This solicitation is for a construction project to upgrade telecommunications infrastructure at the Marion VA Medical Center in Marion, Illinois. The scope of work includes installing new category 6A cabling and fiber optic backbones to various buildings on campus, upgrading telecommunications rooms, and demolishing old cabling systems. The required work will provide new high-speed data network connectivity to clinical and administrative areas. The solicitation is available through the Department of Veterans Affairs Technology Acquisition Center and responses are due by January 2023. The anticipated award date is in February 2023.
View the file
Other files
Show 40 more
Latest 50 of 62 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ABBREVIATIONS
STANDARD MOUNTING HEIGHTSANNOTATION
ELECTRICAL: (AFF, AFG UNLESS NOTED OTHERWISE)
CU
TELECOMMUNICATION PLAN NOTE CALL OUT
EQUIPMENT DESIGNATION TAG
NEW WORK TO EXISTING WORK CONNECTION POINT
IC
CATV
FO
T
D
S
IC
S
WAP
# / #TV
M
S
V
COMMUNICATIONS OUTLET, TYPE AS NOTED
COMMUNICATIONS OUTLET, FLOOR BOX, TYPE AS NOTED
WIRELESS ACCESS POINT, CEILING MOUNTED
COMMUNICATIONS OUTLET, CEILING MTD, TYPE AS NOTED
SPEAKER, WALL MOUNTED
SPEAKER, CEILING MOUNTED
TELECOMMUNICATIONS RACK, TWO-POST, FLOOR MOUNTED
GROUND BAR, TYPE AS NOTED
TELECOMMUNICATIONS ENCLOSURE, WALL MOUNTED
CABLE/BASKET TRAY, TYPE AS NOTED
CABLE TELEVISION LINE
FIBEROPTIC LINE
TELEPHONE LINE
FIBER OPTIC BACKBONE PATHWAY "A"
DATA LINE
SPEAKER LINE
INTERCOM LINE
INTERCOM, "M" DENOTES MASTER STATION
VOLUME CONTROL, WALL MOUNTED
MULTI-SERVICE POWER POLE WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
MULTI-SERVICE FLOOR BOX/POKE-THRU WITH POWER/DATA,
TYPE AS NOTED AND/OR SCHEDULED
TELECOMMUNICATIONS CHANNEL RACK, 7'H x 19"W x 30"D, 4-POST, OPEN FRAME TYPE
SERVER CABINET, FLOOR MOUNTED
# = DATA, # = QUANTITY OF CABLES
#TV = CABLE TELEVISION, # = QUANTITY OF CABLES
# = DATA, # = QUANTITY OF CABLES
#TV = CABLE TELEVISION, # = QUANTITY OF CABLES
#V = VOICE, # = QUANTITY OF CABLES
= DATA, 2 CABLES
# = DATA, # = QUANTITY OF CABLES
TELECOMMUNICATIONS SYMBOLS
#TV = CABLE TELEVISION, # = QUANTITY OF CABLES
#V = VOICE, # = QUANTITY OF CABLES
M (CONT'D)
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
X
W
V
U
T
S
R
P
O
N
M
L
K
J
I
H
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABL FIRE ALARM BELL
FABX FIRE ALARM BOX
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FI FILM ILLUMINATOR
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FLUOR FLUORESCENT
FO FIBER-OPTIC
FP FIRE PROTECTION
FT FEET OR FOOT
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G
F
E
D
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMCP EMER. MONITORING CONTROL PANEL
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
ESMT EASEMENT
ETD EXISTING TO BE DEMOLISHED
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST EXISTING
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DISTR PNL DISTRIBUTION PANEL
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
C CONDUIT
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/
CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER
INSTALLED
CFE CONTRACTOR FURNISHED
EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER
CLF CURRENT LIMITING FUSE
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAX CABLE
COMM COMMUNICATION
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
C
B
A
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VCM VERTICAL CABLE MANAGER
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
TC TIME CLOCK
TEL TELEPHONE
TO TELECOMMUNICATIONS OUTLET
TR TELECOMMUNICATIONS ROOM
TV TELEVISION
TYP TYPICAL
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REC RECESSED
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RU RACK UNIT
N NEUTRAL
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MT MOUNT
MTD MOUNTED
MTG MOUNTING
KV KILOVOLT
KVA KILOVOLT AMPERE
KVAH KILOVOLT AMPERE PER HOUR
KVAR KILOVOLT AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
KWHM KILOWATT HOUR METER
JB JUNCTION BOX
J-BOX JUNCTION BOX
XFER TRANSFER
XFMR TRANSFORMER
XP EXPLOSION PROOF
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LM LUMEN
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LTCP LOCAL TEMPERATURE CONTROL PANEL
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
W WATT
WAO WORK AREA OUTLET
WP WEATHERPROOF
IESNA ILLUMINATION ENGINEERING SOCIETY
OF NORTH AMERICA
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
G OR GND GROUND OR GENERATOR
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
SCC SHORT CIRCUIT CAPACITY
SES SERVICE ENTRANCE SECTION
