Civil Drawings CU-214-CU216.pdf

PDF 14 MB Posted

Attached to
36C77623B0047 - Y1DA--657A5-21-700 EHRM Infrastructure Upgrades Construction Marion, IL VAMC
Solicitation number
36C77623B0047_1
Issued by

About this file

This federal contract opportunity notice seeks construction services for infrastructure upgrades at the Veterans Affairs Medical Center in Marion, Illinois. The Department of Veterans Affairs Technology Acquisition Center Austin is soliciting proposals under solicitation number 36C77623B0047 for construction work related to upgrading the EHRM infrastructure at the Marion VAMC. The scope of work involves civil drawings for construction of buildings CU-214 and CU-216 as indicated in the 14MB Civil Drawings file. Proposals are due by the date listed on the solicitation notice for awarding the contract to upgrade critical infrastructure and support veterans' healthcare services at this facility.

View the file

Other files

File Type Posted
Wage Determination - Williamson County - 9.8.23.pdf PDF
36C77623B0047 0009.docx DOCX document
36C77623B0047 Amendment 0008.docx DOCX document
ae601 door schedule and partition types.pdf PDF
3837_001.pdf PDF
M-105 REFERENCE PLANS - BUILDINGS 81 and 82.pdf PDF
04 20 00 UnitMasonry.pdf PDF
657a5-21-700 ehrm marion il addendum-03.pdf PDF
03 30 00 Cast-in-Place Concrete.pdf PDF
36C77623B0047 Amendment 0007.docx DOCX document
ae408 enlarged plans - bldg 42 43 81.pdf PDF
1 Technical Questions Tracking Spreadsheet - Marion Infra Constr - 8-24-23 Final.pdf PDF
Wage rates - Williamson - 8.14.23.pdf PDF
B 38 Drawing Package_Part5.pdf PDF
Building 14 Boiler Plant Geotechnical Report.pdf PDF
B 38 Drawing Package_Part4.pdf PDF
2. B 37 Marion VA Field Print Model (2 of 2) (1).pdf PDF
2. B 37 Marion VA Field Print Model (2 of 2) (5).pdf PDF
2. B 37 Marion VA Field Print Model (2 of 2) (3).pdf PDF
2017-0502.10 Building 13 Geotech Report.pdf PDF
2. B 37 Marion VA Field Print Model (2 of 2) (2).pdf PDF
36C77623B0047 Amendment 0006.docx DOCX document
B 38 Drawing Package_Part3.pdf PDF
15225023 VA Project 657A5-21-700 EHRM Marion Geotechnical Report.pdf PDF
B 38 Drawing Package_Part1.pdf PDF
B 38 Drawing Package_Part6.pdf PDF
2. B 37 Marion VA Field Print Model (2 of 2) (4).pdf PDF
B 38 Drawing Package_Part2.pdf PDF
Wage Determination - Williamson 8.4.pdf PDF
36C77623B0047 0005.pdf PDF
Attachment 1 - Missing Specs.zip ZIP file
36C77623B0047 0004.pdf PDF
36C77623B0047 0003.pdf PDF
Construction Wage Rates - Williamson County - 7-28-23.pdf PDF
Site Visit Sign-In Sheet - Marion Infra 7-31-23.pdf PDF
Attachment 1 - Electrical Plans 657A5-21-700.zip ZIP file
36C77623B0047 Amendment 0002.pdf PDF
Attachment 1 - 36C77623B0047_1.pdf PDF
36C77623B0047 Amendment 0001.docx DOCX document
ARCHITECTURAL.pdf PDF
Limitations on Subcontracting - Construction.docx DOCX document
STRUCTURAL.pdf PDF
Civil Drawings CU301-CIVIL DETAILS.pdf PDF
HAZARDOUS MATERIALS.pdf PDF
Civil Drawings CU211-CU213.pdf PDF
36C77623B0047_1.docx DOCX document
Civil Drawings CU207-CU210.pdf PDF
GENERAL.pdf PDF
Civil Drawings CU217-CU300.pdf PDF
Brand Name Justification - Marion EHRM Infra Redacted.pdf PDF
Show 40 more

