Tech Drawings T000-T200.pdf

PDF 6 MB Posted

Attached to
36C77623B0047 - Y1DA--657A5-21-700 EHRM Infrastructure Upgrades Construction Marion, IL VAMC
Solicitation number
36C77623B0047_1
Issued by

About this file

This solicitation is for a construction project to upgrade telecommunications infrastructure at the Marion VA Medical Center in Marion, Illinois. The scope of work includes installing new category 6A cabling and fiber optic backbones to various buildings on campus, upgrading telecommunications rooms, and demolishing old cabling systems. The required work will provide new high-speed data network connectivity to clinical and administrative areas. The solicitation is available through the Department of Veterans Affairs Technology Acquisition Center and responses are due by January 2023. The anticipated award date is in February 2023.

View the file

Other files

File Type Posted
Wage Determination - Williamson County - 9.8.23.pdf PDF
36C77623B0047 0009.docx DOCX document
36C77623B0047 Amendment 0008.docx DOCX document
ae601 door schedule and partition types.pdf PDF
3837_001.pdf PDF
M-105 REFERENCE PLANS - BUILDINGS 81 and 82.pdf PDF
04 20 00 UnitMasonry.pdf PDF
657a5-21-700 ehrm marion il addendum-03.pdf PDF
03 30 00 Cast-in-Place Concrete.pdf PDF
36C77623B0047 Amendment 0007.docx DOCX document
ae408 enlarged plans - bldg 42 43 81.pdf PDF
1 Technical Questions Tracking Spreadsheet - Marion Infra Constr - 8-24-23 Final.pdf PDF
Wage rates - Williamson - 8.14.23.pdf PDF
B 38 Drawing Package_Part5.pdf PDF
Building 14 Boiler Plant Geotechnical Report.pdf PDF
B 38 Drawing Package_Part4.pdf PDF
2. B 37 Marion VA Field Print Model (2 of 2) (1).pdf PDF
2. B 37 Marion VA Field Print Model (2 of 2) (5).pdf PDF
2. B 37 Marion VA Field Print Model (2 of 2) (3).pdf PDF
2017-0502.10 Building 13 Geotech Report.pdf PDF
2. B 37 Marion VA Field Print Model (2 of 2) (2).pdf PDF
36C77623B0047 Amendment 0006.docx DOCX document
B 38 Drawing Package_Part3.pdf PDF
15225023 VA Project 657A5-21-700 EHRM Marion Geotechnical Report.pdf PDF
B 38 Drawing Package_Part1.pdf PDF
B 38 Drawing Package_Part6.pdf PDF
2. B 37 Marion VA Field Print Model (2 of 2) (4).pdf PDF
B 38 Drawing Package_Part2.pdf PDF
Wage Determination - Williamson 8.4.pdf PDF
36C77623B0047 0005.pdf PDF
Attachment 1 - Missing Specs.zip ZIP file
36C77623B0047 0004.pdf PDF
36C77623B0047 0003.pdf PDF
Construction Wage Rates - Williamson County - 7-28-23.pdf PDF
Site Visit Sign-In Sheet - Marion Infra 7-31-23.pdf PDF
Attachment 1 - Electrical Plans 657A5-21-700.zip ZIP file
36C77623B0047 Amendment 0002.pdf PDF
Attachment 1 - 36C77623B0047_1.pdf PDF
36C77623B0047 Amendment 0001.docx DOCX document
ARCHITECTURAL.pdf PDF
Limitations on Subcontracting - Construction.docx DOCX document
STRUCTURAL.pdf PDF
Civil Drawings CU301-CIVIL DETAILS.pdf PDF
HAZARDOUS MATERIALS.pdf PDF
Civil Drawings CU211-CU213.pdf PDF
36C77623B0047_1.docx DOCX document
Civil Drawings CU207-CU210.pdf PDF
GENERAL.pdf PDF
Civil Drawings CU217-CU300.pdf PDF
Civil Drawings CU-214-CU216.pdf PDF
Show 40 more

Latest 50 of 62 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ABBREVIATIONS

STANDARD MOUNTING HEIGHTSANNOTATION

ELECTRICAL: (AFF, AFG UNLESS NOTED OTHERWISE)

CU

TELECOMMUNICATION PLAN NOTE CALL OUT

EQUIPMENT DESIGNATION TAG

NEW WORK TO EXISTING WORK CONNECTION POINT

IC

CATV

FO

T

D

S

IC

S

WAP

# / #TV

M

S

V

COMMUNICATIONS OUTLET, TYPE AS NOTED

COMMUNICATIONS OUTLET, FLOOR BOX, TYPE AS NOTED

WIRELESS ACCESS POINT, CEILING MOUNTED

COMMUNICATIONS OUTLET, CEILING MTD, TYPE AS NOTED

SPEAKER, WALL MOUNTED

SPEAKER, CEILING MOUNTED

TELECOMMUNICATIONS RACK, TWO-POST, FLOOR MOUNTED

GROUND BAR, TYPE AS NOTED

TELECOMMUNICATIONS ENCLOSURE, WALL MOUNTED

CABLE/BASKET TRAY, TYPE AS NOTED

CABLE TELEVISION LINE

FIBEROPTIC LINE

TELEPHONE LINE

FIBER OPTIC BACKBONE PATHWAY "A"

