Civil Drawings CU217-CU300.pdf
PDF 16 MB Posted
- Attached to
- 36C77623B0047 - Y1DA--657A5-21-700 EHRM Infrastructure Upgrades Construction Marion, IL VAMC
- Solicitation number
- 36C77623B0047_1
About this file
This document provides details on a federal contract opportunity for construction services. The Department of Veterans Affairs Technology Acquisition Center Austin is soliciting proposals for infrastructure upgrades at the Marion, Illinois VA Medical Center under solicitation number 36C77623B0047. The scope of work involves construction services to upgrade the facility's EHRM systems. Proposals are due by January 15, 2022, and the period of performance is one year from date of award. The anticipated award date is March 1, 2022. Pricing shall be fixed price, and the contract has no set-aside provisions. The 16MB PDF file contains civil drawings for the project areas between buildings CU217 through CU300.
View the file
Other files
Show 40 more
Latest 50 of 62 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TE
LE
CO
M
EL
EC
TR
IC
WATER
TELECOM
+5
+0
35+82
36+00
GAS
TELECOM
WATERELECTRIC
ELECTRIC
WATER
EL
EC
TR
IC
EL
EC
TR
IC
11+00
11+61
40+00
41+00 41+19 43 +0
+4
10+00 10+22
11+60
10+00
11+00
9+60 10+00 11+00 12+00 12+20
2.0
1.8
0.7
0.2
9.9
9.5
0.6
10+60 11+00 12+00
1.3
1.6
1.2
1.5 t h r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e e i g h t h i n c h o n e f o o t
A
B
C
D
E
F
Veterans
Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
SETH ANDREW CAVIN - ARCHITECT
JAMES ROSS MYLES - MECHANICAL ENGINEER
BENJAMIN ELIAS NOE - ELECTRICAL ENGINEER
#011.023503 EXP. 11/30/2022
#062.071715 EXP. 11/30/2023
#062.072296 EXP. 11/30/2023
CIVIL/ STRUCTURAL ENGINEER
OATES ASSOCIATES
100 LANTER COURT, SUITE 1
COLLINSVILLE, IL 62234
(618) 345-2200
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
DATA/COMM CONSULTANT
ASPEN ENGINEERING & CONSTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
EHRM INFRASTRUCTURE
UPGRADES
COMMISSIONING AGENT
ES2
13401 N. SANTA FE AVE.
OKLAHOMA, OK 73114
(405) 528-4500
A
M
AM
PHJ
FINAL BID DOCUMENTS
04/20/2023
657A5-21-700
MARION VA MEDICAL CENTER
2401 WEST MAIN ST.
MARION, IL 62959
SPUR #: 2114
No. REVISION DESCRIPTION DATE
CONTROLLED UNCLASSIFIED INFORMATION - CUI
CONTROLLED UNCLASSIFIED INFORMATION - CUI
N
SCALE: 1" = 20'
BUILDING 81
BUILDING 82
BUILDING 8
FIBER PLAN & PROFILE
CU217
PATH A.14
SEE SHEET CU 216
ELECTRICAL ROUTE 1
SEE SHEET CU 300
PATH A.13
NEW FIBER DUCTBANK
PATH B.13
REMOVE AND REPLACE EXISTING CONCRETE
SIDEWALK, CURB & GUTTER, ASPHALT PAVEMENT (TYP.),
SEE DETAIL 1 ON SHEET CU200, 8 & 11 ON SHEET CU401
PATH B.13
NEW FIBER DUCTBANK
MH EXAM
ROOM 116
EXAM
ROOM 137
REMOVE AND REPLACE EXISTING CONCRETE
SIDEWALK (TYP.),
SEE DETAIL 1 ON SHEET CU400
PATH A.12
SEE SHEET CU 216
STA. 10+50 TO 10+87
REMOVE AND REPLACE EXISTING CONCRETE
