G1

N

1/16" = 1'-0"

REFERENCE PLAN - BLDG 81 LEVEL 12

N

1/16" = 1'-0"

REFERENCE PLAN - BLDG 82 LEVEL 13

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024

JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023

CIVIL/ STRUCTURAL ENGINEER

OATES ASSOCIATES

100 LANTER COURT, SUITE 1

COLLINSVILLE, IL 62234

(618) 345-2200

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

2519 MADISON AVE. STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

DATA/COMM CONSULTANT

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

EHRM INFRASTRUCTURE

UPGRADESCOMMISSIONING AGENT

ES2

13401 N. SANTA FE AVE.

OKLAHOMA, OK 73114

(405) 528-4500

/1

/2

:4 :4

A

M

REFERENCE PLANS - BLDG 43, 81, 82

NR 079 205NR

FINAL BID DOCUMENTS

4/20/2023

657A5-21-700

MARION VA MEDICAL CENTER

2401 WEST MAIN ST. | MARION, IL

62959

AE104

SPUR #: 2114

1" = 400'-0"

KEY PLAN

43, 81, 82

UP UP

EX

EX

EX

EX

FEC

AE409

AE409

OFFICE

OFFICE

OFFICE

OFFICE

RECPT

OFFICE

OFFICE

OFFICE

OFFICE

SPECIAL

PROGRAMS

COUNSEL

OFFICE

COUNSEL

COUNSEL

OFFICE

RR

OFFICE

OFFICE

OFFICE

OFFICE

TESTING

TESTING

GROUP

GROUP

GROUP

GROUP

246ELEC

RR

RR

HAC

STOR

251A

WORK

OFFICE

ADMIN

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

TR

AE409

AE409

GROUP

ACTIVITY

PANTRY

KITCHEN

WAITING

VEST

GROUP

STORAGE

RECEIVING

ELECTRICAL

EQUIP

LOUNGE

OFFICE

128OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

TREAT

MED

115A

EXAM

EXAM

EXAM

CONTROL

OFFICE

EXAM

COUNSEL

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

NAME

RR

RR

GROUP

GROUP

GROUP

RR

RR

EQUIP

HAC

STOR

RR

TR

AE410

AE410

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

CODING

COPY

HAC

OFF

OFF

OFFICE

CREDENTIAL

PRIVILEGING

COMMUNITY

HEALTH

NURSING

SERVICE

NAME

CODING

COMPUTER/NEO

TRAINING

RM

REC MGR

AND CODING

STAFF

OFFICE

OFFICE

HR

OFFICE

COPY

VETERNS

TRANSPORT

HR

OFFICE

OFFICE

OFFICE

OFFICE

PRIMARY

CARE

TR

AE410

AE410

AE410

AE410

OPEN

OFFICE

OFFICE

OFFICE

OFFICE

RR

RR

STORAGE

AE410

AE410

AE410

AE410

OFFICE

OPEN

OFFICE

OFFICE

OFFICE

OFFICE

TR

OFFICE

OFFICE

RR

STORAGE

RR

OFFICE

108A

1. ALL DOOR FRAMES TO BE LOCATED 4" FROM OUTSIDE OF FRAME TO FINISH FACE OF

ADJACENT WALL UNLESS NOTED OTHERWISE.

2. ALL WALL IN-FILL TO MATCH EXSITING OR ADJACENT WALL TYPE CONSTRUCTION. REFER TO

PARTITION TYPES (ON SHEET AE601) FOR WALL TYPES.

3. REFER TO DOOR SCHEDULE & DETAILS SHEET (AE601) FOR DOOR INFORMATION.

4. ALL WALLS ARE DIMENSIONED TO CENTERLINE OF METAL STUD, UNLESS NOTED OTHERWISE.

5. BLOCK OUT SLAB FOR PENETRATIONS SHALL BE 2" LARGER THAN DUCT SIZE TO ALLOW

TOLERANCE FOR DUCT PASSAGE AND FIRE SAFING. COORDINATE WITH MEP FOR DUCT SIZES.

6. FURR AROUND ALL COLUMN PROTRUSIONS AS NEEDED UNLESS NOTED OTHERWISE.

7. REFER TO SHEET AF711 FOR FINISH MATERIAL INFORMATION.

GENERAL PLAN NOTES

MOD-4

MOD-3

MOD-1

N

N

1/16" = 1'-0"

REFERENCE PLAN - BLDG 83 LEVEL 22

N

1/16" = 1'-0"

REFERENCE PLAN - BLDG 83 LEVEL 11

N

1/16" = 1'-0"

REFERENCE PLAN - MOD-13

N

1/16" = 1'-0"

REFERENCE PLAN - MOD-34

N

1/16" = 1'-0"

REFERENCE PLAN - MOD-45

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024

JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023

CIVIL/ STRUCTURAL ENGINEER

OATES ASSOCIATES

100 LANTER COURT, SUITE 1

COLLINSVILLE, IL 62234

(618) 345-2200

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

2519 MADISON AVE. STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

DATA/COMM CONSULTANT

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

EHRM INFRASTRUCTURE

UPGRADESCOMMISSIONING AGENT

ES2

13401 N. SANTA FE AVE.

OKLAHOMA, OK 73114

(405) 528-4500

/1

/2

:4 :4

A

M

REFERENCE PLANS - BLDG 83, MOD-1, 3,

NR 080 205NR

FINAL BID DOCUMENTS

4/20/2023

657A5-21-700

MARION VA MEDICAL CENTER

2401 WEST MAIN ST. | MARION, IL

62959

AE105

SPUR #: 2114

1" = 400'-0"

KEY PLAN

BLDG 83 AND MOD 1, 3, 4, & 7

LEVEL GROUND

0"

LEVEL 1

12'-0"

LEVEL 2

24'-4"

LEVEL 3

35'-10"

LEVEL 4

47'-4"

LEVEL 5

61'-9"

A B

ROOF

59'-8"

D

AE201

AE201

-3

B

-4

B

TR

418B

TR

312B

TR

237A

TR

123C

TR

LEVEL GROUND

0"

LEVEL 1

12'-0"

LEVEL 2

24'-4"

LEVEL 3

35'-10"

LEVEL 4

47'-4"

LEVEL 5

61'-9"

A B

7'-10"

ROOF

59'-8"

EXPANSION JOINT TO

ALGIN WITH EXISTING

CONTROL JOINT, TYP.

NEW EIFS

EXTERIOR WALL

NEW CMU WALL

8' -8

STUCCO CONTROL

JOINT, TYP.