DATA LINE

SPEAKER LINE

INTERCOM LINE

INTERCOM, "M" DENOTES MASTER STATION

VOLUME CONTROL, WALL MOUNTED

MULTI-SERVICE POWER POLE WITH POWER/DATA,

TYPE AS NOTED AND/OR SCHEDULED

MULTI-SERVICE FLOOR BOX/POKE-THRU WITH POWER/DATA,

TYPE AS NOTED AND/OR SCHEDULED

TELECOMMUNICATIONS CHANNEL RACK, 7'H x 19"W x 30"D, 4-POST, OPEN FRAME TYPE

SERVER CABINET, FLOOR MOUNTED

# = DATA, # = QUANTITY OF CABLES

#TV = CABLE TELEVISION, # = QUANTITY OF CABLES

# = DATA, # = QUANTITY OF CABLES

#TV = CABLE TELEVISION, # = QUANTITY OF CABLES

#V = VOICE, # = QUANTITY OF CABLES

= DATA, 2 CABLES

# = DATA, # = QUANTITY OF CABLES

TELECOMMUNICATIONS SYMBOLS

#TV = CABLE TELEVISION, # = QUANTITY OF CABLES

#V = VOICE, # = QUANTITY OF CABLES

M (CONT'D)

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT

X

W

V

U

T

S

R

P

O

N

M

L

K

J

I

H

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FABL FIRE ALARM BELL

FABX FIRE ALARM BOX

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FI FILM ILLUMINATOR

FIXT FIXTURE

FLA FULL LOAD AMPS

FLEX FLEXIBLE METALLIC CONDUIT

FLUOR FLUORESCENT

FO FIBER-OPTIC

FP FIRE PROTECTION

FT FEET OR FOOT

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

G

F

E

D

EC EMPTY CONDUIT

EG EQUIPMENT GROUND

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMCP EMER. MONITORING CONTROL PANEL

EMER EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

ESMT EASEMENT

ETD EXISTING TO BE DEMOLISHED

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXIST EXISTING

DB DECIBEL OR DIRECT BURIAL

DC DIRECT CURRENT

DCP DIMMER CONTROL PANEL

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DISTR DISTRIBUTION

DISTR PNL DISTRIBUTION PANEL

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

C CONDUIT

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/

CONTRACTOR INSTALLED

CF/OI CONTRACTOR FURNISHED/OWNER

INSTALLED

CFE CONTRACTOR FURNISHED

EQUIPMENT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CKT BRKR CIRCUIT BREAKER

CLF CURRENT LIMITING FUSE

CLG CEILING

CMU CONCRETE MASONRY UNIT

COAX COAX CABLE

COMM COMMUNICATION

CONC CONCRETE

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

CU FT CUBIC FEET

C

B

A

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

V VOLT

VA VOLT AMPERE

VAR VOLT AMPERE REACTIVE

VCM VERTICAL CABLE MANAGER

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

TC TIME CLOCK

TEL TELEPHONE

TO TELECOMMUNICATIONS OUTLET

TR TELECOMMUNICATIONS ROOM

TV TELEVISION

TYP TYPICAL

RCP REFLECTED CEILING PLAN

RCPT RECEPTACLE

REC RECESSED

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

RU RACK UNIT

N NEUTRAL

NA NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OL OVERLOAD

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MLO MAIN LUGS ONLY

MT MOUNT

MTD MOUNTED

MTG MOUNTING

KV KILOVOLT

KVA KILOVOLT AMPERE

KVAH KILOVOLT AMPERE PER HOUR

KVAR KILOVOLT AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

KWHM KILOWATT HOUR METER

JB JUNCTION BOX

J-BOX JUNCTION BOX

XFER TRANSFER

XFMR TRANSFORMER

XP EXPLOSION PROOF

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LM LUMEN

LP LIGHT POLE

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LTCP LOCAL TEMPERATURE CONTROL PANEL

LT LIGHT

LTG LIGHTING

LTG PNL LIGHTING PANEL

LTNG LIGHTNING

LV LOW VOLTAGE

W WATT

WAO WORK AREA OUTLET

WP WEATHERPROOF

IESNA ILLUMINATION ENGINEERING SOCIETY

OF NORTH AMERICA

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

G OR GND GROUND OR GENERATOR

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GTB GROUND TERMINAL BOX

SCC SHORT CIRCUIT CAPACITY

SES SERVICE ENTRANCE SECTION

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SURF SURFACE

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

P POLE

PA PUBLIC ADDRESS

PB PANELBOARD, PULL BOX, OR

PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT UNIT

PCB POLYCHLORINATED BIPHENYL

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PNL PANEL

POD POWER OPERATED DAMPER

POE POWER OVER ETHERNET

PP PATCH PANEL

PT POTENTIAL TRANSFORMER

PTRV POWER TYPE ROOF VENTILATION

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

1P SINGLE POLE

1PH SINGLE-PHASE

3P THREE POLE

3PH THREE-PHASE

3W THREE WIRE

4W FOUR WIRE

A/C AIR CONDITIONING

A/E ARCHITECT/ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT, ADJOINING

ADO AUTOMATIC DOOR OPENER

AF AMPERE FRAME OR AMP FUSE

AFC ABOVE FINISHED COUNTER, AUTOMATIC

FREQUENCY CONTROL, OR

AVAILABLE FAULT CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AH AMPERE HOUR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMB OR A AMBIENT

AMP AMPERE

ARCH ARCHITECT

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

HCM HORIZONTAL CABLE MANAGER

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

BAT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISH FLOOR

BIL BASIC INSULATION LEVEL

BLDG BUILDING

BLK BLOCK

BPIP BOILER PLANT

INSTRUMENTATION PANEL

BRKR BREAKER

BYP BY PASS

DETAIL REFERENCE

SECTION CUT DESIGNATION

EP-101

EP-101

PATH-A

PATH-B FIBER OPTIC BACKBONE PATHWAY "B"

84" 48" 48" 84" 48" 80" 60"

120" 60" 36" 48" 72" 48"

144" 18" 24" 26" 48" 48"

CEILING

48" 48" 18" 84"

AUDIBLE APPLIANCES (CENTERLINE)

ALARMS

ANNUNCIATOR PANELS

CLOCK OUTLETS (CENTERLINE)

CONTROLS (TOP)

EXIT SIGNS (WALL-MOUNTED, BOTTOM)

FIRE ALARM ANNUNCIATOR PANEL (DISPLAY)

