S02 - 695-22-117 Drawings Vol 2 Mechanical Sheets 17.pdf
PDF 6 MB Posted
- Attached to
- Z2DA--695-22-117 CN New Audiology Clinic 5BN
- Solicitation number
- 36C25225B0024
About this file
These documents are HVAC (Heating, Ventilation, and Air Conditioning) design and specification drawings for a VA Milwaukee Renovate project, specifically for the Audiology 5BN area. The drawings, prepared by IMEG Corp for the Office of Construction and Facilities Management, detail a fully sprinklered renovation involving a packaged rooftop air handling unit with exhaust fan, complex HVAC system controls, and detailed mechanical specifications.
The technical drawings include floor plans, mechanical sections, HVAC diagrams, and comprehensive control sequences for the rooftop unit, covering detailed specifications such as outside air management, temperature control, fan operations, economizer functionality, and various safety interlocks. Key technical aspects include modulating supply fan control to maintain duct static pressure, temperature reset strategies, ventilation control with minimum outside air requirements, and specific operational sequences for occupied and unoccupied modes. The project is located at 5000 W National Ave in Milwaukee, Wisconsin, with design documents dated September 9, 2024, and appears to be part of a VA facility renovation.
View the file
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AI
AI
AI AI
AO
DO
DI
AI
AI
AI
FM
FMDSD
DSD T H
T
DO DI
EXHAUST
AIR
OUTSIDE
AIRFLOW
UNIT
OUTSIDE
AIR
RTU CONTROLLER
TO/FROM FMCS THROUGH RTU BACNET GATEWAY:
* DUCT DIFFERENTIAL STATIC PRESSURE SET POINT ["W.C.] (ANALOG)
* DUCT STATIC PRESSURE ["W.C.]
* DISCHARGE TEMP SETPOINT ADJUST [°F] (ANALOG)
* SUPPLY AIR TEMPERATURE [°F] (ANALOG)
* BUILDING STATIC PRESSURE SETPOINT ["W.C.] (ANALOG)
* RTU ENABLE/DISABLE
* OA SETPOINT (CFM) (ANALOG)
* OA AIRFLOW (CFM) (ANALOG)
* GENERAL ALARM
* DIRTY FILTER ALARM
DUCT SMOKE DETECTOR: PROVIDED AND WIRED
BY ELECTRICAL CONTRACTOR. INSTALLED BY
MECHANICAL CONTRACTOR. INTERLOCK TO
RTU CONTROL PANEL BY CONTRACTOR IN FIELD.
DUCT MTD TEMP &
HUMIDITY SENSORS
RTU PRESSURE
BUILDING
SENSOR
DUCT
STATIC
PRESSURE
HIGH STATIC
SWITCH
SUPPLY
AIRFLOW
P
COORDINATE EXACT LOCATION
OF PRESSURE SENSOR WITH
MANUFACTURER.
RETURN
AIR
SUPPLY
AIR
BACNET INTERFACE TO
FMCS
CONTROLS PROVIDED BY PACKED EQUIPMENT MANUFACTURER:
PACKAGE ROOFTOP UNIT SYSTEM DESCRIPTION:
REFER TO SECTION 23 74 13 FOR A DESCRIPTION OF THE RTU AND THE CONTROLS PROVIDED BY THE RTU MANUFACTURER.
SUPPLY FAN CONTROL:
RTU CONTROLLER SHALL MODULATE SIGNAL TO SUPPLY MANUFACTURER INSTALLED FAN VFD AS REQUIRED TO MAINTAIN DUCT STATIC PRESSURE SETPOINT AS MEASURED BY STATIC PRESSURE
TRANSMITTER.