6' -4

/4

5'

-1

/4

6' -4

/4

5'

-1

/4

6' -1

1/

4" 5'

-1 0"

6' -4

/4

5'

-1

/4

5' -1

/4

5'

-1

/4

4' -3

/4

EXISTING SEISMIC

TOWER

NEW TR TOWER TO

ALIGN WITH TOP OF

EXISTING

EXISTING CONTROL

JOINT

D

DOWNSPOUT

1'

-9

F V

LEVEL GROUND

0"

LEVEL 1

12'-0"

LEVEL 2

24'-4"

LEVEL 3

35'-10"

LEVEL 4

47'-4"

LEVEL 5

61'-9"

AE201

ROOF

59'-8"

AE201

AE201

-2

A

-1

C

-1

TR

418B

TR

312B

TR

237A

TR

123C

TR

AE201

LEVEL GROUND

0"

LEVEL 1

12'-0"

LEVEL 2

24'-4"

LEVEL 3

35'-10"

LEVEL 4

47'-4"

LEVEL 5

61'-9"

AE201

ROOF

59'-8"

-1

M

TR

312B

TR

237A

TR

123C

TR

TR

418B

A

7.88

5.017.88

ALIGN TYP.

B

D

7.88

5.01 7.88

LEVEL 3

35'-10"

5.01

3.05

9.89

7.87

9.87

9.12

7.107

7.106

6.07

7.104

5.32

5.33

A B

AE201

AE201

AE201

D

1/ 4"

1'

-0

7.63

7.87

7.887.88

7.887.88

7.881/4" / 1'-0"

7.88

7.108

LEVEL 3

35'-10"

B D

5.01

3.05

9.89

7.88

LEVEL 4

47'-4"

A

5.01

3.05

9.89

5.29

7.88

B

D

7.885.01

5.29

7.88

ALIGN

LEVEL 5

61'-9"

ROOF

59'-8"

5.01

7.87

9.87

7.104

7.106

6.07

7.107

9.12

7.18

7.94

9.88

7.02

5.29

7.90

7.104

7.103

6.07

5.10

5.33

5.32

LEVEL 5

61'-9"

ROOF

59'-8"

5.01

9.87

7.104

7.106

6.07

7.107

9.12

7.94

9.88

5.29

7.104

7.103

6.07

5.10

5.33

5.32 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024

JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023

CIVIL/ STRUCTURAL ENGINEER

OATES ASSOCIATES

100 LANTER COURT, SUITE 1

COLLINSVILLE, IL 62234

(618) 345-2200

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

2519 MADISON AVE. STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

DATA/COMM CONSULTANT

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

EHRM INFRASTRUCTURE

UPGRADESCOMMISSIONING AGENT

ES2

13401 N. SANTA FE AVE.

OKLAHOMA, OK 73114

(405) 528-4500

/1

/2

:4 :5

A

M

BUILDING ELEVATION AND SECTION

NR 081 205NR

FINAL BID DOCUMENTS

4/20/2023

657A5-21-700

MARION VA MEDICAL CENTER

2401 WEST MAIN ST. | MARION, IL

62959

AE201

SPUR #: 2114

1/8" = 1'-0" 3/ AE201

BUILDING SECTION2 1/8" = 1'-0" 1/ AE102

BUILDING ELEVATION11/8" = 1'-0" 8/ AE201

BUILDING SECTION31/8" = 1'-0" 8/ AE201

BUILDING SECTION4

KEYNOTE LEGEND

3.05 COMPOSITE CONCRETE DECK, REF: STRUCTURAL

5.01 STRUCTURAL STEEL, REF: STRUCTURAL

5.10 METAL DECK

5.29 HSS BRACING, REF: STRUCTURAL

5.32 METAL STUD SLIDE CLIP, REF: STRUCTURAL

5.33 L5X5X1/4" STEEL ANGLE, REF: STRUCTURAL

6.07 1/2" EXTERIOR SHEATHING

7.02 BACKER-ROD & SEALANT, COLOR MATCH TO WALL FINISH

7.18 SCUPPER

7.63 THRU-WALL SCUPPER

7.87 DOWNSPOUT

7.88 2" EXPANSION JOINT

7.90 FLASHING STRIP

7.94 PREFINISHED ALUMINUM COPING

7.103 INSULATION AND MEMBRANE. REF: SPECS

7.104 AIR/WATER BARRIER

7.106 1 1/2" POLYISO RIGID INSULATION

7.107 5 1/2" BATT INSULATION

7.108 EXISTING SCUPPER TO REMAIN, REF: DETAIL 9/AE102 FOR SIMILAR CONDITION. FLASH AS

REQUIRED TO DRAIN ONTO NEW ROOF

9.12 1/2" GYPSUM WALL BOARD

9.87 STUCCO

9.88 2-7/8" CASING BEAD

9.89 FLOORING, REF: FINISH FLOOR SCHEDULE

N

1" = 1'-0" 2/ AE404

EXPANSION JOINT PLAN DETAIL6

N

1" = 1'-0" 2/ AE404

EXPANSION JOINT PLAN DETAIL5

1" = 1'-0" 3/ AE201

SECTION DETAIL13

N

1/4" = 1'-0"

ROOF PLAN8

1" = 1'-0" 2/ AE201

SECTION DETAIL111" = 1'-0" 2/ AE201

SECTION DETAIL12

N

1" = 1'-0" 2/ AE406

EXPANSION JOINT PLAN DETAIL7

No. REVISION DESCRIPTION DATE

1 1/2" = 1'-0" 3/ AE201

SCUPPER DETAIL91 1/2" = 1'-0" 3/ AE201

PARAPET DETAIL10

TR

C

2.12

2.18

2.20

+/- 18'-5" FV

'-1

F

V

+/- 2'-1" FV +/- 8'-3 1/2" FV +/- 8'-1" FV

'-6

F

V

3' -8

125 SF

TR

+/- 18'-5" FV

C

'-1

F

V

'-6

F

V

5'-1 7/8" 2'-5" 10'-10 1/4"

1/

2" 1'

-8

/2

1/

2"

1' -8

/2

3'

-7

10.31

8-107

+/- 2'-1" FV +/- 8'-3 1/2" FV +/- 8'-1" FV

26.0726.07

9.01

4"

STORAGE

CORRIDOR

STORAGE

4A

2.12 2.14

+/- 4'-0" FV +/- 9'-6 1/2" FV

+/- 13'-6 1/2" FV

6'

-1

1/ 2"

F V

+/- 6'-0 1/2" FV

2'

-2

F V

2.26

75 SF

STORAGE

191 SF

TR

4A

+/- 4'-0" FV +/- 9'-6 1/2" FV

+/- 13'-6 1/2" FV

-4

A

CORRIDOR

A

LI

G N

ALIGN

D3

D3

6'

-1

1/ 2"

F V

7' -9

1'

-8

1/

2" 1'

-8

5' -3

4'-1" 2'-5" 3'-8 1/2"

10.31

+/- 6'-0 1/2" FV

2'

-2

F V

10.319.76

26.05

R.R.