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, PULL BOX, OR
PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PCB POLYCHLORINATED BIPHENYL
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
POD POWER OPERATED DAMPER
POE POWER OVER ETHERNET
PP PATCH PANEL
PT POTENTIAL TRANSFORMER
PTRV POWER TYPE ROOF VENTILATION
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
1P SINGLE POLE
1PH SINGLE-PHASE
3P THREE POLE
3PH THREE-PHASE
3W THREE WIRE
4W FOUR WIRE
A/C AIR CONDITIONING
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC
FREQUENCY CONTROL, OR
AVAILABLE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB OR A AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
HCM HORIZONTAL CABLE MANAGER
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
BAT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISH FLOOR
BIL BASIC INSULATION LEVEL
BLDG BUILDING
BLK BLOCK
BPIP BOILER PLANT
INSTRUMENTATION PANEL
BRKR BREAKER
BYP BY PASS
DETAIL REFERENCE
SECTION CUT DESIGNATION
EP-101
EP-101
PATH-A
PATH-B FIBER OPTIC BACKBONE PATHWAY "B"
84" 48" 48" 84" 48" 80" 60"
120" 60" 36" 48" 72" 48"
144" 18" 24" 26" 48" 48"
CEILING
48" 48" 18" 84"
AUDIBLE APPLIANCES (CENTERLINE)
ALARMS
ANNUNCIATOR PANELS
CLOCK OUTLETS (CENTERLINE)
CONTROLS (TOP)
EXIT SIGNS (WALL-MOUNTED, BOTTOM)
FIRE ALARM ANNUNCIATOR PANEL (DISPLAY)
FIRE ALARM BELL (EXTERIOR)
FIRE ALARM CONTROL PANEL/UNIT (DISPLAY)
INTERCOM (AFEA ONLY)
INTERCOMS (TOP)
PANELS & PANELBOARDS (TOP)
PULL STATIONS (HANDLE)
PHOTOCELLS
RECEPTACLES (BOTTOM)
RECEPTACLES (EXTERIOR)
RECEPTACLES (GARAGES) RECEPTACLES IN
EQUIPMENT ROOMS (TOP) REMOTE INDICATING
LIGHT (EQUIPMENT ROOMS) REMOTE INDICATING
LIGHT (FINISHED AREAS) SAFETY SWITCHES &
STARTERS SWITCHES (TOP)
TELEPHONE/DATA/TV OUTLETS (BOTTOM)
VISIBLE APPLIANCES (CENTERLINE)
#E = ELEVATOR, # = QUANTITY OF CABLES
TE TELECOMMUNICATIONS ENCLOSURE
VERTICAL CABLE MANAGER, 6" WIDE, WITH DOORS
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
EHRM INFRASTRUCTURE
UPGRADES
No. REVISION DESCRIPTION DATE
CIVIL/ STRUCTURAL ENGINEER
OATES ASSOCIATES
100 LANTER COURT, SUITE 1
COLLINSVILLE, IL 62234
(618) 345-2200
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
2519 MADISON AVE. STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
DATA/COMM CONSULTANT
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
COMMISSIONING AGENT
ES2
13401 N. SANTA FE AVE.
OKLAHOMA, OK 73114
(405) 528-4500
SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024
JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023
/1
5/
:5 9:
P
M
TECHNOLOGY SYMBOLS & ABBREVIATIONS
NR 168 205SR04/20/2023
657A5-21-700
MARION VA MEDICAL CENTER
2401 WEST MAIN ST.
MARION, IL 62959 T-000
SPUR #: 2114
FINAL BID DOCUMENTS
204167
4 4
4 4
GENERAL PLAN NOTES
1. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND
DURING INSTALLATION..
2. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF
ADDITIONAL CABLE DROPS.
3. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL
CUT-OVER TO THE NEW CABLING.
4. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN ITS
DESIGNATED TR.
5. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.
6. EXISTING CAT6A CABLING MAY REMAIN IN PLACE.
7. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED
UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.
8. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. ADHERE TO CABLING COLOR CODE AND LABELING
STANDARDS. (SEE SPECIFICATIONS)
9. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS
ALONG THE CABLE PATHWAYS.
10. EXISTING CONDUITS TO REMAIN.
11. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.
12. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE SECONDARY BONDING BUSBAR.BOND ALL PARTS OF TRAY SYSTEMS TO THE TELECOMMUNICATIONS PRIMARY/SECONDARY
BUSBAR.
13. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE
WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR
SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER
ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE
RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES WHERE CABLING
WAS REMOVED.
14. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE
SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE
THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.
ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR BIOMED ARE NOT DISTURBED (TYPICALLY
ORANGE CATEGORY AND AQUA OM4 FIBER OPTIC CABLING).
ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR WIRELESS AND SECURITY SYSTEMS ARE NOT
DISTURBED.
15. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND
CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.
