This document package outlines structural engineering plans and specifications for infrastructure upgrades at the Marion VA Medical Center in Marion, Illinois. The project involves demolishing existing patio structures and concrete slabs, constructing a new seismic tower addition, and upgrading building foundations and framing. Structural steel, metal decking, reinforced concrete, masonry, and cold-formed steel framing will be used. Foundation plans show new drilled piers and grade beams to support the tower addition. Framing plans depict the tower's W-shape beams and HSS bracing up to four levels with roof framing. Elevations and sections provide connection details. Specifications cover materials, welding, anchoring, and erection.
View the file
Other files
Show 40 more
Latest 50 of 62 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CODES AND SPECIFICATIONS
1. PROJECT IS DESIGNED IN ACCORDANCE WITH THE INTERNATIONAL BUILDING
CODE - 2018, INCLUDING ALL REFERENCED STANDARDS AS LISTED IN CHAPTER
35.
2. MINIMUM LOADING CONDITIONS ARE PER THE ASCE STANDARD, "MINIMUM
DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES, ASCE 7-16"
3. WHERE CONFLICT OCCURS BETWEEN REFERENCED CODES AND STANDARDS,
SPECIFICATIONS, AND GENERAL NOTES, THE MOST STRINGENT REQUIREMENT
SHALL GOVERN.
DESIGN CRITERIA: FOR BUILDING 38 ADDITION ONLY
RISK CATEGORY IV
DEAD LOAD:
FLOOR (1st, 2nd, 3rd & 4th):
STEEL BEAMS 3 PSF
CEILING & LIGHTS 5 PSF
MEP/IT TOWERS 10 PSF
SLAB & DECK (4 1/2" LW CONC.) 39 PSF
DEFLECTION CONC. 4 PSF
ROOF:
STEEL BEAMS 3 PSF
MEP 5 PSF
MISCELLANEOUS (CEILING, LIGHTS, ETC.) 4 PSF
METAL DECK (INSULATION) 3 PSF
LIVE LOAD:
FLOOR:
LOBBY/CORRIDORS 100 PSF
CORRIDORS ABOVE 1ST FLR. 80 PSF
ROOF:
MINIMUM LIVE LOAD 20 PSF
SNOW LOAD:
TERRAIN CATEGORY C
IMPORTANCE FACTOR, I 1.2
THERMAL FACTOR, Ct 1.0 EXPOSURE FACTOR, Ce 1.0 GROUND SNOW LOAD, Pg 20 PSF FLAT ROOF SNOW LOAD, Pf 24 PSF
WIND DESIGN DATA:
BASIC WIND SPEED, V 115 MPH
IMPORTANCE FACTOR, I 1.0
EXPOSURE CATEGORY C
INTERNAL PRESSURE COEFFICIENT, GCPI ±0.18
COMPONENTS & CLADDING WIND FORCES SHALL BE DETERMINED BASED ON
ASCE 7-16, CHAPTER 30
SEISMIC DESIGN DATA:
IMPORTANCE FACTOR, I 1.5
MAPPED SPECTRAL RESPONSE ACCELERATIONS
SHORT PERIOD PARAMETER, Ss 0.430
1 SECOND PARAMETER, S1 0.165
SOIL SITE CLASS D
DESIGN SPECTRAL RESPONSE ACCELERATIONS
SHORT PERIOD PARAMETER, SDS 0.417
1 SECOND PARAMETER, SD1 0.235
SEISMIC DESIGN CATEGORY D
BASIC SEISMIC-FORCE-RESISTING SYSTEM
NORTH-SOUTH & EAST-WEST DIRECTION:
ATTACHING TO EXISTING BUILDING WITH ORDINARY REINF. CONC. MOMENT
FRAMES
RESPONSE MODIFICATIONS FACTOR, R 3
SEISMIC RESPONSE COEFFICIENT, Cs 0.186
ANALYSIS PROCEDURE
DYNAMIC RESPONSE SPECTRA ANALYSIS
GEOTECHNICAL INFORMATION:
GEOTECHNICAL RECOMMENDATIONS ARE IN ACCORDANCE WITH THE
GEOTECHNICAL REPORT PROVIDED BY TERRACON DATED MAY 24, 2022.
CONCRETE DRILLED PIERS
26 FT - 31 FT DEPTH:
END BEARING 12,000 PSF
SKIN FRICTION 1,200 PSF
SKIN FRICTION FOR UPLIFT 800 PSF
BELOW 31'-0" DEPTH:
END BEARING 25,000 PSF
SKIN FRICTION 2,500 PSF
SKIN FRICTION FOR UPLIFT 1,667 PSF
(SHAFT TO EXTEND MIN. 1 DIAMETER INTO BEARING STRATUM)
10. ALL STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED, AND ERECTED IN
ACCORDANCE WITH THE AISC CODE OF STANDARD PRACTICE (LATEST EDITION),
EXCEPT AS MODIFIED IN THESE NOTES AND THE PROJECT SPECIFICATIONS.
11. SPLICING OF STEEL MEMBERS, UNLESS SHOWN ON THE DRAWINGS, IS
PROHIBITED WITHOUT WRITTEN APPROVAL OF THE ENGINEER.
12. NO CHANGE IN SIZE OR POSITION OF THE STRUCTURAL ELEMENTS SHALL BE
MADE AND HOLES, SLOTS, CUTS, ETC. ARE NOT PERMITTED THROUGH ANY
MEMBER UNLESS THEY ARE DETAILED ON THE APPROVED SHOP DRAWINGS.
13. NO FINAL BOLTING OR WELDING SHALL BE MADE UNTIL AS MUCH OF THE
STRUCTURE AS WILL BE STIFFENED THEREBY HAS BEEN PROPERLY ALIGNED.
14. UNLESS NOTED OTHERWISE, BEAMS SHALL BEAR 8" MINIMUM ON CONCRETE OR
MASONRY.
15. ALL EXPOSED STRUCTURAL STEEL IS TO BE PREPARED FOR ARCHITECTURAL
FINISHES ACCORDING TO AISC CODE OF STANDARD PRACTICE, SECTION 10,
ARCHITECTURALLY EXPOSED STRUCTURAL STEEL.
16. AN "UNSTABLE STEEL FRAME" SHALL BE CONSIDERED TO EXIST UNTIL ALL
FLOOR AND ROOF STRUCTURE AND PERMANENT BRACING OR SHEAR WALLS
ARE COMPLETED.
17. TEMPORARY BRACING SHALL BE INSTALLED TO PROVIDE STRUCTURAL
STABILITY AND RESIST LATERAL LOADS ON THE STRUCTURE DURING ERECTION.
BRACING SHALL REMAIN IN PLACE UNTIL ALL WELDING IS COMPLETE, ALL BOLTS
ARE COMPLETELY TIGHTENED, FLOORS AND ROOFS ARE COMPLETE, AND ALL
PERMANENT BRACING AND SHEAR WALLS ARE INSTALLED.
18. ALL CONNECTIONS FOR WHICH NO DESIGN ARE INDICATED SHALL BE DESIGNED
AND DETAILED BY THE FABRICATOR. DETAILING SHALL BE PERFORMED USING
RATIONAL ENGINEERING DESIGN AND STANDARD PRACTICE IN ACCORDANCE
WITH THE AISC MANUAL OF STEEL CONSTRUCTION (LRFD) AND THE
REQUIREMENTS OF THE CONTRACT DOCUMENTS. THE GENERAL DETAILS
INDICATED ON THE DRAWINGS ARE CONCEPTUAL ONLY AND DO NOT INDICATE
THE REQUIRED NUMBER OF BOLTS OR WELD SIZES, UNLESS SPECIFICALLY
NOTED. THE CONTRACTOR SHALL SUBMIT ENGINEERED CALCULATIONS AND
CONNECTION DRAWINGS FOR REVIEW TOGETHER WITH THE SUBMITTAL OF
TYPICAL STRUCTURAL STEEL CONNECTION DETAIL DRAWINGS. AFTER REVIEW,
THESE DRAWINGS SHALL BE UTILIZED AS THE STANDARD FOR FABRICATION AND
SHOP DRAWING DETAILING. THE DESIGN CALCULATIONS SHALL BE PREPARED
AND SEALED BY A QUALIFIED STRUCTURAL ENGINEER LICENSED IN THE STATE
OF ILLINOIS.
19. ALL CONNECTIONS, UNLESS NOTED OTHERWISE, SHALL BE SIMPLE SHEAR
CONNECTIONS UTILIZING "SHORT SLOTTED" HOLES AND HIGH STRENGTH BOLTS
IN BEARING-TYPE CONNECTIONS WITH THREADS INCLUDED IN THE SHEAR
PLANE. WHERE NO DESIGN LOAD IS PROVIDED ON THE PLANS, THE CONNECTION
SHALL BE DESIGNED FOR A MINIMUM FACTORED SHEAR REACTION OF 10 KIPS.
20. BEAM-TO-COLUMN AND BEAM-TO-BEAM CONNECTIONS SHALL BE MOMENT
CONNECTED WHERE INDICATED ON THE DRAWINGS. MOMENT CONNECTIONS
PART OF THE SLRS SHALL BE DESIGNED FOR THE MOMENT CAPACITY OF THE
BEAM UNLESS NOTED OTHERWISE AND FOLLOW CONCEPTUAL DETAILS
INDICATED ON THE DRAWINGS.
21. HIGH-STRENGTH BOLTS FOR CONNECTIONS, OTHER THAN THOSE DESIGNED AS
SLIP-CRITICAL, SHALL BE TIGHTENED TO A SNUG-TIGHT CONDITION. HIGH-
STRENGTH BOLTS FOR CONNECTIONS DESIGNED AS SLIP-CRITICAL, SHALL BE
TIGHTENED AS PER APPLICABLE VALUES IN THE RCSC "SPECIFICATION FOR
STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS".
22. THE MINIMUM NUMBER OF BOLTS PER CONNECTION SHALL BE (2) - 3/4 INCH
DIAMETER, A325 BOLTS IN EACH FAYING SURFACE.