103A

OFFICE

103B

D

E

2.13

2.19

'-9

/2

F

V

'-9

/2

F V

5'

-0

F V

+/- 6'-3 1/2" FV

+/- 6'-2 1/2" FV

43 SF

R.R.

103A

258 SF

OFFICE

103B

'-9

/2

F

V

'-9

/2

F V

5'

-0

F V

+/- 6'-3 1/2" FV

D

E

10.32

+/- 6'-2 1/2" FV

MOD-4

MOD-3

MOD-1

7N

1. ALL DOOR FRAMES TO BE LOCATED 4" FROM OUTSIDE OF FRAME TO FINISH FACE OF

ADJACENT WALL UNLESS NOTED OTHERWISE.

2. ALL WALL IN-FILL TO MATCH EXSITING OR ADJACENT WALL TYPE CONSTRUCTION. REFER TO

PARTITION TYPES (ON SHEET AE601) FOR WALL TYPES.

3. REFER TO DOOR SCHEDULE & DETAILS SHEET (AE601) FOR DOOR INFORMATION.

4. ALL WALLS ARE DIMENSIONED TO CENTERLINE OF METAL STUD, UNLESS NOTED OTHERWISE.

5. BLOCK OUT SLAB FOR PENETRATIONS SHALL BE 2" LARGER THAN DUCT SIZE TO ALLOW

TOLERANCE FOR DUCT PASSAGE AND FIRE SAFING. COORDINATE WITH MEP FOR DUCT SIZES.

6. FURR AROUND ALL COLUMN PROTRUSIONS AS NEEDED UNLESS NOTED OTHERWISE.

7. REFER TO SHEET AF711 FOR FINISH MATERIAL INFORMATION.

GENERAL PLAN NOTES

1. ALL EXISTING WALL DIMENSIONS ARE TO FINISH FACE, UNLESS OTHERWISE NOTED

2. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF AS-BUILT CONDITIONS, AND NOTIFY THE

ARCHITECT IN WRITING OF ANY DISCREPANCIES. ALL INFORMATION SHOWN ON THE

CONSTRUCTION DOCUMENTS IS BASED ON FIELD OBSERVATIONS AND/OR THE ORIGINAL

CONSTRUCTION DOCUMENTS OF THE FACILITY.

3. DEMOLITION AND CONSTRUCTION WORK MUST BE DONE UNDER NEGATIVE PRESSURE UTILIZING

HEPA FILTRATION UNITS. SEE INFECTION CONTROL NOTES.

4. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT OT AREA HAS BEEN

INSPECTED BY THE VA CAMPUS SAFETY OFFICER AND INFECTION CONTROL COORDINATOR AND

THOROUGHLY CLEANED BY ENVIRONMENTAL MANAGEMENT SERVICES

5. THE CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR EXISTING FLOOR, WALL AND

CEILING FINISHES IN EXISTING AREAS NOT DESIGNATED FOR DEMOLITION OR NEW

CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGE

CAUSED BY HIS WORK OR ANY SUBCONTRACTOR.

6. THE CONTRACTOR SHALL VERIFY THAT NEW MECHANICAL SYSTEMS CAN BE INSTALLED IN

EXISTING SPACES TO CLEAR EXISTING CEILING AND OTHER CONSTRUCTED ITEMS AND MAINTAIN

FLOOR TO CEILING HEIGHTS INDICATED ON DRAWINGS. IF DISCREPANCIES OCCUR DUE TO

EXISTING CONDITIONS, CONSULT WITH THE ARCHITECT BEFORE PROCEEDING.

7. THE FINISH FACE OF MATERIAL OF NEW PARTITIONS SHALL ALIGN ON BOTH SIDES OF THE PARTITION WITH THE FACE OF THE MATERIALS ON EXISTING COLUMNS, WALLS, OR PARTITIONS, UNLESS NOTED OTHERWISE.

8. NO WORK TO BE DONE IN AREAS HATCHED GRAY IN PLANS, HOWEVER WORK MIGHT NEED TO BE

PERFORMED IN CEILING OR EXISTING CHASES THROUGHOUT BUILDING. REFERENCE

MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT OF WORK. COORDINATE ACCESS TO

ROOMS OUTSIDE OF SCOPE WITH OWNER

GENERAL DEMOLITION NOTES

1. AREAS OF EXISTING CEILING, CEILING GRID, LIGHTING ETC. TO BE PROTECTED DURING

CONTRUCTION. CONTRACTOR TO REPLACE ANY DAMAGED ELEMENTS WITH NEW TO MATCH

EXISTING.

2. ALL NEW CEILING GRID TO BE CENTERED WITHIN ROOM, UNO.

3. ALL EXPOSED CEILINGS TO BE PAINTED P1, UNO.

4. ALL LIGHTING TO BE CENTERED IN ROOM, UNO..

5. PROVIDE HOLD DOWN CLIPS AT VESTIBULES AND AREA NEAR EGRESS DOORS.

GENERAL REFLECTED CEILING PLAN NOTES

EXISTING WALL TO BE DEMOLISHED

EXISTING WALL TO REMAIN

NEW NON-RATED WALLS

PARTITION LEGEND

EXISTING DOOR AND

FRAME TO BE DEMOLISHED

10.30

TR

+/- 18'-5" FV

'-1

F

V

+/- 2'-1" FV +/- 8'-3 1/2" FV +/- 8'-1" FV

'-6

F

V

9.85

TR

4A

STORAGE

10.30

+/- 4'-0" FV +/- 9'-6 1/2" FV

+/- 13'-6 1/2" FV

6'

-1

1/ 2"

F V

+/- 6'-0 1/2" FV

2'

-2

F V

2'-3 1/2" 6'-0" 1'-11"

+/- 10'-2 1/2" FV

3' -8

/2

4'

-0

4' -0

/2

5'

-2

9.85

TR

4A

STORAGE

+/- 4'-0" FV +/- 9'-6 1/2" FV

+/- 13'-6 1/2" FV

6'

-1

1/ 2"

F V

+/- 6'-0 1/2" FV

2'

-2

F V

2.22

EXIT LIGHT

2' x 2' ACOUSTICAL CEILING

TO BE REMOVED

2 x 2 EXISTING LIGHT FIXTURE

TO BE REMOVED

CEILING HEIGHT, ABOVE

FINISH FLOOR

2 x 4 LIGHT FIXTURE TO

BE REMOVED

00'-00"