Latest 50 of 62 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SANITARY

WATER

ELECTRIC

ELECTRIC

WATER

WATER

29+00

30+00

31+00 32+00

+0

+8

22"

22"

10"

WATER

11+60

28+60 29+00 30+00 31+00 32+00 33+00 34+00 34+20

9.6

8.5

7.4

7.2

7.8

8.1

8.0

7.5

7.0

7.3

6.9

6.7

6.5

6.2

5.9

5.6

5.6

5.9

4.4

3.8

4.4

5.8

9.0

9.4

0.1 t h r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e e i g h t h i n c h o n e f o o t

A

B

C

D

E

F

Veterans

Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

SETH ANDREW CAVIN - ARCHITECT

JAMES ROSS MYLES - MECHANICAL ENGINEER

BENJAMIN ELIAS NOE - ELECTRICAL ENGINEER

#011.023503 EXP. 11/30/2022

#062.071715 EXP. 11/30/2023

#062.072296 EXP. 11/30/2023

CIVIL/ STRUCTURAL ENGINEER

OATES ASSOCIATES

100 LANTER COURT, SUITE 1

COLLINSVILLE, IL 62234

(618) 345-2200

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

DATA/COMM CONSULTANT

ASPEN ENGINEERING & CONSTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

EHRM INFRASTRUCTURE

UPGRADES

COMMISSIONING AGENT

ES2

13401 N. SANTA FE AVE.

OKLAHOMA, OK 73114

(405) 528-4500

A

M

AM

PHJ

FINAL BID DOCUMENTS

04/20/2023

657A5-21-700

MARION VA MEDICAL CENTER

2401 WEST MAIN ST.

MARION, IL 62959

SPUR #: 2114

No. REVISION DESCRIPTION DATE

CONTROLLED UNCLASSIFIED INFORMATION - CUI

CONTROLLED UNCLASSIFIED INFORMATION - CUI

N

BUILDING 43

SCALE: 1" = 20'

PATH B.10

NEW FIBER DUCTBANK

BUILDING 82

FIBER PLAN & PROFILE

CU214

SEE SHEET CU215

PATH B.10

STA 29+32 TO 29+37

REMOVE AND REPLACE EXISTING CONCRETE SIDEWALK,

SEE DETAIL 1 ON SHEET CU400

WATER, UNKNOWN DEPTH (TYP.)

ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT

STA 30+17 TO 30+80

REMOVE AND REPLACE EXISTING CONCRETE PAVEMENT

AND CURB & GUTTER, SEE DETAIL 8 & 10 ON SHEET CU401

STA 32+33 TO 32+39

REMOVE AND REPLACE EXISTING CONCRETE SIDEWALK,

SEE DETAIL 1 ON SHEET CU400 STA 33+43 TO 33+50

REMOVE AND REPLACE EXISTING CONCRETE SIDEWALK,

SEE DETAIL 1 ON SHEET CU400

BLDG 43

BLDG 82

EXISTING GROUND

REMOVE AND REPLACE EXISTING

CONCRETE SIDEWALK (TYP.)

SEE DETAIL 1 ON SHEET CU400

REMOVE AND REPLACE EXISTING

CONCRETE PAVEMENT AND CURB &

GUTTER, SEE DETAILS 8 & 10 ON SHEET CU401

REMOVE AND REPLACE EXISTING

CONCRETE SIDEWALK (TYP.)

SEE DETAIL 1 ON SHEET CU400

REMOVE AND REPLACE EXISTING

CONCRETE SIDEWALK (TYP.)

SEE DETAIL 1 ON SHEET CU400

MH EXAM

ROOM 110

SE

E

SH

EE

T

CU

STORM SEWER 24" HDPE, APPROX. INV 452.70

ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT

SANITARY SEWER 8" VCP, APPROX. INV 445.44

ADJUST DUCTBANK ALIGNMENT IF CONFLICT

STORM SEWER 24" HDPE, APPROX. INV 450.41

ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT

STORM SEWER 18" RCP, APPROX INV 448.83

ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT

STORM SEWER 24" HDPE, APPROX. INV 450.55

ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT

6' RADIUS (TYP)

