ae408 enlarged plans - bldg 42 43 81.pdf
PDF 362 KB Posted
- Attached to
- 36C77623B0047 - Y1DA--657A5-21-700 EHRM Infrastructure Upgrades Construction Marion, IL VAMC
- Solicitation number
- 36C77623B0047_1
About this file
This document package includes construction plans and specifications for infrastructure upgrades at the Marion VA Medical Center in Marion, Illinois. The plans detail demolition and construction work for buildings 42, 43, and 81, including communications closets, electrical rooms, offices, corridors and other clinical spaces. Mechanical, electrical, plumbing and communications systems are included. The related federal contract opportunity is solicitation number 36C77623B0047 for construction services to complete the upgrades. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas. The response due date is not provided. Construction is to be completed under negative pressure using HEPA filtration to control infection risks.
View the file
Other files
Show 40 more
Latest 50 of 62 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COMMUNICATIONS
CLOSET
CB13A-42
ELECTRICAL
CB13B-42
2.18
'-3
F
V
+/- 6'-3 1/2" FV +/- 10'-5" FV
'-0
/2
F
V
COMMUNICATIONS
CLOSET
CB13A-42
ELECTRICAL
CB13B-42
9.76 9.76
'-3
F
V
+/- 6'-3 1/2" FV +/- 10'-5" FV
'-0
/2
F
V
STORAGE
123A
TELE.
2.09
2.07
2.07 2.15
2.022.02
2.18
NURSE
STATION
0'
-5
/2
F V
'-0
/2
F
V
'-0
/2
F V
+/- 6'-5" FV
'-8
F
V
CORRIDOR
C106-43
2.272.27
2.07
+/- 14'-2 1/2" FV
1'
-3
/2
F V
CORRIDOR
C106-43
102 SF
TR
NURSE
STATION
ALIGN
ALIGN
9.02C3C3
C3
10.31 9.30
-1
0'
-5
/2
F V
+/- 10'-2 1/2" FV
'-1
F
V
+/- 4'-7" FV +/- 2'-3" FV
4' -0
1'
-8
/2
3' -5
3'-9 1/2" 2'-5" 3'-9 1/2"
26.07
9.86
101 SF
TR
113 SF
OFFICE
102 SF
OFFICE
+/- 7'-10" FV
+/- 24'-9 1/2" FV
D3
D3
10.31
ALIGN
81-135
3'
-2
/2
F V
2'-11" 1'-8 1/2" 3'-0 1/2"
7' -2
2'
-5
3' -7
/2
26.07
OFFICE
TR
OFFICE
3'
-2
/2
F V
+/- 24'-9 1/2" FV
2.07 2.072.07
2.02 2.02
+/- 6'-0" FV +/- 9'-0" FV +/- 9'-0" FV
STORAGE
123A
TELE.
NURSE
STATION
0'
-5
/2
F V
'-0
/2
F
V
'-0
/2
F V
+/- 6'-5" FV
'-8
F
V
+/- 4'-7" FV
9'-0"
TR
NURSE
STATION
0' -5
/2
F
V
+/- 10'-0" FV
'-1
F
V
+/- 4'-7" FV +/- 2'-3" FV
2'-4 1/2" 5'-7" 2'-1"
5' -8
4'
-9
/2
9.85
9'-0"
TR
OFFICE
OFFICE
1' -3
1'
-4
EQ EQ
+/- 7'-10" FV
+/- 24'-9 1/2" FV
3'
-2
/2
F V
23.04
EQ EQ
9.85
26.06
9'-0" 9'-0"
EXIT LIGHT
2' x 2' ACOUSTICAL CEILING
TO BE REMOVED
2 x 2 EXISTING LIGHT FIXTURE
TO BE REMOVED
CEILING HEIGHT, ABOVE
FINISH FLOOR
2 x 4 LIGHT FIXTURE TO
BE REMOVED
00'-00"
REFLECTED CEILING PLAN LEGEND
2' x 4' ACOUSTICAL
CEILING
RETURN AIR GRILLE
SUPPLY AIR GRILLE
EXHAUST AIR GRILLE
EXISTING SUSPENDED
LIGHT FIXTURE
2' x 4' ACOUSTICAL
CEILING TO BE REMOVED
2' x 2' ACOUSTICAL
CEILING
1 x 4 LIGHT FIXTURE TO
BE REMOVED
2 x 4 LIGHT FIXTURE
REF: ELECTRICAL
1 x 4 LIGHT FIXTURE
REF: ELECTRICAL
CAN LIGHT
REF: ELECTRICAL
EXISTING CAN LIGHT TO
BE REMOVED
SUSPENDED LIGHT FIXTURE
TO BE REMOVED
1. ALL DOOR FRAMES TO BE LOCATED 4" FROM OUTSIDE OF FRAME TO FINISH FACE OF
ADJACENT WALL UNLESS NOTED OTHERWISE.