23. THE MINIMUM FILLET WELD SIZES SHALL COMPLY WITH THE AISC SPECIFICATION
REQUIREMENTS, BUT SHALL NOT BE LESS THAN 1/4 INCH, UNLESS NOTED
OTHERWISE.
24. ALL GROOVE WELDS SHALL BE COMPLETE PENETRATION, UNLESS NOTED
OTHERWISE.
25. THE CONTRACTOR SHALL SUBMIT DETAILED, ENGINEERED, COORDINATED AND
CHECKED SHOP DRAWINGS FOR ALL STRUCTURAL STEEL MEMBERS FOR
REVIEW PRIOR TO THE START OF FABRICATION. AS NOTED ABOVE, CONNECTION
CALCULATIONS SHALL BE SUBMITTED IN ADVANCE TO ALLOW REVIEWED
CONNECTIONS TO BE INCORPORATED IN THE SHOP DRAWINGS.
26. ALL BEAMS SHALL BE FABRICATED WITH THE NATURAL CAMBER UP..
27. HEADED STUDS SHALL CONFORM TO ASTM A108, GR 1015, WELDABLE (Fu = 65
KSI).
28. TOP OF ALL TUBES AND PIPES SHALL HAVE A CAP PLATE 3/8 INCH, WELDED ALL
AROUND, UNLESS LARGER CAP PLATE AND/OR WELD IS NOTED. SEE TYPICAL
DETAIL. THIS DOES NOT APPLY TO DIAGONAL/SLOPING TUBES OR PIPES.
29. ALL SIMPLE SHEAR CONNECTIONS SHALL BE CAPABLE OF END ROTATION AS PER
THE REQUIREMENTS OF THE AISC SPECIFICATION, CHAPTER J1.2, "SIMPLE
CONNECTIONS".
30. BOLTS OF DIFFERING STEEL GRADES (A325,A490) MUST VARY IN BOLT DIAMETER
BY AT LEAST 1/4 INCH.
31. ALL STRUCTURAL BEAMS FRAMING INTO NEW AND/OR EXISTING CONCRETE OR
MASONRY MEMBERS SHALL BE DETAILED TO SUIT THE HORIZONTAL FIELD
TOLERANCES.
32. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE CONTROL OF ALL
ERECTION PROCEDURES AND SEQUENCES, INCLUDING, BUT NOT LIMITED TO,
TEMPERATURE DIFFERENTIALS, ERECTION TOLERANCES, AND WITH RESPECT
TO STRUCTURAL STEEL FRAMING INTO REINFORCED CONCRETE WALLS, BEAMS,
OR COLUMNS, OR FRAMING INTO EXISTING CONSTRUCTION.
4. REINFORCING SHALL CONFORM TO:
a. DEFORMED BARS ASTM A615 GRADE 60
b. DEFORMED BARS (WELDED) ASTM A706
c. WELDED WIRE FABRIC ASTM A1064
5. ALL REINFORCING SHALL BE DETAILED, FABRICATED, SUPPORTED, AND PLACED
IN ACCORDANCE WITH THE "ACI DETAILING MANUAL" AND CRSI'S "MANUAL OF
STANDARD PRACTICE", LATEST EDITIONS.
6. REINFORCING SHALL BE PLACED WITH CONCRETE COVER AS SHOWN IN DETAILS.
WHERE BAR PLACEMENT IS NOT SHOWN, PROVIDE CONCRETE COVER PER ACI
318, WITH THE FOLLOWING MINIMUM DIMENSIONS WHERE CONCRETE IS:
a. CAST AGAINST EARTH 3 IN
b. EXPOSED TO EARTH & WEATHER 2 IN
7. SPLICE REINFORCING BARS WITH CLASS "B" SPLICES, UNO, PER THE
REQUIREMENTS OF ACI 318. PROVIDE MINIMUM OF 6" LAP SPLICING FOR WWF IN
SOG AND 12" FOR ELEVATED SLABS.
8. CENTRAL LINE OF SPLICE OF WELDED WIRE FABRIC IN ELEVATED FLOOR SLABS
SHALL BE LOCATED AT MIDSPAN OF FLOOR SLAB.
9. SPLICES SHALL NOT BE LOCATED OVER FLOOR BEAMS.
10. PROVIDE FOUNDATION DOWELS OF THE SAME SIZE AND LOCATION AS THAT
REQUIRED IN COLUMN AND/OR WALL ABOVE. PROVIDE DEVELOPMENT AND
SPLICES PER ACI 318.
11. CONSTRUCTION JOINTS SHALL BE LOCATED ON THE SHOP DRAWINGS AND ARE
SUBJECT TO APPROVAL OF THE ENGINEER. LOCATE AT POINTS OF MINIMUM
SHEAR. REINFORCING SHALL BE CONTINUOUS THROUGH THE JOINT UNLESS IT
ALSO FUNCTIONS AS A CONTROL JOINT (50% PASSES). SUBMIT DETAILS OF
CONSTRUCTION JOINTS IN THE SHOP DRAWINGS. HORIZONTAL CONSTRUCTION
JOINTS ARE NOT ALLOWED IN WALLS OR SLABS.
12. CONTROL JOINTS SHALL BE SPACED AT 15 FOOT MAXIMUM INTERVALS. LAYOUT
SHALL CREATE NEARLY SQUARE OR RECTANGULAR (1.5:1 MAX) SECTIONS.
SUBMIT CONTROL JOINT LAYOUT FOR APPROVAL.
13. PROVIDE 3/4" CHAMFERS AT ALL EDGES THAT ARE EXPOSED TO VIEW IN THE
FINISHED STRUCTURE UNLESS SHOWN OTHERWISE IN THE ARCHITECTURAL
DRAWINGS.
14. CONCRETE EXPOSED TO FREEZE THAW CYCLES SHALL HAVE 6% AIR
ENTRAINMENT. DO NOT AIR ENTRAIN CONCRETE TO BE TROWEL FINISHED.
15. CONCRETE FINISH SHALL CONFORM TO ACI 301 UNO ON ARCHITECTURAL
DRAWINGS.
16. REFER TO ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, ETC. FOR
INFORMATION ON DOOR AND WINDOW LOCATIONS, LOUVER OPENINGS,
SLEEVES, CONDUIT, DRAINS, MISCELLANEOUS EMBEDDED ITEMS, ETC. THAT ARE
TO BE INCORPORATED IN THE WORK. THE VARIOUS TRADES ARE RESPONSIBLE
FOR PROVIDING AND PLACING THEIR ITEMS.
17. SEE MECHANICAL, ELECTRICAL, AND CIVIL DRAWINGS FOR EQUIPMENT PADS
AND FOUNDATION LOCATIONS. SEE TYPICAL DETAILS FOR CONSTRUCTION
UNLESS SPECIFIC DETAILS ARE PROVIDED.
18. SEE PLUMBING AND ARCHITECTURAL DRAWINGS FOR UNDERFLOOR AND
PERIMETER FOUNDATION DRAINS.
19. PROVIDE CONTINUOUS WATERSTOPS IN JOINTS OF PITS, RETAINING WALLS, AND
OTHER SIMILAR CONSTRUCTIONS. WATERSTOP PRODUCTS SHALL BE APPROVED
BY THE ENGINEER WHERE NOT SPECIFICALLY CALLED OUT ON DRAWINGS.
20. ALL STEEL ELEMENTS LOCATED BELOW GRADE SHALL BE COATED WITH A
MINIMUM OF 1/8" MASTIC AND COVERED WITH 3" MINIMUM CONCRETE FOR
PROTECTION.
21. EQUIPMENT PADS, TOPPING SLABS, FILL SLABS, ETC. SHALL BE REINFORCED
WITH #4 AT 16" O.C. EACH WAY, UNO.
22. CONDUITS, PIPES, AND SLEEVES OF ANY MATERIAL NOT HARMFUL TO CONCRETE
AND WITHIN THE LIMITATIONS OF ACI 318 SHALL BE PERMITTED TO BE EMBEDDED
IN CONCRETE, ONLY WITH PRIOR WRITTEN APPROVAL OF THE ARCHITECT. THE
CONTRACTOR SHALL SUBMIT DETAILED DIMENSIONED AND COORDINATED
DRAWINGS OF PROPOSED EMBEDDED CONDUIT, PIPES, AND SLEEVES TO THE
ARCHITECT PRIOR TO CONSTRUCTION.
23. CONDUITS AND PIPES EMBEDDED WITHIN A SLAB, WALL, OR BEAM (OTHER THAN
THOSE MERELY PASSING THROUGH) SHALL SATISFY THE FOLLOWING:
a. THEY SHALL NOT BE LARGER IN OUTSIDE DIAMETER THAN 1/3 THE
OVERALL THICKNESS OF THE SLAB, WALL, OR BEAM IN WHICH THEY
ARE EMBEDDED.
b. THEY SHALL NOT BE SPACED CLOSER THAN 3 DIAMETERS OR
WIDTHS
c. THEY SHALL NOT SIGNIFICANTLY IMPAIR THE STRENGTH OF THE
CONSTRUCTION.
24. ALL ANCHOR BOLTS, INSERTS, SLEEVES AND OTHER EMBEDDED ITEMS SHALL BE
SET BEFORE CONCRETE IS PLACED.
25. THE CONTRACTOR SHALL MAKE ALLOWANCE FOR DEAD LOAD DEFLECTION,
SETTLEMENT OF FORMS AND SHRINKAGE OF CONCRETE WHEN CONSTRUCTING
FORMS AND FORM WORK.
26. THE CONTRACTOR ALONE IS RESPONSIBLE FOR THE ADEQUACY OF ALL FORMS,
SHORING, ETC., USED IN CONSTRUCTION OF CONCRETE WORK.
27. ALL COLUMNS AND FOOTINGS ARE CENTERED ON COLUMN LINES EXCEPT
WHERE OTHERWISE SHOWN ON THE PLANS.