REFLECTED CEILING PLAN LEGEND

2' x 4' ACOUSTICAL

CEILING

RETURN AIR GRILLE

SUPPLY AIR GRILLE

EXHAUST AIR GRILLE

EXISTING SUSPENDED

LIGHT FIXTURE

2' x 4' ACOUSTICAL

CEILING TO BE REMOVED

2' x 2' ACOUSTICAL

CEILING

1 x 4 LIGHT FIXTURE TO

BE REMOVED

2 x 4 LIGHT FIXTURE

REF: ELECTRICAL

1 x 4 LIGHT FIXTURE

REF: ELECTRICAL

CAN LIGHT

REF: ELECTRICAL

EXISTING CAN LIGHT TO

BE REMOVED

SUSPENDED LIGHT FIXTURE

TO BE REMOVED

TR

+/- 18'-5" FV

'-1

F

V

+/- 2'-1" FV +/- 8'-3 1/2" FV +/- 8'-1" FV

'-6

F

V th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024

JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023

CIVIL/ STRUCTURAL ENGINEER

OATES ASSOCIATES

100 LANTER COURT, SUITE 1

COLLINSVILLE, IL 62234

(618) 345-2200

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

2519 MADISON AVE. STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

DATA/COMM CONSULTANT

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

EHRM INFRASTRUCTURE

UPGRADESCOMMISSIONING AGENT

ES2

13401 N. SANTA FE AVE.

OKLAHOMA, OK 73114

(405) 528-4500

/1

/2

:4 :5

A

M

ENLARGED PLANS - BLDG 8, 13, 14

NR 082 205NR

FINAL BID DOCUMENTS

4/20/2023

657A5-21-700

MARION VA MEDICAL CENTER

2401 WEST MAIN ST. | MARION, IL

62959

AE401

SPUR #: 2114

N

1/4" = 1'-0" 1/ AE101

BLDG 8 - LEVEL 1 - 107 - DEMOLITION PLAN1

N

1/4" = 1'-0" 1/ AE101

BLDG 8 - LEVEL 1 - 107 - FLOOR PLAN2

N

1/4" = 1'-0" 2/ AE101

BLDG 13 - LEVEL G - 4A - DEMOLITION PLAN5

N

1/4" = 1'-0" 2/ AE101

BLDG 13 - LEVEL G - 4A - FLOOR PLAN6

N

1/4" = 1'-0" 3/ AE101

BLDG 14 - LEVEL 2 - 103B - DEMOLITION PLAN9

N

1/4" = 1'-0" 3/ AE101

BLDG 14 - LEVEL 2 - 103B - FLOOR PLAN10

8, 13, 14

1" = 400'-0"

KEY PLAN

KEYNOTE LEGEND

2.12 CONTRACTOR TO PATCH AND REPAIR ALL FLOORING AND WALLS WHERE EQUIPMENT IS

BEING REMOVED (TYP). FLOORS WITH EXPOSED CONCRETE WILL NEED TO BE GROUND

SMOOTH WHERE RACKS WERE BOLTED DOWN

2.13 PREPARE WALL FOR NEW TR EQUIPMENT

2.14 PREPARE FLOORING AND WALLS FOR NEW FINISHES

2.18 DEMOLISH NETWORK RACK AND ASSOCIATED DATA AND TELEPHONE CABLING AFTER

CUT-OVER. REF: TELECOM

2.19 DEMOLISH EQUIPMENT. REF: ELECTRICAL

2.20 DEMOLISH EQUIPMENT. REF: MECHANICAL

2.22 OPEN TO BOTTOM OF DECK ABOVE

2.26 EXISTING ACU, REF: MECHANICAL

9.01 WALL INFILL TO MATCH CONSTRUCTION, TEXTURE, AND FINISH OF ADJACENT WALL

9.76 PAINT TO MATCH EXISTING

9.85 NO CEILING, OPEN TO ABOVE

10.30 CABLE TRAY (ABOVE), REFER TO TECHNOLOGY

10.31 TELECOMMUNICATION RACK, REFER TO TECHNOLOGY

10.32 TELECOMMUNICATION RACK MOUNTED ON WALL. SECURITY GATE AROUND UNIT. REFER TO

TECHNOLOGY

26.05 TRANSFORMER, REF: ELECTRICAL

26.07 ELECTRICAL PANEL, REF: ELECTRICAL

N

1/4" = 1'-0"

BLDG 8 - LEVEL 1 - 107 - RCP4

N

1/4" = 1'-0"

BLDG 13 - LEVEL G - 4A - RCP8

N

1/4" = 1'-0"

BLDG 13 - LEVEL G - 4A - DEMOLITION RCP7

N

1/4" = 1'-0"

BLDG 8 - LEVEL 1 - 107 - DEMOLITION RCP3

B

2.12

OI&T ROOM

101D

B

TR

101D

10.31

3'-0" 1'-8 1/2" 5'-4 1/2"

+/- 10'-0 1/2" FV

0'

-2

/2

F V

4' -1

2'

-5

3' -8

/2

15-101D

26.0726.07

TELEPHONE

CLOSET

105C

OFFICE SPACE

105A

15'-4" 3'-8"

+/- 28'-5" FV

4'

-1

/2

F V

8 9

C

2.02

2.02

9'-5"

2.14

13'-11 1/2" 3'-4"

2'

-4

F V

'-9

/2

F

V

5'

-2

F V

TELEPHONE

CLOSET

105C

127 SF

TR

105D

286 SF

OFFICE SPACE

105A

-1

A

8 9

C

D3

10.31

16-105D

9'-2 1/2" 19'-2 1/2"

4'

-1

/2

F V

2'

-4

F V

'-9

/2

F

V

+/- 28'-5" FV

7' -4

/2

1'

-8

/2

5' -0

/2

3'-3 1/2" 2'-5" 3'-3 1/2"

5'

-2

F V

26.07

MOD-4

MOD-3

MOD-1

N

8 9

C

+/- 28'-5" FV

4'

-1

/2

F V

2'

-4

F V

'-9

/2

F

V

5'

-2

F V

8 9

C

OFFICE SPACE

105A

TR

105D

TELEPHONE

CLOSET

105C

9'-0"

AT2

9.85

10.30+

4'

-1

/2

F V

2'

-4

F V

'-9

/2

F

V

+/- 28'-5" FV

5'

-2

F V

2'-1" 4'-9" 2'-2"

E Q

6' -4

E

Q

23.04

26.06 26.07

TR

101D

10.31

+/- 10'-0 1/2" FV

0'

-2

/2

F V

2' -4

/2

6'

-0

1' -1

0"

EQ 4'-0" EQ

9.85

26.06

OI&T ROOM

101D

+/- 10'-0 1/2" FV

0'

-2

/2

F V

2.27

1. ALL DOOR FRAMES TO BE LOCATED 4" FROM OUTSIDE OF FRAME TO FINISH FACE OF

ADJACENT WALL UNLESS NOTED OTHERWISE.

2. ALL WALL IN-FILL TO MATCH EXSITING OR ADJACENT WALL TYPE CONSTRUCTION. REFER TO

PARTITION TYPES (ON SHEET AE601) FOR WALL TYPES.