16. CONTRACTOR SHALL REINSTALL CEILING TILES AT THE END OF EVERY WORK SHIFT.
17. CONTRACTOR SHALL INSTALL TEMPORARY FIRESTOPPING IN ANY PENETRATIONS OF NETWORK
CABLING THROUGH FIRE RATED WALLS AT THE END OF EVERY WORK SHIFT. TEMPORARY
FIRESTOPPING SHALL CONSIST OF MINERAL WOOL AND PROVIDE PROTECTION AGAINST FIRE/SMOKE
SPREAD THROUGH UNSEALED PENETRATION.
18. CONTRACTOR SHALL INSTALL FIRESTOPPING IN ALL FIRE RATED WALLS WHERE NETWORK CABLING
WAS REMOVED TO ENSURE FIRE RATING OF WALL.
CSELECT.
H
SS
T-300
T-300
4 4
4 4
4 4
TR
4 4
4 4
4 4
44 4444
4 4
4 4
TECHNOLOGY KEYNOTES
TELECOMMUNICATIONS EQUIPMENT RACK, 7'H x 19"W x 29"D, 4-POST, OPEN FRAME TYPE.
INSTALL BASKET TRAY ABOVE NETWORK RACKS IN TR AS DEPICTED ON PLANS.
INSTALL BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING ALONG HALLWAY. INSTALL J-HOOKS IN
AREAS WHERE BASKET TRAY IS INAPPROPRIATE.
INBOUND REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE CONNECTORS ON
BOTH ENDS.
INBOUND REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLES FIELD TERMINATED WITH LC TYPE CONNECTORS
ON BOTH ENDS.
CONTRACTOR SHALL PULL CABLES AFTER HOURS IN THIS BUILDING.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
EHRM INFRASTRUCTURE
UPGRADES
No. REVISION DESCRIPTION DATE
CIVIL/ STRUCTURAL ENGINEER
OATES ASSOCIATES
100 LANTER COURT, SUITE 1
COLLINSVILLE, IL 62234
(618) 345-2200
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
2519 MADISON AVE. STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
DATA/COMM CONSULTANT
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
COMMISSIONING AGENT
ES2
13401 N. SANTA FE AVE.
OKLAHOMA, OK 73114
(405) 528-4500
SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024
JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023
/1
5/
:5 9:
P
M
NR 169 205SR04/20/2023
657A5-21-700
MARION VA MEDICAL CENTER
2401 WEST MAIN ST.
MARION, IL 62959 T-100
SPUR #: 2114
N
1/8" = 1'-0"
TECHNOLOGY PLAN - BLDG 8 BASEMENT1
N
1/8" = 1'-0"
TECHNOLOGY PLAN - BLDG 8 LEVEL 12
N
1/8" = 1'-0"
TECHNOLOGY PLAN - BLDG 8 - LEVEL 23
TECHNOLOGY PLANS - BLDG 8
204168
TR
T-300
T-300
UNEXC.
CS-2
UNEXC.
CS-1
STORAGE
STORAGE
STORAGE
STORAGE
4A
STORAGE
STOR.
CLERICAL
101A
CONFERENCE
OFFICE
UP
OFFICE
FILE
STAIR
OFFICE
WOMEN
MEN
OFFICE
LOBBY
OFFICE
CORRIDOR
4 4
4 444
4 4
4 4
DN
OFFICE
WORK AREA
201A
CORR.
OFFICE
204RESTROOM
RESTROOM
OFFICE
OFFICE
MECH.
CLOSET
LOBBY
FEC
6 6
GENERAL PLAN NOTES
1. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND
DURING INSTALLATION..
2. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF
ADDITIONAL CABLE DROPS.
3. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL
CUT-OVER TO THE NEW CABLING.
4. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN ITS
DESIGNATED TR.
5. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.
6. EXISTING CAT6A CABLING MAY REMAIN IN PLACE.
7. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED
UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.
8. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. ADHERE TO CABLING COLOR CODE AND LABELING
STANDARDS. (SEE SPECIFICATIONS)
9. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS
ALONG THE CABLE PATHWAYS.
10. EXISTING CONDUITS TO REMAIN.
11. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.
12. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE SECONDARY BONDING BUSBAR.BOND ALL PARTS OF TRAY SYSTEMS TO THE TELECOMMUNICATIONS PRIMARY/SECONDARY
BUSBAR.
13. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE
WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR
SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER
ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE
RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES WHERE CABLING
WAS REMOVED.
14. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE
SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE
THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.
ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR BIOMED ARE NOT DISTURBED (TYPICALLY
ORANGE CATEGORY AND AQUA OM4 FIBER OPTIC CABLING).
ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR WIRELESS AND SECURITY SYSTEMS ARE NOT
DISTURBED.
15. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND
CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.
16. CONTRACTOR SHALL REINSTALL CEILING TILES AT THE END OF EVERY WORK SHIFT.
17. CONTRACTOR SHALL INSTALL TEMPORARY FIRESTOPPING IN ANY PENETRATIONS OF NETWORK
CABLING THROUGH FIRE RATED WALLS AT THE END OF EVERY WORK SHIFT. TEMPORARY
FIRESTOPPING SHALL CONSIST OF MINERAL WOOL AND PROVIDE PROTECTION AGAINST FIRE/SMOKE
SPREAD THROUGH UNSEALED PENETRATION.