28. WALL CONSTRUCTION AND CONTROL JOINTS SHALL BE LOCATED ON SHOP
DRAWINGS FOR APPROVAL AND SPACED NOT TO EXCEED THE FOLLOWING,
WITHOUT WRITTEN APPROVAL BY STRUCTURAL ENGINEER OF RECORD:
a. CONSTRUCTION JOINTS 65 FEET
b. CONTROL JOINTS 25 FEET
29. ALL ABUTTING CONCRETE MEMBERS SHALL BE DOWELED TOGETHER, UNLESS
POURED MONOLITHICALLY. DOWELS SHALL BE EQUAL IN SIZE AND SPACING TO
THE REINFORCING IN THE ADJACENT MEMBER.
CONCRETE SLAB ON METAL DECK
1. THE CONTRACTOR SHALL PLACE CONCRETE FOR SLABS SO THAT THE FINISH
SURFACE IS SCREEDED LEVEL WITH AN ELEVATION WITHIN 1/4" OF THE TOP OF
SLAB ELEVATION SHOWN ON THE PLANS.
2. SLABS SHALL HAVE A TROWELED FINISH, UNLESS NOTES OTHERWISE ON THE
ARCHITECTURAL DRAWINGS, AND AS A MINIMUM BE TRUE PLANES WITHIN 1/4" IN
10 FEET, AS DETERMINED BY A 10 FOOT, UNLESS NOTED OTHERWISE, STRAIGHT
EDGE PLACED ANYWHERE ON THE SLAB IN ANY DIRECTION.
3. CONSIDERATION SHALL BE GIVEN TO SEQUENCING OF CONCRETE PLACEMENT
SO AS TO CONTROL FINISH ELEVATIONS WITHIN THE SPECIFIED LIMITS.
4. CONTRACTOR SHALL FURNISH THE ADDITIONAL CONCRETE DUE TO WET
CONCRETE DEFLECTION OF THE METAL DECK AND BEAMS, SEE DESIGN
CRITERIA FOR ALLOWABLE ADDITIONAL THICKNESS.
5. MECHANICAL, ELECTRICAL, AND PLUMBING CONDUIT, PIPING, AND OTHER ITEMS
SHALL BE ROUTED BELOW METAL DECK, NO CONDUIT, PIPING, JUNCTION BOXES,
OR OTHER ITEMS SHALL BE ALLOWED TO BE EMBEDDED IN CONCRETE SLAB
WIHTOUT PRIOR WRITTEN APPROVAL FROM THE STRUCTURAL ENGINEER OF
RECORD.
CONCRETE NOTES
1. CONCRETE MATERIALS AND CONSTRUCTIONS SHALL ADHERE TO THE "BUILDING
CODE REQUIREMENTS FOR STRUCTURAL CONCRETE AND COMMENTARY", ACI
318, YEAR ACCORDING TO PROJECT BUILDING CODE.
2. GENERAL CONSTRUCTION SHALL CONFORM TO THE REQUIREMENTS OF THE
"SPECIFICATIONS FOR STRUCTURAL CONCRETE", ACI 301, YEAR ACCORDING TO
PROJECT BUILDING CODE.
3. CONCRETE 28-DAY COMPRESSIVE STRENGTH AND DENSITY SHALL BE AS
FOLLOWS:
INTENDED USE f'c (PSI) DENSITY (PCF)
FOUNDATIONS 4000 145
SLAB ON GRADE 4000 145
DRILLED PIERS 7,000 OR 10,000 145
SLAB ON METAL DECK 4000 110
(LT.CONC.)
ALL OTHER CONCRETE 4000 145
DRILLED CONCRETE PIERS
1. THE BEARING ELEVATION AND CAPACITY, AS NOTED ON THE DRAWINGS, HAVE
BEEN ESTIMATED FROM THE GEOTECHNICAL EXPLORATION REPORT. THE FINAL
BEARING ELEVATIONS MAY VARY AND SHALL BE ESTABLISHED BY THE OWNER'S
SOILS TESTING LABORATORY AT THE TIME OF INSTALLATION OF EACH CAISSON.
2. THE CONTRACTOR SHALL REVIEW ALL EXISTING SITE CONDITIONS AND THE
GEOTECHNICAL EXPLORATION REPORT AND ESTABLISH SPECIFIC
CONSTRUCTION PROCEDURES AND SEQUENCES FOR THE INSTALLATION OF THE
CAISSONS, AND SUBMIT THESE FOR THE REVIEW BY THE OWNER'S SOIL TESTING
LABORATORY. THE CONTRACTOR'S PROCEDURES AND METHODS OF CAISSON
INSTALLATION SHALL MINIMIZE SETTLEMENT OF ADJACENT CONSTRUCTION, AND
THE CONTRACTOR SHALL HAVE SOLE RESPONSIBILITY FOR ALL REMEDIAL WORK
RESULTING FROM SUCH SETTLEMENT.
3. ALL PERMANENT CORRUGATED SHELL CASINGS SHALL BE GALVANIZED AND
CONSTRUCTED OF ASTM A929 CORRUGATED STEEL.
4. IF USED, ALL PERMANENT STEEL PLATE SHELL CASINGS SHALL BE CONSTRUCTED
OF ASTM A36 STEEL WITH CONTINUOUSLY WELDED SEAMS AND WITH A MINIMUM
THICKNESS OF 0.0075 TIMES THE DIAMETER OF THE CAISSON SHAFT, SEAMS ARE
TO BE TESTED BY THE OWNER'S SOILS TESTING LABORATORY (ULTRASONIC
METHOD).
5. IF THERE IS EVIDENCE OF CORROSIVE SOILS, THE DESIGN OF PERMANENT STEEL
PLATE CASINGS SHALL INCLUDE AND ACCOUNT FOR THE PROBABLE EXTENT AND
PENETRATION OF CORROSION.
6. ALL CAISSON CONCRETE SHALL BE NORMAL WEIGHT (145PCF) WITH A MINIMUM
58-DAY COMPRESSIVE STRENGTH OF 7,000 OR 10,000 PSI
7. ALL CAISSON REINFORCING SHALL CONFORM TO THE REQUIREMENTS OF ASTM
A615, GRADE 60..
8. THE BOTTOM OF EACH CAISSON SHALL BE THOROUGHLY CLEANED OF ALL LOOSE
MATERIAL.
9. NO CONCRETE SHALL BE PLACED INTO A CAISSON CONTAINING FREE WATER
WITHOUT PRIOR REVIEW BY THE OWNER'S SOIL TESTING LABORATORY.
10. CAISSON CONCRETE SHALL BE PLACED FULL LENGTH IN ONE CONTINUOUS POUR.
CONSTRUCTION JOINTS SHALL NOT BE USED WITHOUT PRIOR REVIEW BY THE
OWNER'S SOIL TESTING LABORATORY.
11. THE ANNULAR SPACE AROUND THE PERMANENT CORRUGATED STEEL CASING, AT
EACH CAISSON, SHALL BE FULLY GROUTED IMMEDIATELY AFTER PLACEMENT OF
THE SHAFT CONCRETE.
12. THE CONTRACTOR SHALL REMOVE ALL LAITANCE MATERIALS FROM THE TOP OF
EACH CAISSON PRIOR TO PLACEMENT OF FURTHER CONSTRUCTION.
13. SEE SPECIFICATION SECTION 316326, "DRILLED CAISSONS AND SHAFTS," FOR
ADDITIONAL REQUIREMENTS.
STRUCTURAL STEEL
1. STEEL MATERIALS AND CONSTRUCTION SHALL ADHERE TO THE AISC STEEL
CONSTRUCTION MANUAL, INCLUDING BUT NOT LIMITED TO, AISC 360
"SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS", AISC 341 "SEISMIC
PROVISIONS FOR STRUCTURAL STEEL BUILDINGS", RCSC "SPECIFICATION FOR
STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS", AND AISC 303 "CODE OF
STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES", EDITION AND YEAR
SHALL BE ACCORDING TO PROJECT BUILDING CODE.
2. PRIME PAINT STRUCTURAL STEEL AS NOTED BELOW:
a. PER ARCHITECTURAL DRAWINGS
b. INTERIOR STEEL PERMANENTLY EXPOSED TO VIEW
3. GALVANIZE ALL STRUCTURAL STEEL PERMANENTLY EXPOSED TO THE
WEATHER.
4. SEE SPECIFICATION SECTION 051200, "STRUCTURAL STEEL FRAMING", FOR
ADDITIONAL REQUIREMENTS NOT NOTED HEREIN.
5. THESE DRAWINGS SHALL NOT BE CONSIDERED "RELEASED FOR
CONSTRUCTION" UNTIL SPECIFICALLY SO INDICATED IN THE DRAWING ISSUE
BLOCK.
6. STEEL SHALL CONFORM TO THE FOLLOWING ASTM DESIGNATIONS, UNO:
a. WIDE FLANGE SHAPES A992
b. STEEL PIPE A53, GR B
c. HOLLOW STRUCTURAL SECTIONS A500, GR C
d. CHANNELS, ANGLES, PLATES A36
7. ASTM A325 OR ASTM A490 HIGH STRENGTH BOLTS SHALL BE USED FOR STEEL
TO STEEL CONNECTIONS, UNO. ASTM A307 GRADE A STANDARD BOLTS SHALL BE
USED FOR CONNECTIONS BETWEEN STEEL AND OTHER MATERIALS.
8. ALL WELDING SHALL BE IN ACCORDANCE WITH THE "STRUCTURAL WELDING
CODE" (AWS D1.1) PUBLISHED BY THE AMERICAN WELDING SOCIETY.
ELECTRODES FOR WELDING SHALL COMPLY WITH THE REQUIREMENTS OF
TABLE 4.4.1. OF AWS D1.1.
9. ANCHOR BOLTS SHALL BE ASTM F1554, GR 55, UNLESS NOTED OTHERWISE.
30. ALL ERECTION PROCEDURES, DESIGN, AND CALCULATIONS SHALL BE
PERFORMED BY THE CONTRACTOR'S QUALIFIED STRUCTURAL ENGINEER
LICENSED IN THE STATE OF ILLINOIS. ANY REVIEW OF SUCH CALCULATIONS
AND/OR DRAWINGS WILL BE SOLELY LIMITED TO ANY EFFECTS ON THE
INTEGRITY OF THE PERMANENT, PRIMARY STRUCTURE.