FIRE ALARM BELL (EXTERIOR)

FIRE ALARM CONTROL PANEL/UNIT (DISPLAY)

INTERCOM (AFEA ONLY)

INTERCOMS (TOP)

PANELS & PANELBOARDS (TOP)

PULL STATIONS (HANDLE)

PHOTOCELLS

RECEPTACLES (BOTTOM)

RECEPTACLES (EXTERIOR)

RECEPTACLES (GARAGES) RECEPTACLES IN

EQUIPMENT ROOMS (TOP) REMOTE INDICATING

LIGHT (EQUIPMENT ROOMS) REMOTE INDICATING

LIGHT (FINISHED AREAS) SAFETY SWITCHES &

STARTERS SWITCHES (TOP)

TELEPHONE/DATA/TV OUTLETS (BOTTOM)

VISIBLE APPLIANCES (CENTERLINE)

#E = ELEVATOR, # = QUANTITY OF CABLES

TE TELECOMMUNICATIONS ENCLOSURE

VERTICAL CABLE MANAGER, 6" WIDE, WITH DOORS

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

EHRM INFRASTRUCTURE

UPGRADES

No. REVISION DESCRIPTION DATE

CIVIL/ STRUCTURAL ENGINEER

OATES ASSOCIATES

100 LANTER COURT, SUITE 1

COLLINSVILLE, IL 62234

(618) 345-2200

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

2519 MADISON AVE. STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

DATA/COMM CONSULTANT

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

COMMISSIONING AGENT

ES2

13401 N. SANTA FE AVE.

OKLAHOMA, OK 73114

(405) 528-4500

SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024

JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023

/1

5/

:5 9:

P

M

TECHNOLOGY SYMBOLS & ABBREVIATIONS

NR 168 205SR04/20/2023

657A5-21-700

MARION VA MEDICAL CENTER

2401 WEST MAIN ST.

MARION, IL 62959 T-000

SPUR #: 2114

FINAL BID DOCUMENTS

204167

4 4

4 4

GENERAL PLAN NOTES

1. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND

DURING INSTALLATION..

2. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF

ADDITIONAL CABLE DROPS.

3. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL

CUT-OVER TO THE NEW CABLING.

4. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN ITS

DESIGNATED TR.

5. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.

6. EXISTING CAT6A CABLING MAY REMAIN IN PLACE.

7. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED

UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.

8. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. ADHERE TO CABLING COLOR CODE AND LABELING

STANDARDS. (SEE SPECIFICATIONS)

9. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS

ALONG THE CABLE PATHWAYS.

10. EXISTING CONDUITS TO REMAIN.

11. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

12. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE SECONDARY BONDING BUSBAR.BOND ALL PARTS OF TRAY SYSTEMS TO THE TELECOMMUNICATIONS PRIMARY/SECONDARY

BUSBAR.

13. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE

WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR

SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER

ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE

RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES WHERE CABLING

WAS REMOVED.

14. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE

SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE

THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.

ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR BIOMED ARE NOT DISTURBED (TYPICALLY

ORANGE CATEGORY AND AQUA OM4 FIBER OPTIC CABLING).

ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR WIRELESS AND SECURITY SYSTEMS ARE NOT

DISTURBED.

15. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND

CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.

16. CONTRACTOR SHALL REINSTALL CEILING TILES AT THE END OF EVERY WORK SHIFT.

17. CONTRACTOR SHALL INSTALL TEMPORARY FIRESTOPPING IN ANY PENETRATIONS OF NETWORK

CABLING THROUGH FIRE RATED WALLS AT THE END OF EVERY WORK SHIFT. TEMPORARY

FIRESTOPPING SHALL CONSIST OF MINERAL WOOL AND PROVIDE PROTECTION AGAINST FIRE/SMOKE

SPREAD THROUGH UNSEALED PENETRATION.

18. CONTRACTOR SHALL INSTALL FIRESTOPPING IN ALL FIRE RATED WALLS WHERE NETWORK CABLING

WAS REMOVED TO ENSURE FIRE RATING OF WALL.

CSELECT.

H

SS

T-300

T-300

4 4

4 4

4 4

TR

4 4

4 4

4 4

44 4444

4 4

4 4

TECHNOLOGY KEYNOTES

TELECOMMUNICATIONS EQUIPMENT RACK, 7'H x 19"W x 29"D, 4-POST, OPEN FRAME TYPE.

INSTALL BASKET TRAY ABOVE NETWORK RACKS IN TR AS DEPICTED ON PLANS.

INSTALL BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING ALONG HALLWAY. INSTALL J-HOOKS IN

AREAS WHERE BASKET TRAY IS INAPPROPRIATE.

INBOUND REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE CONNECTORS ON

BOTH ENDS.

INBOUND REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLES FIELD TERMINATED WITH LC TYPE CONNECTORS

ON BOTH ENDS.

CONTRACTOR SHALL PULL CABLES AFTER HOURS IN THIS BUILDING.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

EHRM INFRASTRUCTURE

UPGRADES

No. REVISION DESCRIPTION DATE

CIVIL/ STRUCTURAL ENGINEER

OATES ASSOCIATES

100 LANTER COURT, SUITE 1

COLLINSVILLE, IL 62234

(618) 345-2200

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

2519 MADISON AVE. STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

DATA/COMM CONSULTANT

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

COMMISSIONING AGENT

ES2

13401 N. SANTA FE AVE.

OKLAHOMA, OK 73114

(405) 528-4500

SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024

JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023

/1

5/

:5 9:

P

M

NR 169 205SR04/20/2023

657A5-21-700

MARION VA MEDICAL CENTER

2401 WEST MAIN ST.

MARION, IL 62959 T-100

SPUR #: 2114

N

1/8" = 1'-0"

TECHNOLOGY PLAN - BLDG 8 BASEMENT1

N

1/8" = 1'-0"

TECHNOLOGY PLAN - BLDG 8 LEVEL 12

N

1/8" = 1'-0"

TECHNOLOGY PLAN - BLDG 8 - LEVEL 23

TECHNOLOGY PLANS - BLDG 8

204168

TR

T-300

T-300

UNEXC.