3. REFER TO DOOR SCHEDULE & DETAILS SHEET (AE601) FOR DOOR INFORMATION.

4. ALL WALLS ARE DIMENSIONED TO CENTERLINE OF METAL STUD, UNLESS NOTED OTHERWISE.

5. BLOCK OUT SLAB FOR PENETRATIONS SHALL BE 2" LARGER THAN DUCT SIZE TO ALLOW

TOLERANCE FOR DUCT PASSAGE AND FIRE SAFING. COORDINATE WITH MEP FOR DUCT SIZES.

6. FURR AROUND ALL COLUMN PROTRUSIONS AS NEEDED UNLESS NOTED OTHERWISE.

7. REFER TO SHEET AF711 FOR FINISH MATERIAL INFORMATION.

GENERAL PLAN NOTES

1. ALL EXISTING WALL DIMENSIONS ARE TO FINISH FACE, UNLESS OTHERWISE NOTED

2. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF AS-BUILT CONDITIONS, AND NOTIFY THE

ARCHITECT IN WRITING OF ANY DISCREPANCIES. ALL INFORMATION SHOWN ON THE

CONSTRUCTION DOCUMENTS IS BASED ON FIELD OBSERVATIONS AND/OR THE ORIGINAL

CONSTRUCTION DOCUMENTS OF THE FACILITY.

3. DEMOLITION AND CONSTRUCTION WORK MUST BE DONE UNDER NEGATIVE PRESSURE UTILIZING

HEPA FILTRATION UNITS. SEE INFECTION CONTROL NOTES.

4. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT OT AREA HAS BEEN

INSPECTED BY THE VA CAMPUS SAFETY OFFICER AND INFECTION CONTROL COORDINATOR AND

THOROUGHLY CLEANED BY ENVIRONMENTAL MANAGEMENT SERVICES

5. THE CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR EXISTING FLOOR, WALL AND

CEILING FINISHES IN EXISTING AREAS NOT DESIGNATED FOR DEMOLITION OR NEW

CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGE

CAUSED BY HIS WORK OR ANY SUBCONTRACTOR.

6. THE CONTRACTOR SHALL VERIFY THAT NEW MECHANICAL SYSTEMS CAN BE INSTALLED IN

EXISTING SPACES TO CLEAR EXISTING CEILING AND OTHER CONSTRUCTED ITEMS AND MAINTAIN

FLOOR TO CEILING HEIGHTS INDICATED ON DRAWINGS. IF DISCREPANCIES OCCUR DUE TO

EXISTING CONDITIONS, CONSULT WITH THE ARCHITECT BEFORE PROCEEDING.

7. THE FINISH FACE OF MATERIAL OF NEW PARTITIONS SHALL ALIGN ON BOTH SIDES OF THE PARTITION WITH THE FACE OF THE MATERIALS ON EXISTING COLUMNS, WALLS, OR PARTITIONS, UNLESS NOTED OTHERWISE.

8. NO WORK TO BE DONE IN AREAS HATCHED GRAY IN PLANS, HOWEVER WORK MIGHT NEED TO BE

PERFORMED IN CEILING OR EXISTING CHASES THROUGHOUT BUILDING. REFERENCE

MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT OF WORK. COORDINATE ACCESS TO

ROOMS OUTSIDE OF SCOPE WITH OWNER

GENERAL DEMOLITION NOTES

EXISTING WALL TO BE DEMOLISHED

EXISTING WALL TO REMAIN

NEW NON-RATED WALLS

PARTITION LEGEND

EXISTING DOOR AND

FRAME TO BE DEMOLISHED

EXIT LIGHT

2' x 2' ACOUSTICAL CEILING

TO BE REMOVED

2 x 2 EXISTING LIGHT FIXTURE

TO BE REMOVED

CEILING HEIGHT, ABOVE

FINISH FLOOR

2 x 4 LIGHT FIXTURE TO

BE REMOVED

00'-00"

REFLECTED CEILING PLAN LEGEND

2' x 4' ACOUSTICAL

CEILING

RETURN AIR GRILLE

SUPPLY AIR GRILLE

EXHAUST AIR GRILLE

EXISTING SUSPENDED

LIGHT FIXTURE

2' x 4' ACOUSTICAL

CEILING TO BE REMOVED

2' x 2' ACOUSTICAL

CEILING

1 x 4 LIGHT FIXTURE TO

BE REMOVED

2 x 4 LIGHT FIXTURE

REF: ELECTRICAL

1 x 4 LIGHT FIXTURE

REF: ELECTRICAL

CAN LIGHT

REF: ELECTRICAL

EXISTING CAN LIGHT TO

BE REMOVED

SUSPENDED LIGHT FIXTURE

TO BE REMOVED

1. AREAS OF EXISTING CEILING, CEILING GRID, LIGHTING ETC. TO BE PROTECTED DURING

CONTRUCTION. CONTRACTOR TO REPLACE ANY DAMAGED ELEMENTS WITH NEW TO MATCH

EXISTING.

2. ALL NEW CEILING GRID TO BE CENTERED WITHIN ROOM, UNO.

3. ALL EXPOSED CEILINGS TO BE PAINTED P1, UNO.

4. ALL LIGHTING TO BE CENTERED IN ROOM, UNO..

5. PROVIDE HOLD DOWN CLIPS AT VESTIBULES AND AREA NEAR EGRESS DOORS.

GENERAL REFLECTED CEILING PLAN NOTES

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024

JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023

CIVIL/ STRUCTURAL ENGINEER

OATES ASSOCIATES

100 LANTER COURT, SUITE 1

COLLINSVILLE, IL 62234

(618) 345-2200

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

2519 MADISON AVE. STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

DATA/COMM CONSULTANT

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

EHRM INFRASTRUCTURE

UPGRADESCOMMISSIONING AGENT

ES2

13401 N. SANTA FE AVE.

OKLAHOMA, OK 73114

(405) 528-4500

/1

/2

:4 :5

A

M

ENLARGED PLANS - BLDG 15 & 16

NR 083 205NR

FINAL BID DOCUMENTS

4/20/2023

657A5-21-700

MARION VA MEDICAL CENTER

2401 WEST MAIN ST. | MARION, IL

62959

AE402

SPUR #: 2114

N

1/4" = 1'-0" 4/ AE101

BLDG 15 - DEMOLITION PLAN1

N

1/4" = 1'-0" 4/ AE101

BLDG 15 - FLOOR PLAN2

N

1/4" = 1'-0" 5/ AE101

BLDG 16 - LEVEL G - DEMOLITION PLAN5

N

1/4" = 1'-0" 5/ AE101

BLDG 16 - LEVEL G - FLOOR PLAN6

15, 16

1" = 400'-0"