31. ALL ADDITIONAL STEEL REQUIRED BY THE CONTRACTOR FOR ERECTION
PURPOSES AND SITE ACCESS OF STOCKPILED MATERIALS SHALL BE PROVIDED
AT NO COST TO THE OWNER. ALL SUCH ADDITIONAL STEEL SHALL BE REMOVED
BY THE CONTRACTOR UNLESS APPROVED BY THE ARCHITECT IN WRITING.
METAL DECK
1. DECK SHALL BE CONTINUOUS OVER 3 SPANS, UNLESS NOTED OTHERWISE.
2. AT SUPPORTS PARALLEL TO THE DECK, RAISE STEEL SUPPORTS OR PROVIDE
SHIMS AT FASTENING POINTS IF THE DECK VALLEY DOES NOT ENGAGE THE
SUPPORT.
3. WHERE DECK IS WELDED TO SUPPORTS, PROVIDE WELDING WASHERS FOR
DECK WITH DESIGN THICKNESS LESS THAN 0.028 INCH.
4. AT CONTRACTOR'S OPINION, HILTI X-EDN AND ENP FASTENING SYSTEMS OR
APPROVED EQUAL MAY BE USED IN LIEU OF WELDS TO SUPPORTS. CONTACT
HILTI FOR DESIGN INFORMATION AND SUBMIT FOR APPROVAL.
5. METAL DECK ACCESSORIES, INCLUDING BUT NOT LIMITED TO: GIRDER FILLERS,
Z-CLOSURES, AND COVER PLATES THAT ARE INTEGRAL WITH THE FLOOR
DIAPHRAGM OR ROOF DIAPHRAGM SHALL BE OF THE SAME MATERIAL, FINISH,
AND MINIMUM THICKNESS AS THE METAL DECK. ACCESSORIES SHALL BE
ANCHORED TO SUPPORTING MEMBERS BY ARC SPOT WELDS OR SELF-DRILLING
SCREWS AT 12 INCH MAXIMUM SPACING OR AS SHOWN ON THE DESIGN
DRAWINGS.
6. ROOF DECK SHALL BE DESIGNED, FABRICATED, AND INSTALL IN ACCORDANCE
WITH "SDI CODE OF STANDARD PRACTICE AND COMMENTARY", SDI COSP-LATEST
EDITION.
7. 1 1/2" WIDE RIB ROOF DECK WITH DESIGN THICKNESS 0.0358" (20 GAUGE) SHALL
HAVE THE FOLLOWING MINIMUM PROPERTIES: Ip = 0.201 IN4/FT, In = 0.222 IN4/FT, Sp = 0.234 IN3/FT, Sn = 0.247 IN3/FT, Fy = 33 KSI
8. 1 1/2" NON- COMPOSITE FLOOR DECK WITH DESIGN THICKNESS 0.0358" (20
GAUGE) SHALL HAVE THE FOLLOWING MINIMUM PROPERTIES: Ip = 0.409 IN4/FT, In = 0.406 IN4/FT, Sp = 0.341 IN3/FT, Sn = 0.346 IN3/FT, Fy = 50 KSI
9. THE STEEL ROOF DECK HAS BEEN DESIGNED FOR A 20 PSF CONSTRUCTION LIVE
LOAD. THE CONTRACTOR SHALL NOT EXCEED THE ASSUMED CONSTRUCTION
DESIGN LIVE LOAD WITHOUT FIRST TAKING ALL NECESSARY SAFETY
PRECAUTIONS SUCH AS SHORING, ETC.
10. NO LOADS SHALL BE PERMITTED TO BE HUNG FROM ANY STEEL ROOF DECKING.
ALL DUCTWORK, PIPING, ETC., SHALL BE HUNG ON HANGERS DIRECTLY
ATTACHED TO THE STRUCTURAL STEEL FRAMING OR FROM SUPPLEMENTARY
FRAMING MEMBERS PROVIDED BY THE MEP CONTRACTOR. ALL HANGING LOAD
MAGNITUDES AND DETAILS SHALL BE SUBMITTED FOR REVIEW.
S
TATE
OF I L L I NO I S
L
IC
E N
S
ED
STRUCTURAL
ENG
I N E
E
RHALEY J. COONS
081-008013
ST. LOUIS, MO
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024
JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023
CIVIL/ STRUCTURAL ENGINEER
OATES ASSOCIATES
100 LANTER COURT, SUITE 1
COLLINSVILLE, IL 62234
(618) 345-2200
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
2519 MADISON AVE. STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
DATA/COMM CONSULTANT
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
EHRM INFRASTRUCTURE
UPGRADESCOMMISSIONING AGENT
ES2
13401 N. SANTA FE AVE.
OKLAHOMA, OK 73114
(405) 528-4500
/1
/2
:5 :3
P
M
GENERAL NOTES
SLPIMC
FINAL BID DOCUMENTS
04/20/2023
657A5-21-700
MARION VA MEDICAL CENTER
2401 WEST MAIN ST.
MARION, IL 62959
SJ001
205065
SPUR #: 2114
No. REVISION DESCRIPTION DATE
064 204
12. ALL SHOP DRAWINGS AND PRODUCT SUBMITTALS ARE REVIEWED FOR GENERAL
CONFORMANCE WITH THE PROJECT DOCUMENTS. REVIEWED SUBMITTALS DO
NOT RELIEVE THE CONTRACTOR FROM THE RESPONSIBILITY TO CONFORM WITH
THE DESIGN DRAWINGS AND SPECFICATIONS.
13. DETAILS NOTED AS "TYPICAL"/"TYP." ARE TO APPLY TO ALL CONDITIONS,
INCLUDING SIMILAR CONDITIONS, ON THE PROJECT EXCEPT WHERE SPECIFIC
DETAILS OR SECTIONS ARE PROVIDED. "TYPICAL" DETAILS APPLY REGARDLESS
OF BEING SPECIFICALLY NOTED OR CUT ON THE DRAWINGS. SPECIFIC DETAILS
SHALL ALSO APPLY TO THOSE CONDITIONS WHICH ARE THE SAME OR SIMILAR
ELSEWHERE ON THE JOB REGARDLESS OF BEING SPECIFICALLY NOTED OR CUT
ON DRAWINGS.
EXISTING CONDITIONS
1. CONTRACTOR SHALL BECOME FAMILIAR WITH EXISTING CONDITIONS PRIOR TO
BIDDING AND PROVIDE THE NECESSARY MEANS AND METHODS TO ACCOMPLISH
THE SPECIFIED WORK.
2. FIELD VERIFY ALL CONDITIONS, SIZES, SPACINGS, AND DIMENSIONS OF EXISTING
STRUCTURES OR OBSTACLES PRIOR TO FABRICATION AND/OR NEW
CONSTRUCTION. CONTACT ENGINEER IMMEDIATELY IF EXISTING CONDITIONS,
ETC. VARY FROM THOSE SHOWN ON THESE DRAWINGS.
3. CONTRACTOR IS RESPONSIBLE FOR THE TEMPORARY REMOVAL AND
REPLACEMENT/RELOCATION OF ANY NON-STRUCTURAL ELEMENTS NECESSARY
TO COMPLETE THE STRUCTURAL WORK. FOLLOW ALL APPLICABLE CODES AND
REQUIREMENTS OF THE AFFECTED TRADES. PROVIDE FOR THIS REQUIREMENT IN
THE BID.
4. CONTRACTOR SHALL CONFINE ALL OPERATIONS TO THE AREA SHOWN ON THE
PLANS. ANY AREA DISTURBED BEYOND THESE LIMITS SHALL BE RESTORED TO ITS
ORIGINAL CONDITION AT THE CONTRACTOR'S EXPENSE.
5. WHERE NEW CONCRETE MEETS EXISTING CONCRETE, CONTRACTOR SHALL CHIP
OR SAW CUT CONCRETE EDGES TO FORM A FLUSH AND CLEAN SURFACE PRIOR
TO INSTALLATION OF NEW CONCRETE.
6. CONTRACTOR SHALL PROVIDE TEMPORARY OR PERMANENT SHORING TO ALL
EXISTING CONTRUCTION WHERE NEW CONTRUCTION ABUTS, TO PREVENT
DAMAGE DURING NEW CONSTRUCTION WHETHER SHOWN ON THESE DRAWINGS
OR NOT. ANY DAMAGE TO EXISTING STRUCTURES, FOUNDATIONS, ETC. SHALL BE
REPAIRED BY THE CONTRACTOR AT NO COST TO THE OWNER PRIOR TO PROJECT
COMPLETION.
METAL DECK (CON'T)
16. SEE ARCHITECTURAL DRAWINGS FOR FIRE RATING REQUIREMENTS.
17. ALL STEEL ROOF DECK SHALL BE FABRICATED FROM STEEL CONFORMING TO
THE STANDARDS OF ASTM A653, STRUCTURAL QUALITY, HAVING A MINIMUM
YIELD STRENGTH OF 33 KSI. ALL STEEL ROOF DECK SHALL BE HOT-DIP
GALVANIZED TO THE STANDARDS OF ASTM A525 WITH A COATING CLASS OF
G-90, MINIMUM. WHERE APPLICABLE, VERIFY COMPATIBILITY OF GALVANIZING
AND SPRAY-ON-FIRE PROOFING WITH FIRE PROOFING SUPPLIER.
18. ALL STEEL ROOF DECK SHALL BE WIDE RIBBED, UNLESS NOTED OTHERWISE,
WITH DEPTH AND GAUGE AS INDICATED ON THE STRUCTURAL DRAWINGS. THE
DECK GAUGE SHALL NOT BE LESS THAN 20 GAUGE.
19. THE CONTRACTOR SHALL PROVIDE DETAILED AND CHECKED SHOP DRAWINGS
INDICATING LOCATION, GAUGE, AND SIZE OF EACH PIECE OF DECKING AND
RELATED DECKING ACCESSORIES. THE DRAWINGS SHALL CLEARLY SHOW
WELDING DETAILS TO STRUCTURAL FRAMING ELEMENTS, SIDELAP CONNECTION
DETAILS, DECK OPENING/EDGE CLOSURES, AND SUPPLEMENTARY DECK AND/OR
CLOSURE REINFORCING.