WATER, UNKNOWN DEPTH

ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT

ELECTRIC, UNKNOWN DEPTH

ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT

2 BED

ROOM 120

STA. 32+49

COMM. HAND-HOLE

5' X 3'

TOP: 454.86

348' DUCT 6-4" CONDUIT 137' DUCT 6-4" CONDUIT

NOTE:

1. UNDERGROUND FACILITIES, STRUCTURES AND UTILITIES HAVE BEEN

PLOTTED FROM AVAILABLE SURVEYS AND RECORDS. THEIR

LOCATIONS MUST BE CONSIDERED TO BE APPROXIMATE ONLY. IT IS

POSSIBLE THERE MAY BE OTHERS, THE EXISTENCE OF WHICH IS NOT

PRESENTLY KNOWN OR SHOWN. IT IS THE CONTRACTOR'S

RESPONSIBILITY TO DETERMINE THEIR EXISTENCE AND EXACT

LOCATION AND TO AVOID DAMAGE THERETO, WHICH SHALL INCLUDE

ADJUSTMENTS OR RELOCATIONS AS NECESSARY TO COMPLETE THE

WORK SHOWN.

2. ALL OPEN TRENCHES MUST HAVE A 48-INCH TALL, ORANGE MESH

FENCE SURROUNDING THE AREA.

3. INSTALL TOP OF DUCT BANK AT LEAST 24 INCHES BELOW FINISHED

GRADE IN AREAS NOT SUBJECT TO DELIBERATE TRAFFIC, AND AT

LEAST 30 INCHES BELOW FINISHED GRADE IN DELIBERATE TRAFFIC

PATHS FOR VEHICLES.

4. CONTRACTOR SHALL REFER TO THE TECHNOLOGY PLANS TO

ENSURE CONDUIT FROM DUCTBANKS ENTER EACH BUILDING AT THE

INTENDED ROOM AND LOCATION. ADJUST DUCTBANK ALIGNMENT IF

NEEDED.

KEYED NOTES

1 CONTRACTOR TO INSTALL CONDUIT INTO BUILDING IN ACCORDANCE TO

THE VA PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL,

(PSRDM), LATEST EDITION.

MH

MH

PROVIDE AND INSTALL 4" SCH. 80 CONCRETE ENCASED DUCT BANK

ENCLOSURE. CONTRACTOR TO PROVIDE PULL-STRING

THROUGHOUT ENTIRE LENGTH OF CONDUITS.

ELEV. 447.3

ELEV. 449.33

204052

WATER

ELECTRIC

ELECTRIC ELECTRIC

EL

EC

TR

ICELECTRIC

TELECOM

+0

33+00

33+86

+5

36+80 36+00

FI

BE

R

OP

TI

C

GAS

W

AT

ER

11+00

11+61

40+00

10+00 10+22

21+66

20+00

21+00

43+00 43+77

19+60 20+00 21+00 22+00

2.1

1.3

1.1

1.0

1.0

0.9

0.7

0.6

1.3

35+60 36+00 37+00 37+20

1.3

1.1

0.9

1.3

1.2 t h r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e e i g h t h i n c h o n e f o o t

A

B

C

D

E

F

Veterans

Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

SETH ANDREW CAVIN - ARCHITECT

JAMES ROSS MYLES - MECHANICAL ENGINEER

BENJAMIN ELIAS NOE - ELECTRICAL ENGINEER

#011.023503 EXP. 11/30/2022

#062.071715 EXP. 11/30/2023

#062.072296 EXP. 11/30/2023

CIVIL/ STRUCTURAL ENGINEER

OATES ASSOCIATES

100 LANTER COURT, SUITE 1

COLLINSVILLE, IL 62234

(618) 345-2200

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

DATA/COMM CONSULTANT

ASPEN ENGINEERING & CONSTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

EHRM INFRASTRUCTURE

UPGRADES

COMMISSIONING AGENT

ES2

13401 N. SANTA FE AVE.

OKLAHOMA, OK 73114

(405) 528-4500

A

M

AM

PHJ

FINAL BID DOCUMENTS

04/20/2023

657A5-21-700

MARION VA MEDICAL CENTER

2401 WEST MAIN ST.

MARION, IL 62959

SPUR #: 2114

No. REVISION DESCRIPTION DATE

CONTROLLED UNCLASSIFIED INFORMATION - CUI

CONTROLLED UNCLASSIFIED INFORMATION - CUI

N

SCALE: 1" = 20'