18. CONTRACTOR SHALL INSTALL FIRESTOPPING IN ALL FIRE RATED WALLS WHERE NETWORK CABLING
WAS REMOVED TO ENSURE FIRE RATING OF WALL.
TECHNOLOGY KEYNOTES
TELECOMMUNICATIONS EQUIPMENT RACK, 7'H x 19"W x 29"D, 4-POST, OPEN FRAME TYPE.
INSTALL BASKET TRAY ABOVE NETWORK RACKS IN TR AS DEPICTED ON PLANS.
INSTALL BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING ALONG HALLWAY. INSTALL J-HOOKS IN
AREAS WHERE BASKET TRAY IS INAPPROPRIATE.
INBOUND REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE CONNECTORS ON
BOTH ENDS.
INBOUND REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLES FIELD TERMINATED WITH LC TYPE CONNECTORS
ON BOTH ENDS.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
EHRM INFRASTRUCTURE
UPGRADES
No. REVISION DESCRIPTION DATE
CIVIL/ STRUCTURAL ENGINEER
OATES ASSOCIATES
100 LANTER COURT, SUITE 1
COLLINSVILLE, IL 62234
(618) 345-2200
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
2519 MADISON AVE. STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
DATA/COMM CONSULTANT
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
COMMISSIONING AGENT
ES2
13401 N. SANTA FE AVE.
OKLAHOMA, OK 73114
(405) 528-4500
SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024
JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023
/1
5/
:0 0:
P
M
NR 170 205SR04/20/2023
657A5-21-700
MARION VA MEDICAL CENTER
2401 WEST MAIN ST.
MARION, IL 62959 T-101
SPUR #: 2114
N
1/8" = 1'-0"
TECHNOLOGY PLAN - BLDG 13 BASEMENT1
N
1/8" = 1'-0"
TECHNOLOGY PLAN - BLDG 13 LEVEL 12
N
1/8" = 1'-0"
TECHNOLOGY PLAN - BLDG 13 - LEVEL 23
TECHNOLOGY PLANS - BLDG 13
204169
UP
DN
DN
UP
LOCKER
100B
LOCKER
100A
MEZZ. FLOOR
OFFICE
BOILER
DN
DN
DN
T-300
T-300
EQUIP.
MAINT.
104STORAGE
OFFICE
103B
RR
103A
EMERG.
GEN.
BAY
4 4
GENERAL PLAN NOTES
1. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND
DURING INSTALLATION..
2. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF
ADDITIONAL CABLE DROPS.
3. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL
CUT-OVER TO THE NEW CABLING.
4. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN ITS
DESIGNATED TR.
5. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.
6. EXISTING CAT6A CABLING MAY REMAIN IN PLACE.
7. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED
UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.
8. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. ADHERE TO CABLING COLOR CODE AND LABELING
STANDARDS. (SEE SPECIFICATIONS)
9. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS
ALONG THE CABLE PATHWAYS.
10. EXISTING CONDUITS TO REMAIN.
11. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.
12. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE SECONDARY BONDING BUSBAR.BOND ALL PARTS OF TRAY SYSTEMS TO THE TELECOMMUNICATIONS PRIMARY/SECONDARY
BUSBAR.
13. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE
WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR
SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER
ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE
RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES WHERE CABLING
WAS REMOVED.
14. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE
SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE
THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.
ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR BIOMED ARE NOT DISTURBED (TYPICALLY
ORANGE CATEGORY AND AQUA OM4 FIBER OPTIC CABLING).
ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR WIRELESS AND SECURITY SYSTEMS ARE NOT
DISTURBED.
15. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND
CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.
16. CONTRACTOR SHALL REINSTALL CEILING TILES AT THE END OF EVERY WORK SHIFT.
17. CONTRACTOR SHALL INSTALL TEMPORARY FIRESTOPPING IN ANY PENETRATIONS OF NETWORK
CABLING THROUGH FIRE RATED WALLS AT THE END OF EVERY WORK SHIFT. TEMPORARY
FIRESTOPPING SHALL CONSIST OF MINERAL WOOL AND PROVIDE PROTECTION AGAINST FIRE/SMOKE
SPREAD THROUGH UNSEALED PENETRATION.
18. CONTRACTOR SHALL INSTALL FIRESTOPPING IN ALL FIRE RATED WALLS WHERE NETWORK CABLING
WAS REMOVED TO ENSURE FIRE RATING OF WALL.
TECHNOLOGY KEYNOTES
TELECOMMUNICATIONS WALL-MOUNT RACK, 36"H x 26"W x 30"D, VENTED, SOLID WALL TYPE. TO BE
CAGED PER PHYSICAL SECURITY REQUIREMENTS.
INSTALL BASKET TRAY ABOVE NETWORK RACKS IN TR AS DEPICTED ON PLANS.
INSTALL BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING ALONG HALLWAY. INSTALL J-HOOKS IN
AREAS WHERE BASKET TRAY IS INAPPROPRIATE.
INBOUND REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE CONNECTORS ON
BOTH ENDS.