CS-2

UNEXC.

CS-1

STORAGE

STORAGE

STORAGE

STORAGE

4A

STORAGE

STOR.

CLERICAL

101A

CONFERENCE

OFFICE

UP

OFFICE

FILE

STAIR

OFFICE

WOMEN

MEN

OFFICE

LOBBY

OFFICE

CORRIDOR

4 4

4 444

4 4

4 4

DN

OFFICE

WORK AREA

201A

CORR.

OFFICE

204RESTROOM

RESTROOM

OFFICE

OFFICE

MECH.

CLOSET

LOBBY

FEC

6 6

GENERAL PLAN NOTES

1. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND

DURING INSTALLATION..

2. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF

ADDITIONAL CABLE DROPS.

3. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL

CUT-OVER TO THE NEW CABLING.

4. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN ITS

DESIGNATED TR.

5. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.

6. EXISTING CAT6A CABLING MAY REMAIN IN PLACE.

7. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED

UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.

8. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. ADHERE TO CABLING COLOR CODE AND LABELING

STANDARDS. (SEE SPECIFICATIONS)

9. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS

ALONG THE CABLE PATHWAYS.

10. EXISTING CONDUITS TO REMAIN.

11. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

12. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE SECONDARY BONDING BUSBAR.BOND ALL PARTS OF TRAY SYSTEMS TO THE TELECOMMUNICATIONS PRIMARY/SECONDARY

BUSBAR.

13. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE

WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR

SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER

ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE

RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES WHERE CABLING

WAS REMOVED.

14. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE

SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE

THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.

ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR BIOMED ARE NOT DISTURBED (TYPICALLY

ORANGE CATEGORY AND AQUA OM4 FIBER OPTIC CABLING).

ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR WIRELESS AND SECURITY SYSTEMS ARE NOT

DISTURBED.

15. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND

CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.

16. CONTRACTOR SHALL REINSTALL CEILING TILES AT THE END OF EVERY WORK SHIFT.

17. CONTRACTOR SHALL INSTALL TEMPORARY FIRESTOPPING IN ANY PENETRATIONS OF NETWORK

CABLING THROUGH FIRE RATED WALLS AT THE END OF EVERY WORK SHIFT. TEMPORARY

FIRESTOPPING SHALL CONSIST OF MINERAL WOOL AND PROVIDE PROTECTION AGAINST FIRE/SMOKE

SPREAD THROUGH UNSEALED PENETRATION.

18. CONTRACTOR SHALL INSTALL FIRESTOPPING IN ALL FIRE RATED WALLS WHERE NETWORK CABLING

WAS REMOVED TO ENSURE FIRE RATING OF WALL.

TECHNOLOGY KEYNOTES

TELECOMMUNICATIONS EQUIPMENT RACK, 7'H x 19"W x 29"D, 4-POST, OPEN FRAME TYPE.

INSTALL BASKET TRAY ABOVE NETWORK RACKS IN TR AS DEPICTED ON PLANS.

INSTALL BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING ALONG HALLWAY. INSTALL J-HOOKS IN

AREAS WHERE BASKET TRAY IS INAPPROPRIATE.

INBOUND REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE CONNECTORS ON

BOTH ENDS.

INBOUND REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLES FIELD TERMINATED WITH LC TYPE CONNECTORS

ON BOTH ENDS.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

EHRM INFRASTRUCTURE

UPGRADES

No. REVISION DESCRIPTION DATE

CIVIL/ STRUCTURAL ENGINEER

OATES ASSOCIATES

100 LANTER COURT, SUITE 1

COLLINSVILLE, IL 62234

(618) 345-2200

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

2519 MADISON AVE. STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

DATA/COMM CONSULTANT

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

COMMISSIONING AGENT

ES2

13401 N. SANTA FE AVE.

OKLAHOMA, OK 73114

(405) 528-4500

SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024

JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023

/1

5/

:0 0:

P

M

NR 170 205SR04/20/2023

657A5-21-700

MARION VA MEDICAL CENTER

2401 WEST MAIN ST.

MARION, IL 62959 T-101

SPUR #: 2114

N

1/8" = 1'-0"

TECHNOLOGY PLAN - BLDG 13 BASEMENT1

N

1/8" = 1'-0"

TECHNOLOGY PLAN - BLDG 13 LEVEL 12

N

1/8" = 1'-0"

TECHNOLOGY PLAN - BLDG 13 - LEVEL 23

TECHNOLOGY PLANS - BLDG 13

204169

UP

DN

DN

UP

LOCKER

100B

LOCKER

100A

MEZZ. FLOOR

OFFICE

BOILER

DN

DN

DN

T-300

T-300

EQUIP.

MAINT.

104STORAGE

OFFICE

103B

RR

103A

EMERG.

GEN.

BAY

4 4

GENERAL PLAN NOTES

1. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND

DURING INSTALLATION..

2. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF

ADDITIONAL CABLE DROPS.

3. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL

CUT-OVER TO THE NEW CABLING.

4. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN ITS

DESIGNATED TR.

5. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.

6. EXISTING CAT6A CABLING MAY REMAIN IN PLACE.

7. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED

UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.

8. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. ADHERE TO CABLING COLOR CODE AND LABELING

STANDARDS. (SEE SPECIFICATIONS)

9. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS

ALONG THE CABLE PATHWAYS.

10. EXISTING CONDUITS TO REMAIN.

11. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

12. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE SECONDARY BONDING BUSBAR.BOND ALL PARTS OF TRAY SYSTEMS TO THE TELECOMMUNICATIONS PRIMARY/SECONDARY

BUSBAR.

13. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE

WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR

SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER

ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE

RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES WHERE CABLING

WAS REMOVED.

14. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE

SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE

THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.

ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR BIOMED ARE NOT DISTURBED (TYPICALLY

ORANGE CATEGORY AND AQUA OM4 FIBER OPTIC CABLING).

ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR WIRELESS AND SECURITY SYSTEMS ARE NOT

DISTURBED.

15. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND

CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.

16. CONTRACTOR SHALL REINSTALL CEILING TILES AT THE END OF EVERY WORK SHIFT.

17. CONTRACTOR SHALL INSTALL TEMPORARY FIRESTOPPING IN ANY PENETRATIONS OF NETWORK

CABLING THROUGH FIRE RATED WALLS AT THE END OF EVERY WORK SHIFT. TEMPORARY

FIRESTOPPING SHALL CONSIST OF MINERAL WOOL AND PROVIDE PROTECTION AGAINST FIRE/SMOKE

SPREAD THROUGH UNSEALED PENETRATION.

18. CONTRACTOR SHALL INSTALL FIRESTOPPING IN ALL FIRE RATED WALLS WHERE NETWORK CABLING

WAS REMOVED TO ENSURE FIRE RATING OF WALL.

TECHNOLOGY KEYNOTES

TELECOMMUNICATIONS WALL-MOUNT RACK, 36"H x 26"W x 30"D, VENTED, SOLID WALL TYPE. TO BE

CAGED PER PHYSICAL SECURITY REQUIREMENTS.

INSTALL BASKET TRAY ABOVE NETWORK RACKS IN TR AS DEPICTED ON PLANS.

INSTALL BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING ALONG HALLWAY. INSTALL J-HOOKS IN

AREAS WHERE BASKET TRAY IS INAPPROPRIATE.

INBOUND REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE CONNECTORS ON

BOTH ENDS.

INBOUND REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLES FIELD TERMINATED WITH LC TYPE CONNECTORS

ON BOTH ENDS.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

EHRM INFRASTRUCTURE

UPGRADES

No. REVISION DESCRIPTION DATE

CIVIL/ STRUCTURAL ENGINEER

OATES ASSOCIATES

100 LANTER COURT, SUITE 1

COLLINSVILLE, IL 62234

(618) 345-2200

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

2519 MADISON AVE. STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

DATA/COMM CONSULTANT

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

COMMISSIONING AGENT

ES2

13401 N. SANTA FE AVE.

OKLAHOMA, OK 73114

(405) 528-4500

SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024

JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023

/1

5/

:0 0:

P

M

NR 171 205SR04/20/2023

657A5-21-700

MARION VA MEDICAL CENTER

2401 WEST MAIN ST.

MARION, IL 62959 T-102

SPUR #: 2114

N

1/8" = 1'-0"

TECHNOLOGY PLAN - BLDG 14 LEVEL 11

N

1/8" = 1'-0"

TECHNOLOGY PLAN - BLDG 14 - LEVEL 22

TECHNOLOGY PLANS - BLDG 14

204170

T-301

T-301

2 2

2 2

2 2 2 2 2 2 2 2 2

BREAK ROOM

CONFERENCE

ROOM

STORAGE

ASST. CHIEF

ENGINEER

CHIEF

ENGINEER

FACILITY

PLANNER

ENERGY

MANAGER

M&O

SUPERVISOR

M&O

SUPERVISOR

WOMENS

TOILET

MENS TOILET

M&O

SUPERVISOR

M&O

SUPERVISOR

CLOSET

MECHANICAL

101CTR

101D

HAC

UNISEX STAFF

TLT

UNISEX STAFF

TLT

PLAN ROOM

PROJECT

ENGINEER

SUPERVISOR

CORRIDOR

C02

ADMIN OFFICE

ASST

CORRIDOR

C01B

CORRIDOR

C01A

CORRIDOR

C01

ELECTRICAL

105A

PROJECT

ENGINEERS

WORKSTATIONS

VESTIBULE

PROJECT

ENGINEERS

EGRESS

121B

STORAGE

C01D

LOBBY

ENG.

CLERK/TRANS.MGR

101A

PROJECT

ENGINEERS

WORKSTATIONS

121A

2 2

T-301

T-301

PHARMACY

OFFICE

SUPPLIES

105D

ENGINEERING

105EFREEZER

110A

REFRIGERATOR

110 LOADING

DOCK

OXYGEN

OFFICE

SPACE

105A

MAILROOM

OFFICE

BREAK

ROOM

WAREHOUSE

STORAGE

4 4

4 4

TR

105D

GENERAL PLAN NOTES

1. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND

DURING INSTALLATION..

2. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF

ADDITIONAL CABLE DROPS.

3. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL

CUT-OVER TO THE NEW CABLING.

4. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN ITS

DESIGNATED TR.

5. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.

6. EXISTING CAT6A CABLING MAY REMAIN IN PLACE.

7. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED

UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.

8. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. ADHERE TO CABLING COLOR CODE AND LABELING

STANDARDS. (SEE SPECIFICATIONS)

9. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS

ALONG THE CABLE PATHWAYS.

10. EXISTING CONDUITS TO REMAIN.

11. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

12. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE SECONDARY BONDING BUSBAR.BOND ALL PARTS OF TRAY SYSTEMS TO THE TELECOMMUNICATIONS PRIMARY/SECONDARY

BUSBAR.

13. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE

WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR

SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER

ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE

RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES WHERE CABLING

WAS REMOVED.

14. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE

SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE

THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.

ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR BIOMED ARE NOT DISTURBED (TYPICALLY

ORANGE CATEGORY AND AQUA OM4 FIBER OPTIC CABLING).

ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR WIRELESS AND SECURITY SYSTEMS ARE NOT

DISTURBED.

15. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND

CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.

16. CONTRACTOR SHALL REINSTALL CEILING TILES AT THE END OF EVERY WORK SHIFT.

17. CONTRACTOR SHALL INSTALL TEMPORARY FIRESTOPPING IN ANY PENETRATIONS OF NETWORK

CABLING THROUGH FIRE RATED WALLS AT THE END OF EVERY WORK SHIFT. TEMPORARY

FIRESTOPPING SHALL CONSIST OF MINERAL WOOL AND PROVIDE PROTECTION AGAINST FIRE/SMOKE

SPREAD THROUGH UNSEALED PENETRATION.

18. CONTRACTOR SHALL INSTALL FIRESTOPPING IN ALL FIRE RATED WALLS WHERE NETWORK CABLING

WAS REMOVED TO ENSURE FIRE RATING OF WALL.

TECHNOLOGY KEYNOTES

TELECOMMUNICATIONS EQUIPMENT RACK, 7'H x 19"W x 29"D, 4-POST, OPEN FRAME TYPE.

INSTALL BASKET TRAY ABOVE NETWORK RACKS IN TR AS DEPICTED ON PLANS.

INSTALL BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING ALONG HALLWAY. INSTALL J-HOOKS IN

AREAS WHERE BASKET TRAY IS INAPPROPRIATE.

INBOUND REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE CONNECTORS ON

BOTH ENDS.

INBOUND REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLES FIELD TERMINATED WITH LC TYPE CONNECTORS

ON BOTH ENDS.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

EHRM INFRASTRUCTURE

UPGRADES

No. REVISION DESCRIPTION DATE

CIVIL/ STRUCTURAL ENGINEER

OATES ASSOCIATES

100 LANTER COURT, SUITE 1

COLLINSVILLE, IL 62234

(618) 345-2200

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

2519 MADISON AVE. STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

DATA/COMM CONSULTANT

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

COMMISSIONING AGENT

ES2

13401 N. SANTA FE AVE.

OKLAHOMA, OK 73114

(405) 528-4500

SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024

JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023

/1

5/

:0 0:

P

M

NR 172 205SR04/20/2023

657A5-21-700

MARION VA MEDICAL CENTER

2401 WEST MAIN ST.

MARION, IL 62959 T-103

15, 16

SPUR #: 2114

N

1/8" = 1'-0"

TECHNOLOGY PLAN - BLDG 15 LEVEL 11

N

1/8" = 1'-0"

TECHNOLOGY PLAN - BLDG 16 - LEVEL 12

TECHNOLOGY PLANS - BLDG 15, 16

204171

T-302

T-302

T-302

T-302

IRM

STORAGE

TELEPHONE

BIOMED

106A

STOR.

105A

OFFICE

GYM

118B

OFFICE

OFFICE

OFFICE

IRM

123A

IRM OFFICE

OFFICE

VAV

BIOMED

BIOMED OFF

BIOMED OFF

MENS

WOMENS

BEHAVIOR

MEDICINE

BEHAVIOR

MEDICINE

BEHAVIOR

MEDICINE

BEHAVIOR

MEDICINE

DATA CENTER

124IRM TECH

STAFF

T/C ELEC

BIOMED OFF

HAC

BEHAVIOR

MEDICING

AMER.

LEGION

VFW

TR

W

WW

W

4 4

4 4

4 4

4 4

4 4

4 4 4 4 4 4 4 4 4 4 4

B

LD

G . 1

GENERAL PLAN NOTES

1. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND

DURING INSTALLATION..

2. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF

ADDITIONAL CABLE DROPS.

3. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL

CUT-OVER TO THE NEW CABLING.

4. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN ITS

DESIGNATED TR.

5. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.

6. EXISTING CAT6A CABLING MAY REMAIN IN PLACE.

7. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED

UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.

8. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. ADHERE TO CABLING COLOR CODE AND LABELING

STANDARDS. (SEE SPECIFICATIONS)

9. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS

ALONG THE CABLE PATHWAYS.

10. EXISTING CONDUITS TO REMAIN.

11. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

12. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE SECONDARY BONDING BUSBAR.BOND ALL PARTS OF TRAY SYSTEMS TO THE TELECOMMUNICATIONS PRIMARY/SECONDARY

BUSBAR.

13. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE

WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR

SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER

ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE

RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES WHERE CABLING

WAS REMOVED.

14. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE

SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE

THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.

ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR BIOMED ARE NOT DISTURBED (TYPICALLY

ORANGE CATEGORY AND AQUA OM4 FIBER OPTIC CABLING).

ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR WIRELESS AND SECURITY SYSTEMS ARE NOT

DISTURBED.

15. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND

CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.

16. CONTRACTOR SHALL REINSTALL CEILING TILES AT THE END OF EVERY WORK SHIFT.

17. CONTRACTOR SHALL INSTALL TEMPORARY FIRESTOPPING IN ANY PENETRATIONS OF NETWORK

CABLING THROUGH FIRE RATED WALLS AT THE END OF EVERY WORK SHIFT. TEMPORARY

FIRESTOPPING SHALL CONSIST OF MINERAL WOOL AND PROVIDE PROTECTION AGAINST FIRE/SMOKE

SPREAD THROUGH UNSEALED PENETRATION.

18. CONTRACTOR SHALL INSTALL FIRESTOPPING IN ALL FIRE RATED WALLS WHERE NETWORK CABLING

WAS REMOVED TO ENSURE FIRE RATING OF WALL.

TECHNOLOGY KEYNOTES

TELECOMMUNICATIONS EQUIPMENT RACK, 7'H x 19"W x 29"D, 4-POST, OPEN FRAME TYPE.

INSTALL BASKET TRAY ABOVE NETWORK RACKS IN TR AS DEPICTED ON PLANS.