FIBER PLAN & PROFILE

CU215

SEE SHEET CU214

SE

E

SH

EE

T

CU

PATH B.11 PATH B.12

ELECTRIC UNKNOWN DEPTH; ELECTRIC ESTIMATED 2FT

DEEP; FIBER UNKNOWN DEPTH

ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT (TYP)

EXISTING GROUND

BLDG 83

SEE SHEET CU301

SANITARY SEWER 8" PVC ESTIMATED 3.5FT DEEP,

ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT

STA. 36+56 TO 36+62

REMOVE AND REPLACE EXISTING CONCRETE SIDEWALK,

SEE DETAIL 1 ON SHEET CU400

SANITARY SEWER 8"PVC, ESTIMATED 12 FT DEEP

ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT

STORM 8" CPP, EST. 2 FT DEEP,

ELECTRIC UNKNOWN DEPTH

ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT

EXISTING GROUND

BLDG 82BLDG 8

PATH B.11

NEW FIBER DUCTBANK

REMOVE AND REPLACE EXISTING

CONCRETE SIDEWALK,

SEE DETAIL1 ON SHEET CU400,

PRO EXAM

ROOM 140

FILE ROOM

ROOM 016

PATH B.10

SEE SHEET CU214

PATH A.15

SEE SHEET CU218

PATH B.12

NEW FIBER DUCTBANK

REMOVE AND REPLACE EXISTING CONCRETE SIDEWALK,

SEE DETAIL1 ON SHEET CU400

PATH A.12

SEE SHEET CU216

PATH A.13

SEE SHEET CU217

ELECTRICAL ROUTE 2

SEE SHEET CU 300

BUILDING 82

BUILDING 8

BUILDING 83

OFFICE

ROOM 128

STA 20+17 TO 20+50

REMOVE AND REPLACE

EXISTING CONCRETE SIDEWALK

SEE DETAIL 1 ON SHEET CU400

STA 20+53 TO 20+65

REMOVE AND REPLACE

EXISTING CONCRETE SIDEWALK

SEE DETAIL 1 ON SHEET CU400

ELECTRIC ESTIMATED 3FT DEEP

ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT

STA. 21+67

COMM. MANHOLE 8' x 5'

TOP: 461.11

STA. 21+19

COMM. HAND-HOLE 5' X 3'

TOP: 460.82

119' DUCT 4-4" CONDUIT 47' DUCT 4-4" CONDUIT

70' DUCT 4-4" CONDUIT

STA. 21+67

COMM. HAND-HOLE

8' X 5'

TOP: 461.11

9' DUCT 4-4" CONDUIT

6' RADIUS (TYP)

NOTE:

1. UNDERGROUND FACILITIES, STRUCTURES AND UTILITIES HAVE BEEN

PLOTTED FROM AVAILABLE SURVEYS AND RECORDS. THEIR

LOCATIONS MUST BE CONSIDERED TO BE APPROXIMATE ONLY. IT IS

POSSIBLE THERE MAY BE OTHERS, THE EXISTENCE OF WHICH IS NOT

PRESENTLY KNOWN OR SHOWN. IT IS THE CONTRACTOR'S

RESPONSIBILITY TO DETERMINE THEIR EXISTENCE AND EXACT

LOCATION AND TO AVOID DAMAGE THERETO, WHICH SHALL INCLUDE

ADJUSTMENTS OR RELOCATIONS AS NECESSARY TO COMPLETE THE

WORK SHOWN.

2. ALL OPEN TRENCHES MUST HAVE A 48-INCH TALL, ORANGE MESH

FENCE SURROUNDING THE AREA.

3. INSTALL TOP OF DUCT BANK AT LEAST 24 INCHES BELOW FINISHED

GRADE IN AREAS NOT SUBJECT TO DELIBERATE TRAFFIC, AND AT

LEAST 30 INCHES BELOW FINISHED GRADE IN DELIBERATE TRAFFIC

PATHS FOR VEHICLES.

4. CONTRACTOR SHALL REFER TO THE TECHNOLOGY PLANS TO ENSURE

CONDUIT FROM DUCTBANKS ENTER EACH BUILDING AT THE INTENDED

ROOM AND LOCATION. ADJUST DUCTBANK ALIGNMENT IF NEEDED.

KEYED NOTES

1 CONTRACTOR TO INSTALL CONDUIT INTO BUILDING IN ACCORDANCE TO

THE VA PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL,

(PSRDM), LATEST EDITION.

MH

MH

HH

MH

HH

PROVIDE AND INSTALL 4" SCH. 80 CONCRETE ENCASED DUCT BANK

ENCLOSURE. CONTRACTOR TO PROVIDE PULL-STRING

THROUGHOUT ENTIRE LENGTH OF CONDUITS.

ELEV. 456.97

ELEV. 456.45 ELEV. 455.97

PATH B.11

CONNECTION

PATCH B.12 CONNECTION

204053

ELECTRIC

TE

LE

CO

M

EL

EC

TR

IC

WATER

ELECTRIC

TELECOM

33+86

+5

+0

35+82

36+80 36+00

FI

BE

R

OP

TI

C

GAS

TELECOM

WATERELECTRIC

ELECTRIC

WATER

EL

EC

TR

IC

11+00

11+61

40+00

41+00 41+19 43 +0

+4

10+00 10+22

21+66

11+60

10+00

11+00

43+00 43+77

34+20 35+00 36+00

1.7

1.0

1.1

2.1

2.0

1.7

9+60 10+00 10+60

1.2

1.2 t h r e e i n c h e s o n e f o o t o n e a n d o n e h a l f i n c h e s o n e f o o t o n e i n c h o n e f o o t t h r e e q u a r t e r s i n c h o n e f o o t o n e h a l f i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e e i g h t h i n c h o n e f o o t

A

B

C

D

E

F

Veterans

Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

SETH ANDREW CAVIN - ARCHITECT

JAMES ROSS MYLES - MECHANICAL ENGINEER

BENJAMIN ELIAS NOE - ELECTRICAL ENGINEER

#011.023503 EXP. 11/30/2022

#062.071715 EXP. 11/30/2023

#062.072296 EXP. 11/30/2023

CIVIL/ STRUCTURAL ENGINEER

OATES ASSOCIATES

100 LANTER COURT, SUITE 1

COLLINSVILLE, IL 62234

(618) 345-2200

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

DATA/COMM CONSULTANT

ASPEN ENGINEERING & CONSTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

EHRM INFRASTRUCTURE

UPGRADES

COMMISSIONING AGENT

ES2

13401 N. SANTA FE AVE.

OKLAHOMA, OK 73114

(405) 528-4500

A

M

AM

PHJ

FINAL BID DOCUMENTS

04/20/2023

657A5-21-700

MARION VA MEDICAL CENTER

2401 WEST MAIN ST.

MARION, IL 62959

SPUR #: 2114

No. REVISION DESCRIPTION DATE

CONTROLLED UNCLASSIFIED INFORMATION - CUI

CONTROLLED UNCLASSIFIED INFORMATION - CUI

N

SCALE: 1" = 20'

BUILDING 81

BUILDING 82

BUILDING 8

BUILDING 83

FIBER PLAN & PROFILE

CU216

PATH B.11

SEE SHEET CU215

SEE SHEET CU214

PATH A.14

NEW FIBER DUCTBANK

PATH A.13

SEE SHEET CU217

ELECTRICAL ROUTE 1

SEE SHEET CU300

PATH A.12 PATH A.14

STA. 34+63 TO 35+36

REMOVE AND REPLACE EXISTING

CONCRETE SIDEWALK, PAVEMENT, AND

CURB & GUTTER, SEE DETAILS 1 ON

SHEET CU400, 8 & 10 ON SHEET CU401

STA. 35+46 TO 35+58

REMOVE AND REPLACE EXISTING

CONCRETE SIDEWALK,

SEE DETAIL 1 ON SHEET CU400

WATER, ELECTRIC,ESTIMATED 2FT DEEP

ADJUST DUCTBANK ALIGNMENT IF IN

CONFLICT (TYP)

EXISTING GROUND BLDG 81

BLDG 83

REMOVE AND REPLACE EXISTING

ASPHALT PAVEMENT AND CONCRETE CURB,

SEE DETAIL 8 & 11 ON SHEET CU401

REMOVE AND REPLACE EXISTING

CONCRETE SIDEWALK,

SEE DETAIL1 ON SHEET CU400,

REMOVE AND REPLACE EXISTING

CONCRETE SIDEWALK,

SEE DETAIL1 ON SHEET CU400,

REMOVE AND REPLACE EXISTING

CONCRETE SIDEWALK,

SEE DETAIL1 ON SHEET CU400,

ELECTRICAL

ROOM 003

CORRIDOR

ROOM 203

WAITING

ROOM 101B

PATH B.10

SEE SHEET CU214

PATH B.13

SEE SHEET CU217

STORM SEWER 6" PVC ESTIMATED 4FT DEEP

ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT

ELECTRIC ESTIMATED 1FT DEEP

STA. 10+00 TO 10+22

REMOVE AND REPLACE EXISTING CONCRETE SIDEWALK,

SEE DETAIL 1 ON SHEET CU400

EXISTING

GROUND BLDG 8

BLDG 83

STAFF LOUNGE

ROOM 140

ELECTRIC, ESTIMATED 2' DEEP,

ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT

ELECTRIC, ESTIMATED 1' DEEP,

ADJUST DUCTBANK ALIGNMENT IF IN CONFLICT

PATH A.12

NEW FIBER DUCTBANK

ELECTRICAL ROUTE 2

SEE SHEET CU300

24' DUCT 4 - 4"

CONDUIT

132' DUCT 4-4" CONDUIT

NOTE:

1. UNDERGROUND FACILITIES, STRUCTURES AND UTILITIES HAVE BEEN

PLOTTED FROM AVAILABLE SURVEYS AND RECORDS. THEIR

LOCATIONS MUST BE CONSIDERED TO BE APPROXIMATE ONLY. IT IS

POSSIBLE THERE MAY BE OTHERS, THE EXISTENCE OF WHICH IS NOT

PRESENTLY KNOWN OR SHOWN. IT IS THE CONTRACTOR'S

RESPONSIBILITY TO DETERMINE THEIR EXISTENCE AND EXACT

LOCATION AND TO AVOID DAMAGE THERETO, WHICH SHALL INCLUDE

ADJUSTMENTS OR RELOCATIONS AS NECESSARY TO COMPLETE THE

WORK SHOWN.

2. ALL OPEN TRENCHES MUST HAVE A 48-INCH TALL, ORANGE MESH

FENCE SURROUNDING THE AREA.

3. INSTALL TOP OF DUCT BANK AT LEAST 24 INCHES BELOW FINISHED

GRADE IN AREAS NOT SUBJECT TO DELIBERATE TRAFFIC, AND AT

LEAST 30 INCHES BELOW FINISHED GRADE IN DELIBERATE TRAFFIC

PATHS FOR VEHICLES.

4. CONTRACTOR SHALL REFER TO THE TECHNOLOGY PLANS TO

ENSURE CONDUIT FROM DUCTBANKS ENTER EACH BUILDING AT THE

INTENDED ROOM AND LOCATION. ADJUST DUCTBANK ALIGNMENT IF

NEEDED.

KEYED NOTES

1 CONTRACTOR TO INSTALL CONDUIT INTO BUILDING IN ACCORDANCE TO

THE VA PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL,

(PSRDM), LATEST EDITION.

1 1

1 1

PROVIDE AND INSTALL 4" SCH. 80 CONCRETE ENCASED DUCT BANK

ENCLOSURE. CONTRACTOR TO PROVIDE PULL-STRING

THROUGHOUT ENTIRE LENGTH OF CONDUITS.

STA. 35+65

COMM. MANHOLE 5' x 3'

TOP: 462.05

MH

ELEV. 457.32

MH

204054

052_CU214 - FIBER PLAN & PROFILE
053_CU215 - FIBER PLAN & PROFILE
054_CU216 - FIBER PLAN & PROFILE