KEY PLAN

N

1/4" = 1'-0" 1/ AE201

BLDG 16 - LEVEL G - DEMOLITION RCP7

N

1/4" = 1'-0" 1/ AE201

BLDG 16 - LEVEL G - RCP8

KEYNOTE LEGEND

2.02 REMOVE WALL AS REQUIRED FOR NEW CONSTRUCTION

2.12 CONTRACTOR TO PATCH AND REPAIR ALL FLOORING AND WALLS WHERE EQUIPMENT IS

BEING REMOVED (TYP). FLOORS WITH EXPOSED CONCRETE WILL NEED TO BE GROUND

SMOOTH WHERE RACKS WERE BOLTED DOWN

2.14 PREPARE FLOORING AND WALLS FOR NEW FINISHES

2.27 DEMOLISH EXISTING ELECTRICAL BOX, INSTALL STEEL PLATE BELOW CONCRETE SLAB, FILL

WITH CONCRETE FOR A SMOTH SURFACE LEVEL WITH ADJACENT CONCRETE. REF: ELEC

9.85 NO CEILING, OPEN TO ABOVE

10.30 CABLE TRAY (ABOVE), REFER TO TECHNOLOGY

10.31 TELECOMMUNICATION RACK, REFER TO TECHNOLOGY

23.04 DUCTLESS SPLIT INDOOR UNIT, REF: MECHANICAL

26.06 GROUND BAR, REF: ELECTRICAL

26.07 ELECTRICAL PANEL, REF: ELECTRICAL

N

1/4" = 1'-0" 1/ AE201

BLDG 15 - RCP4

N

1/4" = 1'-0" 1/ AE201

BLDG 15 - DEMOLITION RCP3

MAIN

COMPUTER

ROOM

2.14

2'-0"

OFFICE

STAFF

+/- 29'-4" FV+/- 12'-5" FV

+/- 38'-6" FV

'-9

/2

F

V

+/- 18'-0" FV

1'

-1

1/ 2"

F V

1'

-1 1"

F V

9'

-7

/2

F V

2.18

2.19

2.19

2.19

2.242.24

2.242.242.24

2.23

963 SF

MAIN

COMPUTER

ROOM

OFFICE

STAFF

D3

D3

37-124A

+/- 31'-6 1/2" FV

'-9

/2

F

V

+/- 38'-6" FV

1'

-1

1/ 2"

F V

1'

-1 1"

F V

+/- 10'-11 1/2" FV

9'

-7

/2

F V

9.01

TR

AMERICAN

LEGION

VFW

+/- 10'-5 1/2" FV +/- 9'-3 1/2" FV

+/- 26'-8" FV

+/- 6'-1" FV

1'

-1

1/ 2"

F V

'-1

1" F

V

2.022.02

2.06 2.06

2.082.08

2.07

2.07

2.18

6"

84 SF

TR

9'-7 5/8" 9'-10 1/16" 7'-2 7/16"

113 SF

AMERICAN

LEGION

113 SF

VFW

+/- 26'-8" FV

1'

-1

1/ 2"

F V

-1

-1

-1

D3 D3

D3

D3

D3

10.31

6' -2

/2

2'

-5

3' -4

/2

2'-9 1/2" 1'-8 1/2" 2'-6 1/2"

ALIGN

9.019.01 9.01

26.07

1'-0"

MOD-4

MOD-3

MOD-1

N

AMERICAN

LEGION

VFW

TR

+/- 10'-5 1/2" FV +/- 9'-3 1/2" FV

+/- 26'-8" FV

+/- 6'-1" FV

1'

-1

1/ 2"

F V

'-1

1" F

V

2.22

MAIN

COMPUTER

ROOM

OFFICE

STAFF

2'-0"

+/- 29'-4" FV+/- 12'-5" FV

+/- 38'-6" FV

'-9

/2

F

V

9'

-7

/2

F V

AMERICAN

LEGION

VFW

TR

EXP9'-0"9'-0"

AT2AT2

9'-7 5/8" 9'-10 1/16" 7'-2 7/16"

+/- 26'-8" FV

2'

-0

F V

10.30

23.04

9.85

2' -0

7'

-7

/2

2' -4

EQ EQ

26.06

9'

-7

/2

F V

+/- 31'-6 1/2" FV

'-9

/2

F

V

+/- 38'-6" FV

+/- 10'-11 1/2" FV

MAIN

COMPUTER

ROOM

OFFICE

STAFF

10.30

2' -4

/2

8'

-0

8' -0

8'

-0

3' -3

E Q

E Q

8'-0" 8'-0" 8'-0" 8'-0" 3'-0 1/2"

9.85

1. ALL DOOR FRAMES TO BE LOCATED 4" FROM OUTSIDE OF FRAME TO FINISH FACE OF

ADJACENT WALL UNLESS NOTED OTHERWISE.

2. ALL WALL IN-FILL TO MATCH EXSITING OR ADJACENT WALL TYPE CONSTRUCTION. REFER TO

PARTITION TYPES (ON SHEET AE601) FOR WALL TYPES.

3. REFER TO DOOR SCHEDULE & DETAILS SHEET (AE601) FOR DOOR INFORMATION.

4. ALL WALLS ARE DIMENSIONED TO CENTERLINE OF METAL STUD, UNLESS NOTED OTHERWISE.

5. BLOCK OUT SLAB FOR PENETRATIONS SHALL BE 2" LARGER THAN DUCT SIZE TO ALLOW

TOLERANCE FOR DUCT PASSAGE AND FIRE SAFING. COORDINATE WITH MEP FOR DUCT SIZES.

6. FURR AROUND ALL COLUMN PROTRUSIONS AS NEEDED UNLESS NOTED OTHERWISE.

7. REFER TO SHEET AF711 FOR FINISH MATERIAL INFORMATION.

GENERAL PLAN NOTES

1. ALL EXISTING WALL DIMENSIONS ARE TO FINISH FACE, UNLESS OTHERWISE NOTED

2. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF AS-BUILT CONDITIONS, AND NOTIFY THE

ARCHITECT IN WRITING OF ANY DISCREPANCIES. ALL INFORMATION SHOWN ON THE

CONSTRUCTION DOCUMENTS IS BASED ON FIELD OBSERVATIONS AND/OR THE ORIGINAL

CONSTRUCTION DOCUMENTS OF THE FACILITY.

3. DEMOLITION AND CONSTRUCTION WORK MUST BE DONE UNDER NEGATIVE PRESSURE UTILIZING

HEPA FILTRATION UNITS. SEE INFECTION CONTROL NOTES.

4. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT OT AREA HAS BEEN

INSPECTED BY THE VA CAMPUS SAFETY OFFICER AND INFECTION CONTROL COORDINATOR AND

THOROUGHLY CLEANED BY ENVIRONMENTAL MANAGEMENT SERVICES

5. THE CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR EXISTING FLOOR, WALL AND

CEILING FINISHES IN EXISTING AREAS NOT DESIGNATED FOR DEMOLITION OR NEW

CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGE

CAUSED BY HIS WORK OR ANY SUBCONTRACTOR.