20. PROVIDE CONTINUOUS SHEET STEEL CLOSURES AT ALL DECK OPENINGS AND
DECK EDGES, UNLESS NOTED OTHERWISE.
21. PROVIDE, AS REQUIRED, ALL RIDGE AND VALLEY PLATES, COLUMN CLOSURES,
CANT STRIPS, SUMP PLATES AT PIPING PENETRATIONS, AND RECESSED SUMP
PANS AT ROOF DRAINS. PROVIDE SUPPLEMENTARY STRUCTURAL FRAMING,
INCLUDING BEAMS, ANGLES, AND/OR REINFORCING PLATES AT OPENINGS, AS
REQUIRED FOR SUPPORT OF THE STEEL ROOF DECK. ALL DECK OPENINGS
SHALL BE COORDINATED WITH ARCHITECTURAL AND MECHANICAL DRAWINGS.
22. ALL STEEL ROOF DECK ACCESSORIES SHALL BE HOT-DIP GALVANIZED TO A
COATING OF G-90, MINIMUM.
23. ALL STEEL ROOF DECK SHALL BE WELDED TO STRUCTURAL STEEL BY QUALIFIED
WELDERS USING PRE-QUALIFIED PROCEDURES. THE AWS SPECIFICATIONS
ESTABLISH A PROCEDURE FOR PRE-QUALIFICATION OF THE PLUG WELDING OF
THE STEEL DECKING TO THE STRUCTURAL STEEL FOR THE PARTICULAR GAUGES
USED. PRIOR TO THE START OF ERECTION OF THE STEEL COMPOSITE DECK, AND
ON A PERIODIC BASIS, AS DEEMED NECESSARY BY THE ARCHITECT AND THE
OWNER'S TESTING LABORATORY, EACH WELDER SHALL BE QUALIFIED USING
THIS PROCEDURE AS WITNESSED BY THE OWNER'S TESTING LABORATORY.
MISCELLANEOUS
1. STRUCTURAL DRAWINGS ARE INTENDED TO BE USED WITH ARCHITECTURAL AND
MECHANICAL DRAWINGS. CONTRACTOR IS RESPONSIBLE FOR COORDINATING
SUCH REQUIREMENTS INTO THEIR SHOP DRAWINGS AND WORK. IF A
DISCREPANCY BETWEEN DRAWINGS IS OBSERVED, CONTACT THE ENGINEER
IMMEDIATELY.
2. NO OPENING SHALL BE MADE IN ANY STRUCTURAL MEMBER WITHOUT THE
WRITTEN APPROVAL OF THE ARCHITECT/ENGINEER.
3. NO CHANGE IN SIZE OR DIMENSION OF STRUCTURAL MEMBERS SHALL BE MADE
WITHOUT THE WRITTEN APPROVAL OF THE ARCHITECT/ENGINEER.
4. DIMENSIONS OF OPENINGS IN FLOORS, ROOFS, AND WALLS, AND ASSOCIATED
SURROUNDING FRAMING, AND ANCHOR BOLT SIZES AND LOCATIONS ASSOCIATED
WITH MECHANICAL EQUIPMENT, SHALL BE VERIFIED BY THE CONTRACTOR WITH
ACTUAL EQUIPMENT FURNISHED FOR THE PROJECT PRIOR TO FABRICATION AND
INSTALLATION.
5. ALL OPENINGS AND SLEEVES ARE NOT SHOWN ON THE STRUCTURAL DRAWINGS.
FOR REQUIRED OPENINGS, REFER TO THE ARCHITECTURAL, MECHANICAL,
PLUMBING, ELECTRICAL, AND CIVIL DRAWINGS.
6. THE CONFIGURATION OF STRUCTURAL FRAMING REQUIRED TO SUPPORT
MECHANICAL, PLUMBING, AND ELECTRICAL EQUIPMENT IS BASED ON
PRELIMINARY PRODUCT INFORMATION. THE CONTRACTOR SHALL VERIFY WITH
THE MANUFACTURER OF THE EQUIPMENT FURNISHED FOR THE PROJECT THAT
THE CONFIGURATION IS SUITABLE. EQUIPMENT SHALL BE SUPPORTED ON ALL
SIDES BY STRUCTURAL FRAMING, IF FRAMING IS NOT LOCATED UNDER
EQUIPMENT CONTRACTOR SHALL NOTIFY THE ENGINEER IMMEDIATELY.
7. DO NOT SCALE THESE DRAWINGS, USE DIMENSIONS.
8. THE CONTRACTOR IS RESPONSIBLE FOR LIMITING THE AMOUNT OF
CONSTRUCTION LOAD IMPOSED UPON STRUCTURAL FRAMING. CONSTRUCTION
LOADS SHALL NOT EXCEED THE DESIGN CAPACITY OF THE FRAMING AT THE TIME
THE LOADS ARE IMPOSED.
9. THE STRUCTURE IS DESIGNED TO FUNCTION AS A UNIT UPON COMPLETION. THE
CONTRACTOR IS RESPONSIBLE FOR FURNISHING ALL TEMPORARY BRACING
AND/OR SUPPORT THAT MAY BE REQUIRED AS THE RESULT OF THE
CONTRACTOR'S CONSTRUCTION METHODS AND/OR SEQUENCES.
10. ALL THINGS WHICH, IN THE OPINION OF THE CONTRACTOR, APPEAR TO BE
DEFICIENCIES, OMISSIONS, CONTRADICTIONS, OR AMBIGUITIES, IN THE PLANS
AND SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT. PLANS AND/OR SPECIFICATIONS WILL BE CORRECTED, OR WRITTEN
INTERPRETATION OF THE ALLEGED DEFICIENCY, OMISSION, CONTRADICTION, OR
AMBIGUITY WILL BE MADE BY THE ARCHITECT BEFORE THE AFFECTED WORK
PROCEEDS.
11. CHECK ALL DIMENSIONS AGAINST REQUIREMENTS OF OTHER CONTRACT
DOCUMENTS. FIELD VERIFY DIMENSIONS RELATING TO EXISTING CONDITIONS
PRIOR TO ORDERING MATERIALS AND FABRICATION.
COLD-FORMED STEEL FRAMING (CFSF)
1. COLD-FORMED METAL FRAMING SHALL BE DESIGNED, FABRICATED, AND
ERECTED IN ACCORDANCE WITH AISI'S "SPECIFICATION FOR THE DESIGN OF
COLD-FORMED STEEL STRUCTURAL MEMBERS," YEAR ACCORDING TO PROJECT
BUILDING CODE.
2. MATERIALS SHALL CONFORM TO THE FOLLOWING, UNLESS NOTED OTHERWISE:
a. STRUCTURAL STEEL SHEET ASTM A653 SS
1. 0.0451 IN. (43 MILS) THICK OR LESS GRADE 33
2. 0.0566 IN. (54 MILS) THICK OR GREATER GRADE 50, CLASS 1
b. SELF-DRILLING SCREWS SAE 178
c. WELD ELECTRODES E60XX
3. ALL COLD-FORMED STEEL FRAMING AND ACCESSORIES SHALL BE MADE OF THE
TYPE, SIZE, GAUGE, AND SPACING SHOWN ON THE DRAWINGS AND
SPECIFICATIONS.
4. ALL STUDS SHALL HAVE A MINIMUM FLANGE WIDTH OF 1 5/8", A MINIMUM
THICKNESS OF 54 MILS, AND A MAXIMUM SPACING OF 16" O.C., UNLESS NOTED
OTHERWISE.
5. FULL-HEIGHT DOUBLE STUDS SHALL BE PROVIDED AT THE ENDS OF PARTITIONS,
AT WALL OPENINGS, BENEATH BAR JOISTS, BENEATH TRUSSES, AND AT OTHER
LOCATIONS INDICATED IN THE STRUCTURAL DRAWINGS.
a. WELD THE FLANGES OF DOUBLE STUDS TOGETHER FULL HEIGHT
USING 2" OF WELD AT 12" O.C. EA. SIDE.
6. ANCHOR STUD TRACKS WITH LOW-VELOCITY POWDER ACTUATED FASTENERS
WITH A MINIMUM SHANK DIAMETER OF 0.145" AND A MINIMUM PENETRATION OF 1
1/8". LOCATE ANCHORS AT 3' FROM THE ENDS OR PARTITIONS AND AT 6" O.C. MAX.
THROUGHOUT.
7. PROVIDE SHEATHING ATTACHED TO BOTH FACES OF WALL STUDS THROUGHOUT
THE LENGTH OF THE STUDS OR PROVIDE BRIDGING AT 4'-0" O.C.
8. PROVIDE STUD WALL BRIDGING ACCORDING TO MANUFACTURER'S
RECOMMENDATIONS.
9. PROVIDE STIFFENERS IN WEBS OF JOISTS AT BEARING POINTS AND AT
LOCATIONS OF CONCENTRATED LOADS.
10. PROVIDE MATCHING THICKNESS TRACK (54 mil MIN.) AT TOP AND BOTTOM OF
STUD WALLS AND AT HEADERS FOR STUD WALLS.
11. STUDS SHALL BE PLUMBED, ALIGNED, AND SECURELY ATTACHED TO FLANGES OR
WEBS OF LOWER TRACK. STUDS SHALL BE SEATED TIGHT TO TRACK WEBS PRIOR
TO ATTACHMENT. SHIMS AND UNLEVELED BEARING SURFACES ARE NOT
PERMITTED.
12. WALL STUDS SHALL BE SPACED A MAXIMUM OF 16" O.C. AND HAVE THE
FOLLOWING MINIMUM EFFECTIVE PROPERTIES. IN THE DESIGNATION BELOW, 600
IS THE MEMBER EFFECTIVE DEPTH IN 1/100 INCHES, S IS THE MEMBER STYLE, 162
IS THE FLANGE WIDTH IN 1/100 INCHES, AND 54 IS THE MATERIAL THICKNESS IN
MILS, UNLESS NOTED OTHERWISE.
a. EXTERIOR STUDS: 600S162-54
b. PARTITION STUDS: SEE ARCH.