STATIC PRESSURE RESET:
FMCS SHALL RESET SUPPLY DUCT STATIC PRESSURE SETPOINT BELOW THE MAXIMUM SETPOINT AS REQUIRED TO MAINTAIN AT LEAST ONE SUPPLY TAB DAMPER 90% (ADJ.) OPEN. FMCS SHALL
MONITOR ALL SUPPLY TERMINAL AIR BOX POSITIONS TO RESET THE SUPPLY DUCT DIFFERENTIAL STATIC PRESSURE.
EXHAUST FAN CONTROL:
RTU CONTROLLER SHALL MONITOR BUILDING PRESSURE SIGNAL. MODULATE SIGNAL TO EXHAUST FAN VFD AS REQUIRED TO MAINTAIN +0.05" (ADJ.) W.C..
VENTILATION CONTROL:
WHENEVER THE UNIT IS IN OCCUPIED MODE THE OUTSIDE AIR DAMPER SHALL MODULATE TO MAINTAIN MINIMUM OUTSIDE AIR CFM BASED ON QUANTITY OF AIR FROM UNIT MOUNTED AIRFLOW
MEASURING STATION.
SUPPLY AIR TEMPERATURE CONTROL:
DISCHARGE AIR TEMPERATURE SHALL BE 55°F (ADJ.). WHENEVER THE SUPPLY AIR TEMPERATURE IS ABOVE SETPOINT, THE FOLLOWING SHALL OCCUR IN SEQUENCE:
• MODULATE THE HEATING WATER VALVE CLOSED.
• MODULATE OA DAMPER AS REQUIRED UNTIL SET POINT IS REACHED.
• IF SET POINT CANNOT BE MAINTAINED BY OA DAMPER CONTROL, OUTSIDE AIR DAMPER SHALL CLOSE TO MINIMUM POSITION AND THE COMPRESSORS SHALL BE ENABLED AND MFR SHALL
STAGE COMPRRESSOR CAPACITY AS REQUIRED TO MAINTAIN SET POINT.
WHENEVER THE DISCHARGE AIR TEMPERATURE IS BELOW SETPOINT, THE FOLLOWING SHALL OCCUR IN SEQUENCE:
• IF THE DISCHARGE AIR TEMPERATURE IS MORE THAN 5°F (ADJ) BELOW SETPOINT. MFR SHALL STAGE COMPRRESSORS OFF.
• MODULATE OA DAMPER AS REQUIRED UNTIL SET POINT IS REACHED.
• IF SET POINT CANNOT BE MAINTAINED BY OA DAMPER CONTROL, MODULATE HEATING WATER VALVE AS REQUIRED TO MAINTAIN SET POINT.
SEND AN ALARM TO THE CONTROLER INTERFACE [FMCS] FOR THE FOLLOWING:
• SUPPLY FAN FAULT (AIRFLOW, CURRENT OR VFD)
• EXHAUST FAN FAULT (AIRFLOW, CURRENT OR VFD)
• DIRTY FILTERS (WHEN FILTER PRESSURE DROP EXCEEDS 0.6" W.C. (ADJ.)
• IF DISCHARGE AIR TEMPERATURE IS MORE THAN 10°F (ADJ.) ABOVE OR BELOW SETPOINT.
• EMERGENCY STOP
CIRCULATION PUMP OPERATION:
WHEN OUTSIDE AIR TEMPERATURE RISES ABOVE 40°F (ADJ.) FOR 10 MINUTES (ADJ.) HEATING WATER COIL CIRCULATION PUMP SHALL OPERATE ONLY WHEN HEATING IS CALLED FOR (HEATING
WATER VALVE IS COMMANDED TO OPEN). WHEN OUTSIDE AIR TEMP DROPS BELOW 40°F (ADJ.) HEATING WATER COIL CIRCULATION PUMP SHALL OPERATE CONTINUOUSLY. ONCE ENERGIZED, HEATING WATER COIL CIRCULATION PUMP SHALL REMAIN IN OPERATION FOR MINIMUM 5 MINUTES (ADJ.) TO PREVENT SHORT CYCLING.
