Appendix J-8 - Altronix Power Supply Worksheet.xlsx
XLSX spreadsheet 14 KB Posted
- Solicitation number
- SAQMMA11R0187
About this file
Appendix J-8 - Altronix Power Supply Worksheet
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CWS0003R1C0
| ALTRONIX POWER SUPPLY WORKSHEET | AUDITOR(S) | DEVICE LOCATION | ||
| DATE | PROJECT NUMBER | |||
| STATUS KEY: √ = OK / PASS X = NO / FAIL N I = NOT INSTALLED N A = NOT APPLICABLE N T = NOT TESTED | ||||
| QUALITY POINT | STATUS | REMARKS | No. | |
| Verify power supply installed IAW plan set &/or change order. | 1 | |||
| Statement of Work | ||||
| Verify power supply securely mounted. | 2 | |||
| 2002 NEC, paragraph 110.13(a) | ||||
| Verify minimum 4" vertical spacing between power supplies. | 3 | |||
| DME Design Standards pg.STD-019 | ||||
| Verify door on power supply can be opened 90 degrees. | 4 | |||
| 2002 NEC, paragraph 110.26(A)(2) | ||||
| Verify minimum 30" workspace in front of panel. | 5 | |||
| 2002 NEC, paragraph 110.26(A)(2) | ||||
| Verify power supply is bonded. | 6 | |||
| 2002 NEC, paragraph 250.90 | ||||
| Verify power supply is uniquely identified with label. | 7 | |||
| Statement of Work and Drawings --Multiple power supplies | ||||
| Verify electric panel & breaker number are indicated on front of power supply. | 8 | |||
| Statement of Work | ||||
| Verify breaker number indicated on power supply cover is correct breaker. | 9 | |||
| 2002 NEC, paragraph 408.4 | ||||
| Verify ER panel legend is correctly labeled for power supply. | 10 | |||
| 2002 NEC, paragraph 408.4 | ||||
| Verify LED indicator lamp functioning. | 11 | |||
| Altronix power supply installation instructions | ||||
| Verify all cables exiting power supply are labeled. | 12 | |||
| Statement of Work | ||||
| Verify labeling on cable(s) is legible. | 13 | |||
| Statement of Work | ||||
| Verify cable management inside power supply is installed in a workmanlike manner. | 14 | |||
| 2002 NEC, paragraph 110.12 | ||||
| Verify one 12VDC battery is installed. | 15 |
| Verify power supply continues to function with AC power removed. | 16 |
| Altronix Installation Instructions | |
| Verify AC Power Fail alarm output connects to input on I*STAR Panel. | 17 |
Verify DC Power Fail alarm output connects to input on I*STAR Panel. 18
&"Times New Roman,Regular"U.S. Department of State
| Solicitation No. SAQMMA11R0187 | &"Times New Roman,Bold"APPENDIX J-8 |
| ALTRONIX POWER SUPPLY WORKSHEET | &"Times New Roman,Regular"Domestic Security Installation Services |
Section J: Appendices
&"Times New Roman,Regular"Appendix J-8 Altronix Power Supply Worksheet &"Times New Roman,Regular"J-8-&P
File details come from the government source that posted it. Updated .