2. ALL WALL IN-FILL TO MATCH EXSITING OR ADJACENT WALL TYPE CONSTRUCTION. REFER TO
PARTITION TYPES (ON SHEET AE601) FOR WALL TYPES.
3. REFER TO DOOR SCHEDULE & DETAILS SHEET (AE601) FOR DOOR INFORMATION.
4. ALL WALLS ARE DIMENSIONED TO CENTERLINE OF METAL STUD, UNLESS NOTED OTHERWISE.
5. BLOCK OUT SLAB FOR PENETRATIONS SHALL BE 2" LARGER THAN DUCT SIZE TO ALLOW
TOLERANCE FOR DUCT PASSAGE AND FIRE SAFING. COORDINATE WITH MEP FOR DUCT SIZES.
6. FURR AROUND ALL COLUMN PROTRUSIONS AS NEEDED UNLESS NOTED OTHERWISE.
7. REFER TO SHEET AF711 FOR FINISH MATERIAL INFORMATION.
GENERAL PLAN NOTES
1. ALL EXISTING WALL DIMENSIONS ARE TO FINISH FACE, UNLESS OTHERWISE NOTED
2. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF AS-BUILT CONDITIONS, AND NOTIFY THE
ARCHITECT IN WRITING OF ANY DISCREPANCIES. ALL INFORMATION SHOWN ON THE
CONSTRUCTION DOCUMENTS IS BASED ON FIELD OBSERVATIONS AND/OR THE ORIGINAL
CONSTRUCTION DOCUMENTS OF THE FACILITY.
3. DEMOLITION AND CONSTRUCTION WORK MUST BE DONE UNDER NEGATIVE PRESSURE UTILIZING
HEPA FILTRATION UNITS. SEE INFECTION CONTROL NOTES.
4. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT OT AREA HAS BEEN
INSPECTED BY THE VA CAMPUS SAFETY OFFICER AND INFECTION CONTROL COORDINATOR AND
THOROUGHLY CLEANED BY ENVIRONMENTAL MANAGEMENT SERVICES
5. THE CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR EXISTING FLOOR, WALL AND
CEILING FINISHES IN EXISTING AREAS NOT DESIGNATED FOR DEMOLITION OR NEW
CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGE
CAUSED BY HIS WORK OR ANY SUBCONTRACTOR.
6. THE CONTRACTOR SHALL VERIFY THAT NEW MECHANICAL SYSTEMS CAN BE INSTALLED IN
EXISTING SPACES TO CLEAR EXISTING CEILING AND OTHER CONSTRUCTED ITEMS AND MAINTAIN
FLOOR TO CEILING HEIGHTS INDICATED ON DRAWINGS. IF DISCREPANCIES OCCUR DUE TO
EXISTING CONDITIONS, CONSULT WITH THE ARCHITECT BEFORE PROCEEDING.
7. THE FINISH FACE OF MATERIAL OF NEW PARTITIONS SHALL ALIGN ON BOTH SIDES OF THE PARTITION WITH THE FACE OF THE MATERIALS ON EXISTING COLUMNS, WALLS, OR PARTITIONS, UNLESS NOTED OTHERWISE.
8. NO WORK TO BE DONE IN AREAS HATCHED GRAY IN PLANS, HOWEVER WORK MIGHT NEED TO BE
PERFORMED IN CEILING OR EXISTING CHASES THROUGHOUT BUILDING. REFERENCE
MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT OF WORK. COORDINATE ACCESS TO
ROOMS OUTSIDE OF SCOPE WITH OWNER
GENERAL DEMOLITION NOTES
1. AREAS OF EXISTING CEILING, CEILING GRID, LIGHTING ETC. TO BE PROTECTED DURING
CONTRUCTION. CONTRACTOR TO REPLACE ANY DAMAGED ELEMENTS WITH NEW TO MATCH
EXISTING.
2. ALL NEW CEILING GRID TO BE CENTERED WITHIN ROOM, UNO.
3. ALL EXPOSED CEILINGS TO BE PAINTED P1, UNO.
4. ALL LIGHTING TO BE CENTERED IN ROOM, UNO..
5. PROVIDE HOLD DOWN CLIPS AT VESTIBULES AND AREA NEAR EGRESS DOORS.
GENERAL REFLECTED CEILING PLAN NOTES
EXISTING WALL TO BE DEMOLISHED
EXISTING WALL TO REMAIN
NEW NON-RATED WALLS
PARTITION LEGEND
EXISTING DOOR AND
FRAME TO BE DEMOLISHED
COMMUNICATIONS
CLOSET
CB13A-42
ELECTRICAL
CB13B-42
'-3
F
V
+/- 6'-3 1/2" FV +/- 10'-5" FV
'-0
/2
F
V
2.20
2.19
COMMUNICATIONS
CLOSET
CB13A-42
ELECTRICAL
CB13B-42
'-3
F
V
+/- 6'-3 1/2" FV +/- 10'-5" FV
'-0
/2
F
V
9.85
TR
OFFICE
OFFICE
137 +
3'
-2
/2
F V
+/- 24'-9 1/2" FV
+/- 6'-0" FV +/- 9'-0" FV +/- 9'-0" FV
2.22
9'-0" 9'-0"