FMCS SHALL MODULATE HEATING WATER CONTROL VALVE AS REQUIRED TO MAINTAIN DISCHARGE AIR TEMPERATURE SET POINT.
ECONOMIZER OPERATION:
WHEN THE OUTSIDE AIR DRY BULB TEMPERATURE IS LESS THAN THE RETURN AIR DRY BULB TEMPERATURE THE FMCS SHALL ENABLE ECONOMIZER CONTROLS. WHEN OUTSIDE AIR DRY BULB
TEMPERATURE IS GREATER THAN THE RETURN AIR DRY BULB TEMPERATURE FOR 10 MINUTES THE FMCS SHALL DISABLE ECONOMIZER CONTROLS AND SHALL RETURN THE UNIT TO MINIMUM OUTSIDE
AIR MODE. ONCE ECONOMIZER CONTROLS HAVE BEEN ENABLED OR DISABLED, THE UNIT SHALL CONTINUE TO OPERATE IN THAT MODE FOR A MINIMUM OF 10 MINUTES (ADJ.) BEFORE BEING
ALLOWED TO SWITCH BACK (TO PREVENT SHORT CYCLING).
IN ECONOMIZER MODE THE FMCS SHALL MODULATE THE RETURN AND RELIEF DAMPERS AS REQUIRED TO MAINTAIN DISCHARGE AIR TEMPERATURE SETPOINT.
WHENEVER RTU IS SHUT DOWN THE RTU CONTROLLER SHALL COMMAND THE FOLLOWING TO OCCUR:
• SUPPLY FAN AND EXHAUST FAN SHALL STOP.
• OUTSIDE AIR AND EXHAUST AIR DAMPERS SHALL FULLY CLOSE. THE RETURN AIR DAMPER SHALL FULLY OPEN.
• HEATING WATER CIRCULATION PUMP AND HEATING WATER CONTROL VALVE SHALL REMAIN UNDER CONTROL OF ITS INPUT SENSOR.
• COOLING SHALL BE DISABLED.
• OUTSIDE AIR AND RELIEF AIR DAMPER SHALL REMAIN CLOSED. RETURN AIR DAMPER SHALL BE 100% OPEN
UN-OCCUPIED MODE OPERATION:
• OUTSIDE AIR AND RELIEF AIR DAMPER SHALL REMAIN CLOSED. RETURN AIR DAMPER SHALL BE 100% OPEN.
2 2
LOCATE DUCT DIFFERENTIAL STATIC PRESSURE
SENSOR NEAR MOST REMOTE TERMINAL AIR
BOX.
KEYNOTES:
1. SENSOR PROVIDED BY RTU MANUFACTURER. SENSOR FEEDER/RACEWAY AND
CONNECTION SHALL BE INSTALLED BY CONTRACTOR IN THE FIELD.
2. POINT, SENSOR AND FEEDER/RACEWAY PROVIDED BY TCC.
SUPPLY
TEMPERATURE
SENSOR
CONTROLS SEQUENCE PROVIDED BY CONTRACTOR IN FIELD:
SEQUENCE OF OPERATION:
THE T.C.C. SHALL EXTEND THE FMCS NETWORK TO THE RTU BACNET INTERFACE PER THE PROTOCOL SPECIFIED IN SECTION 23 09 00.
WHEN RTU IS INDEXED TO RUN, THE FOLLOWING SHALL OCCUR:
• WHEN THE SUPPLY FAN HAS STARTED THE INTERLOCKED EXHAUST FANS SHALL START AS SHOWN IN THE FAN INTERLOCK SCHEDULE.
BUILDING OCCUPANCY SCHEDULING:
ENABLE RTU TO RUN BASED ON THE FOLLOWING OCCUPANCY SCHEDULE WITH ALLOWANCE FOR ENERGY CODE OPTIMAL START.
