Appendix J-9 - Intrusion Detection Zone Checklist.xlsx

XLSX spreadsheet 17 KB Posted

Attached to
Domestic Security Installation Services - 100% Small Business Set-Aside
Solicitation number
SAQMMA11R0187
Issued by

About this file

Appendix J-9 - Intrusion Detection Zone Checklist

View the file

Other files

File Type Posted
SF30 Domestic Security Installation Services A003.docx DOCX document
Appendix J-22 - STAC Overview.docx DOCX document
DME Solicitation Document - A002.docx DOCX document
SF30 Domestic Security Installation Services A002.docx DOCX document
Appendix J-1 - Projected Workload Table - A002.xlsx XLSX spreadsheet
SF30 Continuation Pages - A002.docx DOCX document
Exhibit B - Pricing Tables - A002.xlsx XLSX spreadsheet
Exhibit B - Pricing Tables - A001.xlsx XLSX spreadsheet
DME Solicitation Document - A001.docx DOCX document
SF30 Continuation Pages - A001.docx DOCX document
Appendix J-1 - Projected Workload Table - A001.xlsx XLSX spreadsheet
SF30 Domestic Security Installation Services A001.docx DOCX document
Appendix J-8 - Altronix Power Supply Worksheet.xlsx XLSX spreadsheet
Appendix J-18 - Preventive Maintenance Procedure Times.docx DOCX document
Appendix J-16 - Medium Project.pdf PDF
Appendix J-14 - UL-681 Quality Audit Checklist.xlsx XLSX spreadsheet
Appendix J-7 - Quality Audit Review of DME SOW Example.xlsx XLSX spreadsheet
Exhibit B - Pricing Tables.xlsx XLSX spreadsheet
Appendix J-1 - Projected Workload Table.xlsx XLSX spreadsheet
Appendix J-3 - Facility Security Engineering Division Overview.docx DOCX document
Exhibit A - Past Performance Questionnaire.docx DOCX document
Appendix J-17 - Large Project.pdf PDF
Appendix J-19 - First Responder Historical Work Order Data.docx DOCX document
Appendix J-11 - CCTV Martix Worksheet.xlsx XLSX spreadsheet
Appendix J-20 - Bidders Form DD 254.pdf PDF
Appendix J-12 - DME Infastructure Checklist.xlsx XLSX spreadsheet
Appendix J-15 - Small Project.pdf PDF
DME Solicitation Document.docx DOCX document
DME SF-33.docx DOCX document
Appendix J-5 - CMMS SOP Listing.docx DOCX document
Appendix J-21 - SCA Wage Determination.pdf PDF
Appendix J-4 - Domestic Customers and Facilities.docx DOCX document
Appendix J-2 - Acronyms and Definitions.docx DOCX document
Appendix J-10 - ACS Door Worksheet.xlsx XLSX spreadsheet
Appendix J-6 - Applicable Authorities and Publications.docx DOCX document
Appendix J-13 - DME iSTAR Panel Worksheet.xlsx XLSX spreadsheet
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CWS0005R1C0

INTRUSION DETECTION ZONEAUDITOR(S)DEVICE LOCATION
DATEPANEL ID
CHECKLISTPROJECT NUMBER
CHECK = OK PASS X = NO FAIL N/I = NOT INSTALLED N/A = NOT APPLICABLE N/T = NOT TESTED
PreparationSTATUSREMARKS
Monitoring station notified of IDS test.
Monitoring station will observe and print (if applicable) alarms reported by IDS being tested.
QUALITY POINTNo.
ISTAR ALARM PANEL
Verify I*STAR Panel installed IAW plan set &/or change order.1
Statement of Work
Verify I*STAR Panel is securely mounted.2
2002 NEC, paragraph 110.13(a)
Verify minimum 4" vertical spacing between I*STAR Panel and any other equipment.3
DME Design Standards pg.STD-019
Verify door on I*STAR Panel can be opened 90 degrees.4
2002 NEC, paragraph 110.26(A)(2)
Verify minimum 30" workspace in front of panel.5
2002 NEC, paragraph 110.26(A)(2)
Verify I*STAR Panel is bonded.6
2002 NEC, paragraph 250.190
Verify alarm zone(s) labeled and legend readily available.7
SOW section 17 paragraph b
Verify alarm zone(s) can be secured.8
C*CURE 800/8000 Advanced Users Guide Ch.6, Technical Security Design Manual Section 6
Verify IDS Keypad reports tamper alarm when removed from wall.9
Technical Security Design Manual Section 6.C.b
Verify IDS Keypad reports tamper alarm when removed from mounting box.9
Technical Security Design Manual Section 6.C.b
Verify 14 gauge wire connecting I*STAR Panel to building ground.11
DME Design Standards pg.STD-001
Verify wire drains from all cables terminating in I*STAR Panel are connected to chassis ground.12
DME Design Standards pg.STD-018
DEVICE NUMBER ON PLAN-SET
IDS SENSORS
What type of sensor is it? (DSM, PIR)13
Plan set or SOW
Verify sensor installed IAW plan set or SOW.14
Plan set or SOW
Verify tamper switch connected and activates tamper alarm when zone is disarmed.15
DME Design Standards pg.STD-003, STD-006
Verify sensor reports alarm when zone is armed.16
C*CURE 800/8000 Advanced Users Guide Ch.6
If the Sensor is a PIR or Glass break or Rex have two cables coming into the sensor, one for power and one for data (Belden 72760 and 82723 respectively)17
DME designator guide, Sow and Drawings
Are there two sets of resistors and are they soldered to the incoming wire and terminated on the alarm strip?18
DME designator guide, Sow and Drawings
Are the sensors wired up in the normally closed position?19
DME designator guide, Sow and Drawings
Are the cables marked in accordance with the cable list found in the SOW and depicted on the drawings?19
DME designator guide, Sow and Drawings
BOX NUMBER ON PLAN-SET
Input Module --I8
Verify the module is installed IAW DME Standards13
Plan set or SOW DME STD-
REMARKS

&"Times New Roman,Regular"U.S. Department of State

Solicitation No. SAQMMA11R0187&"Times New Roman,Bold"APPENDIX J-9
INTRUSION DETECTION ZONE CHECKLIST&"Times New Roman,Regular"Domestic Security Installation Services

Section J: Appendices

&"Times New Roman,Regular"Appendix J-9 Intrusion Detection Zone Checklist &"Times New Roman,Regular"J-9-&P