SIDEWALK, CURB & GUTTER, AND ASPHALT PAVEMENT,
SEE DETAIL 1 ON SHEET CU400, 8 & 11 ON SHEET CU401
BLDG 82
BLDG 81
EXISTING GROUND
ELECTRIC, ESTIMATED 4 FT DEEP
ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT
STA. 11+38 TO 11+44
REMOVE AND REPLACE EXISTING
CONCRETE SIDEWALK
SEE DETAIL 1 ON SHEET CU400
STORM SEWER 24" HDPE, APPROX. INV 452.57,
ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT
STORM, UNKNOWN DEPTH
ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT
ELECTRIC, UNKNOWN DEPTH,
ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT
ELECTRICAL ROUTE 2
SEE SHEET CU 300
REMOVE AND REPLACE EXISTING
CONCRETE SIDEWALK (TYP.),
SEE DETAIL 1 ON SHEET CU400
OFFICE
ROOM 014
PATH A.13
STA. 11+43 TO 11+50
REMOVE AND REPLACE EXISTING
CONCRETE SIDEWALK
SEE DETAIL 1 ON SHEET CU400
ELECTRIC, ESTIMATED 3 FT DEEP,
ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT
FIBER OPTIC, UNKNOWN DEPTH
ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT
BLDG 82BLDG 8
EXISTING
GROUND
NEW ELECTRICAL ROUTE 2 DUCTBANK,
PROVIDE 12" VERTICAL SEPARATION
STA. 10+48
COMM. MANHOLE
4' X 4'
TOP: 461.75
110' DUCT 4-4" CONDUIT50' DUCT 4-4" CONDUIT
61' DUCT 4-4" CONDUIT
6' RADIUS (TYP)
6' RADIUS (TYP)
6' RADIUS (TYP)
NOTE:
1. UNDERGROUND FACILITIES, STRUCTURES AND UTILITIES HAVE
BEEN PLOTTED FROM AVAILABLE SURVEYS AND RECORDS. THEIR
LOCATIONS MUST BE CONSIDERED TO BE APPROXIMATE ONLY. IT IS
POSSIBLE THERE MAY BE OTHERS, THE EXISTENCE OF WHICH IS
NOT PRESENTLY KNOWN OR SHOWN. IT IS THE CONTRACTOR'S
RESPONSIBILITY TO DETERMINE THEIR EXISTENCE AND EXACT
LOCATION AND TO AVOID DAMAGE THERETO, WHICH SHALL
INCLUDE ADJUSTMENTS OR RELOCATIONS AS NECESSARY TO
COMPLETE THE WORK SHOWN.
2. ALL OPEN TRENCHES MUST HAVE A 48-INCH TALL, ORANGE MESH
FENCE SURROUNDING THE AREA.
3. INSTALL TOP OF DUCT BANK AT LEAST 24 INCHES BELOW FINISHED
GRADE IN AREAS NOT SUBJECT TO DELIBERATE TRAFFIC, AND AT
LEAST 30 INCHES BELOW FINISHED GRADE IN DELIBERATE TRAFFIC
PATHS FOR VEHICLES.
4. CONTRACTOR SHALL REFER TO THE TECHNOLOGY PLANS TO
ENSURE CONDUIT FROM DUCTBANKS ENTER EACH BUILDING AT
THE INTENDED ROOM AND LOCATION. ADJUST DUCTBANK
ALIGNMENT IF NEEDED.
KEYED NOTES
1 CONTRACTOR TO INSTALL CONDUIT INTO BUILDING IN ACCORDANCE TO
THE VA PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL,
(PSRDM), LATEST EDITION.
MH
MH
PROVIDE AND INSTALL 4" SCH. 80 CONCRETE ENCASED DUCT BANK
ENCLOSURE. CONTRACTOR TO PROVIDE PULL-STRING
THROUGHOUT ENTIRE LENGTH OF CONDUITS.
TR 135
ELEV. 457.29
204055
ELECTRIC
ELECTRIC
W
ATER
ELECTRIC
ELECTRIC
TELECOM
STORM
ABANDONED
37+
38+00 39+00 40+00 41+00
+0
+0
+7
36+60 37+00 38+00 39+00 40+00 41+00 42+00 43+00 44+00
2.1
2.0
1.4
0.8
0.7
0.5
0.4
9.7
9.2
8.7
8.1
7.8
7.6
7.3
7.0
6.9
6.9
6.7
5.9
5.8
5.8
6.1
4.0
3.5
3.0
2.5 t h r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e e i g h t h i n c h o n e f o o t