• OCCUPIED MODE:
• UNOCCUPIED MODE:
CONTRACTOR SHALL FIELD INSTALL THE FOLLOWING MANUFACTURER PROVIDED EXTERNAL SENSORS AND WIRE BACK TO RTU CONTROLLER:
• DUCT STATIC PRESSURE SENSOR IN SUPPLY DUCT.
• BUILDING PRESSURE SENSOR.
• SUPPLY AIR TEMPERATURE IN SUPPLY DUCT.
ALARMS, INTERLOCKS AND SAFETIES:
THE FOLLOWING SAFETIES SHALL BE INSTALLED AND WIRED IN THE FIELD.
• HIGH STATIC SWITCH (WIRED TO UNIT ENABLE/DISABLE TO TURN FANS OFF)
• LOW STATIC SWITCH (WIRED TO UNIT ENABLE/DISABLE TO TURN FANS OFF)
• FIRE ALARM RELAY (WIRED TO UNIT ENABLE/DISABLE TO TURN FANS OFF)
EXTERNAL CONTROLS PROVIDED BY CONTROLS CONTRACTOR AND
WIRED TO FMCS:
• STATIC SWITCH
• RETURN TEMPERATURE SENSOR
• HUMIDITY SENSOR
• DUCT SMOKE DETECTOR
• DUCT SMOKE DETECTOR INTERLOCK
FAN INTERLOCK SCHEDULE
SYSTEM INTERLOCKED EXHAUST FANS REMARKS
AHU-5B-NORTH EF-0 NOTE 1
NOTES:
1. INTERLOCK EXHAUST FAN OPERATION THROUGH THE FMCS WITH RESPECTIVE AHU IN
ACCORDANCE WITH AHU SEQUENCE OF OPERATION.
MONDAY THROUGH FRIDAY 7:00AM-6:00PM (ADJ.)
MONDAY THROUGH FRIDAY 6:00PM-7:00AM (ADJ.)
SCHEDULED HOLIDAYS AND SATURDAY/SUNDAY
MFR SHALL INSTALL OUTSIDE AIR
FLOW METER TO OBTAIN
ACCURATE AIRFLOW READING
VALVE
MOD.
HWR
N.O.
CS
HWS
PUMP
STATUS
START/
STOP
HWR
TEMP
HWS
TEMP
ECONOMIZER
DAMPER
ACT
N.C.
DMPR
OPEN/
CLOSE
DMPR
FDBK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
DWG. ___ OF XX
7GAE PROJECT NO.: 221236
Sprinkler:
600 E. Michigan Avenue, Suite B
Kalamazoo, MI 49007
P: 269.927.0144 www.7GenAE.com
2850 Eisenhower Ave, Suite 310
Alexandria, VA 22314
P: 202.617.8485 www.alliance.us.com
FULLY SPRINKLERED
HVAC DIAGRAMS VA MILWAUKEE RENOVATE 111
AUDIOLOGY 5BN
5000 W NATIONAL AVE, MILWAUKEE, WI 53295
695-22-117
PROJECT DIRECTOR
September 9, 2024 KRICOT RYALIN
100%
BID DOCUMENTS
M400
2310 CROSSROADS DR
SUITE 3000
MADISON, WI 53718
P: 608.223.9600 F: 608.223.9601 www.imegcorp.com
IMEG CORP. RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS,
TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP. AND
SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT
WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF
IMEG CORP. ©2023 IMEG CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #22010362.00
NO SCALE
AIR HANDLING UNIT - PACKAGED ROOFTOP UNIT WITH EXHAUST FAN
VALV
FDBK
Revisions: Date:
35% SCHEMATIC DESIGN 04/20/2023
65% DESIGN DEVELOPMENT 06/16/2023
95% CONSTRUCTION DOCUMENTS 08/30/2023
95% CONSTRUCTION DOCUMENTS RESUBMITTAL 04/12/2024
100% CONSTRUCTION DOCUMENTS 09/09/2024