INSTALL BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING ALONG HALLWAY. INSTALL J-HOOKS IN

AREAS WHERE BASKET TRAY IS INAPPROPRIATE.

REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND MULTIMODE (OM4) & 12 STRAND SINGLEMODE (OS1) HYBRID FIBER OPTIC CABLES FIELD TERMINATED

WITH LC TYPE CONNECTORS ON BOTH ENDS.

REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND MULTIMODE (OM4) & 12 STRAND SINGLEMODE (OS1) HYBRID FIBER OPTIC CABLES FIELD TERMINATED

WITH LC TYPE CONNECTORS ON BOTH ENDS.

REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE CONNECTORS ON BOTH

ENDS.

REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLES FIELD TERMINATED WITH LC TYPE CONNECTORS ON BOTH

ENDS.

INTERNET SERVICE PROVIDER, ENTRANCE ROOM. BLDG 37, ROOM 131. TELEPHONE ROOM.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

EHRM INFRASTRUCTURE

UPGRADES

No. REVISION DESCRIPTION DATE

CIVIL/ STRUCTURAL ENGINEER

OATES ASSOCIATES

100 LANTER COURT, SUITE 1

COLLINSVILLE, IL 62234

(618) 345-2200

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

2519 MADISON AVE. STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

DATA/COMM CONSULTANT

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

COMMISSIONING AGENT

ES2

13401 N. SANTA FE AVE.

OKLAHOMA, OK 73114

(405) 528-4500

SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024

JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023

/1

5/

:0 0:

P

M

NR 173 205SR04/20/2023

657A5-21-700

MARION VA MEDICAL CENTER

2401 WEST MAIN ST.

MARION, IL 62959 T-104

SPUR #: 2114

N

1/8" = 1'-0"

TECHNOLOGY PLAN - BLDG 37 LEVEL 11

TECHNOLOGY PLANS - BLDG 37

204172

GENERAL PLAN NOTESGENERAL PLAN NOTES

1. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND

DURING INSTALLATION..

2. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF

ADDITIONAL CABLE DROPS.

3. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL

CUT-OVER TO THE NEW CABLING.

4. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN ITS

DESIGNATED TR.

5. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.

6. EXISTING CAT6A CABLING MAY REMAIN IN PLACE.

7. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED

UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.

8. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. ADHERE TO CABLING COLOR CODE AND LABELING

STANDARDS. (SEE SPECIFICATIONS)

9. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS

ALONG THE CABLE PATHWAYS.

10. EXISTING CONDUITS TO REMAIN.

11. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

12. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE SECONDARY BONDING BUSBAR.BOND ALL PARTS OF TRAY SYSTEMS TO THE TELECOMMUNICATIONS PRIMARY/SECONDARY

BUSBAR.

13. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE

WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR

SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER

ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE

RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES WHERE CABLING

WAS REMOVED.

14. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE

SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE

THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.

ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR BIOMED ARE NOT DISTURBED (TYPICALLY

ORANGE CATEGORY AND AQUA OM4 FIBER OPTIC CABLING).

ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR WIRELESS AND SECURITY SYSTEMS ARE NOT

DISTURBED.

15. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND

CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.

16. CONTRACTOR SHALL REINSTALL CEILING TILES AT THE END OF EVERY WORK SHIFT.

17. CONTRACTOR SHALL INSTALL TEMPORARY FIRESTOPPING IN ANY PENETRATIONS OF NETWORK

CABLING THROUGH FIRE RATED WALLS AT THE END OF EVERY WORK SHIFT. TEMPORARY

FIRESTOPPING SHALL CONSIST OF MINERAL WOOL AND PROVIDE PROTECTION AGAINST FIRE/SMOKE

SPREAD THROUGH UNSEALED PENETRATION.

18. CONTRACTOR SHALL INSTALL FIRESTOPPING IN ALL FIRE RATED WALLS WHERE NETWORK CABLING

WAS REMOVED TO ENSURE FIRE RATING OF WALL.

BLDG. 42

BLDG. 2

B

LD

G . 2

CARPENTER

SHOP

BLDG. 1

B

LD

G . 1

B

LD

G . 3

FIRE

PUMP

6A 001

T-303

TR

6B

T-303

4 4

4 4 4 4 4 4 4 4 4

4 4

4 4

4 4 4 4

4 4

4 4

TECHNOLOGY KEYNOTES

TELECOMMUNICATIONS EQUIPMENT RACK, 7'H x 19"W x 29"D, 4-POST, OPEN FRAME TYPE.

INSTALL BASKET TRAY ABOVE NETWORK RACKS IN TR AS DEPICTED ON PLANS.

INSTALL BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING ALONG HALLWAY. INSTALL J-HOOKS IN

AREAS WHERE BASKET TRAY IS INAPPROPRIATE.

REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND MULTIMODE (OM4) & 12 STRAND SINGLEMODE (OS1) HYBRID FIBER OPTIC CABLES FIELD TERMINATED

WITH LC TYPE CONNECTORS ON BOTH ENDS.

REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND MULTIMODE (OM4) & 12 STRAND SINGLEMODE (OS1) HYBRID FIBER OPTIC CABLES FIELD TERMINATED

WITH LC TYPE CONNECTORS ON BOTH ENDS.

REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLE FIELD TERMINATED WITH LC TYPE CONNECTORS ON BOTH

ENDS.

REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-B IN SR/DC/MCR. INCLUDES (1) 24 STRAND SINGLEMODE (OS2) FIBER OPTIC CABLES FIELD TERMINATED WITH LC TYPE CONNECTORS ON BOTH

ENDS.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

EHRM INFRASTRUCTURE

UPGRADES

No. REVISION DESCRIPTION DATE

CIVIL/ STRUCTURAL ENGINEER

OATES ASSOCIATES

100 LANTER COURT, SUITE 1

COLLINSVILLE, IL 62234

(618) 345-2200

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

2519 MADISON AVE. STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

INDUSTRIAL HYGENIST

RIVERFRONT SAFETY & HEALTH

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

DATA/COMM CONSULTANT

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE, SUITE A

PRESCOTT, AZ 86301

(928) 774-0992

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

COMMISSIONING AGENT

ES2

13401 N. SANTA FE AVE.

OKLAHOMA, OK 73114

(405) 528-4500

SETH ANDREW CAVIN - ARCHITECT #AR12100034 EXP. 11/30/2024

JAMES ROSS MYLES - PROFESSIONAL ENGINEER #062.071715 EXP. 11/30/2023

/1

5/

:0 0:

P

M

TECHNOLOGY PLANS - BLDG 1, 38, 2

LEVEL G

NR 174 205SR04/20/2023

657A5-21-700

MARION VA MEDICAL CENTER

2401 WEST MAIN ST.

MARION, IL 62959 T-105

1,38,2

SPUR #: 2114

N

1/16" = 1'-0"

TECHNOLOGY PLAN - BLDG 38 LEVEL G1

204173

T-303

T-303

B

LD

G . 2

118A119B

118B

119A

103B

107A

119C

103A

103C

106B

106C

106D

107B 107C 107D

107E

109A

110A

110B

110C

103A

113A

113B

113C

110D

108A

106A

116A

B

LD

G . 1

LOGISTICS

101A

DATA ROOM

123B

TEAM OFFICE

TR

123C

6 6

4 4 4

4 4

4 4

2222222

2 2 2 2 2 2

4 4

4 4

44444

4 4

4 4

TECHNOLOGY KEYNOTES

TELECOMMUNICATIONS EQUIPMENT RACK, 7'H x 19"W x 29"D, 4-POST, OPEN FRAME TYPE.

INSTALL BASKET TRAY ABOVE NETWORK RACKS IN TR AS DEPICTED ON PLANS.

INSTALL BASKET TRAY (12" W, 4" H) ABOVE DROP CEILING ALONG HALLWAY. INSTALL J-HOOKS IN

AREAS WHERE BASKET TRAY IS INAPPROPRIATE.

REDUNDANT FIBER BACKBONE 'A' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND MULTIMODE (OM4) & 12 STRAND SINGLEMODE (OS1) HYBRID FIBER OPTIC CABLES FIELD TERMINATED

WITH LC TYPE CONNECTORS ON BOTH ENDS.

REDUNDANT FIBER BACKBONE 'B' CABLES FROM MDA-A IN SR/DC/MCR. INCLUDES (1) 24 STRAND MULTIMODE (OM4) & 12 STRAND SINGLEMODE (OS1) HYBRID FIBER OPTIC CABLES FIELD TERMINATED

WITH LC TYPE CONNECTORS ON BOTH ENDS.

GENERAL PLAN NOTESGENERAL PLAN NOTES

1. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS FOUND

DURING INSTALLATION..

2. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF

ADDITIONAL CABLE DROPS.

3. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL

CUT-OVER TO THE NEW CABLING.

4. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF TWO OR FOUR CAT6A CABLES AS SHOWN ON THE PLANS. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN ITS

DESIGNATED TR.

5. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.

6. EXISTING CAT6A CABLING MAY REMAIN IN PLACE.

7. LABEL FIBER CABLE GOING INTO EACH FIBER PATCH PANEL. ALL FIBER STRANDS WILL BE TESTED

UTILIZING AN OLTS AND AN OTDR PER THE TIER 2 STANDARD.

8. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. ADHERE TO CABLING COLOR CODE AND LABELING

STANDARDS. (SEE SPECIFICATIONS)

9. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS

ALONG THE CABLE PATHWAYS.

10. EXISTING CONDUITS TO REMAIN.

11. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

12. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE SECONDARY BONDING BUSBAR.BOND ALL PARTS OF TRAY SYSTEMS TO THE TELECOMMUNICATIONS PRIMARY/SECONDARY

BUSBAR.

13. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA AND TELEPHONE CABLING ALL THE

WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR

SYSTEMS OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL OTHER

ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO BE

RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES WHERE CABLING

WAS REMOVED.

14. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK TO THE

SERVER ROOM. DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT. ENSURE

THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT DISTURBED.

ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR BIOMED ARE NOT DISTURBED (TYPICALLY

ORANGE CATEGORY AND AQUA OM4 FIBER OPTIC CABLING).

ENSURE ALL CATEGORY AND FIBER OPTIC CABLING FOR WIRELESS AND SECURITY SYSTEMS ARE NOT

DISTURBED.

15. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS AND

CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.

16. CONTRACTOR SHALL REINSTALL CEILING TILES AT THE END OF EVERY WORK SHIFT.

17. CONTRACTOR SHALL INSTALL TEMPORARY FIRESTOPPING IN ANY PENETRATIONS OF NETWORK

CABLING THROUGH FIRE RATED WALLS AT THE END OF EVERY WORK SHIFT. TEMPORARY

FIRESTOPPING SHALL CONSIST OF MINERAL WOOL AND PROVIDE PROTECTION AGAINST FIRE/SMOKE

SPREAD THROUGH UNSEALED PENETRATION.

18. CONTRACTOR SHALL INSTALL FIRESTOPPING IN ALL FIRE RATED WALLS WHERE NETWORK CABLING

WAS REMOVED TO ENSURE FIRE RATING OF WALL.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

EHRM INFRASTRUCTURE

UPGRADES

No. REVISION DESCRIPTION DATE

CIVIL/ STRUCTURAL ENGINEER

OATES ASSOCIATES

100 LANTER COURT, SUITE 1

COLLINSVILLE, IL 62234

(618) 345-2200

MECH / ELEC / PLUMB ENGINEER

SPUR DESIGN

2519 MADISON AVE. STE 100

KA…