13. AT LOCATIONS REQUIRING WELDING OF OR TO METAL STUDS, MINIMUM STUD
THICKNESS SHALL BE 54 MILS. ALL STUDS DAMAGED FROM WELDING SHALL BE
REPLACED.
REINFORCED MASONRY:
1. MASONRY MATERIALS AND CONSTRUCTION SHALL ADHERE TO THE BUILDING
CODE REQUIREMENTS FOR MASONRY STRUCTURES, ACI 530 AND THE
SPECIFICATION FOR MASONRY STRUCTURES, ACI 530.1, YEAR ACCORDING TO
PROJECT BUILDING CODE.
2. NOTES APPLY TO MASONRY SHOWN ON STRUCTURAL DRAWINGS AND SHALL BE
THE MINIMUM REQUIREMENTS FOR MASONRY SHOWN ON THE ARCHITECTURAL
DRAWINGS.
3. THE MASONRY SYSTEM SHALL HAVE A MINIMUM NET AREA COMPRESSIVE
STRENGTH, f'm, EQUAL TO 2000 PSI. GROUT SHALL COMPLY WITH ASTM C476.
MORTAR SHALL COMPLY WITH ASTM C270 AND BE TYPE S ABOVE GRADE AND
TYPE M BELOW GRADE, UNLESS NOTED OTHERWISE.
4. MASONRY UNITS SHALL BE NORMAL WEIGHT CONCRETE, 135 PCF, PER ASTM
C90.
5. REINFORCED MASONRY SHALL HAVE SPECIAL INSPECTIONS PER THE DESIGN
CODE REQUIREMENTS. SEE INSPECTION TABLES LOCATED WITHIN THE IBC OR
ACI 530.1 AS REQUIRED BY THE PROJECT BUILDING CODE.
6. REINFORCING SHALL COMPLY WITH ASTM A615, GRADE 60. JOINT REINFORCING
SHALL COMPLY WITH ASTM A951.
7. CONCRETE CONTRACTOR SHALL FURNISH DOWELS PROJECTING FROM CAST-IN-
PLACE CONCRETE. MASONRY CONTRACTOR SHALL FURNISH ALL OTHER
REINFORCING.
8. DOWELS FROM CONCRETE AND/OR MASONRY SHALL ALIGN WITH THE VERTICAL
AND/OR HORIZONTAL REINFORCING IN THE MASONRY. DOWELS SHALL MATACH
THE VERTICAL WALL REINFORCING, UNLESS NOTED OTHERWISE.
9. WHERE DOWELS DO NOT LINE UP WITHIN A BLOCK CELL, THEY MAY BE SLOPED
NO MORE THAN ONE HORIZONTAL TO SIX VERTICL (1H:6V). DOWELS MAY BE
GROUTED INTO A CELL IN VERTICAL ALIGNMENT EVEN THOUGH IT IS IN AN
ADJACENT CELL TO THE VERTICAL WALL REINFORCING.
10. REINFORCING SPLICES SHALL BE LAPPED ACCORDING TO ACI 530/530.1, MINIMUM
OF 24". REINFORCING SHALL BE WIRED TOGETHER.
11. VERTICAL REINFORCING SHALL BE POSITIONED TO MAINTAIN A CLEARANCE OF
3/4" FROM THE MASONRY SURFACE OR ADJACENT BARS AND NOT LESS THAN
ONE BAR DIAMETER BETWEEN BARS NOT SPLICED.
12. REINFORCING SHALL BE FIRMLY POSITIONED WITHIN THE MASONRY
CONSTRUCTION AT TOP AND BOTTOM AND AT INTERVALS NOT EXCEEDING 192
BAR DIAMETERS AND INSPECTED PRIOR TO THE START OF GROUTING.
13. GROUTING OF MASONRY BEAMS OVER OPENINGS SHALL BE DONE IN ONE
CONTINUOUS OPERATION.
14. CONTROL JOINTS SHALL BE LOCATED PER ARCH DRAWINGS. IF CONTROL JOINTS
ARE NOT LOCATED, SUBMIT A CONTROL JOINT PLAN FOR REVIEW.
15. JOINT REINFORCING SHALL TERMINATE AT CONTROL JOINTS. HORIZONTAL
REINFORCING BARS SHALL BE CONTINUOUS THROUGH CONTROL JOINTS AT
ROOF LINES, FLOOR LINES, AND AS NOTED IN THE DRAWINGS.
16. VERTICAL CELLS TO BE GROUTED SHALL BE CONSTRUCTED TO MAINTAIN A
MINIMUM CLEAR GROUT SPACE AS SHOWN BELOW:
a. GROUT LIFT 5'-4" OR LESS: 2 1/2"x3"
b. GROUT LIFT 5'-4" TO 12'-8": 3"x3"
c. GROUT LIFT 12'-8" TO 24'-0": 3"x4
17. PROVIDE GROUT KEYS BETWEEN GROUT POURS. FORM GROUT KEY BY
TERMINATING THE GROUT A MINIMUM OF 1" BELOW THE MORTAR JOINT.
18. ALL ANCHOR BOLTS, HEADED STUDS, REINFORCING, POST-INSTALLED ANCHORS,
ETC. SHALL BE PLACED IN SOLID GROUTED CELLS.
19. ALL MASONRY BELOW GRADE SHALL BE GROUTED SOLID. CAVITIES OF
MULTIWYTHE WALLS BELOW GRADE SHALL BE GROUTED SOLID.
20. DO NOT EMBED ALUMINUM ITEMS IN MASONRY UNLESS EFFECTIVELY COATED
TO RESIST THE REACTION DUE TO DISSIMILAR MATERIALS.
21. JOINT REINFORCING SHALL BE 9 GAGE MINIMUM AND PLACED AT A MINIMUM OF
16" O.C. AND IN THE FIRST TWO BED JOINTS AT THE BASE OF THE WALL. PROVIDE
AT 8" O.C. IN PARAPETS AND CANTILEVERED WALLS. JOINT REINFORCING SHALL
BE SPLICED 6" MINIMUM.
22. REFER TO DRAWINGS BY OTHER DISCIPLINES FOR DETAILS AND SPECIFIC
DIMENSIONS OF WINDOWS, DOORS, LOUVERS, AND OTHER ITEMS WITHIN THE
MASONRY. OPENINGS EQUAL TO OR SMALLER THAN 16"x16" ARE NOT TYPICALLY
SHOWN ON STRUCTURAL DRAWINGS.
23. OPENINGS SHALL BE CORED OR CUT WITH A MASONRY SAW LEAVING CLEAN
EDGES AND NO OVERCUT CORNERS.
24. TEMPORARY SHORING/BRACING OF WALLS IS BY CONTRACTOR. DO NOT
REMOVE UNTIL THE STRUCTURE'S LATERAL LOAD RESISTING SYSTEM IS
COMPLETE.
25. SET POST-INSTALLED ANCHORS AND DOWELS WITH HILTI HIT HY-270 OR EQUAL.
INSTALL PER THE STRICTEST RECOMMENDATION OF THE MANUFACTURER.
SUBSTITUTION REQUESTS MUST BE PRE-APPROVED BY THE ENGINEER.
ANCHORS SHALL BE 3/4" DIAMETER WITH 6" EMBEDMENT SPACED AT 16" O.C.,
UNLESS NOTED OTHERWISE.
15. WHERE STEEL ANGLES OR OTHER SHAPES ARE WELDED TO METAL STUDS,
CONNECT METAL TRACKS TO METAL STUDS WITH WELDS, NOT SCREWS.
16. WHERE STUD SYSTEM ABUTS STRUCTURAL COLUMNS OR WALLS, INCLUDING
MASONRY WALLS, ANCHOR ENDS OF BRIDGING / BLOCKING TO SUPPORTING
STRUCTURE.
S
TATE
OF I L L I NO I S
L
IC
E N
S
ED
STRUCTURAL
ENG
I N E
E
RHALEY J. COONS
081-008013
ST. LOUIS, MO
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024
JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023
CIVIL/ STRUCTURAL ENGINEER
OATES ASSOCIATES
100 LANTER COURT, SUITE 1
COLLINSVILLE, IL 62234
(618) 345-2200
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
2519 MADISON AVE. STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
DATA/COMM CONSULTANT
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
EHRM INFRASTRUCTURE
UPGRADESCOMMISSIONING AGENT
ES2
13401 N. SANTA FE AVE.
OKLAHOMA, OK 73114
(405) 528-4500
/1
/2
:5 :3
P
M
GENERAL NOTES
SLPIMC
FINAL BID DOCUMENTS
04/20/2023
657A5-21-700
MARION VA MEDICAL CENTER
2401 WEST MAIN ST.
MARION, IL 62959
SJ002
205066
SPUR #: 2114
065 204
SCHEDULE FOR F1554 ANCHORS
ANCHOR SIZE
• ROD THREADED 6" AT TOP END AND 3" AT BOTT. END.
4" MIN. PROJECTION.
• UNLESS OTHERWISE SPECIFIED, ALL ANCHOR RODS SHALL
BE GRADE 55.
• SEE THE BASE PLATE SCHEDULE FOR ANCHOR ROD SIZES
REQUIRED ON THIS PROJECT.
• ALL NUTS SHALL BE HEAVY HEX NUTS.
• ALL WASHERS SHALL BE PER AISC TABLE 14-2.
TYPE 1 (GR.36 & 55)
TYPE 2 (GR. 105)
3/4"
1"
1 1/4"
1 1/2"
DOUBLE NUT
PL. 1/2x3x3
L
1/ 2"
TACK
TACK
3/ 4"
M
IN
NUT & WASHER
3/ 4"
M
IN
NUT OR
HEADED BOLT
L
1/ 2"
TYPICAL BASE PL. & ANCHOR ROD DETAIL
1/4
L/
L/
L
W/2 W/2
W
1/
2"
1/ 2"
TYPE "X"
PL. TxLxB
T.O. CONC.
BASE PL., SEE SCHED.
1/
2" G
R O
U T
"T
T.O. CONC.
NUT & WASHER
BASE PL., SEE SCHED.