2.19
MOD-4
MOD-3
MOD-1
44N th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024
JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023
CIVIL/ STRUCTURAL ENGINEER
OATES ASSOCIATES
100 LANTER COURT, SUITE 1
COLLINSVILLE, IL 62234
(618) 345-2200
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
2519 MADISON AVE. STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
DATA/COMM CONSULTANT
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
EHRM INFRASTRUCTURE
UPGRADESCOMMISSIONING AGENT
ES2
13401 N. SANTA FE AVE.
OKLAHOMA, OK 73114
(405) 528-4500
/2
/2
:1 :0
P
M
ENLARGED PLANS - BLDG 42, 43, 81
NR 088 204NR
FINAL BID DOCUMENTS
4/20/2023
657A5-21-700
MARION VA MEDICAL CENTER
2401 WEST MAIN ST. | MARION, IL
62959
AE408
SPUR #: 2114
N
1/4" = 1'-0" 1/ AE103
BLDG 42 - LEVEL G - CB13A-42 - DEMOLITION PLAN1
N
1/4" = 1'-0" 1/ AE103
BLDG 42 - LEVEL G - CB13A-42 - FLOOR PLAN2
N
1/4" = 1'-0" 1/ AE104
BLDG 43 LEVEL G - DEMOLITION PLAN5
N
1/4" = 1'-0" 1/ AE104
BLDG 43 - LEVEL G - FLOOR PLAN6
N
1/4" = 1'-0" 2/ AE104
BLDG 81 - LEVEL 1 - FLOOR PLAN10
N
1/4" = 1'-0" 2/ AE104
BLDG 81 - LEVEL 1 - DEMOLITION PLAN9
42, 43, 81
N
1/4" = 1'-0" 1/ AE201
BLDG 43 - LEVEL G - DEMOLITION RCP7
N
1/4" = 1'-0" 1/ AE201
BLDG 43 - LEVEL G - RCP8 N
1/4" = 1'-0" 1/ AE201
BLDG 81 - LEVEL 1 - RCP12
KEYNOTE LEGEND
2.02 REMOVE WALL AS REQUIRED FOR NEW CONSTRUCTION
2.07 REMOVE FLOOR MATERIAL AND WALL BASE. PREPARE CONCRETE SUB-FLOOR FOR NEW
CONSTRUCTION.
2.09 EXISTING BUILT-IN MILLWORK DESK TO BE DISASSEMBLED AND RELOCATED DURING NEW
CONSTRUCTION.
2.15 EXISTING UPPER AND LOWER CABINETS TO BE DISASSEMBLED AND RELOCATED DURING
NEW CONSTRUCTION
2.18 DEMOLISH NETWORK RACK AND ASSOCIATED DATA AND TELEPHONE CABLING AFTER
CUT-OVER. REF: TELECOM
2.19 DEMOLISH EQUIPMENT. REF: ELECTRICAL
2.20 DEMOLISH EQUIPMENT. REF: MECHANICAL
2.22 OPEN TO BOTTOM OF DECK ABOVE
2.27 DEMOLISH EXISTING ELECTRICAL BOX, INSTALL STEEL PLATE BELOW CONCRETE SLAB, FILL
WITH CONCRETE FOR A SMOTH SURFACE LEVEL WITH ADJACENT CONCRETE. REF: ELEC
9.02 RELOCATED MILLWORK DESK, REF: ELECTRICAL FOR NEW FLOOR BOXES
9.30 RELOCATED UPPER AND LOWER CABINETS, REF: ELECTRICAL FOR NEW ELECTRICAL
CONNECTIONS
9.76 PAINT TO MATCH EXISTING
9.85 NO CEILING, OPEN TO ABOVE
9.86 RELOCATED NURSE STATION. PROVIDE NEW BASE AND TRIM AS REQUIRED
10.31 TELECOMMUNICATION RACK, REFER TO TECHNOLOGY
23.04 DUCTLESS SPLIT INDOOR UNIT, REF: MECHANICAL
26.06 GROUND BAR, REF: ELECTRICAL
26.07 ELECTRICAL PANEL, REF: ELECTRICAL
N
1/4" = 1'-0" 1/ AE201
BLDG 42 - LEVEL G - CB13A-42 - DEMOLITION RCP3
N
1/4" = 1'-0" 1/ AE201
BLDG 42 - LEVEL G - CB13A-42 - RCP4
N
1/4" = 1'-0" 1/ AE201
BLDG 81 - LEVEL 1 - DEMOLITION RCP11
1" = 400'-0"
KEY PLAN
No. REVISION DESCRIPTION DATE
3 Revision 3 08/23/2023
3 ADDENDUM #3 08/23/2023
noe.ramirez Rectangle