6. THE CONTRACTOR SHALL VERIFY THAT NEW MECHANICAL SYSTEMS CAN BE INSTALLED IN

EXISTING SPACES TO CLEAR EXISTING CEILING AND OTHER CONSTRUCTED ITEMS AND MAINTAIN

FLOOR TO CEILING HEIGHTS INDICATED ON DRAWINGS. IF DISCREPANCIES OCCUR DUE TO

EXISTING CONDITIONS, CONSULT WITH THE ARCHITECT BEFORE PROCEEDING.

7. THE FINISH FACE OF MATERIAL OF NEW PARTITIONS SHALL ALIGN ON BOTH SIDES OF THE PARTITION WITH THE FACE OF THE MATERIALS ON EXISTING COLUMNS, WALLS, OR PARTITIONS, UNLESS NOTED OTHERWISE.

8. NO WORK TO BE DONE IN AREAS HATCHED GRAY IN PLANS, HOWEVER WORK MIGHT NEED TO BE

PERFORMED IN CEILING OR EXISTING CHASES THROUGHOUT BUILDING. REFERENCE

MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT OF WORK. COORDINATE ACCESS TO

ROOMS OUTSIDE OF SCOPE WITH OWNER

GENERAL DEMOLITION NOTES

EXISTING WALL TO BE DEMOLISHED

EXISTING WALL TO REMAIN

NEW NON-RATED WALLS

PARTITION LEGEND

EXISTING DOOR AND

FRAME TO BE DEMOLISHED

EXIT LIGHT

2' x 2' ACOUSTICAL CEILING

TO BE REMOVED

2 x 2 EXISTING LIGHT FIXTURE

TO BE REMOVED

CEILING HEIGHT, ABOVE

FINISH FLOOR

2 x 4 LIGHT FIXTURE TO

BE REMOVED

00'-00"

REFLECTED CEILING PLAN LEGEND

2' x 4' ACOUSTICAL

CEILING

RETURN AIR GRILLE

SUPPLY AIR GRILLE

EXHAUST AIR GRILLE

EXISTING SUSPENDED

LIGHT FIXTURE

2' x 4' ACOUSTICAL

CEILING TO BE REMOVED

2' x 2' ACOUSTICAL

CEILING

1 x 4 LIGHT FIXTURE TO

BE REMOVED

2 x 4 LIGHT FIXTURE

REF: ELECTRICAL

1 x 4 LIGHT FIXTURE

REF: ELECTRICAL

CAN LIGHT

REF: ELECTRICAL

EXISTING CAN LIGHT TO

BE REMOVED

SUSPENDED LIGHT FIXTURE

TO BE REMOVED

1. AREAS OF EXISTING CEILING, CEILING GRID, LIGHTING ETC. TO BE PROTECTED DURING

CONTRUCTION. CONTRACTOR TO REPLACE ANY DAMAGED ELEMENTS WITH NEW TO MATCH

EXISTING.

2. ALL NEW CEILING GRID TO BE CENTERED WITHIN ROOM, UNO.

3. ALL EXPOSED CEILINGS TO BE PAINTED P1, UNO.

4. ALL LIGHTING TO BE CENTERED IN ROOM, UNO..

5. PROVIDE HOLD DOWN CLIPS AT VESTIBULES AND AREA NEAR EGRESS DOORS.

GENERAL REFLECTED CEILING PLAN NOTES

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024

JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023

CIVIL/ STRUCTURAL ENGINEER

OATES ASSOCIATES

100 LANTER COURT, SUITE 1

COLLINSVILLE, IL 62234

(618) 345-2200

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

2519 MADISON AVE. STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

DATA/COMM CONSULTANT

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

EHRM INFRASTRUCTURE

UPGRADESCOMMISSIONING AGENT

ES2

13401 N. SANTA FE AVE.

OKLAHOMA, OK 73114

(405) 528-4500

/1

/2

:4 :5

A

M

ENLARGED PLANS - BLDG 37

NR 084 205NR

FINAL BID DOCUMENTS

4/20/2023

657A5-21-700

MARION VA MEDICAL CENTER

2401 WEST MAIN ST. | MARION, IL

62959

AE403

SPUR #: 2114

N

1/4" = 1'-0"

BLDG 37 - LEVEL 1 - COMPUTER ROOM - DEMOLITION PLAN1

N

1/4" = 1'-0"

BLDG 37 - LEVEL 1 - COMPUTER ROOM - FLOOR PLAN2

N

1/4" = 1'-0"

BLDG 37 - LEVEL 1 - DEMOLITION PLAN5

N

1/4" = 1'-0"

BLDG 37 - LEVEL 1 - FLOOR PLAN6

1" = 400'-0"

KEY PLAN

KEYNOTE LEGEND

2.02 REMOVE WALL AS REQUIRED FOR NEW CONSTRUCTION

2.06 REMOVE DOOR, FRAME AND HARDWARE, SAVE FOR RELOCATION.

2.07 REMOVE FLOOR MATERIAL AND WALL BASE. PREPARE CONCRETE SUB-FLOOR FOR NEW

CONSTRUCTION.

2.08 EXISTING RAISED FLOORING SYSTEM TO REMAIN. PATCH AND REPAIR WHERE EXISTING

PARTITIONS ARE REMOVED.

2.14 PREPARE FLOORING AND WALLS FOR NEW FINISHES

2.18 DEMOLISH NETWORK RACK AND ASSOCIATED DATA AND TELEPHONE CABLING AFTER

CUT-OVER. REF: TELECOM

2.19 DEMOLISH EQUIPMENT. REF: ELECTRICAL

2.22 OPEN TO BOTTOM OF DECK ABOVE

2.23 DEMOLISH EXISTING RAISED FLOOR SYSTEM

2.24 DEMOLISH EXISTING RAMP IN ITS ENTIRETY

9.01 WALL INFILL TO MATCH CONSTRUCTION, TEXTURE, AND FINISH OF ADJACENT WALL

9.85 NO CEILING, OPEN TO ABOVE

10.30 CABLE TRAY (ABOVE), REFER TO TECHNOLOGY

10.31 TELECOMMUNICATION RACK, REFER TO TECHNOLOGY

23.04 DUCTLESS SPLIT INDOOR UNIT, REF: MECHANICAL

26.06 GROUND BAR, REF: ELECTRICAL

26.07 ELECTRICAL PANEL, REF: ELECTRICAL

N

1/4" = 1'-0"

BLDG 37 - LEVEL 1 - DEMOLITION RCP7

N

1/4" = 1'-0"

BLDG 37 - LEVEL 1 - COMPUTER ROOM - DEMOLITION RCP3

N

1/4" = 1'-0"