INBOUND REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLES FIELD TERMINATED WITH LC TYPE CONNECTORS
ON BOTH ENDS.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
EHRM INFRASTRUCTURE
UPGRADES
No. REVISION DESCRIPTION DATE
CIVIL/ STRUCTURAL ENGINEER
OATES ASSOCIATES
100 LANTER COURT, SUITE 1
COLLINSVILLE, IL 62234
(618) 345-2200
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
2519 MADISON AVE. STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
DATA/COMM CONSULTANT
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
COMMISSIONING AGENT
ES2
13401 N. SANTA FE AVE.
OKLAHOMA, OK 73114
(405) 528-4500
SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024
JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023
/1
5/
:0 0:
P
M
NR 171 205SR04/20/2023
657A5-21-700
MARION VA MEDICAL CENTER
2401 WEST MAIN ST.
MARION, IL 62959 T-102
SPUR #: 2114
N
1/8" = 1'-0"
TECHNOLOGY PLAN - BLDG 14 LEVEL 11
N
1/8" = 1'-0"
TECHNOLOGY PLAN - BLDG 14 - LEVEL 22
TECHNOLOGY PLANS - BLDG 14
204170
T-301
T-301
2 2
2 2
2 2 2 2 2 2 2 2 2
BREAK ROOM
CONFERENCE
ROOM
STORAGE
ASST. CHIEF
ENGINEER
CHIEF
ENGINEER
FACILITY
PLANNER
ENERGY
MANAGER
M&O
SUPERVISOR
M&O
SUPERVISOR
WOMENS
TOILET
MENS TOILET
M&O
SUPERVISOR
M&O
SUPERVISOR
CLOSET
MECHANICAL
101CTR
101D
HAC
UNISEX STAFF
TLT
UNISEX STAFF
TLT
PLAN ROOM
PROJECT
ENGINEER
SUPERVISOR
CORRIDOR
C02
ADMIN OFFICE
ASST
CORRIDOR
C01B
CORRIDOR
C01A
CORRIDOR
C01
ELECTRICAL
105A
PROJECT
ENGINEERS
WORKSTATIONS
VESTIBULE
PROJECT
ENGINEERS
EGRESS
121B
STORAGE
C01D
LOBBY
ENG.
CLERK/TRANS.MGR
101A
PROJECT
ENGINEERS
WORKSTATIONS
121A
2 2
T-301
T-301
PHARMACY
OFFICE
SUPPLIES
105D
ENGINEERING
105EFREEZER
110A
REFRIGERATOR
110 LOADING
DOCK
OXYGEN
OFFICE
SPACE
105A
MAILROOM
OFFICE
BREAK
ROOM
WAREHOUSE
STORAGE
4 4
4 4
TR
105D
GENERAL PLAN NOTES
1. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND
DURING INSTALLATION..
2. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF
ADDITIONAL CABLE DROPS.
3. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL
CUT-OVER TO THE NEW CABLING.
4. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN ITS
DESIGNATED TR.
5. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.
6. EXISTING CAT6A CABLING MAY REMAIN IN PLACE.
7. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED
UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.
8. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. ADHERE TO CABLING COLOR CODE AND LABELING
STANDARDS. (SEE SPECIFICATIONS)
9. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS
ALONG THE CABLE PATHWAYS.
10. EXISTING CONDUITS TO REMAIN.
11. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.
12. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE SECONDARY BONDING BUSBAR.BOND ALL PARTS OF TRAY SYSTEMS TO THE TELECOMMUNICATIONS PRIMARY/SECONDARY
BUSBAR.
13. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE
WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR
SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER
ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE
RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES WHERE CABLING
WAS REMOVED.
14. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE
SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE
THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.
ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR BIOMED ARE NOT DISTURBED (TYPICALLY
ORANGE CATEGORY AND AQUA OM4 FIBER OPTIC CABLING).
ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR WIRELESS AND SECURITY SYSTEMS ARE NOT
DISTURBED.
15. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND
CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.
16. CONTRACTOR SHALL REINSTALL CEILING TILES AT THE END OF EVERY WORK SHIFT.
17. CONTRACTOR SHALL INSTALL TEMPORARY FIRESTOPPING IN ANY PENETRATIONS OF NETWORK
CABLING THROUGH FIRE RATED WALLS AT THE END OF EVERY WORK SHIFT. TEMPORARY
FIRESTOPPING SHALL CONSIST OF MINERAL WOOL AND PROVIDE PROTECTION AGAINST FIRE/SMOKE
SPREAD THROUGH UNSEALED PENETRATION.
18. CONTRACTOR SHALL INSTALL FIRESTOPPING IN ALL FIRE RATED WALLS WHERE NETWORK CABLING
WAS REMOVED TO ENSURE FIRE RATING OF WALL.
TECHNOLOGY KEYNOTES
TELECOMMUNICATIONS EQUIPMENT RACK, 7'H x 19"W x 29"D, 4-POST, OPEN FRAME TYPE.
INSTALL BASKET TRAY ABOVE NETWORK RACKS IN TR AS DEPICTED ON PLANS.