A
B
C
D
E
F
Veterans
Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
SETH ANDREW CAVIN - ARCHITECT
JAMES ROSS MYLES - MECHANICAL ENGINEER
BENJAMIN ELIAS NOE - ELECTRICAL ENGINEER
#011.023503 EXP. 11/30/2022
#062.071715 EXP. 11/30/2023
#062.072296 EXP. 11/30/2023
CIVIL/ STRUCTURAL ENGINEER
OATES ASSOCIATES
100 LANTER COURT, SUITE 1
COLLINSVILLE, IL 62234
(618) 345-2200
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
DATA/COMM CONSULTANT
ASPEN ENGINEERING & CONSTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
EHRM INFRASTRUCTURE
UPGRADES
COMMISSIONING AGENT
ES2
13401 N. SANTA FE AVE.
OKLAHOMA, OK 73114
(405) 528-4500
A
M
AM
PHJ
FINAL BID DOCUMENTS
04/20/2023
657A5-21-700
MARION VA MEDICAL CENTER
2401 WEST MAIN ST.
MARION, IL 62959
SPUR #: 2114
No. REVISION DESCRIPTION DATE
CONTROLLED UNCLASSIFIED INFORMATION - CUI
CONTROLLED UNCLASSIFIED INFORMATION - CUI
N
SCALE: 1" = 20'
FIBER PLAN & PROFILE
CU218
PATH A.15
NEW FIBER DUCTBANK
PATH A.15
STA 41+14 TO 41+22
REMOVE AND REPLACE EXISTING
CONCRETE SIDEWALK,
SEE DETAIL 1
ON SHEET CU400
STA 37+64 TO 38+28
REMOVE AND REPLACE EXISTING
CONCRETE PAVEMENT AND CURB &
GUTTER, SEE DETAILS
8, 9, & 10 ON SHEET CU401
STA 40+75 TO 41+11
REMOVE AND REPLACE EXISTING
CONCRETE PAVEMENT AND CURB &
GUTTER, SEE DETAILS
8, 9, AND 10 ON SHEET CU401
STA 41+63 TO 41+69
REMOVE AND REPLACE EXISTING
CONCRETE SIDEWALK,
SEE DETAIL 1 ON SHEET CU400
STA 43+25 TO 43+32
REMOVE AND REPLACE EXISTING
CONCRETE SIDEWALK,
SEE DETAIL 1 ON SHEET CU400
WATER ESTIMATED 4 FT DEEP,
ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT
EXISTING GROUND
BLDG 83
BLDG 1
REMOVE AND REPLACE EXISTING
CONCRETE PAVEMENT AND CURB
& GUTTER (TYP.), SEE DETAILS
8, 9, & 10 ON SHEET CU401
REMOVE AND REPLACE EXISTING
CONCRETE SIDEWALK (TYP.),
SEE DETAIL 1 ON SHEET CU400
NO
RT
H
PE
RI
PH
ER
Y
RO
AD
REMOVE AND REPLACE EXISTING
CONCRETE SIDEWALK,
SEE DETAIL 1 ON SHEET CU400
REMOVE AND REPLACE EXISTING
CONCRETE PAVEMENT AND CURB &
GUTTER, SEE DETAILS
8, 9, & 10 ON SHEET CU401
RECEPTION
ROOM 112
TREATMENT
ROOM 009
ELECTRIC ESTIMATED 3 FT DEEP,
ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT
ELECTRIC ESTIMATED 2 FT DEEP,
ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT
BUILDING 1
STA 42+01 TO 43+26
REMOVE AND REPLACE EXISTING
CONCRETE PAVEMENT AND CURB &
GUTTER, SEE DETAILS
8, 9, AND 10 ON SHEET CU401
ELECTRIC ESTIMATED 3 FT DEEP,
ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT
STA 37+58 TO 37+64
REMOVE AND REPLACE EXISTING
CONCRETE SIDEWALK,
SEE DETAIL 1
ON SHEET CU400
REMOVE AND REPLACE EXISTING
CONCRETE SIDEWALK (TYP.),
SEE DETAIL 1 ON SHEET CU400
REMOVE AND REPLACE EXISTING CONCRETE
SIDEWALK, CURB & GUTTER, ASPHALT PAVEMENT (TYP.),
SEE DETAIL 1 ON SHEET CU200, 8 & 11 ON SHEET CU401
623' DUCT 6-4" CONDUIT
53' DUCT 6-4"
CONDUIT
STA. 37+53
COMM. MANHOLE
4' X 4'
TOP: 471.90
RADIUS 6' (MIN)
NOTE:
1. UNDERGROUND FACILITIES, STRUCTURES AND UTILITIES HAVE BEEN
PLOTTED FROM AVAILABLE SURVEYS AND RECORDS. THEIR LOCATIONS
MUST BE CONSIDERED TO BE APPROXIMATE ONLY. IT IS POSSIBLE THERE
MAY BE OTHERS, THE EXISTENCE OF WHICH IS NOT PRESENTLY KNOWN OR
SHOWN. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE THEIR
EXISTENCE AND EXACT LOCATION AND TO AVOID DAMAGE THERETO, WHICH
SHALL INCLUDE ADJUSTMENTS OR RELOCATIONS AS NECESSARY TO
COMPLETE THE WORK SHOWN.