1/
2" G
R O
U T
"T
HOLE Ø
1 5/16"
1 13/16"
2 1/16"
2 5/16"
TYPE 1
1'-0"
1'-6"
1'-9"
2'-0"
TYPE X
1 1/2" 1 1/2"
1/4
L/
L/
L
W/2 W/2
W
1/
2"
1/ 2"
TYPE "X"
PL. TxLxB
1 1/2" 1 1/2"
TYPICAL FLOOR DECK DETAIL
NOTES:
1. METAL FLOOR DECK 1.5C NON-COMPOSITE - 20 GA. WITH
4 1/2" LW CONC. SLAB REINF. WITH 6x6-W1.4xW1.4 WWF.
2. SIDELAP FASTENERS: #10 TEK SCREWS, 3 PER SPAN.
3. ALL SUPPORTS PARALLEL TO FLUTES: 5/8" Ø PUDDLE
WELDS @ 6" O.C.
4. ALL TRANSVERSE SUPPORTS: 5/8" ⌀ PUDDLE WELDS 6
PER SHEET.
TYPICAL ROOF DECK DETAIL
NOTES:
1. METAL ROOF DECK 1.5B - 20 GA.
2. SIDELAP FASTENERS: #10 TEK SCREWS, 3 PER SPAN
3. ALL SUPPORTS PARALLEL TO FLUTES: 5/8" DIA. PUDDLE
WELDS @ 6" O.C.
4. ALL TRANSVERSE SUPPORTS: 5/8"⌀ PUDDLE WELDS 7 PER
SHEET.
TYPICAL DECK DETAILS
TOP OF
STEEL
5/8
TYP.
WELD PATTERN 36/7
3'-0".
TOP OF
STEEL
5/8
TYP.
WELD PATTERN 36/6
3'-0" SPAN
A
A
1/4" MIN.
TYPICAL BEAM SHEAR PL. CONNECTION SCHEDULE
1" M
IN
3" T
Y P
SHEAR PL., MIN 3/8” &
BOLTS PER SCHED.
CONNECTION SCHEDULE
BEAM SIZE MIN NO. OF ROWS OF 3/4” Ø
A325N BOLTS (U.N.O.)
W8/W10
W12/W14
W16
W18
W21
W24
W27
W30
NOTES:
1. BEAM WEB TO BE FILLED WITH MAXIMUM NUMBER OF BOLTS ALLOWED BASED ON
DIAMETER AND SPACING PER AISC.
2. CONNECTIONS TO DEVELOP ALLOWABLE UNIFORM LOADS (AUL) PER AISC MANUAL:
NONCOMPOSITE - 50% OF AUL + 5% AXIAL
GUSSET PL.
ERECTION BOLT
w/ SLOTTED HOLE
WELD
1/16" GAP
(3/16" MAX)
TYPICAL HSS SLOT TO GUSSET PL.
NOTE:
IF THE GAP BETWEEN THE GUSSET PL. AND THE VERTICAL BRACING
HSS EXCEEDS 1/16" THE WELD SIZE SHOWN MUST BE INCREASED BY
1/16" FOR EACH 1/16" INCREASE IN GAP SIZE.
PIER - SEE SCHEDULE⌀
CIRCULAR TIES -
SEE SCHEDULE
VERT. BAR REINF. -
SEE SCHEDULE
6" M
IN
VERT. DWLS
INTO PIER
TYPICAL DRILLED PIER SECTION
NOTES:
1. CIRCULAR TIES
A. ENDS SHALL OVERLAP A MIN. OF 6"
B. ENDS SHALL TERMINATE WITH
STANDARD 135° HOOKS WITH
EXTENSION LENGTH OF 3"
C. OVERLAPS AT ENDS OF ADJACENT
CIRCULAR TIES SHALL BE
STAGGERED AROUND THE
PERIMETER ENCLOSING THE
LONGITUDINAL BARS
2" CLR.
SEE SCHEDULE
PIER =
3" C
LR
3" C
LR
S
LA
B
P
IE
R C
A P
2'
#4 T
IE
S
2" O
.C
TOP OF PIER CAP/
GROUND LEVEL
ELEV. = 100'-0"
(4) #6 DWLS. x
5'-0" LONG
TYP. DRILLED PIER
SCALE: 1" = 1'-0"
'-0
E
N D
B E
A R
IN
G
IN
T
O S
A N
D S
T O
N E
G
E O
T E
C H
. T O
V E
R
IF
Y
IN
T
O S
U B
S T
R A
T E
P
IE
R
E M
B
T.O. SLAB ELEV.,
SEE PLAN
TYPICAL EDGE OF SLAB SUPPORT DETAIL U.N.O.
3/8” BENT PL.
FOR METAL DECK
ORIENTATION, SEE PLAN
3-12
3-12
CL. BEAM
PLAN
SEE
UP TO 4"
T.O. SLAB ELEV.,
SEE PLAN 3/8” BENT PL.
FOR METAL DECK
ORIENTATION, SEE PLAN
3-12
3-12
CL. BEAM
PLAN
SEE
TO 1'-0"
OVER 4"
T.O. SLAB ELEV.,
SEE PLAN 3/8” BENT PL.
FOR METAL DECK
ORIENTATION, SEE PLAN
3-12
3-12
CL. BEAM
PLAN
SEE
OVER 1'-0"
W-SHAPE w/ 3/8”
STIFF. PL. @ 2’-0” O.C.
6"
NOTE:
1. ROOF EDGE OF DECK SUPPORT DETAIL SIMILAR.
2. ROOF EDGE OF DECK SUPPORT SHALL BE CONTINUOUS AROUND ENTIRE PERIMETER,
UNLESS NOTED OTHERWISE. WELD ALL AROUND AT SPLICES TO MAKE CONTINUOUS. AT
CORNERS, MITER ANGLE 45 DEGREES AND WELD ALL AROUND TO MAKE CONTINUOUS.
STIFF. PL. TO MATCH
COLUMN FLANGE
THICKNESS MIN (N.S. & F.S.)
CAP PL. 3/4” w/ (4) 3/4”
Ø A325N BOLTS, MIN.
COL., SEE COL. SCHED.
A-A
TYP.
5/16
MIN.
3/8” MIN STIFF. -
CONN. PL (N.S. &
F.S.) DBL. SHEAR
TYPICAL COLUMN CONNECTION DETAIL
SECTION A-A
SEE PLAN
CANTILEVER
STIFF. PL. TO MATCH COLUMN
FLANGE THICKNESS MIN (N.S. & F.S.)
CAP PL. 3/4” w/ (4) 3/4”
Ø A325N BOLTS, MIN.
COL., SEE COL. SCHED.
A-A
TYP.
5/16
MIN.
3/8” MIN STIFF. -
CONN. PL (N.S. &
F.S.) DBL. SHEAR
TYPICAL CANTILEVER BEAM & COLUMN DETAIL
SECTION A-A
2' - 0"
2'
BAR TO MATCH TYP. VERT. WALL
REINF. OR AS SPECIFIED FOR
SHEAR WALL END BARS
2' - 0"
2'
"BOND BEAM REINF.
CORNER BARS IN MASONRY
BOND BEAMS, MATCH BOND
BEAM REINF.
CORNER BARS IN MASONRY
BOND BEAMS, MATCH BOND
BEAM REINF.
BOND BEAM REINF.
BAR TO MATCH TYP. VERT. WALL
REINF. OR AS SPECIFIED FOR
SHEAR WALL END BARS
TYPICAL MASONRY WALL CORNER REINFORCING
NOTE:
1. TYPICAL VERTICAL WALL REINFORCING NOT SHOWN FOR CLARITY.
TYPICAL SLAB TURN DOWN @ DOORS
GRADE BEAM - SEE 5 &
6 ON SB100 FOR
BALANCE OF INFO
SLAB AT OPENING IN
SCREEN WALL
#5 DWLS x1'-0" x 1'-6" @
12" O.C. @ OPENING
ONLY (3 MIN.)
#5x 2'-0" @ 12" O.C. @
OPENING ONLY (3 MIN.)
S
TATE
OF I L L I NO I S
L
IC
E N
S
ED
STRUCTURAL
ENG
I N E
E
RHALEY J. COONS
081-008013
ST. LOUIS, MO
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024
JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023
CIVIL/ STRUCTURAL ENGINEER
OATES ASSOCIATES
100 LANTER COURT, SUITE 1
COLLINSVILLE, IL 62234
(618) 345-2200
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
2519 MADISON AVE. STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
DATA/COMM CONSULTANT
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
EHRM INFRASTRUCTURE
UPGRADESCOMMISSIONING AGENT
ES2
13401 N. SANTA FE AVE.
OKLAHOMA, OK 73114
(405) 528-4500
/1
/2
:5 :3
P
M
TYPICAL DETAILS
SLPIMC
FINAL BID DOCUMENTS
04/20/2023
657A5-21-700
MARION VA MEDICAL CENTER
2401 WEST MAIN ST.
MARION, IL 62959
SJ003
205067
SPUR #: 2114
066 204
BACK-TO-BACK
BUILT-UP STUD
BACK-TO-BACK
BUILT-UP STUD
(43 mil MIN.)
BOX SHAPED
BUILT-UP STUD
(43 mil MIN.)
2-12 2-12
(2) #10 SDS @
12" O.C.
BACK-TO-BACK
BUILT-UP STUD
#10 SDS @
12" O.C.
BACK-TO-BACK
BUILT-UP STUD
(43 mil MIN.)
2-12
BOX SHAPED
BUILT-UP STUD
(43 mil MIN.)
2-12
TYPICAL BUILT-UP STUD DETAIL
OPTION 1 OPTION 2 OPTION 3
PLAN PLAN PLAN
3" M
IN.
SPA.
2" M
IN.