BLDG 37 - LEVEL 1 - RCP8

N

1/4" = 1'-0"

BLDG 37 - LEVEL 1 - COMPUTER ROOM - RCP4

EL

DM

CR

CLEAN LINEN/

STORAGE

3' -1

0" 6'

-5

0'

-3

F V

A B

2.16

+/- 10'-4" FV

C

D

FIBER OPTIC

TELEPHONE

6A

2.17

+/- 17'-5 1/2" FV

0'

-5

/2

F V

2.182.18

2.21 +/- 10'-3" FV

'-1

/2

F

V

1'

-5

/2

F V

4'

-3

/2

F V

+/- 24'-7 1/2" FV

5'-10" 4'-6"

2.19

2.31

2.31

STORAGE

6A

CLEAN LINEN/

STORAGE

127 SF

TR

3'

-4

6' -8

38-164

A B

AE201

1'-1 1/2" 1'-4 1/2"

+/- 10'-4" FV

7' -4

1/

MECH YARD

100M

38-100M

AE201

AE201

C

D

18'-9"

10.31

AE201

AE201

3'-8 1/2" 2'-5" 4'-2 1/2"

6' -5

/2

1'

-8

/2

6" 1'

-8

/2

3' -3

3'

-7

F V

+/- 10'-3" FV

'-1

/2

F

V

9.769.01

9.01

7.88

26.07

7.88

7.887.88

TEAM OFFICE

1' -3

3'

-1 1"

2"

5' -4

TR

123C

C

D

DATA ROOM

123B

2.18

2.18

2.21

+/- 9'-0" FV

'-1

0" F

V

4'

-3

/2

F V

+/- 10'-4" FV

5'-10" 4'-6"

2.31

2.31

STORAGE

123B

TEAM OFFICE

127 SF

TR

123C

38-123C

A B

AE201

AE201

AE201

C

D

AE201

AE201

'-1

0" F

V

+/- 9'-0" FV

10.31

3' -1

3'

-8

1' -8

/2

6"

1' -8

/2

2'

-1

1/ 2"

3'

-7

F V

3'-8 1/2" 2'-5" 4'-2 1/2"

1'-1 1/2" 1'-4 1/2"

+/- 10'-4" FV

9.76

9.01

7.88

9.01

26.07

7.88

7.88

MOD-4

MOD-3

MOD-1

N

1. ALL DOOR FRAMES TO BE LOCATED 4" FROM OUTSIDE OF FRAME TO FINISH FACE OF

ADJACENT WALL UNLESS NOTED OTHERWISE.

2. ALL WALL IN-FILL TO MATCH EXSITING OR ADJACENT WALL TYPE CONSTRUCTION. REFER TO

PARTITION TYPES (ON SHEET AE601) FOR WALL TYPES.

3. REFER TO DOOR SCHEDULE & DETAILS SHEET (AE601) FOR DOOR INFORMATION.

4. ALL WALLS ARE DIMENSIONED TO CENTERLINE OF METAL STUD, UNLESS NOTED OTHERWISE.

5. BLOCK OUT SLAB FOR PENETRATIONS SHALL BE 2" LARGER THAN DUCT SIZE TO ALLOW

TOLERANCE FOR DUCT PASSAGE AND FIRE SAFING. COORDINATE WITH MEP FOR DUCT SIZES.

6. FURR AROUND ALL COLUMN PROTRUSIONS AS NEEDED UNLESS NOTED OTHERWISE.

7. REFER TO SHEET AF711 FOR FINISH MATERIAL INFORMATION.

GENERAL PLAN NOTES

1. ALL EXISTING WALL DIMENSIONS ARE TO FINISH FACE, UNLESS OTHERWISE NOTED

2. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF AS-BUILT CONDITIONS, AND NOTIFY THE

ARCHITECT IN WRITING OF ANY DISCREPANCIES. ALL INFORMATION SHOWN ON THE

CONSTRUCTION DOCUMENTS IS BASED ON FIELD OBSERVATIONS AND/OR THE ORIGINAL

CONSTRUCTION DOCUMENTS OF THE FACILITY.

3. DEMOLITION AND CONSTRUCTION WORK MUST BE DONE UNDER NEGATIVE PRESSURE UTILIZING

HEPA FILTRATION UNITS. SEE INFECTION CONTROL NOTES.

4. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT OT AREA HAS BEEN

INSPECTED BY THE VA CAMPUS SAFETY OFFICER AND INFECTION CONTROL COORDINATOR AND

THOROUGHLY CLEANED BY ENVIRONMENTAL MANAGEMENT SERVICES

5. THE CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR EXISTING FLOOR, WALL AND

CEILING FINISHES IN EXISTING AREAS NOT DESIGNATED FOR DEMOLITION OR NEW

CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGE

CAUSED BY HIS WORK OR ANY SUBCONTRACTOR.

6. THE CONTRACTOR SHALL VERIFY THAT NEW MECHANICAL SYSTEMS CAN BE INSTALLED IN

EXISTING SPACES TO CLEAR EXISTING CEILING AND OTHER CONSTRUCTED ITEMS AND MAINTAIN

FLOOR TO CEILING HEIGHTS INDICATED ON DRAWINGS. IF DISCREPANCIES OCCUR DUE TO

EXISTING CONDITIONS, CONSULT WITH THE ARCHITECT BEFORE PROCEEDING.

7. THE FINISH FACE OF MATERIAL OF NEW PARTITIONS SHALL ALIGN ON BOTH SIDES OF THE PARTITION WITH THE FACE OF THE MATERIALS ON EXISTING COLUMNS, WALLS, OR PARTITIONS, UNLESS NOTED OTHERWISE.

8. NO WORK TO BE DONE IN AREAS HATCHED GRAY IN PLANS, HOWEVER WORK MIGHT NEED TO BE

PERFORMED IN CEILING OR EXISTING CHASES THROUGHOUT BUILDING. REFERENCE

MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT OF WORK. COORDINATE ACCESS TO

ROOMS OUTSIDE OF SCOPE WITH OWNER

GENERAL DEMOLITION NOTES

EXISTING WALL TO BE DEMOLISHED

EXISTING WALL TO REMAIN

NEW NON-RATED WALLS

PARTITION LEGEND

EXISTING DOOR AND

FRAME TO BE DEMOLISHED

EXIT LIGHT

2' x 2' ACOUSTICAL CEILING

TO BE REMOVED

2 x 2 EXISTING LIGHT FIXTURE

TO BE REMOVED

CEILING HEIGHT, ABOVE

FINISH FLOOR

2 x 4 LIGHT FIXTURE TO

BE REMOVED

00'-00"

REFLECTED CEILING PLAN LEGEND

2' x 4' ACOUSTICAL

CEILING

RETURN…