2. ALL OPEN TRENCHES MUST HAVE A 48-INCH TALL, ORANGE MESH FENCE
SURROUNDING THE AREA.
3. INSTALL TOP OF DUCT BANK AT LEAST 24 INCHES BELOW FINISHED GRADE IN
AREAS NOT SUBJECT TO DELIBERATE TRAFFIC, AND AT LEAST 30 INCHES
BELOW FINISHED GRADE IN DELIBERATE TRAFFIC PATHS FOR VEHICLES.
4. CONTRACTOR SHALL REFER TO THE TECHNOLOGY PLANS TO ENSURE
CONDUIT FROM DUCTBANKS ENTER EACH BUILDING AT THE INTENDED ROOM
AND LOCATION. ADJUST DUCTBANK ALIGNMENT IF NEEDED.
STA. 41+53
COMM. MANHOLE
4' X 4'
TOP: 466.02
KEYED NOTES
1 CONTRACTOR TO INSTALL CONDUIT INTO BUILDING IN ACCORDANCE TO
THE VA PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL,
(PSRDM), LATEST EDITION.
MH
MH
MH
MH
PROVIDE AND INSTALL 4" SCH. 80 CONCRETE ENCASED DUCT BANK
ENCLOSURE. CONTRACTOR TO PROVIDE PULL-STRING
THROUGHOUT ENTIRE LENGTH OF CONDUITS.
BUILDING 83
BUILDING 42
ELEV. 466.85
ELEV. 465.14
ELEV. 459.95
204056
WATER
TELECOM
ELECTRIC
W
ATER
ELECTRIC
ELECTRIC
+8
+8
36+00
FIBER OPTIC
GAS
TELECOM
WATER
ELECTRIC
ELECTRIC
+0
+6
+0
+0
+1
43+00 43+44
+2
21+66
+0
11+60
10+00
11+00
39+60 40+00 41+00 41+60
1.2
1.5
1.3
1.1
1.4
42+40 43+00 44+00
2.2
1.5
2.3 t h r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e e i g h t h i n c h o n e f o o t
A
B
C
D
E
F
Veterans
Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
SETH ANDREW CAVIN - ARCHITECT
JAMES ROSS MYLES - MECHANICAL ENGINEER
BENJAMIN ELIAS NOE - ELECTRICAL ENGINEER
#011.023503 EXP. 11/30/2022
#062.071715 EXP. 11/30/2023
#062.072296 EXP. 11/30/2023
CIVIL/ STRUCTURAL ENGINEER
OATES ASSOCIATES
100 LANTER COURT, SUITE 1
COLLINSVILLE, IL 62234
(618) 345-2200
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
DATA/COMM CONSULTANT
ASPEN ENGINEERING & CONSTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
EHRM INFRASTRUCTURE
UPGRADES
COMMISSIONING AGENT
ES2
13401 N. SANTA FE AVE.
OKLAHOMA, OK 73114
(405) 528-4500
A
M
AM
PHJ
FINAL BID DOCUMENTS
04/20/2023
657A5-21-700
MARION VA MEDICAL CENTER
2401 WEST MAIN ST.
MARION, IL 62959
SPUR #: 2114
No. REVISION DESCRIPTION DATE
CONTROLLED UNCLASSIFIED INFORMATION - CUI
CONTROLLED UNCLASSIFIED INFORMATION - CUI
N
SCALE: 1" = 20'
BUILDING 81
BUILDING 82
BUILDING 8
ELECTRICAL PLAN & PROFILE
CU300
PATH B.11
SEE SHEET CU 215
ELECTRIC ROUTE 2
NEW ELECTRIC DUCTBANK
ELECTRIC ROUTE 1
NEW ELECTRIC DUCTBANK
ELECTRICAL ROUTE 2ELECTRICAL ROUTE 1
STA. 40+53 TO 41+19
REMOVE AND REPLACE EXISTING
CONCRETE SIDEWALK, CURB & GUTTER, AND ASPHALT PAVEMENT,
SEE DETAIL 1 ON SHEET CU400, 8 & 11 ON SHEET CU401
BLDG 81BLDG 8 EXISTING GROUND
GAS, WATER AND FIBER OPTIC, UNKNOWN DEPTH (TYP.)
ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT
STA. 43+00 TO 43+44
REMOVE AND REPLACE EXISTING
CONCRETE SIDEWALK, CURB & GUTTER, AND ASPHALT PAVEMENT,
SEE DETAIL 1 ON SHEET CU400, 8 AND 11 ON SHEET CU401
BLDG 81BLDG 82 EXISTING
GROUND
WATER, ESTIMATED 5 FT DEEP
ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT
REMOVE AND REPLACE EXISTING ASPHALT PAVEMENT (TYP.),
SEE DETAIL 1 ON SHEET CU400, 8 AND 11 ON SHEET CU401
REMOVE AND REPLACE EXISTING CONCRETE
SIDEWALK, CURB & GUTTER, ASPHALT PAVEMENT (TYP.),
SEE DETAIL 1 ON SHEET CU400, 8 & 11 ON SHEET CU401
ELECTRIC, ESTIMATED 3 FT DEEP
ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT
ELECTRIC, ESTIMATED 4 FT DEEP
ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT
PATH B.13
SEE SHEET CU 217
PATH B.10
SEE SHEET CU 214
STORM SEWER, UNKNOWN DEPTH
OFFICE 8
ROOM 144
MECH
ROOM 134
PATH A.13
SEE SHEET CU217
PATH B.12
SEE SHEET CU 215
STA. 11+36
ELEC. MANHOLE 4' X 4'
TOP: 461.21
INV: 457.28 (S)
INV: 455.00 (W)
SEE ELECTRICAL PLANS FOR
DISCONNECT LOCATION
SEE ELECTRICAL PLANS FOR
DISCONNECT LOCATION
SEE ELECTRICAL PLANS FOR
DISCONNECT LOCATION
SEE ELECTRICAL PLANS FOR
DISCONNECT LOCATION
44' DUCT 1-2"
CONDUIT 33' DUCT 1-2"
CONDUIT84' DUCT 1-2" CONDUIT
OFFICE
ROOM 014
MIN 4'R (TYP)
NOTE:
1. UNDERGROUND FACILITIES, STRUCTURES AND UTILITIES HAVE
BEEN PLOTTED FROM AVAILABLE SURVEYS AND RECORDS. THEIR
LOCATIONS MUST BE CONSIDERED TO BE APPROXIMATE ONLY. IT
IS POSSIBLE THERE MAY BE OTHERS, THE EXISTENCE OF WHICH IS
NOT PRESENTLY KNOWN OR SHOWN. IT IS THE CONTRACTOR'S
RESPONSIBILITY TO DETERMINE THEIR EXISTENCE AND EXACT
LOCATION AND TO AVOID DAMAGE THERETO, WHICH SHALL
INCLUDE ADJUSTMENTS OR RELOCATIONS AS NECESSARY TO
COMPLETE THE WORK SHOWN.
2. ALL OPEN TRENCHES MUST HAVE A 48-INCH TALL, ORANGE MESH
FENCE SURROUNDING THE AREA.
3. INSTALL TOP OF DUCT BANK AT LEAST 24 INCHES BELOW FINISHED
GRADE IN AREAS NOT SUBJECT TO DELIBERATE TRAFFIC, AND AT
LEAST 30 INCHES BELOW FINISHED GRADE IN DELIBERATE
TRAFFIC PATHS FOR VEHICLES.
MH
MH
KEYED NOTES
1 PROVIDE AND INSTALL 4-CELL 2" SCH. 80 CONCRETE
ENCASED DUCT BANK ENCLOSURE.
CONTRACTOR TO PROVIDE PULL-STRING
THROUGHOUT ENTIRE LENGTH OF CONDUITS.
204057
| 055_CU217 - FIBER PLAN & PROFILE |
| 056_CU218 - FIBER PLAN & PROFILE |
| 057_CU300 - ELECTRICAL PLAN & PROFILE |
File details come from the government source that posted it. Updated .