FROM EDGE
ATTACH TRACK TO SLAB USING (2) HILTI X-U
UNIVERSAL KNURLED SHANK FASTENERS @
10" O.C. w/ 1 1/8" MIN. PENETRATION
LOCATED AS SHOWN ABOVE, INSTALL PER
MANUFACTURER'S SPECIFICATIONS
CONC. SLAB
(1) #10 SDS @
EA. FLANGE E
.O . S
LA
B
2" M
IN
F
R O
M
S P
A
3" M
IN
TRACK
TYPICAL BOTTOM TRACK CONNECTION
TOP VIEW
INTERIOR DRYWALL PER ARCH. DWGS
ALTERNATE TEMPORARY BRACING UNTIL
DRYWALL IS INSTALLED, FOR WALL HEIGHT LESS
THAN 13'-0", PROVIDE ONE ROW @ MID-HEIGHT.
FOR WALL HEIGHT MORE THAN 13'-0", PROVIDE 2
ROWS OF BRACING @ THIRD POINTS
3 5/8"x 33 mil MIN. STUD OR TRACK.
EXTERIOR SHEATHING
1 SCREW @ EA. STUD
L2x2x54 mils w/ (2) SCREWS
TO STUD & CHANNEL
PERMANENT BRACING:
1 1/2"x54 mil COLD-ROLLED
STEEL CHANNEL, SEE SPECS
PROVIDE EITHER TYPE OF BRACING FOR ALL STUYDS THAT RECEIVE
EXTERIOR SHEATHING BUT WHOSE INTERIOR FLANGES ARE NOT
BRACED WITH DRYWALL EIGHTER TEMPORARILY OR PERMANENTLY.
TYPICAL EXTERIOR STUD WALL BRACING DETAIL
TYPICAL WALL STUD CONNECTION TO STEEL
WITH SLIDE CLIP
ATTACH TO STUD w/ (3) #14
SHOULDERED SCREWS
(PROVIDED), CENTERED IN SLOTS
(ADJACENT TO "≠" STAMP
SIMPSON STRONG-TIE
SC SLIDE CLIP
METAL STUD
TYP.
3/8" MIN.
FULL BEARING AT
ANCHOR LEG
TYP.
1/2" M
IN
5" MIN.
STRUCTURAL STEEL
(4) #12-14 SCREWS, FILL
ALL ANCHOR HOLES
TYPICAL WALL STUD CONNECTION TO
STEEL BEAM ABOVE WITH SLIDE CLIP
STR
U
C
TU
R E
1" C
LR
. TO
DO NOT ATTACH
STUD TO TRACK
SIMPSON STRONG-TIE
SCW5.5 SLIDE CLIP
METAL STUD
TYP.
1/2" MIN.
ATTACH TO STUD w/ (3) #14
SHOULDERED SCREWS
(PROVIDED), CENTERED IN SLOTS
(ADJACENT TO "≠" STAMP
(4) #12-14 SCREWS, FILL
ALL ANCHOR HOLES
5 1/2" M
IN.
TY
P.
1/ 2"
M
IN
(3) #10 SDS @ EA. TRACK
SECTION, EA. SIDE
TRACK (TYP.)
12" LONG STUD SECTION, MATCH
GAGE & SIZE OF TRACK
TYPICAL TRACK SPLICE DETAIL
BACK-TO-BACK
STUD SPLICE
S P
LI
C
E
M
IN
. O V
E R
LA
P
BOTTOM OF SPLICE (6) #10 SDS
SPACED EQUAL
ON SPLICE
T Y
P
2" M
IN
TYPICAL VERTICAL STUD SPLICE DETAIL
BAR
SPACING
BAR SPACING
OPENING
BAR SPACING
B A
R S
P A
C
IN
G
B A
R
S P
A C
IN
G
AT WALL INTERSECTION
AT CORNER AND END
WALL REINFORCEMENT NOTES:
1. PROVIDE BOND BEAMS WITH (2) #5 BARS (CONT.) AT THE FOLLOWING LOCATIONS:
A. AT THE TOP AND BOTTOM OF ALL WALLS.
B. AT THE TOP AND BOTTOM OF ALL WALL OPENINGS (EXTEND BEAM 24"
PAST THE FACE OF THE OPENINGS).
C. AT MIDHEIGHT.
D. AT ROOF SUPPORT LEVELS.
E. AT 4'-0" O.C. MAXIMUM.
2. PROVIDE CORNER BARS AND BARS AT INTERSECTING WALLS OF MATCHING SIZE
AS BOND BEAM REINFORCING AND SPLICE 20" WITH REGULAR BOND BEAM
REINFORCING.
3. PROVIDE CONTINUOUS HORIZONTAL TRUSS REINFORCEMENT AS FOLLOWS:
A. AT 16" VERTICAL CENTERS.
B. PROVIDE 2 TRUSS LAYERS AT 8" VERTICAL CENTERS ABOVE AND BELOW
WALL OPENINGS (EXTEND 24" PAST THE FACE OF THE OPENINGS).
C. HORIZONTAL TRUSS REINFORCING SHALL NOT RUN THROUGH VERTICAL
MASONRY CONTROL JOINTS.
4. PROVIDE VERTICAL REINFORCEMENT IN GROUTED CELLS AS FOLLOWS:
A. NON LOAD BEARING WALLS #4 @ 48" O.C.
B. EXTERIOR & LOAD BEARING WALLS #5 @ 32" O.C.
C. SHEARWALLS SEE SCHED.
5. CORNER BARS AND END BARS SHALL BE THE SAME SIZE AS MAIN VERT.
REINFORCEMENT.
6. LOCATE VERTICAL BARS IN SAME CELL AS FOUNDATION DOWEL BARS.
COORDINATE INSTALLATION WITH CONCRETE CONTRACTOR(S).
TYPICAL MASONRY WALL DETAILS
END BAR
FULL HEIGHT
CORNER BAR
FULL HEIGHT
END BAR
FULL HEIGHT
CORNER BAR FULL HEIGHT
END BAR FULL HEIGHT
TYPICAL EXTERIOR WALL OPENING DETAIL
B-B
A-A
PROVIDE 4 ADD'L 0.157" Ø 1 1/2"
HILTI X-U FASTENERS @ JAMBS
2" MAX.
(3) #10 SDS EA. SIDE
TRACK
STUD BELOW HEADER ONLY
TRACK
STUD BELOW HEADER
BRIDGING
(4) #10 SDS EA. SIDE L2x2x54 mil x 5" LONG w/
(4) #10 SDS EA. LEG
TRACK
(1) #10 SDS EA. SIDE
HEADER
1/4" MAX. GAP
16 GA. STUD16 GA. TRACK w/ (2)
#10 SDS @ 16" O.C.
SECTION B-B
STUD
#10 SDS @ 8" O.C.
(4 PLACES) TRACK
STUD BELOW HEADER
#10 SDS @ 16" O.C.
(TYP.)
SECTION A-A
AT JAMB
CLARK DIETRICH
SPAZZER BAR
TSN BRIDGE BAR (OR CRC)
w/ TSN BRIDGE CLIP (4) #10
SDS REQ'D
CLIP ANGLE L2x2x54 mil w/ (4) #10 SDS, ANGLE
TO BE 1/4" LESS THAN
STUD WIDTH
1 1/2"x54 mil COLD-
ROLLED CHANNEL
TYPICAL EXTERIOR STUD WALL BRACING DETAIL
LAP
1' - 0"
OPTION 1 OPTION 2 OPTION 3
PLAN VIEW
NOTES:
1. AT CONTRACTOR'S OPINION, FIELD WELD BRIDGING TO STUDS.
2. SEE GENERAL NOTES FOR BRIDGING REQUIREMENTS.
NOTE:
SCREWS SHALL HAVE 3/4"
EDGE DISTANCE MINIMUM.
S
TATE
OF I L L I NO I S
L
IC
E N
S
ED
STRUCTURAL
ENG
I N E
E
RHALEY J. COONS
081-008013
ST. LOUIS, MO
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024
JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023
CIVIL/ STRUCTURAL ENGINEER
OATES ASSOCIATES
100 LANTER COURT, SUITE 1
COLLINSVILLE, IL 62234
(618) 345-2200
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
2519 MADISON AVE. STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
DATA/COMM CONSULTANT
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
EHRM INFRASTRUCTURE
UPGRADESCOMMISSIONING AGENT
ES2
13401 N. SANTA FE AVE.
OKLAHOMA, OK 73114
(405) 528-4500
/1
/2
:5 :3
P
M
TYPICAL DETAILS
AuthorChecker
FINAL BID DOCUMENTS
04/20/2023
657A5-21-700
MARION VA MEDICAL CENTER
2401 WEST MAIN ST.
MARION, IL 62959
SJ004
205068
067 204
D
C
SEISMIC TOWER
BUILDING 1
BUILDING 38
BUILDING 2
P A
T
IO
R O
O F
S T
R U
C T
U R
E
V .I.
F
PATIO ROOF STRUCTURE
24' - 7 1/2" +/- V.I.F.
REMOVE PATIO ROOF
STRUCTURE AND HSS
PATIO COLUMNS
REMOVE HSS PATIO
COLUMNS - 8 TOTAL
V.I.F. (TYP.)
EXISTING ENCLOSED
BREEZEWAY TO REMAIN
(V.I.F.)
EXISTING PATIO ROOF STRUCTURE OVER
ENCLOSED BREEZEWAY TO REMAIN
UNLESS GC REQUIRES REMOVAL FOR
CONSTRUCTION PURPOSES (V.I.F.) . IF ANY
PORTIO IS REMOVED GC TO REPLACE TO
MATCH EXISTING.
V .I.
F .E
X T
E N
D O
F C
O N
C . S
LA
B
R E
M O
V A
L P
E R
F O
U N
D A
T
IO
N P
LA
N
/8
10' - 4"
V.I.F. EXTEND OF CONC. SLAB REMOVAL PER FOUNDATION PLAN
17' - 5 1/2" +/-
REMOVE EXIST.
CONC. SLAB
5' - 10"
ADDITIONAL SUPPORT MAY BE
REQUIRED IF PATIO ROOF IS
SUPPORT BY ADJACENT PATIO ROOF
(V.I.F.)
BLDG. 1
BLDG. 2
BLDG. 38
AREA OF
WORK
S
TATE
OF I L L I NO I S
L
IC
E N
S
ED
STRUCTURAL
ENG
I N E
E
RHALEY J. COONS
081-008013
ST. LOUIS, MO
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City,…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .