UL681 CK'LIST
| Ref. No. | System | Component Procedure | UL 681 Paragraph | UL 681, Standard for Safety for Installation and Classification of Burglar and Holdup Alarm Systems13th. Edition, 26-FEB-99, Revisions: This Standard contains revisions through and including January 19, 2001. Department of Defense (DoD) adopted UL 681 on 2-JAN-92. | Requi'nt Met? | Image(s) | Audit Comment(s) |
| 119 | 2.2.3 | Access-controlled egress doors. The entrance doors in a means of egress in buildings with an occupancy in Group A, B, E, M, R-1 or R-2 and entrance doors to tenant spaces in occupancies in Groups A, B, E, M, R-1 and R-2 are permitted to be equipped with an approved entrance and egress access control system which shall be installed in accordance with all of the following criteria: |
120 5.1.1 Access-controlled egress doors. The entrance doors in a means of egress in buildings with an occupancy in Group A, B, E, M, R-1 or R-2 and entrance doors to tenant spaces in occupancies in Groups A, B, E, M, R-1 and R-2 are permitted to be equipped with an approved entrance and egress access control system which shall be installed in accordance with all of the following criteria:
| 121 | 5.1.1 | Installation wiring complying with the requirements for burglar alarm wire and cable shall be used to interconnect various detection, control, and sounding device equipment installed to form a burglar alarm system. This wire shall not be smaller than No. 22 AWG (0.32 mm2) copper wire and shall comply with Article 725 of the National Electrical Code, ANSI/NFPA 70. |
| 122 | 5.2.1 | Installation wiring shall be located where it will be least subject to damage. A nonjacketed wire routed over a sharp corner or projection shall be protected from abrasion by two layers of electrical tape or the equivalent electrical insulation. |
| 123 | 5.1.1 | Installation wiring complying with the requirements for burglar alarm wire and cable shall be used to interconnect various detection, control, and sounding device equipment installed to form a burglar alarm system. This wire shall not be smaller than No. 22 AWG (0.32 mm2) copper wire and shall comply with Article 725 of the National Electrical Code, ANSI/NFPA 70. |
| 124 | 5.2.2 | Installation wiring shall be attached to gypsum wallboard (dry wall) or plaster or wood by staples, drive rings, wire ties, or the equivalent. Wire shall be attached to a masonry surfaces by expansion bolts, plugs and eyelets, drive rings, or the equivalent. |
| 125 | 5.2.3 | Staples or brads shall be spaced not more than 2 feet (610 mm) apart on gypsum wallboard (dry wall), or wood or plaster. Exception No. 1: A wire resting on top of a molding, cabinet, and the like, may be stapled at intervals of 4 feet (1.2 m) or less. Exception No. 2: Areas that are not accessible, such as a duct, a plenum, the space above a suspended ceiling, and the like, where the wiring is supported and protected from damage, need not comply with these requirements. |
| 126 | 5.3.1 | A conductor shall be spliced or joined with a splicing device acceptable for this purpose. A splice intended to be soldered shall be joined mechanically before being soldered. Each splice and joint shall be covered with an insulation equivalent to that of the conductors or with not less than two layers of electrical tape. A splice located in an area subjected to dampness shall be treated with an acceptable sealant or equivalently treated. |
| 127 | 5.4.1 | A connector intended to carry a circuit onto a movable opening shall comply with the applicable requirements in the Standard for Connectors and Switches for Use with Burglar-Alarm Systems, UL 634. |
| 128 | 5.5.1 | Alarm system wiring shall be spaced at least 2 inches (51 mm) from conductors of any electric light, power, or Class 3 circuits unless one of the circuits is in conduit. |
| 129 | 5.7.1 | A control unit shall be connected to an earth ground as required by the installation instructions for the product. Grounding shall be to a cold-water pipe where possible. |
| 130 | 5.7.2 | The system shall test free of grounds with the exception of those circuits that are intended to be connected to the ground side of the protective circuit. Also see 21.4.5. |
| 131 | 15.2.1 | Contacts shall be installed so that a door cannot be opened more than 2 inches (51 mm) without causing an alarm condition. Contacts mounted on the outside of a safe door shall be constructed for mounting outside the protected area and shall comply with the applicable requirements in the Standard for Connectors and Switches for Use with Burglar-Alarm Systems, UL 634. Ordinary-use alarm contacts complying with UL 634 are acceptable if mounted inside, or if mounted outside with a capacitance alarm |
unit.
| 132 | 20.1 | A system shall not depend solely on commercial power at the premises. |
| 133 | 20.2 | The requirement specified in 20.1 requires standby power to maintain the system in normal condition automatically in case of interruption of the commercial power source for periods as follows: e) National Industrial Security Systems– 4 hours. |
| 134 | 10.1.1 | Intrusion detection equipment complying with the Standard for Intrusion-Detection Units, UL 639, may be used in combination with or in place of protective wiring. |
| 135 | 10.1.2 | When an intrusion detection unit used in a mercantile system is controlled by a shunt switch, there shall be a positive indication of whether or not the shunt circuit is closed. The indication shall be located at, or be visible outside, the entrance/exit door where the shunt switch is installed. Exception: Such indication is not required when an exit time-delay shunt is used. |
| 136 | 10.3 | Motion Detection Units: |
| 137 | 10.3.1 | Motion detection units used for channel-type protection of Extent Numbers 2 and 3 shall initiate an alarm when a person walks across each channel at any point at the rate of one step, 30 ±3 inches (760±80 mm) per second. |
| 138 | 10.3.2 | If motion detection (full area) coverage is used for protection of Extent Numbers 2 and 3 the system shall respond to the movement of a person walking not more than four consecutive steps at a rate of one step, 30 ±3 inches (760 ±80 mm), per second. The four-step movement shall constitute a ²trial,² and a sufficient number of detection units shall be installed so that, upon test, an alarm will be initiated in at least three out of every four such consecutive ²trials² made moving progressively through the protected area. The test is to be conducted by taking a four step trial, stopping for 3 to 5 seconds, taking a four step trial, stopping for 3 to 5 seconds, repeating the process throughout the protected area. Whenever possible, the direction of the next trial is to be in a different direction. | ||
| 139 | 10.3.3 | If the area protected by full area motion detection can be traversed in four steps or less in any direction, movement shall be detected when the walk test in that direction is made. | ||
| 140 | 10.3.4 | Each system shall be provided with a test device or method to indicate the overall operability of the system. | ||
| 141 | 10.3.5 | A motion detection unit shall be installed so that it will not be influenced by movement outside the protected area. | ||
| 142 | 10.3.6 | A motion detection unit shall not be installed within a protected area if it will be influenced by moving objects, air turbulence or movement, noise, electrical interference, and the like in a manner that will cause the motion detector to go into an alarm condition. | ||
| 143 | Repairs | Industry Performance Standard | 24.5(f) | Repairs to a national industrial security system shall begin as specified in the Standard for National Industrial Security Systems for the Protection of Classified Material, UL 2050. |
&"Times New Roman,Regular"U.S. Department of State
| Solicitation No. SAQMMA11R0187 | &"Times New Roman,Bold"APPENDIX J-14 |
| UL-681 QUALITY AUDIT CHECKLIST | &"Times New Roman,Regular"Domestic Security Installation Services |
Section J: Appendices
&"Times New Roman,Regular"Appendix J-14 UL-681 Quality Audit Checklist &"Times New Roman,Regular"J-14-&P
File details come from the government source that posted it. Updated .