INSTALL BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING ALONG HALLWAY. INSTALL J-HOOKS IN
AREAS WHERE BASKET TRAY IS INAPPROPRIATE.
INBOUND REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE CONNECTORS ON
BOTH ENDS.
INBOUND REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLES FIELD TERMINATED WITH LC TYPE CONNECTORS
ON BOTH ENDS.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
EHRM INFRASTRUCTURE
UPGRADES
No. REVISION DESCRIPTION DATE
CIVIL/ STRUCTURAL ENGINEER
OATES ASSOCIATES
100 LANTER COURT, SUITE 1
COLLINSVILLE, IL 62234
(618) 345-2200
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
2519 MADISON AVE. STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
DATA/COMM CONSULTANT
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
COMMISSIONING AGENT
ES2
13401 N. SANTA FE AVE.
OKLAHOMA, OK 73114
(405) 528-4500
SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024
JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023
/1
5/
:0 0:
P
M
NR 172 205SR04/20/2023
657A5-21-700
MARION VA MEDICAL CENTER
2401 WEST MAIN ST.
MARION, IL 62959 T-103
15, 16
SPUR #: 2114
N
1/8" = 1'-0"
TECHNOLOGY PLAN - BLDG 15 LEVEL 11
N
1/8" = 1'-0"
TECHNOLOGY PLAN - BLDG 16 - LEVEL 12
TECHNOLOGY PLANS - BLDG 15, 16
204171
T-302
T-302
T-302
T-302
IRM
STORAGE
TELEPHONE
BIOMED
106A
STOR.
105A
OFFICE
GYM
118B
OFFICE
OFFICE
OFFICE
IRM
123A
IRM OFFICE
OFFICE
VAV
BIOMED
BIOMED OFF
BIOMED OFF
MENS
WOMENS
BEHAVIOR
MEDICINE
BEHAVIOR
MEDICINE
BEHAVIOR
MEDICINE
BEHAVIOR
MEDICINE
DATA CENTER
124IRM TECH
STAFF
T/C ELEC
BIOMED OFF
HAC
BEHAVIOR
MEDICING
AMER.
LEGION
VFW
TR
W
WW
W
4 4
4 4
4 4
4 4
4 4
4 4 4 4 4 4 4 4 4 4 4
B
LD
G . 1
GENERAL PLAN NOTES
1. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND
DURING INSTALLATION..
2. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF
ADDITIONAL CABLE DROPS.
3. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL
CUT-OVER TO THE NEW CABLING.
4. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN ITS
DESIGNATED TR.
5. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.
6. EXISTING CAT6A CABLING MAY REMAIN IN PLACE.
7. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED
UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.
8. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. ADHERE TO CABLING COLOR CODE AND LABELING
STANDARDS. (SEE SPECIFICATIONS)
9. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS
ALONG THE CABLE PATHWAYS.
10. EXISTING CONDUITS TO REMAIN.
11. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.
12. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE SECONDARY BONDING BUSBAR.BOND ALL PARTS OF TRAY SYSTEMS TO THE TELECOMMUNICATIONS PRIMARY/SECONDARY
BUSBAR.
13. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE
WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR
SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER
ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE
RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES WHERE CABLING
WAS REMOVED.
14. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE
SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE
THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.
ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR BIOMED ARE NOT DISTURBED (TYPICALLY
ORANGE CATEGORY AND AQUA OM4 FIBER OPTIC CABLING).
ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR WIRELESS AND SECURITY SYSTEMS ARE NOT
DISTURBED.
15. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND
CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.
16. CONTRACTOR SHALL REINSTALL CEILING TILES AT THE END OF EVERY WORK SHIFT.
17. CONTRACTOR SHALL INSTALL TEMPORARY FIRESTOPPING IN ANY PENETRATIONS OF NETWORK
CABLING THROUGH FIRE RATED WALLS AT THE END OF EVERY WORK SHIFT. TEMPORARY
FIRESTOPPING SHALL CONSIST OF MINERAL WOOL AND PROVIDE PROTECTION AGAINST FIRE/SMOKE
SPREAD THROUGH UNSEALED PENETRATION.
18. CONTRACTOR SHALL INSTALL FIRESTOPPING IN ALL FIRE RATED WALLS WHERE NETWORK CABLING
WAS REMOVED TO ENSURE FIRE RATING OF WALL.
TECHNOLOGY KEYNOTES
TELECOMMUNICATIONS EQUIPMENT RACK, 7'H x 19"W x 29"D, 4-POST, OPEN FRAME TYPE.
INSTALL BASKET TRAY ABOVE NETWORK RACKS IN TR AS DEPICTED ON PLANS.
INSTALL BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING ALONG HALLWAY. INSTALL J-HOOKS IN
AREAS WHERE BASKET TRAY IS INAPPROPRIATE.
REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND MULTIMODE (OM4) & 12 STRAND SINGLEMODE (OS1) HYBRID FIBER OPTIC CABLES FIELD TERMINATED
WITH LC TYPE CONNECTORS ON BOTH ENDS.
REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND MULTIMODE (OM4) & 12 STRAND SINGLEMODE (OS1) HYBRID FIBER OPTIC CABLES FIELD TERMINATED
WITH LC TYPE CONNECTORS ON BOTH ENDS.
REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE CONNECTORS ON BOTH
ENDS.
REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLES FIELD TERMINATED WITH LC TYPE CONNECTORS ON BOTH
ENDS.
INTERNET SERVICE PROVIDER, ENTRANCE ROOM. BLDG 37, ROOM 131. TELEPHONE ROOM.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
EHRM INFRASTRUCTURE
UPGRADES
No. REVISION DESCRIPTION DATE
CIVIL/ STRUCTURAL ENGINEER
OATES ASSOCIATES
100 LANTER COURT, SUITE 1
COLLINSVILLE, IL 62234
(618) 345-2200
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
2519 MADISON AVE. STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
DATA/COMM CONSULTANT
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
COMMISSIONING AGENT
ES2
13401 N. SANTA FE AVE.
OKLAHOMA, OK 73114
(405) 528-4500
SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024
JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023
/1
5/
:0 0:
P
M
NR 173 205SR04/20/2023
657A5-21-700
MARION VA MEDICAL CENTER
2401 WEST MAIN ST.
MARION, IL 62959 T-104
SPUR #: 2114
N
1/8" = 1'-0"
TECHNOLOGY PLAN - BLDG 37 LEVEL 11
TECHNOLOGY PLANS - BLDG 37
204172
GENERAL PLAN NOTESGENERAL PLAN NOTES
1. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND
DURING INSTALLATION..
2. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF
ADDITIONAL CABLE DROPS.
3. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL
CUT-OVER TO THE NEW CABLING.
4. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN ITS
DESIGNATED TR.
5. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.
6. EXISTING CAT6A CABLING MAY REMAIN IN PLACE.
7. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED
UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.
8. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. ADHERE TO CABLING COLOR CODE AND LABELING
STANDARDS. (SEE SPECIFICATIONS)
9. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS
ALONG THE CABLE PATHWAYS.
10. EXISTING CONDUITS TO REMAIN.
11. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.
12. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE SECONDARY BONDING BUSBAR.BOND ALL PARTS OF TRAY SYSTEMS TO THE TELECOMMUNICATIONS PRIMARY/SECONDARY
BUSBAR.
13. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE
WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR
SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER
ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE
RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES WHERE CABLING
WAS REMOVED.
14. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE
SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE
THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.
ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR BIOMED ARE NOT DISTURBED (TYPICALLY
ORANGE CATEGORY AND AQUA OM4 FIBER OPTIC CABLING).
ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR WIRELESS AND SECURITY SYSTEMS ARE NOT
DISTURBED.
15. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND
CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.
16. CONTRACTOR SHALL REINSTALL CEILING TILES AT THE END OF EVERY WORK SHIFT.
17. CONTRACTOR SHALL INSTALL TEMPORARY FIRESTOPPING IN ANY PENETRATIONS OF NETWORK
CABLING THROUGH FIRE RATED WALLS AT THE END OF EVERY WORK SHIFT. TEMPORARY
FIRESTOPPING SHALL CONSIST OF MINERAL WOOL AND PROVIDE PROTECTION AGAINST FIRE/SMOKE
SPREAD THROUGH UNSEALED PENETRATION.
18. CONTRACTOR SHALL INSTALL FIRESTOPPING IN ALL FIRE RATED WALLS WHERE NETWORK CABLING
WAS REMOVED TO ENSURE FIRE RATING OF WALL.
BLDG. 42
BLDG. 2
B
LD
G . 2
CARPENTER
SHOP
BLDG. 1
B
LD
G . 1
B
LD
G . 3
FIRE
PUMP
6A 001
T-303
TR
6B
T-303
4 4
4 4 4 4 4 4 4 4 4
4 4
4 4
4 4 4 4
4 4
4 4
TECHNOLOGY KEYNOTES
TELECOMMUNICATIONS EQUIPMENT RACK, 7'H x 19"W x 29"D, 4-POST, OPEN FRAME TYPE.
INSTALL BASKET TRAY ABOVE NETWORK RACKS IN TR AS DEPICTED ON PLANS.
INSTALL BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING ALONG HALLWAY. INSTALL J-HOOKS IN
AREAS WHERE BASKET TRAY IS INAPPROPRIATE.
REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND MULTIMODE (OM4) & 12 STRAND SINGLEMODE (OS1) HYBRID FIBER OPTIC CABLES FIELD TERMINATED
WITH LC TYPE CONNECTORS ON BOTH ENDS.
REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND MULTIMODE (OM4) & 12 STRAND SINGLEMODE (OS1) HYBRID FIBER OPTIC CABLES FIELD TERMINATED
WITH LC TYPE CONNECTORS ON BOTH ENDS.
REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE CONNECTORS ON BOTH
ENDS.
REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLES FIELD TERMINATED WITH LC TYPE CONNECTORS ON BOTH
ENDS.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
EHRM INFRASTRUCTURE
UPGRADES
No. REVISION DESCRIPTION DATE
CIVIL/ STRUCTURAL ENGINEER
OATES ASSOCIATES
100 LANTER COURT, SUITE 1
COLLINSVILLE, IL 62234
(618) 345-2200
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
2519 MADISON AVE. STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
INDUSTRIAL HYGENIST
RIVERFRONT SAFETY & HEALTH
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
DATA/COMM CONSULTANT
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE, SUITE A
PRESCOTT, AZ 86301
(928) 774-0992
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
COMMISSIONING AGENT
ES2
13401 N. SANTA FE AVE.
OKLAHOMA, OK 73114
(405) 528-4500
SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024
JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023
/1
5/
:0 0:
P
M
TECHNOLOGY PLANS - BLDG 1, 38, 2
LEVEL G
NR 174 205SR04/20/2023
657A5-21-700
MARION VA MEDICAL CENTER
2401 WEST MAIN ST.
MARION, IL 62959 T-105
1,38,2
SPUR #: 2114
N
1/16" = 1'-0"
TECHNOLOGY PLAN - BLDG 38 LEVEL G1
204173
T-303
T-303
B
LD
G . 2
118A119B
118B
119A
103B
107A
119C
103A
103C
106B
106C
106D
107B 107C 107D
107E
109A
110A
110B
110C
103A
113A
113B
113C
110D
108A
106A
116A
B
LD
G . 1
LOGISTICS
101A
DATA ROOM
123B
TEAM OFFICE
TR
123C
6 6
4 4 4
4 4
4 4
2222222
2 2 2 2 2 2
4 4
4 4
44444
4 4
4 4
TECHNOLOGY KEYNOTES
TELECOMMUNICATIONS EQUIPMENT RACK, 7'H x 19"W x 29"D, 4-POST, OPEN FRAME TYPE.
INSTALL BASKET TRAY ABOVE NETWORK RACKS IN TR AS DEPICTED ON PLANS.
INSTALL BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING ALONG HALLWAY. INSTALL J-HOOKS IN
AREAS WHERE BASKET TRAY IS INAPPROPRIATE.
REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND MULTIMODE (OM4) & 12 STRAND SINGLEMODE (OS1) HYBRID FIBER OPTIC CABLES FIELD TERMINATED
WITH LC TYPE CONNECTORS ON BOTH ENDS.
REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND MULTIMODE (OM4) & 12 STRAND SINGLEMODE (OS1) HYBRID FIBER OPTIC CABLES FIELD TERMINATED
WITH LC TYPE CONNECTORS ON BOTH ENDS.
GENERAL PLAN NOTESGENERAL PLAN NOTES
1. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND
DURING INSTALLATION..
2. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF
ADDITIONAL CABLE DROPS.
3. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL
CUT-OVER TO THE NEW CABLING.
4. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN ITS
DESIGNATED TR.
5. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.
6. EXISTING CAT6A CABLING MAY REMAIN IN PLACE.
7. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED
UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.
8. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. ADHERE TO CABLING COLOR CODE AND LABELING
STANDARDS. (SEE SPECIFICATIONS)
9. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS
ALONG THE CABLE PATHWAYS.
10. EXISTING CONDUITS TO REMAIN.
11. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.
12. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE SECONDARY BONDING BUSBAR.BOND ALL PARTS OF TRAY SYSTEMS TO THE TELECOMMUNICATIONS PRIMARY/SECONDARY
BUSBAR.
13. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE
WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR
SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER
ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE
RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES WHERE CABLING
WAS REMOVED.
14. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE
SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE
THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.
ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR BIOMED ARE NOT DISTURBED (TYPICALLY
ORANGE CATEGORY AND AQUA OM4 FIBER OPTIC CABLING).
ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR WIRELESS AND SECURITY SYSTEMS ARE NOT
DISTURBED.
15. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND
CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.
16. CONTRACTOR SHALL REINSTALL CEILING TILES AT THE END OF EVERY WORK SHIFT.
17. CONTRACTOR SHALL INSTALL TEMPORARY FIRESTOPPING IN ANY PENETRATIONS OF NETWORK
CABLING THROUGH FIRE RATED WALLS AT THE END OF EVERY WORK SHIFT. TEMPORARY
FIRESTOPPING SHALL CONSIST OF MINERAL WOOL AND PROVIDE PROTECTION AGAINST FIRE/SMOKE
SPREAD THROUGH UNSEALED PENETRATION.
18. CONTRACTOR SHALL INSTALL FIRESTOPPING IN ALL FIRE RATED WALLS WHERE NETWORK CABLING
WAS REMOVED TO ENSURE FIRE RATING OF WALL.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
EHRM INFRASTRUCTURE
UPGRADES
No. REVISION DESCRIPTION DATE
CIVIL/ STRUCTURAL ENGINEER
OATES ASSOCIATES
100 LANTER COURT, SUITE 1
COLLINSVILLE, IL 62234
(618) 345-2200
MECH / ELEC / PLUMB ENGINEER
SPUR DESIGN
2519 MADISON AVE. STE 100
KA…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .